Transcription

1 Air Conditioning Technical Data RZQG-L9V

2

3 TABLE OF CONTENTS RZQG-L9V Features Specifications Capacity and Power input Capacity and Power input Capacity and Power input Capacity and Power input Capacity and Power input Capacity and Power input Capacity and Power input Capacity and Power input Technical Specifications Electrical Specifications Electrical data Options Combination table Capacity tables Cooling/Heating Capacity Tables Capacity Correction Factor Dimensional drawings Centre of gravity Piping diagrams Piping Diagrams Piping Diagram Twin Application Piping Diagram Triple Application Piping Diagram Double Twin Application Wiring diagrams Wiring Diagrams - Single Phase Sound data Sound Pressure Spectrum - Cooling Sound Pressure Spectrum - Heating Sound Pressure Spectrum Quiet Mode Installation Installation Method Operation range Split - Sky Air RZQG-L9V

4 k i n n i - T r 9 o t L, o -i r d l i t pau Z Features, S U w V G Q OIndustry RP S leading technology for commercial applications and even for technical rooms Top efficiency: - energy labels up to A++ in both cooling and heating - compressor that offers substantial efficiency improvements - control logic that optimises efficiency at the most frequently encountered operating conditions and that optimises the auxiliary modes (when the unit is not active) - heat exchangers that optimise the refrigerant flow at the most frequent operating conditions (temperature and load) - via improved nominal performances The perfect balance in efficiency and comfort thanks to Variable Refrigerant Temperature: top seasonal efficiency throughout most of the year and quick reaction speed on the hottest days. Suits high sensible, infrastructure cooling applications Replace existing R-22 or R-7C systems without having to replace the piping Extended operation range down to - C in heating and down to - 5 C in cooling With a gas cooled PCB reliable cooling is guaranteed as it is not influenced by ambient temperature Maximum piping length up to 75m, minimum piping length is 5m. Outdoor units for pair, twin, triple, double twin application Daikin outdoor units are neat, sturdy and can easily be mounted on a roof or terrace or simply placed against an outside wall Units optimized for seasonal efficiency give an indication on how efficient an air conditioner operates over an entire heating or cooling season. Infrastructure cooling Inverter Auto coolingheating changeover 2 Split - Sky Air RZQG-L9V

5 2 Specifications 2- Capacity and Power input FAQ7C9/RZQG7L9V FAQ00C9/RZQG00L9V FAQ00C9/RZQG7L9V Indoor unit FAQ7C - Outdoor unit RZQG7L9V - Cooling capacity Nom. kw Heating capacity Nom. kw Power input Cooling Nom. kw Heating Nom. kw Seasonal efficiency Cooling Energy label A++ (according to Pdesign kw EN4825) SEER Annual energy kwh consumption Heating (Average Energy label A+ climate) Pdesign kw SCOP/A Annual energy consumption kwh 2,5,562 2,5 Eurovent Sound power level outdoor Cooling Nom. dba Sound power level indoor Cooling Nom. dba 6 65 Nominal efficiency EER COP..6 - Annual energy consumption kwh,000 (),5 - Energy label Cooling A - Heating A - 2 () Nominal efficiency: cooling at 5 /27 nominal load, heating at 7 / nominal load Annual energy consumption is according to Energy labeling directive 02//EC SEER and SCOP are according to EN 4825 EER/COP according to Eurovent 2, for use outside EU only 2-2 Capacity and Power input FBQ7D/ RZQG7L9V FBQ00D/ RZQG00L9V FBQ25D/ RZQG25L9V FBQD/ RZQGL9V FBQ00D/ RZQG7L9V FBQD/ RZQG00L9V FBQD/ RZQG25L9V Indoor unit FBQ7D FBQ00D FBQ25D FBQD FBQ00D FBQD Outdoor unit RZQG7L9 V RZQG00L 9V RZQG25L 9V RZQGL 9V RZQG7L9 V RZQG00L 9V RZQG25L 9V Cooling capacity Nom. kw 6.8 () 9.5 () 2.0 ().4 () - Heating capacity Nom. kw 7. () 0.80 (). () 5. () - Power input Cooling Nom. kw.89 () 2.49 ().6 () 4.00 () - Heating Nom. kw.87 () 2.45 ().46 () 4. () - Seasonal efficiency Cooling Energy label A++ A+ A++ - A++ A+ A++ (according to Pdesign kw EN4825) SEER Annual energy consumption kwh Heating (Average Energy label A+ A++ A+ - A+ A++ A+ climate) Pdesign kw SCOP/A Annual energy consumption kwh,949,0 4,54 -,949,0 4,54 Nominal efficiency EER. (2).8 (2). (2).5 (2) - COP 4.0 (2) 4.4 (2).90 (2). (2) - Annual energy consumption kwh 944,247,8 - Energy label Cooling A - Heating A - Split - Sky Air RZQG-L9V

6 2 Specifications () Nominal efficiency: cooling at 5 /27 nominal load, heating at 7 / nominal load (2) EER/COP according to Eurovent 2, for use outside EU only 2 2- Capacity and Power input FCQG7F/ RZQG7L9V FCQG00F/ RZQG00L9V FCQG25F/ RZQG25L9V FCQGF/ RZQGL9V FCQG00F/ RZQG7L9V FCQGF/ RZQG00L9V FCQGF/ RZQG25L9V Indoor unit FCQG7F FCQG00F FCQG25F - FCQG00F FCQGF Outdoor unit RZQG7L9 V RZQG00L 9V RZQG25L 9V RZQGL 9V RZQG7L9 V RZQG00L 9V RZQG25L 9V Cooling capacity Nom. kw Heating capacity Nom. kw Power input Cooling Nom. kw Heating Nom. kw Seasonal efficiency Cooling Energy label A++ A+ - A++ A+ (according to Pdesign kw EN4825) SEER Annual energy consumption kwh Heating (Average Energy label A+ A++ A+ - A+ A++ A+ climate) Pdesign kw SCOP/A Annual energy consumption kwh 2,0,42 4,2-2,0,42 4,2 Eurovent Sound power level Cooling Nom. dba 64 - outdoor Sound power level indoor Cooling Nom. dba 5 - Nominal efficiency EER COP Annual energy consumption kwh,005,225, - Energy label Cooling A - Heating A - Annual energy consumption is according to Energy labeling directive 02//EC SEER and SCOP are according to EN 4825 EER/COP according to Eurovent 2, for use outside EU only Nominal efficiency: cooling at 5 /27 nominal load, heating at 7 / nominal load 2-4 Capacity and Power input FCQHG7F/ RZQG7L9V FCQHG00F/ RZQG00L9V Indoor unit FCQHG7F FCQHG00 F Outdoor unit RZQG7L9 V RZQG00L 9V FCQHG25F/ RZQG25L9V FCQHG25 F RZQG25L 9V FCQHGF/ RZQGL9V FCQHG F RZQGL 9V FCQHG00F/ RZQG7L9V FCQHG00 F RZQG7L9 V FCQHGF/ RZQG00L9V Cooling capacity Nom. kw Heating capacity Nom. kw Power input Cooling Nom. kw Heating Nom. kw RZQG00L 9V FCQHGF FCQHGF/ RZQG25L9V RZQG25L 9V 4 Split - Sky Air RZQG-L9V

