1 A M E R I C A N PERC-RITE WASTEWATER DRIP DISPERSAL SYSTEMS MICRO MOUND TM DESIGNERS GUIDE Use With Approved Netafim Tubings PATENT NO. 5,200,065 PATENT NO. 5,984,574 PATENT NO. 6,261,452B1 Innovative Technology for the Environmental Age American Manufacturing Company, Inc P.O. Box 549 Manassas, Virginia Copyright

2 AMERICAN Manufacturing Company, Inc.

3 Micro-Mound TM DESIGNERS GUIDE AMERICAN PERC-RITE SEPTIC OR SECONDARY TREATED DRIP SYSTEMS 1 ZONE or 2 ZONE SIMPLEX PATENT NOs. 5,200,065 & 5,984,574 & 6,261,452B1 TABLE OF CONTENTS Page No 1. SYSTEM COMPONENTS 2 2. LOADING RATE CHART 7 3. ZONE DETAIL TABLE 9 4. INSTALLATION INSTRUCTIONS STANDARD DETAIL DRAWINGS WARRANTY 24 This Micro-Mound TM Series Perc-Rite Drip System Designer s Guide is for the engineer or experienced non-engineer designer. Procedures have been developed to size, layout and design a low profile Wisconsin Sand Mound with a Perc- Rite Drip System using tables and a Micro Soft Excel spread sheet instead of extensive engineering calculations. The tables have conditions that allow the designer considerable flexibility to layout systems in a variety of siting conditions without being required to do engineering calculations to determine design suitability. The Mound 2000 design manual (Wisconsin Mound Soil Absorption System #15.22, Small Scale Waste Management Project, James Converse & Jerry Tyler, January 2000) represents the most current design guidelines. The manual places conditions on instantaneous dosing of primary infiltrative surface plus orifices per square foot, gallons per orifice, and landscape linear loads. The Perc-Rite process will accommodate virtually any type of pretreatment process, septic tank (anaerobic), aerobic, lagoon, or any type of treatment facility. When advanced system design is required, outside the limitations of this design procedure, the designer must reference the Mound 2000 manual and the Perc-Rite design manual located on our web site and complete a detailed calculation sheet to determine suitability. Reference our web site at The branding of this Wisconsin Mound design as the Micro-Mound TM is due to enhancements to the traditional design. Enhancements to the design include flow equalization, low profile due to elimination of gravel depth and cover requirements, plus enhanced treatment due to dispersal of filtered effluent with drip micro-dosing. Additional pretreatment of the effluent to a secondary standard may be provided. The Perc-Rite Drip System is a unique fluid handling system for dispersal of effluent wastewater in soil systems. The system incorporates equal volume micro-dosing across the entire absorption area, filtration, time and level controlled application and ultra-low rate drip distribution. These characteristics enhance the unsaturated, aerobic condition within to sand bed, providing well managed intermittent sand filter quality, thus later enhancing effluent entrance into the natural soil interface. This timed instantaneous micro-dosing through hundreds of discharge points increases the residence time of the effluent within the sand above the soil, eliminating saturated flow, and thus enhancing final treatment and disinfection. Page No. 1 Copyright 2006

4 Perc-Rite Drip Systems provide for easy installation of the field distribution lines. The effluent discharge volume from each emitter is very small. The installation of the Micro-Mound TM system has a very low profile so little site impact is observed even in established lawns or park areas. After installation there is minimal visible impact compared to other surface infiltration systems. This system is especially suited for landscaped or wooded areas near buildings, trailer parks, apartment complexes or residential subdivisions. AMERICAN Manufacturing Company, Inc. Perc-Rite Drip Dispersal Patent # 5,984,574 Patent # 5,200,065 Patent # 6,261,452B1 Copyright 2006 Page No. 2

5 PERC-RITE MICRO-MOUND TM SYSTEM COMPONENTS 1. The QM and ASD Series PERC-RITE DRIP SYSTEM CONTROLLERS are state of the art control panels, activated by level sensing devices (standard float switches) located in a dosing tank downstream from the pretreatment process or processes. When activated by the rising level of effluent in the dosing tank, the controller will enable the disposal cycle. The system controller on a time clock basis will pump the effluent through the filter module and then to final drip dispersal. 2. FILTER UNIT - Disc filter(s), automatic control valves and solenoid activated diaphragm valves are assembled in a filtration unit with flow meter (optional heater) in valve box enclosure. Wiring is provided with labels for easy connection. 3. PUMP SYSTEM - The pump, Cool Guide TM (Patent No. 6,262,689) and float switches for level indication are provided for installation into the pump tank. The pump is a 15-gpm turbine pump and will be suitable for most residential installations. Reference lift and distance table for pumping limits. 4. DRIPPER TUBING - The dripper tubing is pressure compensating dripper line for wastewater. The tubing delivers a nominal 0.61 gallons per hour (+/- 6% flow rate from 7 to 60 psi). The tubing functions as a turbulent flow emitter between 0 and 7 psi, ensuring that the nominal design flow is not exceeded at system start-up. 5. SIDE FEED MANIFOLD - The side feed manifold is located at one end in the drip zone for easy installation and is provided with an air release valve. If two zones are installed, check valves are provided in order to use the common return pipe. The system provides for the fastest possible pressurization of the zone and the most efficient method of providing drain down venting. Top Feed manifolds (Patent No. 5,984,574B) are available for sloping installations. 6. DRIP FIELD MATERIALS - All special drip fittings and equipment are supplied by American Manufacturing Company, Inc. including the tubing insert fittings, connectors, flex tube and non-schedule 40 PVC standard fittings. 7. MULTI-ZONE SEQUENCING VALVE (OPTIONAL) - In the event more than one zone of tubing is required, a sequencing valve may be used to alternate between zones. The valve is a multi-port device, which is located at the highest point in the dispersal area and requires no electrical activation. An alternate option is a two-zone control unit with electrical activation. 8. STANDARD FIELD MATERIALS - All tanks, wire, standard pipe and fittings are provided by the contractor at the local site. The 1 supply and return pipes, the 1/2 pipe for installation between the top feed manifold system and the laterals and other misc. PVC pipe are to be purchased locally. 9. SAND MOUND - The sand mound design conforms to the Wisconsin Sand Mound 2000 Guidance. Enhancements to the design include flow equalization, low profile due to elimination of gravel depth and cover requirements, plus enhanced treatment due to dispersal of filtered effluent with drip microdosing. Page No. 3 Copyright 2006

6 MICRO-MOUND TM DESIGN PROCEDURES FOR USE WITH EXCEL CALC TOOL 1. DEMAND ANALYSIS - Local codes determine the amount of wastewater to design for. Many codes have a safety factor or peak flow factor in the prescribed design flow. Others are based on more of an average usage. In either event, the designer must determine what the peak (design) flow is. The Perc-Rite Drip System will disperse the average flow through out each day unless the Peak float is enabled at which time the system will disperse effluent at an accelerated design daily flow rate. Record the peak design flow on line 3 of the worksheet. 2. SITE AND SOILS EVALUATION - Soil and site evaluation is required on each site according to state and local criteria and the procedures used are not included in this manual (see page 7). The designer must determine from the information provided by the evaluator the basal area loading rate line 6. The Soil Texture and the depth to limitation need to be determined line 2. The Soil Loading Rate Table provided should be used as a guidance tool only. The professional judgment of the evaluator and designer should determine the wastewater application rate for any specific site. 3. DELINEATE AREA - The installation area should be delineated, long and narrow mound(s) along contour are best. On a site plan or a site sketch, the designer should layout the area of installation on contour. The width along contour should be recorded line 4. The slope should be recorded line 5. Determine on the Landscape Linear Loading table the appropriate loading rate and record on line 11. The spreadsheet will calculate mound dimensions and determine single mound suitability. If the contour loading rate is exceeded, then the number of mounds (line 13) should be adjusted. Once the input adjustments are made to have line 12 indicate YES, then proceed. 4. SELECT ZONE DETAL - Once the number of mounds and the mound dimensions are determined, a standard zone detail is selected based on the width across contour and the number of mounds. See the Zone Detail Table. Determine how wide the system can be based on the delineated area on the plan. Match the distance across contour and from the table select the zone detail for the site. Record the selected zone detail on line 23. Minimum number of runs is estimated based on 9 center to center spacing of tubing. Add more runs with closer spacing to provide supply and return on the same side. 5. LAYOUT SITE - On a site plan or site sketch show the layout of the tanks, filter module and the control panel. On a site plan or site sketch show the route for the supply and return pipes. Determine the lift to the field and record on line 18. Measure and show the distance that the supply and return pipes travel. Determine the length of supply line run and record on line DETERMINE SUITABILITY - Reference the Lift and Distance Table system for suitability. Determine the filter unit gpm capacity (12 gpm secondary treated effluent only or 15 gpm septic or secondary). Determine the length of run to the farthest field and the number of laterals in each zone. The layout must use 1 supply and return lines only. If the selected zone detail is included in the zone table, record the maximum lift in line 24 of the spreadsheet of the corresponding run length met or exceeded in the corresponding filter unit table. If the layout is suitable, the last item will say YES. Copyright 2006 Page No. 4

7 * Find this Microsoft Excel file at Page No. 5 Copyright 2006

8 * See page 17 for Operating Parameters. Copyright 2006 Page No. 6

9 MICROMOUND LOADING RATE CHART For AMERICAN Perc-Rite Drip Systems Instructions: Find the cell where the highlited row and column intersect. Then type that number in the indicated cell to the right of the table. Suggested Hydraulic Loading Rates Based on Soil Characteristics for Conventional Septic Systems AEROBIC Infiltration Loading Rate Soil Characteristics gal/ft 2 /day 0-4% Structure < 30 mg/l Infiltration distance (in.) Texture Shape Grade BOD 8 to to to 48 8 to to to 48 8 to to to 48 COS, S, LCOS, LS -- 0SG FS, VFS, LFS, LVFS -- 0SG CLS, SL FSL, VFSL L SIL SCL, CL, SICL SC, C, SIC Hydraulic Linear Loading Rate, gal/day/ft Infiltration distance (in.) -- 0M PL PR/BK/GR , FALSE FALSE FALSE 0 2, FALSE FALSE FALSE M FALSE FALSE FALSE 0 PL 1,2, FALSE FALSE FALSE PR/BK/GR 2, FALSE FALSE FALSE M FALSE FALSE FALSE 0 PL 1,2, FALSE FALSE FALSE FALSE PR/BK/GR 2, FALSE FALSE FALSE M FALSE FALSE FALSE 0 PL 1,2, FALSE FALSE FALSE PR/BK/GR 2, FALSE FALSE FALSE M FALSE FALSE FALSE 0 PL 1,2, FALSE FALSE FALSE PR/BK/GR 2, FALSE FALSE FALSE M FALSE FALSE FALSE 0 PL 1,2, PR/BK/GR 2, FALSE FALSE FALSE 0 FALSE FALSE FALSE by E. Jerry Tyler, used with permission 8 to % to 12 FALSE FALSE 0 2 FALSE FALSE FALSE FALSE Infiltration distance (in.) *Type INFILTRATION DISTANCE in the outlined cell below. This number gets returned directly to line 11 on the Design Worksheet. Back to Design Worksheet 0 3 FALSE FALSE FALSE FALSE SC, C, SPR/BK/G2,3 0.3 Slope 5-9% > 10% 2.6 Page No. 7 Copyright 2006

