Study of the energy performance of a retrofitting office

Size: px
Start display at page:

Download "Study of the energy performance of a retrofitting office"

Transcription

1 Study of the energy performance of a retrofitting office Paolo Valdiserri CIRI Edilizia Costruzioni, Università di Bologna paolo.valdiserri@unibo.it Abstract Building retrofitting is the most feasible and costeffective method to improve building energy efficiency. To this aim, the building envelope should be equipped with new windows having low thermal transmission coefficients and/or with insulation material in the external partitions. This approach leads to considerable energy saving, but at the same time if the users do not properly ventilate the occupied spaces, it results in a worsening of indoor air quality. The paper presents a comparative analysis of two different strategies to enhance the energy performance of an existing building. The first is to reduce the heat transfer by transmission (i.e. use of low-emissivity glass) and the second to decrease the heat transfer by ventilation (i.e. installation of a heat recovery). The study has been applied to an office block, located in the city of Bologna, Italy. Potential energy savings were calculated by dynamic simulation using Trnsys software. To this purpose, a reference office was selected and then the following cases were studied. The first one took into account the replacement of all the windows, the second one consisted in installing a total energy ventilation recovery system and the last one contemplated both the solutions. Finally, an evaluation of the simple payback time and the net present value was performed. 1. Introduction Buildings consume around 40% of Europe s energy needs and account for 36% of EU CO2 emissions. Member States of the European Union are required to implement energy efficiency measures for buildings under the Energy Performance of Building Directive. In order to reduce this consumption and pursue the goal imposed by the European Union, Italy issued several Legislative Decrees in particular no.192/2005, no.311/2006 and no.28/2011. The need to reduce energy consumption in buildings implies the use of considerable thermal insulation, but at the same time, in the absence of a suitable ventilation system, it could result in a worsening of indoor air quality. A healthy life imposes a good indoor air quality especially where people spend a considerable amount of time, so adequate air exchanges should be guaranteed to reduce indoor pollution. Due to the increase of insulation and the decrease of the thermal transmission coefficients, ventilation constitutes a growing part of the heating demand; between 20 50% for new and retrofitted buildings, depending on the building s insulation, compactness, air change rate, indoor heat sources, indoor set points and outdoor climate. Heat recovery (HRV) from exhaust air in buildings is considered an important strategy to reduce the heat transfer by ventilation and generate consequent energy savings. The principle is to recover heat from the exhaust air and to transfer it to the supply air through a heat exchanger. Primary energy savings of HRV can be highly significant, depending on the type of heat supply system, the airtightness of buildings, and the use of electricity to operate the HRV system. In Italy, like several other European countries, the existing dwellings constructed before the application of energy saving regulations, represent the majority of the edifices. Therefore, building renovation becomes a key strategy to reduce energy consumption and costs. In the present work, simulations of an existing office building (where some energy saving methods were applied) were performed. 281

2 Paolo Valdiserri Table 1 surface of each room of the office and list of acronyms adopted in the simulations. Room Surface, [m 2 ] Acronym Reception R1 Office O1 Office O2 Office O3 Conference room CR Table 2 highlights the thermal characteristics of the building envelope (between the heated offices and the unheated spaces). Table 2 - Values of thermal transmittance referred to the envelope elements. Figure 1 Plant and section of the office block The simulations were conducted using the Trnsys commercial code at the time step of 15 minutes. Trnsys is an extensible simulation environment for the transient simulation of energy systems including multizone buildings. It is used to validate new energy concepts, design and simulation of buildings and their equipment, including control strategies, occupant behaviour, and alternative energy systems (wind, solar, photovoltaic, hydrogen systems, etc.). 2. Description of the building under investigation The numerical model has been applied to an office building, located in Bologna (Italy). The construction, shown in Figure 1, is a three-storey building having heated offices on the first and second floor and parking lots on the ground floor (not heated). The floor surface of the two offices is 534 m 2 ; each floor is composed by one reception, three offices and a conference room. Table 1 illustrates the surface of each room and the acronyms used in the calculations. Envelope element Thermal transmittance U [W m -2 K -1 ] Outside walls 0.51 First floor / Roof 0.44 / 0.46 Internal ceiling 1.57 Windows 2.85 The heating system is supposed to operate 14 hours a day from 5 a.m. to 7 p.m from Monday to Friday. In this period, it is set to maintain the internal temperature of 20 C. The ventilation system is switched on from 7 a.m. to 7 p.m. every working day. In each floor, the fresh air enters the reception, the conference room and the three offices at the flow rate illustrated in Table 3 and extracted from the corridor. Whilst the ventilation is working, a humidification system operates to provide the relative humidity of 50% in the offices. During the night and at the weekend, the heating system is able to provide the temperature of 16 C without any humidity control and with the ventilation system switched off. Table 3 also includes the occupancy and the personal computers (PCs) connected in each office 282

3 Study of the energy performance of a retrofitting office during working hours (7 a.m. to 7 p.m. Monday to Friday). Table 3 Ventilation flow rate, number of people and computers during working hours (7 a.m. to 7 p.m. Monday to Friday). Room Flow rate [m 3 h -1 ] People Reception Office Office Office Conference room and PCs In the present study, the performance of the reference case (Case 0) and of other three cases of retrofitting (Case 1, 2 and 3) are simulated and calculated. Trnsys simulations were conducted with a time step of 15 minutes. The weather data (such as external temperature, solar radiation etc.) are derived from the Meteonorm database. The solar gains are calculated by the software Trnsys from the input of the Meteonorm file. All the cases under investigation refer to the period when the heating system is switched on (winter period) that is for Bologna from October 15 to April Description of the simulated cases 3.1 Case 0 This is the reference case and represents the preretrofitting condition, characterized by the features illustrated in the previous paragraph. All the windows have a thermal transmittance of 2.85 Wm 2 K -1. The ventilation operates at the flow rate illustrated in table 3 with total external fresh air. The infiltration is set at the rate of 0.4 vol h Case 1 Case 1 refers to the replacement of all the windows with new frames and low low-emissivity glass having a thermal transmittance of 1.6 Wm 2 K -1. The ventilation works at the same conditions as Case 0, but the infiltration is reduced to the rate of 0.2 vol h Case 2 This is characterized by the introduction of a heat recovery ventilation system that can save energy from the ejected air, as depicted in Figure 2. The windows remain the same as Case 0. The model employs a total energy recovery with an enthalpy wheel silica gel loaded, able to exchange both heat and humidity. The sensible and latent effectiveness of the heat recovery system are defined as follows: TS S T where: R T T O O X S L X R X X TS and XS are respectively the temperature and the humidity ratio of the supply air. TO and XO represent the temperature and the humidity ratio of the external air (outdoor air). TR and XR are respectively the temperature and the humidity ratio of the extracted air (return air). The heat recovery efficiency values adopted in the simulations derived from the Jeong and Mumma correlation. The authors developed effectiveness correlations as a function of inlet air temperature, relative humidity, and face velocity. In the simulation, the heat recovery is designed to work with a time variable effectiveness and a face velocity of 3 m s -1. The ventilation system extracts air from the two corridors, with the flow rate of 1163 m 3 h -1 for each floor. The fresh air enters the two receptions, the two conference rooms and the six offices at the flow rate illustrated in Table 3. The air leaves the heat recovery at the temperature TS and at the humidity ratio XS which are a time dependent values. The electric power needed for the heat recovery at the design condition is of 500 W. Finally, it is important to highlight that 0.4 air changes per hour for infiltration are considered. O O 283

