1 Uniclass EPIC CI/SfB (52) October 2005 Drainage Products S E L E C T I O N A N D I N S T A L L A T I O N G U I D E

2 Aprivately owned U.K. company with more than forty years experience in the industry, Wade is established as a leading manufacturer of quality drainage products. Much of the success of the business is attributable to an on-going commitment to put technology to practical use, to generate fresh ideas, and to guarantee quality assured manufacturing. This guide presents illustrations and limited data from a comprehensive range of products. For detailed information please refer to Wade Technical Handbooks, our CD Rom, or our website. Certification of compliance with BS EN ISO 9001 underlines our commitment to quality and service.

3 Contents ACCESS COVERS - GENERAL PURPOSE 23 ADAPTORS 24 FLOOR GULLIES and ACCESS COVERS ASPHALT FLOORS 29 DIRECT CONNECTION GRATINGS DIRECT CONNECTION ACCESS COVERS INSTALLATION 4-5 MISCELLANEOUS GULLIES 31 SHOWER GULLIES SIDE INLETS 9 STAINLESS STEEL GULLIES 6-8 VARI-LEVEL - BODIES GRATINGS ACCESS COVERS 16 - ACCESSORIES UNFINISHED FLOORS 30 GREASE CONVERTERS LINEAR DRAINAGE MATERIALS 50 NON-FREEZE WATER POINTS 47 ROOF OUTLETS SEDIMENT / OIL INTERCEPTORS 47 SPEC. CODE INDEX 51 WATER HAMMER ARRESTORS 47

4 FLOOR GULLIES Installation Guidelines 1. Where applicable, screw spigot adaptor into the body outlet using a suitable sealant to ensure the joint is watertight. Finished floor level 6. Where applicable, dress the membrane over the flange and into the sump of the body, ensuring that the membrane does not restrict the outlet; bolt the membrane clamping collar to the body - certain collars are reversible to increase height adjustability. Note 1: If a G series body is being used without a membrane, ensure that membrane clamping collar securing holes on top face of body are sealed. Note 2: In some cases the membrane clamping collar serves to connect the grating or cover to the body, so it must be fitted even where a membrane is not used. 2. Measure the distance between the top of the connecting pipework and finished floor level. 3. Check that this distance will enable the complete gully (with extensions, if applicable) to be installed with the top face of the grating or cover flush and level with the finished floor. Note: Where a damp-proof membrane is used, the body must be installed with the top of the flange at or below membrane level. 7. Fit grating, cover, or funnel, with extensions,frame or collar as applicable; set top face flush and level with the finished floor using height adjustability features. Use a suitable sealant on all threaded joints to ensure a watertight assembly. Membrane Level 4. Connect body (with spigot adaptor if applicable) to pipework. 5. Infill as required. 8. Infill or lay floor screed and apply final floor finish (e.g. tiles, marble, paviors, terrazzo) around the grating or cover. Note: Installation of gratings and covers for use with sheet floor covering, such as vinyl, is included in a separate brochure. 4

5 FLOOR GULLIES Typical Installations FINISHED FLOORS DAMP PROOF MEMBRANE FINISHED FLOOR FLOOR SCREED DAMP PROOF MEMBRANE FINISHED FLOOR FLOOR SCREED GRATING FILTER BUCKET (Optional) L24 SERIES GRATING CONTOURED CHANNEL TILE DAMP PROOF MEMBRANE STRAINER (OPTIONAL) MEMBRANE CLAMPING COLLAR BODY FLOOR SCREED BELL TRAP STRUCTURAL SLAB SPIGOT ADAPTOR (Select separately) STRUCTURAL SLAB OPTIONAL SIDE INLET STRUCTURAL VARI-LEVEL ADAPTOR OR BODY SLAB (G SERIES SHOWN) Stainless Steel Gully (See pages 6 to 8) Vari-Level, Non-Trapped. (See pages 10 to 11 and 14 to 16) Vari-Level, Trapped, with Contoured Grating (See pages 12 to 16) FINISHED FLOOR MEMBRANE GRATING / COVER MEMBRANE CLAMPING COLLAR FINISHED FLOOR SECURED FLAT GRATING MEMBRANE CLAMPING COLLAR SHEET FLOORING CLAMPING COLLAR FLOOR COVERING GRATING / COVER BODY BODY OPTIONAL STRUCTURAL SLAB SPIGOT ADAPTOR REMOVABLE BOTTLE TRAP STRUCTURAL SLAB SPIGOT ADAPTOR (SELECT SEPARATELY) SIDE INLET BODY TIMBER SUPPORT TIMBER PACKING Vari-Level Trapped (with removable Bottle Trap) with Bituminous Membrane (See pages 11,14 to 16 and 17) Uni-Level with Asphalt or Composition Floor (See page 29) Vari-Level with Sheet Floor Covering in a Wooden Floor (See pages 12 to 16) UNFINISHED FLOORS FLOOR DAMP PROOF MEMBRANE FLOOR SCREED GRATING FLOOR DAMP PROOF MEMBRANE FLOOR SCREED GRATING FLOOR FLOOR SCREED GRATING DAMP PROOF MEMBRANE MEMBRANE CLAMPING COLLAR BODY MEMBRANE CLAMPING COLLAR BODY MEMBRANE CLAMPING COLLAR BODY SPIGOT ADAPTOR (Select separately) STRUCTURAL SLAB SPIGOT ADAPTOR (Select separately) STRUCTURAL SLAB SPIGOT ADAPTOR (Select separately) STRUCTURAL SLAB Multi-Level (See page 30) Multi-Level (See page 30) Multi-Level (See page 30) 5

6 STAINLESS STEEL GULLIES FOR FINISHED FLOORS Body Assemblies ( For use with gratings shown opposite ) P TRAPPED - 60mm Seal 350 Dia 150 Sq 400 Dia 200 Sq 193 Max 260 Max 221 Max. 305 Max Q23/30 body assy. with membrane clamping collar and Q42/32 grating. Spec. Outlet Grating Depth Q21/30 75 O.D. 30 Q21/40 75 O.D. 40 Spec. Outlet Grating Depth Q23/ Q23/ Sq 225 Optional side inlets (4" max.) Sq 300 Bolt-on Funnel: U511 Filter Bucket ( B) Spec. Outlet Grating Depth Q27/ Q27/ Spec. Outlet Grating Trap Depth Q12/ P Q12/ P Q13/ Q Q13/ Q Strainer ( S) Trap See page 9 for details of side inlets 6

7 STAINLESS STEEL GULLIES FOR FINISHED FLOORS Body Assemblies, Gratings. BELL TRAPPED - 60mm Seal 350 Dia 150 Sq 400 Dia 200 Sq 200 Sq Filter Bucket ( B) Bolt-on Funnel: U Max 400 Max 325 Strainer ( S) Bell Trap Spec. Outlet Grating Depth Q22/30 75 O.D. 30 Q22/40 75 O.D. 40 Spec. Outlet Grating Depth Q24/ Q24/ Spec. Outlet Grating Depth Q28/ Q28/ Optional side inlets (4" max.) 300 Sq. 160 Filter Bucket ( B) 300 Sq Bolt-on Funnel: U511 Bell Trap Spec. Outlet Grating Depth Q14/ Q14/ Q14/ Q14/ Spec. Outlet Grating Depth Q10/ Q10/ Q10/ Q10/ STAINLESS STEEL GRATINGS ( For use with body assemblies shown above and opposite ) Anti-Slip Mesh Smooth Mesh Smooth Perforated Bar Grating Spec. Size Depth/ Spec. Size Depth/ Spec. Size Depth Spec. Size Depth/ Sq. Load Bar Sq. Load Bar Sq. Sq. Load Bar Q /2 Q /3 Q /2 Q /3 Q /2 Q /3 Q /2 Q /3 Q /2 Q /3 Q /2 Q /3 Q Q Q /5 Q /5 Q /5 Q /5 Q /5 Q /5 Streamline Spec. Size Depth/ Sq. Load Bar Q / 3 Q / 3 NOTE : Please ensure that SIZE and DEPTH of the selected grating match the selected body assembly. 7

8 STAINLESS STEEL GULLIES FOR SHEET FLOOR COVERING Body Assemblies (For use with 300 Sq. gratings shown on page 7) BELL TRAPPED - 60mm Seal 325 Sq Sq Optional Side Inlets Filter Bucket ( B) Spec. Outlet Grating Depth Q14/30V Q14/40V Q14/36V Q14/46V Spec. Outlet Grating Depth Q10/30V Q10/40V Q10/36V Q10/46V Bolt-on Funnel: U511 Bell Trap P TRAPPED - 60mm Seal Optional Side Inlets 325 Sq. Filter Bucket ( B) Bolt-on Funnel: U511 Spec. Outlet Grating Trap Depth Q12/30V P Q12/40V P Q13/30V Q Q13/40V Q 8

9 FLOOR GULLIES Side Inlets For typical installation illustrations, see pages 5 and 25. Side inlets in a gully permit the underfloor connection of pipes from fixtures such as sinks and wash basins, from drainage channels and from other gullies. Side inlets in Wade trapped gullies are located completely above the water level, except in G102, H102 and GD Series where the inlets are partially below the water level. The illustrations represent typical gully bodies, VIEWED FROM ABOVE, and show the SPEC. CODES for all possible combinations of LOCATIONS. Side inlets in cast iron gully bodies are optional extras which unless otherwise requested, will be supplied as BSP female threads (specify thread size); stainless steel bodies have BSP female threads up to 2"; above 2", spigot side inlets are supplied to suit BS 416 pipework. GP11 series plastic gully bodies have 3 side inlets moulded in that will accept 50mm plastic pipework; these inlets are usable by removing knock-outs from the body on site. Denotes side inlet locations. Denotes outlet position (where applicable). Gully Bodies with Vertical Outlet 1A 2A 2B 3A 4A Gully Bodies with P or S Trapped Outlet 1A 1B 1C 2A 2B 2C 3A Gully Bodies with Horizontal Outlet 1A 1B 1C 1D 2A 2B 2C 2D 2E 2F 3A 3B 3C 3D 4A To Specify / Order Quote the Spec. for the selected BODY, with suffix I, and the LOCATION and SIZE of each inlet. e.g. G304 body with 2 side inlets tapped 1.5" BSP, in locations per illustration 2B. Specify: G304 I - 2B x 1.5" BSP 9