10 ZONE DETAIL NUMBERING SYSTEM Each zone is designated by a Z indicating it is a Zone Detail Designation followed by three groups of numbers. The first is the number of zones, the second is the number of laterals per zone, and the third is the runs per lateral. Z = Zone # Zones # Laterals # Runs/Lat EXAMPLE 1 Z Z = Zone # Zones # Laterals # Runs/Lat This example shows a two-zone detail with three laterals per zone and two runs per lateral. ZONE DETAIL SELECTION PROCEDURE Reference the site plan layout to determine the width across contour of the mound area. From the mound spreadsheet determine the total amount of tubing required. The total linear feet of tubing required is determined by the length across contour and the minimum for pump run time. Zone details are configured to has supply and return on same end to provide for easy installation. Increasing the number of runs in order to install a standard zone configuration is encouraged. This provides an additional safety factor for the tubing interface loading rate plus it is easier on the equipment. Use the following step by step procedure to select a zone detail. 1. Determine width across contour. 2. Determine number of runs that can be installed in sand (typically 9 O.C.). 3. Select a standard zone detail from under the column for contour width that has enough tubing to satisfy tubing spacing. 4. In the event more runs are needed to yield enough tubing for the site, the tubing may be placed closer than 4 on center. EXAMPLE 2 Contour width = 100 Feet Tubing required = 800 Linear Feet From the table, the linear feet of tubing provided in 100 foot runs will be between 600 LF and 2400 LF. Therefore, select 8 runs for 800 LF. The zone detail could be: Z Z = Zone # Zones # Laterals # Runs/Lat Finally confirm that the number of runs can be installed into the delineated area. Copyright 2006 Page No. 8

11 Page No. 9 Copyright 2006

12 PERC-RITE LIFT AND DISTANCE TABLE 15 GPM AUTOMATIC DRIP SYSTEMS: 24 EMITTER SPACING LIFT & DISTANCE TABLE INSTRUCTIONS 1. The vertical lift is the elevation difference between the Off Level Float and the highest point in any drip zone. 2. The supply/return line column is the distance from the filter to the farthest drip zone. 3. The diameter of the pipe from the pump tank to the filter unit is 1-1/2 minimum. 4. All zone supply and return pipes are The flush return pipe from the filter box to the pretreatment tank is 1-1/2 gravity. 6. The maximum distance from the pump tank to the filter valve box is 30 and the vertical lift from the pump chamber to the filter valve box is These tables may be used with the appropriate Perc-Rite zone detail table only. An engineering calculation sheet (not included herein) must be filled out for any other configuration. 8. Top feed manifolds must be used when any discernible slope is encountered. 9. Remote zone valves are needed when pumping downhill from the filter. For aid in this aplication call American Manufacturing. 10. Return pressure assembly is needed when lift from filters to zones is greater than 10. LIFT AND DISTANCE TABLE 15 GPM AUTOMATIC DRIP SYSTEMS: 24 EMITTER SPACING Maximum Static Lift ( Off Level Float to Drip Field) Supply/ 1 Return Line 2-Lat 3-Lat 4-Lat 5-Lat 6-Lat 7-Lat (feet) Copyright 2006 Page No. 10

13 PERC-RITE LIFT AND DISTANCE TABLE 12 GPM SEMI-AUTOMATIC DRIP SYSTEMS: 24 EMITTER SPACING LIFT & DISTANCE TABLE INSTRUCTIONS 1. The vertical lift is the elevation difference between the Off Level Float and the highest point in any drip zone. 2. The supply/return line column is the distance from the filter to the farthest drip zone. 3. The diameter of the pipe from the pump tank to the filter unit is 1-1/2 minimum. 4. All zone supply and return pipes are The flush return pipe from the filter box to the pretreatment tank is 1-1/2 gravity. 6. The maximum distance from the pump tank to the filter valve box is 30 and the vertical lift from the pump chamber to the filter valve box is These tables may be used with the appropriate Perc-Rite zone detail table only. An engineering calculation sheet (not included herein) must be filled out for any other configuration. 8. Top feed manifolds must be used when any discernible slope is encountered. 9. Remote zone valves are needed when pumping downhill from the filter. For aid in this aplication call American Manufacturing. 10. Return pressure assembly is needed when lift from filters to zones is greater than 10. LIFT AND DISTANCE TABLE 12 GPM SEMI-AUTOMATIC PERC-RITE DRIP SYSTEMS: 24 EMITTER SPACING Maximum Static Lift ( Off Level Float to Drip Field) Table A: STANDARD 12 GPM QM LIFT & DISTANCE TABLE Supply/ 1 Return Line 2-Lat 3-Lat 4-Lat 5-Lat (feet) Note: Use Table B when using Hydro Seq Valve Table B: 12 GPM QM w/ HYDRO SEQ DISTRIBUTING VALVE Supply/ 1 Return Line 2-Lat 3-Lat 4-Lat 5-Lat (feet) Note: Use this table when using Hydro Seq Valve Page No. 11 Copyright 2006

14 RUN TIME TABLES: 15 GPM AUTOMATIC AND WASHDOWN PERC-RITE DRIP SYSTEMS The run time tables are based on the gallons per day the system is designed for. The run time numbers are based on the average daily flow rate. Selecting the run time is the last design step that is performed. Based on the number of zones and the number of laterals per zone, the run time is selected based on the average gallons per day. For even distribution and minimizing draindown events, the run time is calculated to provide from 3 to 5 times the volume of drip tubing plus the top feed manifolds. Therefore, the number of doses per day per zone will vary in order to maintain optimum dispersal. AMERICAN MANUFACTURING - 2-ZONE Laterals/Zone: 2-Lat 3-Lat 4-Lat 5-Lat 6-Lat 7-Lat Lateral Length: Design Avg. GPM: GPD GPD Min./dose Min./dose Min./dose Min./dose Min./dose Min./dose TOTAL L.F. IN ZONE= AMERICAN MANUFACTURING - 1-ZONE Laterals/Zone: 2-Lat 3-Lat 4-Lat 5-Lat 6-Lat 7-Lat Lateral Length: Design Avg. GPM: GPD GPD Min./dose Min./dose Min./dose Min./dose Min./dose Min./dose TOTAL L.F. IN ZONE= Copyright 2006 Page No. 12 STANDARD & PEAK REST TIMES TO BE SET AT SYSTEM START-UP 1 ZONE 2 ZONE REST TIMES REST TIMES Standard Peak Standard Peak (min) (min) (min) (min) 4 Doses/day/zone Doses/day/zone Doses/day/zone Doses/day/zone Doses/day/zone Doses/day/zone Doses/day/zone Doses/day/zone Doses/day/zone

15 RUN TIME TABLES: 12 GPM SEMI-AUTOMATIC PERC-RITE DRIP SYSTEMS The run time tables are calculated for achieving the best distribution of the average daily flow in gallons per day the system is designed for. Selecting the run time is the last design step that is performed and is based on the number of zones and the number of laterals per zone. The run time should result in even distribution and minimizing draindown events. The run time is calculated to provide from 3 to 7 times the volume of drip tubing plus the top feed manifolds. Therefore, the number of doses per day per zone will vary in order to maintain optimum dispersal. AMERICAN MANUFACTURING - QM SERIES 1-ZONE AMERICAN MANUFACTURING - QM SERIES 2-ZONE Laterals/Zone: 2-Lat 3-Lat 4-Lat 5-Lat Laterals/Zone: 2-Lat 3-Lat 4-Lat 5-Lat Lateral Length: Lateral Length: Design Avg. GPM: Design Avg. GPM: GPD GPD Min./dose Min./dose Min./dose Min./dose GPD GPD Min./Dose Min./dose Min./dose Min./dose TOTAL L.F. IN ZONE= TOTAL L.F. IN ZONE= STANDARD & PEAK REST TIMES TO BE SET AT SYSTEM START-UP ONE ZONE LEGEND: REST TIMES TWO ZONE LEGEND: REST TIMES Standard Peak Standard Peak (min) (min) (min) (min) 4 Doses/day/zone Doses/day/zone Doses/day/zone Doses/day/zone Doses/day/zone Doses/day/zone Doses/day/zone Doses/day/zone Doses/day/zone Doses/day/zone Page No. 13 Copyright 2006