4 Paolo Valdiserri 3.4 Case 3 Case 3 contemplates both the replacement of the windows (described in Case1) and the introduction of the total energy recovery (described in Case 2). This case considers a rate of 0.2 vol h -1 for infiltration. of 85% for the heating and humidification system, the primary energy for heating and humidification is kwh and 6930 kwh respectively. Table 5 Case 1: Energy need for heating and humidification Energy need [kwh] for Month Heating Humidification 4. Simulation results 4.1 Case 0 The energy need for heating and humidification in the winter period is shown in Table 4: Table 4 Case 0: Energy need for heating and humidification Energy need [kwh] for Month Heating Humidification October November December January February March April TOTAL The amount of energy need requested for ventilation and infiltration is equal to kwh and 9718 kwh, respectively. Given an energy efficiency of 85% for the heating and humidification system, the primary energy for heating and humidification is kwh and 7925 kwh, respectively. 4.2 Case 1 The energy need for heating and humidification in the winter period can be seen in Table 5. Since the new windows are placed, the infiltration is reduced and the energy need for infiltration becomes 4933 kwh. Considering energy efficiency October November December January February March April TOTAL Case 2 Table 6 shows the energy need for heating and humidification in the winter period: Table 6 Case 2: Energy need for heating and humidification Energy need [kwh] for Month Heating Humidification October November December January February March April TOTAL The energy need for ventilation is equal to 2185 kwh. Considering energy efficiency of 85% for the 284

5 Study of the energy performance of a retrofitting office heating and humidification system, the primary energy for heating and humidification is kwh and 1428 kwh respectively. In this case, the electric energy need for heat recovery accounts for an additional 786 kwh. Considering a conversion coefficient of 0.46, the primary energy for the ventilation recovery system is 1709 kwh. 4.4 Case 3 The energy need for heating and humidification in the winter period for case 3 is highlighted in Table 7: Table 7 Case 3: Energy need for heating and humidification Energy need [kwh] for Month Heating Humidification October November December January February March April TOTAL Considering energy efficiency of 85% for the heating and humidification system, the primary energy for heating and humidification is kwh and 736 kwh respectively. The primary energy for the recovery system is 1709 kwh. 4.5 Comparison between the different solutions Table 8 shows the primary energy demands for the different cases analysed. The primary energy include the energy for heating, humidification and the operation of the total recovery. Table 8 Primary energy for heating, humidification and recovery electricity for the four different cases. Primary energy [kwh] Month Case 0 Case 1 Case 2 Case 3 October November December January February March April TOTAL A mere comparison of the primary energy request among the simulated cases shows that case 3 (where the combination of window replacement and the total energy recovery introduction) is the most efficient. The primary energy saved in the different scenarios is: - Scenario 1 (Case 1 versus Case 0): 9544 kwh; - Scenario 2 (Case 2 versus Case 0): kwh; - Scenario 3 (Case 3 versus Case 0): kwh; - Scenario 4 (Case 3 versus Case 1): kwh. The latter scenario was included to evaluate the advantages of the heat recovery installation following the windows replacement. 5. Economic issues The two retrofitting solutions presented in this study aim at decreasing energy demand and improving energy performance of the office block. Nevertheless, the application of energy saving measures usually needs to be evaluated in relation to economic assessments. Simple Payback Time (SPBT) and Net Present Value (NPV) are used as financial parameters for evaluating the economic feasibility of the different approach. 285

6 Paolo Valdiserri I0 SPBT S where: NPV I LS Sn n 1 - I0 is the initial investment cost of the project, - S is the energy saving evaluated at year 0, - Sn is the energy saving for year n, - Cn is the maintenance cost for year n, - n is the time period, - LS is the lifespan, - r is the cost of capital. The economic analysis was carried out for the retrofitting cases in the four different scenarios and was based on the technical-economic situation in Italy in The following data have been used for the evaluation: - cost of the energy: natural gas: 0.10 /kwh, electricity: 0.18 /kwh, - cost for replacement windows: , - cost for installing the heat recovery system: The yearly cost for heating, humidification and electricity for heat recovery are reported below: Case 0: 5,675 Case 1: 4,721 Case 2: 3,885 Case 3: 2,964 In Table 9 the initial investment, the energy saving obtained during the first year since the retrofitting, and the SPT are reported. Table 9 Initial investment, energy saving during the first year and Simple Payback Time for the four different scenarios. 0 1 r C n n Sc. 1 Sc. 2 Sc. 3 Sc. 4 Investment ( ) Energy saving ( ) SPBT (years) NPV is calculated for each scenario considering different increments of the cost of energy (2%, 4% or 6%). In the present evaluation, we considered a lifespan of 30 years for windows, and of 15 years for the heat recovery system. According to the Italian regulation on energy saving, it is possible to claim a tax refund of 65% of the cost of the investment over 10 years. NPV was reported either without tax refund claim (i.e. NPV(0)) or considering a 65% tax refund over 10 years (i.e. NPV(65)). NPV calculated for the different scenarios are reported in Tables Table 10 Net Present Value calculated for Scenario 1 (Case 1 vs Case 0) at different increment of the cost of energy (i) considering or not the tax refund of 65% - lifespan 30 years. Scenario 1 i = 2% i = 4% i =6% NPV (0) NPV (65) In the evaluation of NPV, the maintenance cost of the heat recovery system (1% per year, revaluated at 2% of inflation) was taken into account. In the case of Scenario 2 (Table 11), the value of NPV was reported at two time points: i) 15 years (the lifespan of the recovery system), and ii) 30 years. In the case of the latter time points it is necessary to add the cost of the heat recovery replacement and extraordinary maintenance works on the entire system, for a total amount of 9,421 (to be paid 15 years after the retrofitting). Table 11 Net Present Value calculated for Scenario 2 (Case 2 vs Case 0) at different increment of the cost of energy (i) considering or not the tax refund of 65%, after 15 years and after 30 years. Scenario 2 i = 2% i = 4% i =6% NPV (0) 15ys NPV (65) 15ys NPV (0) 30 ys NPV (65) 30 ys In the case of Scenario 3 and 4 (Table 12-13) the evaluation of NPV was done only for time point 30 years, considering the replacement of the heat recovery and other extraordinary maintenance works after 15 years. 286

