1 Steven Winter Associates, Inc. 293 Route 18 South Telephone (866) Building System Consultants East Brunswick, NJ Web: May 5, 2010 Local Government Energy Program Energy Audit Report Township of Parsippany Troy Hills Community Center and Tennis Club 1130 Knoll Road Parsippany, NJ Project Number: LGEA26 Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 1/47

2 TABLE OF CONTENTS INTRODUCTION...3 EXECUTIVE SUMMARY HISTORIC ENERGY CONSUMPTION ENERGY USAGE, LOAD PROFILES AND COST ANALYSIS UTILITY RATE ANALYSIS ENERGY BENCHMARKING FACILITY AND SYSTEMS DESCRIPTION BUILDING CHARACTERISTICS BUILDING OCCUPANCY PROFILES BUILDING ENVELOPE EXTERIOR WALLS ROOF BASE WINDOWS EXTERIOR DOORS BUILDING AIR TIGHTNESS HVAC SYSTEMS HEATING COOLING VENTILATION DOMESTIC HOT WATER ELECTRICAL SYSTEMS LIGHTING APPLIANCES ELEVATORS PROCESS AND OTHERS ELECTRICAL SYSTEMS EQUIPMENT LIST ENERGY CONSERVATION MEASURES...24 CATEGORY I RECOMMENDATIONS: CAPITAL IMPROVEMENTS...24 CATEGORY II RECOMMENDATIONS: OPERATIONS AND MAINTENANCE...24 CATEGORY III RECOMMENDATIONS: ENERGY CONSERVATION MEASURES RENEWABLE AND DISTRIBUTED ENERGY MEASURES EXISTING SYSTEMS WIND SOLAR PHOTOVOLTAIC SOLAR THERMAL COLLECTORS COMBINED HEAT AND POWER GEOTHERMAL ENERGY PURCHASING AND PROCUREMENT STRATEGIES ENERGY PURCHASING ENERGY PROCUREMENT STRATEGIES METHOD OF ANALYSIS ASSUMPTIONS AND TOOLS DISCLAIMER...38 APPENDIX A: LIGHTING STUDY...39 APPENDIX B: THIRD PARTY ENERGY SUPPLIERS (ESCOS)...42 APPENDIX C: GLOSSARY AND METHOD OF CALCULATIONS...44 Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 2/47

3 INTRODUCTION As an approved energy consulting firm under the Local Government Energy Audit Program (LGEA), Steven Winter Associates, Inc. (SWA) was selected to perform an energy audit and assessment for the Township of Parsippany Troy Hills buildings. The audit included a review of the Parsippany Troy Hills Town Hall, Public Library, Community Center and Tennis Club, Police Headquarters, Parks Forestry and Recreation building, as well as the Water Utilities Office, DPW building, Park Road Booster Station building, Well 21 building, and Sewer Pump station # 4 building. The buildings are located in Parsippany and Lake Hiawatha, NJ. A separate energy audit report is issued for each of the referenced buildings. This report addresses the Parsippany Troy Hills Community Center and Tennis Club located at 1130 Knoll Road, Parsippany, NJ. The current conditions and energy-related information were collected in order to analyze and suggest the implementation of building improvements and energy conservation measures. The Parsippany Troy Hills Community Center and Tennis Club located at 1130 Knoll Road was opened in 1979, when work was completed as a new construction however, at the time of its original construction the facility consisted of both tennis and racquetball courts and no community center. The community center was opened in 1991, when it replaced the previously existing racquetball courts. Combined the facility now consists of 34,000 square feet of conditioned space. The tennis club center encompasses 4 tennis courts, a clubhouse and separate locker rooms for men and women. The community center is home to a theatre, auditoriums, various meeting rooms many of which are used for table tennis, a used book store, cafeteria, senior center, gymnasium and rehab center, recreation gaming area, EMS storage and ready room as well as numerous municipal offices. The community center is open to the public from 9:00 AM to 5:00 PM, Monday through Friday and the Tennis Club is open seven days a week from 7:30 AM 9:30 PM. While the community center is a two floor flat roof building, the tennis club is a single floor pitched roof building. The goal of this Local Government Energy Audit (LGEA) is to provide sufficient information to the Township of Parsippany Troy Hills to make decisions regarding the implementation of the most appropriate and most cost effective energy conservation measures for the building. Launched in 2008, the LGEA Program provides subsidized energy audits for municipal and local government-owned facilities, including offices, courtrooms, town halls, police and fire stations, sanitation buildings, transportation structures, schools and community centers. The Program will subsidize 75% of the cost of the audit. If the net cost of the installed measures recommended by the audit, after applying eligible NJ SmartStart Buildings incentives, exceeds the remaining cost of the audit, then that additional 25% will also be paid by the program. The Board of Public Utilities (BPU s) Office of Clean Energy has assigned TRC Energy Services to administer the Program. Section 1 and section 2 of the report cover a description and analysis of the building existing conditions. Section 3 provides a detail inventory of major electrical and mechanical systems in the building. Sections 4 through 5 provide a description of our recommendations. Appendices include further details and information supporting our recommendations. Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 3/47

4 EXECUTIVE SUMMARY The Parsippany Troy Hills Community Center and Tennis Club located at 1130 Knoll Road was opened in 1979, when work was completed as a new construction however, at the time of its original construction the facility consisted of both tennis and racquetball courts and no community center. The community center was opened in 1991, when it replaced the previously existing racquetball courts. Combined the facility now consists of 34,000 square feet of conditioned space. The tennis club center encompasses 4 tennis courts, a clubhouse and separate locker rooms for men and women. The community center is home to a theatre, auditoriums, various meeting rooms many of which are used for table tennis, a used book store, cafeteria, senior center, gymnasium and rehab center, recreation gaming area and numerous municipal offices. The community center is open to the public from 9:00 AM to 5:00 PM, Monday through Friday and the Tennis Club is open seven days a week from 7:30 AM 9:30 PM. While the community center is a two floor flat roof building, the tennis club is a single floor pitched roof building. Based on the field visit performed by the SWA staff on October 22 nd and 23 rd, 2009 and the results of a comprehensive energy analysis, this report describes the site s current conditions and recommendations for improvements. Suggestions for measures related to energy conservation and improved comfort are provided in the scope of work. Energy and resource savings are estimated for each measure that results in a reduction of heating, cooling, and electric usage. Existing conditions From July 2008 through June 2009, the period of analysis for this audit, the building consumed 554,118 kwh or $97,574 worth of electricity at an approximate rate of $0.176/kWh and 11,243 therms or $14,837 worth of natural gas at an approximate rate of $1.320/therm. The joint energy consumption for the building, including both electricity and fossil fuel, was 3,019 MMBtus of energy that cost a total of $112,411. SWA has entered energy information about the community center in the U.S. Environmental Protection Agency s (EPA) Energy Star Portfolio Manager Energy benchmarking system. Currently, the building is not eligible to receive a performance rating due to the floor area and building usage. SWA encourages the Township of Parsippany - Troy Hills to continue entering utility data in Energy Star Portfolio Manager in order to track weather normalized source energy use over time. The Site Energy Use Intensity is 88.7 kbtu/sq ft yr compared to the national average of a public assembly building consuming 66.0 kbtu/sq ft yr. Implementing this report s highly recommended Energy Conservations Measures (ECMs) will reduce use by approximately 15.6 kbtu/sqft yr, with an additional 0.7 kbtu/sq ft yr from the recommended End of Life Cycle (>10 year payback) ECMs. Implementing this report s recommendations will reduce use by approximately 16.3 kbtu/ft 2 yr, which would decrease the building's energy use intensity to 72.4 kbtu/ft 2 yr. Recommendations The HVAC system of the Community and Tennis Center was observed in good condition; however the system appears to be unbalanced and could benefit from having an HVAC performing testing and balancing work. SWA recommends a package of measures that updates lighting fixtures as well as introduces a Solar photovoltaic system and also recommends having the HVAC system properly balanced. The building has been reasonably well-maintained with old equipment being replaced as it begins to lose efficiency. Based on the assessment of the building, SWA has separated the recommendations into three categories (See Section 4 for more details). These are summarized as follows: Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 4/47

5 Category I Recommendations: Capital Improvement Measures Upgrade rooftop packaged units with high efficiency units (as they fail) Replace kitchen equipment with Energy Star appliances Category II Recommendations: Operations and Maintenance Program all computers for power save mode Perform bi-annual inspections of roofs Perform bi-annual inspections of exterior wall surfaces Provide weather stripping / air sealing Provide water efficient fixtures and controls Use Energy Star labeled appliances Category III Recommendations: Energy Conservation Measures At this time, SWA highly recommends a total of 5 Energy Conservation Measures (ECMs) for the Community Center and Tennis Club that is summarized in the following Table 1. The total investment cost for these ECMs with incentives is $231,343. SWA estimates a first year savings of $58,262 with a simple payback of 3.3 years. SWA also recommends 2 ECMs with a payback of greater than 10 years.. The implementation of all the recommended ECMs would reduce the building electric usage by 134,302 kwh annually, or 24% of the building s current electric consumption. The implementation of all the recommended ECMs would also reduce the building natural gas usage by 964 therms annually, or 9% of the building s current natural gas consumption. SWA estimates that implementing these ECMs will reduce the carbon footprint of the Community Center and Tennis Club by 251,094 lbs of CO 2, which is equivalent to removing approximately 18 cars from the roads each year or avoiding the need of 605 trees to absorb the annual CO 2 produced. SWA also recommends that Township of Parsippany - Troy Hills contacts third party energy suppliers in order to negotiate a lower electricity rate. Comparing the current electric rate to average utility rates of similar type buildings in New Jersey, it may be possible to save up to $0.026/kWh, which would have equated to $14,407 for the past 12 months. There are various incentives that Township of Parsippany - Troy Hills could apply for that could also help lower the cost of installing the ECMs. SWA recommends that the Township of Parsippany - Troy Hills apply for the NJ SmartStart program through the New Jersey Office of Clean Energy. This incentive can help provide technical assistance for the building in the implementation phase of any energy conservation project. A new NJ Clean Power program, Direct Install, to be rolled out soon, could also assist to cover 80% of the capital investment. Renewable ECMs require application approval and negotiations with the utility and proof of performance. There is also a utility-sponsored loan program through JCP&L that would allow the building to pay for the installation of the PV system through a loan issued by JCP&L. The following two tables summarize the proposed Energy Conservation Measures (ECM) and their economic relevance. Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 5/47

