ANNEXURE-III. Cdac Electrical PRICE BID. SL DESCRIPTION OF ITEM QTY UNIT Rate In Fig Rate In Words Amount PANELS

Size: px
Start display at page:

Download "ANNEXURE-III. Cdac Electrical PRICE BID. SL DESCRIPTION OF ITEM QTY UNIT Rate In Fig Rate In Words Amount PANELS"

Transcription

1 PANELS Supply and fixing 4th floor & 5th floor light and power distribution panel consisting of x 00 A TPN MCCB, 50 KA as incomer along with metering and nos 63 A 4 pole MCB as out going feeders along with ON indicating lamps etc complete with internal wiring and suitable size PVC insulated, copper conductor flexible cable with suitable size crimpled lugs, sleeves, ferules insulators and terminals etc. complete as required. No Supply and fixing First floor Data Centre UPS Distribution Panel, consisting of x 630 A 4 pole MCCB as incomer and 6 x 00 A four pole MCCB and 0 63 A 4 pole MCBs as out going feeders complete with internal wiring with suitable size of PVC insulated, Copper conductor flexible wire with suitable size of crimpled lugs, sleeves, ferules insulators and terminals etc. complete as reqd. DISTRIBUTION BOARDS Supply, Installation, Testing & Commissioning of following type Distribution board surface / flush mounted with Double Door MCB DBs. The DB shall have appropriate no. of top & bottom knock outs for outgoing circuits & shall be complete with necessary bus bars, interconnection terminals & earth studs. All terminations in DB shall be complete with ferruling, dressing & all circuits shall be properly labeled with PVC strip (sticker type) having identification as per the final approval of Consultant. 3 3 Way TPN DB Horizontal type a) 4

2 b) 4 Way Vertical MCB DB 6 c) 6 Way Vertical MCB DB 6 d) 8 Way Vertical MCB DB 8 e) Way Vertical MCB DB 5 f) 4 Way SPN DB 6 F MCBs Supply and fixing following type MCBs in existing MCB DBs including its incoming and out going connection with suitable size of PVC insulated, copper conductor flexible wire etc. as reqd. a) 63A 4 Pole MCB 60

3 b) 40A 4 Pole MCB 0 c) 3A 4 Pole MCB 70 d) 6-3A SP MCB 500 e) 3 A 4 Pole MCB with Suitable Sheet Steel Enclosure 0 G CABLES AND ACCESSORIES laying of following LT cables rated for 600/00 volt AC PVC insulated PVC sheathed Cu./Al. conductor armored cable as per IS standard 554 part I with necessary M.S. clamps and spaces on existing wall, tray, Hume pipe etc. complete as reqd. including necessary terminations with required legs and glands. (Supply of cables will be by EPIL) a) 3.5c x 300sq.mm. al. armored cable 355 Mtrs b) 3.5c x 85sq.mm. al. armored cable 70 Mtrs c) 3.5c x 0sq.mm. al. armored cable 4 Mtrs d) 3.5c x 70sq.mm. al. armored cable 30 Mtrs e) 3.5c x 50sq.mm. al. armored cable 60 Mtrs f) 3.5c x 5sq.mm. al. armored cable 800 Mtrs g) 4c x 6sq.mm. al. armored cable 350 Mtrs h) 4c x 0sq.mm. cu. armored cable 800 Mtrs I) 4c x 6sq.mm. Cu. armored cable 3600 Mtrs J) 4c x.5sq.mm. Cu. armored cable 300 Mtrs K) c x.5sq.mm. Co. armored cable 000 Mtrs 3

4 Supply and fixing of GI perforated cable trays, fabricated out of 6 Swg GSS, with supports, fittings etc. complete for the following sizes. a) 50 mm width x 50mm 00 Mtrs b) 50mm width x50mm 400 Mtrs c) 450 mm width X 50 mm 00 Mtrs H POINT WIRING Providing point wiring for Primary light points using x.5 Sq.mm copper Flexible conductor PVC insulated wires conduits of 5/0mm dia. & mm. wall thickness, surface mounted on ceiling, concealed in wall and or through partitions with necessary boxes, Ceiling rose, 6A modular type switch, mounting plate and concealed Metal Box and proper clamping complete as per the final approval of Architect / Consultant. (Average length considered 0 Meters) the wiring points shall be with extension of earthing to all the points. Providing point wiring for Secondary light points using x.5 sq.mm copper Flexible conductor PVC insulated wires in GI conduits of 0mm dia. & mm. wall thickness, surface mounted on ceiling, concealed in wall and or through partitions with necessary boxes, Ceiling rose and proper clamping complete as per the final approval of Architect / Consultant.( Average length considered 5 Meters) all the point wirings shall be along with necessary earthing arrangements