7 2 Specifications 2-4 Capacity and Power input FCQHG7F/ RZQG7L9V FCQHG00F/ RZQG00L9V FCQHG25F/ RZQG25L9V FCQHGF/ RZQGL9V FCQHG00F/ RZQG7L9V FCQHGF/ RZQG00L9V FCQHGF/ RZQG25L9V Seasonal efficiency Cooling Energy label A++ - A++ (according to Pdesign kw EN4825) SEER Annual energy consumption kwh Heating (Average Energy label A+ A++ - A+ A++ climate) Pdesign kw SCOP/A Annual energy consumption kwh 2,44,296,829-2,44,296,829 Eurovent Sound power level Cooling Nom. dba 64 - outdoor Sound power level indoor Cooling Nom. dba 5 - Nominal efficiency EER COP Annual energy consumption kwh 80,075,0 - Energy label Cooling A - Heating A - 2 Annual energy consumption is according to Energy labeling directive 02//EC SEER and SCOP are according to EN 4825 EER/COP according to Eurovent 2, for use outside EU only Nominal efficiency: cooling at 5 /27 nominal load, heating at 7 / nominal load 2-5 Capacity and Power input FDQ25C/RZQG25L9V Indoor unit FDQ25C Outdoor unit RZQG25L9V Cooling capacity Nom. kw 2.0 Heating capacity Nom. kw.5 Power input Cooling Nom. kw. Heating Nom. kw.5 Seasonal efficiency Cooling Energy label A+ (according to Pdesign kw 2.00 EN4825) SEER 5.8 Annual energy kwh 72 consumption Heating (Average Energy label A+ climate) Pdesign kw 2.7 SCOP/A 4.2 Annual energy kwh 4,227 consumption Nominal efficiency EER.75 COP.8 Annual energy consumption kwh,0 Energy label Cooling A Heating A EER/COP according to Eurovent 2, for use outside EU only Nominal efficiency: cooling at 5 /27 nominal load, heating at 7 / nominal load Split - Sky Air RZQG-L9V 5

8 2 Specifications Capacity and Power input FHQ7CB/ RZQG7L9V FHQ00CB/ RZQG00L9V FHQ25CB/ RZQG25L9V FHQ00CB/ RZQG7L9V FHQCB/ RZQGL9V FHQCB/ RZQG00L9V FHQCB/ RZQG25L9V Indoor unit FHQ7C - Outdoor unit RZQG7L9 V - Cooling capacity Nom. kw Heating capacity Nom. kw Power input Cooling Nom. kw Heating Nom. kw Seasonal efficiency Cooling Energy label A++ - (according to Pdesign kw EN4825) SEER Annual energy consumption kwh Heating (Average Energy label A+ - climate) Pdesign kw SCOP/A Annual energy consumption kwh 2,46,42 4,677 2,46 -,42 4,677 Eurovent Sound power level outdoor Cooling Nom. dba Sound power level indoor Cooling Nom. dba Nominal efficiency EER COP Annual energy consumption kwh 890 (),245 (),790 () - 2,025 () - Energy label Cooling A - Heating A - () Nominal efficiency: cooling at 5 /27 nominal load, heating at 7 / nominal load Annual energy consumption is according to Energy labeling directive 02//EC SEER and SCOP are according to EN 4825 EER/COP according to Eurovent 2, for use outside EU only 2-7 Capacity and Power input FUQ7C/RZQG7L9V FUQ00C/RZQG00L9V FUQ25C/RZQG25L9V FUQ00C/RZQG7L9V Indoor unit FUQ7C FUQ00C FUQ25C FUQ00C Outdoor unit RZQG7L9V RZQG00L9V RZQG25L9V RZQG7L9V Cooling capacity Nom. kw Heating capacity Nom. kw Power input Cooling Nom. kw Heating Nom. kw Seasonal efficiency Cooling Energy label A++ A+ A++ (according to Pdesign kw EN4825) SEER Annual energy consumption kwh Heating (Average Energy label A+ climate) Pdesign kw SCOP/A Annual energy consumption kwh 2,54,56 4,456 2,54 Eurovent Sound power level Cooling Nom. dba 64 - outdoor Sound power level indoor Cooling Nom. dba 59-6 Split - Sky Air RZQG-L9V

9 2 Specifications 2-7 Capacity and Power input FUQ7C/RZQG7L9V FUQ00C/RZQG00L9V FUQ25C/RZQG25L9V FUQ00C/RZQG7L9V Nominal efficiency EER COP Annual energy consumption kwh 8 (),,7 - Energy label Cooling A - Heating A B - 2 () Nominal efficiency: cooling at 5 /27 nominal load, heating at 7 / nominal load Annual energy consumption is according to Energy labeling directive 02//EC SEER and SCOP are according to EN 4825 EER/COP according to Eurovent 2, for use outside EU only 2-8 Capacity and Power input FVQ7C/ RZQG7L9V FVQ00C/ RZQG00L9V FVQ25C/ RZQG25L9V FVQC/ RZQGL9V FVQ00C/ RZQG7L9V FVQC/ RZQG00L9V FVQC/ RZQG25L9V Indoor unit FVQ7C FVQ00C FVQ25C FVQC FVQ00C FVQC Outdoor unit RZQG7L9 V RZQG00L 9V RZQG25L 9V RZQGL 9V RZQG7L9 V RZQG00L 9V RZQG25L 9V Cooling capacity Nom. kw Heating capacity Nom. kw Power input Cooling Nom. kw Heating Nom. kw Seasonal efficiency Cooling Energy label A++ A+ - A++ A+ (according to Pdesign kw EN4825) SEER Annual energy consumption kwh Heating (Average Energy label A+ A - A+ A climate) Pdesign kw SCOP/A Annual energy consumption kwh 2,89,767 4,088-2,89,767 4,088 Eurovent Sound power level Cooling Nom. dba 64 - outdoor Sound power level indoor Cooling Nom. dba 55 - Nominal efficiency EER COP Annual energy consumption kwh,00 (),245,8 2,085 - Energy label Cooling A - Heating A - () Nominal efficiency: cooling at 5 /27 nominal load, heating at 7 / nominal load Annual energy consumption is according to Energy labeling directive 02//EC SEER and SCOP are according to EN 4825 EER/COP according to Eurovent 2, for use outside EU only 2-9 Technical Specifications RZQG7L9V RZQG00L9V RZQG25L9V RZQGL9V Capacity control Method Inverter controlled Casing Colour Ivory white Material Painted galvanized steel plate Split - Sky Air RZQG-L9V 7