7 Study of the energy performance of a retrofitting office Table 12 Net Present Value calculated for Scenario 3 (Case 3 vs Case 0) at different increment of the cost of energy (i) considering or not the tax refund of 65% - lifespan 30 years. (Scenario 2) is better than the combination of the two investments (Scenario 3). Scenario 3 i = 2% i = 4% i =6% NPV (0) NPV (65) Table 13 Net Present Value calculated for Scenario 4 (Case 4 vs Case 1) at different increment of the cost of energy (i) considering or not the tax refund of 65% - lifespan 30 years. Scenario 4 i = 2% i = 4% i =6% NPV (0) Figure 3 Cash flows considering an increment of 4% in the cost of energy, without tax refund for Scenario 1, 2 and scenario 1 scenario 2 scenario 3 NPV (65) Discussion The conducted analysis highlighted that replacing windows (Scenario 1) does not produce a significant energy saving. Moreover, the SPBT is 22 years, a very long period of time compared to a 30- year lifespan. Conversely, the installation of a heat recovery system seems a valid alternative for saving energy, with an SPBT of 7.8 and 8 years, for Scenario 2 and Scenario 4 respectively. These observations are supported by the values of NPV shown in tables Fig. 3 and Fig. 4 represent the variation of Net Present Value during the 30 years for the different scenarios analysed with or without the tax refund. Here, NPV was calculated using an increment of the cost of energy of 4% per year. The curve of NPV for Scenario 4 was similar to the one of Scenario 2, and it not shown. Figure 3 shows that the retrofitting solution with the highest NPV is the one which includes both windows replacement and the setting of a heat recovery system (Scenario 3). However, this solution is the one which requires a major investment. After 30 years, the difference of NPV between Scenario 3 and Scenario 2 is less than 7,000. For this reason it appears that the installation of the heat recovery system alone The deflection of the curves of Scenario 2 and 3 at the end of year 14 is due the cost of the replacement of the heat recovery and extraordinary maintenance at year 15. Figure 4 Cash flows considering an increment of 4% in the cost of energy, and 65% of tax refund in 10 years for Scenario 1, 2 and In Figure 4, the change of the slope at year ten is due to the end of the period of the tax refund. As shown previously without tax refund (Figure 3), also Figure 4 illustrates that the highest value of NPV is obtained with Scenario 3. In this case, at the end of the 10 years of tax refund the NPV values are roughly the same for Scenario 2 and Scenario 3. After 30 years the NPV difference between the two scenarios is about 17,700. For these two reasons, in the case of the tax refund, Scenario 3 is to be preferred. scenario 1 scenario 2 scenario 3 287

8 Paolo Valdiserri 7. Conclusion In the present work, a dynamic simulation of an existing office building, located in Bologna, Italy was performed, where different energy saving variations were applied. Two different strategies to enhance the energy performance were used. The first consisted in reducing the heat transfer by transmission, the other implied the decrease of the heat transfer by ventilation. Potential energy savings were calculated by transient simulation using Trnsys software and three hypothetic retrofitting cases were exploited. The first took into account the replacement of all the windows, the second consisted in installing a total energy ventilation recovery system and the last one contemplated both the solutions. Finally, an evaluation of the simple payback time and the net present value was performed. From the conducted analysis, only changing the windows (Scenario 1) does not produce an interesting value of NPV, unless one could benefit from a tax refund. Notably, the installation of a total energy recovery system resulted in sensible reduction of energy consumption and gave good values of NPV for all the three different analysed variation of the cost of energy. This is particularly relevant since the case studied was an office with high ventilation flow rate to guarantee a good air quality. Clearly, when the cost of energy arises, individuals are driven to find energy-saving measures. Nevertheless, given the actual cost of energy, energy-saving measures in building renovation and subsequent maintenance, the key strategy to make the retrofitting on existing dwellings economically appealing is to introduce or maintain tax refunding. References Directive, 2002/91/EC of the European Parliament and of the Council of 16 December 2002 on the energy performance of buildings. Directive 2010/31/EU of the European Parliament and of the Council of 19 May 2010 on the energy performance of buildings. Dodoo A., L. Gustavssona L., Sathrea R., Primary energy implications of ventilation heat recovery in residential buildings, Energy and Buildings, vol. 43, pp , European Commission, 2020 Vision: Saving energy, 2011, web accessed at publications/saving-energy-2011.pdf. Jeong J., Mumma S.A., Practical thermal performance correlations for molecular sieve and silica gel loaded enthalpy wheels, Applied Thermal Engineering, vol. 25, pp , Legislative Decree n 192, August 19, Legislative Decree n 311, December 29, Legislative Decree n 28, March 3, Simonson C., Energy consumption and ventilation performance of naturally ventilated ecological house in a cold climate, Energy and Buildings, vol. 37, pp , Solar Energy Laboratory, Manual of TRNSYS 17 a TRaNsient SYstem Simulation program, Solar Energy Laboratory, University of Wisconsin- Madison, 2012.Reference List, Entry number 2. Reference style according to Chigaco Manual of Style. Paragraph style: Reference List Entry. UNI EN 308, Heat exchangers - Test procedures for establishing performance of air to air and flue gases heat recovery devices, Acknowledgement The Author wish to thank the Italian Ministry of Education, University and Research for funding this study. 288

Energy performance of a ventilation system for an apartment according to the Italian regulation

Energy performance of a ventilation system for an apartment according to the Italian regulation Int J Energy Environ Eng (2016) 7:353 359 DOI 10.1007/s40095-014-0159-4 ORIGINAL RESEARCH Energy performance of a ventilation system for an apartment according to the Italian regulation P. Valdiserri C.

More information

Energy performance of a ventilation system for a block of apartments with a ground source heat pump as generation system

Energy performance of a ventilation system for a block of apartments with a ground source heat pump as generation system Journal of Physics: Conference Series PAPER OPEN ACCESS Energy performance of a ventilation system for a block of apartments with a ground source heat pump as generation system To cite this article: M

More information

Chapter 6. Space heating load

Chapter 6. Space heating load Chapter 6 Space heating load 1 Outdoor Design Conditions Heating systems should provide just enough heat to match the heat loss from the structure. Local knowledge should be obtained for design conditions.

More information

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models L. Pagliano et al, I: Optimization of air tightness and night ventilation for Passive houses in Italian climates... 1 Optimization of air tightness and night ventilation for Passive houses in Italian climates

More information

ENERGY EFFICIENT RETROFIT MEASURES GUIDE

ENERGY EFFICIENT RETROFIT MEASURES GUIDE ENERGY EFFICIENT RETROFIT MEASURES GUIDE ENERGY EFFICIENCY RETROFIT PROGRAM FOR LOW-INCOME HOUSEHOLDS CO-OP COMPONENT For nonprofit continuing housing cooperatives listed in the Québec Enterprise Register

More information

AM-55, AM-56) B U I L D I N G P A R T N E R S H I P S F O R E N E R G Y S E C U R I T Y

AM-55, AM-56) B U I L D I N G P A R T N E R S H I P S F O R E N E R G Y S E C U R I T Y Nearly zero-energy building and components of the DIRECTIVE on energy performance of buildings 2010/31/EU Albin Zsebik, PhD, CEM Improving university curricula in the areas of a) energy efficiency in the

More information

SUMMER THERMAL COMFORT IN TYPICAL FRENCH RESIDENTIAL BUILDINGS: IMPACT ASSESSMENT OF BUILDING ENVELOPE INSULATION ENHANCEMENT

SUMMER THERMAL COMFORT IN TYPICAL FRENCH RESIDENTIAL BUILDINGS: IMPACT ASSESSMENT OF BUILDING ENVELOPE INSULATION ENHANCEMENT 13th Conference of International Building Simulation Association, Chambéry, France, August 26-28 SUMMER THERMAL COMFORT IN TYPICAL FRENCH RESIDENTIAL BUILDINGS: IMPACT ASSESSMENT OF BUILDING ENVELOPE INSULATION