16 GENERAL NOTES FOR DRIP DISPERSAL AND MOUND 1. All installation and construction techniques shall conform to county codes and state board of health pertaining to on-site sewage systems and the permit for this site. 2. The installation of this system shall be in accordance with specifications and procedures as supplied by the manufacturer of the equipment. 3. All pvc pipe and fittings shall be pvc sch 40 type 1 rated for pressure applications. All glued joints shall be cleaned and primed with purple (dyed) pvc primer prior to being glued. 4. All cutting of pvc pipe, flexible pvc and dripper tubing shall be accomplished with pipe cutters approved by the manufacturer. No sawing of pvc pipe, pvc flexible or drip tubing. 5. All pvc pipe, flexible pvc and drip tubing in the work area shall have the ends covered with duct tape to prevent construction debris from entering the pipe. Prior to gluing all joints and piping shall be inspected for and cleared of any construction debris. 6. No wet weather installation is permitted. 7. No activity on drain field area other than minimum required to install system. Do not park equipment, drive large equipment over or store building or soil materials on drain field site. 8. Horizontal spacing between dripper lines shall be as specified. 9. Prior to start up of the drip disposal system the air release valves shall be removed and each zone in the system shall be flushed as follows: a.) Using an appropriate length of flexible pvc pipe with a male fitting attached to the air release connection to direct the flushing water away from the construction area. B.) Flush the zone with a volume of clean water (to be provided by the contractor) equal to 1.5 times the volume of the pipes from the central unit to the air release valve. C.) Repeat this procedure for each zone (flushing of the system is accomplished by manual override of the control panel by the manufacturer or engineer). 10. If trees are to be removed from site, cut stumps flush with the ground level. Do not remove. 11. Gravel base under central control unit is to be drained via 2 pvc pipe, screened at inlet and outlet, discharge to be at grade down slope (to ensure drainage of surface water from the unit. 12. CONTRACTOR CERTIFICATION: the manufacturer shall certify the contractor to install this type of system. Contact the Manufacturer to set up a training meeting. INSTALLATION INSTRUCTIONS FOR MOUND 1. Stake out area. The absorption area must be placed on contour. Measure the ground surface elevation along the upslope edge of the adsorption area. Note that installation activity is to take place from the up slope portion of the adsorption area only with as little activity as possible. If multiple adsorption areas are placed on the same slope, the lower area of installation activity should be in as narrow corridor as possible. Install the lower areas first, scarifying the up slope construction areas. 2. The preservation of the original soil structure of the soil in the adsorption area is essential to maintaining the infiltrative and percolative capacity of the soil. No activity other than the minimum to construct the system is permitted within the adsorption area. The footprint of the adsorption area should be prepared only when the soil moisture is within a satisfactory range. 3. Prepare absorption area location for installation. The absorption area not only includes the sand bed area, but the down slope extended toe of basal area also. Grass, shrubs, and trees must be cut as close to the ground surface as possible and removed, preferably by hand from the site. In wooded area with excess litter, it is recommended to rake the majority of the material from the site. Do not pull out stumps, do not remove sod, top soil, or boulders. Copyright 2006 Page No. 14

17 4. Scarify (plow) entire basal area. Typically plowing depths are 6-8, although slightly deeper may be specified in the case of shallow thin weak fragi (plow) pans. The satisfactory moisture range in the plowed area is defined as where the soil will crumble and not form a wire when rolled between the palms. In addition, the soil within a minimum of 12 of the ground surface is not to be sufficiently moist to exceed its plastic limit. The plastic limit is exceeded when the soil can be rolled between the palms of the hands to produce threads 1/8 in diameter without breaking and crumbling. Do not till if there is any question. 5. The purpose of the tillage is to roughen the surface to allow better infiltration into the topsoil, and providing a more transitional contact between / from the sand to the soil. Excessive tillage will destroy the soil structure and reduce infiltration. Several methods are available. The most preferred method is using chisel teeth mounted on a backhoe, which can be easily removed. This method works the fastest around stumps. Secondly, a chisel plowed pulled behind a tractor. This method works fastest on open turf sites. The furrows are to be along the contour. Lastly a backhoe bucket with short, sharp teeth to flip the soil may be used, but this method can be time consuming. Rototillers are prohibited on all but structure less sands. Small shrub and tree stumps dislodged during tillage may be removed. 6. Once the site has been tilled, a layer of sand must be placed before it rains. The sand is not to be mixed into the soil but applied / spread such that is fills the naturally occurring / exposed structure voids. Sand should be placed with a backhoe and spread. A minimum of 6 of sand is required below the tubing. The sand bed surface must be even, along the contour, but is not required to be flat, that is it does not have to be deeper on the down slope side on sloping sites. Tapering and extending sand into the toe / basal area is preferred. Sand Specification: As required by Code for mounds. Sand to have an effective diameter of between and a uniformity coefficient between 4 and 6. No more than 20% by weight of material >2 mm and < 5% by weight <.053 mm. ASTM C-33 may be suitable. Sand certification to be presented to designer prior to installation. 7. Carefully taper and incorporate 2-4 sand throughout the basal area. 8. Place sand specified fill depth over sandbed basal area 9. Determine where the drip zone supply lines and return line will enter the adsorption area. All drip tubing distribution systems will likely feed and return from the same end. Regardless of whether it is end or center feed, these lines should always enter from the upslope side of the mound at the edge of the adsorption area or from the end if appropriate. Keep below frost line to this point. 10. Place drip tubing over sandbed area. (See Drip Installation Instructions) 11. Sod staples will help in the placement. Connect to supply and return manifolds. Connect to hydraulic unit supply / return lines. Elevate loops 2 with pressure treated wood (2 x 6 ) or bricks, secured firmly on sand bed. Install observation wells in the bed center at the 1/3 and 2/3 point along the length. 12. Cover drip tubing with minimum 2 sand. 13. Once the system has been pressure tested and started up, cover sand bed with geotextile synthetic fabric. 14. Place suitable soil cover (loam) over the mound. There should be a minimum of 8 on the sides and shoulder with 12 on the top. Be sure the supply / return lines have of sand / soil cover for frost protection. Remember the side slope will be typically be 3: 1 to extend over the basal, toe of berm area. The covered area will include an extended toe if required. The cover should be able to support vegetation. Page No. 15 Copyright 2006

18 15. Place filtration unit and mount control panel. 16. Set switch tree in pump tank. 17. Wire filtration unit and float switches to control panel. 18. Final grade the mound and area so surface water moves away from and does not accumulate on top of or up slope of the mound. Use lightweight equipment. 19. Seed and mulch the entire area as soon as possible to avoid erosion. Sod is recommended. Establish and maintain an aggressive turf cover. If other cover is necessary, provisions need to be made to control erosion. INSTALLATION INSTRUCTIONS FOR DRIP DISPERSAL 1. Dig header ditch for field manifold. 2. Install dripper tubing. Horizontal spacing between dripper lines shall be as specified and installation depth shall be as specified. Install on contour. 3. Install loops (flex tubing) and construct field supply / return manifolds. All PVC pipe and fittings shal be PVC SCH 40 type 1 rated for pressure applications. All glued joints shall be cleaned and primed with purple (dyed) PVC primer prior to being glued. All cutting of PVC pipe, flexible PVC and/or dripper tubing shall be accomplished with pipe cutters. Sawing of PVC pipe, flexible PVC and/or dripper tubing shall be followed by cleaning all shavings or sawing should not be allowed. All open PVC pipe, flexible PVC and/or dripper tubing in the work area shall have the ends covered with duct tape during construction to prevent construction to prevent construction debris from entering the pipe. Prior to gluing all glue joints shall be inspected for and cleared of construction debris. 4. Dig ditches for conveyance lines, pump supply line, and flush return line. Install. Connect supply / return lines with manifolds. 5. Place Filtration Unit and mount control panel. Connect conveyance, supply, and flush return lines to hydraulic unit. 6. Set switch tree in pump tank. 7. Install electrical (and phone line if applicable). Check power supply and power up unit. 8. Provide one-day volume of clean water for startup. Prior to startup of the drip disposal system the air release valves shall be removed and each zone in the system shall be flushed as follows: a) using an appropriate length of flexible PVC pipe with a male fitting attached to the air release connection to direct the flushing away from the construction are, b) flush the zone with a volume of water (clean water to be provided by contractor) equal to 1.5 times the volume of the pipes from the central unit to the air release valve, c) repeat this procedure for each zone (the flushing of the system is accomplished by manual override of the control panel by the manufacturer of engineer.) Once completed replace and glue air relief valves. 9. Pressure check all fittings and lines. Inspect field and loops. Find leaks and repair. 10. Check setup values against calculated values. Set run time for Central Unit. 11. Backfill once lines and fields are determined to have no leaks. Backfilling is to be controlled to prevent the damaging of pipes or fittings. Once completed, drainfield area should be graded to shed surface water with additional clean soil as necessary. Establish fescue or other turf cover, cut long (6-8 ). Copyright 2006 Page No. 16

19 Page No. 17 Copyright 2006

20 Copyright 2006 Page No. 18

21 Page No. 19 Copyright 2006

22 AMERICAN Manufacturing Company, Inc. Copyright 2006 Page No. 20

23 Page No. 21 Copyright 2006

24 Copyright 2006 Page No. 22

25 Mound Separation Distance = 4 x A or 25 (which ever value is greater) Page No. 23 Copyright 2006

26 OPERATION AND MONITORING FOR PERC-RITE DRIP SYSTEM The PERC-RITE DRIP SYSTEM has been developed to automatically monitor operational functions. The system is designed to be easily fixed after it breaks, in other words periodic monitoring can confirm good operating conditions but there are no maintenance procedures necessary until a mechanical component needs repair. Furthermore, any malfunction or breakage of a mechanical component will result in a failure similar to any traditional system, including a wet spot in the field, a backup or a high level alarm. The MONITORING FREQUENCY should be no more than traditional systems. The most important component for the operational success is owner awareness. All onsite systems have a finite hydraulic capacity. Drip systems have no storage capacity in the soil system so storage or flow equalization must be provided in the pump tank. The owner must be aware system exists and their limitations for usage. After a successful installation and startup the system should be inspected from one to three months after the owner takes occupancy to confirm operational compliance and to inform the owner of the operational characteristics of the system. The system should then go on a schedule of annual inspections to monitor usage and inspect system for wear in order to minimize emergency service requirements. Each system is provided with an owners manual. The local dealer has a more detailed installation and maintenance supplement manual. If more than septic pretreatment is provided, more frequent monitoring may be required. Provide monitoring frequency at the rate determined by the most sensitive component. An OPERATIONAL CHECKLIST is provided in the dealer s supplement manual for determining satisfactory operation of the system. The following topics are covered; 1. Field Conditions 2. Check septic tank and pump tank condition 3. Check operation of pump, control and valves. 4. Check zone dose rates. 5. Evaluate and record meter for usage. Page No. 24 Copyright 2006

27 ELECTRICAL AND OPERATIONAL SPECIFICATIONS CUST. NAME: JOB NAME: JOB NUMBER: PERMIT INFO: DESIGNER NAME: SYSTEM INFORMATION GPD MAX GPM NO. ZONES ZONE DETAIL NO. DOSES PER DAY MODEL NUMBER AMERICAN PERC-RITE MICRO MOUND TM RUN TIME SECONDARY EFFLUENT 1. AMD151-S ABD121-S ABD121-S121SV2 SEPTIC OR SECONDARY EFFLUENT 4. ASD151-S ASD152-S ASD154-D124 Check the model number that has the number of zones per the zone detail. Record the run time from the Run Time Table. SPECIAL SPECIFICATIONS (use back if necessary) OPTIONS Return Pressure Assembly (Y) Use pressure assembly anytime the lift from filter unit to drip field is discernable and using a valve box model. Sequence Valve Drain Down Assembly Blower Cut-out Heater 225w Valve Box (insulated) Tubing Rolls (500 ) Tubing Rolls (1000 ) (Y) (Y) (Y) (Y) (Y) SPECIAL INSTRUCTIONS (use back if necessary) AUTHORIZED SIGNATURE Date: ( )Owner ( )Agent NOTE: ATTACHED SHOULD BE A ZONE DETAIL Sales Order Number File No. SBT Input BY AMERICAN USE ONLY ELECTRICAL CIRCUIT REQUIREMENTS 1. PUMP 1/2 HP, 115V, 1 PHASE 2. CONTROL 15 AMP, 115V, 1 PHASE 3. OTHER Page No. 25 Copyright 2006