10 2 Specifications Technical Specifications RZQG7L9V RZQG00L9V RZQG25L9V RZQGL9V Dimensions Unit Height mm 990, Width mm 9 Depth mm Packed unit Height mm,, Width mm,05 Depth mm 422 Weight Unit kg Packed unit kg Heat exchanger Fin Type WF fin Treatment Anti-corrosion treatment (PE) Compressor Quantity Type Hermetically sealed swing compressor Starting method Inverter driven Fan Type Propeller fan Discharge direction Horizontal Quantity 2 Air flow rate Cooling Nom. m³/min Heating Nom. m³/min Fan motor Quantity 2 Model Brushless DC motor Output W 94 Drive Direct drive Speed Cooling Super rpm - low Heating Super low rpm - Sound power level Cooling dba Heating dba - Sound pressure level Cooling Nom. dba Heating Nom. dba 52 5 Night quiet mode Level dba 4 45 Operation range Cooling Ambien Min. CDB -5 t Max. CDB Heating Ambien Min. CWB - t Max. CWB 5.5 Refrigerant Type R-A Charge kg TCO 2 eq Control Expansion valve (electronic type) GWP 2,087.5 Circuits Quantity 8 Split - Sky Air RZQG-L9V

11 2 Specifications 2-9 Technical Specifications RZQG7L9V RZQG00L9V RZQG25L9V RZQGL9V Piping connections Liquid Quantity Type Flare connection OD mm 9.52 Gas Quantity Type Flare connection OD mm 5.9 Drain Quantity 5 Type Hole ID mm - OD mm 26 Piping length OU - IU Min. m 5 () Max. m 75 System Equival ent m 90 Chargel ess m 0 Additional refrigerant charge kg/m See installation manual Level difference IU - OU Max. m 0.0 IU - IU Max. m 0.5 Heat insulation Both liquid and gas pipes Refrigerant oil Type FVCK Charged volume l Defrost method Reversed cycle Defrost control Sensor for outdoor heat exchanger temperature Safety devices Item 0 High pressure switch 02 Low pressure switch 0 Fan driver overload protector 04 Fuse Standard Accessories : Tie-wraps; Quantity : 2; Standard Accessories : Installation manual; Quantity : ; Electrical Specifications RZQG7L9V RZQG00L9V RZQG25L9V RZQGL9V Power supply Name V Phase ~ Frequency Hz Voltage V 2-2 Voltage range Min. % -0 Max. % 0 Current - Hz Maximum fuse amps (MFA) A 25 Current Zmax List Complies to EN00-- Recommended fuses A 25 Current - Hz Maximum fuse amps (MFA) A - Wiring connections For power supply Remark See installation manual outdoor unit For connection with Remark See installation manual outdoor unit indoor Power supply intake Outdoor unit only () with re-charging PED: assembly = category l : excluded from scope of PED due to article, item.6 of 97/2/EC Minimum Ssc (=Short-circuit power) value: Equipment complying with EN/IEC 00--2: European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current \>6A and 75A per phase See separate drawing for electrical data Contains fluorinated greenhouse gases MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). For more detailed information on each combination, please refer to the electrical data drawing. Split - Sky Air RZQG-L9V 9

12 Electrical data - Electrical Data RZQG L9V Unit combination restrictions Indoor Outdoor COMP OFM IFM 2 MCA MFA RHz RLA kw FLA kw FLA Power supply The RLA is based on the following conditions. Indoor temperature 27 C DB / 9 C WB Outdoor temperature 5 C DB 2 Select the wire size according to the MCA. The maximum allowable voltage that is unbalanced between phases is 2%. 4 Use a circuit breaker instead of a fuse. Symbols Hz MCA MFA RLA Voltage Voltage range Minimum Circuit Ampere (A) Maximum Fuse Ampere (A) Rated load amps [A] OFM Outdoor fan motor IFM Indoor fan motor FLA Full Load Ampere (A) kw Fan motor rated output [kw] RHz Rated operating frequency [Hz] COMP Compressor D0965C RZQG7 25L9V Unit combination restrictions Indoor Outdoor COMP OFM IFM 2 MCA MFA RHz RLA kw FLA kw FLA Power supply 2 4 The RLA is based on the following conditions. Indoor temperature 27 C DB / 9 C WB Outdoor temperature 5 C DB Select the wire size according to the MCA. The maximum allowable voltage that is unbalanced between phases is 2%. Use a circuit breaker instead of a fuse. Symbols Hz MCA MFA RLA Voltage Voltage range Minimum Circuit Ampere (A) Maximum Fuse Ampere (A) Rated load amps [A] OFM IFM FLA kw RHz COMP Outdoor fan motor Indoor fan motor Full Load Ampere (A) Fan motor rated output [kw] Rated operating frequency [Hz] Compressor D09486B 0 Split - Sky Air RZQG-L9V

13 Electrical data - Electrical Data RZQG25 L9V Unit combination restrictions Indoor Outdoor COMP OFM IFM 2 MCA MFA RHz RLA kw FLA kw FLA Power supply 2 4 The RLA is based on the following conditions. Indoor temperature 27 C DB / 9 C WB Outdoor temperature 5 C DB Select the wire size according to the MCA. The maximum allowable voltage that is unbalanced between phases is 2%. Use a circuit breaker instead of a fuse. Symbols Hz MCA MFA RLA Voltage Voltage range Minimum Circuit Ampere (A) Maximum Fuse Ampere (A) Rated load amps [A] OFM IFM FLA kw RHz COMP Outdoor fan motor Indoor fan motor Full Load Ampere (A) Fan motor rated output [kw] Rated operating frequency [Hz] Compressor D09486B RZQGL9V Unit combination restrictions Indoor Outdoor COMP OFM IFM 2 MCA MFA RHz RLA kw FLA kw FLA Power supply 2 4 The RLA is based on the following conditions. Indoor temperature 27 C DB / 9 C WB Outdoor temperature 5 C DB Select the wire size according to the MCA. The maximum allowable voltage that is unbalanced between phases is 2%. Use a circuit breaker instead of a fuse. MCA MFA RLA Symbols Hz Voltage Voltage range Minimum Circuit Ampere (A) Maximum Fuse Ampere (A) Rated load amps [A] OFM IFM FLA kw RHz COMP Outdoor fan motor Indoor fan motor Full Load Ampere (A) Fan motor rated output [kw] Rated operating frequency [Hz] Compressor D0965C Split - Sky Air RZQG-L9V

