Modelling of Indirect Evaporative Air Coolers

Size: px
Start display at page:

Download "Modelling of Indirect Evaporative Air Coolers"

Transcription

1 416 2nd PALENC Conference and 28th AIVC Conference on Building Low Energy Cooling and Modelling of Indirect Evaporative Air Coolers Gh. Heidarinejad Building and Housing Research Centre (BHRC), Iran M. Bozorgmehr University of Tarbiat Modares, Iran ABSTRACT In this paper, indirect evaporative cooling in an air cooler has been modeled. This model has been obtained from the governing equations of heat and mass transfer in primary and secondary air and water flows. Factors affecting on evaporative cooling performance such as mass flow rates, geometry and flow configuration has been investigated. Results show that cooling efficiency considerably depends on mass flow rates ratios of primary and secondary air flows and spacing between plates of wet and dry passages. The performance of this cooling system for typical conditions of some Iranian cities has been investigated. Using a first stage indirect evaporative cooling prior to conventional direct evaporative cooling systems in most regions of Iran will provide cooling comfort conditions as a low energy consumer alternative. 1. INTRODUCTION Evaporative air conditioning is an environmentally friendly and energy efficient method for cooling buildings. Two main different methods are used, the direct and the indirect one. In the direct method air passes through a wetted media in an adiabatic saturation process. In the indirect method, two distinct air flows pass through a wet surface heat exchanger, primary flow in the dry channels and secondary flow in the wet channels. In this case without adding water to the primary air, it is cooled and secondary air carries away the heat energy from it as water evaporates in wet channels, so the indirect stage sensibly cools the primary air. Secondary air could be supplied from outdoor or room exhaust which is so-called recovery. Also it may be extracted from primary air outlet which is referred to regenerative and in this case secondary air passes two times through the heat exchanger. Heat and mass transfer occur simultaneously in an indirect evaporative heat exchanger. Maclaine-cross and Banks (1983) analyzed the evaporative heat transfer in an indirect cooler. They suggested a simplified analysis model assuming that water film is stationary and continuously replenished with water at the same temperature and saturation line is a linear func- tion of temperature. The resulting decoupled equations describing the wet and the dry passages of the cooler were solved by defining a new independent variable: wet bulb depression which is the difference between dry bulb and wet bulb temperatures. This model could be used to predict the cooler performance by analogy to dry surface heat exchangers. Hsu et al. (1989) investigated three basic types of wet surface heat exchangers. They found that cooling effectiveness of each configuration increases with increasing dry channel NTU (Number of Transfer Units) and reaches maximum values asymptotically at some large values of NTU. They assumed that the non-circulating water is locally replenished and its local temperature was calculated from the mass and energy balance equations. They took into account the effect of longitudinal plate conduction. Their results showed that it has almost no effect on the cocurrent and counter-current configurations and its degrading effect on efficiency of cross flow is accelerated when the dry-passage length to that of the wet passage is large. Pescod (1979) proposed a simple design method for indirect evaporative cooler using parallel plastic plates with small protrusions. Although the thermal conductivity of plastic is very low, the heat transfer resistance across a thin plastic plate would be less than of the thermal resistance between the air and plate in dry side. Predictions of the efficiencies of Pescod s wet surface plate heat exchanger were found to be higher than the experimental data. Thus incomplete wetting of plate surfaces was suspected. Kettleborough and Hsieh (1983) described a counterflow indirect evaporative cooler with configuration of upward flow of the primary air and downward flows of secondary air and water. Numerical analysis was utilized to study the thermal performance of the unit. By applying wetting factor better agreement between calculated and measured performance data qualitatively was achieved. Erens and Dreyer (1993) reviewed three different models describing evaporative indirect cooler: (1) Poppe modelconsidering a variable Lewis factor, spray water evaporation rate and modeling over saturation in the secondary air; (2) Merkel model- can be derived from Poppe model by assuming a Lewis factor of unity and negligible effect of spray water evaporation and assuming that the sec- PALENC Vol 1.indd 416 3/9/2007 1:25:07 µµ

2 2nd PALENC Conference and 28th AIVC Conference on Building Low Energy Cooling and 417 ondary air never becomes over saturated; (3) Simplified model- assuming that the water temperature is constant through out the cooler. They applied these models to a cross flow indirect cooler and simplified model was recommended for small units and for initial design purpose. Chengqin and Hongxing (2006) developed an analytical model for the indirect evaporative cooling with parallel/ counter flow configurations. Similar to any other analytical model, humidity ratio of air in equilibrium with water surface was assumed to be a linear function of the surface temperature. Effects of spray water evaporation, spray water temperature variation along the heat exchanger, non unity surface wetability and Lewis factor were considered in the model. Results of analytical solutions were found to be in good agreement with those of numerical integrations. Review of the previous researches show that there are two main approaches to model indirect evaporative cooler: 1-Numerical integration; 2-Analytical model. Analytical models are limited to co-current and counter-current configurations with some simplifications and linear assumption for the saturation curve. In this paper using a numerical integration approach, three different configurations i.e. parallel, counter and cross flow are analyzed to determine the configuration that optimizes the performance. As can be seen from Figure 1 each repeated section of the cooler consists of a half of dry channel, plate wall and a half of wet channel. Figure 2 shows this section and a differential element. 2. MODELLING 2.1 Physical description of indirect cooler Indirect evaporative cooler consists of a series of parallel plates in which one is open for primary air flow and the other one is open for water and secondary air flows. Circulation water is sprayed onto the top of the heat exchanger and flows downward along wall surfaces of wet channels. Primary air flows in the alternative channels. A typical indirect cooler with counter flow configuration can be shown schematically in Figure 1. Figure 2: (a) Model section and its adjacent section, (b) Differential element. Sp: Dry channel spacing, Sa: Wet channel spacing. The following assumptions here are considered: There is no diffusion in the flow direction; Cooler is insulated from the surrounding; Specific heats are constant; Heat and mass transfer coefficients are constant and Lewis factor is unity; Plate wall, bulk water and air/water interface have the same temperature; Spray water is circulated. 2.2 Governing equations of heat and mass transfer For a differential element as shown in Figure 2b, by applying principles of mass and energy conservation, a set of differential equations can be obtained as follows Energy balance Energy balance equation for the primary air Figure 1: Typical indirect evaporative cooler with counter flow configuration. (1) PALENC Vol 1.indd 417 3/9/2007 1:25:07 µµ