5 3 Providing point wiring for Primary 5A switch socket using x.5 Sq.mm copper Flexible conductor PVC insulated wires in GI conduits of 5/0mm dia. & mm. wall thickness, surface mounted on ceiling, concealed in wall and or through partitions with necessary boxes, Ceiling rose, 6A modular type switch, and socket mounting plate and concealed Metal Box and proper clamping complete as per the final approval of Architect / Consultant. ( Average length considered 0 Meters) Providing Secondary point wiring for 5A switch socket using.5 sq.mm copper conductor PVC insulated wires with 6A modular type switch and socket, mounting plate and concealed Metal Box and proper clamping complete as per the final approval of Architect / Consultant. ( Average length considered 0 Meters)

6 5 Providing point wiring for Primary 6A switch socket using R X.5 sq.mm copper conductor PVC insulated wires in GI conduits of 5/0mm dia. & mm. wall thickness, surface mounted on ceiling, concealed in wall and or through partitions with necessary boxes, Ceiling rose, 6A modular type switch, and socket mounting plate and concealed Metal Box and proper clamping complete as per the final approval of Architect / Consultant. ( Average length considered 0 Meters) along with earthing 60 I LIGHTING FUXTURE Installation, Testing & Commissioning of the following concealed /surface mounted or suspended light fixtures with lamps, Electronic ballast & all necessary mounting & supporting accessories as per the final approval of Architect / Consultant.(Lighting Fixtures Supply shall be by EPIL) a) x 8 W CFL Recess Mounted CFL down lighter with frosted glass x 4 W CFL recess decorative type fitting equivalent to GE Make TC 4 b) x 4 MO MLC HF 800 x 3 W CFL recess down lighter equivalent to GE make CFL x 3 DN c) FG R 740 d) x 50 W CFL light fixture equivalent to GE make MR C DNR R 5 e) x 8 W fluorescent tube light fitting recess type 5 f) x 8 W Fluorescent recessed type fittings complete. 700 g) x 8 W spot light fittings with lamps 40 h) 8 W post top fitting all as per std. specifications 60 I) 8 W CFL decorative fittings as per the selection of Architect 00 J) 50 W Halogen flood light fittings with gear box. 8 6

7 COMPOUND LIGHTING Street Light Pole: Supply, assembling, installation, and erection of single arm 6 meter Octagonal galvanized tapered pole (above ground level) similar to M/s. Bajaj or equivalent, fabricated out of 3mm thick sheet complete with built in junction box, base plate size 5 x 5 x 6 mm, one arm of galvanized pipe of 48.3 mm OD, 3.5 mm thick and.5 m in length on one side of pole shaft as per detailed specifications. Junction box should be provided 500 mm above base plate with 4 brass terminals on epoxy insulator, no 6A SP MCB & no. Neutral link mounted on 3mm thick Bakelite sheet, gland plate etc. Base plate should have 4 nos holes suitable for mounting on RCC foundation 00 mm above FGL, as per specification. The cost of pole shall include the cost of RCC foundation M 0 grade, foundation bolts, anchor plates, nuts, washers, PVC grade pipe 63 mm dia bend to shape & including excavation in all types of soil/foot path cutting, temporary reinstatement, back filling, dewatering, consolidation, disposal of excess earth within the radius of 500 mtrs and making good to the original finish etc. as required to complete the work in all respect as per instructions of the E-I-C. 5 Light Fitting & Fixtures: Installation, testing & commissioning of following Luminaire including internal wiring with 3 x.5 Sq.mm PVC insulated copper conductor cable from terminal box at bottom of the pole to the fixture, earthing of fixture etc as per instructions of the EIC. Street light fitting with 50 W SONT lamp similar to Philips cat. No. CRP a) 330/SON-T-50W or equivalent. 5 7

8 b) Earthing of street light pole with nos of 8 SWG G.I earth wires each 8 m long coiled in m dia coil at a depth of 400 mm below ground level complete with soldering and connections with sockets etc all as per specifications and as per instruction of E.I.C 5 3 Supply, Installation, Testing & Commissioning of compound light Control Box fabricated from mm thick MS CRCA sheet suitable for wall mounting type complete with seven tank processing and painting, earthing locking arrangement fixed on 40x40x5mm angle iron frame, incoming and outgoing cable/ wire way box etc with internal control wiring with FRLS PVC insulated copper conductor wires consisting of following & as per the instructions of E.I.C. GA drawing to be got approved before fabrication. a) 63 Amp.TP & N MCB - No. b) 63 A T P contractor (AC-3) No c) Modular Astronomical Digital time switch similar to M/s Legrand make cat no Astrorex D or equivalent approved make (with software based self adjustment of all days in the year based on longitude of location.) with 6/0 A SP MCB and supporting arrangement - set. d) ON/OFF push buttons with indicating lamps - set. e) R, Y, B indicating lamp for main supply with HRC protection fuse - set. f) Auto Manual Switch - No. g) A HRC fuse for control circuit - No. 8

