Performance Analysis of Cooling Tower

Size: px
Start display at page:

Download "Performance Analysis of Cooling Tower"

Transcription

1 Performance Analysis of Cooling Tower M.V.H.Satish Kumar, Associate Professor, Department of Mechanical Engineering PVP Siddhartha Institute of Technology, Kanuru, Vijayawada 7. Andhra Pradesh, India. Abstract Power plants, some other industries produce a large quantity of waste heat in the form of hot water. In the present scenario, in most of the places, the water supply is limited and thermal pollution is also a serious concern. Considering the recent increase of interest in analysing these problems and solving them for the well being of the environment, this work is an attempt to deal with the technology, applications of cooling towers. In this present study, the factors affecting the performance like environmental conditions, cooling water quality have been studied on Induced draft cooling tower of 32 Mw thermal power plant. The performance parameters like range, approach, cooling capacity, evaporation loss liquid to gas ratio have been evaluated when the plant is operated at full load and part load under the same water flow rates.. Keywords Power plant, cooling tower, induced draft, range, approach, environmental conditions, cooling capacity, evaporation loss, L/G ratio, water flow rates. 1. INTRODUCTION The Cooling tower is a direct contact type heat exchanger. It is a semi-closed, evaporative cooler. The water is sprayed through a certain height and an air current passes over it. Some water evaporates and the heat of evaporation is extracted from falling water and surrounding air, thus water cool. NECESSITY OF COOLING THE CONDENSER WATER: The cooling water system is one of the most important systems of power plant and its availability predominantly decides the plant site. The high cost of water makes it necessary to use cooling towers for water cooled condensers. As the cooling water absorb the latent heat of steam in the condenser, the temperature of the water increases. The hot water coming out of the condenser cannot be used again in a closed system without pre reaches near to T s saturation temperature of steam at condenser pressure and the condenser vacuum cannot be maintained. Therefore it is absolutely necessary to pre cool the water coming out of condenser before using again. The cooling water requirement in an open system is about 50 times the flow of steam to the condenser. Even with closed cooling system using cooling towers, the requirement for cooling water is also considerably large as 5 to 8 kg/kw hr. This means a 1000 MW station will require about 100 thousand tunes of circulating water per day even with the use of cooling towers. 2. Merkel Theory: Dr. Merkel developed a cooling tower theory for the mass (evaporation of a small portion of water) and sensible heat transfer between the air and water in a counter flow cooling tower. The theory considers the flow of mass and energy from the bulk water to an interface, and then from the interface to the surrounding air mass. The flow crosses these two boundaries, each offering resistance resulting in gradients in temperature, enthalpy, and humidity ratio. Merkel demonstrated that the total heat transfer is directly proportional to the difference between the enthalpy of saturated air at the water temperature and the enthalpy of air at the point of contact with water. Q = K x S x (h w - h a ) Where, l Q = total heat transfer Btu/h l K = overall enthalpy transfer coefficient lb/hr.ft 2 l S = heat transfer surface ft 2. S = a x V, Which "a" means area of transfer surface per unit of tower volume. (ft 2 /ft 3 ), and V means an effective tower volume (ft 3 ). l h w = enthalpy of air-water vapor mixture at the bulk water temperature, Btu/Lb dry air l h a = enthalpy of air-water vapor mixture at the wet bulb temperature, Btu/Lb dry air The water temperature and air enthalpy are being changed along the fill and Merkel relation can only be applied to a small element of heat transfer surface ds. dq = d[k x S x (h w - h a )] = K x (h w - h a ) x ds The heat transfer rate from water side is Q = C w x L x Cooling Range, Where C w = specific heat of water = 1, ISSN: Page 442

2 L = water flow rate. Therefore, dq = d[c w x L x (tw 2 - tw 1 )] = C w x L x dtw. 3. Heat Balance Also, the heat transfer rate from air side is Q = G x (ha 2 - ha 1 ), where G = air mass flow rate Therefore, dq = d[g x (ha 2 - ha 1 )] = G x dha. Then, the relation of K x (h w - h a ) x ds = G x dha or K x (h w - h a ) x ds = C w x L x dtw are established, and these can be rewritten in K x ds = G / (h w - h a ) x dha or K x ds / L = C w / (h w - h a ) x dtw. By integration, This basic heat transfer equation is integrated by the four point Tchebycheff, which uses values of y at predetermined values of x within the interval a to b in numerically evaluating the integral The sum of these values of y multiplied by a constant times the interval (b - a) gives the desired value of the integral. In its four-point form the values of y so selected are taken at values of x of , , , and of the interval (b - a). For the determination of KaV/L, rounding off these values to the nearest tenth is entirely adequate. The approximate formula becomes: HEAT in = HEAT out WATER HEAT in + AIR HEAT in = WATER HEAT out + AIR HEAT out C w L 2 tw 2 + G h a1 = C w L 1 tw 1 + G h a2 The difference between L 2 (entering water flow rate) and L 1 (leaving water flow rate) is a loss of water due to the evaporation in the direct contact of water and air. This evaporation loss is a result of difference in the water vapor content between the inlet air and exit air of cooling tower. Evaporation Loss is expressed in G x (w 2 -w 1 ) and is equal to L 2 - L 1. Therefore, L 1 = L 2 - G x (w 2 -w 1 ) is established. Let's replace the term of L 1 in the right side of Eq. 2-1 with the equation of L 1 = L 2 - G x (w 2 -w 1 ) and rewrite. Then, C w L 2 tw 2 + G h a1 = C w [L 2 - G x (w 2 - w 1 )] x tw 1 + G h a2 is obtained. This equation could be rewritten in C w x L 2 x (tw 2 - tw 1 ) = G x (h a2 - h a1 ) - C w x t w1 x G x (w 2 - w 1 ). For the evaluation of KaV/L, In general, the 2nd term of right side is ignored to simplify the calculation under the assumption of G x (w 2 - w 1 ) = 0. Finally, the relationship of C w x L 2 x (tw 2 - tw 1 ) = G x (h a2 - h a1 ) is established and this can be expressed to C w x L x (t w2 - t w1 ) = G x (h a2 - h a1 ) again. Therefore, the enthalpy of exit air, h a2 = h a1 + C w x L / G x (t w2 - t w1 ) is obtained. The value of specific heat of water is Eq. 2-1 and the term of t w2 (entering water temperature) - t w1 ISSN: Page 443

3 (leaving water temperature) is called the cooling range. Simply, h a2 = h a1 + L/G x Range Consequently, the enthalpy of exit air is a summation of the enthalpy of entering air and the addition of enthalpy from water to air (this is a value of L/G x Range). In cross flow induced draft towers, the water enters at the top and passes over the fill. The air, however, is introduced at the side either on one side (single-flow tower) or opposite sides (double-flow tower). An induced draft fan draws the air across the wetted fill and expels it through the top of the structure. 4. Mechanical draft towers: Mechanical draft towers are available in the following airflow arrangements: a. Counter flow forced draft. b. Counter flow induced draft. c. Cross flow induced draft. In the counter flow induced draft design, hot water enters at the top, while the air is introduced at the bottom and exits at the top. Both forced and induced draft fans are used Fig. 2.7 Cross flow induced draft. 5. Performance Parameters: The measured parameters are used to determine the cooling tower performance in several ways. These are: Fig. 2.5 Counter flow forced draft Fig. 2.6 Counter flow induced draft Range: This is the difference between the cooling tower water inlet and outlet temperature. A high CT Range means that the cooling tower has been able to reduce the water temperature effectively, and is thus performing well. The formula is: CT Range ( C) = [CW inlet temp ( C) CW outlet temp ( C)] Approach: This is the difference between the cooling tower outlet coldwater temperature and ambient wet bulb temperature. The lower the approach the better the cooling tower performance. Although, both range and approach should be monitored, the `Approach is a better indicator of cooling tower performance. CT Approach ( C) = [CW outlet temp ( C) Wet bulb temp ( C)] Effectiveness: This is the ratio between the range and the ideal range (in percentage), i.e. difference between cooling water inlet temperature and ambient wet bulb temperature, or in other words it is = Range / (Range + Approach). The higher this ratio, the higher the cooling tower effectiveness. ISSN: Page 444