More information

ADVANCED FAÇADES AND HVAC SYSTEMS: PRELIMINARY RESULTS OF FULL-SCALE MONITORING

ADVANCED FAÇADES AND HVAC SYSTEMS: PRELIMINARY RESULTS OF FULL-SCALE MONITORING ADVANCED FAÇADES AND HVAC SYSTEMS: PRELIMINARY RESULTS OF FULL-SCALE MONITORING M. Kragh, M. Colombari and M. Zobec Permasteelisa Group, Research & Engineering, 31020 San Vendemiano (TV), Italy www.permasteelisa.com,

More information

Active solar heating system with concrete plate heating analysed with dynamical thermal simulations

Active solar heating system with concrete plate heating analysed with dynamical thermal simulations Active solar heating system with concrete plate heating analysed with dynamical thermal simulations Dr. D. Pahud SUPSI DCT Laboratory of Energy, Ecology and Economy, phone + 41 91 935 13 53, fax + 41 91

More information

Thermal comfort analysis in a passive house using dynamic simulations*

Thermal comfort analysis in a passive house using dynamic simulations* Revista Română de Inginerie Civilă, Volumul 4 (2013), Numărul 3 Matrix Rom Thermal comfort analysis in a passive house using dynamic simulations* Tiberiu Catalina 1 1 Technical University of Civil Engineering,

More information

Effects of the use of DIN on the energetic assessment of residential buildings reflection on the calculation

Effects of the use of DIN on the energetic assessment of residential buildings reflection on the calculation Abstract Effects of the use of DIN 18599 on the energetic assessment of residential buildings reflection on the calculation approaches The research report was financially supported by the research initiative

More information

A Study on the Evaluation of Heating and Cooling Energy Efficiency in Residential Buildings for Climatic Zones of Turkey

A Study on the Evaluation of Heating and Cooling Energy Efficiency in Residential Buildings for Climatic Zones of Turkey Journal of Energy and Power Engineering 8 (2014) 20452052 D DAVID PUBLISHING A Study on the Evaluation of Heating and Cooling Energy Efficiency in Residential Buildings for Climatic Zones of Turkey Suzi

More information

ANALYSIS OF ENVELOPE THERMAL BEHAVIOUR THROUGH PARAMETRIC STUDIES. Civil Engineer, PhD, Assistant Professor, Civil Engineering Department (3)

ANALYSIS OF ENVELOPE THERMAL BEHAVIOUR THROUGH PARAMETRIC STUDIES. Civil Engineer, PhD, Assistant Professor, Civil Engineering Department (3) Eighth International IBPSA Conference Eindhoven, Netherlands August 11-14, 2003 ANALYSIS OF ENVELOPE THERMAL BEHAVIOUR THROUGH PARAMETRIC STUDIES Chvatal, Karin M. S. (1), Corvacho, M. Helena P. (2), Maldonado,

More information

Thermal Performance of Retrofitted Envelopes with Internal Insulation: A Comparative Analysis

Thermal Performance of Retrofitted Envelopes with Internal Insulation: A Comparative Analysis PLEA2013-29th Conference, Sustainable Architecture for a Renewable Future, Munich, Germany 10-12 September 2013 Thermal Performance of Retrofitted Envelopes with Internal Insulation: A Comparative Analysis

More information

BUILDING DESIGN AND THERMAL INERTIA: WHEN, WHY, WHERE

BUILDING DESIGN AND THERMAL INERTIA: WHEN, WHY, WHERE Int. Journal for Housing Science, Vol.34, No.4 pp. 221-231, 2010 Published in the United States BUILDING DESIGN AND THERMAL INERTIA: WHEN, WHY, WHERE R. Albatici, S. Penasa Department of Civil and Environmental

More information

Towards nzeb buildings: a historical building case study

Towards nzeb buildings: a historical building case study Towards nzeb buildings: a historical building case study The recast of EU Directive 2010/31 introduced the concept of (nearly) zero energy building (NZEB). In Italy this challenge is remarkable: existing

More information

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS Bjarne W. Olesen Ph. D, International Centre for Indoor Environment and Energy, Department of Mechanical Engineering, Technical

More information

The main mode of air change of rooms is Ventilation. Ventilation and Energy maybe not that irreconcilable. articles

The main mode of air change of rooms is Ventilation. Ventilation and Energy maybe not that irreconcilable. articles Ventilation and Energy maybe not that irreconcilable Vítor M. S. Leal Department of Mechanical Engineering Faculty of Engineering of the University of Porto vleal@fe.up.pt Hugo R. R. Santos Department

More information

Comparative Study On Simulation Tools Of Annual Heat Load For Energy Management Y. Takahashi 1 *, G. Yoon 1, M. Yoshinaga 2, and R. Chiba 3 1 Graduate

Comparative Study On Simulation Tools Of Annual Heat Load For Energy Management Y. Takahashi 1 *, G. Yoon 1, M. Yoshinaga 2, and R. Chiba 3 1 Graduate Comparative Study On Simulation Tools Of Annual Heat Load For Energy Management Y. Takahashi 1 *, G. Yoon 1, M. Yoshinaga 2, and R. Chiba 3 1 Graduate School of Design and Architecture, Nagoya City University,

More information

Analysis of different shading strategies on energy demand and operating cost of office building

Analysis of different shading strategies on energy demand and operating cost of office building Analysis of different shading strategies on energy demand and operating cost of office building Kwiatkowski, J 1,2 ; Rucińska, J 1,2 ; Panek, A 1,2 1 Warsaw University of Technology, Faculty of Environmental

More information

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Healthy Buildings 217 Europe July 2-5, 217, Lublin, Poland Paper ID 89 ISBN: 978-83-7947-232-1 THERMAL RETROFIT OF A RESIDENTIAL BUILDING IN ROMANIA TO REACH LOW-CONSUMPTION ENERGY TARGETS Andrei DAMIAN

More information

Demonstration of modeling of radiant cooling system in design builder. Prashant Bhanware & Bharath Reddy

Demonstration of modeling of radiant cooling system in design builder. Prashant Bhanware & Bharath Reddy Demonstration of modeling of radiant cooling system in design builder Prashant Bhanware & Bharath Reddy CONTENTS Introduction to Design Builder Building Energy Simulation Modeling procedure Making a model

More information

Optimisation of an HVAC system for energy saving and thermal comfort in a university classroom

Optimisation of an HVAC system for energy saving and thermal comfort in a university classroom Optimisation of an HVAC system for energy saving and thermal comfort in a university classroom Giovanni Semprini DIN / CIRI, University of Bologna, Bologna, Italy Cosimo Marinosci DIN / CIRI, University

More information

Efficient and smart climate shell. refurbishment of residential buildings PART OF SMART SOLUTION 1: EFFICIENT AND SMART CLIMATE SHELL REFURBISHMENT

Efficient and smart climate shell. refurbishment of residential buildings PART OF SMART SOLUTION 1: EFFICIENT AND SMART CLIMATE SHELL REFURBISHMENT 6 Efficient and smart climate shell FACTSHEET refurbishment of residential buildings PART OF SMART SOLUTION 1: EFFICIENT AND SMART CLIMATE SHELL REFURBISHMENT Fig. 1: Image: www.idae.es LOW ENERGY DISTRICT

More information

ZEMedS ds: Case studies

ZEMedS ds: Case studies ZEMedS: Case studies Case study: ITC EINSTEIN High School, Ancona, Italy The sole responsibility for the content of this publication lies with the authors. It does not necessarily reflect the opinion of