3 418 2nd PALENC Conference and 28th AIVC Conference on Building Low Energy Cooling and q: Rate of heat transfer (W) : Mass flow rate (kg/ s) c p : Specific heat at constant pressure (J/kg K) t: Temperature (ºC) : Overall heat transfer coefficient (W/m 2 K) A: Area (m 2 ) Subscripts p and w stand for primary air and spray water respectively. Energy balance equation for the secondary air (2) i: Enthalpy of moist air (J/kg dry air) K: Mass transfer coefficient (kg/m 2 s) Subscripts asw and a stand for saturated air at water temperature and secondary air, respectively. This equation is a result of the assumption of Lewis number being unity (Hassan, 2005). Another approach considers the effect of variable Lewis number. Erens and Dreyer (1993) implemented the two methods on a cross flow wet liquid cooler. Their calculation showed insignificant differences between the results by these two methods. Energy balance equation for the three streams flowing inside the element With the assumption of constant water flow rate, energy balance equation for the streams flowing inside the element shown in Figure 2b is: Equation (4) sets the condition for inlet and outlet water temperature and this temperature has to be found iteratively. Equation (5) can be solved separately after once solution of the set of equations (1)-(3) has been found, because water temperature is necessary to solve this equation. The solution procedure depends on the configuration of the cooler. Three main configurations could be considered which are parallel, counter and cross flow. These configurations are shown schematically in Figure 3. The main purpose of this paper is to study the cooling performance of these configurations. For parallel flow the integration starts from the top with known conditions of primary and secondary air flows and a guessed inlet water temperature. Integration for each element proceeds from top to the bottom. At the bottom obtained value for the outlet water temperature is compared with guessed inlet value and is corrected until both inlet and outlet water temperatures would be the same. For the counter flow, because of scattered inlet conditions at the top and bottom of the heat exchanger, another iteration to find the outlet enthalpy of secondary air is added. Each time at the bottom, calculated enthalpy at the inlet and inlet enthalpy of the secondary air are compared until they would be equal. For cross flow configuration, because primary air and secondary air flow in perpendicular direction, the heat exchanger is divided into a series of two-dimensional elements. Integration starts from the upmost element in the inlet of primary air and proceeds downward. (3) Spray water temperature varies inside the heat exchanger. Because of water circulation, the inlet spray water temperature will equal the outlet spray water temperature. (4) Mass balance The mass balance for the element gives the rate of spray water evaporation (kg/s) (5) w: Humidity ratio of air (kg water/ kg dry air) Equations (1)-(5) govern heat and mass transfer in an indirect evaporative cooler. 2.3 Numerical integration procedure Equations (1)-(3) form a set of coupled ordinary differential equations which can be solved simultaneously, using a multi step numerical integration procedure. Figure 3: Three flow configurations, (a) parallel, (b) counter, (c) cross. P: primary air, W: spray water, S: Secondary air. Inlet, Outlet 3. RESULTS AND DISCUSSION Results for typical temperature profiles in various configurations of indirect cooler have been shown in Figure 4. The size of cooler is assumed m 3. For the sake of comparison between different configurations, values for mass transfer coefficient and overall heat transfer coefficient has been considered equal. Outdoor air tem- PALENC Vol 1.indd 418 3/9/2007 1:25:07 µµ

4 2nd PALENC Conference and 28th AIVC Conference on Building Low Energy Cooling and 419 perature is assumed 25ºC and has a relative humidity of 50%. Results show that counter configuration has the highest cooling efficiency. In cross configuration, averaged temperature of primary air in outlet is close to that in counter configuration. Figure 6: Effect of ratio of primary to secondary air mass flow rate on temperature for cross configuration. (mass flow rate of secondary air, ms=2.0 kg/s) Figure 4: Profiles of primary air temperature in various configurations along the flow direction. In some simplified methods, water temperature is considered constant throughout the cooler because of its circulation. Figure 5 shows the water temperature profiles along the water flow direction for various configurations. As it can be seen only for parallel flow it is expected to be constant and for counter and cross configuration it somehow varies in opposite manner. It should be noted that temperatures for cross configuration are averaged in each section because they shape a two dimensional distribution. Ratio of mass flow rates of primary and secondary air is a design parameter and its effect on cooling performance just for cross configuration is illustrated in Figure 6. Figure 5: Profiles of water temperature in various configurations along the flow direction. It can be seen from Figure 6, higher cooling efficiency is obtained as mass flow rate ratio decreases. For evaporative air conditioning, cooling capacity is defined which is determined from supply air temperature and mass flow rate. However lower primary air temperature is obtainable as mass flow rate ratio is decreased, but an optimum value for this ratio can be found from viewpoint of cooling capacity. Minimum spacing between channels should be considered while minimizing the total pressure drop (dry and wet passages). Figure 7 shows the effect of channel width on primary air temperature. In a fixed cooler volume, decreasing spacing between plates means increasing number of channels and therefore more area for heat and mass transfer. The efficiency of an evaporative cooler is defined as follows: (6) : Dry bulb temperature of primary air inlet : Dry bulb temperature of primary air outlet : Wet bulb temperature of secondary air inlet From Figure 4 it can be seen that for cross configuration a cooling efficiency of 80% is predicted which agrees with expected values for modern plate type indirect evaporative cooler (Watt, 1997). Pescod (1979) measured temperature cooling efficiency between 69 and 82 percent, while Maclaine-cross (1983) calculated 78 to 98 percent as possible in a theoretical model based upon cross-flow cooling tower theory. Excess water flow down the wet passages seemed to be the reason of difference between measured and calculated efficiencies, because mathematical model assumed stationary water layer which for finite water mass flow rate is not true. In the present work water is not stationary and it is PALENC Vol 1.indd 419 3/9/2007 1:25:08 µµ

5 420 2nd PALENC Conference and 28th AIVC Conference on Building Low Energy Cooling and circulated. For perfect surface wetting, circulation water mass flow should be several times of that evaporate. However excess water flow deteriorates cooling efficiency and should be kept as minimum as possible. 5. CONCLUSIONS Main results of modelling indirect cooler for three main configurations are as follows. Counter configuration has the highest cooling efficiency. Increasing ratio of primary to secondary air mass flow and heat exchanger plates spacing decreases cooling efficiency. Using a pre cooling indirect stage prior to a direct stage provides comfort conditions in major cities of Iran as a clean and energy efficient alternative for conventional systems. REFERENCES Figure 7: Effect of channel width on primary air temperature profile for cross configuration. 4. COMFORT PERFORMANCE Iran has a wide variety of climatic conditions. In most hot and dry regions direct evaporative cooler is a common cooling system providing comfort for residential buildings. In regions or conditions with high wet-bulb temperature that the direct systems do not provide comfort conditions, vapour-compression cooling systems are used. If a first indirect stage is added to a second direct stage, a two stage indirect/direct cooler is obtained which could provide comfort conditions for a number of cities. Commonly 65% indirect stage efficiency (performance factor) and 85% direct stage efficiency is reached. Table 1 illustrates 2.5% design conditions in four major cities of Iran. Chengqin, R., Hongxing, Y. (2006). An analytical model for the heat and mass transfer processes in indirect evaporative cooling with parallel/counter flow configurations. Heat Mass Transfer Erens, P. J., Dreyer, A. A. (1993). Modeling of indirect evaporative air cooler. Heat Mass Transfer Hasan, A. A. (2005). Performance analysis of heat transfer processes from wet and dry surfaces: cooling towers and heat exchangers. Doctoral dissertation. Helsinki University of technology. Hsu, S. T., Lavan, Z., Worek, W.M. (1989). Optimization of wet surface heat exchangers. Energy Kettleborough, C. F., Hsieh, C. S. (1983). The thermal performance of the wet surface plastic plate heat exchanger used as an indirect evaporative cooler. ASME J. Heat Transfer Maclaine-cross, I. L., Banks, P. J. (1983). A general theory of wet surface heat exchangers and its application to regenerative cooling. ASME J. Heat Transfer Pescod, D. (1979). A heat exchanger for energy saving in an air conditioning plant. Trans. ASHRAE Watt, J. R., Brown, W. K. (1997). Evaporative air conditioning handbook. Lilburn: Fairmont Press. Figure 8: shows that room air comfort condition is achieved with indirect/direct cooling systems for major cities of Iran. For each city the process consists of indirect stage cooling, direct stage cooling and room air conditioning. PALENC Vol 1.indd 420 3/9/2007 1:25:08 µµ

A NEW POLYNOMIAL BASED MODEL FOR DETERMINING COOLING TOWER EVAPORATION WATER LOSS. Aaron Powers Johnson Controls, Inc.