10 VARI-LEVEL NON-TRAPPED BODIES (CAST IRON) (For use with Vari-Level threaded gratings / covers shown on pages 14-16, 29 and 31) 185 Dia. 200 Dia (C3) 75(C2) C204 Body Spec. Outlet Pipework Size System B BS 416 / DIN B BS 416 B BS 416 / Din / Plastic B202 2"BSP B203 3"BSP Spec. Outlet Pipework Size System C202 2"BSP C203 3"BSP C204 4"BSP C Plastic C Plastic C BS437 C BS437 C BS416 C BS Dia. Deep Sump 200 Dia. 265 Dia C504 Body illustrated with optional side inlet see page 9 for details. Optional side inlets - max.2" BSP Spec. C502 C503 C504 Outlet Size 2"BSP 3"BSP 4"BSP Spec. D204 D206 Outlet Size 4"BSP 6"BSP Optional side inlets - max. 4" BSP Spec. Outlet Size D404 4"BSP D406 6"BSP 265 Dia. 188 Dia. 265 Dia B D604 Body 45 Outlet 45 Outlet Horizontal Outlet Spec. Outlet Spec. Outlet Spec. Pipework B Size Size System B504 4"BSP D604 4"BSP D702 2"BSP 86 D703 3"BSP 73 D704 4"BSP 83 Note: C and D Series bodies are supplied with membrane clamping collar, which is optional on B Series bodies 10

11 VARI-LEVEL NON-TRAPPED BODIES (CAST IRON) (For use with Vari-Level threaded gratings / covers shown on pages 14-16, 29 and 31.) A 265 Dia. Horizontal Outlet Optional Side Inlets - max.4" BSP (See page 9 for details) Spec. Outlet A Size D802 2"BSP 280 D803 3"BSP 272 D804 4"BSP 260 D804 Body D8 Series bodies are supplied with Membrane Clamping Collar Vari-Level Non-Trapped Bodies (Cast Iron) for use with Bituminous Membrane ( For use with Vari-Level threaded gratings / covers shown on pages 14-16, 29 and 31.) Typical Gully Assembly D1109 body with membrane clamping collar and K2103 nickel bronze grating 305 Dia. 305 Dia. 305 Dia. A B 90 Threaded Outlet Spec. Outlet Size D1002 2"BSP D1003 3"BSP D1004 4"BSP Spigot Outlet Spec. Outlet A Size D mm BS D mm BS Horizontal Outlet Spec. Outlet B Size D1207 2"BSP 80 D1208 3"BSP 67 D1209 4"BSP 117 D Series bodies are supplied with Membrane Clamping Collar. Connections Bodies with spigot outlet are for direct connection to pipework, versions with threaded outlet are for connection to pipework by means of a spigot adaptor shown on page

12 VARI-LEVEL TRAPPED BODIES (CAST IRON) (For use with Vari-Level threaded gratings / covers shown on pages 14-16, 29 and 31) P TRAPPED - 50 mm seal E E B B A A G303 body illustrated with optional side inlets Optional side inlets - max.2" BSP Spec. Outlet A E B Size *G102 2"BSP Optional side inlets - max.2" BSP Spec. Outlet A E B Size G202 2"BSP G203 3"BSP G303 75mm G mm G mm G804 Body S TRAPPED - 50 mm seal G604 Body A E Optional side inlets - max.2" BSP Spec. Outlet A E B Size G502 2"BSP G503 3"BSP G603 75mm G mm G mm B Options All cast iron trapped bodies except H304 have facility for optional side inlets, see page 9 for details. Membrane clamping collar is supplied with GC and GD Series and is optional on other bodies except H304. Connections Bodies with spigot outlet are for direct connection to pipework, versions with threaded outlet are for connection to pipework by means of a spigot adaptor shown on page 24. G1004 Body P TRAPPED mm seal E 'E' B 'B' A 'A' H204 Body * Denotes 3" throat Optional side inlets (H1= max.11 /2" BSP) (H2= max. 2" BSP) Spec. Outlet A E B Size *H102 2"BSP H203 3"BSP H204 4"BSP Spec. Outlet A E B Size H304 4"BSP

13 VARI-LEVEL TRAPPED BODIES - CAST IRON (For use with Vari-Level threaded gratings / covers shown on pages 14-16, 29 and 31) P TRAPPED - with rodding access mm seal J204 Body A B D C Optional side inlets - max.2" BSP Spec. Outlet A B C D Size J204 4 BSP x Close proximity of grating and access cover prevents the adjacent use of widest versions. Options All cast iron trapped bodies except H304 have facility for optional side inlets, see page 9 for details. Membrane clamping collar is supplied with GC and GD Series and is optional on other bodies except H304. Connections Bodies with spigot outlet are for direct connection to pipework, versions with threaded outlet are for connection to pipework by means of a spigot adaptor shown on page 24. BELL TRAPPED - 50mm seal with full bore rodding access 265 Dia. TRAPPED - 50mm seal For use in low volume drainage applications 200 Dia GD144 Body illustrated with optional side inlet. (Note: Side inlets up to 2" are completely above water level, over 2" are partially below). Optional side inlets - max.4" BSP Spec. Outlet Pipework Size System BS 416 / DIN / GD { Plastic 110mm GD BS 437 Removable Bottle Trap Optional side inlets - max.2" BSP Spec. Outlet Pipework Size System GC { BS 416 / DIN / Plastic 110mm VARI-LEVEL TRAPPED BODIES - PLASTIC 220 Dia. 187 Dia. 220 Dia (Invert) 50 Dia mm Seal 50mm Seal 50mm Seal and optional side inlets Spec. Outlet Pipework Size System GP Plastic Spec. Outlet Pipework Size System GP /50 Plastic Spec. Outlet Pipework Size System GP Plastic Note: All bodies on this page are for use with gratings / covers with 4" throat, (not K2801, K2901, K3001, K32 or gratings with option suffix V ) except J204 which may also be used with 3" versions. (if used with U1101 reducing bush - see p.17). K2801 may be used with GP312 and GP

14 VARI-LEVEL GRATINGS For use with bodies shown on pages CAST IRON - BS EN sherardized, matt finish Circular grating K2103 CI 155 Suitable for service and parking areas, plant rooms etc. K Spec. L2501 CI Size 150 sq. Spec. L2601 Size 150 sq. Decorative floral pattern Suitable for service and parking areas, plant rooms etc. NICKEL BRONZE - BS satin finish Circular grating K K K Indirect waste connector K For use with sheet floor covering such as vinyl. K K K K K K For use with trowel applied composition flooring. 4mm flange depth. For security areas. Cover screws down to permit drainage. Reduces risk of blockages in channels. Removable dome protudes 30mm 176 dia.to take multiple indirect waste pipes; with peripheral grating Spec. Size above FFL L W H K dia.to take single indirect waste pipe; with peripheral grating Spec. Size above FFL Dia. H K dia.to take single indirect waste pipe; with peripheral cover and vermin guard. Spec. Size above FFL Dia. H K diato take multiple indirect waste pipes; with peripheral coveand vermin guard. Spec. Size above FFL L W H K dia. For use with sheet floor covering such as vinyl. With peripheral cover and vermin guard. Spec. Size above FFL Dia. H K Denotes 3" throat (all others 4") Spec. Size above FFL L W H K sq.to take single indirect waste pipe; with peripheral cover and vermin guard. Spec. Size above FFL Dia. H L sq.to take multiple indirect waste pipes; with peripheral cover and vermin guard. Spec. Size above FFL L W H L

15 VARI-LEVEL GRATINGS For use with bodies shown on pages NICKEL BRONZE - BS satin finish Standard square grating Rectangular Square framed grating Johnson 4200 Spec. Size Spec. Size Spec. Size Spec. Size L sq. L x 204 L sq. L sq. L sq. L x 430 L sq. L sq. Gail 4420 Pilkington / Wooliscroft 2302 Platt 2300 Ruabon Keramic Spec. Size Spec. Size Spec. Size Spec. Size Spec. Size L x 240 L sq. L sq. L sq. L sq. Langley / Buchtal 4420 / Decorative floral pattern Hinged grating Spec. L2409 Size 150 sq. Spec. L2501 Size 150 sq. Spec. L3001 Size 161 sq. Grating concealed by solid hinged cover. L5401 version has sealed cover. Spec. Size L sq. L sq. STAINLESS STEEL - Grade satin finish With peripheral slot for use with sheet floor covering such as vinyl. K Circular grating K For use with sheet floor covering such as vinyl. K For use with trowel applied composition flooring. 6mm flange depth K Flanged with peripheral slot. Self securing K Security area drainage Square grating Streamline heel-proof reverse wedge profile Spec. Size Spec. Size K L sq. L sq. L sq. L sq. Square perforated grating Spec. Size L sq. L sq. Hinged cover with circular non-secured grating inside Spec. Size L sq. 176 dia.condensate funnel with vermin guard, for use with sheet floor covering Spec. Size above FFL Dia. H K sq.condensate funnel with vermin guard Spec. Size above FFL Dia. H L Denotes 3" throat (all others 4") 15

16 VARI-LEVEL ACCESS COVERS For use with bodies shown on pages DUCTILE IRON - BS EN 1563 and sherardized, matt finish SuperSeal (double sealed) K SuperSeal (double sealed) Spec. Size L Sq. NICKEL BRONZE - BS satin finish Gasketed, for use with sheet floor covering, such as vinyl K K K Gasketed K K K Gasketed - for use with trowel applied composition flooring. 4mm flange depth. K Plug with O ring seal for use in plunge & foot baths. K SuperSeal (double sealed) K SuperSeal (double sealed) For use with sheet floor covering, such as vinyl. K SuperSeal (double sealed) Recessed for flooring material. K Gasketed Spec. Size L Sq. Gasketed Spec. Size L Sq. Hinged cover in square frame. (unsealed) Spec. Size L Sq. Hinged cover with grating inside. L5401 version has sealed cover. Spec. Size L Sq. L Sq. SuperSeal (double sealed) Spec. Size L Sq. SuperSeal (double sealed) Spec. Size L Sq. STAINLESS STEEL - GRADE satin finish For use with sheet floor covering, such as vinyl (unsealed) K Gasketed - for use with trowel Gasketed applied composition flooring. 6mm flange depth. K K SuperSeal (double sealed) K SuperSeal (double sealed) for use with sheet floor covering, such as vinyl K Hinged cover with a circular non-secured grating inside. (unsealed) Spec. Size L Sq. SuperSeal (double sealed) Spec. Size L Sq. SuperSeal (double sealed) Recessed for flooring material. Spec. Size L Sq. 16 Denotes 3" throat (all others 4")

17 VARI-LEVEL ACCESSORIES For use with Vari-Level Gratings and Access Covers BOLT-ON FUNNELS PORTABLE FUNNEL Stainless Steel Spec. Size Dia. H U501 N/Bronze U502 Cast iron U511 S/Steel Spec. Size L W H U601 N/Bronze U602 Cast iron Spec. Size L W H U BACKWATER VALVE FILTER BUCKET - Nylon 6 Used to intercept debris, valuables etc. REMOVABLE BOTTLE TRAP (50mm Seal) Spec. Throat Dia. U703 3" For use with Vari-Level grating/cover, 4" throat version, add suffix V to grating Spec.. (Not for use with GC, GD or GP Series bodies) NOTE: A filter bucket cannot be fitted if a backwater valve is used. UP701 UP702 To fit inside gratings with 4" throat. (Not K28, K29 or K30). Typical installation is shown on page 5. Deep version for use with Vari-Level gratings with bodies C5, D4, and D8, adaptors T702, T901 and extensions U1 series. U1404 To fit inside grating or body with 4" throat / outlet. Typical installation is shown on page 5. GRATING EXTENSION - Cast Iron 130 Dia. GULLY ADAPTORS - To connect Vari-Level gratings/ covers to clay or PVC bodies 150 mm sq. REDUCING BUSH Spec. Thread Height Female Male U101 3" 3" 127 U102 4" 4" 60 U103 4" 4" 100 U104 4" 4" 152 U201 4" 3" 115 U208 4" 25 UP104 4" 4" 152 T1302 For use with 3" throat Grating/Cover T1301 For use with 4" throat Grating/Cover 188 mm dia. T1402 T1401 Weephole For use with 3" throat Grating/Cover For use with 4" throat Grating/Cover To enable 3" throat U1101 gratings/covers to be used in Vari-Level bodies / adaptors with 4" inlet. Note: Height of grating / cover will be increased by 15mm min./ 27mm max. Plastic (ABS) version See T1401 for illustration 17