28 12 GPM and 15 GPM Automatic PERC-RITE DRIP SYSTEMS ASD 15 Series - septic & Secondary Effluent QUALITY AMD151-S GPM 1 ZONE SIMPLEX MANUAL CLEAN INSERT & LCD Control ABD121-S GPM 1 ZONE QM skid mount with LCD Control line # component DESCRIPTION QUANTITY line # component DESCRIPTION QUANTITY 1 DP0-B Zone Simplex LCD Control 1 2 DH0-1MKIT 1-1/2 MANUAL FILTER ASSY W/PUMP DISC. 1 3 DH-FLOWFLUSHKIT FIELD FLUSH & FLOW METER KIT W/VB 1 4 DH-TOPFEEDKIT1 TOP FEED MANIFOLD KIT SUPPLY & RETURN 1 5 BIOLINE 1000 DRIP TUBING PER 1000 FT ROLL 1 6 PVC12FLEX 1/2 X 100 PVC FLEX TUBE/DRIP 1 7 PVCPRFIP12X34 1/2 X 3/4 PVC PRESS S X FIP AD 25 8 BIOINSERT12X34 1/2 BIOLINE X 3/4 MIP DRIP ADAPTER 25 9 BIOCOUP BIOLINE REPAIR COUPLING 1/2 IN 3 10 COOLGUIDE15 LAMINAR FLOW COOLING GUIDE 1 11 PUTURB W 15 GPM TURBINE PUMP 1/2HP, 115V, 2 wire 1 1 DP0-B Zone Simplex LCD Control 1 2 DH0-2BKIT 2 FILTER, 1 ZONE QM kit 1 3 DH-TOPFEEDKIT1 TOP FEED MANIFOLD KIT SUPPLY & RETURN 1 4 BIOLINE 1000 DRIP TUBING PER 1000 FT ROLL 1 5 PVC12FLEX 1/2 X 100 PVC FLEX TUBE/DRIP 1 6 PVCPRFIP12X34 1/2 X 3/4 PVC PRESS S X FIP AD 25 7 BIOINSERT12X34 1/2 BIOLINE X 3/4 MIP DRIP ADAPTER 25 8 BIOCOUP BIOLINE REPAIR COUPLING 3 9 COOLGUIDE15 LAMINAR FLOW COOLING GUIDE 1 10 PUTURB W 15 GPM TURBINE PUMP 1/2HP, 115V, 2 wire 1 11 PUMPKITDRIP 1-1/2 IN DRIP PUMP KIT 1 ASD152-S GPM 2 Zone drip w/ simplex 2 filter, 2-zone control panel ABD121-S121SV2 12 GPM 2 ZONE QM SKID WITH SEQUENCER & LCD Control line # component DESCRIPTION QUANTITY 1 DH2-22KIT 2 ZONE DRIP SYSTEM KIT 1 2 DP1-B9140P SIMPLEX 2 ZONE CONTROL 1 3 PUTURB W 15 GPM TURBINE 1 4 COOLGUIDE 15 LAMINAR FLOW COLLAR, 6, 15 GPM 1 5 PUMPKITDRIP DRIP PUMP KIT 1 1/2 1 6 BIOLINE 1000 DRIP TUBING PER 1000 FT ROLLS 2 7 PVC12FLEX 1/2 FLEX PVC BIOINSERT12X34 BIOLINE INSERT ADAPTER 1/2 X 3/ PVCPRFIP12X34 FEMALE ADAPTER 12X34 SXT SCH BIOCOUP BIOLINE REPAIR COUPLING 1/ DH-TOPFEEDKIT TOP FEED MANIFOLD KIT 1 2 line # component DESCRIPTION QUANTITY 1 DP0-B Zone Simplex LCD Control 1 2 DH0-2RKIT 2 FILTER, 1 ZONE QM Insert KIT 1 3 DH-TOPFEEDKIT1 TOP FEED MANIFOLD KIT SUPPLY & RETURN 2 4 BIOLINE 1000 DRIP TUBING PER 1000 FT ROLL 2 5 PVC12FLEX 1/2 X 100 PVC FLEX TUBE/DRIP 1 6 PVCPRFIP12X34 1/2 X 3/4 PVC PRESS S X FIP AD 50 7 BIOINSERT12X34 1/2 BIOLINE X 3/4 MIP DRIP ADAPTER 50 8 BIOCOUP BIOLINE REPAIR COUPLING 1/2 IN 3 9 COOLGUIDE15 LAMINAR FLOW COOLING GUIDE 1 10 PUTURB W 15 GPM TURBINE PUMP 1/2HP, 115V, 2 wire 1 11 SEQUENCEVLV2 TWO ZONE SEQUENCE VALVE 1 12 PUMPKITDRIP 1-1/2 IN DRIP PUMP KIT 1 ASD154-D GPM 4 Zone drip w/ DUplex 2 filter, 4-zone control panel ASD151-S GPM 2 remote zone drip w/ simplex 2 filter, 4-zone control line # component DESCRIPTION QUANTITY line # component DESCRIPTION QUANTITY 1 DH2-24KIT 4 ZONE DRIP SYSTEM KIT 1 2 DP1-B9146P DUPLEX 4 ZONE CONTROL PANEL 1 3 PUTURB W 15 GPM TURBINE 2 4 COOLGUIDE15 LAMINAR FLOW COLLAR, 6, 15 GPM 2 5 PUMPKITDRIPDX DRIP PUMP KIT 1 1/2 DUPLEX 1 6 BIOLINE 1000 DRIP TUBING PER 1000 FT ROLL 4 7 PVC12FLEX 1/2 FLEX PVC BIOINSERT12X34 BIOLINE INSERT ADAPTER 1/2 X 3/ PVCPRFIP12X34 FEMALE ADAPTER 12X34 SXT SCH BIOCOUP BIOLINE REPAIR COUPLING, 1/ DH-TOPFEEDKIT TOP FEED MANIFOLD KIT DH2-21KIT MASTER VALVE DRIP SYSTEM KIT 1 2 DP1-B9157P SIMPLEX 4 ZONE W/MASTER VALVE 1 3 PUTURB W 15 GPM TURBINE 1 4 COOLGUIDE15 LAMINAR FLOW COLLAR, 6, 15 GPM 1 5 PUMPKITDRIP DRIP PUMP KIT 1 1/2 1 6 ZONEVALVE 1 REMOTE ZONE VALVE 1 VLV X 1 PIPE 2 7 BIOLINE1000 DRIP TUBING PER 1000 FT ROLL 2 8 PVC12FLEX 1/2 FLEX PVC BIOINSERT12X34 BIOLINE INSERT ADAPTER 1/2 X 3/ PVCPRFIP12X34 FEMALE ADAPTER 12X34 SXT SCH BIOCOUP BIOLINE REPAIR COUPLING, 1/ DH-TOPFEEDKIT TOP FEED MANIFOLD KIT 1 2 AMERICAN Manufacturing Company, Inc. Copyright 2006 Page No. 26

29 DESIGN SUBMITTAL PROCEDURES Design and submittal of a Perc-Rite system is very simple using the following procedures; 1. Fill out design submittal form for jurisdiction. The form may be generic, state adjusted, or locally required. 2. Provide a separate site plan or sketch. 3. Print out determined zone detail. 4. Submit the proper number of copies to the jurisdiction of authority. AMERICAN MANUFACTURING COMPANY - DATA CENTER ONLINE WARRANTY REGISTRATION American provides online warranty tracking and regulatory reporting. You must be an authorized user to access this feature. Go to then click on Data Center at the bottom of the menu on the left. The Data Center can be used by service providers to keep up-to-date information on all systems. It is user friendly and easily accessible anywhere an internet connection is available. REQUIRED FIELDS FOR WARRANTY REGISTRATION 1. COUNTY 2. SYSTEM TRACKING NUMBER (SAME AS SERIAL NUMBER) 3. NAME 4. PHONE NUMBER 5. ADDRESS 6. CITY 7. STATE 8. ZIP CODE 9. LOCALE 10. TYPE OF PERMIT 11. SYSTEM COMPONENTS 12. FINAL INSPECTION DATE 13. SERVICE PROVIDER 14. FLOW METER READING Page No. 27 Copyright 2006

30 WARRANTY AMERICAN MANUFACTURING LIMITED WARRANTY For one year (12 months) after the date of purchase, American Manufacturing Company, Inc. will repair or replace any product or portion thereof which proves to be defective due to materials or workmanship of American Manufacturing. We reserve the right to repair or replace defective materials at our discretion. This warranty does not cover the following conditions: 1. Defects or problems caused by improper installation or maintenance of materials. 2. Abuse, neglect or accidental damage of products. 3. Normal maintenance or upkeep of products. 4. Lightning, war, floods, or other acts beyond our control. 5. Misapplication of our products for their designed purpose, or misapplication according to local, state or national codes when in effect. Defective or warranted materials must be returned to us or a place designated by American Manufacturing. All returns must be accompanied by a return authorization number supplied by American Manufacturing. American Manufacturing will in no way be responsible for any losses or damages incurred by failure of equipment, parts or service. NOTE: Some states do not allow exclusion of damages so this may not apply to you. There are no other warranties written or implied. Copyright 2006 Page No. 28

31 AMERICAN Manufacturing Company, Inc.

32 AMERICAN MANUFACTURING Company, Inc. American Manufacturing Company, Inc. manufactures many specialty Onsite Wastewater products including the Cool Guide TM, Bull Run TM Valve, Dial-A-Flow TM, Distribution Boxes, Perc-Rite drip equipment, Timer Controls, Accessories, etc. American also supplies as an Original Equipment Manufacturer (OEM) with many other products unique to the Onsite Industry. Cool Guide TM Bull Run TM Valve Control Panels Hydraulic Unit Dial-A-Flow TM Toll Free: P.O. Box 549, Manassas, VA Drip Tubing