More information

A Case Study of Energy Demand in Housing Units

A Case Study of Energy Demand in Housing Units A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar 1, Former Graduate Student Dr. Sudhir Misra 1, Professor Dr. Naveen Tiwari 2, Associate Professor 1 Department of Civil Engineering,

More information

EFFECTS OF WEATHERS AND INDOOR TEMPERATURES ON PERFORMANCE OF ENERGY RECOVERY VENTILATOR. Yanping Zhou, Jingyi Wu, Ruzhu Wang

EFFECTS OF WEATHERS AND INDOOR TEMPERATURES ON PERFORMANCE OF ENERGY RECOVERY VENTILATOR. Yanping Zhou, Jingyi Wu, Ruzhu Wang EFFECTS OF WEATHERS AND INDOOR TEMPERATURES ON PERFORMANCE OF ENERGY RECOVERY VENTILATOR Yanping Zhou, Jingyi Wu, Ruzhu Wang (Institute of Refrigeration and Cryogenics, Shanghai Jiaotong University, Shanghai,

More information

ZEMedS: Case studies

ZEMedS: Case studies ZEMedS: Case studies Case study: ANTONIO SALVETTI Primary School, Colle di Val d'elsa, Italy The sole responsibility for the content of this publication lies with the authors. It does not necessarily reflect

More information

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates Kittitach Pichatwatana, and Fan Wang Abstract This paper examines the TAS computer

More information

Passive Houses Worlswide: International Developments

Passive Houses Worlswide: International Developments Passive Houses Worlswide: International Developments Henk Kaan, ECN Energy Research Centre of the Netherlands, P.O. Box 1, 1755 ZG Petten, The Netherlands, Isolda Strom, DHV Building and Industry, P.O.

More information

Passive Houses in South West Europe

Passive Houses in South West Europe Dr. Wolfgang Feist Passivhaus Institut Rheinstraße 44/46 D-64283 Darmstadt www.passiv.de Passive Houses in South West Europe A quantitative investigation of some passive and active space conditioning techniques

More information

Understanding "Heat Load & Psychometric. by Djunaidi HS

Understanding Heat Load & Psychometric. by Djunaidi HS Understanding "Heat Load & Psychometric by Djunaidi HS Welcome To The Heat Load Calculation Course 2 3 Understanding Of Heat Load (Human Comfort) 1) Heat Load - Classified into 2 main types : 1. Sensible

More information

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION

CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating

More information

IMPACT OF USING DIFFERENT MODELS IN PRACTICE A CASE STUDY WITH THE SIMPLIFIED METHODS OF ISO STANDARD AND DETAILED MODELLING PROGRAMS

IMPACT OF USING DIFFERENT MODELS IN PRACTICE A CASE STUDY WITH THE SIMPLIFIED METHODS OF ISO STANDARD AND DETAILED MODELLING PROGRAMS IMPACT OF USING DIFFERENT MODELS IN PRACTICE A CASE STUDY WITH THE SIMPLIFIED METHODS OF ISO 13790 STANDARD AND DETAILED MODELLING PROGRAMS Kokogiannakis Georgios 1, Clarke Joe 1, Strachan Paul 1 1 Energy

More information

PASSIVHAUS Designed for you to enjoy maximum comfort with minimum energy.

PASSIVHAUS Designed for you to enjoy maximum comfort with minimum energy. PASSIVHAUS Designed for you to enjoy maximum comfort with minimum energy. + Energy efficiency + Savings +Comfort WHAT IS PASSIVHAUS? The Passivhaus (Passive House) standard is the most stringent international

More information

S. LONGO. The paper shows analysis of the impact on thermal comfort of natural ventilation in a nonresidential Mediterranean case-study.

S. LONGO. The paper shows analysis of the impact on thermal comfort of natural ventilation in a nonresidential Mediterranean case-study. Natural ventilative cooling in school buildings in Sicily M. CELLURA maurizio.cellura@unipa.it F. GUARINO guarino@dream.unipa.it S. LONGO sonia.longo@unipa.it M. MISTRETTA University of Reggio Calabria

More information

Computational and the real energy performance of a single-family residential building in Poland an attempt to compare: a case study

Computational and the real energy performance of a single-family residential building in Poland an attempt to compare: a case study Computational and the real energy performance of a single-family residential building in Poland an attempt to compare: a case study Piotr Kowalski 1,*, and Paweł Szałański 1 1 Department of Air Conditioning,

More information

Module 3.6. Calculation of U-value for elements adjacent to an unheated space.

Module 3.6. Calculation of U-value for elements adjacent to an unheated space. Module 3.6 Calculation of U-value for elements adjacent to an unheated space. Learning Outcomes On successful completion of this module learners will be able to - Describe the procedure for the calculation

More information

Solar gains in the glazing systems with sun-shading

Solar gains in the glazing systems with sun-shading 729 Solar gains in the glazing systems with sun-shading G. Oliveti, N. Arcuri, R. Bruno, M. De Simone University of Calabria, Italy ABSTRACT This paper presents the optical and thermal performances of

More information

Dynamic simulation of buildings: Problems and solutions Università degli Studi di Trento

Dynamic simulation of buildings: Problems and solutions Università degli Studi di Trento Dynamic simulation of buildings: Problems and solutions Università degli Studi di Trento Paolo BAGGIO The basic problem To design (and operate) energy efficient buildings, accurate modeling tools are needed.

More information

Energy study of a non-residential and historic building in transient conditions

Energy study of a non-residential and historic building in transient conditions Energy and Sustainability VI 511 Energy study of a non-residential and historic building in transient conditions S. Grignaffini, M. Romagna & A. Vallati Department of Astronautical, Electrical and Energetic

More information

Solar cooling design: a case study

Solar cooling design: a case study Eco-Architecture IV 399 Solar cooling design: a case study S. Grignaffini & M. Romagna Department of Astronautic, Electric and Energetic Engineering, Sapienza, University of Rome, Italy Abstract Throughout

More information

Evaluation methods for indoor environmental quality assessment according to EN15251

Evaluation methods for indoor environmental quality assessment according to EN15251 Summary of this article was published in the REHVA European HVAC Journal Vol 49, Issue 4 (August), 2012, pages 14-19, available at http://www.rehva.eu/en/rehva-european-hvac-journal. Evaluation methods

More information

Air distribution and temperature control in classrooms

Air distribution and temperature control in classrooms Air distribution and temperature control in classrooms Jarek Kurnitski D.Sc., Docent HELSINKI UNIVERSITY OF TECHNOLOGY Laboratory of Heating, Ventilation and Air Conditioning Swegon Air Academy 11.6.2008

More information

The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort

The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort Ongun Berk Kazanci, Bjarne W. Olesen 1 1 International Center for Indoor Environment and

More information

Residential buildings retrofit: the role of solar technologies

Residential buildings retrofit: the role of solar technologies Residential buildings retrofit: the role of solar technologies Chiara Dipasquale 1, Roberto Fedrizzi 1 and Alessandro Bellini 1 1 Institute for Renewable Energy, Eurac Research, Bolzano (Italy) Abstract

More information

Effect of passive cooling strategies on overheating in low energy residential buildings for Danish climate

Effect of passive cooling strategies on overheating in low energy residential buildings for Danish climate Proceedings of 8 th Windsor Conference: Counting the Cost of Comfort in a changing world Cumberland Lodge, Windsor, UK, 10-13 April 2014. London: Network for Comfort and Energy Use in Buildings, http://nceub.org.uk