6 Table 1 - Highly Recommended 0-5 Year Payback ECMs ECM # ECM description Source est. installed cost, $ est. incentives, $ net est. ECM cost with incentives, $ kwh, 1st yr savings kw, demand reduction/mo therms, 1st yr savings kbtu/sq ft, 1st yr savings est. operating cost, 1st yr savings, $ total 1st yr savings, $ life of measure, yrs est. lifetime cost savings, $ simple payback, yrs lifetime return on investment, % annual return on investment, % internal rate of return, % net present value, $ reduced, lbs/yr CO 2 1 Install 7 new CFL lamps RS Means , , ,197 2 Install 353 T8 fluorescent fixtures RS Means 78,808 10,590 68,218 81, ,558 27, , , ,633 3 Install 23 new Occupancy Sensors RS Means 5, ,600 7, , , ,947 12,576 4 Install 30kW roof-mounted Solar PV array Similar Project 140,000 30, ,000 35, , , ,256 63,405 5 HVAC testing and balancing RS Means 7, ,000 1, , , ,503 13,949 TOTALS 231,343 41, , , ,565 58, , , ,761 Assumptions: Discount Rate: 3.2% per DOE FEMP; Energy Price Escalation Rate: 0% per DOE FEMP Guidelines Note: A 0.0 electrical demand reduction / month indicates that it is very low / negligible Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 6/47

7 Table 2 - Recommended End of Life Cycle ECMs ECM # 6 7 ECM description Source est. installed cost, $ est. incentives, $ net est. ECM cost with incentives, $ kwh, 1st yr savings kw, demand reduction/mo therms, 1st yr savings Install 52 new LED exit signs RSMeans 10,573 1,040 9,533 3, , ,443 6,611 Install 14 new Pulse Start Metal Halide fixtures RSMeans 11, ,731 3, , ,759 5,722 TOTALS 21,654 1,390 20,264 6, ,610-18, ,316 12,333 kbtu/sq ft, 1st yr savings est. operating cost, 1st yr savings, $ total 1st yr savings, $ life of measure, yrs est. lifetime cost savings, $ simple payback, yrs lifetime return on investment, % annual return on investment, % internal rate of return, % net present value, $ reduced, lbs/yr CO 2 Note: For more details on End of Life Cycle ECMs and associated incremental cost for high efficiency equipment and performance see Section 4. Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 7/47

8 1. HISTORIC ENERGY CONSUMPTION 1.1. Energy usage, load profiles and cost analysis SWA analyzed utility bills from July 2008 through June 2009 (period of analysis) that were received from the utility companies supplying the community center with electric and natural gas. Electricity The Community center and tennis club buys electricity from JCP&L at an average rate of $0.176/kWh based on 12 months of utility bills from July 2008 to June The community center and tennis club purchased approximately 554,118 kwh or $97,574 worth of electricity in the previous year. The Community center and tennis club is currently charged for demand (kw) which has been factored into each monthly bill. The building had an average monthly demand of kw and an annual peak demand of kw. Natural gas - The Community center and tennis club is currently served by one meter for natural gas. They currently buy natural gas from New Jersey Natural Gas (NJNG) at an average aggregated rate of $1.320/therm based on 12 months of utility bills for July 2008 to June The community center and tennis club purchased approximately 11,243 therms or $14,837 worth of natural gas in the previous year. The following chart shows electricity use versus cost for the office based on utility bills for the 12 month period of July 2008 to June ,000 Community Center- Electric Usage (kwh) vs. Electric Cost ($) 12,000 Electric Usage (kwh) 60,000 50,000 40,000 30,000 20,000 10,000 8,000 6,000 4,000 Electricity Cost ($) 10, ,000 0 Jun-08 Jul-08 Aug-08 Sep-08 Oct-08 Nov-08 Dec-08 Jan-09 Feb-09 Mar-09 Apr-09 May-09 Electricity Usage (kwh) Electricity Cost ($) Date (Month-Year) Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 8/47

9 Electricity does follow the expected trend as usage is peaking in the summer; however, there are small upward trends in the winter which seems to be because of the use of electrically fueled heating equipment. The cost of electricity fluctuates as expected with usage. The following is a chart of the natural gas annual load profile for the building versus natural gas costs, peaking in the coldest months of the year and a chart showing natural gas consumption following the heating degree days curve. Community Center - Natural Gas Usage (therms) vs. Natural Gas Cost ($) 3,500 $4,500 Natural Gas Usage (therms) 3,000 2,500 2,000 1,500 1, Natural Gas Usage (therms) Natural Gas Cost ($) $4,000 $3,500 $3,000 $2,500 $2,000 $1,500 $1,000 $500 $0 Jul-08 Aug-08 Sep-08 Oct-08 Natural Gas Cost ($) Nov-08 Dec-08 Jan-09 Feb-09 Mar-09 Apr-09 May-09 Jun-09 Date (Month-Year) In the above chart, the natural gas use follows a heating trend as expected. During the summer it is clear that the natural gas use is very minimal which reflects that heat is not being used and the domestic hot water (DHW) load is minimal. The following chart shows combined natural gas and electric consumption in Btu/sq ft for the community center and tennis club based on utility bills for the 12 month period of July 2008 to June Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 9/47

10 Energy Use Intensity (Btu/Sq. Ft.) 14,000 12,000 10,000 8,000 6,000 4,000 2,000 0 Community Center - Energy Use Intensity (Btu/Sq. Ft.) Jul-08 Aug-08 Sep-08 Oct-08 Nov-08 Dec-08 Jan-09 Feb-09 Mar-09 Apr-09 May-09 Date (Month-Year) Jun-09 The following table and chart pies show energy use for the Community Center and Tennis Club based on utility bills for the 12 month period of July 2008 to June Note electrical cost at $52/MMBtu of energy is more than 3 times as expensive to use as natural gas at $13/MMBtu. Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 10/47

11 1.2. Utility rate analysis The community center and tennis club currently purchases electricity from JCP&L at a general service market rate for electricity use (kwh) including a separate (kw) demand charge that is factored into each monthly bill. The community center and tennis club currently pays an average rate of approximately $0.176/kWh based on the 12 months of utility bills of July 2008 to June Demand prices are reflected in the utility bills and can be verified by observing the price fluctuations throughout the year. The electric rate does not show large fluctuations throughout the year except for an anticipated rise in the summer time. Based on these observations this appears to be the appropriate rate for the building. Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 11/47

12 Community Center - Electricity Usage (kwh) vs. Electricty Rate ($/kwh) 70,000 $0.250 Electric Usage (kwh) 60,000 50,000 40,000 30,000 20,000 10,000 Electricity Usage (kwh) $0.200 $0.150 $0.100 $0.050 Electricity Rate ($/kwh) 0 $0.000 Jun-08 Jul-08 Aug-08 Sep-08 Oct-08 Nov-08 Dec-08 Jan-09 Feb-09 Mar-09 Apr-09 May-09 Electricity Rate ($/kwh) Date (Month-Year) The community center and tennis club currently purchases natural gas supply from the NJNG at a general service market rate for natural gas (therms). There is one gas meter that provides natural gas service to The community center and tennis club currently. The average aggregated rate (supply and transport) for the meter is approximately $1.320/therm based on 12 months of utility bills for July 2008 to June The suppliers general service rate for natural gas charges a market-rate price based on use and the community center and tennis club billing does not breakdown demand costs for all periods. Demand prices are reflected in the utility bills and can be verified by observing the price fluctuations throughout the year. Typically, the natural gas prices increase during the heating months when natural gas is used by the hot water boilers. The high gas price per therm fluctuations in the summer may be due to low use caps for the non-heating months. Thus the building pays for fixed costs such as meter reading charges during the summer months. Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 12/47

13 3,500 Community Center - Natural Gas Usage (therms) v. Natural Gas Rate ($/Therm) $ ,000 $3.000 Natural Gas Usage (therms) 2,500 2,000 1,500 1, Natural Gas Usage (therms) Natural Gas Rate ($/Therms) $2.500 $2.000 $1.500 $1.000 $0.500 $0.000 Jul-08 Aug-08 Sep-08 Oct-08 Nov-08 Natural Gas Cost ($) Dec-08 Jan-09 Feb-09 Mar-09 Apr-09 May-09 Jun-09 Date (Month-Year) 1.3. Energy benchmarking SWA has entered energy information about the community center in the U.S. Environmental Protection Agency s (EPA) Energy Star Portfolio Manager Energy benchmarking system. Currently, the building is not eligible to receive a performance rating due to the floor area and building usage. SWA encourages the Township of Parsippany - Troy Hills to continue entering utility data in Energy Star Portfolio Manager in order to track weather normalized source energy use over time. The Site Energy Use Intensity is 88.7 kbtu/sq ft yr compared to the national average of a public assembly building consuming 66.0 kbtu/sq ft yr. Implementing this report s highly recommended Energy Conservations Measures (ECMs) will reduce use by approximately 15.6 kbtu/sqft yr, with an additional 0.7 kbtu/sq ft yr from the recommended End of Life Cycle (>10 year payback) ECMs. Per the LGEA program requirements, SWA has assisted Parsippany-Troy Hills to create an Energy Star Portfolio Manager account and has shared the Firehouse building facility information to allow future data to be added and tracked using the benchmarking tool. SWA is sharing this Portfolio Manager Site information with TRC Energy Services. As per requirements, the account information is provided below: Username: ParsippanyTroyHillsTownship Password: PARSIPPANY Also, below is a statement of energy performance generated based on historical energy consumption from the Portfolio Manager Benchmarking tool. Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 13/47