4 CT Effectiveness (%) = 100 x (CW temp CW out temp) / (CW in temp WB temp) Cooling capacity: This is the heat rejected in kcal/hr or TR, given as product of mass flow rate of water, specific heat and temperature difference. Evaporation loss: This is the water quantity evaporated for cooling duty. Theoretically the evaporation quantity works out to 1.8 m 3 for every 1,000,000 kcal heat rejected. The following formula can be used (Perry): Evaporation loss (m 3 /hr) = x 1.8 x circulation rate (m 3 /hr) x (T 1 -T 2 ) T 1 - T 2 = temperature difference between inlet and outlet water Cycles of concentration (C.O.C): This is the ratio of dissolved solids in circulating water to the dissolved solids in make up water. Blow down: Blow down losses depend upon cycles of concentration and the evaporation losses and is given by formula: Blow down = Evaporation loss / (C.O.C. 1) Liquid/Gas (L/G) ratio: The L/G ratio of a cooling tower is the ratio between the water and the air mass flow rates. Cooling towers have certain design values, but seasonal variations require adjustment and tuning of water and air flow rates to get the best cooling tower effectiveness. Adjustments can be made by water box loading changes or blade angle adjustments. Thermodynamic rules also dictate that the heat removed from the water must be equal to the heat absorbed by the surrounding air. Therefore the following formulae can be used: L(T 1 T 2 ) = G(h 2 h1) L/G = (h 2 h 1 ) / (T 1 T2) Where: L/G = liquid to gas mass flow ratio (kg/kg) T 1 = hot water temperature ( 0 C) T 2 = cold-water temperature ( 0 C) h 2 = enthalpy of air-water vapor mixture at exhaust wet-bulb temperature (same units as above) h 1 = enthalpy of air-water vapor mixture at inlet wet-bulb temperature (same units as above). 6. TECHNICAL DATA OF THE COOLING TOWER: Type of cooling tower: Induced draft counter flow Number of cells : 3 Cooling water flow : 7000 m 3 /hr Hot water inlet temperature: 43 0 C Wet bulb temperature : C Re-cooled water temperature: 33 0 C Make-up water temperature (Based on COC-4) : m 3 /hr Inlet air enthalpy : 18.10kCal/kg Exit air enthalpy : 35.55kCal/kg Approach to inlet WBT : 5 0 C Cooling range :10 0 C Air flow : kg/m 2 -hr L/G ratio : 1.65 Guaranteed drift losses : 3.50 m 3 /hr-(0.05%) Evaporation losses based on 60% RH: 1.59% Blow down for concentration of 4 : 0.48% 6.1 AT 100% LOAD OF GENERATING STATION (I.E. AT 32 MW): Data at 32 MW: Circulating water flow = 7000 m 3 /hr =1.944kg/sec Circulating water inlet temperature = 43 0 C Circulating water outlet temperature= 33 0 C Air inlet temperatures T 1 = DBT=32 0 C WBT=28 0 C (i.e., RH is 74%) Air outlet temperatures T 2 = DBT = 40 0 C WBT = 39 0 C (i.e., RH is 95%) Dissolved solids in circulating water =800ppm Dissolved solids in make-up water =120ppm Specific humidity of entering air ω 1: Vapor pressure of the entering air pv 1 : Pv 1 = ( Pvsat ) wb - P vsat at 28 0 C WBT = [P- (P vsat ) wb] [DBT-WBT] [(1.8 DBT) + 32] = bar [ ] [32-28] [(1.8x32) + 32] = bar Absolute humidity or specific humidity of entering air ω 1 : P v ω 1 = P a - P v ω 1 = ISSN: Page 445

5 = kg/kg of dry air Specific humidity of leaving air ω 3: Vapor pressure of the leaving air pv 3 : Pv 3 = ( Pvsat ) wb - P vsat at 39 0 C WBT = [P- (P vsat ) wb] [DBT-WBT] [(1.8 DBT) + 32] = bar [ ] [40-39] [(1.8x32) + 32] = bar Absolute humidity or specific humidity of leaving air ω 3 : P v P a - P v = kg/kg of dry air Range: CT Range ( C) = [CW inlet temp ( C) CW outlet temp ( C)] = =10 0 C Approach: CT Approach ( C) = [CW outlet temp ( C) Wet bulb temp ( C)] = = 5 0 C Effectiveness: CT Effectiveness (%) =100 x (CW in temp CW out temp) / (CW in temp WBT) = 100 x (43-33) / (43-38) = 66.67% Cooling capacity: This is the heat rejected in kcal/hr or TR, given as product of mass flow rate of water, specific heat (4.2kJ/kg) and temperature difference. Cooling capacity (Q) = mass flow rate of water X spe.heat X temp. difference = X 4.2 X (43-33) = kJ/sec =19.5kCal/sec Evaporation loss: Evaporation loss(m 3 /hr)= x 1.8 x circulation rate(m 3 /hr) (T1-T2) = X 1.8 X 7000 X (43-33) = 107.1m 3 /hr Percentage of evaporation = (107.1/7000) x 100 Cycles of concentration (COC): COC = = 1.53% Dissolved solids in circulating water Dissolved solids in makeup water = 800/120 = 6.67 Blow down = Evaporation loss / (C.O.C. 1) = / (6.67-1) = 18.89m 3 /hr = 0.27% Make-up water required: Total losses in circulating water=make-up water Evaporation losses + Blow down losses + Drift losses = = m 3 /hr = 1.85% Liquid/Gas (L/G) ratio: L(T 1 T 2 ) = G(h 3 h 1 ) (h 3 h 1 ) L/G = (T 1 T 2 ) Where: L/G = liquid to gas mass flow ratio (kg/kg) T 1 = hot water temperature ( 0 C) T 2 = cold-water temperature ( 0 C) h 3 =enthalpy of air-water vapor mixture at exhaust wet-bulb temperature (i.e. at 39 0 C) from steam tables in kcal/kg = (CpT 3wb + ω 3 hv 3wb ) = (1.005 x 39) + ( x ) = kJ/kg =37.54 kcal/kg h 1 =enthalpy of air-water vapor mixture at inlet wetbulb temperature (i.e. at 28 0 C in kcal/kg = (CpT 1wb + ω 1 hv 1wb ) = (1.005 x 28) + (0.022 x ) = 84.3kJ/kg =20.07 kcal/kg ISSN: Page 446