More information

Indoor environment for energy performance of buildings a new European draft standard

Indoor environment for energy performance of buildings a new European draft standard International Conference Passive and Low Energy Cooling 1109 Indoor environment for energy performance of buildings a new European draft standard O. Seppänen Helsinki University of Technology, Finland

More information

Two-Pipe Chilled Beam System for Both Cooling and Heating of Office Buildings

Two-Pipe Chilled Beam System for Both Cooling and Heating of Office Buildings Downloaded from vbn.aau.dk on: March 30, 2019 Aalborg Universitet Two-Pipe Chilled Beam System for Both Cooling and Heating of Office Buildings Afshari, Alireza; Gordnorouzi, Rouzbeh; Hultmark, Göran;

More information

Aalborg Universitet Two-Pipe Chilled Beam System for Both Cooling and Heating of Office Buildings General rights Take down policy

Aalborg Universitet Two-Pipe Chilled Beam System for Both Cooling and Heating of Office Buildings General rights Take down policy Aalborg Universitet Two-Pipe Chilled Beam System for Both Cooling and Heating of Office Buildings Afshari, Alireza; Gordnorouzi, Rouzbeh; Hultmark, Göran; Bergsøe, Niels Christian Published in: Proceedings

More information

COOLING LOAD ESTIMATION OF A ROOM

COOLING LOAD ESTIMATION OF A ROOM COOLING LOAD ESTIMATION OF A ROOM Prof. Deepak Kumar Yadav 1, Aviral Srivastava 2, Ayush Chauhan 3, Gaurang Tripathi 4, Ankur Kumar 5 1Assistant Professor, Mechanical Engineering, IMS Engineering College,

More information

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016 Aalborg Universitet CLIMA 2016 - proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols Publication date: 2016 Document Version Publisher's PDF, also known as Version of record Link to publication

More information

Thermal insulation of buildings and cooling demand

Thermal insulation of buildings and cooling demand 411 Thermal insulation of buildings and cooling demand C. Hamans Rockwool International S.A.,The Netherlands ABSTRACT Thermal insulation in the warm climate can reduce the energy demand for cooling in

More information

A, B, C, D VENTILATION SYSTEMS: COMPARISON

A, B, C, D VENTILATION SYSTEMS: COMPARISON A, B, C, D VENTILATION SYSTEMS: COMPARISON ATIC-ULg Ventilation day 19/11/2015 Samuel Gendebien University of Liège Table of content Objectives of the presentation Introduction - Key figures Definitions

More information

Passive Houses for Arctic Climates

Passive Houses for Arctic Climates Downloaded from orbit.dtu.dk on: Feb 16, 2018 Passive Houses for Arctic Climates Vladyková, Petra; Rode, Carsten; Nielsen, Toke Rammer; Pedersen, Søren Published in: Passivhus Norden 2008 Publication date:

More information

Proceedings of Clima 2007 WellBeing Indoors

Proceedings of Clima 2007 WellBeing Indoors Energy Performances Of A Radiant Floor Heating System Supplied By Solar Collectors With Ventilation Stream Heating By An Air To Air And An Air To Water Heat Exchanger Oliveti G., Arcuri N., Bruno R., De

More information

PRINCIPLES AND POTENTIALS OF VENTILATIVE COOLING

PRINCIPLES AND POTENTIALS OF VENTILATIVE COOLING PRINCIPLES AND POTENTIALS OF VENTILATIVE COOLING PER HEISELBERG OPERATING AGENT IEA EBC ANNEX 62 BACKGROUND THE CURRENT DEVELOPMENT TOWARDS NEARLY- ZERO ENERGY BUILDINGS HAVE LEAD TO AN INCREASED NEED

More information

ZEMedS ds: Case studies

ZEMedS ds: Case studies ZEMedS: Case studies Case study: Don Milani Primary School, San Miniato, Italy The sole responsibility for the content of this publication lies with the authors. It does not necessarily reflect the opinion

More information

UNDERFLOOR AIR DISTRIBUTION INTEGRATED WITH AN INDIRECT AND DIRECT EVAPORATIVE COOLING ASSISTED 100% OUTDOOR AIR SYSTEM

UNDERFLOOR AIR DISTRIBUTION INTEGRATED WITH AN INDIRECT AND DIRECT EVAPORATIVE COOLING ASSISTED 100% OUTDOOR AIR SYSTEM UNDERFLOOR AIR DISTRIBUTION INTEGRATED WITH AN INDIRECT AND DIRECT EVAPORATIVE COOLING ASSISTED 100% OUTDOOR AIR SYSTEM YJ Seok, HJ Cho, SK Han and JW Jeong Department of Architectural Engineering, Sejong

More information

Available online at ScienceDirect. Energy Procedia 48 (2014 )

Available online at  ScienceDirect. Energy Procedia 48 (2014 ) Available online at www.sciencedirect.com ScienceDirect Energy Procedia 48 (2014 ) 1482 1492 Energy saving technology screening within the EU-project School of the Future Ove C. Mørck a, *, Anton J. Paulsen

More information

Reducing energy demand in non-domestic buildings: integrating smart facades, ventilation, and surface heating and cooling

Reducing energy demand in non-domestic buildings: integrating smart facades, ventilation, and surface heating and cooling Reducing energy demand in non-domestic buildings: integrating smart facades, ventilation, and surface heating and cooling Phil Jones, Shan Shan Hou and XiaoJun Li Welsh School of Architecture, Cardiff

More information

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort Energy-Efficient Passive House using thermal mass to achieve high thermal comfort Loa Andersson Managing Director RLI Byggdata AB rli@termodeck.com Alexander Engström Technical Director RLI Byggdata AB

More information

A FIELD STUDY OF A VENTILATED BEAM SYSTEM FEASIBILITY IN THE TROPICAL CLIMATE

A FIELD STUDY OF A VENTILATED BEAM SYSTEM FEASIBILITY IN THE TROPICAL CLIMATE A FIELD STUDY OF A VENTILATED BEAM SYSTEM FEASIBILITY IN THE TROPICAL CLIMATE Risto Kosonen 1, Freddie Tan 2 and Maija Virta 1 1 Halton Oy 2 CapitaLand Commercial ABSTRACT Ventilated beams systems are

More information

Engineers Ireland Cork Region CPD lecture series

Engineers Ireland Cork Region CPD lecture series Engineers Ireland Cork Region CPD lecture series NZEB and Emerging Legislation & SEAI s Deep Retrofit Pilot Programme Orla Coyle NZEB Programme Manager Conor Hanniffy Deep Retrofit Pilot Programme Manager

More information

Retrofit of an historical building toward NZEB

Retrofit of an historical building toward NZEB Available online at www.sciencedirect.com ScienceDirect Energy Procedia 00 (2015) 000 000 www.elsevier.com/locate/procedia 6th International Building Physics Conference, IBPC 2015 Retrofit of an historical

More information

CALCULATIONS OF COST-OPTIMAL LEVELS OF ENERGY PERFORMANCE REQUIREMENTS FOR RENOVATED BUILDINGS AND BUILDING ELEMENTS: A LATVIAN CASE