14 4 Options 4 - Options RZQG L9V 4 Available options for RZQG models Option Bottom plate heater Refrigerant branch piping Demand adaptor kit Option kit RZQG7L9VB RZQG00L9VB RZQG25L9VB RZQGL9VB EKBPHL7 Twin KHRQ22MTA Triple KHRQ27H Double twin KHRQ22MTA (x) SB.KRP58M5 D09056A 2 Split - Sky Air RZQG-L9V

15 5 Combination table 5 - Combination Table RZQG L9V RZQG L(8)Y Sky Air Possible combinations Model P= Pair 2= Twin = Triple 4= Double twin (*) ++ (*) (*) (*): Maximum capacity of outdoor units High Cassette Thin cassette 2x2 cassette Duct (medium ESP) Ceiling-suspended Ceiling-mounted - 4-way blow FCQHG7FVEB FCQHG00FVEB FCQHG25FVEB FCQHGFVEB FCQG5FVEB FCQGFVEB FCQGFVEB FCQG7FVEB FCQG00FVEB FCQG25FVEB FCQGFVEB FFQ5C2VEB FFQC2VEB FFQC2VEB FBQ5C8VEB FBQC8VEB FBQC8VEB FBQ7C8VEB FBQ00C8VEB FBQ25C8VEB FBQC8VEB FHQ5BVVB8 FHQBVVB8 FHQBVVB8 FHQG7CVEB FHQG00CVEB FHQG25CVEB FHQGCVEB FUQ7CVEB FUQ00CVEB FUQ25CVEB FAQ7CVEB FAQ00CVEB Duct (high ESP) FDQ25C7VEB FVQ7CVEB FVQ00CVEB FVQ25CVEB FVQCVEB FDXS5F2VEB FDXSF2VEB9 FDXSF2VEB RZQG7L9VB RZQG7L8YB P 2 P 2 2 P 2 P P P P 2 RZQG00L9VB RZQG00L8YB P 2 P 2 2 P 2 P P P P 2 RZQG25L9VB RZQG25L8YB P 4 2 P P 4 2 P P P P 4 2 RZQGL9VB RZQGL7YB 2 P 4 2 P P 4 2 P 2 2 P 4 Wall mounted type Floor standing type Slim duct 5 Sky Air Duct (medium ESP) Concealed floor standing type Model FBQ5D2VEB FBQD2VEB FBQD2VEB FBQ7D2VEB FBQ00D2VEB FBQ25D2VEB FBQD2VEB FNQ25A2VEB FNQ5A2VEB FNQA2VEB FNQA2VEB RZQG7L9VB RZQG00L9VB RZQG25L9VB RZQGL9VB RZQG7L8YB RZQG00L8YB RZQG25L8YB RZQGL7YB 2 P 2 2 P P P 4. The capacities in the table are combined capacities (multiple units operating simultaneously) and not individual indoor unit capacities. 2. When combining multiple indoor units, designate the unit whose remote controller is equipped with the most functions as the master unit.. For the selection of the correct refnet kit, required to install a multi-combination, refer to the option list. Twin : Triple : Double twin : KHRQ22MTA or KHRQ58T KHRQ27H or KHRQ58H KHRQ22MTA or KHRQ58T D0906B RZQG-L9V RZQG-L(8)Y ooling SkyAir High Cassette Thin cassette 2x2 cassette Duct (medium ESP) Ceiling-suspended Wall Ceiling-mounted mounted - 4-way blow type Duct (high ESP) Floor standing type Slim duct Concealed floor standing type Model FCQHG7FVEB FCQHG00FVEB FCQHG25FVEB FCQHGFVEB FCQG5FVEB FCQGFVEB FCQGFVEB FCQG7FVEB FCQG00FVEB FCQG25FVEB FCQGFVEB FFQ5C2VEB FFQC2VEB FFQC2VEB FBQ5D2VEB FBQD2VEB FBQD2VEB FBQ7D2VEB FBQ00D2VEB FBQ25D2VEB FBQD2VEB FHQ5CAVEB FHQCAVEB FHQCAVEB FHQ7CAVEB FHQ00CAVEB FHQ25CAVEB FHQCAVEB FUQ7CVEB FUQ00CVEB FUQ25CVEB FAQ7CVEB FAQ00CVEB FDQ25C7VEB FVQ7CVEB FVQ00CVEB FVQ25CVEB FVQCVEB FDXS5F2VEB FDXSF2VEB9 FDXSF2VEB FNQ5A2VEB FNQA2VEB RZQG7L9VB RZQG7L8YB P 2 P 2 2 P 2 P P P P 2 RZQG00L9VB RZQG00L8YB P 2 P 2 P 2 P 2 2 P RZQG25L9VB RZQG25L8YB 2 P 4 2 P P 4 2 P 2 2 P 4 RZQGL9VB RZQGL7YB 2 P 4 2 P P 4 2 P 2 2 P 4 Possible combinations P= Pair 2= Twin = Triple 4= Double twin. The capacities in the table are combined capacities (multiple units operating simultaneously) and not individual indoor unit capacities. 2. When combining multiple indoor units, designate the unit whose remote controller is equipped with the most functions as the master unit.. For the selection of the correct refnet kit, required to install a multi-combination, refer to the option list. Twin : KHRQ22MT or KHRQ58T Triple : KHRQ27H or KHRQ58H Double twin : KHRQ22MT or KHRQ58T D078D Split - Sky Air RZQG-L9V

