Dharam V. Punwani Avalon Consulting, Inc. Tom L. Pierson Turbine Air Systems, Ltd.

Size: px
Start display at page:

Download "Dharam V. Punwani Avalon Consulting, Inc. Tom L. Pierson Turbine Air Systems, Ltd."

Transcription

1 Turbine Inlet Air Cooling: A Great Strategy for Maximizing the Potential of Combustion Turbines and Addressing the Needs of Restructuring Energy Market Dharam V. Punwani Avalon Consulting, Inc. Tom L. Pierson Turbine Air Systems, Ltd. Presented at Technical, Energy and Government Activities (TEGA) Issues Update Seminar ASHRAE Winter Meeting, Chicago, IL January 26, 2003

2 Impacts of Current and Future Restructured Energy Markets Offer potential for lower energy costs for consumers Challenge producers to reduce cost of electric energy production Increase potential for greater price and service volatility Increase potential for high electric prices and service interruption due to lower reserve margins

3 Primary Benefits and Shortcomings of Combustion Turbines Benefit Lowest Installed Capital Cost Quick to Market Environmentally Friendly Shortcomings Power output decreases as outdoor air temperature increases Fuel utilization efficiency decreases as outdoor temperature increases

4 Combustion Turbine Inlet Cooling (TIC) May be the Best Option for Power Plant Owners/Operators As ambient temperature increases power output and fuel utilization efficiency of a combustion turbine decrease. TIC helps maximize the potential of combustion turbines: Prevents drop in power output and fuel utilization efficiency Allows even increase in power output and fuel utilization efficiency beyond the ISO ratings Reduces environmental emissions per kwh of electric energy

5 Effect of Outdoor Ambient Temperature on Output Capacity of Combustion Turbines Effects of Inlet Air Temperature and Gas Turbine Characteristics on Power Output Power Output, Relative to Rated Capacity Industrial 0.80 Aeroderivative Inlet Air Temperature, o F

6 Effect of Outdoor Ambient Temperature on Heat Rate of Combustion Turbines 110% Aeroderivative Percent Design 105% 100% 95% Frame 90% Ambient Temperature - F

7 Turbine Inlet Cooling Technologies Options Evaporative cooling Fogging system Electric centrifugal chillers Direct-fired double-effect absorption chillers Steam-Heated single- or double-effect absorption chillers Hot water heated single-effect (HWSE) absorption chillers Hybrid systems of some of the compatible options

8 Effect of TIC on Power Output of a 83.5 MW Rated Gas Turbine Los Angeles (87F DB, 64F WB); Evap (90% Approach); Fogging (98% approach); Electric chiller (Cools to 45 o F) Power Output, MW No Cooling Evap Cooling Fogging Chiller Cooling Technology

9 Effect of TIC on Plant Capital Cost for a Cogen Plant with a 83.5 MW Rated Gas Turbine Los Angeles (87F DB, 64F WB); Evap (90% Approach); Fogging (98% approach); Electric chiller (Cools to 45 o F) Cogen Plant $750,00/MW; Evap & Fogging $1,.900/MW; Chiller $800/RT 840, ,141 Total Plant Capital Cost, $/MW 830, , , , , , , , , , , ,000 No Cooling Evap Cooling Fogging Chiller Cooling Technology

10 Effect of TIC on Power Output of a 42.0 MW Rated Gas Turbine Los Angeles (87F DB, 64F WB); Evap (90% Approach); Fogging (98% approach); Electric chiller (Cools to 45 o F) Power Output, MW No Cooling Evap Cooling Fogging Chiller Cooling Technology

11 Effect of TIC on Plant Capital Cost for a Cogen Plant with a 42.0 MW Rated Gas Turbine Los Angeles (87F DB, 64F WB); Evap (90% Approach); Fogging (98% approach); Electric chiller (Cools to 45 o F) Cogen Plant $750,000/MW; Evap & Fogging $1,.900/MW; Chiller $800/RT Plant Capital Cost with TIC, $/MW 950, , , , , , , , , ,472 No Cooling Evap Cooling Fogging Chiller Cooling Technology