CALCULATIONS OF COST-OPTIMAL LEVELS OF ENERGY PERFORMANCE REQUIREMENTS FOR RENOVATED BUILDINGS AND BUILDING ELEMENTS: A LATVIAN CASE Green design and sustainable architecture CALCULATIONS OF COST-OPTIMAL LEVELS OF ENERGY PERFORMANCE REQUIREMENTS FOR RENOVATED BUILDINGS AND BUILDING ELEMENTS: A LATVIAN CASE Dr. phys. Staņislavs Gendelis

More information

Assessment of the energy demand in energy-saving office buildings from the viewpoint of variations of internal heat gains

Assessment of the energy demand in energy-saving office buildings from the viewpoint of variations of internal heat gains Assessment of the energy demand in energy-saving office buildings from the viewpoint of variations of internal heat gains Andrzej Baranowski 1,2 and Joanna Ferdyn-Grygierek 1,2 1 Silesian University of

More information

Achieving the nearly zero energy building concept - A study based on practical experience

Achieving the nearly zero energy building concept - A study based on practical experience Achieving the nearly zero energy building concept - A study based on practical experience SIMON PESCARI, VALERIU STOIAN, DANIEL DAN, DAN STOIAN Department of Civil Engineering and Equipment, Faculty of

More information

A STUDY ON DESIGN OPTIMIZATION OF A NEAR NET-ZERO ENERGY HOUSE

A STUDY ON DESIGN OPTIMIZATION OF A NEAR NET-ZERO ENERGY HOUSE Int. Journal for Housing Science, Vol.37, No.1 pp.23-31, 2013 Published in the United States A STUDY ON DESIGN OPTIMIZATION OF A NEAR NET-ZERO ENERGY HOUSE Narghes Doust, Gabriele Masera and Marco Imperadori

More information

POTROŠNJA ENERGIJE U STAMBENOM FONDU BEOGRADA PART 1: MODELING AND SIMULATION OF BUILDINGS AND HOUSES FROM REPRESENTATIVE SAMPLE

POTROŠNJA ENERGIJE U STAMBENOM FONDU BEOGRADA PART 1: MODELING AND SIMULATION OF BUILDINGS AND HOUSES FROM REPRESENTATIVE SAMPLE POTROŠNJA ENERGIJE U STAMBENOM FONDU BEOGRADA PART 1: MODELING AND SIMULATION OF BUILDINGS AND HOUSES FROM REPRESENTATIVE SAMPLE ENERGY CONSUMPTION IN BELGRADE HOUSEHOLDS SECTOR PRVI DEO: MODELIRANJE I

More information

Ceiling Radiant Cooling Panels

Ceiling Radiant Cooling Panels 2006, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc (wwwashraeorg) Published in ASHE Journal Vol 48, Oct 2006 For personal use only Additional reproduction, distribution,

More information

Modeling and Simulation of Energy Use and Indoor Thermal Environment of Highly-Insulated Buildings

Modeling and Simulation of Energy Use and Indoor Thermal Environment of Highly-Insulated Buildings Modeling and Simulation of Energy Use and Indoor Thermal Environment of Highly-Insulated Buildings Laurent Georges Energy and Process Engineering Department, Norwegian University of Science and Technology

More information

ENERGY SAVINGS, SIMULATIONS AND ECONOMIC ANALYSIS OF A GROUND SOURCE HEAT PUMP WITH VERTICAL BOREHOLE HEAT EXCHANGERS FOR A BELGIAN OFFICE BUILDING

ENERGY SAVINGS, SIMULATIONS AND ECONOMIC ANALYSIS OF A GROUND SOURCE HEAT PUMP WITH VERTICAL BOREHOLE HEAT EXCHANGERS FOR A BELGIAN OFFICE BUILDING - 1 - ENERGY SAVINGS, SIMULATIONS AND ECONOMIC ANALYSIS OF A GROUND SOURCE HEAT PUMP WITH VERTICAL BOREHOLE HEAT EXCHANGERS FOR A BELGIAN OFFICE BUILDING J. Desmedt, Expert, H. Hoes, Expert, Energy technology

More information

Cool Roof Case Studies

Cool Roof Case Studies Michele Zinzi ENEA Cool Roof Case Studies 09/03/2014 European Cool Roofs Council 1 Solar reflecting materials for the building envelope were a widely used construction technology The Mediterranean region

More information

TREES Training for Renovated Energy Efficient Social housing. Section 1 Techniques 1.2 Replacement of glazing

TREES Training for Renovated Energy Efficient Social housing. Section 1 Techniques 1.2 Replacement of glazing TREES Training for Renovated Energy Efficient Social housing Intelligent Energy -Europe programme, contract n EIE/05/110/SI2.420021 Section 1 Techniques 1.2 Replacement of glazing Bruno PEUPORTIER ARMINES

More information

Optimising Ventilative Cooling and Airtightness for [Nearly] Zero-Energy Buildings, IAQ and Comfort

Optimising Ventilative Cooling and Airtightness for [Nearly] Zero-Energy Buildings, IAQ and Comfort Copenhagen, Denmark Axelborg Building 10 11 October 2012 Joint Conference 33 rd AIVC Conference and 2 nd TightVent Conference Optimising Ventilative Cooling and Airtightness for [Nearly] Zero-Energy Buildings,

More information

1 Exam Prep Manual J Residential Load Calculation 8 th Edition Tabs and Highlights

1 Exam Prep Manual J Residential Load Calculation 8 th Edition Tabs and Highlights 1 Exam Prep Manual J Residential Load Calculation 8 th Edition Tabs and Highlights These 1 Exam Prep tabs are based on the Manual J Residential Load Calculation for Small Commercial Buildings, 8 th Edition.

More information

Renovation of a Detached Single-Family House into an Energy Efficient Low Energy House Larsen, Tine Steen; Maagaard, Steffen; Jensen, Rasmus Lund

Renovation of a Detached Single-Family House into an Energy Efficient Low Energy House Larsen, Tine Steen; Maagaard, Steffen; Jensen, Rasmus Lund Aalborg Universitet Renovation of a Detached Single-Family House into an Energy Efficient Low Energy House Larsen, Tine Steen; Maagaard, Steffen; Jensen, Rasmus Lund Published in: Proceedings of the 9th

More information

THE ROAD TO NEARLY ZERO-ENERGY BUILDINGS

THE ROAD TO NEARLY ZERO-ENERGY BUILDINGS Int. Journal for Housing Science, Vol.38, No.4 pp. 239-250, 2014 Published in the United States THE ROAD TO NEARLY ZERO-ENERGY BUILDINGS Z. Szalay Department of Architectural Engineering Budapest University

More information

A cooling tower combined with chilled ceiling: system optimisation

A cooling tower combined with chilled ceiling: system optimisation A cooling tower combined with chilled ceiling: system optimisation Ala Hasan 1, Mika Vuolle 1, Kai Sirén 1, Riikka Holopainen 2 and Pekka Tuomaala 2 1 Laboratory for HVAC-technology, Helsinki University

More information

Energy Efficiency in Building Active Design Part II

Energy Efficiency in Building Active Design Part II Energy Efficiency in Building Active Design Part II Presented by: CK Tang BSEEP Component 4 Manager Veritas Enviornment Sdn Bhd ck.tang@veritas.com.my Air Conditioning System System Sizing 1 Current Industry