18 VARI-LEVEL ACCESSORIES For use with Vari-Level Gratings, Access Covers and Bodies ADAPTORS TO PIPEWORK: Vari-Level Gratings and Access Covers, when used without a body, may be connected to pipework by means of a cast iron adaptor, as shown in the following table. Adaptors for use with Vari-Level Gratings and Access Covers with 3" throat. Spec. Pipework Overall System Length T701 Plastic 82mm O.D. 127 T714 Plastic 75mm O.D. 130 T712 Plastic 110mm O.D. 115 T801 C.I. BS mm 127 T712 C.I. BS mm 115 T701 C.I. DIN SMU 75mm 127 T712 C.I. DIN mm 115 T911 Clay SuperSleve 100mm 145 All made of cast iron, except TP702, plastic (ABS) Adaptors for use with Vari-Level Gratings and Access Covers with 4" throat. Spec. Pipework Overall System Length T703 Plastic 82mm O.D. 115 T704 Plastic 75mm O.D. 115 TP702 Plastic 110mm O.D. 152 T803 C.I. BS mm 115 T702 C.I. BS mm 100 TP702 C.I. BS mm 152 T703 C.I. DIN SMU 75mm 115 TP702 C.I. DIN mm 152 T901 Clay SuperSleve 100mm 130 INSTALLATION ADAPTORS - For use with G2 - G10 series trapped bodies. 245 Dia. 300 Dia. U1501 Stainless steel support plate and cast iron membrane clamp to adapt G2-G10 series bodies for installation in a timber deck with tile floor finish. U1601 Stainless steel asphalt flange for use with G2-G10 series bodies. 90 SWEPT BEND Malleable iron DEEP SEAL P TRAP Cast Iron C A Spec. U1301 Thread 2" BSP M/F Spec. Inlet / Outlet A C Thread Size U902 2" BSP U903 3" BSP U904 4" BSP

19 CAST IRON - BS EN sherardized, matt finish DIRECT CONNECTION GRATINGS For accessories see page 17. Pipework adaptors are shown on page 24. Standard circular grating K2193CI 155 4" C.I. + P Suitable for service and parking areas, plant rooms etc. K " C.I. + P Decorative floral pattern. L2591CI 150sq. 4" C.I. + P Suitable for service and parking areas, plant rooms etc. Spec. Size Pipework L Sq. 4" C.I. + P NICKEL BRONZE - BS satin finish (see also pages 20-21) With central securing screw K " BSP Self securing K " BSP Standard circular grating K mm Plastic K " C.I. + P K " BS416 K " C.I. + P Indirect waste connector K " C.I. + P For use with trowel applied composition flooring. 4mm flange depth For security areas. Cover screws down to permit drainage. Reduces risk of blockages in channels. Removable dome protrudes 30mm. 176 dia.to take multiple indirect waste pipes; with peripheral grating K " C.I. + P K " C.I. + P K " C.I. + P Spec. Funnel Size Pipework K x 85 x 99 4" C.I. + P 176 dia.to take single indirect waste pipe; with peripheral grating. Spec. Funnel Size Pipework K dia.x 96 4" C.I. + P 150 dia.to take single (K3391) or multiple (K3392) indirect waste pipe; with peripheral cover and vermin guard. Spec. Funnel Size Pipework K dia.x 101 4" C.I. + P K x 85 x 96 4" C.I. + P 176 dia.for use with sheet floor covering such as vinyl. With peripheral cover and vermin guard. Spec. Funnel Size Pipework K dia.x 101 4" C.I. + P 176 dia.for use with sheet floor covering such as vinyl. With peripheral cover and vermin guard. Spec. Funnel Size Pipework K dia.x85x99 4" C.I. + P 150 dia.to take single indirect waste pipe; with peripheral cover and vermin guard. Spec. Funnel Size Pipework L dia.x101 4" C.I. + P 150 diato take multiple indirect waste pipes; with peripheral coveand vermin guard. Spec. Funnel Size Pipework L x 85 x 96 4" C.I. + P C.I. + P means Cast Iron BS 416 / DIN and plastic 19

20 NICKEL BRONZE - BS satin finish DIRECT CONNECTION GRATINGS (For accessories see page 17. Pipework adaptors are shown on page 24. With central securing screw Spec. Size Pipework L Sq. 2" BSP Self securing Spec. Size Pipework L Sq. 2" BSP Standard square grating Spec. Size Pipework L Sq. 82mm Plastic L Sq. 3" BS416 L Sq. 4" C.I. + P L Sq. 4" C.I. + P L Sq. 4" C.I. + P Rectangular Spec. Size Pipework L x mm Plastic L x 204 3" BS416 L x 430 4" C.I. + P Square framed grating Spec. Size Pipework L Sq. 4" C.I. + P Decorative floral pattern. Spec. Size Pipework L Sq. 4" C.I. + P Hinged Grating Spec. Size Pipework L Sq. 4" C.I. + P Grating concealed by solid hinged cover. L5491 version has sealed cover. Spec. Size Pipework L Sq. 4" C.I. + P L Sq. 4" C.I. + P Johnson 4200 Gail 4420 Pilkington / Wooliscroft 2302 Platt 2300 Spec. Size Pipework Spec. Size Pipework Spec. Size Pipework Spec. Size Pipework L Sq. 82mm Plastic L x 240 4" C.I. + P L Sq. 82mm Plastic L Sq. 4" C.I. + P L Sq. 3" BS416 L Sq. 3" BS416 Ruabon Spec. Size Pipework L Sq. 82mm Plastic L Sq. 3" BS416 Keramic Spec. Size Pipework L Sq. 4" C.I. + P Langley Buchtal 4420 / Spec. Size Pipework L Sq. 82mm Plastic L Sq. 3" BS416 C.I. + P means Cast Iron BS416 / DIN19522 and Plastic 20

21 NICKEL BRONZE - BS satin finish For use with sheet floor covering DIRECT CONNECTION GRATINGS N mm Plastic N mm Plastic N mm Plastic N mm Plastic N mm Plastic N mm Plastic C.I. + P means Cast Iron BS 416 / DIN and Plastic Versions with cast iron backnut for use in timber floors N " BS416 N mm Plastic N mm Plastic DIN N " BS437 N " SuperSleve K " C.I.+P STAINLESS STEEL - Grade satin finish With peripheral slot for use with sheet floor covering such as vinyl. K " C.I. + P Circular Grating K " C.I. + P For use with sheet floor covering, such as vinyl K " C.I. + P For use with trowel applied composition flooring. 6mm flange depth K " C.I. + P Flanged with peripheral slot. Self securing Security area drainage Square Grating Streamline heel - proof reverse wedge profile K " C.I. + P K Plastic K " BS416 Spec. Size Pipework L Sq. 4" C.I. + P Spec. Size Pipework L Sq. 4" C.I. + P L sq. 4" C.I. + P Square perforated grating Spec. Size Pipework L Sq. 4" C.I. + P L Sq. 4" C.I. + P Hinged cover with a circular non - secured grating inside Spec. Size Pipework L Sq. 4" C.I. + P 176 dia.condensate funnel with vermin guard, for use with sheet floor covering Spec. Size above FFL Dia. H K Condensate funnel with vermin guard Spec. Size Pipework L Dia.x 100H 4" C.I. + P C.I. + P means Cast Iron BS 416 / DIN and Plastic 21

22 DIRECT CONNECTION ACCESS COVERS For accessories see page 17. Pipework adaptors are shown on page 24. DUCTILE IRON - BS EN sherardized, matt finish (with cast iron frame) SuperSeal (double sealed) K "C.I. + P SuperSeal (double sealed) Spec. Size Pipework L Sq. 4"C.I. + P NICKEL BRONZE - BS satin finish Gasketed K mm Plastic K " BS416 K " C.I. + P K " C.I. + P Gasketed - for use with trowel applied composition flooring. Stainless steel flange 220mm dia. 4mm flange depth. K "C.I. + P Plug with O ring seal for use in plunge and foot baths K "C.I. + P SuperSeal (double sealed) K "C.I. + P SuperSeal (double sealed) Recessed for flooring material K "C.I. + P Gasketed Spec. Size Pipework L Sq. 4"C.I. + P Gasketed Spec. Size Pipework L Sq. 4"C.I. + P Hinged cover (unsealed) in square frame Spec. Size Pipework L Sq. 4"C.I. + P Hinged cover with grating inside. L5391 version is unsealed, L5491 version has sealed cover Spec. Size Pipework L Sq. 4" C.I. + P L Sq. 4" C.I. + P SuperSeal (double sealed) Spec. Size Pipework L Sq. 4" C.I. + P SuperSeal (double sealed) Spec. Size Pipework L Sq. 4" C.I. + P C.I. + P means Cast Iron BS 416 / DIN and Plastic 22

23 NICKEL BRONZE - BS satin finish For use with sheet floor covering DIRECT CONNECTION ACCESS COVERS STAINLESS STEEL - Grade satin finish Gasketed Gasketed Gasketed SuperSeal (Double Sealed) Gasketed N mm Plastic N " BS 416 N " BS 437 N mm Plastic N mm Plastic N " SuperSleve N mm Plastic N mm Plastic N mm Plastic (N214 and N218 have backnut included) K " CI + P K " CI + P For use with sheet floor covering, such as vinyl (unsealed) K " CI + P Gasketed K " CI + P Gasketed - for use with trowel applied composition flooring.6mm flange depth. K " CI + P SuperSeal (double sealed) K " CI + P SuperSeal (double sealed) For use with sheet floor covering, such as vinyl Hinged cover with a circular nonsecured grating inside Spec. Size Pipework K " CI + P L Sq. 4" C.I. + P C.I. + P means Cast Iron BS 416 / DIN and Plastic SuperSeal (double sealed) Spec. Size Pipework L Sq. 4" C.I. + P SuperSeal (double sealed) Recessed for flooring material Spec. Size Pipework L Sq. 4" C.I. + P NICKEL BRONZE BS Satin Finish ACCESS COVERS - GENERAL PURPOSE Unsealed, secured. R Unsealed, secured. Spec. Size R Sq. R Sq. Sealed, recessed for flooring material. R Sealed, secured, recessed for flooring material. Spec. Size R Sq. ACCESS COVERS FOR FLEXIBLE SHEET FLOOR COVERING DOUBLE SEALED ACCESS COVER FOR MAN ENTRY Stainless Steel clamping frame 50mm wide,is only part visible when insalled Sealed R Spec. Clear Opening Size R x 450 R x 450 R x 600 R x 600 R x 750 R x 600 Stainless Steel cover. For use in wall Spec. Size R Sq. R Sq. 23

