Investigation of indoor climate in a naturally ventilated building

Size: px
Start display at page:

Download "Investigation of indoor climate in a naturally ventilated building"

Transcription

1 Investigation of indoor climate in a naturally ventilated building Indoor Air 2008 Tine S. Larsen Assistant professor Department of Civil Engineering Aalborg University tsl@civil.aau.dk 1/9

2 Introduction to the Office Building - Five-storied office building. - The ground floor is mechanically ventilated. - Second to fifth floors are naturally ventilated. - All windows have a manually and an automatically controlled part. - Each floor is divided into 14 zones controlled by an automatic control system which measures temperature (all zones) and CO 2 (four zones at each floor). Zone 43 Zone 44 Zone 45 Zone 46 Zone 42 Zone etage Zone 47 Zone 40 Zone 38 Zone 37 Zone 33 Zone 39 Zone 36 Zone 35 Zone 34 2/9

3 Questionnaire Aim To obtain a general evaluation of the indoor climate in the building To find critical zones in the building Result Overall results were good Problems Insufficient use of solar shadings in offices facing south and west Draught in zones with high internal heat gains Internal noise 3/9

4 Long-term measurements Hours with t > 26 C Aim To evaluate the air quality and thermal conditions in the building during a year (by holding it up against recommendations from Danish regulations) Results Average of 52 hours > 26 C Average of 8 hours > 27 C CO 2 -level always below 1000 ppm Hours Hours Zone Zone Zone Zone Zone Zone Zone Zone Zone Zone Zone Zone Zone Zone Zone Zone Zone Hours with t > 27 C 0 Zone Zone Zone Zone Zone Zone Zone Zone Zone Zone Zone Zone Zone Zone Zone Zone Zone /9

5 Short-term measurements Measurement were made one week during summer, winter and spring Two zones were found from the questionnaire The following were investigated In the zones: Thermal comfort (room temperature, draught, internal heat load, solar shading) Air quality (indicated by CO 2 ) & relative humidity Local air change rates In the building: Ventilation capacity (infiltration, air change rate during service hours, air distribution between floors) 5/9

6 The zones A 3 windows towards west 3 workplaces Int. heat load = 16 W/m² B 2 windows towards east 2 windows towards south 6 workplaces Int. heat load = 34 W/m² 6/9

7 Results - short-term measurements Zone A Thermal comfort all year round High air change rates due to high internal heat gains and solar gains Zone B Thermal comfort all year round but close to the upper limit Problems with draught!!! Internal heat load = 34 W/m² 7/9

8 Results - short-term measurements The entire building Average air change rate 3h -1 to 5h -1 Good indoor air quality in the building Low temperature gradient (0.2 C/m) and CO 2 gradient up through the building Low air change rates in the closed building 0.1h -1 to 0.2h -1 8/9

9 Conclusions Good thermal comfort and excellent perceived indoor air quality can be obtained in a building with open plan offices ventilated by natural ventilation by window openings in the façade Integration of the ventilation strategy at an early stage in the building design is important Simple guidance for the users is important to obtain an optimum use of e.g. solar shadings and manual opening of the windows 9/9