A NEW POLYNOMIAL BASED MODEL FOR DETERMINING COOLING TOWER EVAPORATION WATER LOSS. Aaron Powers Johnson Controls, Inc. ASHRAE and IBPSA-USA SimBuild 2016 Building Performance Modeling Conference Salt Lake City, UT August 8-12, 2016 A NEW POLYNOMIAL BASED MODEL FOR DETERMINING COOLING TOWER EVAPORATION WATER LOSS Aaron

More information

Thermal and Exergy Analysis of Counter Flow Induced Draught Cooling Tower

Thermal and Exergy Analysis of Counter Flow Induced Draught Cooling Tower International Journal of Current Engineering and Technology E-ISSN 2277 4106, P-ISSN 2347 5161 2015 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Thermal

More information

QATAR UNIVERSITY. Graduate Studies. College of Engineering INVESTIGATION OF A REGENERATIVE INDIRECT EVAPORATIVE COOLING SYSTEM.

QATAR UNIVERSITY. Graduate Studies. College of Engineering INVESTIGATION OF A REGENERATIVE INDIRECT EVAPORATIVE COOLING SYSTEM. QATAR UNIVERSITY Graduate Studies College of Engineering INVESTIGATION OF A REGENERATIVE INDIRECT EVAPORATIVE COOLING SYSTEM A Thesis in Mechanical Engineering By Ali Pakari 2015 Ali Pakari Submitted in

More information

Performance Analysis of An Indirect Evaporative Cooling System using M Cycle Devang S. Patel 1 Hardik M.Patel 2

Performance Analysis of An Indirect Evaporative Cooling System using M Cycle Devang S. Patel 1 Hardik M.Patel 2 IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 05, 2015 ISSN (online): 2321-0613 Performance Analysis of An Indirect Evaporative Cooling System using M Cycle Devang S.

More information

PERFORMANCE CORRELATIONS FOR COUNTERFLOW COOLING TOWER

PERFORMANCE CORRELATIONS FOR COUNTERFLOW COOLING TOWER Jurnal Mekanikal June 2016, Vol 39, 15-26 PERFORMANCE CORRELATIONS FOR COUNTERFLOW COOLING TOWER Mohd Yusoff Senawi* Faculty of Mechanical Engineering Universiti Teknologi Malaysia 81310 UTM Johor Bahru

More information

Development and Performance Evaluation of Indirect-Direct Evaporative Cooling System

Development and Performance Evaluation of Indirect-Direct Evaporative Cooling System Development and Performance Evaluation of Indirect-Direct Evaporative Cooling System #1 Mr. Amit T. Sadgir, #2 Prof.N.C.Ghuge #1 PG. Scholar, Matoshri college of Engineering and Research centre, Eklahare,

More information

CFD Modelling and Analysis of Different Plate Heat Exchangers

CFD Modelling and Analysis of Different Plate Heat Exchangers CFD Modelling and Analysis of Different Plate Heat Exchangers Ahmed Y Taha Al-Zubaydi a *, Guang Hong b and W. John Dartnall c Faculty of Engineering and Information Technology, UTS, Sydney, Australia

More information

COUPLING MODEL AND SOLVING APPROACH FOR PERFORMANCE EVALUATION OF NATURAL DRAFT COUNTER-FLOW WET COOLING TOWERS

COUPLING MODEL AND SOLVING APPROACH FOR PERFORMANCE EVALUATION OF NATURAL DRAFT COUNTER-FLOW WET COOLING TOWERS THERMAL SCIENCE: Year 2016, Vol. 20, No. 1, pp. 291-301 291 COUPLING MODEL AND SOLVING APPROACH FOR PERFORMANCE EVALUATION OF NATURAL DRAFT COUNTER-FLOW WET COOLING TOWERS by Wei WANG *, Deliang ZENG,

More information

Sustaining thermal power plant production in low water supply regions using cooling towers

Sustaining thermal power plant production in low water supply regions using cooling towers Energy and Sustainability V 679 Sustaining thermal power plant production in low water supply regions using cooling towers H. H. Al-Kayiem 1 & M. A. W. Theeb 2 1 Mechanical Engineering Department, Universiti

More information

Energy Conversion and Management

Energy Conversion and Management Energy Conversion and Management 51 (2010) 1298 13 Contents lists available at ScienceDirect Energy Conversion and Management journal homepage: www.elsevier.com/locate/enconman Thermal performance of cross

More information

INVESTIGATION OF THE THERMAL PERFORMANCE OF A CROSS-FLOW WATER COOLING TOWER WITH DIFFERENT PACKINGS

INVESTIGATION OF THE THERMAL PERFORMANCE OF A CROSS-FLOW WATER COOLING TOWER WITH DIFFERENT PACKINGS Number1 INVESTIGATION OF THE THERMA PERFORMANCE OF A CROSS-FOW WATER COOING TOWER WITH DIFFERENT PACKINGS ABSTRACT Dr. A. N. S. Kassim and Basim A. Rasheed University of Baghdad College of Engineering

More information

Performance Improvement of Mechanical Induced Draft Cooling Tower by Using Aluminum as Fill Medium

Performance Improvement of Mechanical Induced Draft Cooling Tower by Using Aluminum as Fill Medium Available online www.ejaet.com European Journal of Advances in Engineering and Technology, 2016, 3(11): 10-14 Research Article ISSN: 2394-658X Performance Improvement of Mechanical Induced Draft Cooling

More information

Energy and Buildings

Energy and Buildings Energy and Buildings 42 (2010) 2131 2138 Contents lists available at ScienceDirect Energy and Buildings journal homepage: www.elsevier.com/locate/enbuild A two-stage system of nocturnal radiative and indirect

More information

Theoretical and computational analysis of closed wet cooling towers and its applications in cooling of buildings

Theoretical and computational analysis of closed wet cooling towers and its applications in cooling of buildings Energy and Buildings 34 2002) 477±486 Theoretical and computational analysis of closed wet cooling towers and its applications in cooling of buildings Ala Hasan *, Kai SireÂn Helsinki University of Technology,