6 ( ) L/G = (43 33) = AT 70% LOAD OF GENERATING STATION (I.E. AT 22.4 MW): Data at 22.4MW : Circulating water inlet temperature Circulating water outlet temperature = 40 0 C = 30 0 C Air inlet temperatures T 1 = DBT=32 0 C WBT=28 0 C (i.e. RH is 78.7%) Air outlet temperatures T 2 = DBT = 38 0 C WBT = 37 0 C (i.e.rh is 98.9%) Specific humidity of entering air ω 1: From previous calculation; Vapor pressure of the entering air pv 1 = bar Absolute humidity or specific humidity of entering air ω 1 =0.022kg/kg of dry air Specific humidity of leaving air ω 3 : Vapor pressure of the leaving air pv 3 : [P- (P vsat ) wb] [DBT-WBT] 1.8 Pv 3 = (P vsat ) wb [(1.8 DBT) + 32] P vsat at 37 0 C WBT = bar [ ] [38-37] 1.8 = [(1.8x38) + 32] = bar Absolute humidity or specific humidity of leaving air ω 3 : P v P a - P v = kg/kg of dry air Range: CT Range ( C) = [CW inlet temp ( C) CW outlet temp ( C)] = =10 0 C Approach: CT Approach ( C) = [CW outlet temp ( C) Wet bulb temp ( C)] = = 2 0 C Effectiveness: CT Effectiveness (%) =100 x (CW in temp CW out temp) / (CW in temp WBT) = 100 x (40-30) / (40-28) = 83.33% Cooling capacity: This is the heat rejected in kcal/hr or TR, given as product of mass flow (1.944kg/sec) rate of water, specific heat (4.2kJ/kg) and temperature difference (40-30). Cooling capacity (Q)= mass flow rate of water X spe.heat X temp. Difference = X 4.2 X (40-30) Evaporation loss: Evaporation loss (m 3 /hr) = kJ/sec = 19.5 kcal/sec = x1.8x circulation rate (m 3 /hr)x(t1-t2) = X 1.8 X 7000 X(40-30) = 107.1m 3 /hr Percentage of evaporation = (107.1/7000) x 100 =1.53% Liquid/Gas (L/G) ratio: L(T 1 T 2 )= G(h3 h1) Where: T 1 = hot water temperature ( 0 C)=40 0 C = cold-water temperature ( 0 C)=30 0 C T 2 h 3 =enthalpy of air-water vapor mixture at exhaust wet-bulb temperature (i.e. at 37 0 C) from steam tables in kcal/kg = (CpT 3wb + ω 3 hv 3wb ) = (1.005 x 37) + ( x ) = kJ/kg =33.7 kcal/kg h 1 =enthalpy of air-water vapor mixture at inlet wetbulb temperature (i.e. at 28 0 C in kcal/kg = (CpT 1wb + ω 1 hv 1wb ) = (1.005 x 28) + (0.022 x ) = 84.3kJ/kg =20.07 kcal/kg ( ) L/G = (40 30) = DISCUSSION OF RESULTS For the same ambient air inlet conditions the range of the cooling tower is maintaining at the same value even though at part load. Approach has been improved (i.e. value is decreased) in part load operation of the cooling tower. Effectiveness or efficiency of the cooling tower has been improved during part load operation. This increase in effectiveness may be due to increase in potentiality to absorb heat from ISSN: Page 447

7 cooling water, because of more difference between hot water and wet bulb temperature of entering air. Cooling capacity of the cooling tower is same for both full load and part load condition because the temperature differential is same in both the conditions and also the water flow rate is kept constant. Evaporation loss in both cases is same. It is evident that, during part load condition, maintaining cooling water flow at the same rate as in full load condition may not be economical, because for the same power output evaporation losses are seems to be more. It can be observed that in part load condition liquid to gas ratio is decreased even for same heat removal and same temperature differential as in full load condition. We know that L/G ratio is depends on inlet and outlet air enthalpies at their wet bulb temperatures and differential temperature of cooling water and however as outlet air enthalpy at WBT is decreased obviously the L/G ratio decreased. CONCLUSION The climatic conditions like air dry bulb and wet bulb temperature, relative humidity will affect the performance of the cooling tower. References [1] Dvoršek, M., Hočevar, M. (2011). The influence of air flow inlet region modifications on the local efficiency of natural draft cooling tower operation. Strojniški vestnik Journal of Mechanical Engineering, vol. 57, no. 10, p , DOI: /svjme [2] Kröger, D.G. (1998). Air-cooled Heat Exchangers and Cooling Towers, Befell House, New York, p [3] Geoffrey, F.H. (2002). Heat Exchanger Design Handbook, Begell House, London, p [4] Satoshi, Y. (1996). Experimental performance of the shower cooling tower in Japan. Renewable Energy, vol. 10, no. 2-3, p [5] Thirapong, M., Wanchai, A., Somchai, W. (2007). An energy analysis on the performance of a counter flow wet cooling tower. Applied Thermal Engineering, vol. 27, no. 5-6, p , DOI: /j. applthermaleng ISSN: Page 448

Plant Utilities and Energy Efficiency CH505

Plant Utilities and Energy Efficiency CH505 Plant Utilities and Energy Efficiency CH505 Teaching Scheme Course code CH505 Course Name Plant Utilities and Energy Efficiency Teaching scheme L T P Credit 3 0 0 3 Process Process is simply a method by

More information

An Investigation in Performance Enhancement of Induced Draft Counter Flow Wet Cooling Tower

An Investigation in Performance Enhancement of Induced Draft Counter Flow Wet Cooling Tower An Investigation in Performance Enhancement of Induced Draft Counter Flow Wet Cooling Tower Manoj Kumar Chopra 1, Rahul Kumar 2 1Vice Principal, Dean Academic & Head, Dept. Of Mechanical Engineering, R.K.D.F

More information

Chapter 3.7: Cooling Towers

Chapter 3.7: Cooling Towers Part-I: Objective type questions and answers Chapter 3.7: Cooling Towers 1. The type of cooling towers with maximum heat transfer between air to water is. a) Natural draft b) Mechanical draft c) Both a

More information

COOLING TOWER DESIGN FOR CENTRAL GENERATORS OF CUET, BANGLADESH. Mohammad Sharif Khan, Golam Mainuddin, Abu Sadat Mohammad Sayem, Nadeem Nafis

COOLING TOWER DESIGN FOR CENTRAL GENERATORS OF CUET, BANGLADESH. Mohammad Sharif Khan, Golam Mainuddin, Abu Sadat Mohammad Sayem, Nadeem Nafis Proceedings of the 4 th BSME-ASME International Conference on Thermal Engineering 7-9 December, 008, Dhaka, Bangladesh COOLING TOWER DESIGN FOR CENTRAL GENERATORS OF CUET, BANGLADESH. Mohammad Sharif Khan,

More information

Seasonal effect on the performance of counter flow induced draft cooling tower of class800 for 2x250mw

Seasonal effect on the performance of counter flow induced draft cooling tower of class800 for 2x250mw Seasonal effect on the performance of counter flow induced draft cooling tower of class800 for 2x250mw Abhisheak Kumar Verma¹, Sanjay Agrawal 1 1 Department of Mechanical Engineering, B.I.E.T Jhansi, India

More information

IMPROVEMENT IN PERFORMANCE OF COOLING TOWER OF THERMAL POWER PLANT

IMPROVEMENT IN PERFORMANCE OF COOLING TOWER OF THERMAL POWER PLANT IMPROVEMENT IN PERFORMANCE OF COOLING TOWER OF THERMAL POWER PLANT Prof. Dhaval P Patel 1, Prof. N R Sheth 2, Ankit Patel 3 1 Mechanical Engineering Department, Gandhinagar Institute of Technology, dhaval.patel@git.org.in

More information

Thermal and Exergy Analysis of Counter Flow Induced Draught Cooling Tower

Thermal and Exergy Analysis of Counter Flow Induced Draught Cooling Tower International Journal of Current Engineering and Technology E-ISSN 2277 4106, P-ISSN 2347 5161 2015 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Thermal

More information

16 th NATIONAL CERTIFICATION EXAMINATION FOR ENERGY MANAGERS & ENERGY AUDITORS September, 2016

16 th NATIONAL CERTIFICATION EXAMINATION FOR ENERGY MANAGERS & ENERGY AUDITORS September, 2016 Regn No: Name : (To be written by the candidate) 16 th NATIONAL CERTIFICATION EXAMINATION FOR ENERGY MANAGERS & ENERGY AUDITORS September, 2016 PAPER 4:Energy Performance Assessment for Equipment and Utility

More information

16 th NATIONAL CERTIFICATION EXAMINATION FOR ENERGY MANAGERS & ENERGY AUDITORS September, 2016

16 th NATIONAL CERTIFICATION EXAMINATION FOR ENERGY MANAGERS & ENERGY AUDITORS September, 2016 Regn No: Name : (To be written by the candidate) 16 th NATIONAL CERTIFICATION EXAMINATION FOR ENERGY MANAGERS & ENERGY AUDITORS September, 2016 PAPER 4:Energy Performance Assessment for Equipment and Utility

More information

Performance Improvement of Mechanical Induced Draft Cooling Tower by Using Aluminum as Fill Medium

Performance Improvement of Mechanical Induced Draft Cooling Tower by Using Aluminum as Fill Medium Available online www.ejaet.com European Journal of Advances in Engineering and Technology, 2016, 3(11): 10-14 Research Article ISSN: 2394-658X Performance Improvement of Mechanical Induced Draft Cooling

More information

Parameters of the Atmospheric Air in the Dimensioning of Industrial Cooling Tower

Parameters of the Atmospheric Air in the Dimensioning of Industrial Cooling Tower 17 th Symposium on Thermal Science and Engineering of Serbia Sokobanja, Serbia, October 20 23, 2015 Society of Thermal Engineers of Serbia Faculty of Mechanical Engineering in Niš Parameters of the Atmospheric

More information

Conventional Analysis of Performance of Cooling Tower Used for Industrial Purpose

Conventional Analysis of Performance of Cooling Tower Used for Industrial Purpose International Journal of Engineering and Advanced Technology (IJEAT) ISSN: 9 898, Volume- Issue-, April Conventional Analysis of Performance of Cooling Tower Used for Industrial Purpose Rahul Patel, Ramji

More information

Regn No: Name : (To be written by the candidate)

Regn No: Name : (To be written by the candidate) Regn No: Name : (To be written by the candidate) 17 th NATIONAL CERTIFICATION EXAMINATION FOR ENERGY MANAGERS & ENERGY AUDITORS September, 2016 PAPER 4:Energy Performance Assessment for Equipment and Utility

More information

THE ITER HEAT REJECTION CHALLENGE.