14 Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 14/47

15 2. FACILITY AND SYSTEMS DESCRIPTION 2.1. Building Characteristics The Parsippany Troy Hills Community Center and Tennis Club located at 1130 Knoll Road was opened in 1979, when work was completed as a new construction however, at the time of its original construction the facility consisted of both tennis and racquetball courts and no community center. The community center was opened in 1991, when it replaced the previously existing racquetball courts. Combined the facility now consists of 34,000 square feet of conditioned space. The tennis club center encompasses 4 tennis courts, a clubhouse and separate locker rooms for men and women. The community center is home to a theatre, auditoriums, various meeting rooms many of which are used for table tennis, a used book store, cafeteria, senior center, gymnasium and rehab center, recreation gaming area and numerous municipal offices. The community center is open to the public from 9:00 AM to 5:00 PM, Monday through Friday and the Tennis Club is open seven days a week from 7:30 AM 9:30 PM. While the community center is a two floor flat roof building, the tennis club is a single floor pitched roof building Building occupancy profiles The typical occupancy for the tennis center is for 2 full time employees and a varying amount of patrons, it is open seven days a week from 7:30 AM 9:30 PM. Between the various offices, senior center and other parts of the community center there are approximately 16 full time employees in the community center which is open Monday through Friday 9:00 AM to 5:00 PM with occasional usage at night for theatre use, senior programs or public meetings. Both portions of the building are subject to large changes in the occupancy rate and are rarely at maximum capacity Building envelope Exterior Walls The typical exterior wall for the community center portion of the building is constructed of a gray 6 precast concrete panel at the exterior with a 3-5/8 18 ga. metal stud wall with a 10 layer of rigid foam insulation to its interior and a 5/8 layer of gypsum board to at the interior. The typical exterior wall for the tennis court is constructed of aluminum siding panels at the exterior with a 3-5/8 18 ga. metal stud wall with a 10 layer of rigid foam insulation to its interior and a 5/8 layer of gypsum board to at the interior. At the clubhouse section of the tennis court the typical exterior wall is composed of a 4 layer of brick masonry units at its exterior with a layer of 8 concrete masonry units at its interior along with a 1.5 layer of rigid insulation and 5/8 layer of gypsum board. Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 15/47

16 Existing Exterior Walls Overall, exterior and interior wall finishes of the envelope were found to be in age-appropriate, good condition with no major signs of water or air leakage. There were some isolated instances of damaged siding, and damaged brick masonry units that need to be addressed. Additionally there were numerous instances of plant overgrowths and insect infestation that should be removed and continuously monitored by the buildings maintenance staff.. SWA also recommends biannual maintenance inspections to inspect the exterior walls with a focus on cracks, water damage, damaged bricks and missing siding Roof Exterior wall plant overgrowths and insect infestations There are two different roofing systems for the entire facility. Above the community center portion is flat membrane roof that is slight sloped for drainage purposes. It consists of a 3 ply built-up roofing membrane above a 2 layer of rigid board insulation and 1.5 later of metal decking with an open web metal roof joist to its interior, additionally the flat roof is covered with a ¼ rock bed layer. Additionally, there is a 6 layer of BATT insulation in the upper level ceiling. Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 16/47

17 Existing Built-up Roof Above the tennis court is a layer of aluminum roof siding at the exterior of a metal roof truss system. While most of the roof is in age-appropriate, good condition there are sections that were recently repaired or patched and some areas of aluminum roofing with an air gap. There are no improvements to the roof assembly as a whole or insulation that would provide a significant improvement to the building performance. SWA does recommend biannual maintenance inspections with a focus on the drainage, penetrations, flashing and seams of the roof. Example of the Pitched Roof Above the Tennis Courts Example of the Pitched Roof Air Gap Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 17/47

18 Base The building s base is a 5 reinforced poured concrete slab-on-grade and compact granular backfill layer and 8 mil polyethylene vapor barrier. The foundation wall is constructed of 8 concrete masonry units. The benefits of installing slab perimeter insulation would not justify the expense and disruption of excavating around the entire building. If excavation is ever required for other reasons, consideration should be given to installing a minimum of 2 inches of rigid foam board insulation Windows The existing windows of the community center are fixed casement, sidelight and transom units with that are double paned with an air gap. Additionally, there are also a few aluminum frame domed skylights with roof penetrations installed in the community center portion of the building. These installations appear to be in good age appropriate condition with no apparent damage to the frames, water damage to the surround roof and ceiling area or damage to the flashing. Installation of new windows would not be economically viable, but as a best practice, SWA recommends that all windows be inspected at least once a year. Any gaps, cracks, or damage to weather-stripping or caulking should be repaired or replaced, as needed, to minimize energy loss around those openings. Most of the windows appear to be in good age-appropriate condition. Typical Window installation Exterior doors There are three different types of exterior doors at the community center and tennis club. Most entrance doors are aluminum frame glass doors with glazing identical to the windows; however, there are also aluminum frame insulated hollow core metal doors, and aluminum frame fiberglass doors. The exterior doors are in excellent condition and virtually all of the weather-stripping is still intact except for a few exit doors and the main tennis club entrance door. If not properly maintained, exterior doors can become major sources of heat loss and infiltration. As a best practice, SWA recommends checking the weather-stripping of each door on a regular basis and replacing any broken seals immediately. This will help optimize comfort and energy performance. Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 18/47

19 Typical Exterior Door Installations Exterior Door With Poor Weather-stripping Building air tightness Based on a visual inspection and communication with the building staff, the building was observed to be well-sealed and air tight which is consistent with the age and intended use of the building. As a best practice, weather-stripping on doors and windows should be checked every 6 months for deficiencies and replaced as they fail HVAC Systems The Community and Tennis Center building is divided into two sections; the Community Center and the Tennis Center. Each section is served entirely by rooftop packaged units that provide gas heating and DX cooling. Each space within the building contains Braeburn non-programmable thermostats. The building is ultimately controlled by a BMS system located at the Parsippany-Troy Hills municipally building to ensure that temperatures are set back at night and modulated correctly with outside temperature. The HVAC system was observed to be operating properly however there is Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 19/47

20 some concern that air is not being distributed properly to all of the spaces. During the audit, it was clear that some areas such as the racquetball courts, storage areas and Senior Center rooms were warmer than other areas and appeared to be stuffy, even though the thermostats were at the same temperatures. The rooftop units used for HVAC have been replaced several times, during renovations or as they age and sizing may have been changed. In addition, with each addition, the distribution system was altered to accommodate for new use of spaces and interior areas may have changed slightly. SWA recommends hiring an HVAC contractor to performing testing and properly balance the system. Areas such as the theater are used sporadically and occupancy can go from low occupancy to high occupancy throughout the day. SWA recommends that the HVAC contractor correctly balance the system as well as consider altering controls for the system to modulate the amount of air delivered to the Theater based on CO2 levels and occupancy Heating The heating system for the Community and Tennis Center consists of entirely rooftop packaged units that provide heated forced air to all the spaces. The entire building is clearly divided into two sections between the Community Center section and the Tennis Center. The roof for the Community Center contains 6 packaged rooftop units to serve the entire space; however one of these units has already been de-commissioned and is in the process of being removed from the building. The roof of the Tennis Center contains 2 packaged rooftop units to serve the entire Tennis Center space. All of the rooftop units were installed between 1999 and 2002 and have not yet reached the end of their useful lifetime. Each packaged rooftop unit was observed to have gas heating with DX electric cooling and have efficiencies in the range of 80-83%. All rooftop units are controlled by programmable thermostats located within the building space. SWA does not recommend that any equipment be replaced at this time, however as rooftop units reach the end of their useful lifetime, SWA recommends upgrading each unit to more efficient units in order to decrease energy usage associated with heating and cooling loads Cooling All areas of the Community and Tennis Center are cooled using the same rooftop packaged units mentioned in the heating section above. All of the rooftop units were similar models that used R-22 refrigerant cooling with Energy Efficient Ratios (EERs) of Ventilation As mentioned above, a majority of the building is provided conditioned air from the packaged rooftop units. The units mix return air from the building with fresh outside air before conditioning the air to a specified temperature and delivering it to each of the building s spaces. In addition to the rooftop units, there are several exhaust fans that help rid the building of stale air and also help induce fresh air into the building. These rooftop exhaust fans were observed to all be working with no major maintenance issues Domestic Hot Water The Community Center portion of the building contains one Rheem commercial gas-fired, domestic hot water heater that has been recently installed within the last 18 months. This unit was observed to be high efficiency and is not recommended to upgrade at this point in time. The Tennis Center portion of the building contains a separate Bradford-White, gas-fired domestic hot water heater that is Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 20/47