More information

Performance Analysis for Natural Draught Cooling Tower & Chimney through Numerical Simulation

Performance Analysis for Natural Draught Cooling Tower & Chimney through Numerical Simulation Performance Analysis for Natural Draught Cooling Tower & Chimney through Numerical Simulation Kanteyya A 1, Kiran Kumar Rokhade 2 Assistant Professor, Department of Mechanical Engineering, HKESSLN College

More information

Study on the heat transfer characteristics of an evaporative cooling tower B

Study on the heat transfer characteristics of an evaporative cooling tower B Study on the heat transfer characteristics of an evaporative cooling tower B Paisarn Naphon Department of Mechanical Engineering, Faculty of Engineering, Srinakharinwirot University, 63 Rangsit-Nakhonnayok,

More information

IMPLEMENTATION OF ANALYTICAL MODELS FOR PASSIVE DOWN-DRAFT EVAPORATIVE COOLING (PDEC) TOWER WITH SPRAY SYSTEMS

IMPLEMENTATION OF ANALYTICAL MODELS FOR PASSIVE DOWN-DRAFT EVAPORATIVE COOLING (PDEC) TOWER WITH SPRAY SYSTEMS IMPLEMENTATION OF ANALYTICAL MODELS FOR PASSIVE DOWN-DRAFT EVAPORATIVE COOLING (PDEC) TOWER WITH SPRAY SYSTEMS Daeho Kang 1, Richard K. Strand 2 1 Department of Environmental Control Technology, New York

More information

Application of a cooling tower model for optimizing energy use

Application of a cooling tower model for optimizing energy use Advances in Fluid Mechanics X 305 Application of a cooling tower model for optimizing energy use G. C. O Mary & D. F. Dyer Department of Mechanical Engineering, Auburn University, USA Abstract The overall

More information

Performance Analysis of Cooling Tower

Performance Analysis of Cooling Tower Performance Analysis of Cooling Tower M.V.H.Satish Kumar, Associate Professor, Department of Mechanical Engineering PVP Siddhartha Institute of Technology, Kanuru, Vijayawada 7. Andhra Pradesh, India.

More information

MODELLING AND SIMULATION OF A TYPICAL CROSS FLOW COOLING TOWER

MODELLING AND SIMULATION OF A TYPICAL CROSS FLOW COOLING TOWER 1. Amr Ahmad YASEEN, 1. Salah El-Din El-MORSHEDY, 1. Hesham ELKHATIB, 2. Masoud Abd El-Hakeem El-SHAFEI, 2. Tarek Mohammad ABOUL-FOTOUH MODELLING AND SIMULATION OF A TYPICAL CROSS FLOW COOLING TOWER 1.

More information

Performance of a counterflow heat exchanger with heat loss through the wall at the cold end

Performance of a counterflow heat exchanger with heat loss through the wall at the cold end Cryogenics 39 (1999) 43 5 Performance of a counterflow heat exchanger with heat loss through the wall at the cold end S. Pradeep Narayanan, G. Venkatarathnam * Department of Mechanical Engineering, Indian

More information

INVESTIGATION ON THE OPTIMUM DESIGN OF HEAT EXCHANGERS IN A HYBRID CLOSED CIRCUIT COOLING TOWER

INVESTIGATION ON THE OPTIMUM DESIGN OF HEAT EXCHANGERS IN A HYBRID CLOSED CIRCUIT COOLING TOWER 52 INVESTIGATION ON THE OPTIMUM DESIGN OF HEAT EXCHANGERS IN A HYBRID CLOSED CIRCUIT COOLING TOWER M. M. A. Sarker Department of Mathematics, BUET, Dhaka-1000, Bangladesh. Corresponding email: masarker@math.buet.ac.bd

More information

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Available online at   ScienceDirect. Procedia Engineering 121 (2015 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 121 (2015 ) 881 890 9th International Symposium on Heating, Ventilation and Air Conditioning (ISHVAC) and the 3rd International

More information

Fresh air pre-cooling and energy recovery by using indirect evaporative cooling in hot and humid region a case study in Hong Kong

Fresh air pre-cooling and energy recovery by using indirect evaporative cooling in hot and humid region a case study in Hong Kong Available online at www.sciencedirect.com ScienceDirect Energy Procedia 61 (2014 ) 126 130 The 6 th International Conference on Applied Energy ICAE2014 Fresh air pre-cooling and energy recovery by using

More information

Critical exergy analysis of counterflow reversibly used cooling towers

Critical exergy analysis of counterflow reversibly used cooling towers Critical exergy analysis of counterflow reversibly used cooling towers Jiasheng Wu 1, Guoqiang Zhang 1,*, Quan Zhang 1, Jin Zhou 1 1 College of Civil Engineering, Hunan University, Changsha, China * Corresponding

More information

Cooling Tower Operation

Cooling Tower Operation Cooling Tower Operation Forced draught cooling towers use the evaporation of a liquid (often water) into air to achieve cooling. The tower often consists of a sprinkler system which wets a high-surface-area

More information

Modeling Techniques for Increased Accuracy

Modeling Techniques for Increased Accuracy SECTION 1 Modeling Techniques for Increased Accuracy Ed Haack Duke Energy 1-1 Modeling Techniques for Increased Accuracy By Ed Haack, Duke Power Company The PEPSE model for the Catawba Units have been

More information

Sensitivity Studies of a Low Temperature Low Approach Direct Cooling Tower for Building Radiant Cooling Systems

Sensitivity Studies of a Low Temperature Low Approach Direct Cooling Tower for Building Radiant Cooling Systems Dublin Institute of Technology ARROW@DIT Conference Papers School of Mechanical and Design Engineering 212-7-16 Sensitivity Studies of a Low Temperature Low Approach Direct Cooling Tower for Building Radiant

More information

Heat Rejection using Cooling Towers

Heat Rejection using Cooling Towers MEBS6006 Environmental Services I http://www.hku.hk/bse/mebs6006 Heat Rejection using Cooling Towers Dr. Benjamin P.L. Ho (beplho@yahoo.com.hk) Part-time Lecturer Department of Mechanical Engineering The

More information

Potential of passive design strategies using the free-running temperature

Potential of passive design strategies using the free-running temperature 850 2nd PALENC Conference and 28th AIVC Conference on Building Low Energy Cooling and Potential of passive design strategies using the free-running temperature L. Rosales, M. E. Hobaica Universidad Central

More information

Heat Transfer Correlations for Low Approach Evaporative Cooling Systems in Buildings

Heat Transfer Correlations for Low Approach Evaporative Cooling Systems in Buildings Heat Transfer Correlations for ow Approach Evaporative Cooling Systems in Buildings B. Costelloe, D.P. Finn To cite this version: B. Costelloe, D.P. Finn. Heat Transfer Correlations for ow Approach Evaporative

More information

COOLING TOWER DESIGN FOR CENTRAL GENERATORS OF CUET, BANGLADESH. Mohammad Sharif Khan, Golam Mainuddin, Abu Sadat Mohammad Sayem, Nadeem Nafis