24 ADAPTORS Adaptors and couplings are available to connect Wade products to pipework made by others T6 Series T1103 T12 Series T1501 T1603 Hub adaptor for caulk joint. Push fit coupling BS416/437 to SuperSleve Copper to BS 416. Adaptor must be brazed / soldered to copper pipe before connecting to BS 416 by means of a proprietary coupling. MJ coupling BS 416 to Plastic FROM TO ADAPTOR Spec. kg 2" BSP Female 50mm cast iron caulk joint T " BSP Female 75mm cast iron caulk joint T " BSP Female 100mm cast iron caulk joint T mm BS 416 or BS mm SuperSleve T mm BS mm copper T mm BS mm copper T mm BS mm copper T mm BS mm plastic T mm BS mm DIN Ensign T MJ coupling 75mm BS 416 to Ensign SPIGOT ADAPTORS A comprehensive range of spigot adaptors, shown in the following table, is available to enable gully bodies with BSP threaded outlet to be connected speedily and effectively to all pipework in general use. To complete the connection a coupling may be required as indicated. Longer spigots, such as required to pass through a slab, can be made in 10mm increments up to 1000mm. To specify/order add suffix # and length (mm), eg. T103#250. PIPEWORK BODY SPIGOT ADAPTOR REQUIRED OUTLET COUPLING System Nom.Dia. BSP Spec. O.D. Length Material Weight mm mm mm kg Cast Iron BS " T Mild Steel, sherardized 0.5 Proprietary Cast Iron BS " T Mild Steel, sherardized 0.9 Proprietary Cast Iron BS " T Cast Iron 1.2 Proprietary Cast Iron BS " T Cast Iron 1.1 Proprietary Cast Iron BS " T Cast Iron 1.4 Proprietary Cast Iron BS " T Cast Iron 1.8 Proprietary Cast Iron DIN (Ensign + SMU) 50 2" T Mild Steel, sherardized 0.5 Proprietary Cast Iron DIN (SMU) 75 3" T Mild Steel, sherardized 0.7 Proprietary Cast Iron DIN (Ensign) 75 3" T Mild Steel, sherardized 0.9 Wade T1603 Cast Iron DIN (Ensign + SMU) 100 4" T Cast Iron 1.2 Proprietary Cast Iron DIN (Ensign + SMU) 150 6" T Cast Iron 1.1 Proprietary Plastic 50 2" T Plastic (ABS) 0.1 None Plastic 82 3" T Plastic (ABS) 0.2 Proprietary Plastic 110 4" T Plastic (ABS) 0.2 None Plastic 160 6" T Plastic (ABS) 0.6 Proprietary Clay (Densleve) 100 4" T Cast Iron 4.0 Proprietary Clay (SuperSleve) 100 4" T Cast Iron 2.8 Proprietary Clay (SuperSleve) 150 6" T Cast Iron 4.6 Proprietary Solvent weld socket 24

25 FLOOR GULLIES AND ACCESS COVERS Wade offers a comprehensive range of gullies with versions to suit different kinds of floor and floor finish, for connection to all pipework in general use, as shown on pages 4 to Stainless steel gully with side inlets. 2. Super-Seal access cover in a tiled floor. 3. Watertight drainage in a vinyl covered timber floor. 4. A selection of floor gullies, access covers, and accessories

26 ROOF OUTLETS Wade offers a range of roof outlets with versions for use with different types of roof construction, as shown on pages 34 to A selection of Roof Outlets and accessories. 2. WF105 parapet outlet connected to a WJ104 downspout nozzle in an installation with a single ply membrane WC224Z roof outlet with WG102 underdeck clamp and WT103 spigot, in a warm roof with single membrane. 4. WD204 roof outlet in an inverted roof. 4 26

27 LINEAR DRAINAGE Wade offers a range of gratings of stainless steel, nickel bronze, aluminium and cast iron for use in frames or stainless steel channel, as shown pages 40 to Heavy duty bar grating designed for trolley wheel-loading. Austenitic stainless steel channel and grating meet the high standards of hygiene demanded in today's working environments. Channel profile SVF ensures watertight connection when used with flexible sheet floor covering such as vinyl. 2. Stainless steel channel with Streamline stainless steel grating. 3. Typical installation in a vinyl covered floor. A selection of gratings. 27

28 Wade drainage products are installed in and near all kinds of buildings, some examples of which are shown below. A.E.L.T.C.C. Wimbledon Chep Lap Kok Airport, Hong Kong Drainage and access in a vinyl floor A McDonalds Restaurant The British Library Drainage in block paving Asda Store, Runcorn Access covers in a marble floor 28

29 GULLIES FOR ASPHALT / COMPOSITION FINISHED FLOORS Suitable for areas with an asphalt finish, subject to car and light commercial traffic. UNI-LEVEL NON-TRAPPED GULLIES 305 Dia. A A 90 WB324 Gully Cast iron body with 220 dia. sherardized ductile iron grating Vertical threaded outlet Spec. Outlet Size WB322 2" BSP WB323 3" BSP WB324 4" BSP B Horizontal threaded outlet Spec. Outlet A B Size WB332 2" BSP WB333 3" BSP WB334 4" BSP Dia. (Integral) Spigot outlet Spec. Outlet A Size WB303 75mm 165 WB m 190 A WB514 Gully Cast iron body with 320 sq. sherardized ductile iron grating 350 Dia. Vertical threaded outlet Spec. Outlet A Size WB514 4" BSP 171 WB516 6" BSP 149 VARILEVEL AND DIRECT CONNECTION GRATINGS (Sherardized Cast Iron) Vari-Level version is for use with Vari-Level cast iron bodies shown on pages 10 to 13. With stainless steel asphalt membrane clamp. Spec. Overall Vari - Level Direct Con. Size K2501A K2591A 176 dia. Direct connection version is for use without a body and for connection to 100 mm pipework - Cast iron BS 416 / DIN or PVC. See page 24 for pipework adaptors. 29

30 GULLIES FOR UNFINISHED FLOORS For use in unfinished floors such as plant rooms, yards and car parks MULTI-LEVEL NON-TRAPPED GULLIES - For use with Vari-Level bodies D2 - D8 and GD, shown on pages 10 to 13 Sher. ductile iron grtg. Spec. Overall Size M dia. Cast Iron Extension Spec. U301 Cast Iron Body with hinged sherardized ductile iron grating. ( F3 have stainless steel body ) Spec. Overall Overall Outlet Width Height Size F x max. 4" BSP F x max. 6" BSP F x max. 100mm F x max. 150mm For use with E Series bodies shown below Sher. ductile iron grtg. Spec. Overall Size M dia. Sher. ductile iron grtg. Spec. Overall Size M sq. Cast Iron Extension Spec. U401 Note: Versions with D, GD and E Series bodies are supplied with a membrane clamping collar, which is optional on F Series. See page 9 for details of side inlets. Cast Iron Body Medium Sump Cast Iron Body Deep Sump Optional side inlets - Max. 4" BSP Spec. Outlet Height Size E204 4" BSP 125 E206 6" BSP 125 Spec. Outlet Height Size E404 4" BSP 280 E406 6" BSP 280 OPTION: Filter Bucket - add suffix B to the Spec. ALSO AVAILABLE: WD2 to WD7 Series, Multi-Level Non-Trapped Gullies - see page 37 for details of roof outlets which are commonly used as floor gullies. 30

31 MISCELLANEOUS FLOOR GULLIES GUNMETAL GULLIES - For use in metal decks Trapped Non-Trapped For tile or composition flooring Spec. Outlet Height Dia Size Max. P P For sheet floor covering Spec. Outlet Height Dia Size Max. P P For tile or composition flooring Spec. Outlet Height Dia Size Max. P For sheet floor covering Spec. Outlet Outlet Height Dia Size Con. Max. P BSPT Male P Copper HIGH CAPACITY GULLIES - Non-Trapped unless stated L: 717 x W: 699 x H: 220 L: 295 x W: 295 x H: 289 L: 450 x W: 450 x H: 280 L: 633 x W:220 x H: 405 Zinc coated mild steel body with sher. cast iron grating Cast iron body with nickel bronze grating Trapped stainless steel body with hinged sher. ductile iron grating. Trapped cast iron body with nickel bronze grating and nickel Spec. Outlet Spec. Outlet Body Spec. Outlet bronze sealed cover Finish Spec. Outlet Q mm BS 416 Q301 4" BSP Lacquered Q mm BS 416 Q mm BS 416 Q302 4" BSP Plastic coated Q mm BS 437 L: 419 x W: 216 x H:118 L: 552 x W: 292 x H:146 L: 410 x W: 295 x H: Dia. x H: 357 Max. Cast iron body with sher. cast iron grating for use in gutters Cast iron body with sher. cast iron grating for use in gutters Cast iron body with stainless steel grating for use in pools and pits Cast iron body with sher. cast iron grating and trenches and trenches Spec. Outlet Spec. Outlet Spec. Outlet Spec. Outlet Q mm with backwater Q mm BS 437 Q601 4" BSP Q702 4" BSP Q mm } valve BS 437 Q1102 6" BSP Female DRAINAGE OF PLANTING AREAS AND ROOF GARDENS POOL OVERFLOW 90 GULLY L Ductile iron grating with perforated stainless steel ballast guard Spec. Use with Bodies P801 D10 - D12 + length ( Page 11 ) 104 Dia.x L(Std.pipe) 200 min. Copper dome with PVC standpipe Spec. Use with Bodies P901 Vari- level + length (Pages 10-13) 120 Dia. x L( Standpipe ) Dia. x H: 40 Stainless steel standpipe for Stainless steel use with Vari-Level bodies Spec. Membrane Use with Bodies P1001 Sheet or brush on C2-C5 P1002 Asphalt D10-D12 ( Pages 10,11 ) Spec. K3201 Without cap K3202 With cap K3211 For tiles etc. K3212 For vinyl etc. L: 220 x W: 158 x H: 185 max. Cast iron body with nickel bronze grating Spec. Outlet P BSP P BSP P BSP 31