PERC-RITE DRIP DISPERSAL DESIGN SUBMITTAL American Manufacturing Company, Inc

PERC-RITE DRIP DISPERSAL DESIGN SUBMITTAL American Manufacturing Company, Inc PERC-RITE DRIP DISPERSAL DESIGN SUBMITTAL American Manufacturing Company, Inc. 1-800-345-3132 www.americanonsite.com ASD152-S122 ASD153-S124 ASD154-S124 ASD153-D124 ASD154-D124 2 ZONE DRIP W/ SIMPLEX 2

More information

COLD WEATHER INSTALLATION NOTES Minimum construction techniques for all American Perc-Rite Drip systems in cold weather climates: Top feed manifolds should be used on all sites with a discernible slope

More information

PERC-RITE WASTEWATER DRIP DISPERSAL SYSTEMS DESIGNERS' GUIDE

PERC-RITE WASTEWATER DRIP DISPERSAL SYSTEMS DESIGNERS' GUIDE PERC-RITE WASTEWATER DRIP DISPERSAL SYSTEMS DESIGNERS' GUIDE Appendices 1. PERC-RITE DRIP SYSTEM CONTROL 2. SEQUENCE OF OPERATION 3. PERC-RITE DRIP SYSTEM FILTER SYSTEM 4. STANDARD MODEL NUMBERS & DESCRIPTION

More information

Alternate Systems Guidance

Alternate Systems Guidance Alternate Systems Guidance COMMONWEALTH OF PENNSYLVANIA Department of Environmental Protection For more information, visit us through the PA PowerPort at www.state.pa.us or visit DEP directly at www.dep.state.pa.us

More information

Commonwealth of Pennsylvania Department of Environmental Protection (DEP) Bureau of Water Standards and Facility Regulation Harrisburg, PA

Commonwealth of Pennsylvania Department of Environmental Protection (DEP) Bureau of Water Standards and Facility Regulation Harrisburg, PA Commonwealth of Pennsylvania Department of Environmental Protection (DEP) Bureau of Water Standards and Facility Regulation Harrisburg, PA Issued to: Eljen Corporation 125 McKee Street East Hartford, CT

More information

Innovative and Alternative System Approval

Innovative and Alternative System Approval State of Delaware Department of Natural Resources & Environmental Control Division of Water Resources Ground Water Discharges Section Innovative and Alternative System Approval ISSUED TO: American Manufacturing

More information

Commonwealth of Pennsylvania Department of Environmental Protection (DEP) Bureau of Water Standards and Facility Regulation Harrisburg, PA

Commonwealth of Pennsylvania Department of Environmental Protection (DEP) Bureau of Water Standards and Facility Regulation Harrisburg, PA Commonwealth of Pennsylvania Department of Environmental Protection (DEP) Bureau of Water Standards and Facility Regulation Harrisburg, PA Issued to: Technology: American Manufacturing Co, Inc. PO Box

More information

OSCAR-III Treatment System Design Manual January 2019, WA

OSCAR-III Treatment System Design Manual January 2019, WA OSCAR-III Treatment System Design Manual January 2019, WA Manufactured by: Lowridge Onsite Technologies PO Box 1179 Lake Stevens, WA 98258 877 476-8823 info@lowridgetech.com! 1 Width PLAN VIEW 1500 gallon

More information

Geotextile Sand Filter

Geotextile Sand Filter Geotextile Sand Filter CORPORATION Innovative Onsite Products & Solutions Since 1970 Table of Contents SUBJECT PAGE GLOSSARY OF TERMS...4 GSF SYSTEM DESCRIPTION...5 1.0 CONDITIONS FOR USE...6 1.1 SYSTEM

More information

AMERICAN PERC-RITE DRIP DISPERSAL SYSTEMS

AMERICAN PERC-RITE DRIP DISPERSAL SYSTEMS American Manufacturing Company, Inc. P.O. Box 97, Elkwood, VA 22718 1-800-345-3132 AMERICAN PERC-RITE DRIP DISPERSAL SYSTEMS ENGINEERING DESIGN GUIDELINES FOR COMMUNITY AND COMMERCIAL SIZED DISPERSAL SYSTEMS

More information

Innovative and Alternative System Approval

Innovative and Alternative System Approval State of Delaware Department of Natural Resources & Environmental Control Division of Water Resources Ground Water Discharges Section Innovative and Alternative System Approval ISSUED TO: Delta Environmental

More information

Ohio. Design and Installation Manual for the Infiltrator ATL System in Ohio. Infiltrator ATL System in Ohio

Ohio. Design and Installation Manual for the Infiltrator ATL System in Ohio. Infiltrator ATL System in Ohio Design and Installation Manual for the Infiltrator ATL System in Ohio Infiltrator ATL System in Ohio INTRODUCTION 2 SYSTEM CONFIGURATIONS SYSTEM DESIGN 9 SYSTEM DESIGN EXAMPLE INFORMATION FOR SYSTEM OWNERS

More information

DRIP EMITTER SYSTEM STUDY GUIDE

DRIP EMITTER SYSTEM STUDY GUIDE DRIP EMITTER SYSTEM STUDY GUIDE Minimum Criteria for Pressurized Subsurface Absorption Fields Utilizing Emitters. Subsurface systems utilizing emitters may be used in lieu of conventional or other alternative

More information

Grand Traverse County Health Department Environmental Health Division. Pressure Mound System (PMS) Policy and Procedure Manual

Grand Traverse County Health Department Environmental Health Division. Pressure Mound System (PMS) Policy and Procedure Manual Grand Traverse County Health Department Environmental Health Division Pressure Mound System (PMS) Policy and Procedure Manual This document is authorized under the authority of Section 5.19 (Variations)

More information

Section 9: Sand Mounds. 9. Sand Mounds

Section 9: Sand Mounds. 9. Sand Mounds Section 9: Sand Mounds 9. Sand Mounds 9. Sand Mounds 9.1 Design...107 9.2 Installation...108 9.3 Inspection...113 9.4 Operation...113 9.5 Common technical issues...117 9.6 Case study...117 The sand mound

More information

Commonwealth of Pennsylvania Department of Environmental Protection (DEP) Bureau of Point and Non-Point Source Management Harrisburg, PA

Commonwealth of Pennsylvania Department of Environmental Protection (DEP) Bureau of Point and Non-Point Source Management Harrisburg, PA Commonwealth of Pennsylvania Department of Environmental Protection (DEP) Bureau of Point and Non-Point Source Management Harrisburg, PA Issued to: Eljen Corporation 125 McKee Street East Hartford, CT

More information

PERC-RITE DRIP DISPERSAL DESIGN GUIDE FOR SEPTIC TANK OR ADVANCED TREATMENT EFFLUENT MASSACHUSETTS

PERC-RITE DRIP DISPERSAL DESIGN GUIDE FOR SEPTIC TANK OR ADVANCED TREATMENT EFFLUENT MASSACHUSETTS PERC-RITE DRIP DISPERSAL DESIGN GUIDE FOR SEPTIC TANK OR ADVANCED TREATMENT EFFLUENT MASSACHUSETTS This Design Guide is to assist you in specifying a Perc-Rite Drip Dispersal System for General Use or

More information

Commonwealth of Pennsylvania Department of Environmental Protection (DEP) Bureau of Point and Non-Point Source Management Harrisburg, PA

Commonwealth of Pennsylvania Department of Environmental Protection (DEP) Bureau of Point and Non-Point Source Management Harrisburg, PA Commonwealth of Pennsylvania Department of Environmental Protection (DEP) Bureau of Point and Non-Point Source Management Harrisburg, PA Issued to: Technology: American Manufacturing Co, Inc. PO Box 97

More information

Commonwealth of Pennsylvania Department of Environmental Protection (DEP) Bureau of Point and Non-Point Source Management Harrisburg, PA

Commonwealth of Pennsylvania Department of Environmental Protection (DEP) Bureau of Point and Non-Point Source Management Harrisburg, PA Commonwealth of Pennsylvania Department of Environmental Protection (DEP) Bureau of Point and Non-Point Source Management Harrisburg, PA Issued to: Technology: Generic Classification Type: Alternate technology

More information

I. Preconstruction Meeting and Site Preparation Date: Inspector: A. MDE Certified Installer Name

I. Preconstruction Meeting and Site Preparation Date: Inspector: A. MDE Certified Installer Name AT-GRADE MOUND SEWAGE DISPOSAL SYSTEM INSPECTION CHECKLIST I. Preconstruction Meeting and Site Preparation Date: Inspector: A. MDE Certified Installer Name B. MDE Certified Installer Present for entire

More information

Commonwealth of Pennsylvania Department of Environmental Protection (DEP) Bureau of Point and Non-Point Source Management Harrisburg, PA

Commonwealth of Pennsylvania Department of Environmental Protection (DEP) Bureau of Point and Non-Point Source Management Harrisburg, PA Commonwealth of Pennsylvania Department of Environmental Protection (DEP) Bureau of Point and Non-Point Source Management Harrisburg, PA Issued to: Technology: American Manufacturing Co, Inc. PO Box 97

More information

Name: Company: Address: Telephone: PEI Cert. #

Name: Company: Address: Telephone: PEI Cert. # DESIGNED BY: Name: Company: Telephone: PEI Cert. # SYSTEM OWNER(S): Name: Telephone: Enviro-Septic Wastewater Treatment System DESIGN CRITERIA WORKSHEET Manufactured by Presby Environmental, Inc. (800)

More information

Other Septic Tank Effluent Dispersal Options

Other Septic Tank Effluent Dispersal Options Other Septic Tank Effluent Dispersal Options CEE484 Decentralized and Onsite Waste water Management and Reuse April 16, 2007 Department of Civil and Environmental Engineering University of Washington Septic

More information

Pressure Distribution Design

Pressure Distribution Design Pressure Distribution Design Presented at the 2011 CEHA Annual Educational Conference By Roger J. Shafer, P.E. Distribution Systems Non-pressurized Distribution Distribution Systems Non-pressurized Distribution

More information

Klickitat County. On-Site Sewage System. Construction Manual

Klickitat County. On-Site Sewage System. Construction Manual Homeowner OSS Design and Construction Guide Klickitat County On-Site Sewage System Construction Manual Minimum standards and recommendations expected for the construction of on-site wastewater treatment

More information

APPENDIX B SAND MOUND

APPENDIX B SAND MOUND 3701-29-15 1 I. Introduction APPENDIX B SAND MOUND All soil absorption components and technologies shall be designed and installed to meet the requirements of rule 3701-29-15 of the Administrative Code

More information

THIS IS A COURTESY COPY OF THIS RULE. ALL OF THE DEPARTMENT S RULES ARE COMPILED IN TITLE 7 OF THE NEW JERSEY ADMINISTRATIVE CODE.