16 6 Capacity tables 6 - Cooling/Heating Capacity Tables RZQG7L9V RZQG7L8Y Cooling Heating 6 Coefficient of the power input Coefficient of the power input Symbols AFR: Air flow rate [m³/min] BF: Bypass factor EWB: Entering wet bulb temperature ( C WB) EDB: Entering dry bulb temperature ( C DB) TC: Maximum total cooling/heating capacity [kw] SHC: Sensible heat capacity [kw] CPI: Coefficient of the power input PI: Power input [kw] Capacity range Rated point Capacity range Rated point compressor + indoor and outdoor fan motors Cooling capacity [kw] Heating capacity [kw] Cooling Heating Outdoor temperature [ C DB] Indoor TC SHC CPI TC SHC CPI TC SHC CPI TC SHC CPI TC SHC CPI Indoor WB DB kw kw kw kw kw kw kw kw kw kw 6,0 22 8,0 5,45,00 7,76 5,2, 7,48 5,,2 7,2 5,06,2 5,52,9 0,94 8,0 25 8, 5,45,00 8, 5,2, 7,8 5,9,22 7,54 5,05, 5,78,9 0,95 9,0 27 8,59 5,44,0 8,0 5,2,2 8,00 5,8,22 7, 5,05, 5,90,9 0,95 9,5 27 8,68 5,4,0 8,9 5,,2 8,09 5,7,22 7,79 5,05, 5,97,9 0,95 22,0 0 9,5 5,8,0 8,84 5,25,2 8,52 5,,2 8,2 4,99,4 6,29,86 0,96 24,0 2 9,5 5,,0 9, 5,9, 8,87 5,06,25 8,54 4,92,5 6,54,8 0,97. The ratings shown are net capacities which include a deduction for indoor fan motor heat. 2. = Maximum at standard conditions =Rated capacity and rated coefficient of the power input The maximum capacity is not guaranteed except at standard conditions.. SHC is based on indoor units EWB & EDB. SHC for other dry bulb temperatures = SHC + SHC* SHC* = SHC correction for other dry bulb temperatures =0.02 x AFR (m³/min) x ( BF) x (DB* EDB) 4. The capacities are based on the following conditions: Outdoor air: 85% RH However, the outdoor ambient condition of the rated capacity during heating operation is 7 C DB / 6 C WB. Corresponding refrigerant piping length: 5.0 m Level difference: 0m 5. CPI is a percentage value compared to the rated value which is The error rate for this value is less than 5% and depends on the indoor unit type. 7. The heating performance takes into account the drop that occurs during defrost operation. 8. The air flow rate and bypass factor are mentioned in the table. 9. The rated power input for each model is mentioned in the table below. Pair Pair FCQHG7F FCQG7F FBQ7C FHQG7C FAQ7C FVQ7C FHQ7CA FUQ7C FBQ7D FCQHG7F FCQG7F FBQ7C FHQG7C FAQ7C FVQ7C FHQ7CA FUQ7C FBQ7D AFR Cooling,66 2,0,94,78 2,00 2,02,78,67,89 (BF) ( 0.2) (0.4) (0.08) (0.) (0.6) (0.6) (0.) (0.24) (0.) Heating,56,89 2,05,82 2,0 2,06,82,68,87 Twin Twin FCQG5F X 2 FBQ5C X 2 FHQ5CA X 2 FFQ5C X 2 FDXS5F X 2 FBQ5D X 2 FNQ5A X 2 FCQG5F X 2 FBQ5C X 2 FHQ5CA X 2 FFQ5C X 2 FDXS5F x 2 FBQ5D X 2 FNQ5A X 2 AFR 2.5 x 2 6 x2 4 x 2 0 x 2 8,7 x 2 5 x 2 8,7 x 2 Cooling 2,04,98 2,4 2,02 2,2 2,0 2,2 (BF) (0.4 x 2) (0.5 x 2) (0.7 x 2) (0.25 x 2) (0.7 x 2) (0.08 x 2) (0.7 x 2) Heating,92 2,6 2,,88 2,55 2,08 2,55 D076748F RZQG00L9V RZQG00L8Y Cooling Heating Coefficient of the power input Coefficient of the power input Symbols AFR: Air flow rate [m³/min] BF: Bypass factor EWB: Entering wet bulb temperature ( C WB) EDB: Entering dry bulb temperature ( C DB) TC: Maximum total cooling/heating capacity [kw] SHC: Sensible heat capacity [kw] CPI: Coefficient of the power input PI: Power input [kw] compressor + indoor and outdoor fan motors Cooling Capacity range Cooling capacity [kw] Rated point Capacity range Heating capacity [kw] Rated point Heating Outdoor temperature [ C DB] Outdoor temperature [ C WB] Indoor TC SHC CPI TC SHC CPI TC SHC CPI TC SHC CPI TC SHC CPI Indoor WB DB kw kw kw kw kw kw kw kw kw kw 6,0 22, 7,6,0 0,85 7,44, 0, 7,29,22 0, 7,09,2 7,67 5,46 0,90 8,0 25,80 7,59,0,7 7,49,2,00 7,27,2 0,55 7,09, 7,97 5,45 0,9 9,0 27 2,00 7,57,02,62 7,44,2, 7,26,2 0,80 7,04, 8, 5,42 0,9 9,5 27 2,5 7,59,02,74 7,7,,4 7,4,2 0,9 7,04,4 8,28 5,4 0,9 22,0 0 2,80 7,52,02 2,7 7,6,,90 7,6,24,52 7,0,5 8,7 5, 0,92 24,0 2,0 7,42,0 2,88 7,27,4 2, 7,06,25,97 6,9,6 9, 5, 0,9. The ratings shown are net capacities which include a deduction for indoor fan motor heat. 2. = Maximum at standard conditions =Rated capacity and rated coefficient of the power input The maximum capacity is not guaranteed except at standard conditions.. SHC is based on indoor units EWB & EDB. SHC for other dry bulb temperatures = SHC + SHC* SHC* = SHC correction for other dry bulb temperatures =0.02 x AFR (m³/min) x ( BF) x (DB* EDB) 4. The capacities are based on the following conditions: Outdoor air: 85% RH However, the outdoor ambient condition of the rated capacity during heating operation is 7 C DB / 6 C WB. Corresponding refrigerant piping length: 5.0 m Level difference: 0m 5. CPI is a percentage value compared to the rated value which is The error rate for this value is less than 5% and depends on the indoor unit type. 7. The heating performance takes into account the drop that occurs during defrost operation. 8. The air flow rate and bypass factor are mentioned in the table. 9. The rated power input for each model is mentioned in the table below. Pair Pair FCQHG00F FCQG00F FBQ00C FHQG00C FAQ00C FVQ00C FHQ00CA FUQ00C FBQ00D FCQHG00F FCQG00F FBQ00C FHQG00C FAQ00C FVQ00C FHQ00CA FUQ00C FBQ00D AFR Cooling 2,5 2,45 2,44 2,49 2,6 2,49 2,49 2, 2,49 (BF) (0.7) (0.7) (0.) (0.09) (0.0) (0.) (0.09) (0.) (0.0) Heating 2,6 2, 2,57 2,,00 2,6 2, 2,62 2,45 Twin Twin FCQGF X 2 FBQC X 2 FHQCA X 2 FFQC X 2 FDXSF9 X 2 FBQD X 2 FNQA X 2 FCQGF X 2 FBQC X 2 FHQCA X 2 FFQC X 2 FDXSF9 X 2 FBQD X 2 FNQA X 2 AFR (BF) 2.6 x 2 6 x2 5 x 2 2 x 2 6 x 2 5 x 6 x 2 (0.22 x 2) (0.6 x 2) (0.8 x 2) (0.6 x 2) (0. x 2) (0. x 2) (0. x 2) Cooling 2,2 2,5 2,9 2,65 2,5 2,87 2,5 Heating 2,46 2,86,28 2,89 2,96 2,7 2,96 Triple Triple FCQG5F X FBQ5C X FHQ5CA X FFQ5C X FDXS5F X FBQ5D x FNQ5A X FCQG5F X FBQ5C X FHQ5CA X FFQ5C X FDXS5F X FBQ5D x FNQ5A X AFR 2.5 x 6 x 4 x 0 x 8.7 x 5 x 8.7 x Cooling 2,8 2,5 2,9 2,45 2,8 2,68 2,8 (BF) (0.4 x ) (0.5 x ) (0.7 x ) (0.25 x ) (0.7 x ) (0.08 x ) (0.7 x ) Heating 2,5 2,86, 2,59,68 2,,68 D076749F 4 Split - Sky Air RZQG-L9V