THE ITER HEAT REJECTION CHALLENGE. THE ITER HEAT REJECTION CHALLENGE Steve Ployhar 1, Warren Curd 1, Ajith Kumar 2, Giovanni Dell Orco 1, Babulal Gopalapillai 1, Dinesh Gupta 2, Hiren Patel 2, Keun-Pack Chang 1, Fan Li 1, Fabio Somboli

More information

MODELLING AND SIMULATION OF A TYPICAL CROSS FLOW COOLING TOWER

MODELLING AND SIMULATION OF A TYPICAL CROSS FLOW COOLING TOWER 1. Amr Ahmad YASEEN, 1. Salah El-Din El-MORSHEDY, 1. Hesham ELKHATIB, 2. Masoud Abd El-Hakeem El-SHAFEI, 2. Tarek Mohammad ABOUL-FOTOUH MODELLING AND SIMULATION OF A TYPICAL CROSS FLOW COOLING TOWER 1.

More information

Heat Rejection using Cooling Towers

Heat Rejection using Cooling Towers MEBS6006 Environmental Services I http://www.hku.hk/bse/mebs6006 Heat Rejection using Cooling Towers Dr. Benjamin P.L. Ho (beplho@yahoo.com.hk) Part-time Lecturer Department of Mechanical Engineering The

More information

INDUSTRIAL COOLING TOWER DESIGN AND OPERATION IN THE MODERATE-CONTINENTAL CLIMATE CONDITIONS

INDUSTRIAL COOLING TOWER DESIGN AND OPERATION IN THE MODERATE-CONTINENTAL CLIMATE CONDITIONS Laković, M. S., et al.: Industrial Cooling Tower Design and Operations in the S203 INDUSTRIAL COOLING TOWER DESIGN AND OPERATION IN THE MODERATE-CONTINENTAL CLIMATE CONDITIONS by Mirjana S. LAKOVI] a*,

More information

Sustaining thermal power plant production in low water supply regions using cooling towers

Sustaining thermal power plant production in low water supply regions using cooling towers Energy and Sustainability V 679 Sustaining thermal power plant production in low water supply regions using cooling towers H. H. Al-Kayiem 1 & M. A. W. Theeb 2 1 Mechanical Engineering Department, Universiti

More information

Performance Evaluation of Cooling Tower in Thermal Power Plant - A Case Study of RTPS, Karnataka

Performance Evaluation of Cooling Tower in Thermal Power Plant - A Case Study of RTPS, Karnataka Performance Evaluation of Cooling Tower in Thermal Power Plant - A Case Study of RTPS, Karnataka Pushpa B. S, Vasant Vaze, P. T. Nimbalkar Abstract: An evaporative cooling tower is a heat exchanger where

More information

Cooling Tower Operation

Cooling Tower Operation Cooling Tower Operation Forced draught cooling towers use the evaporation of a liquid (often water) into air to achieve cooling. The tower often consists of a sprinkler system which wets a high-surface-area

More information

AMENDMENT NO. 4 AUGUST 2010 TO IS 1391 (PART 1) : 1992 ROOM AIR CONDITIONERS SPECIFICATION

AMENDMENT NO. 4 AUGUST 2010 TO IS 1391 (PART 1) : 1992 ROOM AIR CONDITIONERS SPECIFICATION AMENDMENT NO. 4 AUGUST 2010 TO IS 1391 (PART 1) : 1992 ROOM AIR CONDITIONERS SPECIFICATION PART 1 UNITARY AIR CONDITIONERS ( Second Revision ) (Page 9, clause 11.1.1) Substitute the following for the existing:

More information

COUPLING MODEL AND SOLVING APPROACH FOR PERFORMANCE EVALUATION OF NATURAL DRAFT COUNTER-FLOW WET COOLING TOWERS

COUPLING MODEL AND SOLVING APPROACH FOR PERFORMANCE EVALUATION OF NATURAL DRAFT COUNTER-FLOW WET COOLING TOWERS THERMAL SCIENCE: Year 2016, Vol. 20, No. 1, pp. 291-301 291 COUPLING MODEL AND SOLVING APPROACH FOR PERFORMANCE EVALUATION OF NATURAL DRAFT COUNTER-FLOW WET COOLING TOWERS by Wei WANG *, Deliang ZENG,

More information

15 th NATIONAL CERTIFICATION EXAMINATION FOR ENERGY AUDITORS August, 2014

15 th NATIONAL CERTIFICATION EXAMINATION FOR ENERGY AUDITORS August, 2014 15 th NATIONAL CERTIFICATION EXAMINATION FOR ENERGY AUDITORS August, 2014 Paper 4 SET A PAPER 4: Energy Performance Assessment for Equipment and Utility Systems Date: 24.8.2013 Timings: 14:00-16:00 Hrs

More information

OPERATING PARAMETERS Reliable Means to Continuously Monitor Facility Performance

OPERATING PARAMETERS Reliable Means to Continuously Monitor Facility Performance OPERATING PARAMETERS Reliable Means to Continuously Monitor Facility Performance RICHARD SCHERRER Ogden Martin Systems, Inc. Fairfield, New Jersey ABSTRACT Energy sales are a major source of revenues for

More information

Modelling of Indirect Evaporative Air Coolers

Modelling of Indirect Evaporative Air Coolers 416 2nd PALENC Conference and 28th AIVC Conference on Building Low Energy Cooling and Modelling of Indirect Evaporative Air Coolers Gh. Heidarinejad Building and Housing Research Centre (BHRC), Iran M.

More information

Lecture 8. Design of cooling systems for effluent temperature reduction. L08-1 Energy System Design Update

Lecture 8. Design of cooling systems for effluent temperature reduction. L08-1 Energy System Design Update Lecture 8 Design of cooling systems for effluent temperature reduction L08-1 Energy System Design Update Wastewater Treatment Utility System Wastewater Heat Exchanger Network Separation System Reactor

More information

A NEW POLYNOMIAL BASED MODEL FOR DETERMINING COOLING TOWER EVAPORATION WATER LOSS. Aaron Powers Johnson Controls, Inc.