32 GULLY ASSEMBLIES FOR SHEET FLOOR COVERING For use in wet bathrooms, kitchen and shower areas decked with sheet floor covering, such as vinyl of a thickness up to 3.5mm. ABS Plastic body with stainless steel or nickel bronze clamp collar and grating/ cover/funnel. P TRAPPED GULLY - 50mm seal. GV5 Series - 50mm socket outlet. Grating 220 Dia. 160 Dia. Clamping collar 1 - Peripheral Slot 2 - Slotted Grating (Invert) 50 Dia. Removable dip tube Removable sediment bucket Dimensions shown are for GV Solid Cover 4 - Funnel Spec. Illus. Top Version Load kg No. Material Rating Class GV Stainless Steel Grating (periph. slot) K3 1.1 GV Nickel Bronze Grating (slotted) L GV Stainless Steel Grating (slotted) L GV Nickel Bronze Solid Cover (gasketed) L GV Stainless Steel Solid Cover (unsealed) L GV Nickel Bronze Funnel (tapered) 101 Dia.x 100H n/a 2.4 GV Stainless Steel Funnel (parallel) 101 Dia.x 100H n/a 1.7 GV Nickel Bronze Funnel (oval) 224L x 85W x 99H n/a 3.7 OPTIONS Suffix H Fitted with allen screws for security applications (not GV5007) I Tapped to provide a direct connection for waste pipes - specify size 1 1 /4", 1 1 /2" or 2" (solid cover versions only) PB Made of polished bronze ( available for nickel bronze versions only) P Polished (GV5817 is polished as standard) FEATURES Watertight - clamping collar provides a water-tight seal between the flooring material and gully even when the grating is removed. Flow rate - (grating and funnel versions) rate in excess of 40 l/min; comfortably exceeds the minimum rate of 24 l/min required by BS EN 274 for the discharge from a single shower head. Installation - ideally suited for installation in timber or concrete floors where space is limited. Note: The gully must be supported and installed in accordance with instructions which accompany the product. 32

33 GULLY ASSEMBLIES FOR SHEET FLOOR COVERING For use in wet bathrooms, kitchen and shower areas decked with sheet floor covering, such as vinyl of a thickness up to 3.5mm. ABS Plastic body with stainless steel or nickel bronze clamp collar and grating/ cover/funnel. TRAPPED GULLY WITH VERTICAL OUTLET - 50mm seal. GV6 Series - 110mm spigot outlet with 50mm reducer. 220 Dia. 160 Dia. Grating Clamping collar 1 - Peripheral Slot 2 - Slotted Grating Removable dip tube Removable sediment bucket 50 dia. 3 - Solid Cover 4 - Funnel 110 dia. Dimensions shown are for GV6007 Spec. Illus. Top Version Load kg No. Material Rating Class GV Stainless Steel Grating (periph. slot) K3 1.1 GV Nickel Bronze Grating (slotted) L GV Stainless Steel Grating (slotted) L GV Nickel Bronze Solid Cover (gasketed) L GV Stainless Steel Solid Cover (unsealed) L GV Nickel Bronze Funnel (tapered) 101 Dia.x 100H n/a 2.4 GV Stainless Steel Funnel (parallel) 101 Dia.x 100H n/a 1.7 GV Nickel Bronze Funnel (oval) 224L x 85W x 99H n/a 3.7 OPTIONS Suffix H Fitted with allen screws for security applications (not GV6007) I Tapped to provide a direct connection for waste pipes - specify size 1 1 /4", 1 1 /2" or 2" (solid cover versions only) PB Made of polished bronze ( available for nickel bronze versions only) P Polished (GV6817 is polished as standard) FEATURES Watertight - clamping collar provides a water-tight seal between the flooring material and gully even when the grating is removed. Flow rate - (grating and funnel versions) rate in excess of 40 l/min; comfortably exceeds the minimum rate of 24 l/min required by BS EN 274 for the discharge from a single shower head. Installation - ideally suited for installation in timber or concrete floors where space is limited. Note: The gully must be supported and installed in accordance with instructions which accompany the product. 33

34 ROOF OUTLETS Installation Guidelines The design of the layout of roof outlets should be in accordance with the recommendations given in BS EN 12056:3 Wade offers a range of roof outlets with versions for use with different types of roof construction (warm, cold, inverted, no fines screed) for installation in different types of deck (concrete, metal, wood) with different types of waterproofing membrane (mastic asphalt, built-up felt roofing, single ply), as shown on following pages. Cast iron bodies are available with medium sump (3400 series) or deep sump (3100 series) with choice of outlet size and connection type, with polycarbonate dome or sherardized cast or ductile iron flat grating. Bodies with spigot outlet are for direct connection to pipework; versions with threaded outlet are for connection to pipework by means of a spigot adaptor. Roof outlets should be placed at the roof low points to allow efficient flow of water to the outlets. Note : For versions with bonded insulation jacket add suffix K to the Spec.. For versions with integral PVC flange for use with PVC single ply membranes add suffix Z to the Spec.. 1. Check Dimensions Prior to installation, check height of components to ensure compatibility with roof build-up, making allowances for the membrane thickness. 2. Fit Spigot, Check Outlet Where applicable, screw spigot into body, using a suitable sealant to ensure the joint is watertight. Position body in roof deck and ensure outlet is accessible for pipework connection. 3. Install Body Install body such that flange is flush or sub-flush with roof deck. Ensure body is fixed securely, either bonded or clamped to the deck if not cast-in. Use a suitable sealant on any threaded joints e.g. extension flange, to ensure a water-tight assembly. Note: Membrane flange level is determined by roof build up. 4. Dress Membrane and Clamp Refer to membrane manufacturer s instructions. Prepare flange of body with suitable primer and apply membrane, dressing over flange and into sump of body. Position membrane clamping collar and secure to body using fixings supplied. 5. Install Insulation Install any intermediate roof build-up (e.g. insulation) around outlets. 6. Fit Grating, Apply Finish Fit dome/grating using height adjustment where applicable to ensure grating is flush with roof finish. Apply roof finish around grating. 34

35 ROOF OUTLETS Typical Installations WARM ROOF ( See page 36 and 39 ) MEMBRANE CLAMPING COLLAR MEMBRANE EXTENSION FLANGE BEARING PAN (OPTIONAL) MEMBRANE CLAMPING COLLAR ADJUSTABLE BEARING PAN MEMBRANE INSULATION INSULATION ROOF DECK ROOF DECK BONDED INSULATION JACKET WITH OR WITHOUT TRACE HEATING (OPTIONAL) UNDERDECK CLAMP (OPTIONAL) OPTIONAL BONDED INSULATION JACKET WITH OR WITHOUT TRACE HEATING RAISING TUBE BODY COLD ROOF ( See page 37 and 39 ) MEMBRANE SECURED DOME MEMBRANE CLAMPING COLLAR SECURED FLAT GRATING MEMBRANE CLAMPING COLLAR MEMBRANE ROOF DECK BODY ROOF DECK BODY SPIGOT ADAPTOR (SELECT SEPARATELY) UNDERDECK CLAMP ( OPTIONAL ) INVERTED ROOF ( See page 37 and 39 ) FLAT GRATING SLOTTED COLLAR / MEMBRANE CLAMPING MEMBRANE COLLAR ROOF FINISH INSULATION BODY ROOF DECK SPIGOT ADAPTOR (SELECT SEPARATELY) MEMBRANE BODY MEMBRANE CLAMPING COLLAR GRAVEL GUARD ROOF FINISH INSULATION SCREED ROOF DECK UNDERDECK CLAMP (OPTIONAL) PARAPET OUTLET ( See page 38 ) DOWNSPOUT NOZZLE ( See page 38 ) BALCONY OUTLET ( See page 38 ) MEMBRANE GRATING BODY DOWNSPOUT NOZZLE GRATING MEMBRANE CLAMPING COLLAR RAINWATER DOWNNPIPE GRATING MEMBRANE SCREED MEMBRANE C0NNECTING SPIGOT BODY BODY 35

36 ROOF OUTLETS For Warm Roof ( Comprising cast iron body with sherardized ductile iron grating, or polycarbonate dome ) 3400 Series (Medium Sump) For use with insulation thicknesses between 80mm and 100mm For use with insulation thicknesses between 20 and 135mm 190 dia. dome 220 dia. grating 190 dia. dome 220 dia. grating SPIGOT OUTLET THREADED OUTLET SPIGOT OUTLET THREADED OUTLET SPIGOT OUTLET THREADED OUTLET SPIGOT OUTLET THREADED OUTLET Spec Outlet Size WC WC WC Spec WC222 WC223 WC224 Outlet Size 2" BSP 3" BSP 4" BSP Spec Outlet Size WC WC WC Spec Outlet Size WC322 2" BSP WC323 3" BSP WC324 4" BSP Spec Outlet Size WC WC WC Spec WC422 WC423 WC424 Outlet Size 2" BSP 3" BSP 4" BSP Spec Outlet Size WC WC WC Spec Outlet Size WC522 2" BSP WC523 3" BSP WC524 4" BSP HORIZ. THREADED OUTLET Spec Outlet Size WC232 2" BSP WC233 3" BSP WC234 4" BSP HORIZ. THREADED OUTLET Spec Outlet Size WC332 2" BSP WC333 3" BSP WC334 4" BSP For larger thicknesses of insulation, please contact our Technical Services Dept Series (Deep Sump) Threaded Outlet For use with insulation thicknesses between 80mm - 115mm 190 dia. dome 320 sq. grating 310 dia. grating Spec WC644 WC646 Outlet Size 4" BSP 6" BSP Spec WC744 WC746 Outlet Size 4" BSP 6" BSP Spec WC1044 WC1046 Outlet Size 4" BSP 6" BSP For use with insulation thicknesses between 20 and 135mm 190 dia. dome 320 sq. grating 310 dia. grating Spec WC814 WC816 Outlet Size 4" BSP 6" BSP Spec WC914 WC916 Outlet Size 4" BSP 6" BSP Spec WC1114 WC1116 Outlet Size 4" BSP 6" BSP 36