THIS IS A COURTESY COPY OF THIS RULE. ALL OF THE DEPARTMENT S RULES ARE COMPILED IN TITLE 7 OF THE NEW JERSEY ADMINISTRATIVE CODE. 2. The type of drainage fabric used shall be specified in the engineering design and shall have adequate tensile strength to prevent ripping during installation and backfilling, adequate permeability to

More information

Unit 1 - Introduction, Testing Criteria, and Design Criteria 1-1 Introduction 1-2 Testing Criteria Requirements 1-3 System Design Requirements

Unit 1 - Introduction, Testing Criteria, and Design Criteria 1-1 Introduction 1-2 Testing Criteria Requirements 1-3 System Design Requirements Unit 1 - Introduction, Testing Criteria, and Design Criteria 1-1 Introduction 1-2 Testing Criteria Requirements 1-3 System Design Requirements What You Will Learn in This Lesson In this lesson, you will

More information

Mounded Wastewater Treatment Systems

Mounded Wastewater Treatment Systems Mounded Wastewater Treatment Systems Technical Guidance for Site Suitability, Design, Construction, Operation and Maintenance Distribution Cell Cover Material Sand Media Pump Chamber Colorado Department

More information

Montana. Design and Installation Manual for the Infiltrator ATL TM System in Montana. Infiltrator ATL System in Montana

Montana. Design and Installation Manual for the Infiltrator ATL TM System in Montana. Infiltrator ATL System in Montana Design and Installation Manual for the Infiltrator ATL TM System in Montana Infiltrator ATL System in Montana INTRODUCTION 2 MONTANA- SPECIFIC INFORMATION SYSTEM CONFIGURATIONS SYSTEM DESIGN 8 3 5 The

More information

DESIGN REGULATIONS FOR SUBSURFACE DRIP DISPERSAL SYSTEMS

DESIGN REGULATIONS FOR SUBSURFACE DRIP DISPERSAL SYSTEMS DESIGN REGULATIONS FOR SUBSURFACE DRIP DISPERSAL SYSTEMS Boone County Regional Sewer District Boone County, Missouri Adopted: March 20, 2018 Chapter 5 Contents 5.1. Introduction... 1 5.2. General Provisions...

More information

Woodford County Health Department 1831 S. Main Street, Eureka, IL Phone: (309) Fax: (309)

Woodford County Health Department 1831 S. Main Street, Eureka, IL Phone: (309) Fax: (309) Woodford County Health Department 1831 S. Main Street, Eureka, IL 61530 Phone: (309) 467-3064 Fax: (309) 467-5104 www.woodfordhealth.org APPLICATION/PERMIT FOR PRIVATE SEWAGE DISPOSAL SYSTEM FEE: $225.00

More information

Enviro-Septic Wastewater Treatment Systems Design and Installation Manual Vermont State Attachment

Enviro-Septic Wastewater Treatment Systems Design and Installation Manual Vermont State Attachment Enviro-Septic Wastewater Treatment Systems Design and Installation Manual Vermont State Attachment The information in this manual is subject to change without notice. Your suggestions and comments are

More information

Site Plan: General: Common Omissions-Mistakes on Plans: Ohio EPA Southeast District Office Logan, Ohio November 22, 2005 Bruce Goff, P.E.

Site Plan: General: Common Omissions-Mistakes on Plans: Ohio EPA Southeast District Office Logan, Ohio November 22, 2005 Bruce Goff, P.E. Common Omissions-Mistakes on Plans: Ohio EPA Southeast District Office Logan, Ohio 43138 November 22, 2005 Bruce Goff, P.E. Site Plan: Inadequate site survey, e.g. no topographic contours Locations of

More information

National Onsite Wastewater Recycling Association. Recommended Guidance for the Design of Wastewater Drip Dispersal Systems

National Onsite Wastewater Recycling Association. Recommended Guidance for the Design of Wastewater Drip Dispersal Systems 1. SCOPE National Onsite Wastewater Recycling Association Recommended Guidance for the Design of Wastewater Drip Dispersal Systems 1.1 Drip dispersal is a method used to distribute wastewater that has

More information

Indiana. Design and Installation Manual for the Infiltrator ATL TM System in Indiana. Infiltrator ATL System in Indiana

Indiana. Design and Installation Manual for the Infiltrator ATL TM System in Indiana. Infiltrator ATL System in Indiana Design and Installation Manual for the Infiltrator ATL TM System in Indiana 2 The purpose of this manual is to provide the minimum specifications for design and installation of the Infiltrator ATL TM (Advanced

More information

PERC-RITE DRIP DISPERSAL DESIGN GUIDE FOR SEPTIC TANK OR ADVANCED TREATMENT EFFLUENT MASSACHUSETTS

PERC-RITE DRIP DISPERSAL DESIGN GUIDE FOR SEPTIC TANK OR ADVANCED TREATMENT EFFLUENT MASSACHUSETTS PERC-RITE DRIP DISPERSAL DESIGN GUIDE FOR SEPTIC TANK OR ADVANCED TREATMENT EFFLUENT MASSACHUSETTS This Design Guide is to assist you in preparing for the design of a Perc-Rite Drip Dispersal System for

More information

ON-SITE SEWAGE PERMITTING PROCESS

ON-SITE SEWAGE PERMITTING PROCESS Whitman County Environmental Health ON-SITE SEWAGE PERMITTING PROCESS STEP I. SOIL & SITE EVALUATION Complete the front page of the OSS Site Evaluation Application and schedule an appointment with an Environmental

More information

NORTH CAROLINA DEPARTMENT OF HEALTH AND HUMAN SERVICES DIVISION OF PUBLIC HEALTH ENVIRONMENTAL HEALTH SECTION ON-SITE WATER PROTECTION BRANCH

NORTH CAROLINA DEPARTMENT OF HEALTH AND HUMAN SERVICES DIVISION OF PUBLIC HEALTH ENVIRONMENTAL HEALTH SECTION ON-SITE WATER PROTECTION BRANCH NORTH CAROLINA DEPARTMENT OF HEALTH AND HUMAN SERVICES DIVISION OF PUBLIC HEALTH ENVIRONMENTAL HEALTH SECTION ON-SITE WATER PROTECTION BRANCH INNOVATIVE WASTEWATER SYSTEM APPROVAL INNOVATIVE WASTEWATER

More information

SPECIAL SPECIFICATION 3504 Septic Tank System

SPECIAL SPECIFICATION 3504 Septic Tank System 1993 Specifications CSJ s 3136-01-126, etc. & 0683-01-070, etc. SPECIAL SPECIFICATION 3504 Septic Tank System 1. Description. This Item shall govern for all materials, equipment and labor necessary for

More information

Australia Design & Installation Manual

Australia Design & Installation Manual Geotextile Sand Filter Australia Design & Installation Manual CORPORATION Innovative Environmental Products & Solutions Since 1970 May 2016 www.eljen.com Table of Contents SUBJECT PAGE GLOSSARY OF TERMS...

More information

Geotextile Sand Filter

Geotextile Sand Filter Geotextile Sand Filter CORPORATION Innovative Environmental Products & Solutions Since 1970 Table of Contents SUBJECT PAGE GLOSSARY OF TERMS... 3 GSF SYSTEM DESCRIPTION... 5 TESTING AND PERFORMANCE...

More information

FOR BENEFICIAL REUSE & DISPERSAL OF WASTEWATER WASTEWATER PRODUCTS

FOR BENEFICIAL REUSE & DISPERSAL OF WASTEWATER WASTEWATER PRODUCTS N E T A F I M U S A FOR BENEFICIAL REUSE & DISPERSAL OF WASTEWATER WASTEWATER PRODUCTS OVERVIEW We face a global challenge to responsibly use and protect our finite supply of fresh water, yet all too often

More information

On-lot System Component Requirements

On-lot System Component Requirements On-lot System Component Requirements All system components used with an on-lot system employing an Eljen GSF System must meet either the requirements of Title 25, Chapter 73 or the Eljen GSF Listing. The

More information

Contact Information Owner s Name Home Phone Cell Phone Mailing Address City Zip Code

Contact Information Owner s Name Home Phone Cell Phone Mailing Address City Zip Code Henry & Stark County Health Department Environmental Health 4424 US Hwy 34, Kewanee, IL 61443 309-852-0197--309-852-3115 www.henrystarkhealth.com Henry County Stark County Received by: Amount Received:

More information

Design and Installation Manual for the Infiltrator ATL System in British Columbia

Design and Installation Manual for the Infiltrator ATL System in British Columbia Design and Installation Manual for the Infiltrator ATL System in British Columbia Infiltrator ATL System in British Columbia INTRODUCTION 2 BC- SPECIFIC INFORMATION DESIGN INFORMATION 4 INFORMATION FOR

More information

Contact Information Owner s Name Home Phone Cell Phone Mailing Address City Zip Code

Contact Information Owner s Name Home Phone Cell Phone Mailing Address City Zip Code Henry & Stark County Health Department Environmental Health 4424 US Hwy 34, Kewanee, IL 61443 309-852-0197--309-852-3115 www.henrystarkhealth.com Henry County Stark County Received by: Amount Received:

More information

APPENDIX A LOW PRESSURE DOSED SAND FILTERS

APPENDIX A LOW PRESSURE DOSED SAND FILTERS 3701-29-13 1 I. Introduction APPENDIX A LOW PRESSURE DOSED SAND FILTERS Low pressure dosed sand filters (LPDSF) are aerobic, fixed-film bioreactors that are capable of treating septic tank effluent (or

More information

SECTION A-A. Blower Housing. Settling Zone Volume times daily flow. Treatment Zone. SaniTEE 818-B. Vent. Shutoff Valve.

SECTION A-A. Blower Housing. Settling Zone Volume times daily flow. Treatment Zone. SaniTEE 818-B. Vent. Shutoff Valve. A Shutoff Valve Influent Distribution Box See note 11 Volume 0.5-1 times daily flow Mixing Pump Recirculation Pump Discharge SaniTEE 818-B Recirculation Pump Vent Control Panel Blower Housing A NOTES 1.