9 L.T.Cable: Supply, installation, testing & commissioning of core 4 sq,mm.. KV grade copper stranded circular/ sector shape core conductor with PVC/XLPE insulation, PVC extruded (inner) sheathed type ST-, G.I flat strip/wire armored, PVC outer sheathed with antirodent & anti termite treatment FR grade PVC sheath type ST- cable conforming to IS : 554 Part I / IS 7098 Part-I with latest amendments, fixed on wall/column /slab /false ceiling or in existing Hume pipe/gi pipe/ trench / shaft/pit/ on 5mm thick M.S. flat /GI spacer/angle/ support fixed with coach screws /grouted in wall/anchor fasteners mm. thick G.I. fabricated saddle, all fixing accessories, etc complete including painting of M.S spacers/ angles and saddles or in ground at a - depth of 900 mm below ground level/in all types of soil/concrete road cutting /foot path cutting except hard rock excavation including excavation, sand bedding, laying of baked bricks on side & top, temporary reinstatement, back filling, dewatering, consolidation, disposal of excess earth within the radius of 500 mtrs and making good to the original finish etc providing brass cable number tag as per enclosed detailed specifications, drawings & as per instructions of the E-I-C & of the following sizes. 00 Mtrs LIGHTNING ARRESTERS a) Providing & fixing of conventional spike rod type copper air terminal / lightening arrestor (.5 Kg 5mm solid copper rod of m length with 5 fingers) at shown location including making suitable fixing arrangement etc. complete as per site requirement. 6 9

10 AVIATION LAMP a) Aviation obstruction light LED type with meter mounting Bracket and necessary wiring, termination including necessary earthing etc. complete for auto operation. J TELEPHONE AND DATA CABLING Telephone instruments connections laying. (Telephone instruments will be supply by EPIL) 400 Telephone jacks with back box P 0.5 sqmm cu telephone cable in raceways 300 Mtrs 4 4P 0.5 sqmm cu telephone cable in raceways 7000 Mtrs 5 0P 0.5 sqmm cu telephone cable in raceways x5 krone connector module in box for 0 IC lines 7 0x5 krone connector module in box for EPABX 8 0x 30 krone module in krone box (300 users) pair jelly filled 0.5sqmm Cu telephone armored cable 350 Mtrs 0 EPBAX 0IC000OG with console & PC for MIS Cabinet for switches 0 C multimode outdoor armored OM3 OFC back bone 350 Mtrs 3 4P Cat VI 0.5sqmm Cu UTP data cable (Cable will be supply by EPIL) 0000 Mtrs 4 4 C multimode indoor OM3 OFC fly cable 9000 Mtrs 5 6 C multimode indoor OM3 OFC fly cable 700 Mtrs 6 C multimode indoor OM3 OFC fly cable 7500 Mtrs 7 Live Interface Unit at the end of fly cable (for OFC backbone) 8 3 M long SCLC OFC patch cord Sets 9 Media convertor at patch panel for OFC to UTP signal Sets Mtrs 0

11 0 6swg GI C shape channel with removable cover data 50 x 38mm laying (Channels will be supply by EPIL) 3900 Mtrs K PUMP SETS Supply, installation, testing and commissioning of Building water supply pumps having capacity of mtr head along with inter connecting valves, piping up to mtrs, all electrical and control accessories for auto mode operation for filling the tanks with necessary sensors and controls etc. complete. Supply, installation, testing and commissioning of De- Watering pumps having capacity of 00 5 mtr head along with inter connecting valves, piping up to mtrs, all electrical and control accessories for auto mode operation for filling the tanks with necessary sensors and controls etc. complete. L FIRST AID AND SAFETY MATS Rubber mat 40 First Aid Box 8 3 Shock treatment chart M TESTING COMMISSIONING AND WARRANTY OF SYSTEM Installation testing commissioning of entire installation including the system already installed and system included in this boq. Etc. complete. Providing all necessary documentations, training to the maintenance staff and warranty for entire system for a period of one year from the date of handing over to the user. TOTAL JOB JOB