A NEW POLYNOMIAL BASED MODEL FOR DETERMINING COOLING TOWER EVAPORATION WATER LOSS. Aaron Powers Johnson Controls, Inc. ASHRAE and IBPSA-USA SimBuild 2016 Building Performance Modeling Conference Salt Lake City, UT August 8-12, 2016 A NEW POLYNOMIAL BASED MODEL FOR DETERMINING COOLING TOWER EVAPORATION WATER LOSS Aaron

More information

PERFORMANCE TESTING OF HYBRID WET-DRY COOLING SYSTEMS: INSIGHTS FROM NUMERICAL MODELING

PERFORMANCE TESTING OF HYBRID WET-DRY COOLING SYSTEMS: INSIGHTS FROM NUMERICAL MODELING Proceedings of the ASME 2014 Power Conference POWER2014 July 28-31, 2014, Baltimore, Maryland, USA POWER2014-32189 PERFORMANCE TESTING OF HYBRID WET-DRY COOLING SYSTEMS: INSIGHTS FROM NUMERICAL MODELING

More information

INVESTIGATION OF THE THERMAL PERFORMANCE OF A CROSS-FLOW WATER COOLING TOWER WITH DIFFERENT PACKINGS

INVESTIGATION OF THE THERMAL PERFORMANCE OF A CROSS-FLOW WATER COOLING TOWER WITH DIFFERENT PACKINGS Number1 INVESTIGATION OF THE THERMA PERFORMANCE OF A CROSS-FOW WATER COOING TOWER WITH DIFFERENT PACKINGS ABSTRACT Dr. A. N. S. Kassim and Basim A. Rasheed University of Baghdad College of Engineering

More information

R13. II B. Tech I Semester Regular/Supplementary Examinations, Oct/Nov THERMODYNAMICS (Com. to ME, AE, AME) Time: 3 hours Max.

R13. II B. Tech I Semester Regular/Supplementary Examinations, Oct/Nov THERMODYNAMICS (Com. to ME, AE, AME) Time: 3 hours Max. SET - 1 1. a) Discuss about PMM I and PMM II b) Explain about Quasi static process. c) Show that the COP of a heat pump is greater than the COP of a refrigerator by unity. d) What is steam quality? What

More information

EXPERIMENTAL INVESTIGATION AND OPTIMIZATION OF COOLING TOWER EFFICIENCY BY FORCED DRAFT SYSTEM

EXPERIMENTAL INVESTIGATION AND OPTIMIZATION OF COOLING TOWER EFFICIENCY BY FORCED DRAFT SYSTEM EXPERIMENTAL INVESTIGATION AND OPTIMIZATION OF COOLING TOWER EFFICIENCY BY FORCED DRAFT SYSTEM Sankar raj S 1,Vignesh S 2, Surulivelrajan T 3 ¹ U G Student Department of Mechanical Engineering, PSVPEC,

More information

NATIONAL CERTIFICATION EXAMINATION 2004 FOR ENERGY MANAGERS

NATIONAL CERTIFICATION EXAMINATION 2004 FOR ENERGY MANAGERS NATIONAL CERTIFICATION EXAMINATION 004 FOR ENERGY MANAGERS PAPER EM3: Energy Efficiency in Electrical Utilities Date: 3.05.004 Timings: 0930-30 HRS Duration: 3 HRS Max. Marks: 50 General instructions:

More information

PAPER-I (Conventional)

PAPER-I (Conventional) 1. a. PAPER-I (Conventional) 10 kg of pure ice at 10 ºC is separated from 6 kg of pure water at +10 O C in an adiabatic chamber using a thin adiabatic membrane. Upon rupture of the membrane, ice and water

More information

DESIGN OF VAPOUR ABSORPTION REFRIGERATION SYSTEM OF 1.5TR CAPACITY BY WASTE HEAT RECOVERY PROCESS

DESIGN OF VAPOUR ABSORPTION REFRIGERATION SYSTEM OF 1.5TR CAPACITY BY WASTE HEAT RECOVERY PROCESS Volume 115 No. 7 2017, 613-619 ISSN: 1311-8080 (printed version); ISSN: 1314-3395 (on-line version) url: http://www.ijpam.eu ijpam.eu DESIGN OF VAPOUR ABSORPTION REFRIGERATION SYSTEM OF 1.5TR CAPACITY

More information

PARAMETRIC STUDY OF GAS TURBINE CYCLE COUPLED WITH VAPOR COMPRESSION REFRIGERATION CYCLE FOR INTAKE AIR COOLING

PARAMETRIC STUDY OF GAS TURBINE CYCLE COUPLED WITH VAPOR COMPRESSION REFRIGERATION CYCLE FOR INTAKE AIR COOLING International Journal of Mechanical Engineering and Technology (IJMET) Volume 9, Issue 9, September 2018, pp. 248 261, Article ID: IJMET_09_09_029 Available online at http://www.iaeme.com/ijmet/issues.asp?jtype=ijmet&vtype=9&itype=9

More information

INVESTIGATION ON THE OPTIMUM DESIGN OF HEAT EXCHANGERS IN A HYBRID CLOSED CIRCUIT COOLING TOWER

INVESTIGATION ON THE OPTIMUM DESIGN OF HEAT EXCHANGERS IN A HYBRID CLOSED CIRCUIT COOLING TOWER 52 INVESTIGATION ON THE OPTIMUM DESIGN OF HEAT EXCHANGERS IN A HYBRID CLOSED CIRCUIT COOLING TOWER M. M. A. Sarker Department of Mathematics, BUET, Dhaka-1000, Bangladesh. Corresponding email: masarker@math.buet.ac.bd

More information

R13 SET - 1 '' ''' '' ' '''' Code No: RT31035

R13 SET - 1 '' ''' '' ' '''' Code No: RT31035 R13 SET - 1 III B. Tech I Semester Regular/Supplementary Examinations, October/November - 2016 THERMAL ENGINEERING II (Mechanical Engineering) Time: 3 hours Max. Marks: 70 Note: 1. Question Paper consists

More information

Performance Investigation of Window Air Conditioner

Performance Investigation of Window Air Conditioner IOSR Journal of Civil and Mechanical Engineering (IOSR-JMCE) ISSN: 2278-1684, PP: 32-37 www.iosrjournals.org Performance Investigation of Window Air Conditioner Prof. S.M.Shaikh 1, Prof. A.M.Patil 2, Prof.

More information

ANALYSIS OF PERFORMANCE OF NATURAL DRAFT COOLING TOWER AT OPTIMIZED INJECTION HEIGHT

ANALYSIS OF PERFORMANCE OF NATURAL DRAFT COOLING TOWER AT OPTIMIZED INJECTION HEIGHT International Journal of Mechanical Engineering and Technology (IJMET) Volume 9, Issue 7, July 2018, pp. 687 694, Article ID: IJMET_09_07_071 Available online at http://www.iaeme.com/ijmet/issues.asp?jtype=ijmet&vtype=9&itype=7

More information

Problems in chapter 9 CB Thermodynamics

Problems in chapter 9 CB Thermodynamics Problems in chapter 9 CB Thermodynamics 9-82 Air is used as the working fluid in a simple ideal Brayton cycle that has a pressure ratio of 12, a compressor inlet temperature of 300 K, and a turbine inlet

More information

Chapter Six{ TC "Chapter Six" \l 1 } System Simulation

Chapter Six{ TC Chapter Six \l 1 } System Simulation Chapter Six{ TC "Chapter Six" \l 1 } System Simulation In the previous chapters models of the components of the cooling cycle and of the power plant were introduced. The TRNSYS model of the power plant

More information

Sensitivity Studies of a Low Temperature Low Approach Direct Cooling Tower for Building Radiant Cooling Systems

Sensitivity Studies of a Low Temperature Low Approach Direct Cooling Tower for Building Radiant Cooling Systems Dublin Institute of Technology ARROW@DIT Conference Papers School of Mechanical and Design Engineering 212-7-16 Sensitivity Studies of a Low Temperature Low Approach Direct Cooling Tower for Building Radiant

More information

A. the temperature of the steam at the turbine exhaust increases. B. additional moisture is removed from the steam entering the turbine.

A. the temperature of the steam at the turbine exhaust increases. B. additional moisture is removed from the steam entering the turbine. P77 Overall nuclear power plant thermal efficiency will decrease if... A. the temperature of the steam at the turbine exhaust increases. B. additional moisture is removed from the steam entering the turbine.