More information

Section 8: Amended Soil Mounds. 8. Amended Soil Mounds

Section 8: Amended Soil Mounds. 8. Amended Soil Mounds Section 8: Amended Soil Mounds 8. Amended Soil Mounds 8. Amended Soil Mounds 8.1 Design...95 8.2 Installation...96 8.3 Inspection...101 8.4 Operation...101 8.5 Common technical issues...105 8.6 Case study...105

More information

Geotextile Sand Filter

Geotextile Sand Filter Geotextile Sand Filter CORPORATION Innovative Environmental Products & Solutions Since 1970 Table of Contents Subject Page Terms and Definitions 3 GSF System Description 6 1.0 Basic System Design 7 2.0

More information

DRAFT DESIGN REGULATIONS FOR SUBSURFACE DRIP DISPERSAL SYSTEMS

DRAFT DESIGN REGULATIONS FOR SUBSURFACE DRIP DISPERSAL SYSTEMS DRAFT DESIGN REGULATIONS FOR SUBSURFACE DRIP DISPERSAL SYSTEMS Boone County Regional Sewer District Boone County, Missouri Adopted xx/xx/xxxx Chapter 5 Contents 5.1. Introduction... 1 5.2. General Provisions...

More information

FLOWTECH WASTEWATER TRENCH SYSTEMS Manufactured with 100% Recycled Artificial Aggregate

FLOWTECH WASTEWATER TRENCH SYSTEMS Manufactured with 100% Recycled Artificial Aggregate FLOWTECH WASTEWATER TRENCH SYSTEMS Manufactured with 100% Recycled Artificial Aggregate STATE OF NORTH CAROLINA INSTALLATION MANUAL May 8, 2012 Manufactured by ICC TECHNOLOGIES, LLC MARLBORO, N.J. 1-877-422-3569

More information

Rhode Island Design & Installation Manual

Rhode Island Design & Installation Manual Geotextile Sand Filter Rhode Island Design & Installation Manual CORPORATION Innovative Onsite Products & Solutions Since 1970 November 2018 www.eljen.com Table of Contents SUBJECT PAGE GLOSSARY OF TERMS...

More information

Section 11: Evapotranspiration Absorption Beds. 11. Evapotranspiration Absorption Beds

Section 11: Evapotranspiration Absorption Beds. 11. Evapotranspiration Absorption Beds Section 11: Evapotranspiration Absorption Beds 11. Evapotranspiration Absorption Beds 11. Evapotranspiration Absorption / Beds 11.1 Design...143 11.2 Installation...143 11.3 Testing...151 11.4 Operation...151

More information

DESIGN, INSTALLATION AND MAINTENANCE GUIDELINES

DESIGN, INSTALLATION AND MAINTENANCE GUIDELINES SUBSURFACE DRIP DISPOSAL SYSTEMS DESIGN, INSTALLATION AND MAINTENANCE GUIDELINES Subsurface drip disposal systems are specifically engineered for each site by a design professional and are constructed

More information

Pump Tank and Pretreatment Inspection & Troubleshooting. Sara Heger University of Minnesota

Pump Tank and Pretreatment Inspection & Troubleshooting. Sara Heger University of Minnesota Pump Tank and Pretreatment Inspection & Troubleshooting Sara Heger University of Minnesota sheger@umn.edu Evaluate Presence of Odor Odors are improper venting Check seals Lid Conduit Tank Access a. Access

More information

1.0 BACKGROUND 2.0 DIAGRAMS. The attached diagrams illustrate a typical NDDS system. 3.0 CDPHE OWTS REGULATION #43

1.0 BACKGROUND 2.0 DIAGRAMS. The attached diagrams illustrate a typical NDDS system. 3.0 CDPHE OWTS REGULATION #43 COLORADO PROFESSIONALS IN ONSITE WASTEWATER (CPOW) GUIDELINES FOR THE DESIGN AND INSTALLATION OF NON-PRESSURIZED DRIP DISPERSAL SYSTEMS (NDDS) REVISED DECEMBER 11, 2014 1.0 BACKGROUND Non-Pressurized Drip

More information

REVISION OF SECTION 623 IRRIGATION SYSTEM GENERAL

REVISION OF SECTION 623 IRRIGATION SYSTEM GENERAL 623.01 SUMMARY: GENERAL Section Includes: Landscape irrigation system as shown on the drawings for complete coverage to landscape areas. Furnish design for layout, pipe sizing, valving and head types and

More information

Figure 1. Report of Inspection Process Flowchart.

Figure 1. Report of Inspection Process Flowchart. INSTRUCTIONS FOR A REPORT OF INSPECTION FOR AN ON-SITE WASTEWATER TREATMENT FACILITY INSTRUCTIONS Within six months before the date of a property transfer, the person who is transferring a property served

More information

Geotextile Sand Filter

Geotextile Sand Filter Geotextile Sand Filter CORPORATION Innovative Environmental Products & Solutions Since 1970 Table of Contents SUBJECT PAGE GLOSSARY OF TERMS... 3 HOW THE GSF SYSTEM WORKS... 5 TESTING AND PERFORMANCE...

More information

Enviro-Septic Wastewater Treatment System Indiana Design and Installation Manual for Residential Systems

Enviro-Septic Wastewater Treatment System Indiana Design and Installation Manual for Residential Systems Enviro-Septic Wastewater Treatment System Indiana Design and Installation Manual for Residential Systems PRESBY ENVIRONMENTAL, INC. INNOVATIVE SEPTIC TECHNOLOGIES 143 Airport Rd., Whitefield, NH 03598

More information

The system is capable of operating in (3) three modes, each with (2) two different dose modes.

The system is capable of operating in (3) three modes, each with (2) two different dose modes. Integrated Leachate Pumping Systems www.leachator.com info@leachator.com Introduction The Leach-Rite Dispersal System installed in your landfill is a unique system for dispersing leachate back into the

More information

Massachusetts Design & Installation Manual

Massachusetts Design & Installation Manual Geotextile Sand Filter Massachusetts Design & Installation Manual CORPORATION Innovative Onsite Products & Solutions Since 1970 September 2018 www.eljen.com Table of Contents SUBJECT PAGE GLOSSARY OF TERMS...

More information

INSTRUCTIONS FOR SUBMITTING A COMMERCIAL SEWAGE DISPOSAL PERMIT APPLICATION

INSTRUCTIONS FOR SUBMITTING A COMMERCIAL SEWAGE DISPOSAL PERMIT APPLICATION Permits will be processed only when ALL required information is provided Application MUST be accompanied by the following: Property address or road location with distance from nearest intersection. IT

More information

Calculating Length and Width for Limiting Zone with 20 Inches of Suitable Soil

Calculating Length and Width for Limiting Zone with 20 Inches of Suitable Soil Calculating Length and Width for Limiting Zone with 20 Inches of Suitable Soil The final design square footage is dependent on the total number of required modules and corresponding specified sand dimensions.

More information

Complex Sewage Disposal Course 2017

Complex Sewage Disposal Course 2017 Complex Sewage Disposal Course 2017 Updates to the Technical Guidance Manual This information is based on the most recent version of the TGM. Updates from previous versions can be found on DEQ s website

More information

TRI-STATE PUMP & SEPTIC SUPPLY February 20, 2010

TRI-STATE PUMP & SEPTIC SUPPLY February 20, 2010 TRI-STATE PUMP & SEPTIC SUPPLY February 20, 2010 We service New Jersey, New York and Pennsylvania We specialize in alternative septic system products We offer products, service, support and training www.pumpandseptic.com

More information

SUMP / EFFLUENT PUMPS ARE SINGLE PHASE WITH PIGGYBACK FLOAT SWITCH. Max. Flow 44. Max. Head 20. Voltage 115

SUMP / EFFLUENT PUMPS ARE SINGLE PHASE WITH PIGGYBACK FLOAT SWITCH. Max. Flow 44. Max. Head 20. Voltage 115 SUMP / EFFLUENT PUMPS ARE SINGLE PHASE WITH PIGGYBACK FLOAT SWITCH PL-CPSE3A 1/3 44 0 1½ NPT EFFLUENT PUMPS ARE SINGLE PHASE WITH PIGGYBACK FLOAT SWITCH PL-CPE4A-1 PL-CPE5A-1 PL-CPEH5A1 PL-CPSTEP51A PL-CPSTEP10A

More information

Homeowner Online Septic System Training (HOST)

Homeowner Online Septic System Training (HOST) Homeowner Online Septic System Training (HOST) Provided By: Whatcom County Health Department E-mail address: Health_EH_Parcel@whatcomcounty.us Phone Number: 360-778-6000 1 There are three requirements

More information

Geotextile Sand Filter

Geotextile Sand Filter Geotextile Sand Filter CORPORATION Innovative Environmental Products & Solutions Since 1970 Table of Contents SUBJECT PAGE Glossary of Terms 4 GSF System Description 6 1.0 Basic System Design 8 2.0 Systems

More information

GRAY WATER RECYCLING SYSTEMS

GRAY WATER RECYCLING SYSTEMS GRAY WATER RECYCLING SYSTEMS Note: Section P2601.2 of the International Residential Code requires all plumbing fixtures that receive water or waste to discharge to the sanitary drainage system of the structure.