21 high efficiency and was installed in There have been no reports of domestic hot water problems within the building Electrical systems Lighting Interior Lighting The office contains mostly inefficient lighting. Most of the lighting in the building uses 4 T12 fixtures with magnetic ballasts that SWA recommends replacing with 4 T8 fixtures. There are also a lot of incandescent fixtures the SWA recommends replacing with CFL s (Compact Fluorescent Lightbulbs). SWA also recommends installing 23 occupancy sensors throughout the building to limit the amount of runtime of certain fixtures. See attached lighting schedule in Appendix A for a complete lighting inventory throughout the building and estimated power consumption. Exit Lights - Exit signs were found to be LED type and incandescent. SWA recommends replace the fluorescent exit signs with LED type fixtures. Exterior Lighting - The exterior lighting surveyed was recessed 40W Incandescent fixtures in the soffit of the buildings roof overhang, 75W metal halide wall mounted exterior fixtures, and 65W halogen wall mounted exterior fixtures. SWA recommends replacing the incandescent fixtures with 13W CFL s, metal halides with 50W pulse start metal halides and halogens with 22W CFL s Appliances SWA performed a basic survey of appliances installed at the Parsippany - Troy Hills Community Center and Tennis Club and has determined that it would not be cost-effective to replace any appliances at this time due to the age of the building. Areas of the building such as the nutrition site contained equipment that was observed to be aging, however it would not be cost-effective to upgrade the equipment at this time. SWA recommends that this equipment is upgraded with energy efficient options as each piece of equipment is replaced at the end of its useful lifetime. Appliances, such as refrigerators, that are over 10 years of age should be replaced with newer efficient models with the Energy Star label. For example, Energy Star refrigerators use as little as 315 kwh / yr. When compared to the average electrical consumption of older equipment, Energy Star equipment results in a large savings. Building management should select Energy Star label appliances and equipment when replacing: refrigerators, printers, computers, copy machines, etc. More information can be found in the Products section of the Energy Star website at: Computers left on in the building consume a lot of energy. A typical desk top computer uses 65 to 250 watts and uses the same amount of energy when the screen saver is left on. Televisions in meeting areas use approximately 3-5 watts of electricity when turned off. SWA recommends all computers and all appliances (i.e. refrigerators, coffee makers, televisions, etc) be plugged in to power strips and turned off each evening just as the lights are turned off. The community center and tennis club computers are generally programmed for the power save mode, to shut down after a period of time that they have not been used Elevators The community center and tennis club contains one hydraulic elevator. recommendations to upgrade this elevator at this point in time. There are no Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 21/47

22 Process and others electrical systems The Community and Tennis Center contains two 45.0 kva transformers that step down the electrical voltage before being delivered to the rest of the building. These units were observed in good condition and would not be cost-effective to replace at this point in time. Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 22/47

23 3. EQUIPMENT LIST Inventory Building System Description Physical Location Make/ Model Fuel Heating/Cooling Heating/Cooling Heating/Cooling Heating/Cooling Heating/Cooling Heating/Cooling Heating/Cooling Cooling Cooling Domestic Hot Water Domestic Hot Water Transformers Transformers RTU; Trane packaged unit, DX cooling, gas heating, 250,000 BTUH input, 80% thermal efficiency, 203,000 BTUH output, 10 ton, R22 refrigerant RTU; Trane packaged unit, DX cooling, gas heating, 250,000 BTUH input, 80% thermal efficiency, 203,000 BTUH output, 10 ton, R22 refrigerant RTU; Carrier packaged unit, DX cooling, gas heating, 360,000 BTUH input, 275,000 BTUH output, 81% thermal efficiency, R22 refrigerant, 16 tons, EER 9.5 RTU; Trane packaged unit, DX cooling, gas heating, 250,000 BTUH input, 80% thermal efficiency, 203,000 BTUH output, 10 ton, R22 refrigerant RTU; Carrier packaged unit, DX cooling, gas heating, 460V, 3Ph, 60 Hz, 250 MBH input, 200 MBH output, 80% thermal efficiency, 12 1/2 tons, EER 9.5 RTU; Carrier packaged unit, DX cooling, gas heating, 460V, 3Ph, 60 Hz, 250 MBH input, 200 MBH output, 80% thermal efficiency, 12 1/2 tons, EER 9.5 Trane rooftop packaged unit, DX cooling, gas heating, 130,000 BTUH input, 108 BTUH output, 83% thermal efficiency, 5 ton CU; York condensing unit for split AC system, R22 refrigerant CU; Unknown make condensing unit for split AC system, R22 refrigerant, portion of nameplate missing Bradford White, gas-fired hot water heater, sealed combustion, 80 gallons storage Rheem commercial gas-fired hot water heater, sealed combustion, Input 125,000 BTUH, ANSI GE Transformer, 45.0 kva, 60 Hz, 3PH, 4.9% impedance Cutler-Hammer Transformer, 45.0 kva, 60 Hz, 3PH, 4.9% impedance Tennis Center roof Tennis Center roof Community Center roof Community Center roof Community Center roof Community Center roof Community Center roof Behind Tennis Courts Behind Tennis Courts Mechanical Room, Tennis Center Electrical room near elevator, 1st floor Community Center Electrical room near elevator, 1st floor Community Center Electrical room near elevator, 1st floor Community Center Trane Voyager, Model #YCH120B4H0EB, Serial #Z D Natural Gas/ Electricity Trane Voyager, Natural Model Gas/ #YCH120B4H0EB, Electricity Serial #P D Carrier Weather Maker, Model #48TMF HAA, Serial #NA Natural Gas/ Electricity Trane Voyager, Natural Model # Gas/ YCH120B4H0EB, Electricity Serial # P D Carrier, Weathermaker, Natural Model# 48TME Gas/ 601, Serial Electricity #4106G50262 Carrier Weathermaker, Natural Model #48TME Gas/ 601, Serial Electricity #0208G40688 Trane, Model Natural #YSC060A4EHA0FC Gas/ , Serial Electricity # L York, Model #H1RA D, Serial #WDLM Electricity Space served Tennis Center Tennis Center Community Center Community Center Community Center Community Center Community Center Men's locker rooms in Tennis Center Women's Make NA, Model locker rooms #****3MC-W0485A, Electricity in Tennis Serial #EHDM Center Bradford-White, Model # MRE80RD- 6/M80RD-6, Serial #CH Rheem, Model #G75-125, Serial #URNG0807G00780 GE, Model #9T23B3873, Serial #NA Cutler-Hammer, Catalog # , Model #NA, Serial #NA Concord, Model #NA, Serial #NA Natural Gas Natural Gas Electricity Electricity Tennis Center Community Center All areas of community center All areas of community center Date Installed Estimated Remaining useful life % % % % % % % % % % % % % % Near entrance of Elevator Concord hydraulic elevator, serves two floors Electricity First/Second % Community Center Floors Lighting See Appendix A Note: The remaining useful life of a system (in %) is an estimate based on the system date of built and existing conditions derived from visual inspection. Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 23/47

24 4. ENERGY CONSERVATION MEASURES Based on the assessment of The community center and tennis club, SWA has separated the investment opportunities into three recommended categories: 1. Capital Improvements - Upgrades not directly associated with energy savings 2. Operations and Maintenance - Low Cost / No Cost Measures 3. Energy Conservation Measures - Higher cost upgrades with associated energy savings Category I Recommendations: Capital Improvements Upgrade rooftop packaged units with high efficiency units (as they fail) SWA recommends that as the rooftop packaged units fail, they are replaced with high efficiency units that use R-410A refrigerant. R- 410A refrigerant produces the same cooling effects with less impact on the environment. Replace kitchen equipment with Energy Star appliances SWA performed a basic survey of kitchen equipment and appliances at the Community Center building. Most of the equipment was observe to be aging, however it would not be cost-effective to replace at this point in time. SWA recommends that Parsippany-Troy Hills consider upgrading to Energy Star labeled appliances when this equipment reaches the end of its useful life cycle. Category II Recommendations: Operations and Maintenance Program all computers for power save mode Based on field observations, the computers at the building were typically programmed for power save mode in order to reduce electricity consumption. Some computers may not be programmed correctly or as efficiently as possible. SWA recommends that all computers are programmed to shut down with the exception of the hard drive when left inactive. One new power strip product called, Smart strips are now commercially available that shut down a computer s components with the help of an occupancy sensors. Smart strips can be purchased for approximately $100. Perform bi-annual inspections of roofs SWA recommends performing bi-annual inspections of all roof surfaces to ensure that water is properly drained and all seals are properly formed. There areas inside of the building, such as racquetball courts that showed stained ceiling tiles, indicating water leaking from the roof surface directly above. SWA recommends that all detected leaks are addressed immediately to prevent any further water damage. Perform bi-annual inspections of exterior wall surfaces SWA recommends performing bi-annual inspections of all exterior wall surfaces with a focus on cracks, transition areas and sealing. SWA recommends addressing any notice of concern immediately. Provide weather stripping / air sealing SWA observed that all windows and doors had proper weatherstripping and air sealing due to their age. As a best practice, SWA recommends that each window and door is inspected twice per year for deficiencies. Any time that a seal has been compromised, building maintenance staff should repair and replace the seal immediately to ensure that thermal barriers are not breached. Provide water efficient fixtures and controls - Adding controlled on / off timers on all lavatory faucets is a cost-effective way to reduce domestic hot water demand and save water. Building staff can also easily install faucet aerators and / or low-flow fixtures to reduce water consumption. There are many retrofit options, which can be installed now or incorporated as equipment is replaced. Routine maintenance Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 24/47

25 practices that identify and quickly address water leaks are a low-cost way to save water and energy. Retrofitting with more efficient water-consumption fixtures / appliances will save both energy and money through reduced energy consumption for water heating, while also decreasing water / sewer bills. Use Energy Star labeled appliances - such as Energy Star refrigerators that should replace older energy inefficient equipment. Category III Recommendations: Energy Conservation Measures Summary table ECM# Description of Highly Recommended 0-5 Year Payback ECMs 1 Install 7 new CFL lamps 2 Install 353 T8 fluorescent fixtures 3 Install 23 new Occupancy Sensors 4 Install 30kW roof-mounted Solar PV array 5 HVAC Testing and Balancing Description of Recommended End of Life Cycle (>10 Year Payback) ECMs 6 Install 52 new LED exit signs 7 Install 14 new Pulse Start Metal Halide fixtures Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 25/47