COOLING TOWER DESIGN FOR CENTRAL GENERATORS OF CUET, BANGLADESH. Mohammad Sharif Khan, Golam Mainuddin, Abu Sadat Mohammad Sayem, Nadeem Nafis Proceedings of the 4 th BSME-ASME International Conference on Thermal Engineering 7-9 December, 008, Dhaka, Bangladesh COOLING TOWER DESIGN FOR CENTRAL GENERATORS OF CUET, BANGLADESH. Mohammad Sharif Khan,

More information

Heat and Mass Transfer in Convective Drying Processes

Heat and Mass Transfer in Convective Drying Processes Presented at the COMSOL Conference 2008 Hannover Heat and Mass Transfer in Convective Drying Processes Camelia GAVRILA* Adrian Gabriel GHIAUS* Ion GRUIA** *Technical University of Civil Engineering Bucharest

More information

OPTIMIZATION OF PARAMETERS FOR HEAT RECOVERY STEAM GENERATOR (HRSG) IN COMBINED CYCLE PLANTS

OPTIMIZATION OF PARAMETERS FOR HEAT RECOVERY STEAM GENERATOR (HRSG) IN COMBINED CYCLE PLANTS OPTIMIZATION OF PARAMETERS FOR HEAT RECOVERY STEAM GENERATOR (HRSG) IN COMBINED CYCLE PLANTS Muammer Alus, Milan V. Petrovic University of Belgrade-Faculty of Mechanical Engineering, Laboratory of Thermal

More information

The formation of oscillation marks in continuous casting of steel

The formation of oscillation marks in continuous casting of steel The formation of oscillation marks in continuous casting of steel 1 Introduction Continuous casting is a method of producing an infinite solid strand from liquid metal by continuously solidifying it as

More information

M. Karagiorgas, M. Tsagouris, K. Galatis BONAIR Meletitiki, Greece. A. Botzios-Valaskakis CRES, Greece ABSTRACT

M. Karagiorgas, M. Tsagouris, K. Galatis BONAIR Meletitiki, Greece. A. Botzios-Valaskakis CRES, Greece ABSTRACT 491 Solar assisted heat pump in dual mode: direct and indirect space. Heating by the air collectors. Simulation results and evaluation with measurement results M. Karagiorgas, M. Tsagouris, K. Galatis

More information

Performance Improvement on Water-cooled Cold-Plate

Performance Improvement on Water-cooled Cold-Plate Proceedings of the 4th WSEAS International Conference on Heat and Mass Transfer, Gold Coast, Queensland, Australia, January 17-19, 2007 104 Performance Improvement on Water-cooled Cold-Plate SHYAN-FU CHOU,

More information

ME ENGINEERING THERMODYNAMICS UNIT III QUESTION BANK SVCET

ME ENGINEERING THERMODYNAMICS UNIT III QUESTION BANK SVCET 1. A vessel of volume 0.04m 3 contains a mixture of saturated water and steam at a temperature of 250 0 C. The mass of the liquid present is 9 kg. Find the pressure, mass, specific volume, enthalpy, entropy

More information

Process intergration: Cooling water systems design

Process intergration: Cooling water systems design Process intergration: Cooling water systems design Khunedi Vincent Gololo a,b and Thokozani Majozi a* a Department of Chemical Engineering, University of Pretoria, Lynnwood Road, Pretoria, 0002, South

More information

Thermal performance of a closed wet cooling tower for chilled ceilings: measurement and CFD simulation

Thermal performance of a closed wet cooling tower for chilled ceilings: measurement and CFD simulation INTERNATIONAL JOURNAL OF ENERGY RESEARCH Int. J. Energy Res. 2000; 24:1171}1179 Thermal performance of a closed wet cooling tower for chilled ceilings: measurement and CFD simulation Sa!a Ri!at*, Armando

More information

Enhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis

Enhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Enhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis Elias

More information

EFFECTS OF WEATHERS AND INDOOR TEMPERATURES ON PERFORMANCE OF ENERGY RECOVERY VENTILATOR. Yanping Zhou, Jingyi Wu, Ruzhu Wang

EFFECTS OF WEATHERS AND INDOOR TEMPERATURES ON PERFORMANCE OF ENERGY RECOVERY VENTILATOR. Yanping Zhou, Jingyi Wu, Ruzhu Wang EFFECTS OF WEATHERS AND INDOOR TEMPERATURES ON PERFORMANCE OF ENERGY RECOVERY VENTILATOR Yanping Zhou, Jingyi Wu, Ruzhu Wang (Institute of Refrigeration and Cryogenics, Shanghai Jiaotong University, Shanghai,

More information

Modern CFD application on aerothermal engineering aspects of natural draft cooling towers

Modern CFD application on aerothermal engineering aspects of natural draft cooling towers CHAPTER 6 Modern CFD application on aerothermal engineering aspects of natural draft cooling towers D. Bohn 1 & K. Kusterer 2 1 Institute of Steam and Gas Turbines, RWTH Aachen University, Aachen, Germany.

More information

A cooling tower combined with chilled ceiling: system optimisation

A cooling tower combined with chilled ceiling: system optimisation A cooling tower combined with chilled ceiling: system optimisation Ala Hasan 1, Mika Vuolle 1, Kai Sirén 1, Riikka Holopainen 2 and Pekka Tuomaala 2 1 Laboratory for HVAC-technology, Helsinki University

More information

Coupling Model and Solving Approach for Performance Evaluation of Natural Draft Counter-Flow Wet Cooling Towers

Coupling Model and Solving Approach for Performance Evaluation of Natural Draft Counter-Flow Wet Cooling Towers 1 Coupling Model and Solving Approach for Performance Evaluation of Natural Draft Counter-Flow Wet Cooling Towers Wei Wang*, Deliang Zeng, Yong Hu, Jizhen Liu, Yuguang Niu State Key Laboratory of Alternate

More information

2. TECHNICAL DESCRIPTION OF THE PROJECT

2. TECHNICAL DESCRIPTION OF THE PROJECT 2. TECHNICAL DESCRIPTION OF THE PROJECT 2.1. What is a Combined Cycle Gas Turbine (CCGT) Plant? A CCGT power plant uses a cycle configuration of gas turbines, heat recovery steam generators (HRSGs) and

More information

CFD and Wind Tunnel Study of the Performance of a Multi- Directional Wind Tower with Heat Transfer Devices

CFD and Wind Tunnel Study of the Performance of a Multi- Directional Wind Tower with Heat Transfer Devices Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (2015 ) 1692 1697 The 7 th International Conference on Applied Energy ICAE2015 CFD and Wind Tunnel Study of the Performance of

More information

1. To improve heat exchange between a gas & a liquid stream in a heat exchanger, it is decided to use fins. Correct the suitable option.