More information

Gas Turbine Inlet Air Cooling System

Gas Turbine Inlet Air Cooling System Gas Turbine Inlet Air Cooling System Presented by Bob Omidvar Heavy Duty GT - Effects of Ambient Temp 110% 105% 100% 95% 90% 85% 80% 75% 0 5 10 15 20 25 30 35 40 45 GT Inlet Temp (deg C) Heat rate kj/kwh

More information

WHY IS THERE A NEED FOR MORE ACCURACY IN DRY KILN CONTROL

WHY IS THERE A NEED FOR MORE ACCURACY IN DRY KILN CONTROL WHY IS THERE A NEED FOR MORE ACCURACY IN DRY KILN CONTROL Leon Breckenridge Integrated Energy Economic Services, Inc. Yakima, Washington INTRODUCTION Section A Parameters for Measurement and Control The

More information

LAHU Heat Recovery System Optimal Operation and Control Schedules

LAHU Heat Recovery System Optimal Operation and Control Schedules Yujie Cui Nexant, Inc., 44 South Broadway, 5th Floor, White Plains, NY 10601 e-mail: ycui@nexant.com Mingsheng Liu Architectural Engineering, University of Nebraska Lincoln, 206C, PKI, 1110 S. 67th St.,

More information

International Journal Of Scientific Research And Education Volume 3 Issue 3 Pages March-2015 ISSN (e): Website:

International Journal Of Scientific Research And Education Volume 3 Issue 3 Pages March-2015 ISSN (e): Website: International Journal Of Scientific Research And Education Volume 3 Issue 3 Pages-2969-2977 March-2015 ISSN (e): 2321-7545 Website: http://ijsae.in Experimental Analyses for NDWCT Performance Using Trickle

More information

ME ENGINEERING THERMODYNAMICS UNIT III QUESTION BANK SVCET

ME ENGINEERING THERMODYNAMICS UNIT III QUESTION BANK SVCET 1. A vessel of volume 0.04m 3 contains a mixture of saturated water and steam at a temperature of 250 0 C. The mass of the liquid present is 9 kg. Find the pressure, mass, specific volume, enthalpy, entropy

More information

Overall nuclear power plant thermal efficiency will decrease if... A. the temperature of the steam at the turbine exhaust increases.

Overall nuclear power plant thermal efficiency will decrease if... A. the temperature of the steam at the turbine exhaust increases. P77 Overall nuclear power plant thermal efficiency will decrease if... A. the temperature of the steam at the turbine exhaust increases. B. additional moisture is removed from the steam entering the turbine.

More information

PERFORMANCE CORRELATIONS FOR COUNTERFLOW COOLING TOWER

PERFORMANCE CORRELATIONS FOR COUNTERFLOW COOLING TOWER Jurnal Mekanikal June 2016, Vol 39, 15-26 PERFORMANCE CORRELATIONS FOR COUNTERFLOW COOLING TOWER Mohd Yusoff Senawi* Faculty of Mechanical Engineering Universiti Teknologi Malaysia 81310 UTM Johor Bahru

More information

Administrative Building Cooling Tower. University of Tennessee Chattanooga

Administrative Building Cooling Tower. University of Tennessee Chattanooga Administrative Building Cooling Tower University of Tennessee Chattanooga Ben Dalton Lab Partner: Murat Ozkaya ENCH 435 Dr. Jim Henry December 2, 2008 Abstract Experimental data was taken at the air inlet

More information

World Journal of Engineering Research and Technology WJERT

World Journal of Engineering Research and Technology WJERT wjert, 2017, Vol. 3, Issue 6, 83-92. Original Article ISSN 2454-695X Ajayi et al. WJERT www.wjert.org SJIF Impact Factor: 4.326 DEVELOPMENTS OF LABORATORY COOLING TOWER MODEL Ajayi I. S.*, Oladimeji E.

More information

Fresh air pre-cooling and energy recovery by using indirect evaporative cooling in hot and humid region a case study in Hong Kong

Fresh air pre-cooling and energy recovery by using indirect evaporative cooling in hot and humid region a case study in Hong Kong Available online at www.sciencedirect.com ScienceDirect Energy Procedia 61 (2014 ) 126 130 The 6 th International Conference on Applied Energy ICAE2014 Fresh air pre-cooling and energy recovery by using

More information

Performance evaluation of a plate type (HTST) milk pasteurizer

Performance evaluation of a plate type (HTST) milk pasteurizer Research Journal of Animal Husbandry and Dairy Science e ISSN-31-644 RESEARCH PAPER Volume 6 Issue Dec., 015 130-134 DOI: 10.15740/HAS/RJAHDS/6./130-134 Visit us: www.researchjournal.co.in Performance

More information

07059, Antalya / TURKEY ABSTRACT

07059, Antalya / TURKEY   ABSTRACT 1 The Effects of Natural Ventilation Air Exchange on Psychrometric Results in Poultry Houses in Hot Environment---Design Characteristics S. Mutaf 1, S.Alkan 1, N.Seber 1 1 Akdeniz University, Faculty of

More information

Critical exergy analysis of counterflow reversibly used cooling towers

Critical exergy analysis of counterflow reversibly used cooling towers Critical exergy analysis of counterflow reversibly used cooling towers Jiasheng Wu 1, Guoqiang Zhang 1,*, Quan Zhang 1, Jin Zhou 1 1 College of Civil Engineering, Hunan University, Changsha, China * Corresponding

More information

Performance Improvement of Single-Flash Geothermal Power Plant Applying Three Cases Development Scenarios Using Thermodynamic Methods

Performance Improvement of Single-Flash Geothermal Power Plant Applying Three Cases Development Scenarios Using Thermodynamic Methods Proceedings World Geothermal Congress 2015 Melbourne, Australia, 19-25 April 2015 Performance Improvement of Single-Flash Geothermal Power Plant Applying Three Cases Development Scenarios Using Thermodynamic

More information

Performance Analysis of An Indirect Evaporative Cooling System using M Cycle Devang S. Patel 1 Hardik M.Patel 2

Performance Analysis of An Indirect Evaporative Cooling System using M Cycle Devang S. Patel 1 Hardik M.Patel 2 IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 05, 2015 ISSN (online): 2321-0613 Performance Analysis of An Indirect Evaporative Cooling System using M Cycle Devang S.

More information

Modeling Techniques for Increased Accuracy

Modeling Techniques for Increased Accuracy SECTION 1 Modeling Techniques for Increased Accuracy Ed Haack Duke Energy 1-1 Modeling Techniques for Increased Accuracy By Ed Haack, Duke Power Company The PEPSE model for the Catawba Units have been

More information

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Available online at   ScienceDirect. Procedia Engineering 121 (2015 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 121 (2015 ) 881 890 9th International Symposium on Heating, Ventilation and Air Conditioning (ISHVAC) and the 3rd International

More information

Design of Chiller Type Inlet Air Cooling System to Enhance the Performance of Combined Cycle Power Plant

Design of Chiller Type Inlet Air Cooling System to Enhance the Performance of Combined Cycle Power Plant Design of Chiller Type Inlet Air Cooling System to Enhance the Performance of Combined Cycle Power Plant 1 Panchalinge Gowda. H. L M.Tech. s tudent (Thermal Power Engg.), Dept. of Mechanical Engg. SIT,

More information

Pultruded FRP Cooling Tower - Design, Development and Validation

Pultruded FRP Cooling Tower - Design, Development and Validation Pultruded FRP Cooling Tower - Design, Development and Validation. Prof. Chavan Dattatraya K. Professor Mechanical Engineering Dept., MMCOE, Pune-52. University of Pune,Maharashtra,India PhD scholar,jjt

More information

PERFORMANCE ANALYSIS OF NATURAL DRAFT WET COOLING TOWER AT OPTIMIZED INJECTION HEIGHT

PERFORMANCE ANALYSIS OF NATURAL DRAFT WET COOLING TOWER AT OPTIMIZED INJECTION HEIGHT PERFORMANCE ANALYSIS OF NATURAL DRAFT WET COOLING TOWER AT OPTIMIZED INJECTION HEIGHT 1 ALOK SINGH, 2 SANJAY SONI, 3 R. S. RANA 1 Assistant Professor, 2 Associate Professor, 3 Mechanical Engineering Department

More information

Rankine (steam) Cycle Cooling Options

Rankine (steam) Cycle Cooling Options Rankine (steam) Cycle Cooling Options Babul Patel Nexant, Inc. San Francisco, CA Energy Solutions October 23, 2009 1 ankine Cycle Cooling Considerations Steam turbine output and Rankine cycle efficiency