26 ECM#1: Install 7 new CFL lamps Description: The Community and Tennis Center currently contains 5 interior fixtures as well as 2 exterior fixtures that should be upgraded to Compact Fluorescent Lamps (CFLs). CFLs typically use 2/3 less energy and power over incandescent and halogen lamps while providing the same quality of light. See Appendix A for complete lighting schedule and analysis. Installation cost: Estimated installed cost: $475 Source of cost estimate: RS Means; Published and established costs Economics: ECM # ECM description Source est. installed cost, $ est. incentives, $ net est. ECM cost with incentives, $ kwh, 1st yr savings kw, demand reduction/mo therms, 1st yr savings kbtu/sq ft, 1st yr savings est. operating cost, 1st yr savings, $ total 1st yr savings, $ life of measure, yrs est. lifetime cost savings, $ simple payback, yrs lifetime return on investment, % annual return on investment, % internal rate of return, % net present value, $ reduced, lbs/yr CO 2 1 Install 7 new CFL lamps RS Means , , ,197 Assumptions: SWA calculated the savings for this measure using measurements taken the days of the field visits and using the billing analysis. SWA assumes operation cost savings based on avoided bulb replacement when upgrading to lighting that consists of longer rated burn hours. Rebates / financial incentives: There are currently no incentives for this measure at this time. Options for funding ECM: This project may benefit from enrolling in NJ SmartStart program with Technical Assistance to offset a portion of the cost of implementation. Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 26/47

27 ECM#2: Install 353 T8 fluorescent fixtures Description: The Community Center and Tennis Club currently contains 353 T12 fluorescent fixtures with magnetic ballasts. SWA recommends replacing each of these fixtures with T8 fluorescent fixtures containing electronic ballasts. Typically, T8 electronic fixtures use 30% less energy and power compared to T12 magnetic fixtures. See Appendix A for complete lighting schedule and analysis. Installation cost: Estimated installed cost: $68,218 Source of cost estimate: RS Means; Published and established costs Economics: ECM # ECM description Source est. installed cost, $ est. incentives, $ net est. ECM cost with incentives, $ kwh, 1st yr savings kw, demand reduction/mo therms, 1st yr savings kbtu/sq ft, 1st yr savings est. operating cost, 1st yr savings, $ total 1st yr savings, $ life of measure, yrs est. lifetime cost savings, $ simple payback, yrs lifetime return on investment, % annual return on investment, % internal rate of return, % net present value, $ reduced, lbs/yr CO 2 2 Install 353 T8 fluorescent fixtures RS Means 78,808 10,590 68,218 81, ,558 27, , , ,633 Assumptions: SWA calculated the savings for this measure using measurements taken the days of the field visits and using the billing analysis. SWA assumes operation cost savings based on avoided bulb replacement when upgrading to lighting that consists of longer rated burn hours. Rebates / financial incentives: NJ Clean Energy Prescriptive lighting, T-8 fixtures with electronic ballasts ($30 per fixture). Maximum incentive is $10,590. Options for funding ECM: This project may benefit from enrolling in NJ SmartStart program with Technical Assistance to offset a portion of the cost of implementation. Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 27/47

28 ECM#3: Install 23 new Occupancy Sensors Description: Based on field observations, there are 23 areas within the Community Center and Tennis Club that would benefit from occupancy sensors. SWA recommends that these 23 areas are upgraded to occupancy sensors in order to reduce the amount of runtime based on occupancy schedules. See Appendix A for complete lighting schedule and analysis. Installation cost: Estimated installed cost: $4,600 Source of cost estimate: RS Means; Published and established costs Economics: ECM # ECM description Source est. installed cost, $ est. incentives, $ net est. ECM cost with incentives, $ kwh, 1st yr savings kw, demand reduction/mo therms, 1st yr savings kbtu/sq ft, 1st yr savings est. operating cost, 1st yr savings, $ total 1st yr savings, $ life of measure, yrs est. lifetime cost savings, $ simple payback, yrs lifetime return on investment, % annual return on investment, % internal rate of return, % net present value, $ reduced, lbs/yr CO 2 3 Install 23 new Occupancy Sensors RS Means 5, ,600 7, , , ,947 12,576 Assumptions: SWA calculated the savings for this measure using measurements taken the days of the field visits and using the billing analysis. SWA assumes amount of reduced hours based on field observations. Rebates / financial incentives: NJ Clean Energy Prescriptive Lighting Controls Wall-mounted occupancy sensors ($20 per control) Maximum incentive amount is $460. Options for funding ECM: This project may benefit from enrolling in NJ SmartStart program with Technical Assistance to offset a portion of the cost of implementation. Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 28/47

29 ECM#4: Install 30kW roof-mounted Solar PV array Description: Currently, the Community Center and Tennis Club does not use any renewable energy systems. Renewable energy systems such as photovoltaic panels, can be mounted on the building roofs, and can offset a portion of the purchased electricity for the building. Power stations generally have two separate electrical charges: usage and demand. Usage is the amount of electricity in kilowatt-hours that a building uses from month to month. Demand is the amount of electrical power that a building uses at any given instance in a month period. During the summer periods, when electric demand at a power station is high due to the amount of air conditioners, lights, equipment, etc being used within the region, demand charges go up to offset the utility s cost to provide enough electricity at that given time. Photovoltaic systems not only offset the amount of electricity use by a building, but also reduce the building s electrical demand, resulting in a higher cost savings as well. SWA presents below the economics, and recommends at this time that Township of Parsippany - Troy Hills further review installing a 30kW PV system to offset electrical demand and reduce the annual net electric consumption for the building, and review guaranteed incentives from NJ rebates to justify the investment. The community center and tennis club is not eligible for a 30% federal tax credit. Instead, Township of Parsippany - Troy Hills may consider applying for a grant and / or engage a PV generator / leaser who would install the PV system and then sell the power at a reduced rate. JCP&L provides the ability to buy SRECs at $600 / MWh or best market offer. There are a few locations for a 30kW PV installation on the building roofs and away from shade. A commercial multi-crystalline 123 watt panel (17.2 volts, 7.16 amps) has 10.7 square feet of surface area (11.51 watts per square foot). A 5kW system needs approximately 247 panels which would take up 2,610 square feet. The installation of a renewable Solar Photovoltaic power generating system could serve as a good educational tool and exhibit for the community. Installation cost: Estimated installed cost: $110,000 Source of cost estimate: Similar projects Economics: ECM # ECM description Source est. installed cost, $ est. incentives, $ net est. ECM cost with incentives, $ kwh, 1st yr savings kw, demand reduction/mo therms, 1st yr savings kbtu/sq ft, 1st yr savings est. operating cost, 1st yr savings, $ total 1st yr savings, $ life of measure, yrs est. lifetime cost savings, $ simple payback, yrs lifetime return on investment, % annual return on investment, % internal rate of return, % net present value, $ reduced, lbs/yr CO 2 4 Install 30kW roofmounted Solar PV array Similar Project 140,000 30, ,000 35, , , ,256 63,405 Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 29/47

30 Assumptions: SWA estimated the cost and savings of the system based on past PV projects. SWA projected physical dimensions based on a typical Polycrystalline Solar Panel (123 Watts, model #ND-123UJF). PV systems are sized based on Watts and physical dimensions for an array will differ with the efficiency of a given solar panel (W/sq ft). Rebates/financial incentives: NJ Clean Energy - Renewable Energy Incentive Program, Incentive based on $1.00 / watt Solar PV application. Incentive amount for this application is $30, NJ Clean Energy - Solar Renewable Energy Certificate Program. Each time a solar electric system generates 1000kWh (1MWh) of electricity, a SREC is issued which can then be sold or traded separately from the power. The buildings must also become net-metered in order to earn SRECs as well as sell power back to the electric grid. $21,000 has been incorporated in the above costs for a period of 15 year; however it requires proof of performance, application approval and negotiations with the utility. Options for funding ECM: This project may benefit from enrolling in NJ SmartStart program with Technical Assistance to offset a portion of the cost of implementation. ECM#5: HVAC testing and balancing Description: The Community Center and Tennis Club has undergone several renovations since it was first built. With each renovation, interior spaces were generally re-configured and HVAC equipment was replaced. Based on field conditions, the HVAC system was observed to be operating properly however there is some concern that air is not being distributed properly to all of the spaces. During the audit, it was clear that some areas such as the racquetball courts, storage areas and Senior Center rooms were warmer than other areas and appeared to be stuffy, even though the thermostats were at the same temperatures. The rooftop units used for HVAC have been replaced several times, during renovations or as they age and sizing may have been changed. In addition, with each addition, the distribution system was altered to accommodate for new use of spaces and interior areas may have changed slightly. SWA recommends hiring an HVAC contractor to performing testing and properly balance the system. Areas such as the theater are used sporadically and occupancy can go from low occupancy to high occupancy throughout the day. SWA recommends Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 30/47

31 that the HVAC contractor correctly balance the system as well as consider altering controls for the system to modulate the amount of air delivered to the Theater based on CO2 levels and occupancy. Installation cost: Estimated installed cost: $7,000 Source of cost estimate: Similar Projects Economics: ECM # ECM description Source est. installed cost, $ est. incentives, $ net est. ECM cost with incentives, $ kwh, 1st yr savings kw, demand reduction/mo therms, 1st yr savings kbtu/sq ft, 1st yr savings est. operating cost, 1st yr savings, $ total 1st yr savings, $ life of measure, yrs est. lifetime cost savings, $ simple payback, yrs lifetime return on investment, % annual return on investment, % internal rate of return, % net present value, $ reduced, lbs/yr CO 2 5 HVAC testing and balancing RS Means 7, ,000 1, , , ,503 13,949 Assumptions: SWA calculated the savings for this measure using measurements taken the days of the field visits and using the billing analysis. SWA assumes that Testing and Balancing (TAB) contracting will have to be performed on 7 rooftop units and corresponding distribution systems. SWA assumes the cost of TAB contracting to be $1,000 per unit. SWA assumes savings equivalent to 10% of total heating and cooling loads only. Rebates / financial incentives: There are currently no incentives for this measure at this time. Options for funding ECM: This project may benefit from enrolling in NJ SmartStart program with Technical Assistance to offset a portion of the cost of implementation. Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 31/47