17 6 Capacity tables 6 - Cooling/Heating Capacity Tables RZQG25L9V RZQG25L8Y Cooling Heating Coefficient of the power input Coefficient of the power input Capacity range Capacity range Rated point Cooling capacity [kw] Heating capacity [kw] Rated point Cooling Outdoor temperature [ C DB] Indoor TC SHC CPI TC SHC CPI TC SHC CPI TC SHC CPI TC SHC CPI Symbols AFR: Air flow rate [m³/min] BF: Bypass factor EWB: Entering wet bulb temperature ( C WB) EDB: Entering dry bulb temperature ( C DB) TC: Maximum total cooling/heating capacity [kw] SHC: Sensible heat capacity [kw] CPI: Coefficient of the power input PI: Power input [kw] compressor + indoor and outdoor fan motors Heating Outdoor temperature [ C WB] Indoor 6 WB DB kw kw kw kw kw kw kw kw kw kw 6,0 22 4,0 9,54,00, 9,0,0,0 9,2, 2, 8,78, 9,80 6,95 0,9 8,0 25 4, 9,,00 4, 9,2,0, 9,09,2, 8,8,2 0,27 6,97 0,92 9,0 27 5,00 9,52,0 4, 9,4, 4,00 9,06,2, 8,87,2 0, 6,99 0,92 9,5 27 5,2 9,52,0 4,68 9,26,2 4,5 9,08,2,64 8,8,2 0,58 6,96 0,92 22,0 0 6,00 9,9,0 5,47 9,4,2 4,90 8,95,2 4,8 8,74,, 6,88 0,9 24,0 2 6, 9,,02 6,0 9,09, 5, 8,8,24 4,97 8,6,4,66 6,79 0,94. The ratings shown are net capacities which include a deduction for indoor fan motor heat. 2. = Maximum at standard conditions =Rated capacity and rated coefficient of the power input The maximum capacity is not guaranteed except at standard conditions.. SHC is based on indoor units EWB & EDB. SHC for other dry bulb temperatures = SHC + SHC* SHC* = SHC correction for other dry bulb temperatures =0.02 x AFR (m³/min) x ( BF) x (DB* EDB) 4. The capacities are based on the following conditions: Outdoor air: 85% RH However, the outdoor ambient condition of the rated capacity during heating operation is 7 C DB / 6 C WB. Corresponding refrigerant piping length: 5.0 m Level difference: 0m 5. CPI is a percentage value compared to the rated value which is The error rate for this value is less than 5% and depends on the indoor unit type. 7. The heating performance takes into account the drop that occurs during defrost operation. 8. The air flow rate and bypass factor are mentioned in the table. 9. The rated power input for each model is mentioned in the table below. Pair AFR (BF) Twin AFR (BF) Triple AFR (BF) Pair FCQHG25F FCQG25F FBQ25C FHQG25C FDQ25C FVQ25C FHQ25CA FUQ25C FBQ25D FCQHG25F FCQG25F FBQ25C FHQG25C FDQ25C FVQ25C FHQ25CA FUQ25C FBQ25D Cooling,00,22,5,58,,74,58,44,6 (0.9) (0.2) (0.6) (0.4) (0.6) (0.6) (0.4) (0.9) (0.06) Heating,07,72,5,48,5,65,48,86,46 Twin FCQGF X 2 FBQC X 2 FHQCA X 2 FFQC X 2 FDXSF X 2 FBQD X 2 FNQA X 2 FCQGF X 2 FBQC X 2 FHQCA X 2 FFQC X 2 FDXSF X 2 FBQD X 2 FNQA X 2.6 x 2 8 x x x 2 6 x 2 8 x 2 6 x 2 Cooling,4,28,67,6,75 4,0,75 (0.2 x 2) (0.5 x 2) (0. x 2) (0. x 2) (0.2 x 2) (0.8 x 2) (0.2 x 2) Heating,64,74 4, 4,0 4,,85 4, Triple FCQGF X FBQC X FHQCA X FFQC X FDXSF9 X FBQD X FNQA X FCQGF X FBQC X FHQCA X FFQC X FDXSF9 X FBQD X FNQA X 2.6 x 6 x 5 x 2 x 6 x 5 x 6 x Cooling,7,28,66,2,45,97,45 (0.22 x ) (0.6 x ) (0.8 x ) (0.6 x ) (0. x ) (0. x ) (0. x ) Heating,66,74 4,0,55,6,8,6 Double twin Double twin FCQG5F X 4 FBQ5C X 4 FHQ5CA X 4 FFQ5C X 4 FDXS5F X 4 FBQ5D X 4 FNQ5A X 4 FCQG5F X 4 FBQ5C X 4 FHQ5CA X 4 FFQ5C X 4 FDXS5F X 4 FBQ5D X 4 FNQ5A X 4 AFR 2.5 x 4 6 x4 4 x 4 0 x x 4 5 x x 4 Cooling,2,28,64,0,94,74,94 (BF) (0.4 x 4) (0.5 x 4) (0.7 x 4) (0.25 x 4) (0.7 x 4) (0.08 x 4) (0.7 x 4) Heating,72,74 4,00,0 4,45,78 4,45 D0767F RZQGL9V RZQGLY