More information

West Virginia Department of Health & Human Resources Department of Health

West Virginia Department of Health & Human Resources Department of Health SS-182A Rev 6/07 West Virginia Department of Health & Human Resources Department of Health Application for a Permit to Install or Modify an Onsite Sewage Disposal System Property Owner Phone (H) (W) Address

More information

Design and Construction Manual for Sand Mound Systems

Design and Construction Manual for Sand Mound Systems Design and Construction Manual for Sand Mound Systems February 2016 (5 th Edition) State of Maryland Department of the Environment Water Management Administration Wastewater Permits Program On-Site Systems

More information

On-Site Leaching Chamber Specifications & Features. Design & Installation Manual Ohio

On-Site Leaching Chamber Specifications & Features. Design & Installation Manual Ohio On-Site Leaching Chamber Specifications & Features Design & Installation Manual Ohio 1 This manual provides general design and installation information for use of Arc plastic leaching chambers in the State

More information

Introduction to Advanced Enviro-Septic Wastewater Treatment System

Introduction to Advanced Enviro-Septic Wastewater Treatment System Introduction to Advanced Enviro-Septic Wastewater Treatment System Sales & Distribution Contact Justin DaMore of Morning Star Distribution Justin@meyersenv.com 585-377-1700 (office) 585-781-4602 (cell)

More information

NORTH CAROLINA DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES DIVISION OF ENVIRONMENTAL HEALTH ON-SITE WATER PROTECTION SECTION

NORTH CAROLINA DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES DIVISION OF ENVIRONMENTAL HEALTH ON-SITE WATER PROTECTION SECTION NORTH CAROLINA DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES DIVISION OF ENVIRONMENTAL HEALTH ON-SITE WATER PROTECTION SECTION INNOVATIVE WASTEWATER SYSTEM APPROVAL INNOVATIVE WASTEWATER SYSTEM NO: IWWS-2011-1

More information

Drip Irrigation in the Municipal Landscape. Dino Viale- Area Sales Manager, Northern California (510)

Drip Irrigation in the Municipal Landscape. Dino Viale- Area Sales Manager, Northern California (510) Drip Irrigation in the Municipal Landscape Dino Viale- Area Sales Manager, Northern California (510) 365-5186 Started in Israel in 1965 Netafim Global company focusing on the Agricultural, Landscape, Mining,

More information

On-Site Leaching Chamber Specifications & Features. Design & Installation Manual New York

On-Site Leaching Chamber Specifications & Features. Design & Installation Manual New York On-Site Leaching Chamber Specifications & Features Design & Installation Manual New York 1 This manual provides general design and installation information for use of Arc plastic leaching chambers in the

More information

FIELD GUIDE FOR MILLENNIUM MOUNDS CLERMONT CO. GENERAL HEALTH DISTRICT 2010

FIELD GUIDE FOR MILLENNIUM MOUNDS CLERMONT CO. GENERAL HEALTH DISTRICT 2010 FIELD GUIDE FOR MILLENNIUM MOUNDS CLERMONT CO. GENERAL HEALTH DISTRICT 2010 DIMENSIONS BETWEEN DRAINS SINGLE LENGTH MOUND 2 BEDROOM 98 X 20 3 BEDROOM 139 X 20 4 BEDROOM 184 X 20 HALF STRUCTURE MOUND 2

More information

THE FATE OF FECAL COLIFORM BACTERIA IN THE OSCAR SYSTEM. Dave Lowe 1 ABSTRACT

THE FATE OF FECAL COLIFORM BACTERIA IN THE OSCAR SYSTEM. Dave Lowe 1 ABSTRACT THE FATE OF FECAL COLIFORM BACTERIA IN THE OSCAR SYSTEM Dave Lowe 1 ABSTRACT The OSCAR is a patent pending onsite sewage treatment technology that employs the principles of thin film flow and micro dosing

More information

Arizona Design & Installation Manual

Arizona Design & Installation Manual Geotextile Sand Filter Arizona Design & Installation Manual CORPORATION Innovative Onsite Products & Solutions Since 1970 March 2018 www.eljen.com Table of Contents SUBJECT PAGE GLOSSARY OF TERMS... 3

More information

Procedures for Connecting to Central Sewer System

Procedures for Connecting to Central Sewer System Procedures for Connecting to Central Sewer System These procedures and requirements are taken from the Taney County Regional Sewer District s appoved Sewer Use Regulation, Article 4 Building Sewers and

More information

Geotextile Sand Filter

Geotextile Sand Filter Geotextile Sand Filter CORPORATION Innovative Environmental Products & Solutions Since 1970 Table of Contents SUBJECT PAGE GSF SYSTEM DESCRIPTION... 5 1.0 BASIC SYSTEM DESIGN... 6 2.0 SYSTEMS FOR LEVEL

More information

Typical Local Erosion Control Requirements (Storm Water Management Authority, Inc.)

Typical Local Erosion Control Requirements (Storm Water Management Authority, Inc.) Module 2: Selection of Controls and Site Planning for Construction Site Erosion Prevention Robert Pitt Department of Civil, Construction, and Environmental Engineering University of Alabama Tuscaloosa,

More information

SEPTIC TANK CONSTRUCTION GUIDELINES

SEPTIC TANK CONSTRUCTION GUIDELINES SEPTIC TANK CONSTRUCTION GUIDELINES Septic tank for this airport will be designed/ built by the general contractor of the building facilities. At the time of the project design, availability of a septic

More information

All vendors, distributors, and resellers must provide each purchaser of the System with copies of applicable Certification or Approval.

All vendors, distributors, and resellers must provide each purchaser of the System with copies of applicable Certification or Approval. Updated March 2011 The information in this manual is subject to change without notice. Your suggestions and comments are welcome. Please contact us at Presby Environmental, Inc. 143 Airport Road Whitefield,

More information

Private Sewage Systems Standard of Practice Proposed Revisions

Private Sewage Systems Standard of Practice Proposed Revisions Private Sewage Systems Standard of Practice Proposed Revisions The Government of Alberta is currently reviewing the Standard of Practice (SOP) for Private Sewage Systems. To this end, the Alberta government

More information

SANDERS COUNTY ENVIRONMENTAL HEALTH PROPERTY OWNER SEPTIC INSTALLATION BOOKLET

SANDERS COUNTY ENVIRONMENTAL HEALTH PROPERTY OWNER SEPTIC INSTALLATION BOOKLET SANDERS COUNTY ENVIRONMENTAL HEALTH PO BOX 519 406-827-6961 1111 MAIN STREET, THOMPSON FALLS, MT 59873 sanitarian@sanderscounty.mt.gov PROPERTY OWNER SEPTIC INSTALLATION BOOKLET This booklet discusses

More information

Design and Installation Manual for Quick4 Chambers in New Brunswick, Canada

Design and Installation Manual for Quick4 Chambers in New Brunswick, Canada Design and Installation Manual for Quick4 Chambers in New Brunswick, Canada APPROVAL LETTERS 2 INTRODUCTION 4 CHAMBER TECHNOLOGY 5 PRODUCTS 6 SYSTEM SIZING 7 IN-GROUND TRENCHES 8 TRENCH CONFIGURATIONS

More information

RESEARCH AND DEMONSTRATION CENTER ON-LOT SYSTEMS AND SMALL FLOW TECHNOLOGIES DELAWARE VALLEY COLLEGE DOYLESTOWN, PA

RESEARCH AND DEMONSTRATION CENTER ON-LOT SYSTEMS AND SMALL FLOW TECHNOLOGIES DELAWARE VALLEY COLLEGE DOYLESTOWN, PA RESEARCH AND DEMONSTRATION CENTER ON-LOT SYSTEMS AND SMALL FLOW TECHNOLOGIES DELAWARE VALLEY COLLEGE DOYLESTOWN, PA Project Funding Provided by: Pennsylvania Dept. of Environmental Protection Thomas J.

More information

NORTH CAROLINA DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES DIVISION OF ENVIRONMENTAL HEALTH ON-SITE WASTEWATER SECTION

NORTH CAROLINA DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES DIVISION OF ENVIRONMENTAL HEALTH ON-SITE WASTEWATER SECTION NORTH CAROLINA DEPARTMENT OF ENVIRONMENT AND NATURAL RESOURCES DIVISION OF ENVIRONMENTAL HEALTH ON-SITE WASTEWATER SECTION INNOVATIVE WASTEWATER SYSTEM APPROVAL, Attachment INNOVATIVE WASTEWATER SYSTEM

More information

SECTION A-A. Control Panel

SECTION A-A. Control Panel SaniTEE 818-B Blower Housing Settling Zone 1050 Gallon MIN 4500 Gallons Control [4000 L MIN] [17000L] Panel 183 MX 72 MX Height of Effluent Line 1. Blower piping to BioBarrier MBR may not exceed 40 FT

More information

Geotextile Sand Filter

Geotextile Sand Filter Geotextile Sand Filter CORPORATION Innovative Environmental Products & Solutions Since 1970 Table of Contents SUBJECT PAGE GLOSSARY OF TERMS... 3 GSF SYSTEM DESCRIPTION... 5 1.0 DESIGN AND INSTALLATION...

More information

AdvanTex AX-RT Treatment Systems

AdvanTex AX-RT Treatment Systems AdvanTex Design Criteria AdvanTex AX-RT Treatment Systems For Single-Family Home Applications System Description The AdvanTex Treatment System is a multiple-pass, packed-bed aerobic wastewater treatment

More information

AERATED POND REVIEW CHECKLIST

AERATED POND REVIEW CHECKLIST Water Quality AERATED POND REVIEW CHECKLIST Wastewater Technical Review and Guidance FACILITY NAME Water/Wastewater/#5.04, May 2001 DATE CONSULTING ENGINEER SITE INSPECTION (DATE & INSPECTOR) PLANNING

More information

SECTION A-A. Blower Housing. SaniTEE 818-B. Shutoff Valve. Influent. Settling Zone Volume times daily flow. Treatment Zone.

SECTION A-A. Blower Housing. SaniTEE 818-B. Shutoff Valve. Influent. Settling Zone Volume times daily flow. Treatment Zone. Shutoff Valve Influent Distribution Box See note 11 SaniTEE 818-B Blower Housing Control Panel NOTES 1. Blower piping to BioBarrier HSMBR may not exceed 40 FT [12 m] total length and use 4 elbows maximum

More information

MASTER. Water Conditioning Corp. OPERATION MANUAL. PURO PRO 1200 SCP Series Modular Reverse Osmosis System. January 2012 Version

MASTER. Water Conditioning Corp. OPERATION MANUAL. PURO PRO 1200 SCP Series Modular Reverse Osmosis System.  January 2012 Version MASTER Water Conditioning Corp. www.masterwater.com OPERATION MANUAL PURO PRO 1200 SCP Series Modular Reverse Osmosis System January 2012 Version Table of Contents Model Number... 1 Shipping Description

More information

NORTH CAROLINA DEPARTMENT OF HEALTH AND HUMAN SERVICES DIVISION OF PUBLIC HEALTH ENVIRONMENTAL HEALTH SECTION ON-SITE WATER PROTECTION BRANCH

NORTH CAROLINA DEPARTMENT OF HEALTH AND HUMAN SERVICES DIVISION OF PUBLIC HEALTH ENVIRONMENTAL HEALTH SECTION ON-SITE WATER PROTECTION BRANCH NORTH CAROLINA DEPARTMENT OF HEALTH AND HUMAN SERVICES DIVISION OF PUBLIC HEALTH ENVIRONMENTAL HEALTH SECTION ON-SITE WATER PROTECTION BRANCH ACCEPTED WASTEWATER SYSTEM APPROVAL Accepted Wastewater System

More information

Cascade Irrigation Efficiency Program Rebate Application

Cascade Irrigation Efficiency Program Rebate Application Cascade Irrigation Efficiency Program Rebate Application Introduction Cascade Water Alliance wants to help you save water. To reduce summer water demand, Cascade s Irrigation Efficiency Program offers

More information