32 ECM#6: Install 52 new LED exit signs Description: The Community Center and Tennis Club building currently contains 52 fluorescent exit signs that are inefficient. Exit signs are generally a good opportunity to reduce electrical consumption since they are operated 24 hours per day. SWA recommends replacing each fluorescent exit signs with LED exit signs. See Appendix A for complete lighting schedule and analysis. Installation cost: Estimated installed cost: $9,533 Source of cost estimate: RS Means; Published and established costs Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 32/47

33 Economics: ECM # ECM description Source est. installed cost, $ est. incentives, $ net est. ECM cost with incentives, $ kwh, 1st yr savings kw, demand reduction/mo therms, 1st yr savings kbtu/sq ft, 1st yr savings est. operating cost, 1st yr savings, $ total 1st yr savings, $ life of measure, yrs est. lifetime cost savings, $ simple payback, yrs lifetime return on investment, % annual return on investment, % internal rate of return, % net present value, $ reduced, lbs/yr CO 2 6 Install 52 new LED exit signs RS Means 10,573 1,040 9,533 3, , ,443 6,611 Assumptions: SWA calculated the savings for this measure using measurements taken the days of the field visits and using the billing analysis. SWA assumes operation cost savings based on avoided bulb replacement when upgrading to lighting that consists of longer rated burn hours. Rebates / financial incentives: NJ Clean Energy Prescriptive Lighting LED exit signs ($20 per fixture) Maximum incentive amount is $1,040. Options for funding ECM: This project may benefit from enrolling in NJ SmartStart program with Technical Assistance to offset a portion of the cost of implementation. ECM#7: Install 14 new Pulse Start Metal Halide fixtures Description: The Community Center and Tennis Club building currently contains 14 Probe Start Metal Halide fixtures used for exterior lighting. SWA recommends replacing these fixtures with Pulse Start Metal Halides. Probe Start Metal Halide fixtures are generally installed with excessive wattages since they degrade over time. Pulse Start Metal Halide fixtures are installed at lower wattages and do not degrade overtime. In addition, Pulse Start Metal Halides save money since they require less bulb changes per the lifetime of the fixture. See Appendix A for complete lighting schedule and analysis. Installation cost: Estimated installed cost: $10,731 Source of cost estimate: RS Means; Published and established costs Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 33/47

34 Economics: ECM # ECM description Source est. installed cost, $ est. incentives, $ net est. ECM cost with incentives, $ kwh, 1st yr savings kw, demand reduction/mo therms, 1st yr savings kbtu/sq ft, 1st yr savings est. operating cost, 1st yr savings, $ total 1st yr savings, $ life of measure, yrs est. lifetime cost savings, $ simple payback, yrs lifetime return on investment, % annual return on investment, % internal rate of return, % net present value, $ reduced, lbs/yr CO 2 7 Install 14 new Pulse Start Metal Halide fixtures RS Means 11, ,731 3, , ,759 5,722 Assumptions: SWA calculated the savings for this measure using measurements taken the days of the field visits and using the billing analysis. SWA assumes operation cost savings based on avoided bulb replacement when upgrading to lighting that consists of longer rated burn hours. Rebates / financial incentives: NJ Clean Energy Prescriptive Lighting Metal Halide with Pulse Start ($25 per fixture) Maximum incentive amount is $350. Options for funding ECM: This project may benefit from enrolling in NJ SmartStart program with Technical Assistance to offset a portion of the cost of implementation. Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 34/47

35 5. RENEWABLE AND DISTRIBUTED ENERGY MEASURES 5.1. Existing systems There aren t currently any existing renewable energy systems Wind A Wind system is not applicable for this building because the area does not have winds of sufficient velocity to justify installing a wind turbine system Solar Photovoltaic Pleases see the above recommended ECM# Solar Thermal Collectors Solar thermal collectors are not cost effective for this building and would not be recommended due to the insufficient and not constant use of domestic hot water throughout the building to justify the expenditure Combined Heat and Power CHP is not applicable for this building because of the existing HVAC system and insufficient domestic hot water use Geothermal Geothermal is not applicable for this building because current HVAC equipment uses gasheating with DX coils. 6. ENERGY PURCHASING AND PROCUREMENT STRATEGIES 6.1. Energy Purchasing The community center and tennis club receives natural gas via one incoming meter. New Jersey Natural Gas supplies gas to the building. There is not an ESCO engaged in the process. An Energy Services Company (ESCO) is a consultancy group that engages in a performance based contract with a client firm to implement measures which reduce energy consumption and costs in a technically and financially viable manner. Electricity is also purchased via one incoming meter directly for The community center and tennis club from JCP&L without an ESCO. SWA analyzed the utility rate for natural gas and electricity supply over an extended period. Electric bill analysis shows fluctuations of 20% over a recent 12 month period. Natural gas bill analysis shows fluctuations up to 83% over a recent 12 month period. Some of these fluctuations may have been caused by adjustments between estimated and actual meter readings, and low use caps for the non-heating months. Thus the building pays for fixed costs such as meter reading charges during the summer months. Currently, New Jersey commercial buildings of similar type pay $0.150/kWh for electricity and $1.55/therm for natural gas. Currently, the electricity rate for Community and Tennis Center is Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 35/47

36 $0.176/kWh, which means there is a potential cost savings of $14,407 per year. The current natural gas rate for the community center and tennis club is $1.320/therm which is better than the average natural gas cost. A large cost savings potential for electricity exists, however this involves contacting third party suppliers and negotiating utility rates. SWA recommends that Township of Parsippany - Troy Hills further explore opportunities of purchasing electricity from third party energy suppliers in order to reduce rate fluctuation and ultimately reduce the annual cost of energy for the community center and tennis club. Appendix B contains a complete list of third party energy suppliers for the Township of Parsippany - Troy Hills service area. Township of Parsippany - Troy Hills may want to consider partnering with other school districts, municipalities, townships and communities to aggregate a substantial electric and natural gas use for better leveraging in negotiations with ESCOs and of improving the pricing structures. This sort of activity is happening in many parts of the country and in New Jersey. $0.250 Annual Electric Rate ($/kwh) Electric Rate ($/kwh) $0.200 $0.150 $0.100 $0.050 $0.000 Electricity Rate ($/kwh) Jun-08 Jul-08 Aug-08 Sep-08 Oct-08 Nov-08 Dec-08 Jan-09 Feb-09 Mar-09 Apr-09 May-09 Date (Month-Year) Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 36/47

37 $3.500 Natural Gas Rate ($/Therm) Natural Gas Rate ($/therm) $3.000 $2.500 $2.000 $1.500 $1.000 $0.500 $0.000 Natural Gas Rate ($/therm) Jul-08 Aug-08 Sep-08 Oct-08 Nov-08 Dec-08 Jan-09 Feb-09 Mar-09 Apr-09 May-09 Jun-09 Date (Month-Year) 6.2. Energy Procurement strategies Also, the community center and tennis club would not be eligible for enrollment in a Demand Response Program, because there isn t the capability at this time to shed a minimum of 150 kw electric demand when requested by the utility during peak demand periods, which is the typical threshold for considering this option. Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 37/47

38 7. METHOD OF ANALYSIS 7.1. Assumptions and tools Energy modeling tool: Cost estimates: Established / standard industry assumptions, DOE e-quest RS Means 2009 (Facilities Maintenance & Repair Cost Data) RS Means 2009 (Building Construction Cost Data) RS Means 2009 (Mechanical Cost Data) Published and established specialized equipment material and labor costs Cost estimates also based on utility bill analysis and prior experience with similar projects 7.2. Disclaimer This engineering audit was prepared using the most current and accurate fuel consumption data available for the site. The estimates that it projects are intended to help guide the owner toward best energy choices. The costs and savings are subject to fluctuations in weather, variations in quality of maintenance, changes in prices of fuel, materials, and labor, and other factors. Although we cannot guarantee savings or costs, we suggest that you use this report for economic analysis of the building and as a means to estimate future cash flow. THE RECOMMENDATIONS PRESENTED IN THIS REPORT ARE BASED ON THE RESULTS OF ANALYSIS, INSPECTION, AND PERFORMANCE TESTING OF A SAMPLE OF COMPONENTS OF THE BUILDING SITE. ALTHOUGH CODE-RELATED ISSUES MAY BE NOTED, SWA STAFF HAVE NOT COMPLETED A COMPREHENSIVE EVALUATION FOR CODE-COMPLIANCE OR HEALTH AND SAFETY ISSUES. THE OWNER(S) AND MANAGER(S) OF THE BUILDING(S) CONTAINED IN THIS REPORT ARE REMINDED THAT ANY IMPROVEMENTS SUGGESTED IN THIS SCOPE OF WORK MUST BE PERFORMED IN ACCORDANCE WITH ALL LOCAL, STATE, AND FEDERAL LAWS AND REGULATIONS THAT APPLY TO SAID WORK. PARTICULAR ATTENTION MUST BE PAID TO ANY WORK WHICH INVOLVES HEATING AND AIR MOVEMENT SYSTEMS, AND ANY WORK WHICH WILL INVOLVE THE DISTURBANCE OF PRODUCTS CONTAINING MOLD, ASBESTOS, OR LEAD. Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 38/47