Cooling Heating Coefficient of the power input Cooling Capacity range Cooling capacity [kw] Rated point Coefficient of the power input Capacity range Heating capacity [kw] Rated point Symbols AFR: Air flow rate [m³/min] BF: Bypass factor EWB: Entering wet bulb temperature ( C WB) EDB: Entering dry bulb temperature ( C DB) TC: Maximum total cooling/heating capacity [kw] SHC: Sensible heat capacity [kw] CPI: Coefficient of the power input PI: Power input [kw] compressor + indoor and outdoor fan motors Heating Indoor Outdoor temperature [ C DB] SHC SHC CPI TC SHC SHC SHC TC CPI TC CPI TC CPI TC CPI Indoor Outdoor temperature [ C WB] WB DB kw kw kw kw kw kw kw kw kw kw 6,0 22 5, 0,47 0,98 4,9 0,25,08 4,44 0,0,8,86 9,69,28,27 8,02 0,92 8,0 25 6,7 0,55 0,98 5,62 0,2,09 5, 0,0,9 4,52 9,7,0,76 7,95 0,9 9,0 27 6,56 0,4 0,99 5,96 0,8,09 5, 9,98,9 4,8 9,76,0 2,00 8,0 0,9 9,5 27 6,74 0,49 0,99 6,4 0,6,0 5,57 0,00,9 4,98 9,66,0 2,6 7,9 0,9 22,0 0 7,6 0,7 0,99 7,0 0,6,0 6,6 9,8,2 5,76 9,, 2,8 7,9 0,94 24,0 2 8,8 0,,00 7,72 0,00, 7,04 9,67,22 6,4 9,47,2,0 7,74 0,95. The ratings shown are net capacities which include a deduction for indoor fan motor heat. 2. = Maximum at standard conditions =Rated capacity and rated coefficient of the power input The maximum capacity is not guaranteed except at standard conditions.. SHC is based on indoor units EWB & EDB. SHC for other dry bulb temperatures = SHC + SHC* SHC* = SHC correction for other dry bulb temperatures =0.02 x AFR (m³/min) x ( BF) x (DB* EDB) 4. The capacities are based on the following conditions: Outdoor air: 85% RH However, the outdoor ambient condition of the rated capacity during heating operation is 7 C DB / 6 C WB. Corresponding refrigerant piping length: 5.0 m Level difference: 0m 5. CPI is a percentage value compared to the rated value which is The error rate for this value is less than 5% and depends on the indoor unit type. 7. The heating performance takes into account the drop that occurs during defrost operation. 8. The air flow rate and bypass factor are mentioned in the table. 9. The rated power input for each model is mentioned in the table below. Pair AFR (BF) Twin AFR (BF) Triple AFR (BF) Pair FCQHGF FCQGF FBQC FHQGC FVQC FHQCA FBQD FCQHGF FCQGF FBQC FHQGC FVQC FHQCA FBQD.5.0 9:C/4:H Cooling 4,00 4,7 4,02 4,05 4,7 4,05 4,00 (0.5) (0.2) (0.4) (0.7) (0.8) (0.7) (0.06) Heating,77 4,0 4,0 4,27 4,0 4,27 4, Twin FCQHG7F X 2 FCQG7F X 2 FBQ7C X 2 FHQG7C X 2 FAQ7C X 2 FHQ7CA X 2 FUQ7C X 2 FBQ7D X 2 FCQHG7F X 2 FCQG7F X 2 FBQ7C X 2 FHQG7C X 2 FAQ7C X 2 FHQ7CA X 2 FUQ7C X 2 FBQ7D X x x x 2.5 x x 2.5 x x x 2 Cooling,94 4,,75,59,8,59,5,75 (0.2 x2) (0.4 x 2) (0.08 x 2) (0. x 2) (0.6 x 2) (0. x 2) (0.24 x2 ) (0. x2 ) Heating,7 4,24 4, 4,47 4,68 4,47 4,6 4, Triple FCQGF X FBQC X FHQCA X FFQC X FDXSF9 X FBQD X FNQA X FCQGF X FBQC X FHQCA X FFQC X FDXSF9 X FBQD X FNQA X 2.6 x 6 x 5 x 2 x 6 x 5 x 6 x Cooling 4,2,75 4,25 4,5 4,26,75 4,26 (0.22 x ) (0.6 x ) (0.8 x ) (0.6 x ) (0. x ) (0. x ) (0. x ) Heating 4,24 4, 5,4 4,5 4,7 4, 4,7 Double twin Double twin FCQG5F X 4 FBQ5C X 4 FHQ5CA X 4 FFQ5C X 4 FDXS5F X 4 FBQ5D X 4 FNQ5A X 4 FCQG5F X 4 FBQ5C X 4 FHQ5CA X 4 FFQ5C X 4 FDXS5F X 4 FBQ5D X 4 FNQ5A X 4 AFR 2.5 x 4 6 x4 4 x 4 0 x x 4 5 x x 4 Cooling 4,8,75 4,2,8 5,8,75 5,8 (BF) (0.4 x 4) (0.5 x 4) (0. x 4) (0.25 x 4) (0.7 x 4) (0.08 x 4) (0.7 x 4) Heating 4,0 4, 5,,8 5,85 4, 5,85 D07675F Split - Sky Air RZQG-L9V 5