1. To improve heat exchange between a gas & a liquid stream in a heat exchanger, it is decided to use fins. Correct the suitable option. 1. To improve heat exchange between a gas & a liquid stream in a heat exchanger, it is decided to use fins. Correct the suitable option. a) Fins are generally attached on gas side. b) Fins are generally

More information

Thermal insulation of buildings and cooling demand

Thermal insulation of buildings and cooling demand 411 Thermal insulation of buildings and cooling demand C. Hamans Rockwool International S.A.,The Netherlands ABSTRACT Thermal insulation in the warm climate can reduce the energy demand for cooling in

More information

07059, Antalya / TURKEY ABSTRACT

07059, Antalya / TURKEY   ABSTRACT 1 The Effects of Natural Ventilation Air Exchange on Psychrometric Results in Poultry Houses in Hot Environment---Design Characteristics S. Mutaf 1, S.Alkan 1, N.Seber 1 1 Akdeniz University, Faculty of

More information

Keywords: CFD; Cooling tower; Evaporative cooling; NTU; Spray water

Keywords: CFD; Cooling tower; Evaporative cooling; NTU; Spray water International Journal of Technology (205) 3: 365-379 ISSN 2086-964 IJTech 205 EXPERIMENTAL AND SIMULATION STUDY ON THE PERFORMANCE OF COUNTER FLOW CLOSED COOLING TOWER SYSTEMS Budihardjo *, Nasruddin,

More information

Review on Numerical Simulation of frosting behavior on Ambient air vaporizer

Review on Numerical Simulation of frosting behavior on Ambient air vaporizer Review on Numerical Simulation of frosting behavior on Ambient air vaporizer Lokesh Shivrajsingh Thakur Masters in Thermal Engineering, Mechanical Engineering Department, A.D. Patel institute of technology,

More information

Investigating Two Configurations of a Heat Exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System

Investigating Two Configurations of a Heat Exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System Journal of Energy and Power Engineering 7 (2013) 66-73 D DAVID PUBLISHING Investigating Two Configurations of a Heat Exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System

More information

Compound ejectors with improved off-design performance

Compound ejectors with improved off-design performance Compound ejectors with improved off-design performance Dr M. Dennis 1, Dr K. Garzoli 2 1,2 Centre for Sustainable Energy Systems School of Engineering The Australian National University Canberra, ACT 0200

More information

Supersonic Nozzle Flow in the Two-Phase Ejector as Water Refrigeration System by Using Waste Heat

Supersonic Nozzle Flow in the Two-Phase Ejector as Water Refrigeration System by Using Waste Heat HEFAT2012 9 th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics 16 18 July 2012 Malta Supersonic Nozzle Flow in the Two-Phase Ejector as Water Refrigeration System by Using

More information

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Available online at   ScienceDirect. Energy Procedia 78 (2015 ) Available online at www.sciencedirect.com ScienceDirect Energy Procedia 8 (201 ) 2421 2426 6th International Building Physics Conference, IBPC 201 Technical potential of evaporative cooling in Danish and

More information

Solar Distillation System Based on Multiple-Effect Diffusion Type Still

Solar Distillation System Based on Multiple-Effect Diffusion Type Still Solar Distillation System Based on Multiple-Effect Diffusion Type Still Bin-Juine Huang *1, Tze-Ling Chong 1, Hsien-Shun Chang 1, Po-Hsien Wu 1, Yeong-Chuan Kao 2 1 Department of Mechanical Engineering

More information

Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems

Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water

More information

CFD ANALYSIS OF CONVECTIVE FLOW IN A SOLAR DOMESTIC HOT WATER STORAGE TANK

CFD ANALYSIS OF CONVECTIVE FLOW IN A SOLAR DOMESTIC HOT WATER STORAGE TANK International Journal of Scientific & Engineering Research Volume 4, Issue 1, January-2013 1 CFD ANALYSIS OF CONVECTIVE FLOW IN A SOLAR DOMESTIC HOT WATER STORAGE TANK Mr. Mainak Bhaumik M.E. (Thermal

More information

An Investigation in Performance Enhancement of Induced Draft Counter Flow Wet Cooling Tower

An Investigation in Performance Enhancement of Induced Draft Counter Flow Wet Cooling Tower An Investigation in Performance Enhancement of Induced Draft Counter Flow Wet Cooling Tower Manoj Kumar Chopra 1, Rahul Kumar 2 1Vice Principal, Dean Academic & Head, Dept. Of Mechanical Engineering, R.K.D.F

More information

R13. II B. Tech I Semester Regular/Supplementary Examinations, Oct/Nov THERMODYNAMICS (Com. to ME, AE, AME) Time: 3 hours Max.

R13. II B. Tech I Semester Regular/Supplementary Examinations, Oct/Nov THERMODYNAMICS (Com. to ME, AE, AME) Time: 3 hours Max. SET - 1 1. a) Discuss about PMM I and PMM II b) Explain about Quasi static process. c) Show that the COP of a heat pump is greater than the COP of a refrigerator by unity. d) What is steam quality? What

More information

COOLING EFFECTIVENESS OF MIST PRECOOLER FOR IMPROVING ENERGY PERFORMANCE OF AIR-COOLED CHILLER

COOLING EFFECTIVENESS OF MIST PRECOOLER FOR IMPROVING ENERGY PERFORMANCE OF AIR-COOLED CHILLER Yu, F. W., et al.: Cooling Effectiveness of Mist Precooler for THERMAL SCIENCE: Year 2018, Vol. 22, No. 1A, pp. 193-204 193 COOLING EFFECTIVENESS OF MIST PRECOOLER FOR IMPROVING ENERGY PERFORMANCE OF AIR-COOLED

More information

MODELING AND EXPERIMENTAL VALIDATION IN PARTIALLY WET CONDITIONS OF AN AIR-TO-AIR HEAT RECOVERY EXCHANGER

MODELING AND EXPERIMENTAL VALIDATION IN PARTIALLY WET CONDITIONS OF AN AIR-TO-AIR HEAT RECOVERY EXCHANGER Proceedings of Building Simulation 211: 1 2 3 4 5 6 7 8 9 1 MODELING AND EXPERIMENTAL VALIDATION IN PARTIALLY WET CONDITIONS OF AN AIR-TO-AIR HEAT RECOVERY EXCHANGER ABSTRACT Samuel Gendebien 1, Stephane

More information

Design Features of Combined Cycle Systems

Design Features of Combined Cycle Systems Design Features of Combined Cycle Systems 1.0 Introduction As we have discussed in class, one of the largest irreversibilities associated with simple gas turbine cycles is the high temperature exhaust.