39 Appendix A: Lighting Study Marker Floor Location Existing Fixture Information Retrofit Information Annual Savings Room Identificatio n Fixture Type Ballast Lamp Type # of Fixtures # of Lamps per Fixture Watts per Lamp Controls Operational Hours per Day Operational Days per Year Ballast Wattage Total Watts Energy Use kwh/year Category Fixture Type Lamp Type Ballast Controls # of Fixtures # of Lamps per Fixture Watts per Lamp Operational Hours per Day Operational Days per Ballast Y Watts 1 1 Staircase Parabolic M 4'T S N/A Parabolic 4'T8 M S Multipurpose Room Recessed M 4'T S ,840 3,842 T8 Recessed 4'T8 E S Archive room Recessed M 4'T S ,840 3,842 T8 Recessed 4'T8 E OS Library Recessed M 4'T S ,840 3,842 T8 Recessed 4'T8 E OS Meeting Room Recessed M 4'T S ,840 3,842 T8 Recessed 4'T8 E OS EMS Ready Room Recessed M 4'T S ,100 4,385 T8 Recessed 4'T8 E OS EMS Storage Recessed M 4'T S T8 Recessed 4'T8 E S EMS Locker Room Recessed M 4'T S T8 Recessed 4'T8 E S Multipurpose Room Recessed M 2'T S ,403 T8 Recessed 2'T8 E OS Green Room Recessed M 4'T S ,046 T8 Recessed 4'T8 E S Green Rom Exit Sign N LED N N/A Exit Sign LED N N Office 2'U-Shape E 2'T S N/A 2'U-shape 2'T8 E S Theater Parabolic M 4'T S T8 Parabolic 4'T8 E S Theater HID N MH S ,504 3,140 PSMH HID PSMH N S Theater HID N MH S ,504 5,228 PSMH HID PSMH N S Theater Exit Sign M LED N N/A Exit Sign LED M N Dance Studio Exit Sign M LED N N/A Exit Sign LED M N Dance Studio Parabolic M 4'T S ,846 T8 Parabolic 4'T8 E S Office Recessed M 4'T S T8 Recessed 4'T8 E S Bathroom Women Recessed M 4'T S T8 Recessed 4'T8 E S Bathroom Men Recessed M 4'T S T8 Recessed 4'T8 E S Bathroom Men Recessed M 4'T S T8 Recessed 4'T8 E S Sauna 2'U-Shape M 2'T S T8 2'U-shape 2'T8 E S Sauna Storage Recessed E 4'T S N/A Recessed 4'T8 E S Sauna Storage Screw-in N CFL S N/A Screw-in CFL N S Lunch Room Parabolic M 4'T S ,208 4,610 T8 Parabolic 4'T8 E S Lunch Room Exit Sign N LED N N/A Exit Sign LED N N Lunch Room Screw-in N Inc S N/A Screw-in CFL N S Bar Recessed M 4'T S ,153 T8 Recessed 4'T8 E S Bar Recessed M 4'T S ,153 T8 Recessed 4'T8 E S Elevator Control Room Screw-in N Inc S N/A Screw-in CFL N S Storage Room 2'U-Shape M 2'T S T8 2'U-shape 2'T8 E S Atrium Recessed E 4'T S ,462 N/A Recessed 4'T8 E S Atrium Screw-in N Inc S N/A Screw-in CFL N S Elevator Exit Sign N LED N N/A Exit Sign LED N N Vestibule Screw-in N Inc S N/A Screw-in CFL N S Exercise Room Recessed M 4'T S ,104 2,305 T8 Recessed 4'T8 E OS Exercise Room Recessed M 4'T S ,104 2,305 T8 Recessed 4'T8 E OS Exercise Room Screw-in N Inc S N/A Screw-in CFL N S Reading Room Screw-in N Inc S ,086 C Screw-in CFL N OS Office Recessed M 4'T S ,840 3,842 T8 Recessed 4'T8 E S Library Recessed M 4'T S ,537 T8 Recessed 4'T8 E S Total Watts Energy Use kwh/year Fixture Savings (kwh) Controls Savings (kwh) Total Savings (kwh) Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 39/47

40 Location Existing Fixture Information Retrofit Information Annual Savings Marker Floor Room Identification Fixture Type Ballast Lamp Type # of Fixtures # of Lamps per Fixture Watts per Lamp Controls Operational Hours per Day Operational Days per Year Ballast Wattage Total Watts Energy Use kwh/year 43 2 Library Recessed M 4'T S ,537 T8 Recessed 4'T8 E S Gaming Area Screw-in N Inc S ,560 3,257 N/A Screw-in CFL N S Gaming Area Screw-in N Inc S ,560 3,257 N/A Screw-in CFL N S Gaming Area Screw-in N Inc S N/A Screw-in CFL N S Gaming Area Screw-in N Inc S N/A Screw-in CFL N S Gaming Room Closet Recessed M 4'T S T8 Recessed 4'T8 E S Lunch Room Recessed M 4'T S ,656 3,458 T8 Recessed 4'T8 E OS Kitchen Recessed M 4'T S T8 Recessed 4'T8 E OS Storage Room Recessed M 4'T S T8 Recessed 4'T8 E S Meeting Room Recessed M 4'T S ,472 3,074 T8 Recessed 4'T8 E OS Conference Room Exit Sign N LED N N/A Exit Sign LED N N Conference Room Screw-in N CFL S N/A Screw-in CFL N S Storage Room Recessed M 4'T S T8 Recessed 4'T8 E S Bathroom Men Recessed M 4'T S ,153 T8 Recessed 4'T8 E OS Bathroom Women Recessed M 4'T S ,153 T8 Recessed 4'T8 E OS Bathroom Women Screw-in N Inc S N/A Screw-in CFL N S Bathroom Men Screw-in N Inc S N/A Screw-in CFL N S Meeting Room Screw-in N Inc D ,680 9,772 N/A Screw-in CFL N D Meeting Room Screw-in N Inc D ,680 9,772 N/A Screw-in CFL N D Meeting Room Screw-in N Inc D ,680 9,772 N/A Screw-in CFL N D Office Recessed M 4'T S ,921 T8 Recessed 4'T8 E S Storage Room Recessed M 4'T S T8 Recessed 4'T8 E S Storage Room Recessed M 4'T S T8 Recessed 4'T8 E S Office - Fire Dept. Recessed M 4'T S ,840 3,842 T8 Recessed 4'T8 E S Office - Fire Dept. Recessed M 4'T S ,840 3,842 T8 Recessed 4'T8 E S Hallway Recessed M 4'T S T8 Recessed 4'T8 E S Staircase Recessed M 4'T S ,153 T8 Recessed 4'T8 E S Staircase Recessed M 4'T S T8 Recessed 4'T8 E S Staircase Exit Sign N LED N N/A Exit Sign LED N N Hallway Exit Sign N LED N N/A Exit Sign LED N N Hallway Screw-in N Inc S N/A Screw-in CFL N S Health Office Closet Recessed M 4'T S T8 Recessed 4'T8 E S Health Office 2'U-Shape M 2'T S ,604 T8 2'U-shape 2'T8 E S Health Office Screw-in N Inc S N/A Screw-in CFL N S Health Office Screw-in N Inc S ,086 N/A Screw-in CFL N S Bathroom Men Recessed M 4'T S T8 Recessed 4'T8 E S Bathroom Women Recessed M 4'T S T8 Recessed 4'T8 E S Bathroom Women Recessed M 4'T S T8 Recessed 4'T8 E S Storage Room Recessed M 4'T S T8 Recessed 4'T8 E S Storage Room Recessed M 4'T S T8 Recessed 4'T8 E S Office Recessed M 4'T S T8 Recessed 4'T8 E S Office Recessed M 4'T S T8 Recessed 4'T8 E S Category Fixture Type Lamp Type Ballast Controls # of Fixtures # of Lamps per Fixture Watts per Lamp Operational Hours per Day Operational Days per Year Ballast Watts Total Watts Energy Use kwh/year Fixture Savings (kwh) Controls Savings (kwh) Total Savings (kwh) Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 40/47