18 6 Capacity tables 6-2 Capacity Correction Factor 6 6 Split - Sky Air RZQG-L9V

19 7 Dimensional drawings 7 - Dimensional Drawings 7 Split - Sky Air RZQG-L9V 7

20 8 Centre of gravity 8 - Centre of Gravity RZQG7L9V D Split - Sky Air RZQG-L9V

21 8 Centre of gravity 8 - Centre of Gravity RZQG00-L9V D Split - Sky Air RZQG-L9V 9

22 9 Piping diagrams 9 - Piping Diagrams 9 Split - Sky Air RZQG-L9V

23 9 Piping diagrams 9-2 Piping Diagram Twin Application 9 Split - Sky Air RZQG-L9V 2

24 9 Piping diagrams 9 - Piping Diagram Triple Application 9 22 Split - Sky Air RZQG-L9V

25 9 Piping diagrams 9-4 Piping Diagram Double Twin Application 9 Split - Sky Air RZQG-L9V 2

26 0 Wiring diagrams 0 - Wiring Diagrams - Single Phase RZQG7L9V 0 H2P H4P H6P A2P HP HP H5P H7P N Hz ON DS 2-2V Z6 X5A C 2 XM OFF N N= Z2 2 BS BS2 BS BS4 GRN/YLW XM L L N C Z Z N= QDI C YE M C RT R2T RT R4T R5T R6T N= N= t t t t t t RED BLU LA NA X80A XA X2A XA X2A X5A F2U K4R FU K2R X28A GRN E ZF R4 KR R5 PS C2 TC VD Z2F K5R R6 X6A +t R7T K0R X804A X805A KM C RC LR V2R X806A SEE WHT HR + - NOTE 7 HAP Z5 BRNHR VT KR R8T X25A X77A C V2T YS X2A XA N= +t PPLHR4 V2D 6 + C REDHR2 VD F6U R2 P> P< + - SPH SPL VR AP U V W X06A Z4 C A2P N= RED WHT BLU MF MS HAP X2A 4 LR U V W AP MC MS ~ XM U V W ZF BLK WHT RED 2D089497B RZQG00-L9V N L N Hz 2-2V QDI GRN AP LR VD E GRN A2P L2R V2D E2 Z6 C N= XML N Z C N= 2 RED BLU LA NA F2U FU ZF GRN/YLW F4U ZF X80A C K5R R Z4F C2 Z2F FU LB NB X98A E Z RED BLU GRN C N= 2 LC NC X99A KM V2R LR VD K0R R Z6F Z5F + C VT V2T VT + - R2 F6U VR U V W Z4 C N= RED WHT BLU X2A 6 U V W MC MS ~ X804A MF MS BLK BLU RED KR X805A X806A X06A 2 XM Z2 C N= 2 V V4D R5 M2F MS U W K4R TC PS X07A R4 HAP RC X802A Z5 C N= X80A H2P H4P H6P HP HP H5P H7P BS BS2 BS BS4 ON DS OFF 2 R7T t XA RT t XA R2T t X6A KR YS RT t X2A X25A R4T t R5T t R6T t K4R XA SEE NOTE 7 X77A X28A XA X2A X2A 6 HAP AP SEE NOTE 7 SPL P< SPH P> YE M XM A2P 2D088865C 24 Split - Sky Air RZQG-L9V

27 Sound data - Sound Pressure Spectrum - Cooling NR75 65 NR NR65 55 NR Sound pressure level [db] NR55 NR NR45 NR NR NR0 5 NR0 NR5 NR0 NR5 NR NR dba Octave band centre frequency [Hz] 0 NR75 65 NR NR65 55 NR Sound pressure level [db] NR55 NR NR45 NR NR NR0 5 NR0 NR5 NR0 NR5 NR NR dba Octave band centre frequency [Hz] 0 Split - Sky Air RZQG-L9V 25

28 Sound data - Sound Pressure Spectrum - Cooling NR75 65 NR NR65 55 NR Sound pressure level [db] NR55 NR NR45 NR NR NR0 5 NR0 NR5 NR0 NR5 NR NR dba Octave band centre frequency [Hz] 0 NR75 65 NR NR65 55 NR Sound pressure level [db] NR55 NR NR45 NR NR NR0 5 NR0 NR5 NR0 NR5 NR NR dba Octave band centre frequency [Hz] 0 26 Split - Sky Air RZQG-L9V

29 Sound data - 2 Sound Pressure Spectrum - Heating NR75 65 NR NR65 55 NR Sound pressure level [db] NR55 NR NR45 NR NR NR0 5 NR0 NR5 NR0 NR5 NR NR dba Octave band centre frequency [Hz] 0 NR75 65 NR NR65 55 NR Sound pressure level [db] NR55 NR NR45 NR NR NR0 5 NR0 NR5 NR0 NR5 NR NR dba Octave band centre frequency [Hz] 0 Split - Sky Air RZQG-L9V 27

30 Sound data - 2 Sound Pressure Spectrum - Heating NR75 65 NR NR65 55 NR Sound pressure level [db] NR55 NR NR45 NR NR NR0 5 NR0 NR5 NR0 NR5 NR NR dba Octave band centre frequency [Hz] 0 NR75 65 NR NR65 55 NR Sound pressure level [db] NR55 NR NR45 NR NR NR0 5 NR0 NR5 NR0 NR5 NR NR dba Octave band centre frequency [Hz] 0 28 Split - Sky Air RZQG-L9V

31 Sound data - Sound Pressure Spectrum Quiet Mode NR75 65 NR NR65 55 NR Sound pressure level [db] NR55 NR NR45 NR NR NR0 5 NR0 NR5 NR0 NR5 NR NR dba Octave band centre frequency [Hz] 0 NR75 65 NR NR65 55 NR Sound pressure level [db] NR55 NR NR45 NR NR NR0 5 NR0 NR5 NR0 NR5 NR NR dba Octave band centre frequency [Hz] 0 Split - Sky Air RZQG-L9V 29

32 Sound data - Sound Pressure Spectrum Quiet Mode NR75 65 NR NR65 55 NR Sound pressure level [db] NR55 NR NR45 NR NR NR0 5 NR0 NR5 NR0 NR5 NR NR dba Octave band centre frequency [Hz] 0 NR75 65 NR NR65 55 NR Sound pressure level [db] NR55 NR NR45 NR NR NR0 5 NR0 NR5 NR0 NR5 NR NR dba Octave band centre frequency [Hz] 0 0 Split - Sky Air RZQG-L9V

33 2 Installation 2 - Installation Method 2 Split - Sky Air RZQG-L9V

34 2 Installation 2 - Installation Method 2 2 Split - Sky Air RZQG-L9V

35 Operation range - Operation Range Split - Sky Air RZQG-L9V

36

37 Daikin Europe N.V. Naamloze Vennootschap - Zandvoordestraat 00, B-80 Oostende - Belgium BE RPR Oostende EEDEN XXX-06/6 Daikin Europe N.V. participates in the Eurovent Certification programme for Liquid Chilling Packages (LCP), Air handling units (AHU), Fan coil units (FCU) and variable refrigerant flow systems (VRF) Check ongoing validity of certificate online: or using: The present leaflet is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this leaflet to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this leaflet. All content is copyrighted by Daikin Europe N.V.