COMMUNITY COLLEGE OF ALLEGHENY COUNTY PURCHASING DEPARTMENT 800 ALLEGHENY AVENUE, PITTSBURGH, PA 15233

Size: px
Start display at page:

Download "COMMUNITY COLLEGE OF ALLEGHENY COUNTY PURCHASING DEPARTMENT 800 ALLEGHENY AVENUE, PITTSBURGH, PA 15233"

Transcription

1 COMMUNITY COLLEGE OF ALLEGHENY COUNTY PURCHASING DEPARTMENT 800 ALLEGHENY AVENUE, PITTSBURGH, PA ADDENDUM NO. 1 BID PROPOSAL NO. 979 MODIFICATIONS TO CHEMISTRY LAB SOUTH CAMPUS JUNE 29, 2016 The following additional information is hereby made a part of this bid proposal: 1. Drawing A1.1 Chemistry Lab Plan: Text box at top of page titled Base Bids: Delete reference to Base Bid #2. There is no Base Bid #2. 2. It is the College s intent to have the successful bidder under contractor by August 1, Work within the classroom spaces can only occur after Monday, December 5, 2016 and must be completed by Friday, January 15, Work on the roof and other areas not affecting the classroom space can commence any time after execution of the contract. 3. Roofing contact: Richard J. Kosuda Senior Field Advisor Tremco Roofing and Building Maintenance rkosuda@tremcoinc.com Cell Phone: Fax: EFax As stated in specification Section Summary, the owner will order and pay for the fume hoods along with delivery to a holding area at the South Campus. An inventory of that equipment is listed on the attached proposal from Nycom. Contractor is to include the cost of moving the equipment to the classrooms and setting of casework by factory certified union installers to manufacturer s specifications and recommendations. 5. See the attached attendance list from the mandatory pre-bid meeting. End of Addendum 1. ****************************************************************************** Sign addendum and submit to the College with your original bid. Company Name Bidder s Signature

2 Proposal # March 2, 2016 Ray Marks Community College of Allegheny County 800 Allegheny Avenue Pittsburgh, PA RE: Modifications To Chemistry Lab CCAC South Campus Based on: Drawing A1.1 dated , Elevation 2, FH-1 assembly only, quantity of 2 Specification section 11600, Laboratory Fume Hoods Specification section 11610, Ducted Exhaust Hoods Kewaunee Scientific Items - Section Laboratory Fume Hoods Quantity of 2 Each Kewaunee Scientific Supreme Air Fume Hoods Constant volume auxiliary air Vertical rising sash Ceiling closure panel 20 high Rectangular exhaust outlet Stainless steel airfoil Polyresin liner Two lamp T-8 light fixtures Black flush plates Air Alert 600 alarm/monitor Factory pre-wired Cold water gooseneck fixture, factory pre-plumbed Kemresin worktop Cupsink Steel base cabinet with 2 cupboard doors for general storage CORPORATE OFFICE MICHAUX GLEN DRIVE MIDLOTHIAN, VIRGINIA TEL: FAX: Maryland Virginia District of Columbia North Carolina South Carolina Georgia Tennessee Alabama Mississippi Louisiana Florida NORTH CAROLINA 606 CHURCH STREET, SUITE 101 MORRISVILLE, NORTH CAROLINA PHONE: FAX:

3 CCAC 3/2/16 Page 2 of 3 External Purchase Items - Section Ducted Exhaust Hoods Sentry Air Systems Ducted Exhaust Hoods Quantity of 12 Model # SS-324-E Per attached cut sheet With optional 24 spill tray with anti-skid surface Installation Our installation includes one time distribution and setting of our casework during normal working hours, leaving premises broom clean and orderly. Our installation is performed by factory certified union installers to manufacturer s specifications and recommendations including removing all packaging materials to an on-site container provided by the owner. Exclusions Gaskets at chemical fume hood interior access panels (none required) Gas, air and vacuum service fixtures. Each hood includes 1 cold water fixture. Hood exhaust and supply blowers, transitions and ductwork Wiring and wiring interconnections between the hoods and controller, sensors, dampers/actuators, limit switches and power source, velocity controllers Air balancing System calibration and adjustments Final MEP hook-ups Base molding Hoisting (quote is based on elevator being available for our use at no charge) 1

4 CCAC 3/2/16 Page 3 of 3 PRICING IS IN ACCORDANCE WITH PA STATE CONTRACT # Purchase Order Should Be Written To: Kewaunee Scientific Corporation P.O. Box 1842 Statesville, NC Attn: Chris Webb Please to: shoe@nycominc.com Respectfully, Nycom, Inc. Sherri Hoe Account Manager Office: Mobile: shoe@nycominc.com 1

5 Exhausting Fume Hood Ducted Fume Hood- 24 Wide Model # SS-324-E Product Specifications HOOD DIMENSIONS Outer Dimensions.: 24" D x 26" W x 25" H Interior Dimensions: 23.5" D x 24" W x 24" H Access Area: 8 x 24 HOOD MATERIAL Sides: 0.250" White Acrylic Base: 0.500" White High Density Polyethylene Top: 0.500" Clear Polycarbonate Front: 0.250" Clear Polycarbonate EXHAUST CONNECTION 6 O.D. Exhaust Collar. 4 Exhaust Collar also available. Ducting & Fan Not Included with this Product WEIGHT Approx. 45 lbs. MAX. OPERATING TEMPERATURE Not to exceed 170 degrees Fahrenheit WARRANTY Limited two-year warranty from date of shipment on defects due to materials or workmanship. PATENT #5,843, MADE IN THE USA Shown with outer dimensions. Measurements are approximate. Disclaimer: The end user is ultimately responsible for conforming to all applicable exhaust ventilation regulations. Consult local, state and federal agencies regarding the suitability of your application prior to venting fumes to the environment. It is your ultimate responsibility to ensure the safety and suitability of your application. For more information, contact a local safety professional (certified industrial hygienist) for conformance and suitability. Product Features Fluorescent Light Included Custom Material Options Custom Size & Modification Options Other Standard Sizes: 18, 30, 40, 50, 60, 70 Optional Spill Trays Optional Anti-Static Vinyl Strip Curtains Compact, Sturdy, Cost-effective. The 24 Wide Ducted Fume Hood, often referred to as a Ducted Exhaust Hood, is an excellent choice for manufacturing, laboratories, and medical clinics that handle volatile organics, powder and capsule filling, solvent vapors, acid etching processes, or applications where filter media is not an appropriate strategy. This exterior-exhausting hood is compact and manufactured with features that simplify relocation and transport should it be necessary. The 24 Wide Ducted Fume Hood is also: Designed to achieve and maintain 100 FPM face velocity with the appropriate fan. Composed of shatter-resistant materials. Built with slip hatches and access ports for instruments and cords. Equipped with a fluorescent lamp. Constructed from materials that are resistant to most chemicals and many solvents. Customization to Your Needs. If you need an exhaust hood of a specific size, material, or with an application-specific amendment, our engineering team will design and fabricate a hood to meet your needs. We have designed transparent hoods, PVC hoods, and hoods with rotating trays. Simple Solutions for Cleaner Air sales@sentryair.com This unit includes a 6 Exhaust Collar (optional 4 Exhaust Collar) and does not include ducting or fan. Ask Sentry Air Systems Applications Specialists for assistance in selecting a suitable fan. Sentry Air Systems also manufactures fume hoods that include a fan and filtration media (Ductless Fume Hood).

6