More information

ENERGETIC MONITORING AND OPTIMIZATION OF A SOLAR HOUSE

ENERGETIC MONITORING AND OPTIMIZATION OF A SOLAR HOUSE Bulletin of the Transilvania University of Braşov Vol. 3 (52) - 2010 Series I: Engineering Sciences ENERGETIC MONITORING AND OPTIMIZATION OF A SOLAR HOUSE M. MOLDOVAN 1 I. VIŞA 1 A. DUŢĂ 1 Abstract: Into

More information

SectIon Energy Effldency

SectIon Energy Effldency SectIon 9.36. Energy Effldency The objective of this Code is to limit the probability that, as a resuft ofthe design or construction ofthe building, resources will be used in a manner that will have an

More information

Nearly Zero Energy Building in Lecco Modern technological building compared to an ancient Villa

Nearly Zero Energy Building in Lecco Modern technological building compared to an ancient Villa Nearly Zero Energy Building in Lecco Modern technological building compared to an ancient Villa Matteo BRASCA *, Oscar Luigi PAGANI **, Kanza RAUF*** * partner - AIACE S.r.l. società di ingegneria, contract

More information

Building Concepts for a mid-century energy-neutral society

Building Concepts for a mid-century energy-neutral society ECN-M--6-15 SET26-5 th International Conference on Sustainable Energy Technologies. Vicenza, Italy Page 1 of 8 Building Concepts for a mid-century energy-neutral society I.J. Opstelten, E.J. Bakker, B.J.

More information

School Tito Maccio Plauto Cesena (IT)

School Tito Maccio Plauto Cesena (IT) School Tito Maccio Plauto Cesena (IT) 1. INTRODUCTION PROJECT SUMMARY - Major renovation of a primary school, built in the 60s - 440 students, 50 employees - 20 classes (about 22 students) - Area: 6.420

More information

Evaluating the Building Performance of the Center for Promotion of Science in Block 39 in Belgrade, Serbia

Evaluating the Building Performance of the Center for Promotion of Science in Block 39 in Belgrade, Serbia Evaluating the Building Performance of the Center for Promotion of Science in Block 39 in Belgrade, Serbia Berrak Balci Abstract This paper presents the evaluation of the building performance of the previously

More information

Application of a Computer Model for Integrated Hygrothermal Building Analysis

Application of a Computer Model for Integrated Hygrothermal Building Analysis Application of a Computer Model for Integrated Hygrothermal Building Analysis Carsten Rode, Technical University of Denmark car@byg.dtu.dk Lars C. Sørensen Birch & Krogboe A/S LCS@birch-krogboe.dk Karl

More information

gskin Application Note: U-Value Measurement Case Study

gskin Application Note: U-Value Measurement Case Study 1 / 7 gskin Application Note: U-Value Measurement Case Study The overall energy consumption for housing is responsible for 35% of global energy consumption on average. In Europe, roughly 3 100 TWh (or

More information

Cost-Benefit Analysis of Dwelling Retrofit Options

Cost-Benefit Analysis of Dwelling Retrofit Options Cost-Benefit Analysis of Dwelling Retrofit Options The objective was to study the thermal behaviour of the existing house and suggest cost effective improvements. Over recent years the energy efficiency

More information

The requirement system of the Hungarian directive on the energy performance of buildings

The requirement system of the Hungarian directive on the energy performance of buildings Ŕ periodica polytechnica Architecture 39/2 (2008) 41 48 doi: 10.3311/pp.ar.2008-2.01 web: http:// www.pp.bme.hu/ ar c Periodica Polytechnica 2008 The requirement system of the Hungarian directive on the

More information

ENERGY DEMAND ANALYSIS AND ENERGY LABELLING OF NEW RESIDENTIAL BUILDINGS IN TUSCANY (ITALY)

ENERGY DEMAND ANALYSIS AND ENERGY LABELLING OF NEW RESIDENTIAL BUILDINGS IN TUSCANY (ITALY) ENERGY DEMAND ANALYSIS AND ENERGY LABELLING OF NEW RESIDENTIAL BUILDINGS IN TUSCANY (ITALY) F. Fantozzi, F. Leccese, G. Salvadori, G. Tuoni Department of Energy L. Poggi Faculty of Engineering, University

More information

Ceiling Radiant Cooling Panels

Ceiling Radiant Cooling Panels Copyright 2006, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc This posting is by permission from ASHE Journal This article may not be copied nor distributed in either paper

More information

The Elithis Tower is an experimental and demonstration. Elithis Tower in Dijon, France. nzeb case studies

The Elithis Tower is an experimental and demonstration. Elithis Tower in Dijon, France. nzeb case studies COM Elithis Tower in Dijon, France Elithis Tower, located in Dijon, France, provides strong evidence that net zero energy office buildings are achievable in near future. The building, which was designed

More information

Feasibility Study of Multiple-Pass Total Energy Recovery Ventilator with Built-in Economizer Using TRNSYS: A Case Study for Toronto, Ontario

Feasibility Study of Multiple-Pass Total Energy Recovery Ventilator with Built-in Economizer Using TRNSYS: A Case Study for Toronto, Ontario Feasibility Study of Multiple-Pass Total Energy Recovery Ventilator with Built-in Economizer Using TRNSYS: A Case Study for Toronto, Ontario Jun Long Zhang 1, Alan S. Fung 1 1 Department of Mechanical

More information

Energy consumption and thermal comfort in a passive house built in Romania

Energy consumption and thermal comfort in a passive house built in Romania Chapter 3 - High Performance Sustainable Building Solutions Energy consumption and thermal comfort in a passive house built in Romania Cristina Tanasa, Cristian Sabau, Daniel Dan & Valeriu Stoian Polytechnic

More information

THEORETICAL STUDY OF COOLING TECHNOLOGIES DRIVEN BY GEOTHERMAL ENERGY FOR USE IN TERTIARY BUILDINGS IN BELGIUM

THEORETICAL STUDY OF COOLING TECHNOLOGIES DRIVEN BY GEOTHERMAL ENERGY FOR USE IN TERTIARY BUILDINGS IN BELGIUM Proceedings of BS13: THEORETICAL STUDY OF COOLING TECHNOLOGIES DRIVEN BY GEOTHERMAL ENERGY FOR USE IN TERTIARY BUILDINGS IN BELGIUM Eric Dumont, Nicolas Heymans, Marie-Eve Duprez and Marc Frère Research

More information

Energy Audit. Project: ENergy Efficiency and Renewables SUPporting Policies in Local level for EnergY (ENER-SUPPLY) Work Package 4

Energy Audit. Project: ENergy Efficiency and Renewables SUPporting Policies in Local level for EnergY (ENER-SUPPLY) Work Package 4 Project: ENergy Efficiency and Renewables SUPporting Policies in Local level for EnergY (ENER-SUPPLY) Work Package 4 Energy Audit Date: Country: SERBIA Partner: University of Novi Sad (UNS) Building: Health

More information

ISO INTERNATIONAL STANDARD. Energy performance of buildings Calculation of energy use for space heating and cooling

ISO INTERNATIONAL STANDARD. Energy performance of buildings Calculation of energy use for space heating and cooling INTERNATIONAL STANDARD ISO 13790 Second edition 2008-03-01 Energy performance of buildings Calculation of energy use for space heating and cooling Performance énergétique des bâtiments Calcul des besoins

More information