1 Product Data Sheet 3M Fire Barrier Product Description The 3M Fire Barrier is a one-piece hinged metal enclosure designed to prevent the passage of fire and smoke. The metal device has a fixed firestopping intumescent material which works in conjunction with foam smoke seals and an optional It has been contractor-designed to allow for use in either retrofit or new construction applications where an install and be done technology is needed. It is designed to provide years of dependable through-penetration firestopping with no reapplication of additional product to maintain its rating. 3M Fire Barrier s offer excellent performance achieving Fire Resistance Ratings of up to 4 hours. Product Features One-piece, hinged metal enclosure makes installations fast and easy Blank to multiple penetrants tested Red colour easy to identify as a fire rated device during inspect penetrations Warning labels part of device Convenient pictorial installation instructions 3M Logos on both sides of the penetration for easy identification Stackable for multiple penetrations Testing in accordance with AS1530.4, EN1366, and ASTM E814 (UL Listed). Fire Barrier Page 1

2 Physical Properties 3M Fire Barrier s 101.6mm (4") 63.5mm (2.5") s 63.5mm (2.5") 101.6mm (4") Nominal Dimensions Height 63.5mm (2.5") 101.6mm (4") Width 63.5mm (2.5") 101.6mm (4") Length 254mm (10") 254mm (10") Colour Red with Black label Red with Black label s 50.8mm (2") 101.6mm (4") Nominal Dimensions Diameter 50.8mm (2") 101.6mm (4") Length 254mm (10") 254mm (10") Colour Red with Black label Red with Black label 101.6mm (4") 50.8mm (2") 3M Fire Barrier Pass-Through Mounting Brackets Single Mounting Bracket Triple Mounting Bracket Availability 3M Fire Barrier s are available from Authorized 3M Fire Protection Products Distributors. 3M Order Code Packing Unit/Case mm (2") mm (4") mm (2.5") mm (4") Mounting Bracket 50.8mm (2") 1 Pair Stud Bracket 50.8mm (2") 1 Pair Single Mounting Bracket 101.6mm (4") 24 Pair Stud Bracket 101.6mm (4") 1 Pair Stud Bracket 63.5mm (2.5") Stud Bracket 101.6mm (4") Single Mounting Bracket 63.5mm (2.5") 24 Pair Single Mounting Bracket 101.6mm (4") 24 Pair Triple Mounting Bracket 63.5mm (2.5") 24 Pair Triple Mounting Bracket 101.6mm (4") 24 Pair Sixplex Mounting Bracket 63.5mm (2.5") 1 Pair Sixplex Mounting Bracket 101.6mm (4") 1 Pair Sixplex Mounting Bracket Maintenance The 3M Fire Barrier requires no maintenance over a normal life cycle. Fire Barrier Page 2

3 New Installations New Installations with existing cables Installation Techniques: Walls and Floors New-Installations Prepare the opening by cutting the correct size hole, up to 5mm clearance on each side of the Pass-Through Device(s) is acceptable Remove the foam smoke seals and place in a safe location Slide the Device(s) either over existing cables or into the opening Run a bead of 3M Fire Barrier IC15WB+ sealant around the perimeter of the opening/devices and secure the 3M Fire Barrier Pass-Through Mounting Brackets in place on each side Install cables with up to 75% fill Re-install the foam smoke seals flush with the device ends. 1. Insert around penetration(s) optional. 2. Close cover and slide into wall assembly. mounting bracket then insert foam seal. Re-Installations Remove the foam smoke seals and place in a safe location 1. Insert around penetration(s) optional. 2. Close cover and slide into wall assembly. mounting bracket then insert foam seal. Install new cables up to 75% fill Re-install the foam smoke seals flush with the device ends. Fire Barrier Page 3

4 Performance Specifications for Installers Australian Standard FRLs Fire Resistance Level (FRL) 3M Fire Barrier System Building Element Unpenetrated PVC Insulated Cables, Cable trays and Cable bundles All Pass-Through and Bracket combinations All Pass-Through and Bracket combinations Floor: Concrete slab. Minimum 120mm thickness -/240/- -/120/- Wall: Plasterboard Dry Wall, solid masonry, hollow masonry or concrete construction. Minimum 116mm thickness -/120/30 -/120/- In order to achieve the above FRLs you must ensure that the Pass-Through device is installed as per the Installation Techniques and the building element you are installing into has an FRL performance equal to or better than that of the. The Installation Techniques can be found on the final page of this document. What does FRL mean? FRL stands for Fire Resistance Level. For example, an FRL of -/120/30 indicates: Structural Adequacy. The first dash - indicates that the is non load bearing Integrity. The middle number 120 indicates for how many minutes the can resist the passage of flames and hot gasses Insulation. The last number 30 indicates how many minutes it takes the unexposed face to heat up by more than 140 o C. Fire Barrier Page 4

5 Performance Specifications for Engineers and Specifiers 3M Fire Barrier s have been tested in accordance with AS and assessed in accordance with AS under BWA Report No: The following illustrations provide a summary of the test results for D1 and D2 cable configurations and unpenetrated blank openings with Pass-Through devices installed as per the installation techniques. Specifications for standard D1 and D2 cable configurations can be found in AS Appendix D. D1 Cable Pack Power Transmission Cables. Dry Wall 116mm FRL: -/120/- Solid Masonry, Hollow Masonry or Concrete Wall 116mm FRL: -/120/- Concrete Floor 120mm FRL: -/120/- D2 Cable Pack Telecom Cables. Dry Wall 116mm FRL: -/120/- Solid Masonry, Hollow Masonry or Concrete Wall 116mm FRL: -/120/- Concrete Floor 120mm FRL: -/120/- Unpenetrated Dry Wall 116mm FRL: -/120/30 Solid Masonry, Hollow Masonry or Concrete Wall 116mm FRL: -/240/30 Concrete Floor 120mm FRL: -/240/- Fire Barrier Page 5

6 For further information Call: TO THE EXTENT PERMITTED BY LAW 3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. User is responsible for determining whether the 3M product is fit for a particular purpose and suitable for user s application. If this 3M product is defective within the warranty period stated above, your exclusive remedy and 3M s sole obligation under this warranty shall be, at 3M s option, to replace or repair the 3M product or refund the purchase price of the 3M product. Limitation of Liability. Except where prohibited by law, 3M will not be liable for any loss or damage arising from this 3M product, whether direct, indirect, special, incidental or consequential, regardless of the legal theory asserted, including warranty, contract, negligence or strict liability. 3M Building and Commercial Services Division 950 Pacific Highway, Pymble NSW 2073 Call: Please recycle. Printed in Australia. 3M All rights reserved. 3MLK0014 Fire Barrier Page 6