37 ROOF OUTLETS For Cold Roof, Inverted Roof and No Fines Screed ( Comprising cast iron body with sherardized ductile iron grating, stainless steel grating, or polycarbonate dome ) COLD ROOF 3400 Series (Medium Sump) 190 dia. dome THREADED OUTLET Spec Outlet Size WB222 2 BSP WB223 3 BSP WB224 4 BSP SPIGOT OUTLET Spec Outlet Size WB WB WB HORIZ. THREADED OUTLET Spec Outlet Size WB232 2 BSP WB233 3 BSP WB234 4 BSP 220 dia. grating THREADED OUTLET SPIGOT OUTLET Spec Outlet Spec Outlet Size Size WB322 2 BSP WB WB323 3 BSP WB WB324 4 BSP WB HORIZ. THREADED OUTLET Spec Outlet Size WB332 2 BSP WB333 3 BSP WB334 4 BSP 3100 Series (Deep Sump) 190 dia. dome 320 sq. grating 310 dia. grating THREADED OUTLET THREADED OUTLET THREADED OUTLET Spec Outlet Size WB414 4 BSP WB416 6 BSP Spec Outlet Size WB514 4 BSP WB516 6 BSP Spec Outlet Size WB614 4" BSP WB616 6" BSP INVERTED ROOF AND NO FINES SCREED 3410 Series - (Medium Sump) 220 dia. grating THREADED OUTLET Spec Outlet Size WD222 2 BSP WD223 3 BSP WD224 4 BSP SPIGOT OUTLET Spec Outlet Size WD WD WD HORIZ.THREADED OUTLET Spec Outlet Size WD232 2 BSP WD233 3 BSP WD234 4 BSP 224 sq. grating THREADED SPIGOT OUTLET OUTLET Spec Outlet Spec Outlet Size Size WD322 2 BSP WD WD323 3 BSP WD WD324 4 BSP WD HORIZ. THREADED OUTLET Spec Outlet Size WD332 2 BSP WD333 3 BSP WD334 4 BSP 3410 Series - (Medium Sump) 3400 Series (Medium Sump) 200 sq. stainless steel grating 190 dia. dome THREADED OUTLET SPIGOT OUTLET HORIZ. THREADED OUTLET THREADED OUTLET SPIGOT OUTLET HORIZ. THREADED OUTLET Spec Outlet Spec Outlet Size Size WD722 2 BSP WD WD723 3 BSP WD WD724 4 BSP WD Spec Outlet Size WD732 2 BSP WD733 3 BSP WD734 4 BSP Spec Outlet Spec Outlet Size Size WD122 2 BSP WD WD123 3 BSP WD WD124 4 BSP WD Spec Outlet Size WD132 2 BSP WD133 3 BSP WD134 4 BSP 3100 Series - (Deep Sump) 220 dia. grating 224 sq. grating 200 sq.stainless steel grating THREADED OUTLET Spec Outlet Size WD514 4" BSP WD516 6" BSP THREADED OUTLET Spec Outlet Size WD614 4" BSP WD616 6" BSP THREADED OUTLET Spec Outlet Size WD744 4" BSP WD746 6" BSP 37

38 ROOF OUTLETS Parapet and Balcony Outlets, Downspout Nozzles PARAPET OUTLETS - Reversible cast iron body WF102 - WF125 WF152 - WF155 WF162 - WF165 WF156 WF166 WF176 Spec Outlet Grating Size WF102 2" BSP Nickel Bronze WF103 3" BSP Nickel Bronze WF104 4" BSP Nickel Bronze WF105 4" BSP Nickel Bronze WF112 2" BSP Aluminium WF113 3" BSP Aluminium WF114 4" BSP Aluminium WF115 4" BSP Aluminium WF122 2" BSP Cast Iron WF123 3" BSP Cast Iron WF124 4" BSP Cast Iron WF125 4" BSP Cast Iron WF152 2" BSP Aluminium WF153 3" BSP Aluminium WF154 4" BSP Aluminium WF155 4" BSP Aluminium WF156 6" BSP Aluminium WF162 2" BSP Aluminium WF163 3" BSP Aluminium WF164 4" BSP Aluminium WF165 4" BSP Aluminium WF166 6" BSP Aluminium WF176 6" BSP Aluminium With PVC body for use with single ply membrane, see centre pages for illustration. DOWNSPOUT NOZZLES - Cast Gunmetal BALCONY OUTLETS - Cast Iron Spec WJ102 WJ103 WJ104 Outlet Size 2 BSP 3 BSP 4 BSP Spec WJ202 WJ203 Outlet Size 2 BSP 3 BSP Spec WF604 Outlet Size 100mm BS416 Spec WF704 Outlet Size 100mm BS416 38

39 ROOF OUTLETS Accessories GRAVEL GUARD - Stainless Steel UNDERDECK CLAMP 3400 Series 3100 Series Spec Height Spec Height WG WG WH WH Series 3100 Series Spec Material Spec Material WG102 Mild Steel WH202 Mild Steel WG102SS S/Steel WH202SS S/Steel BEARING PAN - Galv. Mild Steel FILTER BUCKET - Stainless Steel 3400 Series 3100 Series 3400 Series 3100 Series Spec WG201 Spec WH301 Spec WG301 Spec. WH401 Compatible with WC6,WC10,WD4 WH402 WC7-9,WC11,WB4-6 EXTENSION PIECE Stainless steel (Inverted roof only) WD2 - WD7 Series Spec Height WG WG BONDED INSULATION JACKET A factory fitted bonded insulation jacket is used to prevent condensation forming on the underside of a body. To specify/order add suffix K to the roof outlet Spec.. Trace heating of insulated bodies is available to help prevent blockage by ice or snow; for details please contact our Technical Services Dept. SPIGOT ADAPTORS A comprehensive range of spigot adaptors, shown in the following table, is available to enable gully bodies with BSP threaded outlet to be connected speedily and effectively to all pipework in general use. To complete the connection a coupling may be required as indicated. Longer spigots, such as required to pass through a slab, can be made in 10mm increments up to 1000mm. To specify/order add suffix # and length (mm), eg. WT103#250. On request, spigots may also be threaded both ends. For details, please contact our Technical Services Dept. PIPEWORK BODY SPIGOT ADAPTOR REQUIRED OUTLET COUPLING System Nom.Dia. BSP Spec. O.D. Length Material Weight mm mm mm kg Cast Iron BS " WT Mild Steel, sherardized 1.0 Proprietary Cast Iron BS " WT Mild Steel, sherardized 1.7 Proprietary Cast Iron BS " WT Cast Iron 2.5 Proprietary Cast Iron BS " WT Cast Iron 4.0 Proprietary Cast Iron BS " WT Cast Iron 2.6 Proprietary Cast Iron BS " WT Cast Iron 4.1 Proprietary Cast Iron DIN (Ensign + SMU) 50 2" WT Mild Steel, sherardized 1.0 Proprietary Cast Iron DIN (SMU) 75 3" WT Mild Steel, sherardized 1.2 Proprietary Cast Iron DIN (Ensign) 75 3" WT Mild Steel, sherardized 1.7 Wade T1603 Cast Iron DIN (Ensign + SMU) 100 4" WT Cast Iron 2.5 Proprietary Cast Iron DIN (Ensign + SMU) 150 6" WT Cast Iron 4.0 Proprietary Plastic 50 2" T Plastic (ABS) 0.1 None Plastic 82 3" T Plastic (ABS) 0.2 Proprietary Plastic 110 4" T Plastic (ABS) 0.2 None Plastic 160 6" T Plastic (ABS) 0.6 Proprietary Solvent weld socket 39

40 LINEAR DRAINAGE Installation Guidelines 1. Remove any gratings and clamping frames from channel. 2. Taking care not to twist, turn the channel upside down (base uppermost). 3. If there is more than one section to the channel, apply silicone sealant to jointing flange faces or fit rubber gaskets if supplied, and securely bolt sections together. 4. If connecting to a Wade gully, follow the instructions supplied. 8. lf not supplied, provide and insert spacer bars across channel at approx. 500mm centres. Spacer bars prevent channel being squeezed while backfill is being compacted and must not be removed until backfill is set. 9. Fix the channel into position by first grouting buildin ties and any adjustment legs firmly in place. 10. Taking care not to damage show surfaces, place heavy weights on top of the channel prior to pouring backfill to prevent any lift or movement. 11. Backfill around the channel ensuring that backfill material flows evenly under and around the channel such that no voids are formed. 5. Taking care not to twist, turn the channel the correct way up and lower it into the trench and into any installed gullies: ensure top edge of channel is flush with finished floor level, use the adjustment legs when supplied. 6. Bend the build-in ties as necessary. 7. Make the pipework joints below the channel Note : After positioning the channel it is recommended that a water test be undertaken to check that height is correct, that, where applicable the fall in the channel works effectively, that there are no leakages from the channel system and that there are no signs of deformation or damage to the channel which may have occured during installation. At this stage it may still be possible for any necessary rectification work to take place. Please consult our Technical Services Dept. if this situation arises. 12. Remove immediately any material which falls into the channel. 13. When backfill is set, remove spacer bars. 14. Fit gratings. 15. Clean channels and gratings with water and a suitable cleaning agent where necessary. Under no circumstances use metal scouring pads or wire wool as these will contaminate surfaces. 40

41 LINEAR DRAINAGE Installation Guidelines contd. DRAINAGE CHANNEL PROFILE SVF- FOR USE WITH FLEXIBLE SHEET FLOOR COVERING The following additional notes / procedures apply: Typical Installation in a vinyl covered floor 1. Dress floor covering into channel and fix in accordance with flooring manufacturer's instructions. 2. Fit clamping frames and gratings. SUPASLOT CHANNELS The following additional notes / procedures apply. 1. The slot is covered with an adhesive tape to prevent debris falling into the channel during installation. Do not remove the tape until installation is complete. DRAINAGE CHANNELS WITH PERIMETER ANGLE FRAME The following additional notes / procedures apply: 1. The gap between the outside edge of the channel and the angle frame is covered with an adhesive tape to prevent debris filling up the gap during installation. Do not remove the tape until installation is complete. 2. When the channel is installed, lay the floor into the perimeter angle frame. 3. Once the floor is set, carefully remove the spacer bars between the angle frame and the channel using an angle grinder or similar. Note: Do not remove the spacer bars before fitting the channel, as it would then be impossible to maintain the position of the frame relative to the channel. 4. Thoroughly clean the gap between the channel and angle frame, degrease and fill with a permanently elastic expansion joint sealant. If corrosive chemicals are likely to be present, consult sealant manufacturer on suitability. Typical Installation Gullies with Linear Drainage Wade floor gullies, trapped or untrapped can be used with stainless steel drainage channel as illustrated. Details of a comprehensive range of stainless steel, cast iron and gunmetal floor gullies are included in pages 4 to 33. With D1004 LD Non-Trapped body. With G304 LD P trapped body. With optional tile upstand (SVFT profile shown) 41

42 LINEAR DRAINAGE Channel Gratings ( For use with channel shown opposite ) Stainless Steel STAINLESS STEEL - Austenitic grade 304 STREAMLINE Spec Illust. Length Width Depth Slot Free Area Load Rating No. Width cm2 /m Class SS A 15 SS A 15 SS A15 SS A 15 SS A 15 SMOOTH MESH Spec Illust. Length Width Depth Slot Free Area Load Rating No. Width cm2 /m Class SS x A 15 SS x A 15 ANTI-SLIP MESH Spec Illust. Length Width Depth Slot Free Area Load Rating No. Width cm2 /m Class SS Sq A 15 SS Sq B 125 SS Sq B 125 SS Sq B 125 SS Sq B 125 SS Sq A 15 SS Sq B 125 SS Sq A 15 PRESSED Spec Illust. Length Width Depth Slot Free Area Load Rating No. Width cm2 /m Class SS A 15 SS A 15 SS A15 STAINLESS STEEL BAR ( Illustration No.7 ) Manufactured to order Nickel Bronze NICKEL BRONZE - BS Satin Finish STANDARD SLOT Spec Illust. Length Width Depth Slot Free Area Load Rating No. Width cm2 /m Class SN A 15 SN A 15 SN B 125 SN A 15 SN A 15 SN B 125 FLORAL Spec Illust. Length Width Depth Slot Free Area Load Rating No. Width cm2 /m Class SN max. 475 A 15 DECORATIVE Spec Illust. Length Width Depth Slot Free Area Load Rating No. Width cm2 /m Class SN A 15 ALUMINIUM - LM 6 STANDARD SLOT Spec Illust. Length Width Depth Slot Free Area Load Rating No. Width cm2 /m Class SA A 15 SA A 15 SA A 15 42