12 Effect of Chiller Technology on Increase in Net Power Capacity Ambient DB 95 o F (35 o C) and WB 80 o F (26.6 o C); Chillers cool inlet air to 50 o F (10 o C); 90% and 98% approaches to equilibrium for evap and fogging systems, respectively Net Power Capacity Enhancement, MW Evaporative Cooling Fogging Electric Centrifugal Hot-Water Heated Single Effect Direct-Fired Double Effect

13 Effect of Chiller Technology on Total Plant Cost Including TIC System Ambient DB 95 o F (35 o C) and WB 80 o F (26.6 o C); Chillers cool inlet air to 50 o F (10 o C); 90% and 98% approaches to equilibrium for evap and fogging systems, respectively 869,911 Total Plant Cost Including TIC System, $/MW 870, , , , , , , , , ,616 Hot-Water Heated Single Effect Electric Centrifugal 818,479 Fogging 819,939 Direct-Fired Double Effect 823,207 Evaporative Cooling No Cooling

14 Effect of Cooling Technology on Increase in Annual Net Electric Energy Produced 8760 hour annual operation; Chillers cool inlet air to 50 o F (10 o C) whenever ambient temperature exceeds 50 o F (10 o C); 90% and 98% approaches to equilibrium for evap and fogging systems, respectively 190, , ,062 Annual Net Electric Energy Production, MWh/Yr 170, , , ,000 90,000 70,000 50,000 52,115 58, ,963 30,000 Evaporative Cooling Fogging Electric Centrifugal Hot-Water Heated Single Effect Direct-Fired Double Effect

15 Effect of Cooling Technology on Monthly Increase in Net Electric Energy Produced 8760 hour annual operation; Chillers cool inlet air to 50 o F (10 o C) whenever ambient temperature exceeds 50 o F (10 o C); 90% and 98% approaches to equilibrium for evap and fogging systems, respectively Net Electrical Energy Increase, MWh Electric Centrifugal Hot-Water Heated Single Effect Direct-Fired Double Effect Evaporative Cooling Fogging 0 Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

16 Factors Affecting the Selection and Economics of TIC Technology Combustion turbine characteristics Plant location (Local DB and WB temperature profile) Electric power demand profile Electric energy selling price profile Combustion turbine fuel cost profile TIC system must be optimized for each plant

17 CTIC is Flexible and Compatible with and Complementary to Many Other Technologies Applications Stand-alone technology Combined with other technologies: -Cogeneration - Thermal Storage - District Energy - Duct Firing

18 One Example of TIC Integrated with Cogeneration and Thermal Storage 317 MW (3x105.6 MW) Cogeneration plant in Pasadena, Texas incorporates: 8,300 RT hot-water heated absorption chiller 1,200 RT electric centrifugal chiller 107,000 Ton-hr Thermal Storage capacity. 184,000 Ton-Hrs of Cooling

19 Turbine Inlet Cooling Association (TICA): A Comprehensive Source of TIC Information TICA promotes development and exchange of knowledge related to TIC TICA Website is a comprehensive source of information on - TIC technology - TIC-related published papers - TIC system & component vendors and their Websites and information on some specific TIC installations

20 CT-Based Plants in the U.S. Total U.S. Gas Turbine Capacity in MW in 2002 Planned, 117,839 Operating, 168,833 Construction, 79,647

21 Combustion Turbine Inlet Cooling (CTIC) is a Well Established Technology CTIC is Commercially used around the world Hundreds of plants in the U.S. use CTIC Many more power plants could benefit from CTIC

22 Summary TIC could be very attractive for combustion turbine power plants for dealing with current and restructured energy markets TIC is being commercially used in many plants across the U.S. and the world Significant potential exists for many other plants to benefit from TIC TICA Website is a comprehensive source of information on TICA