More information

Performance Analysis of Surface Condenser in 525MW Thermal Power Plant

Performance Analysis of Surface Condenser in 525MW Thermal Power Plant Performance Analysis of Surface Condenser in 525MW Thermal Power Plant Gaurav Masiwal #1, P.S.Kumar *2, Sumit Chaudhary *3 # Operation and Efficiency Department, Steag Operation and Maintenance Company

More information

OPTIMIZATION OF PARAMETERS FOR HEAT RECOVERY STEAM GENERATOR (HRSG) IN COMBINED CYCLE PLANTS

OPTIMIZATION OF PARAMETERS FOR HEAT RECOVERY STEAM GENERATOR (HRSG) IN COMBINED CYCLE PLANTS OPTIMIZATION OF PARAMETERS FOR HEAT RECOVERY STEAM GENERATOR (HRSG) IN COMBINED CYCLE PLANTS Muammer Alus, Milan V. Petrovic University of Belgrade-Faculty of Mechanical Engineering, Laboratory of Thermal

More information

ERT 318/4 UNIT OPERATIONS SEMESTER 1 (2013/2014)

ERT 318/4 UNIT OPERATIONS SEMESTER 1 (2013/2014) ERT 318/4 UNIT OPERATIONS SEMESTER 1 (2013/2014) WATER COOLING TOWER School of Bioprocess Engineering University Malaysia Perlis EXPERIMENT Water Cooling Tower 1.0 OBJECTIVES 1.1 To determine energy and

More information

MECHANICAL ENGINEERING DEPARTMENT, OITM

MECHANICAL ENGINEERING DEPARTMENT, OITM Sem.:4 th Subject: Energy Conversion Paper: ME-201E UNIT-1 Q1. Explain the seismometer with its working principle. (Important Question) (20) Q2. Classify the fuels and define calorific value of fuels.

More information

Chapter 5: Thermodynamic Processes and Cycles

Chapter 5: Thermodynamic Processes and Cycles Chapter 5: Thermodynamic Processes and Cycles 5-6) This problem examines the Rankine heat engine introduced in Figure 5-5. Saturated steam at T = 250 C enters the turbine and the condenser operates at

More information

OUTCOME 2 TUTORIAL 2 STEADY FLOW PLANT

OUTCOME 2 TUTORIAL 2 STEADY FLOW PLANT UNIT 47: Engineering Plant Technology Unit code: F/601/1433 QCF level: 5 Credit value: 15 OUTCOME 2 TUTORIAL 2 STEADY FLOW PLANT 2 Be able to apply the steady flow energy equation (SFEE) to plant and equipment

More information

ANSYS, Inc. March 31, Phase Change Models in FLUENT

ANSYS, Inc. March 31, Phase Change Models in FLUENT 1 2016 ANSYS, Inc. March 31, 2016 Phase Change Models in FLUENT Phase Change Models in ANSYS FLUENT In ANSYS Fluent the following are available for modeling phase change Boiling models RPI Non equilibrium

More information

OBJECT SYSTEM Figure 1 shows the object air conditioning system. Flesh outdoor air is supplied to desiccant system directly or via earth tube dependin

OBJECT SYSTEM Figure 1 shows the object air conditioning system. Flesh outdoor air is supplied to desiccant system directly or via earth tube dependin Study On Performance Evaluation And Modeling Of Temperature And Humidity Independent Control Of Air Conditioning System Based On Operation Data M. Ukai 1,*, H. Tanaka 2, M. Okumiya 1 and H. Tanaka 1 1

More information

Appendices, Thermodynamics, Phases of Water, Laws of Thermodynamics and Thermodynamic Processes By

Appendices, Thermodynamics, Phases of Water, Laws of Thermodynamics and Thermodynamic Processes By Appendices, Thermodynamics, Phases of Water, Laws of Thermodynamics and Thermodynamic Processes By S. Bobby Rauf, P.E., CEM, MBA Credit: 11 PDH Thermodynamics Fundamentals Series Appendix A This appendix

More information

IMPLEMENTATION OF ANALYTICAL MODELS FOR PASSIVE DOWN-DRAFT EVAPORATIVE COOLING (PDEC) TOWER WITH SPRAY SYSTEMS

IMPLEMENTATION OF ANALYTICAL MODELS FOR PASSIVE DOWN-DRAFT EVAPORATIVE COOLING (PDEC) TOWER WITH SPRAY SYSTEMS IMPLEMENTATION OF ANALYTICAL MODELS FOR PASSIVE DOWN-DRAFT EVAPORATIVE COOLING (PDEC) TOWER WITH SPRAY SYSTEMS Daeho Kang 1, Richard K. Strand 2 1 Department of Environmental Control Technology, New York

More information

Challenger Center Cooling Tower

Challenger Center Cooling Tower Challenger Center Cooling Tower University of Tennessee at Chattanooga ENCH/ENEV 435 Lab Report By: Dianah Dugan Lab Partner: Alex Saputa Professor: Dr. Jim Henry Date: October, 8, 2008 ABSTRACT Over the

More information

a. The power required to drive the compressor; b. The inlet and output pipe cross-sectional area. [Ans: kw, m 2 ] [3.34, R. K.

a. The power required to drive the compressor; b. The inlet and output pipe cross-sectional area. [Ans: kw, m 2 ] [3.34, R. K. CHAPTER 2 - FIRST LAW OF THERMODYNAMICS 1. At the inlet to a certain nozzle the enthalpy of fluid passing is 2800 kj/kg, and the velocity is 50 m/s. At the discharge end the enthalpy is 2600 kj/kg. The

More information

Ceiling Radiant Cooling Panels

Ceiling Radiant Cooling Panels Copyright 2006, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc This posting is by permission from ASHE Journal This article may not be copied nor distributed in either paper

More information

Boiler and. steadily increases while the supply decreases energy

Boiler and. steadily increases while the supply decreases energy FEATURE ARTICLE by William G. Acker ENERGY SURVEYS FOR Stewart Cohen/Stone The efficient use of energy is fast becoming a top concern for industry. As business managers become more conscientious about

More information

Ceiling Radiant Cooling Panels

Ceiling Radiant Cooling Panels 2006, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc (wwwashraeorg) Published in ASHE Journal Vol 48, Oct 2006 For personal use only Additional reproduction, distribution,

More information

Code No: R31034 R10 Set No: 1

Code No: R31034 R10 Set No: 1 Code No: R31034 R10 Set No: 1 JNT University Kakinada III B.Tech. I Semester Regular/Supplementary Examinations, Dec - 2014/Jan -2015 THERMAL ENGINEERING-II (Com. to Mechanical Engineering and Automobile

More information

Experimental and Analytical Investigation to Improve the Efficiency of Industrial Cooling Tower

Experimental and Analytical Investigation to Improve the Efficiency of Industrial Cooling Tower IJIRST International Journal for Innovative Research in Science & Technology Volume 2 Issue 12 May 2016 ISSN (online): 2349-6010 Experimental and Analytical Investigation to Improve the Efficiency of Industrial

More information

The Effect of High Temperature Feedwater on the Performance of an Evaporative Cooler Installed in a Gas Turbine Combustion Air Inlet System

The Effect of High Temperature Feedwater on the Performance of an Evaporative Cooler Installed in a Gas Turbine Combustion Air Inlet System THE AMERICAN SOCIETY OF MECHANICAL ENGINEERS 345 E. 47th St, Now York. N.Y. 10017 96-GT-229 The Society shall not be responsible for statements or opinions advanced in papers or discussion at meetings

More information

- 2 - SME Q1. (a) Briefly explain how the following methods used in a gas-turbine power plant increase the thermal efficiency:

- 2 - SME Q1. (a) Briefly explain how the following methods used in a gas-turbine power plant increase the thermal efficiency: - 2 - Q1. (a) Briefly explain how the following methods used in a gas-turbine power plant increase the thermal efficiency: i) regenerator ii) intercooling between compressors (6 marks) (b) Air enters a

More information

7 th NATIONAL CERTIFICATION EXAMINATION Nov FOR ENERGY MANAGERS & ENERGY AUDITORS

7 th NATIONAL CERTIFICATION EXAMINATION Nov FOR ENERGY MANAGERS & ENERGY AUDITORS Regn No: Name: (To be written by the candidates) 7 th NATIONAL CERTIFICATION EXAMINATION Nov. 2008 FOR ENERGY MANAGERS & ENERGY AUDITORS PAPER 2: Energy Efficiency in Thermal Utilities Date: 22.11.2008

More information

Demonstration of IAEA program for water management (WAMP) K. Kavvadias. Ph.D Chemical Engineer

Demonstration of IAEA program for water management (WAMP) K. Kavvadias. Ph.D Chemical Engineer Demonstration of IAEA program for water management (WAMP) K. Kavvadias Ph.D Chemical Engineer IAEA Training Workshop September 2017 Introduction Motivation for development Program features and architecture

More information

Chapters 5, 6, and 7. Use T 0 = 20 C and p 0 = 100 kpa and constant specific heats unless otherwise noted. Note also that 1 bar = 100 kpa.