More information

PARAMETRIC STUDY OF GAS TURBINE CYCLE COUPLED WITH VAPOR COMPRESSION REFRIGERATION CYCLE FOR INTAKE AIR COOLING

PARAMETRIC STUDY OF GAS TURBINE CYCLE COUPLED WITH VAPOR COMPRESSION REFRIGERATION CYCLE FOR INTAKE AIR COOLING International Journal of Mechanical Engineering and Technology (IJMET) Volume 9, Issue 9, September 2018, pp. 248 261, Article ID: IJMET_09_09_029 Available online at http://www.iaeme.com/ijmet/issues.asp?jtype=ijmet&vtype=9&itype=9

More information

Performance Evaluation of an Integrated Hybrid Photovoltaic/Thermal (PV/T) Greenhouse

Performance Evaluation of an Integrated Hybrid Photovoltaic/Thermal (PV/T) Greenhouse 12 EAAS & ARF. All rights reserved Performance Evaluation of an Integrated Hybrid Photovoltaic/Thermal (PV/T) Greenhouse Shahana Parveen 1, Dr. Qamar Parvez Rana 2 Jamia Hamdard, India Shahanaparveen_amu@gmail.com

More information

Steam compression with inner evaporative spray cooling: a case study

Steam compression with inner evaporative spray cooling: a case study Int. J. Computer Applications in Technology, Vol. 21, No. 4, 2004 189 Steam ression with inner evaporative spray cooling: a case study Jian Qiu, Zhaolin Gu* and Guoguang Cai School of Environmental and

More information

Investigating two configurations of a heat exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System (IHICSSWHS)

Investigating two configurations of a heat exchanger in an Indirect Heating Integrated Collector Storage Solar Water Heating System (IHICSSWHS) European Association for the Development of Renewable Energies, Environment and Power Quality (EA4EPQ) International Conference on Renewable Energies and Power Quality (ICREPQ 12) Santiago de Compostela

More information

Heat Exchangers. Introduction. Classification of heat Exchangers

Heat Exchangers. Introduction. Classification of heat Exchangers Heat Exchangers Introduction Heat Exchanger is an adiabatic steady flow device in which two flowing fluids exchange or transfer heat between themselves due to a temperature difference without losing or

More information

Creating a New Model to Predict Cooling Tower Performance and Determining Energy Saving Opportunities through Economizer Operation

Creating a New Model to Predict Cooling Tower Performance and Determining Energy Saving Opportunities through Economizer Operation University of Massachusetts Amherst ScholarWorks@UMass Amherst Masters Theses May 2014 - current Dissertations and Theses 2015 Creating a New Model to Predict Cooling Tower Performance and Determining

More information

Ceiling Radiant Cooling Panels

Ceiling Radiant Cooling Panels Copyright 2006, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc This posting is by permission from ASHE Journal This article may not be copied nor distributed in either paper

More information

Ceiling Radiant Cooling Panels

Ceiling Radiant Cooling Panels 2006, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc (wwwashraeorg) Published in ASHE Journal Vol 48, Oct 2006 For personal use only Additional reproduction, distribution,

More information

Air Cycle Refrigeration Systems Nagendra M CBM Engineer, Hindusthan Zink.Ltd The specific objectives of the lesson This lesson discusses various gas cycle refrigeration systems based on air, namely: 1.

More information

Liquid-Solid Phase Change Modeling Using Fluent. Anirudh and Joseph Lam 2002 Fluent Users Group Meeting

Liquid-Solid Phase Change Modeling Using Fluent. Anirudh and Joseph Lam 2002 Fluent Users Group Meeting Liquid-Solid Phase Change Modeling Using Fluent Anirudh and Joseph Lam 2002 Fluent Users Group Meeting Solidification Model FLUENT can be used to solve fluid flow problems involving both solidification

More information

Energy towers A renewable energy technology for producing electricity and desalinated water in arid climates

Energy towers A renewable energy technology for producing electricity and desalinated water in arid climates 1167 Energy towers A renewable energy technology for producing electricity and desalinated water in arid climates D. Zaslavsky, R. Guetta and S. Hassid Technion-Israel Institute of Technology, Israel Abstract

More information

Adsorption Air Conditioner for Electric Vehicle Applications

Adsorption Air Conditioner for Electric Vehicle Applications UCRL-JC-117938 Rev 1 PREPRINT Adsorption Air Conditioner for Electric Vehicle Applications Salvador M. Aceves This paper was prepared for submittal to the American Institute of Chemical Engineers San Francisco,

More information

COUPLED FEM MODEL FOR CONCRETE EXPOSED TO FIRE LOADING

COUPLED FEM MODEL FOR CONCRETE EXPOSED TO FIRE LOADING COUPLED FEM MODEL FOR CONCRETE EXPOSED TO FIRE LOADING Ji í Surovec (1), Petr Kabele (1) and Jan ervenka (2) (1) Czech Technical University in Prague, Czech Republic (2) ervenka Consulting, Czech Republic

More information

ERT 318/4 UNIT OPERATIONS SEMESTER 1 (2013/2014)

ERT 318/4 UNIT OPERATIONS SEMESTER 1 (2013/2014) ERT 318/4 UNIT OPERATIONS SEMESTER 1 (2013/2014) WATER COOLING TOWER School of Bioprocess Engineering University Malaysia Perlis EXPERIMENT Water Cooling Tower 1.0 OBJECTIVES 1.1 To determine energy and

More information

Contents. Part I Design: Theory and Practice 1

Contents. Part I Design: Theory and Practice 1 Contents Preface to the Fourth Edition Preface to the Third Edition Preface to the Second Edition Preface to the First Edition Foreword to the First Edition About the Author xix xxiii xxvii xxix xxxi xxxiii

More information

Experimental Performance Analyses of a Heat Recovery System for Mechanical Ventilation in Buildings

Experimental Performance Analyses of a Heat Recovery System for Mechanical Ventilation in Buildings Available online at www.sciencedirect.com ScienceDirect Energy Procedia 82 (2015 ) 465 471 ATI 2015-70th Conference of the ATI Engineering Association Experimental Performance Analyses of a Heat Recovery

More information

The 3-D Numerical Simulation of a Walking Beam Type Slab Heating Furnace with Regenerative Burners

The 3-D Numerical Simulation of a Walking Beam Type Slab Heating Furnace with Regenerative Burners The 3-D Numerical Simulation of a Walking Beam Type Slab Heating Furnace with Regenerative Burners Jiin-Yuh Jang, Chien-Nan Lin, Sheng-Chih Chang, Chao-Hua Wang Abstract: This study investigates the furnace

More information

INDUSTRIAL COOLING TOWER DESIGN AND OPERATION IN THE MODERATE-CONTINENTAL CLIMATE CONDITIONS

INDUSTRIAL COOLING TOWER DESIGN AND OPERATION IN THE MODERATE-CONTINENTAL CLIMATE CONDITIONS Laković, M. S., et al.: Industrial Cooling Tower Design and Operations in the S203 INDUSTRIAL COOLING TOWER DESIGN AND OPERATION IN THE MODERATE-CONTINENTAL CLIMATE CONDITIONS by Mirjana S. LAKOVI] a*,

More information

THERMAL ANALYSIS OF WELDING IN T-JOINT PLATES USING FINITE ELEMENT ANALYSIS

THERMAL ANALYSIS OF WELDING IN T-JOINT PLATES USING FINITE ELEMENT ANALYSIS THERMAL ANALYSIS OF WELDING IN T-JOINT PLATES USING FINITE ELEMENT ANALYSIS Mr. K.KRISHNAMOORTHY 1, Mr.S.SHEIK SULAIMAN 2, Mr.R.KARTHIKEYAN. 3 Assistant Professor/Mechanical Engineering, Francis Xavier