41 Location Existing Fixture Information Retrofit Information Annual Savings Marker Floor Room Identification Fixture Type Ballast Lamp Type # of Fixtures # of Lamps per Fixture Watts per Lamp Controls Operational Hours per Day Operational Days per Year Ballast Wattage Total Watts Energy Use 85 2 Office Recessed M 4'T S T8 Recessed 4'T8 E S Office 2'U-Shape M 2'T S T8 2'U-shape 2'T8 E S Copy Room Recessed M 4'T S T8 Recessed 4'T8 E S Office Recessed M 4'T S T8 Recessed 4'T8 E S Office Recessed M 4'T S T8 Recessed 4'T8 E S Office Recessed M 4'T S T8 Recessed 4'T8 E S Office Recessed M 4'T S T8 Recessed 4'T8 E S Office Screw-in N Inc S N/A Screw-in CFL N S Hallway Screw-in N Inc S ,086 N/A Screw-in CFL N S Hallway Exit Sign N LED S N/A Exit Sign LED N S Hallway Exit Sign N LED S N/A Exit Sign LED N S Hallway Screw-in N Inc S ,470 5,157 N/A Screw-in CFL N S Hallway Screw-in N Inc S ,380 7,057 N/A Screw-in CFL N S Hallway Exit Sign N Inc N ,080 4,343 LEDex Exit Sign LED N N Tennis Courts Recessed M 8'T S , ,645 T8 Recessed 8'T8 E S Office Recessed M 4'T S T8 Recessed 4'T8 E S Storage Room Screw-in N Inc S N/A Screw-in CFL N S Main lobby Screw-in N Inc S ,495 7,116 N/A Screw-in CFL N S Vestibule Screw-in N Inc S N/A Screw-in CFL N S Vestibule Exit Sign N LED N N/A Exit Sign LED N N Kitchen Recessed M 4'T S ,752 T8 Recessed 4'T8 E S Tennis Courts Exit Sign N LED N N/A Exit Sign LED N N Locker Room Men Screw-in N Inc S ,238 N/A Screw-in CFL N S Locker Room Men Exit Sign N LED N C Exit Sign LED N OS Shower Men Screw-in N CFL S N/A Screw-in CFL N S Sauna Men Screw-in N Inc S C Screw-in CFL N OS Locker Room Men Recessed M 4'T S ,628 T8 Recessed 4'T8 E S Bathroom Men Recessed M 4'T S T8 Recessed 4'T8 E S Bathroom Men Screw-in N Inc S N/A Screw-in CFL N S Office Recessed M 4'T S ,752 T8 Recessed 4'T8 E OS Locker Room Women Screw-in N Inc S ,238 C Screw-in CFL N OS Locker Room Women Exit Sign N LED N C Exit Sign LED N OS Shower Women Screw-in N CFL S C Screw-in CFL N OS Sauna Women Screw-in N Inc S C Screw-in CFL N OS Locker Room Women Recessed M 4'T S ,628 T8 Recessed 4'T8 E S Bathroom Women Recessed M 4'T S T8 Recessed 4'T8 E S Bathroom Women Screw-in N Inc S N/A Screw-in CFL N S Ext Exterior Exterior N Inc T C Exterior CFL N OS Ext Exterior Exterior N MH T PSMH Exterior PSMH N OS Ext Exterior Exterior N Hal T CFL Exterior CFL N OS Totals: ,335 1, , , , , , ,489 7,024 Rows Highlighed Yellow Indicate an Energy Conservation Measure is recommended for that space kwh/year Category Fixture Type Lamp Type Ballast Controls # of Fixtures # of Lamps per Fixture Watts per Lamp Operational Hours per Day Operational Days per Year Ballast Watts Total Watts Energy Use kwh/year Fixture Savings (kwh) Controls Savings (kwh) Total Savings (kwh) Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 41/47

42 Appendix B: Third Party Energy Suppliers (ESCOs) Third Party Electric Suppliers for JCPL Service Territory Telephone & Web Site Hess Corporation (800) Hess Plaza Woodbridge, NJ BOC Energy Services, Inc. (800) Mountain Avenue Murray Hill, NJ Commerce Energy, Inc. (800) Route 9 South, Suite Freehold, NJ Constellation NewEnergy, Inc. (888) A Lake Street, Suite 2 Ramsey, NJ Direct Energy Services, LLC (866) Wood Avenue, Suite Iselin, NJ FirstEnergy Solutions (800) Madison Avenue Morristown, NJ Glacial Energy of New Jersey, Inc. (877) LaRoche Avenue Harrington Park, NJ Integrys Energy Services, Inc. (877) Wood Ave, South, Suite Iselin, NJ Liberty Power Delaware, LLC (866) Park 80 West Plaza II, Suite Saddle Brook, NJ Liberty Power Holdings, LLC (800) Park 80 West Plaza II, Suite Saddle Brook, NJ Pepco Energy Services, Inc. (800) Main St. Lebanon, NJ PPL EnergyPlus, LLC (800) Church Road Cherry Hill, NJ Sempra Energy Solutions (877) Main Street, 8th Floor Woodbridge, NJ South Jersey Energy Company (800) One South Jersey Plaza, Route 54 Folsom, NJ Suez Energy Resources NA, Inc. (888) Thornall Street, 6th Floor Edison, NJ UGI Energy Services, Inc. (856) East Main Street, Suite 1 Moorestown, NJ Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 42/47

43 Third Party Gas Suppliers for NJNG Service Territory Telephone & Web Site Cooperative Industries (800) Washington Avenue Belleville, NJ Direct Energy Services, LLC (866) Wood Avenue, Suite Iselin, NJ Gateway Energy Services Corp. (800) Whispering Pines Lane Lakewood, NJ UGI Energy Services, Inc. (856) East Main Street, Suite 1 Moorestown, NJ Hess Corporation (800) Hess Plaza Woodbridge, NJ Intelligent Energy (800) Center Avenue, Suite Fort Lee, NJ Metromedia Energy, Inc. (877) Industrial Way Eatontown, NJ MxEnergy, Inc. (800) Thornall Street, Suite Edison, NJ NATGASCO (Mitchell Supreme) (800) Freeman Street Orange, NJ NJ Gas & Electric (866) Bridge Plaza, Fl. 2 Fort Lee, NJ Pepco Energy Services, Inc. (800) Main Street Lebanon, NJ PPL EnergyPlus, LLC (800) Church Road Cherry Hill, NJ South Jersey Energy Company (800) One South Jersey Plaza, Route 54 Folsom, NJ Sprague Energy Corp. (800) Ridge Road Chatham Township, NJ Woodruff Energy (800) Water Street Bridgeton, NJ Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 43/47

44 Appendix C: Glossary and Method of Calculations Glossary of ECM Terms. Net ECM Cost: The net ECM cost is the cost experienced by the customer, which is typically the total cost (materials + labor) of installing the measure minus any available incentives. Both the total cost and the incentive amounts are expressed in the summary for each ECM. Annual Energy Cost Savings (AECS): This value is determined by the audit firm based on the calculated energy savings (kwh or Therm) of each ECM and the calculated energy costs of the building. Lifetime Energy Cost Savings (LECS): This measure estimates the energy cost savings over the lifetime of the ECM. It can be a simple estimation based on fixed energy costs. If desired, this value can factor in an annual increase in energy costs as long as the source is provided. Simple Payback: This is a simple measure that displays how long the ECM will take to breakeven based on the annual energy and maintenance savings of the measure. ECM Lifetime: This is included with each ECM so that the owner can see how long the ECM will be in place and whether or not it will exceed the simple payback period. Additional guidance for calculating ECM lifetimes can be found below. This value can come from manufacturer s rated lifetime or warranty, the ASHRAE rated lifetime, or any other valid source. Operating Cost Savings (OCS): This calculation is an annual operating savings for the ECM. It is the difference in the operating, maintenance, and / or equipment replacement costs of the existing case versus the ECM. In the case where an ECM lifetime will be longer than the existing measure (such as LED lighting versus fluorescent) the operating savings will factor in the cost of replacing the units to match the lifetime of the ECM. In this case or in one where one-time repairs are made, the total replacement / repair sum is averaged over the lifetime of the ECM. Return on Investment (ROI): The ROI is expresses the percentage return of the investment based on the lifetime cost savings of the ECM. This value can be included as an annual or lifetime value, or both. Net Present Value (NPV): The NPV calculates the present value of an investment s future cash flows based on the time value of money, which is accounted for by a discount rate (assumes bond rate of 3.2%). Internal Rate of Return (IRR): The IRR expresses an annual rate that results in a break-even point for the investment. If the owner is currently experiencing a lower return on their capital than the IRR, the project is financially advantageous. This measure also allows the owner to compare ECMs against each other to determine the most appealing choices. Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 44/47

45 ECM = Energy Conservation Measure AOCS = Annual Operating Cost Savings AECS = Annual Energy Cost Savings LOCS = Lifetime Operating Cost Savings LECS = Lifetime Energy Cost Savings NPV = Net Present Value IRR = Internal Rate of Return DR = Discount Rate Net ECM Cost = Total ECM Cost Incentive LECS = AECS X ECM Lifetime AOCS = LOCS / ECM Lifetime Calculation References Note: The lifetime operating cost savings are all avoided operating, maintenance, and / or component replacement costs over the lifetime of the ECM. This can be the sum of any annual operating savings, recurring or bulk (i.e. one-time repairs) maintenance savings, or the savings that comes from avoiding equipment replacement needed for the existing measure to meet the lifetime of the ECM (e.g. lighting change outs). Simple Payback = Net ECM Cost / (AECS + AOCS) Lifetime ROI = (LECS + LOCS Net ECM Cost) / Net ECM Cost Annual ROI = (Lifetime ROI / Lifetime) = (AECS + OCS) / Net ECM Cost 1 / Lifetime It is easiest to calculate the NPV and IRR using a spreadsheet program like Excel. Excel NPV and IRR Calculation In Excel, function =IRR(values) and =NPV(rate, values) are used to quickly calculate the IRR and NPV of a series of annual cash flows. The investment cost will typically be a negative cash flow at year 0 (total cost - incentive) with years 1 through the lifetime receiving a positive cash flow from the annual energy cost savings and annual maintenance savings. The calculations in the example below are for an ECM that saves $850 annually in energy and maintenance costs (over a 10 year lifetime) and takes $5,000 to purchase and install after incentives: Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 45/47

46 ECM and Equipment Lifetimes Determining a lifetime for equipment and ECM s can sometimes be difficult. The following table contains a list of lifetimes that the NJCEP uses in its commercial and industrial programs. Other valid sources are also used to determine lifetimes, such as the DOE, ASHRAE, or the manufacturer s warranty. Lighting is typically the most difficult lifetime to calculate because the fixture, ballast, and bulb can all have different lifetimes. Essentially the ECM analysis will have different operating cost savings (avoided equipment replacement) depending on which lifetime is used. When the bulb lifetime is used (rated burn hours / annual burn hours), the operating cost savings is just reflecting the theoretical cost of replacing the existing case bulb and ballast over the life of the recommended bulb. Dividing by the bulb lifetime will give an annual operating cost savings. When a fixture lifetime is used (e.g. 15 years) the operating cost savings reflects the avoided bulb and ballast replacement cost of the existing case over 15 years minus the projected bulb and ballast replacement cost of the proposed case over 15 years. This will give the difference of the equipment replacement costs between the proposed and existing cases and when divided by 15 years will give the annual operating cost savings. Parsippany Troy Hills Community Center SWA, Inc. - Local Government Energy Audit Report Page 46/47