Chapters 5, 6, and 7. Use T 0 = 20 C and p 0 = 100 kpa and constant specific heats unless otherwise noted. Note also that 1 bar = 100 kpa. Chapters 5, 6, and 7 Use T 0 = 20 C and p 0 = 100 kpa and constant specific heats unless otherwise noted. Note also that 1 bar = 100 kpa. 5-1. Steam enters a steady-flow device at 16 MPa and 560 C with

More information

Comparative Analysis on Performance of a Gas Turbine Power Plant with a Spray Cooler

Comparative Analysis on Performance of a Gas Turbine Power Plant with a Spray Cooler International Journal of scientific research and management (IJSRM) Volume 1 Issue 7 Pages 354-358 2013 Website: www.ijsrm.in ISSN (e): 2321-3418 Comparative Analysis on Performance of a Gas Turbine Power

More information

Pinch Analysis for Power Plant: A Novel Approach for Increase in Efficiency

Pinch Analysis for Power Plant: A Novel Approach for Increase in Efficiency Pinch Analysis for Power Plant: A Novel Approach for Increase in Efficiency S. R. Sunasara 1, J. J. Makadia 2 * 1,2 Mechanical Engineering Department, RK University Kasturbadham, Rajkot-Bhavngar highway,

More information

17 th NATIONAL CERTIFICATION EXAMINATION FOR ENERGY MANAGERS & ENERGY AUDITORS September, PAPER 3: Energy Efficiency in Electrical Utilities

17 th NATIONAL CERTIFICATION EXAMINATION FOR ENERGY MANAGERS & ENERGY AUDITORS September, PAPER 3: Energy Efficiency in Electrical Utilities Regn No: Name : (To be written by the candidate) 17 th NATIONAL CERTIFICATION EXAMINATION FOR ENERGY MANAGERS & ENERGY AUDITORS September, 2016 PAPER 3: Energy Efficiency in Electrical Utilities Date:

More information

EFFECT OF INLET AIR COOLING ON GAS TURBINE PERFORMANCE

EFFECT OF INLET AIR COOLING ON GAS TURBINE PERFORMANCE EFFECT OF INLET AIR COOLING ON GAS TURBINE PERFORMANCE WAIEL KAMAL ELSAIED 1,*, ZAINAL AMBRI BIN ABDUL KARIM 2,* Universiti Teknologi PETRONAS Bandar Seri Iskandar, 31750 Tronoh, Perak, Malaysia UTP_waiel@yahoo.com,

More information

19 th NATIONAL CERTIFICATION EXAMINATION FOR ENERGY MANAGERS & ENERGY AUDITORS SEPTEMBER, 2018 PAPER 3 : ENERGY EFFICIENCY IN ELECTRICAL UTILITIES

19 th NATIONAL CERTIFICATION EXAMINATION FOR ENERGY MANAGERS & ENERGY AUDITORS SEPTEMBER, 2018 PAPER 3 : ENERGY EFFICIENCY IN ELECTRICAL UTILITIES Paper 3 Set A 19 th NATIONAL CERTIFICATION EXAMINATION FOR ENERGY MANAGERS & ENERGY AUDITORS SEPTEMBER, 2018 PAPER 3 : ENERGY EFFICIENCY IN ELECTRICAL UTILITIES Section I: OBJECTIVE TYPE Marks: 50 x 1

More information

Enthalpy Calculations. Change in enthalpy can occur because of change in temperature, change in phase, or mixing of solutions and reactions.

Enthalpy Calculations. Change in enthalpy can occur because of change in temperature, change in phase, or mixing of solutions and reactions. Enthalpy Calculations Change in enthalpy can occur because of change in temperature, change in phase, or mixing of solutions and reactions. Enthalpy Change as a Result of Temperature Sensible heat is the

More information

EAS1600 Spring 2014 Lab 05 Heat Transfer

EAS1600 Spring 2014 Lab 05 Heat Transfer Name Lab section EAS1600 Spring 2014 Lab 05 Heat Transfer Objectives In this lab we will investigate the ways heat can be transferred between bodies. Using the calorimetric approach, we will verify the

More information

Cooling Water System Modelling for Control and Energy Optimisation Purposes

Cooling Water System Modelling for Control and Energy Optimisation Purposes Proceedings of the 19th World Congress The International Federation of Automatic Control Cooling Water System Modelling for Control and Energy Optimisation Purposes Cornelius J. Muller, Ian K. Craig Sasol

More information

CHAPTER 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES

CHAPTER 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES Thermodynamics: An Engineering Approach 8th Edition in SI Units Yunus A. Ç engel, Michael A. Boles McGraw-Hill, 2015 CHAPTER 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES Objectives Develop the conservation

More information

Energy and Exergy Analysis of Boiler and Extraction cum Condensing Steam Turbine in Sugar Cogeneration Plant

Energy and Exergy Analysis of Boiler and Extraction cum Condensing Steam Turbine in Sugar Cogeneration Plant Energy and Exergy Analysis of Boiler and Extraction cum Condensing Steam Turbine in Sugar Cogeneration Plant V.H. Bhagat 1, A.I.Rehman 2, D.N.Hatkar 3 1 M.E.(Scholar) Mechanical Engineering Department,

More information

Chapter 4.3: Cogeneration, Turbines (Gas, Steam)

Chapter 4.3: Cogeneration, Turbines (Gas, Steam) Short type questions Chapter 4.3: Cogeneration, Turbines (Gas, Steam) 1. What could be the range of energy saving potential from co-generation systems? Co-generation offers energy savings in the range

More information

16 th NATIONAL CERTIFICATION EXAMINATION FOR ENERGY MANAGERS & ENERGY AUDITORS September, 2015

16 th NATIONAL CERTIFICATION EXAMINATION FOR ENERGY MANAGERS & ENERGY AUDITORS September, 2015 16 th NATIONAL CERTIFICATION EXAMINATION FOR ENERGY MANAGERS & ENERGY AUDITORS September, 2015 PAPER 4:Energy Performance Assessment for Equipment and Utility Systems Date: 20.09.2015 Timings: 14:00-16:00

More information

Performance Rating of Air-to-Air Exchangers for Energy Recovery Ventilation Equipment

Performance Rating of Air-to-Air Exchangers for Energy Recovery Ventilation Equipment AHRI Standard 1061 (SI) 2018 Standard for Performance Rating of Air-to-Air Exchangers for Energy Recovery Ventilation Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not

More information

DECREASE THE OUTLET WATER TEMPERATURE OF CROSS FLOW COOLING TOWER

DECREASE THE OUTLET WATER TEMPERATURE OF CROSS FLOW COOLING TOWER DECREASE THE OUTLET WATER TEMPERATURE OF CROSS FLOW COOLING TOWER *R.Immanual, **S.Rajakumar, ***B.Ragupathi, ***S.P.Ramkumar, *PG student, ** Assistant Professor Department of Mechanical Engineering,

More information