More information

on a Run-Around Membrane Energy Exchanger Saskatoon

on a Run-Around Membrane Energy Exchanger Saskatoon The Impacts of Outdoor Air Conditions and Non-Uniform Exchanger Channels on a Run-Around Membrane Energy Exchanger A Thesis Submitted to the College of Graduate Studies and Research In Partial Fulfillment

More information

- 2 - SME Q1. (a) Briefly explain how the following methods used in a gas-turbine power plant increase the thermal efficiency:

- 2 - SME Q1. (a) Briefly explain how the following methods used in a gas-turbine power plant increase the thermal efficiency: - 2 - Q1. (a) Briefly explain how the following methods used in a gas-turbine power plant increase the thermal efficiency: i) regenerator ii) intercooling between compressors (6 marks) (b) Air enters a

More information

Heat Transfer Correlations for Low Approach Evaporative Cooling Systems in Buildings

Heat Transfer Correlations for Low Approach Evaporative Cooling Systems in Buildings Dublin Institute of Technology ARROW@DIT Articles School of Civil and Structural Engineering 2009-01-01 Heat Transfer Correlations for Low Approach Evaporative Cooling Systems in Buildings Ben Costelloe

More information

Parameters of the Atmospheric Air in the Dimensioning of Industrial Cooling Tower

Parameters of the Atmospheric Air in the Dimensioning of Industrial Cooling Tower 17 th Symposium on Thermal Science and Engineering of Serbia Sokobanja, Serbia, October 20 23, 2015 Society of Thermal Engineers of Serbia Faculty of Mechanical Engineering in Niš Parameters of the Atmospheric

More information

II. SYSTEM DESCRIPTION AND MATHEMATICAL MODELING

II. SYSTEM DESCRIPTION AND MATHEMATICAL MODELING Mathematical Modeling and Analysis of Absorption Refrigeration System Using Waste Heat of Diesel Genset Yashvir Singh 1*, Deepak Kumar 2, Ajay Kumar 3, Amneesh Singla 4 1,2,3,4 Mechanical Engineering,

More information

Wastewater Pretreatment by Normal Freezing Cool Thermal Storage Process with Convective Heat Transfer Mechanism

Wastewater Pretreatment by Normal Freezing Cool Thermal Storage Process with Convective Heat Transfer Mechanism Tamkang Journal of Science and Engineering, Vol. 14, No. 2, pp. 115 122 (2011) 115 Wastewater Pretreatment by Normal Freezing Cool Thermal Storage Process with Convective Heat Transfer Mechanism Chao-Ching

More information

Modelling and Simulation of Thermodynamic Processes of Vertical Shaft Kiln in Magnesia Plant Using CFD Code Fluent

Modelling and Simulation of Thermodynamic Processes of Vertical Shaft Kiln in Magnesia Plant Using CFD Code Fluent Proceedings of the 5th IASME/WSEAS Int. Conference on Heat Transfer, Thermal Engineering and Environment, Athens, Greece, August 25-27, 2007 85 Modelling and Simulation of Thermodynamic Processes of Vertical

More information

Improving the Energy Performance of HVAC Systems in Operating Theatres by Using Heat Recovery Devices

Improving the Energy Performance of HVAC Systems in Operating Theatres by Using Heat Recovery Devices Improving the Performance of HVAC Systems in Operating Theatres by Using Heat Recovery Devices Mohammad Ahmadzadehtalatapeh* *Department of Mechanical Engineering, Chabahar Maritime University, Iran. (m_ahmadzadeh56@yahoo.com)

More information

Introduction. Objective

Introduction. Objective Introduction In this experiment, you will use thin-film evaporator (TFE) to separate a mixture of water and ethylene glycol (EG). In a TFE a mixture of two fluids runs down a heated inner wall of a cylindrical

More information

The Effect of High Temperature Feedwater on the Performance of an Evaporative Cooler Installed in a Gas Turbine Combustion Air Inlet System

The Effect of High Temperature Feedwater on the Performance of an Evaporative Cooler Installed in a Gas Turbine Combustion Air Inlet System THE AMERICAN SOCIETY OF MECHANICAL ENGINEERS 345 E. 47th St, Now York. N.Y. 10017 96-GT-229 The Society shall not be responsible for statements or opinions advanced in papers or discussion at meetings

More information

The Performance of Compression-absorption Heat Pump System Using Low-temperature Geothermal Tail Water

The Performance of Compression-absorption Heat Pump System Using Low-temperature Geothermal Tail Water Proceedings World Geothermal Congress 01 Melbourne, Australia, 19- April 01 The Performance of Compression-absorption Heat Pump System Using Low-temperature Geothermal Tail Water Yulie Gong, Chao Luo,

More information

A STEADY STATE MODEL FOR THE HEAT PIPE-ENCAPSULATED NUCLEAR HEAT SOURCE

A STEADY STATE MODEL FOR THE HEAT PIPE-ENCAPSULATED NUCLEAR HEAT SOURCE Joint International Workshop: Nuclear Technology and Society Needs for Next Generation Berkeley, California, January 6-8, 2008, Berkeley Faculty Club, UC Berkeley Campus A STEADY STATE MODEL FOR THE HEAT

More information

Two-Phase Distribution of R-134a in a Header of a Parallel Flow Heat Exchanger

Two-Phase Distribution of R-134a in a Header of a Parallel Flow Heat Exchanger Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering Two-Phase Distribution of Ra in a Header of a Parallel Flow Heat Exchanger Naehyun

More information

THE ITER HEAT REJECTION CHALLENGE.

THE ITER HEAT REJECTION CHALLENGE. THE ITER HEAT REJECTION CHALLENGE Steve Ployhar 1, Warren Curd 1, Ajith Kumar 2, Giovanni Dell Orco 1, Babulal Gopalapillai 1, Dinesh Gupta 2, Hiren Patel 2, Keun-Pack Chang 1, Fan Li 1, Fabio Somboli

More information

Study of a high efficiency residential split water-cooled air conditioner

Study of a high efficiency residential split water-cooled air conditioner Applied Thermal Engineering 25 (2005) 1599 1613 www.elsevier.com/locate/apthermeng Study of a high efficiency residential split water-cooled air conditioner S.S. Hu, B.J. Huang * Department of Mechanical

More information

Effect of Drying Condition on Natural Block Rubber: Simulation and Experiments

Effect of Drying Condition on Natural Block Rubber: Simulation and Experiments Effect of Drying Condition on Natural Block Rubber: Simulation and s Tasara, J. 1, Tirawanichakul, S. 1* and Tirawanichakul, Y. 1 Department of Chemical Engineering, Faculty of Engineering, Department

More information

LAHU Heat Recovery System Optimal Operation and Control Schedules

LAHU Heat Recovery System Optimal Operation and Control Schedules Yujie Cui Nexant, Inc., 44 South Broadway, 5th Floor, White Plains, NY 10601 e-mail: ycui@nexant.com Mingsheng Liu Architectural Engineering, University of Nebraska Lincoln, 206C, PKI, 1110 S. 67th St.,

More information