43 LINEAR DRAINAGE Channel Gratings and Channel (Cont.) Cast Iron CAST IRON - SHERARDIZED CAST IRON BS EN 1561 Spec Illust. Length Width Depth Slot Free Area Load Rating No. Width cm2 /m Class SC B 125 SC sq 184 B 125 SC B 125 SC B 125 SC max 475 A 15 LACQUERED CAST IRON BS EN 1561 Spec Illust. Length Width Depth Slot Free Area Load Rating No. Width cm2 /m Class SI max. 475 A 15 SI C 250 SHERARDIZED DUCTILE IRON BS EN Spec Illust. Length Width Depth Slot Free Area Load Rating No. Width cm2 /m Class SG C 250 SG C 250 Stainless Steel Channel - Austenitic grade 304. For use with gratings shown above and opposite. All channel profiles are also available with optional tile upstand (see page 41). To specify add suffix T and provide details. Profile: RFP - Resin floor Not suitable for use with hard setting flooring compound. (Use profiles RE or NE) NE - Narrow edge Show edge may also be manufactured of materials to complement grating, e.g. nickel bronze, cast iron etc. RP - Regular RE - Return edge SE- Support edge D E A ( Visible length at FFL ) B F To Specify / Order Channel with Grating Quote: GRATING Spec CHANNEL PROFILE Spec GENERAL DIMENSIONS in mm (A to E) OUTLET CONNECTION details - (F above - size / type of pipework system) THICKNESS OF FLOOR FINISH Some typical Layouts C PA - Perimeter angle frame SVF-For use with sheet floor covering such as vinyl. Min. grating width required is 80 mm. Straight section L section RPV - Profile RP is available with a decorative factory fitted PVC angle edging strip to which sheet floor covering can be butt welded at the time of installation; such channel is particularly suited to heavy duty applications. T section U section 43

44 LINEAR DRAINAGE JUBILEE and BUDGET Modular systems JUBILEE MODULAR SYSTEM Channel of grade 304 austenitic stainless steel. Gratings of epoxy coated ductile iron. For use in unfinished floors such as in factories, plant rooms and service areas. FEATURES Load rating of C 250. Security locking deters unauthorised removal of gratings. Modular parts enable forming of short runs, junctions and corners. 250 M 2 drained per single outlet (based on B.R.E. rainfall figures of 75mm/hr). One outlet recommended for every 20 gratings. Gratings 303 mm sq. To Specify / Order: Each straight section must be in multiples of 303mm. After channel layout is decided select appropriate spec. codes with quantities of each item required. Spec. S4700 S4701 S4702 S4703 S4706 S4724 S4733 S4791 S4792 Description Section with single grating and 4 BSP outlet Section with single grating Section with 2 gratings Section with 3 gratings Section with 6 gratings T Section with 4 gratings L Section with 3 gratings Jointing piece Stop end BUDGET MODULAR SYSTEM Grade 304 austenitic stainless steel To Specify / Order: Select channel sections and indicate choice of grating. (suffix 5 or 7 ) Example: S = Section with 4 smooth mesh gratings S = L Section with 2 secured anti-slip mesh gratings General purpose product for use in doorways, walkways, kitchens etc. ( Not suitable for barefoot traffic.) FEATURES Channel and gratings of grade 304 austenitic stainless steel. Depth of only 55mm. Modular parts easily bolt together to form straight runs. Inclined side walls ensure secure bedding of channel. Choice of vertical or horizontal outlets. Choice of smooth or anti-slip mesh gratings. Gratings, 123 mm wide, may be secured. Spec Descrption Length S6000 Section with single grating 500 and 100mm vertical outlet S6001 Section with single grating 500 S6002 Section with 2 gratings 1000 S6003 Section with 3 gratings 1500 S6004 Section with 4 gratings 2000 S6005 Section with 5 gratings 2500 S6006 Section with 6 gratings 3000 S6007 L Section with 2 gratings S6008 T Section with 3 gratings S6097 Height adjustable feet (optional) (4 needed per section) S6098 Stop end S6099 Horizontal outlet S61-- Secured grating (SS50322) Smooth mesh grating - add suffix 5 (SS70222) Anti-slip grating - add suffix 7 44

45 LINEAR DRAINAGE Channel - SUPASLOT, Hidden Lift and Dual Level Drainage Stainless Steel austenitic grade 304 SUPASLOT CHANNEL Suitable for large areas with low volumes of waste water such as in abattoirs, butcheries, dairies, breweries etc. SL SSL HL FEATURES Depth from 65mm to 180mm with or without fall. Slot width 18mm (5mm on SSL) Suitable for tiled and resin floors. Easily cleaned by directing jet of water along the channel towards the outlet. Can be combined with Wade gullies and channel gratings. To Specify/ Order, quote : Spec SL, SSL or HL, length of channel, position and diameter of outlet HIDDEN CHANNEL Hidden channels are suited for draining large areas finished with block paving and can be designed to accommodate a range of paving thicknesses and flow rate requirements. FEATURES Paving depth from 15mm to 60mm Channel depth below flange from 30mm to 150mm with or without fall Slot width 5mm to 18mm Easily cleaned by directing jet of water along the channel towards the outlet. Can be combined with Wade gullies, recessed access covers and channel gratings. Load rating class of B125 Dual-Level drainage available - if required add suffix DSD or SSD to Spec. Spec. : HC Spec. : HCE Designed for use against a wall. To Specify/ Order, quote : Spec HC or HCE, length of channel, paving depth, channel depth, slot width, position and diameter of outlets DUAL LEVEL DRAINAGE CHANNEL Provides primary drainage at finished floor level plus secondary drainage at membrane level. Suitable for installation in pedestrian and light vehicular areas only. Secondary drainage is available with the Channel profiles shown on page 7. To order / specify, quote: GRATING Spec. CHANNEL PROFILE Spec. SECONDARY DRAINAGE : Single - Spec. SSD Double - Spec. DSD GENERAL DIMENSIONS in mm. OUTLET CONNECTION details MEMBRANE DEPTH from finished floor level 45

46 LINEAR DRAINAGE Channel - Firefighting Lift, Angle Frame and Tree Grille Stainless Steel austenitic grade 304. CHANNEL AND GRATING FOR FIREFIGHTING LIFT To prevent water, such as from a sprinkler, entering a lift well. FEATURES Will deal with flow of 25 l/s in accordance with BS Streamline,135 mm wide gratings are secured in the channel leaving a peripheral slot 8 mm wide. Channel has two 150 mm outlets in corner locations. To Specify/ Order, quote : Spec S4800 and lengths of channel ANGLE FRAME For use over pre-formed channels, with gratings shown on pages 42 to 43. FEATURES Angle frame can be custom made to suit various applications; sections can be produced to match any of the channel profiles shown on page 43. Please contact our Technical Services Dept. for details. TREE GRILLE 321 For use in shopping precincts or similar areas subject to pedestrian traffic FEATURES Gratings of nickel bronze set in frames of stainless steel austenitic grade gratings set in 2 sections allow fitting around an existing tree. Suitable for tree trunks up to 300mm dia. Matches decorative channel grating SN Spec S

47 NON-FREEZE WATER POINTS Wall thickness 130mm min. available in 10mm increments /4" BSP 1 1 /4" BSP Backnut 150 x 90 3/4" BSP Connection Hinged Cover Provides an external water source for plant watering, area cleaning, vehicle wash down and similar activities. The product is designed to be installed with the valve seal located inside a building, whilst the on/off control mechanism and hose connections are outside; when the valve is turned off, water drains out from the unit so that freezing cannot occur. Spec Wall Box Material Finish YA101 + Wall thickness mm Without Wall Box YA201 Aluminium White epoxy coated YA202 Nickel Bronze Satin YA203 Gunmetal Satin Option: Locking cover (only on versions with wall box) - Suffix L The Wade non-freeze water point is a U.K. Water Byelaws Scheme Approved Product - Certificate No WATER HAMMER ARRESTORS 'A' Maintenance free, mechanical, water hammer arrestors are designed to eliminate water hammer (shockwaves) caused by fast closing valves, such as quick action taps and solenoid valves within pipework systems (e.g. dishwashers and washing machines). For sizing information, please contact our Technical Services Dept. Spec A B BSP WSC /2" WSC /4" WSC " WSC /4" WSC /2" WSC " 'B' SEDIMENT INTERCEPTORS Sediment Interceptors are used to help prevent blockages where solids such as food scraps, hair, plaster, sediment etc. are discharged into drain lines. Material: Stainless Steel Bucket lifting handle 105 Fastener 2" BSP Inlet sq. Sealed removable cover 125 2" BSP Outlet Sediment bucket or filter bag Spec Flow rate Solids l / sec. collector Bucket - stainless steel Bag - polyester Note:Minimum clearance above cover of 450mm is required for removal of bucket / bag OIL INTERCEPTORS Oil Interceptors are installed in drain lines to help prevent the pollution of rivers, streams, drainage systems and water treatment plants. Units are used where spillages of oil or diesel could occur such as garages, transport workshops, diesel re-fuelling and storage areas, and where vehicles or plant are washed down or steam cleaned. Oil Interceptors are not suitable for petrol and volatile liquids. To Specify /Order Select the appropriate code from the table and add the required C dimension, e.g. for oil interceptor to accept a flow 3.5 l/sec. and having a C dimension of 250mm. - Specify 5360, C dimension = 250mm. Spec Flow rate Inlet / Outlet Length Width l / sec. Size B.S.P. mm mm C D " To be " specified 432 on order* " C dimension is from top of cover to centre of inlet. D dimension is from bottom of interceptor to centre of inlet. Note:*Minimum C dimension available is 150mm, larger dimensions should be specified in increments of 10mm. Larger sizes of oil interceptors are available, please contact our Technical Services Dept. for details. 47

48 GREASE CONVERTERS A Wade Actimatic Grease Converter provides a NATURAL, safe and environmentally friendly means of PERMANENTLY converting grease to bio-degradable products. In powder or liquid form, Wade Actimatic is a bacterial product (not enzyme), which maintains a micro-biological culture within the grease converter to deal with kitchen effluent. Types of Installation FLOOR STANDING (Standard and low profile models) FULLY RECESSED IN GROUND FLOOR (Standard invert models) FULLY RECESSED IN GROUND FLOOR (Deep invert models) INSTALLATION GUIDELINES FULLY RECESSED IN INTERMEDIATE FLOOR (Hanger Type) Wade Actimatic Grease Converters are designed to be installed in existing or new kitchens, at restaurants, canteens, hotels, hospitals, etc., and also at commercial or industrial premises where food is cooked, prepared or processed. They are not suitable for use with dedicated chicken rotisserie ovens unless special housekeeping measures are taken, including the introduction of water. There is no optimum distance between the last fixture and the converter; it is generally accepted that pipework longer than 8 metres may allow grease to solidify before it reaches the converter. Waste disposal units may discharge into a Grease Converter, but this practice is not advisable because frequent cleaning out will be necessary. Waste from vegetable peelers must be filtered before discharging. Certain cleaning agents (Chlorine, strong caustics, bleach etc.) in concentrated form, have a detrimental effect, and should not be discharged into a Grease Converter. Installations may require prior approval from the Local Authority Environmental Health Dept. Wade Actimatic Grease Converters satisfy current Building Regulations / Standards in the U.K., and meet requirements of drainage systems designed in accordance with BS EN : 2000 Spigot adaptors for connecting to different types and sizes of pipework are shown on page 24. Note: Do not reduce the stated inlet or outlet size otherwise blockages could occur. INDEPENDENT PRODUCT ASSESSMENT : In 1989 Wade became the first manufacturer of grease converters to be awarded an Agrément Certificate. Since 1990 The Royal Institute of Public Health has annually awarded its Certificate of Hygienic Merit to Wade for the Actimatic Grease Converter. 48

49 GREASE CONVERTERS HOW TO SELECT AND SIZE GREASE CONVERTERS To determine the optimum size of converter to be used, account must be taken of the volume of fixtures discharging into the converter. Use the table below to calculate total volume by entering the quantity of each fixture, multiply by the volume shown and enter as Total Vol.; finally, add up your answers. Type of Fixture Approx. Size Approx. Vol. Qty. Total Vol. (mm) (litres) (litres) Handwash Sink 300 dia. x 180 deep 12 Domestic Single Sink 450 x 350 x Domestic Double Sink (450 x 350 x 200) x 2 64 Commercial Sink 600 x 450 x Double Commercial Sink (600 x 450 x 300) x Commercial Potwash Sink 760 x 500 x Tilting Kettle 150 Small Dishwasher Outlet pipe 32 dia. 185 Medium Dishwasher Outlet pipe 40 dia. 235 Large Diswasher Outlet pipe 50 dia. 350 Other fixtures TOTAL VOLUME OF FIXTURES (LITRES) 2" BSP Vent Pipe Connection (Vent to atmosphere if required) A B G A B F C 150 Min. C 200 min. 140 E D E D Series 5200 Series After selecting the appropriate type of installation, and calculating the total volume of fixtures, select the Spec. from the table below and add the required C dimension. e.g. for Converter to serve fixtures with a total volume of 325 litres and having a C dimension of 400mm, Specify : 5060XT C = 400mm Type of Max.total vol. of Spec. In/Oulet A B C D E F G Required Installation Fixtures in Ltrs. BSP Inches mm mm mm mm mm mm mm slab opening open LR FLOOR STANDING LR Low profile LR LR FLOOR STANDING Standard invert FULLY RECESSED XT GROUND FLOOR XT Deep invert XT FULLY RECESSED GROUND FLOOR Deep Invert Large capacity FULLY RECESSED H x 445 INTERMEDIATE FLOOR H x 545 Hanger Type H x 730 } } } } } To be specified on order For the hanger types listed, the dimension from finished floor level to the underside of the hanger frame (normally slab level) is adjustable on site from 35mm min to 75mm max. N.B. In practice fixtures do not all discharge at the full rate simultaneously. This has been allowed for and the table enables the correct grease converter to be selected. In abnormally high or dump situations contact our Technical Services Dept. AUTOMATIC DOSING SYSTEM A mains powered dispenser unit is available for use with Actimatic Liquid. The unit automatically doses the Converter with diluted Actimatic Liquid once daily at a time selected by the user. The system, once set, requires only monthly attention to replenish the liquid supply, and is suitable for use in most new and existing drainage systems. A warning light and audible alarm indicates low level of liquid. To Specify / Order: Spec. : ADU Automatic Dosing Unit Spec. : AL1 Actimatic Liquid ( 1 ltr.) Options: Wall mounting bracket for storage drum - made of grade 304 stainless steel with large radiussed corners to facilitate cleaning - add suffix MB to Spec.. 49

50 MATERIALS Materials and finish of Wade products, described below, are selected to provide lasting performance and to blend with surroundings. The products require the minimum of maintenance, but periodic inspection should be carried out to ensure absence of matter which could impede drainage. Measures set out below will sustain appearance and prolong service life. STAINLESS STEEL - AUSTENITIC GRADE 304 Used for bodies, channels, gratings, funnels, covers, gravel guards, filter buckets and fixings. A corrosion-resistant metal containing significant amounts of nickel snd chromium. Clean with soap and warm water rinse and wipe dry. Gratings may also be cleaned in certain dishwashers. Under no circumstances treat with metal scouring pads, metal scrapers or wire wool as these will contaminate surfaces leaving rust spots. NICKEL BRONZE - BS 1400 Satin finish Used for gratings, covers and funnels. A cast alloy with a fine grain effect which blends well with most floor finishes. The satin finish is generally maintained by the slight abrasive action of passing traffic. In unused areas the material will gradually tarnish. To restore lustre, apply a plain nylon scouring pad (not soapfilled) in the direction of the grain. POLISHED BRONZE - BS 1400 Used for gratings, covers and funnels. A cast alloy suited for finished floors where the rich, bronze colour complements the decor. The "mirror" finish is produced by polishing. If left alone polished bronze will gradually tarnish. To restore lustre, use metal polish and buff with a cloth. The mirror finish must not be treated with any abrasive cleaning material otherwise the surface will be permanently scratched. DUCTILE IRON - BS EN Used only for gratings. A casting with the ductility of steel, yet with more than twice the tensile strength of cast iron. A zinc anti-corrosion coating is applied by galvanising or sherardizing. CAST ALUMINIUM - LM6 Used for parapet and channel gratings. An alloy chosen for its chemical resistance and durability. CAST IRON - BS EN 1561 Used for bodies, membrane clamping collars, spigot adaptors and accessories such as extensions. A widely used metal in the drainage industry, its resistance to corrosion permits extended use under extreme conditions. Castings are coated with a high grade lacquer paint applied by full immersion dip to provide internal and external surface coverage. Paint will gradually wear off and is replaceable; oxidisation (surface rusting) is a natural process which does not weaken the material. A zinc anti-corrosion coating is applied to certain castings by galvanising or sherardizing. MILD STEEL Used for adjustable bearing pans and raising tubes. A cost effective material to which a zinc anti-corrosion material is applied by galvanising or sherardizing. POLYCARBONATE Used for roof outlet domes A polycarbonate / ABS blend which offers durability, high impact strength and long term resistance to ultraviolet light. POLYPROPYLENE Used for the removable trap in stainless steel gullies. PVC Used for roof outlet body versions for use with PVC single ply membranes. This material enables a waterproof joint to be produced on site. ABS Used for bodies, dip tubes, extensions and spigot adaptors A cost effective, fire-resistant material. NYLON 6 Used for bottle trap and filter bucket Chosen for its toughness and durability. 50

51 INDEX Spec Page Spec Page ADU 49 B1 - B5 10 C2 - C5 10 D2 - D7 10 D8 11 D10 - D12 11 DSD 45 E2, E4 30 F2, F3 30 G1 - G10 12 GC1 13 GD1 13 GP 13 GV H1 - H3 12 HC, HE 45 HL 45 J2 13 K Jacket 39 K18 15, 21 K19 - K20 19 K21 - K22 14, 15, 19, 21 K23 14, 15, 21 K24 14, 15, 19, 21 K25 14, 19, 29 K26,K27 14, 19 K28,K29 15, 21 K30,K31 14, 19 K32 31 K33 14, 19 K34 14, 15, 19, 21 K51 - K58 16, 22, 23 L19, L20 20 L21 14, 15, L22 14, 15, L23 15, 20 L24 15, 20 L25 14, 15, 19, 20 L2614, 19 L27 15, 21 L28 14, 19 L29 15, 21 L30 15, 20 L31 15, 21 L51, 52 16, 22 L53, L54 15, 16, 20, 22 L55 16, 22, 23 L56, L57 16, 22 L58 16, 23 M1 - M4 30 N1 21 N2 - N4 21, 23 NE 43 PA 43 P3 - P5 31 P8 - P10 31 P14 31 Q1- Q8 31 Q10 7 Q11 31 Q12, Q13 6 Q14 7 Q21, Q23, Q27 6 Q22, Q24, Q28 7 Q41- Q93 7 R1, R3 - R6, R8 23 RE 43 RP 43 SA 42 SC 43 SI 43 SG 43 SL 45 SN 42 SS 42 SSD 45 SVF 43 S644 S47 44 S48 46 T1 - T624 T7 - T9 18 T11 - T12 24 T13 - T14 17 T15 - T17 24 TP7 18 U1 - U2 17 U3 - U4 30 U5 - U617 U9 18 U11 17 U13 18 U14 17 U15 - U1618 UP7 17 WB2 37 WB3 37, 29 WB4 37 WB5 37, 29 WB637 WC 36 WD 37 WF 38 WG - WH 39 WJ 38 WSC 47 WT 39 YA , 37, , 37, , ,

52 CI/SfB April 2003 CI/SfB June 2003 CI/SfB (52) May 2003 Information Technology from Wade Wade literature is available on CD ROM, accessible on an IBM compatible PC with a CD ROM drive and Windows 95 or above. The CD also includes WADE-CAD - a selection of drawings in both Autocad and DXF format, accessible on PC or Apple Mac. Our website also contains product information, price list and CAD files. Uniclass EPIC Uniclass EPIC Uniclass EPIC Roof Outlets Drainage Products for use with sheet floor covering Linear Drainage Service Product Information and technical advice are available from the Wade Technical Services Department at Halstead, Essex, from Wade Drainage Technical Consultants located throughout the U.K. and from selected distributors throughout the world. A computer-aided design service is available free of charge for layouts and assemblies of Wade products. Warranty The Company warrants its products to be free from defects in material and workmanship for a period of 12 months from the date of delivery. The Company s obligation under this warranty is limited, at its option, to the repair or replacement, free of charge, or refund of the net invoiced price of any part found to be defective, and which, in the Company s opinion, has not been subject to undue wear and tear, accident, alteration, abuse or misuse. Consequential damages are expressly disclaimed. Technical advice from Wade International Ltd., whether verbal, in writing or by way of trials, is given in good faith but without warranty. The application, use and installation of the Company s products are beyond the control of the Company, and the purchaser is solely responsible for ensuring that goods are fit for any particular purpose. In line with the Company s policy of continual research and development, product specifications and availability are subject to change or withdrawal without prior notice. Dimensions In line with general practice all dimensions shown are nominal. QUALITY BY TRADITION PERFORMANCE BY DESIGN WADE INTERNATIONAL LTD Third Avenue. Halstead Essex. CO9 2SX. U.K. Telephone: +44 (0) Facsimilie: +44 (0) tech@wadedrainage.co.uk. website: