IDENTIFICATION OF VENTILATION PROBLEMS IN AN UNDERGROUND BUS TERMINAL IN KOREA

Size: px
Start display at page:

Download "IDENTIFICATION OF VENTILATION PROBLEMS IN AN UNDERGROUND BUS TERMINAL IN KOREA"

Transcription

1 IDENTIFICATION OF VENTILATION PROBLEMS IN AN UNDERGROUND BUS TERMINAL IN KOREA H Han 1* and Y-I Kwon 2 1 Dept. Of Mechanical Engineering, Kookmin University, Korea 2 Dept. Of Building Mechanical Engineering, Shinheung College, Korea ABSTRACT It is the objective of the present study to identify ventilation problems and to suggest design modifications of the ventilation system to improve IAQ in the terminal. Numerical results on air velocity and concentration distributions are presented along with some of field experimental data on indoor concentrations of NO x, CO and suspended particles. Results show many interesting aspects of airflow patterns affecting the ventilation characteristics of the building. System modifications on airflow rates and grille locations have been suggested from the numerical results in order to prevent direct short-circuiting of outdoor air and recirculation of contaminated indoor air. The overall exhaust performances of the modified conditions are compared quantitatively with existing ventilation condition using the concept of the mean residual-life-time of contaminated air. INDEX TERMS Ventilation effectiveness, Underground bus terminal, Numerical, Indoor air quality INTRODUCTION Bus terminals are usually built on a ground level, which are completely open or partially enclosed for weather protection. Engine emissions are exhausted mostly by natural ventilation with supplementary mechanical ventilation equipments for platform areas. For an enclosed underground terminal, however, a proper design of mechanical air distribution system is very important to control terminal environment since the natural ventilation is limited (ASHRAE, 2001). A large bus terminal complex with ground area of square meters was constructed in a newly built city of Sung-Nam; located approximately 30km south of Seoul. In order to prevent engine emissions from being dispersed out of the terminal to nearby residential areas, the underground level was assigned for a bus terminal. As there was a great concern on indoor air quality in the terminal, however, bus companies and shop renters asked for clarifications of the indoor air quality issue before they started businesses in the building. A research project has been undertaken for the assessment of the indoor environment and the ventilation systems of the terminal building, and for the suggestions of ventilation system modifications (SAREK, 2001). Field experiments were conducted to visualize airflow patterns by the existing ventilation system and to measure indoor concentrations of CO, NO x, and suspended particles with 19 buses idling at the platform. The actual airflow rates through supply and exhaust ducts and grilles were measured and compared with the design values. Computational fluid dynamic calculations were also conducted to simulate airflow and concentration distributions not only for the current ventilation condition but also for suggested modified conditions. * Contact author hhan@kookmin.ac.kr 337

2 The objective of the present paper is to report some of the engineering findings from the investigation. The distributions of local mean residual-life-time of contaminated air are obtained from the calculated airflow velocity distributions for various configurations of ventilation systems; i.e. exhaust grille locations and ventilation airflow rates. CFD results show that ventilation effectiveness can be improved significantly by relocating exhaust grilles and supply ducts to prevent a stagnation of indoor air and a direct short-circuiting of outdoor air to exhausts. VENTILATION SYSTEM The terminal complex consists of a 11-story shopping center building and a multilevel (7 levels above ground and 3 stories underground) garage building. The basement of the shopping building is used for ticket counters, waiting rooms, and some retail stores. The underground level of the garage building is used for passenger platforms and other facilities for bus operations. The platform has a sawtooth gate configuration as is shown in Fig. 1. There are two busway ramps to ground level, A and B, and two ramps to B2 level, C and D. Supply grilles are located above the platform in two rows, and exhaust grilles are located near ramps on the other side of the platform. There are two fan rooms for exhaust. Exhaust grille α is connected to Fan room 1, and grilles β, γ are to Fan room 2. The principal design concept is to displace contaminated indoor air in one direction, from the platform areas to the other side of the building. Tangential long-fans are installed on the ceiling to help creating uniform flow in the direction. The locations of long-fans are also shown in Fig. 1. Figure 1. Plan view of the terminal building and calculation domain. The design airflow rate is 180,000CMH, which corresponds to 8ACH approximately. 100% outside air is supplied with no recirculation. There is no IAQ standard for underground bus terminals. As a pertinent standard, there is an Act on Air Quality in Underground Spaces, 338

3 which states PM10 be less than 150µg/m 3, CO 10ppm, CO ppm, NO ppm. There is a regulation on outdoor parking lots, which states CO should be below 50ppm on 8hr basis. SIMULATION METHODS The airflow rates under actual operations of the existing ventilation systems have been measured lower compared to the design values, because of duct leakages and fan performances. Numerical simulations are conducted for four difference conditions as shown in Table 1. Case 1 is the design condition, and Case 2 is the measured condition. Case 3 and 4 are modified conditions with increased airflow rates and modified grille locations and configurations. Table 1. Airflow conditions for numerical simulation Design T.A.B. Modified Condition Condition Condition 1 (Case 1) (Case 2) (Case 3) Supply airflow rate Exhaust airflow rate Modified condition 2 (Case 4) 180, , , , , , , ,000 Exhaust at α 90,000 61,400 80, ,000 Exhaust at β+γ 90,000 78, , ,000 Remarks -Ramps D closed. -Additional supply diffusers at corners. -Ramps D closed. -Additional supply diffusers at corners. -Supply air in the downward direction. -Long-fan locations shifted. A commercial CFD code based on the finite element method has been utilized. A continuity equation and momentum equations are solved simultaneously along with temperature and concentration equations. A standard k-e model is used to calculate turbulent quantities. The dimensions of the simulation domain are 110mx70mx5m, and the numbers of grids are 204x99x50. A body-fitted coordinate system is used to account for complex boundaries as shown in Fig. 1 with bold lines. Boundary conditions used are no slip conditions for velocity, and adiabatic conditions for heat and mass transfer along the boundaries except bus ramps and supply/exhaust grilles. Pressure boundary conditions are applied for the ramp openings. The indoor air temperature is assumed to be isothermal at 20 o C, except the temperature along the boundaries of Ramps A and B at 30 o C. Nineteen buses with diesel engines are simulated, idling at the platform area. Since the concentration of emission gas varies significantly from one engine to another, the concentration equation is non-dimensionalized with a tailpipe emission concentration. Local mean residual-life-time (LMR) is defined as the time for an air particle at a point P to reach an exhaust. It indicates how quickly contaminated air can be removed from the system. LMR can be calculated from a transient concentration decay, C ex p (t), measured at the exhaust by a step-up generation at point P using the following equation (Etheridge and Sandberg, 1996). LMR p Cex ( t) p = 1 dt (1) 0 p Cex ( ) where t= means a steady state condition. The mean value of LMR shows overall ventilation performance of the exhaust system with the given emission locations. The mean values can be also calculated from the concentration at the exhaust (Han, 1996). The higher the 339

4 concentration is at the exhaust, the higher the exhaust effectiveness is for the given emission source locations. The overall exhaust effectiveness is defined as the ratio of the nominal time constant to the mean value of LMR. RESULTS AND DISCUSSION Concentration distributions and air quality standards The dimensionless concentration contours are shown in Fig. 2a superimposed with some of measured CO and NO x concentrations. Measured CO varies from 4.1 to 13.1ppm. Even though the actual TAB airflow rate is lower than the design value, measured CO is below the parking lot standard, but is slightly over indoor air quality standard of 10ppm. NO x is measured between 1.0 and 2.9ppm, and PM10 is measured between 297 and 359 µg/m 3, which is approximately twice of the IAQ standard. Generally speaking, there is a good agreement between calculated and measured concentrations in a relative sense. Figure 2b shows the concentration distribution for the modified condition 2 (Case 4). The concentration is significantly lowered especially at platform areas not only because of the increased flow rate but also because of the unidirectional airflow pattern created in the terminal. Details of the system modifications will be shown subsequently in the followings based on numerical observations. (a) TAB condition (Case 2) (b) Modified condition 2 (Case 4) Figure 2. Concentration distributions calculated for Case 2 and Case 4 (Y=0.3m) Stagnation of contaminated air at platform corners As the supply grilles have not been distributed uniformly along the platform, contaminated air is stagnant at corners and is not pushed toward exhaust grilles. As is shown in Fig. 2, relatively high concentrations are obtained near buses 1-2 and Additional supply diffusers need to be installed at the corners of the platform. The concentrations are significantly decreased especially at the corners as is shown in Fig. 2b for the modified condition 2. Short-circuiting of outdoor air to exhaust Since the exhausts are located near large ramp openings, fresh air from outside is shortcircuited to the exhaust grilles directly without attracting contaminated indoor air as was originally designed. For winter conditions, significant amount of cold air is expected to be down-drafted from the ground level due to the temperature difference. The entrained outdoor air would lower the concentration level in the vicinity of the entrance, but deteriorate the overall exhaust performance seriously. This is not the case for summer conditions. However, a short-circuiting at the exhaust α is serious for summer conditions. Flow visualization also 340

5 exhibits the fact and the entrainment takes place mostly through the upper part of Ramp D. A concentration distribution normal to the exhaust grille is plotted in Fig. 3. Because of the entrainment, the concentration is decreased in the range of 1-3m away from the exhaust especially at Y=4m. It is suggested to close the ramps to B2 level completely to minimize short-circuiting of entrained air from below. Figure 3. Concentration distribution in the normal direction from the center of Exhaust α Induction by high-speed air jets It is desirable to pressurize the platform area slightly so that contaminated air should displace away from passengers. The horizontal supply air jets of high velocity generate entrainment from surroundings. In Fig. 4, it is interesting to notice a region of negative air velocity for Z=16m. Because of the high speed discharges from the jets, the air between the jets can flow in the opposite direction towards the platform area to satisfy flow continuity. As the air jets move toward the exhausts (as Z increases), two jets are merged together eventually. Some of the horizontal jet are impacted on the crossing beams and deflected. They do not contribute to push the contaminated air to exhaust area effectively. It is suggested to discharge supply air in the downward vertical direction with increased grille areas. Decreased face velocity would help to reduce thermal discomfort by draft also. Figure 4. Velocity profile in the x-direction between two horizontal supply jets (Y=1.0m). Distraction of thermal plume by long fans Hot exhaust gases from a tail pipe are discharged horizontally, but have slight upward buoyancy. One of the trajectories of the exhaust plumes is shown in Fig. 5 for bus #19 idling at the platform. The dispersion of an exhaust gas depends on the surrounding airflow conditions. However, it is found, on the average, that the exhaust plumes reach the ceiling between 8-13m from the bus rears. The existing long fans distract the upcoming plumes. The locations of the long fans are required to shift in the z-direction by 6-7m approximately to push effectively the emission plumes. With the shifted long fans, emission plumes no longer 341

6 rise to the ceiling but move horizontally to exhausts, except the plumes from bus #14-#19. Ceiling exhausts, if needed, are suggested to install at approximately 10m from the rear of the buses to capture the rising plume effectively. Figure 5. An emission plume from a bus tail pipe Intrusion of contaminated air to waiting areas The original design intends to neutralize the pressure in the underground terminal by balancing supply and exhaust airflow rates. In winter, the pressure is negative in the basement of the shopping building due to the stack effect. The contaminated terminal air can be entrained into the waiting area through the cracks between doors. The underground terminal should be depressurized. Moreover, it is suggested to use swing doors to minimize the airflow exchange between the terminal building and the shopping building. Overall exhaust effectiveness Results on overall exhaust performances are compared in Table 2. The current TAB condition shows the worst effectiveness. The design condition and the modified condition 1 show similar effectiveness. The effectiveness is greatly improved up to 128.5% for the modified condition 2. Note the exhaust effectiveness is 100% for a completely mixed condition. Table 2. Overall exhaust effectiveness for the conditions considered. Design Condition T.A.B. Condition Modified Condition 1 Modified Condition 2 Mean concentration at exhaust 1.06x x x x10-4 Space average concentration 2.30x x x x10-3 Mean residual-life-time of exhaust (sec) Nominal time constant (sec) Exhaust effectiveness (%) ACKNOWLEDGEMENTS This paper is an extension of the project funded by the Korea Real Estate Trust. The authors also would like to express thanks to the persons participated in the project, especially Dr. H.J. Shin, Prof. J.O. Yoo, and Prof S.K. Sung. REFERENCES ASHRAE Fundamentals-Handbook, Atlanta: American Society of Heating, Refrigerating, Airconditioning Engineers, Inc. Etheridge DW, and Sandberg M Building Ventilation: Theory and Measurement. Chichester: John Wiley and Sons. Han H Evaluating Exhaust Effectiveness using Inverse-Flow Calculation Method, Proceedings of 5 th Int. Conference on Air Distribution in Rooms Room Vent 96, pp Yokohama: Room Vent 96. SAREK Problem Identifications and Remediation Suggestions on Ventilation Systems of Sung- Nam Passenger Bus Terminal Complex Underground Platforms. Final Report: Seoul: The Society of Air-conditioning, Refrigerating Engineers of Korea. 342

ENERGY EFFICIENT AIR QUALITY CONTROL IN LABORATORIES USING BENCH EXHAUSTS

ENERGY EFFICIENT AIR QUALITY CONTROL IN LABORATORIES USING BENCH EXHAUSTS ENERGY EFFICIENT AIR QUALITY CONTROL IN LABORATORIES USING BENCH EXHAUSTS Farhad Memarzadeh 1, Jane Jiang 2, and Andy Manning 2 1 PhD, PE, National Institutes of Health, Bethesda, MD, USA 2 PhD, Flomerics,

More information

A study on the effect of the airflow rate of the ceiling type air-conditioner on the ventilation performance

A study on the effect of the airflow rate of the ceiling type air-conditioner on the ventilation performance A study on the effect of the airflow rate of the ceiling type air-conditioner on the ventilation performance Kwang-Chul Noh 1, Chang-Woo Han 2 and Myung-Do Oh 2 1 Institute of Industrial Technology, University

More information

PERFORMANCE EVALUATION OF TWO AIR DISTRIBUTION SYSTEMS. T Karimipanah 1 and H B Awbi 2

PERFORMANCE EVALUATION OF TWO AIR DISTRIBUTION SYSTEMS. T Karimipanah 1 and H B Awbi 2 PERFORMANCE EVALUATION OF TWO AIR DISTRIBUTION SYSTEMS T Karimipanah 1 and H B Awbi 2 1 Air Innovation AB, Sweden 2 University of Reading, UK ABSTRACT This paper focuses on evaluating the performance of

More information

Performance Improvement Analysis for a Negative-pressurized Biosafety Level Laboratory

Performance Improvement Analysis for a Negative-pressurized Biosafety Level Laboratory Performance Improvement Analysis for a Negative-pressurized Biosafety Level Laboratory F.J. Wang* and J.S. Huang 1 Department of Refrigeration, Air Conditioning and Energy Engineering, National Chin-Yi

More information

Influence of Stack Effect on Ventilation in a High-rise Residential Building

Influence of Stack Effect on Ventilation in a High-rise Residential Building Influence of Stack Effect on Ventilation in a High-rise Residential Building Jungmin Seo 1, a, Sungmin Yoon 1, b, Joonghoon Lee 2, c, Doosam Song 3, d, Shinsuke Kato 4, e 1 Graduate School, Sungkyunkwan

More information

DISPLACEMENT VENTILATION

DISPLACEMENT VENTILATION DISPLACEMENT VENTILATION D3 OVERVIEW The fundamental approach to displacement ventilation utilizes the natural buoyancy forces created by the convective flows from heat sources in the space. As supply

More information

E/V Shaft Cooling Method as a Stack Effect Countermeasure in Tall Buildings

E/V Shaft Cooling Method as a Stack Effect Countermeasure in Tall Buildings ctbuh.org/papers Title: Authors: Subject: Keywords: E/V Shaft Cooling Method as a Stack Effect Countermeasure in Tall Buildings Joonghoon Lee, Samsung C&T Corporation Doosam Song, Sungkyunkwan University

More information

FANROOMLESS VENTILATION SYSTEM FOR AN UNDERGROUND PARKING LOT

FANROOMLESS VENTILATION SYSTEM FOR AN UNDERGROUND PARKING LOT FANROOMLESS VENTILATION SYSTEM FOR AN UNDERGROUND PARKING LOT Eon Ku Rhee 1, Seong Hwan Yi 2,* 1Ph.D. Professor of Architecture, Chung-Ang University, Seoul, Korea 2 Ph.D. Candidate of Architecture, Chung-Ang

More information

On the performance of the Stravent ventilation system in an office space Numerical and experimental investigations

On the performance of the Stravent ventilation system in an office space Numerical and experimental investigations On the performance of the Stravent ventilation system in an office space Numerical and experimental investigations S. Janbakhsh 1, 2 and.b. Moshfegh 1, 2 1 Division of Energy and Mechanical Engineering,

More information

INFLUENCE ANALYSIS OF STACK EFFECT ON ODOR DISPERSION FROM UNIT TO CORE IN THE HIGH-RISE RESIDENTIAL BUILDINGS. South Korea METHOD

INFLUENCE ANALYSIS OF STACK EFFECT ON ODOR DISPERSION FROM UNIT TO CORE IN THE HIGH-RISE RESIDENTIAL BUILDINGS. South Korea METHOD INFLUENCE ANALYSIS OF STACK EFFECT ON ODOR DISPERSION FROM UNIT TO CORE IN THE HIGH-RISE RESIDENTIAL BUILDINGS Hyesoo Suh 1, Byungseon Sean Kim 2, Taeyeon Kim 2, and Jeonghee Lim 2 1 Research and Engineering

More information

CFD Study on Inter-Action between NonIsothermal Airflow and Buoyancy Plume in an AirConditioned Space

CFD Study on Inter-Action between NonIsothermal Airflow and Buoyancy Plume in an AirConditioned Space Wang et al. CFD Letters www.cfdl.issres.net Vol. 2(3) 2010 Vol. 2(3) September 2010 CFD Study on Inter-Action between NonIsothermal Airflow and Buoyancy Plume in an AirConditioned Space Xin. Wang1C and

More information

Analysis of Uniformity and Energy Consumption in. Supermarket installed DurkeeSox Air Dispersion System. with PE Air Dispersion Model

Analysis of Uniformity and Energy Consumption in. Supermarket installed DurkeeSox Air Dispersion System. with PE Air Dispersion Model Analysis of Uniformity and Energy Consumption in Supermarket installed DurkeeSox Air Dispersion System with PE Air Dispersion Model Summary: Taking partial area of a large supermarket for example, to simulate

More information

A new proposal of a control method for the stack effect in super tall buildings: E/L Shaft cooling system

A new proposal of a control method for the stack effect in super tall buildings: E/L Shaft cooling system A new proposal of a control method for the stack effect in super tall buildings: E/L Shaft cooling system Hyun Woo Lim 1, a, June ho Lee 1, b, Doo Sam Song 2, c, Joong hoon Lee 3, d, Holger Wallbaum 4,

More information

Energy Consumption and Indoor Environment Predicted by a Combination of Computational Fluid Dynamics and Building Energy Performance Simulation

Energy Consumption and Indoor Environment Predicted by a Combination of Computational Fluid Dynamics and Building Energy Performance Simulation Aalborg Universitet Energy Consumption and Indoor Environment Predicted by a Combination of Computational Fluid Dynamics and Building Energy Performance Simulation Nielsen, Peter Vilhelm Published in:

More information

EXPERIMENTAL AND NUMERICAL STUDY OF SMOKE CONDITIONS IN AN ATRIUM WITH MECHANICAL EXHAUST

EXPERIMENTAL AND NUMERICAL STUDY OF SMOKE CONDITIONS IN AN ATRIUM WITH MECHANICAL EXHAUST , Volume 1, Number 3, p.183-187, 1999 EXPERIMENTAL AND NUMERICAL STUDY OF SMOKE CONDITIONS IN AN ATRIUM WITH MECHANICAL EXHAUST G.V. Hadjisophocleous and G. Lougheed Fire Risk Management Program, Institute

More information

Analysis of Lecturing Room using Computational Fluid Dynamics Natural and Forced Ventilation

Analysis of Lecturing Room using Computational Fluid Dynamics Natural and Forced Ventilation Analysis of Lecturing Room using Computational Fluid Dynamics Natural and Forced Ventilation 1. Md Atiqur Rahman, 2. Narahari. G. A 1,2. Department of Mechanical Engineering, BTL institution of Technology

More information

Ventilation performance measurement of a decentralized mechanical system with heat recovery using Tracer gas decay method

Ventilation performance measurement of a decentralized mechanical system with heat recovery using Tracer gas decay method Ventilation performance measurement of a decentralized mechanical system with heat recovery using Tracer gas decay method Youness Ajaji 1,*, Philippe André 1 1 University of Liege, Arlon Campus Environnement,

More information

OPENING DESIGN TO IMPROVE THE NATURAL VENTILATION PERFORMANCE OF HIGH-RISE RESIDENTIAL BUILDINGS

OPENING DESIGN TO IMPROVE THE NATURAL VENTILATION PERFORMANCE OF HIGH-RISE RESIDENTIAL BUILDINGS OPENING DESIGN TO IMPROVE THE NATURAL VENTILATION PERFORMANCE OF HIGH-RISE RESIDENTIAL BUILDINGS Cho Rong Kim 1, Ga Young Cho 1, Sun Woo Lee 1, Myoung Souk Yeo 2, and Kwang Woo Kim 2 1 Department of Architecture,

More information

Comparison of Standards Requirements with CFD Simulations for Determining Sizes of Hazardous Locations in Hydrogen Energy Station

Comparison of Standards Requirements with CFD Simulations for Determining Sizes of Hazardous Locations in Hydrogen Energy Station Comparison of Standards Requirements with CFD Simulations for Determining Sizes of Hazardous Locations in Hydrogen Energy Station Abstract Andrei TCHOUVELEV, Gary HOWARD and Vladimir AGRANAT Stuart Energy

More information

AIRFLOW PATTERNS AND STACK PRESSURE SIMULATION IN A HIGH RISE RESIDENTIAL BUILDING LOCATED IN SEOUL

AIRFLOW PATTERNS AND STACK PRESSURE SIMULATION IN A HIGH RISE RESIDENTIAL BUILDING LOCATED IN SEOUL 92 AIRFLOW PATTERNS AND STACK PRESSURE SIMULATION IN A HIGH RISE RESIDENTIAL BUILDING LOCATED IN SEOUL Khoukhi Maatouk Abstract Buoyancy forces due to air density difference between outdoor air and indoor

More information

CFD SIMULATION OF A NOVEL VENTILATION SYSTEM OF SUBWAY STATION IN HARBIN

CFD SIMULATION OF A NOVEL VENTILATION SYSTEM OF SUBWAY STATION IN HARBIN CFD SIMULATION OF A NOVEL VENTILATION SYSTEM OF SUBWAY STATION IN HARBIN Xiyan Guan 1, Yiqiang Jiang 1,and Yang Yao 1 1 School of Municipal & Environmental Engineering, Harbin Institute of Technology,

More information

Investigation of air quality, comfort parameters and effectiveness for two floor level air supply systems in classrooms

Investigation of air quality, comfort parameters and effectiveness for two floor level air supply systems in classrooms Investigation of air quality, comfort parameters and effectiveness for two floor level air supply systems in classrooms T. Karimipanah 1,2,3, H.B. Awbi 2, M. Sandberg 3 and C. Blomqvist 3 1 Fresh AB, Sweden,

More information

Numerical simulation of inter-flat pollutant dispersion routes and cross-contamination risk in high-rise residential buildings Di Mu, Naiping Gao* Ins

Numerical simulation of inter-flat pollutant dispersion routes and cross-contamination risk in high-rise residential buildings Di Mu, Naiping Gao* Ins Numerical simulation of inter-flat pollutant dispersion routes and cross-contamination risk in high-rise residential buildings Di Mu, Naiping Gao* Institute of Thermal and Environment Engineering, School

More information

A COMPARATIVE STUDY OF DIFFERENT AIR DISTRIBUTION SYSTEMS IN A CLASSROOM

A COMPARATIVE STUDY OF DIFFERENT AIR DISTRIBUTION SYSTEMS IN A CLASSROOM ROOMVENT 2000, Vol. 2, pp. 1013-1018, Reading, UK, 9-12 July 2000. A COMPARATIVE STUDY OF DIFFERENT AIR DISTRIBUTION SYSTEMS IN A CLASSROOM T. Karimipanah 1, M. Sandberg 2, and H.B. Awbi 3 1 Air Innovation

More information

Indoor Air 2005, Beijing, China Effectiveness of confluent jets ventilation system for classrooms

Indoor Air 2005, Beijing, China Effectiveness of confluent jets ventilation system for classrooms Effectiveness of confluent jets ventilation system for classrooms T. Karimipanah 1, H.B. Awbi 2, C. Blomqvist 3 and M. Sandberg 3 ABSTRACT 1 Fresh AB, Sweden, taghi.k@comhem.se 2 University of Reading,

More information

NUMERICAL MODELING OF THE INFLUENCE OF ANGLE ADJUSTMENT OF A/C DIFFUSER VANES ON THERMAL COMFORT IN A COMPUTER ROOM

NUMERICAL MODELING OF THE INFLUENCE OF ANGLE ADJUSTMENT OF A/C DIFFUSER VANES ON THERMAL COMFORT IN A COMPUTER ROOM Seventh International IBPSA Conference Rio de Janeiro, Brazil August 13-15, 2001 NUMERICAL MODELING OF THE INFLUENCE OF ANGLE ADJUSTMENT OF A/C DIFFUSER VANES ON THERMAL COMFORT IN A COMPUTER ROOM Jan

More information

NUMERICAL SIMULATIONS OF THE NATURAL VENTILATION DESIGN MIX OF ELEMENTARY SCHOOL CLASSROOMS

NUMERICAL SIMULATIONS OF THE NATURAL VENTILATION DESIGN MIX OF ELEMENTARY SCHOOL CLASSROOMS NUMERICAL SIMULATIONS OF THE NATURAL VENTILATION DESIGN MIX OF ELEMENTARY SCHOOL CLASSROOMS Hsin-hung Wu 1, Fu-Jen Wang 2, Che-ming Chiang 1 and Chi-ming Lai 3* 1 Department of Architecture, National Cheng-Kung

More information

LOCAL VENTILATION SYSTEMS: SOME INVESTIGATIONS ABOUT COMFORT LEVELS AND ENERGY DEMANDS

LOCAL VENTILATION SYSTEMS: SOME INVESTIGATIONS ABOUT COMFORT LEVELS AND ENERGY DEMANDS LOCAL VENTILATION SYSTEMS: SOME INVESTIGATIONS ABOUT COMFORT LEVELS AND ENERGY DEMANDS Elena Buchberger - ebuch@iuav.it Luca Porciani, porciani@iuav.it Fabio Peron, fperon@iuav.it Universita IUAV di Venezia,

More information

THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING. Gang Wang, Yafeng Hu, and Songtao Hu

THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING. Gang Wang, Yafeng Hu, and Songtao Hu THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING Gang Wang, Yafeng Hu, and Songtao Hu School of Environmental & Municipal Engineering, Qingdao Technological University, Qingdao

More information

These systems are offered an alternative to overhead, mixing ventilation (MV), systems. Due to their potential advantages which are [1]:

These systems are offered an alternative to overhead, mixing ventilation (MV), systems. Due to their potential advantages which are [1]: Prediction of thermal comfort, IAQ, and Energy consumption in a dense occupancy environment with the under floor air distribution system Ghassem Heidarinejad 1, Mohammad Hassan Fathollahzadeh 2, Hadi Pasdarshahri

More information

The Pennsylvania State University. The Graduate School. Department or Architectural Engineering THERMAL AND VENTILATION PERFORMANCE

The Pennsylvania State University. The Graduate School. Department or Architectural Engineering THERMAL AND VENTILATION PERFORMANCE The Pennsylvania State University The Graduate School Department or Architectural Engineering THERMAL AND VENTILATION PERFORMANCE OF COMBINED PASSIVE CHILLED BEAM DISPLACEMENT VENTILATION SYSTEMS A Thesis

More information

ADVANCES in NATURAL and APPLIED SCIENCES

ADVANCES in NATURAL and APPLIED SCIENCES ADVANCES in NATURAL and APPLIED SCIENCES ISSN: 1995-0772 Published BYAENSI Publication EISSN: 1998-1090 http://www.aensiweb.com/anas 2017 May 11(7): pages 910-918 Open Access Journal Analysis Of Ventilation

More information

WIND FLOW IN THE RECESSED CAVITIES OF A TALL

WIND FLOW IN THE RECESSED CAVITIES OF A TALL The Seventh Asia-Pacific Conference on Wind Engineering, November 8-12, 2009, Taipei, Taiwan WIND FLOW IN THE RECESSED CAVITIES OF A TALL BUILDING Charles C.K. Cheng 1, K.M. Lam 2 and Andrew Y.T. Leung

More information

ASSESSMENT OF AIR CHANGE RATE AND CONTRIBUTION RATIO IN IDEALIZED URBAN CANOPY LAYERS BY TRACER GAS SIMULATIONS

ASSESSMENT OF AIR CHANGE RATE AND CONTRIBUTION RATIO IN IDEALIZED URBAN CANOPY LAYERS BY TRACER GAS SIMULATIONS Topic B4: Ventilation ASSESSMENT OF AIR CHANGE RATE AND CONTRIBUTION RATIO IN IDEALIZED URBAN CANOPY LAYERS BY TRACER GAS SIMULATIONS Qun WANG 1, Mats SANDBERG 2, Jian HANG 1* 1 Department of Atmospheric

More information

Air Distribution and Microenvironment Evaluation of a Desktop Task. Conditioning System 1

Air Distribution and Microenvironment Evaluation of a Desktop Task. Conditioning System 1 Air Distribution and Microenvironment Evaluation of a Desktop Task Conditioning System 1 Guozhong Zheng School of Energy and Power Engineering, North China Electric Power University Baoding, P.R. China,

More information

CFD and Wind Tunnel Study of the Performance of a Multi- Directional Wind Tower with Heat Transfer Devices

CFD and Wind Tunnel Study of the Performance of a Multi- Directional Wind Tower with Heat Transfer Devices Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (2015 ) 1692 1697 The 7 th International Conference on Applied Energy ICAE2015 CFD and Wind Tunnel Study of the Performance of

More information

USE OF MULTI-ZONE AIR FLOW SIMULATIONS TO EVALUATE A HYBRID VENTILATION SYSTEM. Åke Blomsterberg 1, Tomas Johansson 1.

USE OF MULTI-ZONE AIR FLOW SIMULATIONS TO EVALUATE A HYBRID VENTILATION SYSTEM. Åke Blomsterberg 1, Tomas Johansson 1. Ninth International IBPSA Conference Montréal, Canada August 15-18, 25 USE OF MULTI-ZONE AIR FLOW SIMULATIONS TO EVALUATE A HYBRID VENTILATION SYSTEM Åke Blomsterberg 1, Tomas Johansson 1 1 WSP Environmental,

More information

Numerical Analysis of Ventilation Effectiveness in Occupied Zones for Various Industrial Ventilation Systems

Numerical Analysis of Ventilation Effectiveness in Occupied Zones for Various Industrial Ventilation Systems Numerical Analysis of Ventilation Effectiveness in Occupied Zones for Various Industrial Ventilation Systems Seohiro Kikuchi a *, Kazuhide Ito b, Nobuyuki Kobayashi c a Graduate Student, Tokyo Polytechnic

More information

A STUDY OF CROSS CONTAMINATION OF IN-SUITE VENTILATION SYSTEMS USED IN MULTI-UNIT RESIDENTIAL BUILDINGS

A STUDY OF CROSS CONTAMINATION OF IN-SUITE VENTILATION SYSTEMS USED IN MULTI-UNIT RESIDENTIAL BUILDINGS A STUDY OF CROSS CONTAMINATION OF IN-SUITE VENTILATION SYSTEMS USED IN MULTI-UNIT RESIDENTIAL BUILDINGS C.A. Parker, K.D. Pressnail, M.F. Touchie, D. DeRose, and S. Dedesko ABSTRACT Complaints of cross

More information

Indoor air quality in a bus

Indoor air quality in a bus Safety and Security Engineering V 749 Indoor air quality in a bus A. Gajewski Department of Heat Engineering, Faculty of Civil Engineering and Environmental Engineering, Bialystok University of Technology,

More information

FEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF

FEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF FEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF Oliver Baumann 1, and Claudius Reiser 1/2 1 Ebert & Baumann Consulting Engineers, Washington, D.C. 2 Ebert-Ingenieure GmbH &Co. KG, Munich,

More information

Validation of Numerical Modeling of Air Infiltration through Building Entrance Doors

Validation of Numerical Modeling of Air Infiltration through Building Entrance Doors Validation of Numerical Modeling of Air Infiltration through Building Entrance Doors Sherif Goubran, Dahai Qi, Wael F. Saleh, Liangzhu (Leon) Wang, Radu Zmeureanu Department of Building, Civil and Environmental

More information

Floor-Supply Displacement Ventilation in a Small Office

Floor-Supply Displacement Ventilation in a Small Office Kobayashi, N. and Chen, Q. 2003. Floor-supply displacement ventilation in a small office, Indoor and Built Environment, 12(4), 281-292. Floor-Supply Displacement Ventilation in a Small Office Nobukazu

More information

XVII th World Congress of the International Commission of Agricultural and Biosystems Engineering (CIGR)

XVII th World Congress of the International Commission of Agricultural and Biosystems Engineering (CIGR) XVII th World Congress of the International Commission of Agricultural and Biosystems Engineering (CIGR) Hosted by the Canadian Society for Bioengineering (CSBE/SCGAB) Québec City, Canada June 13-17, 2010

More information

3D Simulation of a fire inside a river tunnel and optimisation of the ventilation using Computational Fluid Dynamics

3D Simulation of a fire inside a river tunnel and optimisation of the ventilation using Computational Fluid Dynamics 3D Simulation of a fire inside a river tunnel and optimisation of the ventilation using Computational Fluid Dynamics Authors: B. TRUCHOT, A. TRIPATHI Fluidyn-France Abstract CFD simulation is used to predict

More information

Guide to air change effectiveness

Guide to air change effectiveness Guide to air change effectiveness Kemal Gungor, M.AIRAH, of Norman Disney & Young Abstract Green Star rating under the Green Building Council of Australia is increasingly considered and demanded by the

More information

Numerical Modeling of Buoyancy-driven Natural Ventilation in a Simple Three Storey Atrium Building

Numerical Modeling of Buoyancy-driven Natural Ventilation in a Simple Three Storey Atrium Building Numerical Modeling of Buoyancy-driven Natural Ventilation in a Simple Three Storey Atrium Building Shafqat Hussain and Patrick H. Oosthuizen Department of Mechanical and Materials Engineering, Queen s

More information

Using CFD to Wring Out Energy Efficiency in Laboratory Settings

Using CFD to Wring Out Energy Efficiency in Laboratory Settings Using CFD to Wring Out Energy Efficiency in Laboratory Settings Energy Conservation Strategies for Cornell University Laboratories Primary focus is on controls to reduce outside air use Occupancy sensors

More information

An Analytical Solution for Steady Temperature Profiles in a Vertically Stratified Environment

An Analytical Solution for Steady Temperature Profiles in a Vertically Stratified Environment Modern Applied Science; Vol. 8, No. 4; 2014 ISSN 1913-1844 E-ISSN 1913-1852 Published by Canadian Center of Science and Education An Analytical Solution for Steady Temperature Profiles in a Vertically

More information

Computational Fluid Dynamics and Building Energy Performance Simulation Nielsen, Peter Vilhelm; Tryggvason, T.

Computational Fluid Dynamics and Building Energy Performance Simulation Nielsen, Peter Vilhelm; Tryggvason, T. Aalborg Universitet Computational Fluid Dynamics and Building Energy Performance Simulation Nielsen, Peter Vilhelm; Tryggvason, T. Published in: Proceedings of ROOMVENT '98 : Sixth International Conference

More information

Analysis of Flue Gas Flow Behavior in Economiser Duct Using Cfd

Analysis of Flue Gas Flow Behavior in Economiser Duct Using Cfd Analysis of Flue Gas Flow Behavior in Economiser Duct Using Cfd Anand Kumar S Malipatil 1, Shivaraj 2 Department of Thermal Power Engineering, VTU-Gulbarga Abstract-- Energy saving and efficiency are the

More information

Building and Environment

Building and Environment Building and Environment 45 (2010) 1993e2001 Contents lists available at ScienceDirect Building and Environment journal homepage: www.elsevier.com/locate/buildenv The spatial distribution of carbon dioxide

More information

Live Transportation Research and Improvement Initiatives

Live Transportation Research and Improvement Initiatives Live Transportation Research and Improvement Initiatives MLF Transport Working Committee As a major chicken processor in Canada, MLF recognizes the critical need to identify improved live bird transportation

More information

Findings of Field Survey for Thermal Comfort and Ventilation in US Office Buildings

Findings of Field Survey for Thermal Comfort and Ventilation in US Office Buildings Findings of Field Survey for Thermal Comfort and Ventilation in US Office Buildings Liangcai Tan 1, Samir Moujaes, HDR Inc. University of Nevada Las Vegas SUMMARY This paper presents the measured data

More information

Proceedings of Clima 2007 WellBeing Indoors

Proceedings of Clima 2007 WellBeing Indoors Experimental Study of Thermal Environment and Comfort in an Office Room with a Variable Air Volume (VAV) System under Low Supply Air Temperature Conditions Mari-Liis Maripuu Chalmers University of Technology,

More information

Faculty of Mechanical Engineering, Universiti Teknologi Malaysia, Skudai, Johor Bahru, Malaysia

Faculty of Mechanical Engineering, Universiti Teknologi Malaysia, Skudai, Johor Bahru, Malaysia A CFD SIMULATION OF INDOOR AIR CONTAMINANT ON VENTILATION SYSTEM IN A BUS PASSENGER COMPARTMENT Noor Emilia Ahmad Shafie 1, a, Haslinda Mohamed Kamar 2, b * and Nazri Kamsah 3, c 1,2,3 Faculty of Mechanical

More information

UNDERFLOOR AIR DISTRIBUTION INTEGRATED WITH AN INDIRECT AND DIRECT EVAPORATIVE COOLING ASSISTED 100% OUTDOOR AIR SYSTEM

UNDERFLOOR AIR DISTRIBUTION INTEGRATED WITH AN INDIRECT AND DIRECT EVAPORATIVE COOLING ASSISTED 100% OUTDOOR AIR SYSTEM UNDERFLOOR AIR DISTRIBUTION INTEGRATED WITH AN INDIRECT AND DIRECT EVAPORATIVE COOLING ASSISTED 100% OUTDOOR AIR SYSTEM YJ Seok, HJ Cho, SK Han and JW Jeong Department of Architectural Engineering, Sejong

More information

Chapter 6. Space heating load

Chapter 6. Space heating load Chapter 6 Space heating load 1 Outdoor Design Conditions Heating systems should provide just enough heat to match the heat loss from the structure. Local knowledge should be obtained for design conditions.

More information

Thermal performance of a closed wet cooling tower for chilled ceilings: measurement and CFD simulation

Thermal performance of a closed wet cooling tower for chilled ceilings: measurement and CFD simulation INTERNATIONAL JOURNAL OF ENERGY RESEARCH Int. J. Energy Res. 2000; 24:1171}1179 Thermal performance of a closed wet cooling tower for chilled ceilings: measurement and CFD simulation Sa!a Ri!at*, Armando

More information

Thermal comfort study of a hawker center in Singapore

Thermal comfort study of a hawker center in Singapore September 004 Page of 6 Thermal comfort study of a hawker center in Singapore Song Jiafang, Wong Nyuk Hien, Agustinus Djoko Istiadji Department of Building, School of Design and Environment, National University

More information

Postprint.

Postprint. http://www.diva-portal.org Postprint This is the accepted version of a paper presented at 13th International Conference on Indoor Air Quality and Climate, July 7-12, 2014, Hong Kong. Citation for the original

More information

INNOVATIONS IN VENTILATION TECHNOLOGY 21ST ANNUAL INTERNATIONAL AIVC CONFERENCE THE HAGUE, NETHERLANDS, SEPTEMBER 2000

INNOVATIONS IN VENTILATION TECHNOLOGY 21ST ANNUAL INTERNATIONAL AIVC CONFERENCE THE HAGUE, NETHERLANDS, SEPTEMBER 2000 INNOVATIONS IN VENTILATION TECHNOLOGY 21ST ANNUAL INTERNATIONAL AIVC CONFERENCE THE HAGUE, NETHERLANDS, 26-29 SEPTEMBER 2000 Impact of Ventilator Parameters on System Energy Consumption Dipak J. Shah Senior

More information

Energy efficient thermal comfort. Bin Yang Assistant Professor (Umeå University) Mar 24 th, 2017

Energy efficient thermal comfort. Bin Yang Assistant Professor (Umeå University) Mar 24 th, 2017 Energy efficient thermal comfort Bin Yang Assistant Professor (Umeå University) Mar 24 th, 2017 Outlines 1 Mixing ventilation (MV) 2 Displacement ventilation (DV) and underfloor air distribution (UFAD)

More information

NUMERICAL STUDY ON AIRFLOW IN AN OFFICE ROOM WITH A DISPLACEMENT VENTILATION SYSTEM Yukihiro Hashimoto 1 1

NUMERICAL STUDY ON AIRFLOW IN AN OFFICE ROOM WITH A DISPLACEMENT VENTILATION SYSTEM Yukihiro Hashimoto 1 1 Ninth International IBPSA Conference Montréal, Canada August 5-8, 5 NUMERICAL STUDY ON AIRFLOW IN AN OFFICE ROOM WITH A DISPLACEMENT VENTILATION SYSTEM Yukihiro Hashimoto Polytechnic University, Dept.

More information

Sensitivity Analysis of Personal Exposure Assessment Using a Computer Simulated Person Brohus, Henrik; Jensen, H. K.

Sensitivity Analysis of Personal Exposure Assessment Using a Computer Simulated Person Brohus, Henrik; Jensen, H. K. Aalborg Universitet Sensitivity Analysis of Personal Exposure Assessment Using a Computer Simulated Person Brohus, Henrik; Jensen, H. K. Published in: Healthy Buildings 2009 Publication date: 2009 Document

More information

Federation of European Heating, Ventilation and Air-conditioning Associations

Federation of European Heating, Ventilation and Air-conditioning Associations Federation of European Heating, Ventilation and Air-conditioning Associations Address: Rue Washington 40 1050 Brussels Belgium www.rehva.eu info@rehva.eu Tel: +32 2 514 11 71 Fax: +32 2 512 90 62 Use of

More information

Evaluating Alternative Fume Hood System Technologies Using Advanced Building Simulation

Evaluating Alternative Fume Hood System Technologies Using Advanced Building Simulation Evaluating Alternative Fume Hood System Technologies Using Advanced Building Simulation William J. Kosik, P.E., C.E.M. 1 Karl Aveard, AIA Associate 2 Heather R. Beaudoin, P.E., C.E.M. 3 Erik L. Olsen 3

More information

ENERGY SIMULATION AND ANALYSIS OF AN INTERMITTENT VENTILATION SYSTEM UNDER TWO CLIMATES

ENERGY SIMULATION AND ANALYSIS OF AN INTERMITTENT VENTILATION SYSTEM UNDER TWO CLIMATES ENERGY SIMULATION AND ANALYSIS OF AN INTERMITTENT VENTILATION SYSTEM UNDER TWO CLIMATES Alan Kabanshi, Arman Ameen, Bin Yang, Hans Wigö, Mats Sandberg CORRESPONDENCE ADDRESSES: Alan Kabanshi, Ph.D., University

More information

Validation of a Coupled Multizone and CFD Program for Building Airflow and Contaminant Transport Simulations

Validation of a Coupled Multizone and CFD Program for Building Airflow and Contaminant Transport Simulations Wang, L. and Chen, Q. 2007. Validation of a coupled multizone and CFD program for building airflow and contaminant transport simulations, HVAC&R Research, 13(2), 267-281. Validation of a Coupled Multizone

More information

EXPERIMENTAL INVESTIGATION OF THERMAL AND VENTILATION ANALYSIS FOR STRATUM VENTILATION CFD STUDY

EXPERIMENTAL INVESTIGATION OF THERMAL AND VENTILATION ANALYSIS FOR STRATUM VENTILATION CFD STUDY e-issn 2455 1392 Volume 2 Issue 4, April 2016 pp. 202-207 Scientific Journal Impact Factor : 3.468 http://www.ijcter.com EXPERIMENTAL INVESTIGATION OF THERMAL AND VENTILATION ANALYSIS FOR STRATUM VENTILATION

More information

A Sensitivity Analysis on Mixing Energy Loss in Air-Conditioned Rooms by Using CFD

A Sensitivity Analysis on Mixing Energy Loss in Air-Conditioned Rooms by Using CFD A Sensitivity Analysis on Mixing Energy Loss in Air-Conditioned Rooms by Using CFD S. Iizuka 1, S. Shiba 1,*, M. Sasaki 1, M. Okumiya 1 1 Nagoya University, Nagoya, Japan ABSTRACT In some office buildings,

More information

ENGINEERING UPDATE JULY VOLUME 11 THIS PACKAGE INCLUDES A COLLECTION OF ARTICLES FROM VOLUME 11 OF THE JULY 2013 ENGINEERING UPDATE.

ENGINEERING UPDATE JULY VOLUME 11 THIS PACKAGE INCLUDES A COLLECTION OF ARTICLES FROM VOLUME 11 OF THE JULY 2013 ENGINEERING UPDATE. ENGINEERING UPDATE JULY 2013 - VOLUME 11 THIS PACKAGE INCLUDES A COLLECTION OF ARTICLES FROM VOLUME 11 OF THE JULY 2013 ENGINEERING UPDATE. TABLE OF CONTENTS: Terminal Unit Acoustical Considerations...

More information

Terminal. 3 Las Vegas, NV

Terminal. 3 Las Vegas, NV McCarran International Airport Terminal 3 Thesiss Proposal Mechanical Systems Project Proposal December 18, 2007 Prepared By: Jason A. Witterman Faculty Advisor: Dr. William Bahnfleth, Ph.D., P..E. Table

More information

Thermal Management of Densely-packed EV Battery Set

Thermal Management of Densely-packed EV Battery Set EVS28 KINTEX, Korea, May 3-6, 2015 Thermal Management of Densely-packed EV Battery Set Abstract Z. Lu 1, X.Z. Meng 1, W.Y. Hu 2, L.C. Wei 3, L.Y. Zhang 1, L.W. Jin 1* 1 Building Environment and Equipment

More information

DESIGN ANALYSIS OF AN OFFICE VENTILATION SYSTEM VIA CALIBRATED CFD APPLICATION

DESIGN ANALYSIS OF AN OFFICE VENTILATION SYSTEM VIA CALIBRATED CFD APPLICATION DESIGN ANALYSIS OF AN OFFICE VENTILATION SYSTEM VIA CALIBRATED CFD APPLICATION M. Taheri, M. Schuss, A. Fail, and A. Mahdavi Department of Building Physics and Building Ecology, Vienna University of Technology,

More information

Carbon Monoxide Dispersion in Enclosed Car Parks: Pollutant Source Modelling Methods. Jason Gaekwad 1 1. Mott MacDonald, Melbourne, Australia

Carbon Monoxide Dispersion in Enclosed Car Parks: Pollutant Source Modelling Methods. Jason Gaekwad 1 1. Mott MacDonald, Melbourne, Australia Carbon Monoxide Dispersion in Enclosed Car Parks: Pollutant Source Modelling Methods Jason Gaekwad 1 1 Mott MacDonald, Melbourne, Australia Abstract Adequate ventilation of enclosed car parking areas is

More information

Development of a straightforward method of estimating ageof-air

Development of a straightforward method of estimating ageof-air Ref: C0564 Development of a straightforward method of estimating ageof-air using CFD Sang-yeon Lee, In-bok Lee and Se-jun Park, Department of Rural Systems Engineering, Research Institute for Agriculture

More information

Numerical and Experimental Modeling of Producer Gas Carburettor

Numerical and Experimental Modeling of Producer Gas Carburettor Numerical and Experimental Modeling of Producer Gas Carburettor S.S.Vinay l, S.D.Ravi 2, G PremaKumar 3 and N.K.S.Rajan 4 l M.E Student, Bangalore University, Bangalore. 2 Project Assistant, CGPL, Dept

More information

DYNAMIC ENERGY MODELING OF AN EXPERIMENTAL BUILDING EQUIPPED WITH AN UNDERFLOOR AIR DISTRIBUTION (UFAD) SYSTEM

DYNAMIC ENERGY MODELING OF AN EXPERIMENTAL BUILDING EQUIPPED WITH AN UNDERFLOOR AIR DISTRIBUTION (UFAD) SYSTEM American Journal of Engineering and Applied Sciences 7 (1): 23-35, 2014 ISSN: 1941-7020 2014 Megri and Yu, This open access article is distributed under a Creative Commons Attribution (CC-BY) 3.0 license

More information

Numerical thermal analysis of helical-shaped heat exchanger to improve thermal stratification inside solar storage tank

Numerical thermal analysis of helical-shaped heat exchanger to improve thermal stratification inside solar storage tank Ref: C0152 Numerical thermal analysis of helical-shaped heat exchanger to improve thermal stratification inside solar storage tank M. Imtiaz Hussain and Gwi Hyun Lee*, Department of Biosystems Engineering,

More information

Development of a Zonal Model. to Analyze a Thermal Storage Tank with an Electric Heater

Development of a Zonal Model. to Analyze a Thermal Storage Tank with an Electric Heater Development o a Zonal Model to Analyze a hermal Storage ank with an Electric Heater Seung Hyo Baek, 1 Hyun Min Nam, 1 Myoung Souk Yeo, 2 and Kwang Woo Kim. 2 1 Department o Architecture and Architectural

More information

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 5 Heiselberg, Per Kvols. Publication date: 2016

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 5 Heiselberg, Per Kvols. Publication date: 2016 Downloaded from vbn.aau.dk on: april 01, 2019 Aalborg Universitet CLIMA 2016 - proceedings of the 12th REHVA World Congress volume 5 Heiselberg, Per Kvols Publication date: 2016 Document Version Publisher's

More information

Indoor Air Quality and Mechanical Ventilation (Page 1 of 5)

Indoor Air Quality and Mechanical Ventilation (Page 1 of 5) Indoor Air Quality and Mechanical Ventilation (Page 1 of 5) Title 24, Part 6, Section 150.0(o) Ventilation for Indoor Air Quality. All dwelling units shall meet the requirements of ANSI/ASHRAE Standard62.2.

More information

Single-sided natural ventilation through a centre-pivot roof window Iqbal, Ahsan; Nielsen, Peter Vilhelm; Gunner, Amalie; Afshari, Alireza

Single-sided natural ventilation through a centre-pivot roof window Iqbal, Ahsan; Nielsen, Peter Vilhelm; Gunner, Amalie; Afshari, Alireza Aalborg Universitet Single-sided natural ventilation through a centre-pivot roof window Iqbal, Ahsan; Nielsen, Peter Vilhelm; Gunner, Amalie; Afshari, Alireza Published in: Proceedings Indoor Air 214 Publication

More information

Investigation of the Flow Pattern in a Complex Inlet Duct of a Heat Recovery Steam Generator

Investigation of the Flow Pattern in a Complex Inlet Duct of a Heat Recovery Steam Generator Energy and Power 2012, 2(1): 1-8 DOI: 10.5923/j.ep.20120201.01 Investigation of the Flow Pattern in a Complex Inlet Duct of a Heat Recovery Steam Generator Hyuntae Shin 1, Daehee Kim 2, Hyungjun Ahn 2,

More information

COMPUTATIONAL ANALYSIS ON THE EFFECTS OF FAÇADE MODIFICATIONS ON WIND-DRIVEN NATURAL VENTILATION PERFORMANCE OF A SINGLE-CELL ROOM

COMPUTATIONAL ANALYSIS ON THE EFFECTS OF FAÇADE MODIFICATIONS ON WIND-DRIVEN NATURAL VENTILATION PERFORMANCE OF A SINGLE-CELL ROOM COMPUTATIONAL ANALYSIS ON THE EFFECTS OF FAÇADE MODIFICATIONS ON WIND-DRIVEN NATURAL VENTILATION PERFORMANCE OF A SINGLE-CELL ROOM Mohd Farid Mohamed Department of Architecture, Faculty of Engineering

More information

Thermal and Fluid-dynamical Optimisation of Passengers Comfort in a Touring Bus Cabin

Thermal and Fluid-dynamical Optimisation of Passengers Comfort in a Touring Bus Cabin Excerpt from the Proceedings of the COMSOL Conference 2008 Hannover hermal and Fluid-dynamical Optimisation of Passengers Comfort in a ouring Bus Cabin Petrone G. (*), Fichera G. (**), Scionti M. (*) (*)

More information

Standards for Ventilation and Indoor Air Quality in relation to the EPBD

Standards for Ventilation and Indoor Air Quality in relation to the EPBD Standards for Ventilation and Indoor Air Quality in relation to the EPBD Bjarne W. Olesen International Center for Indoor Environment and Energy Technical University of Denmark, Denmark bwo@byg.dtu.dk

More information

Estimating a Building Airflow Network using CO2 Measurements from a Distributed Sensor Network

Estimating a Building Airflow Network using CO2 Measurements from a Distributed Sensor Network Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2010 Estimating a Building Airflow Network using CO2 Measurements from a Distributed

More information

Thermal and indoor air quality are important

Thermal and indoor air quality are important se 1693 ms 7/9/01 9:40 AM Page 735 ESTABLISHING CRITERIA FOR SIDEWALL AIR INLET PERFORMANCE AND EVALUATION OF FOUR COMMERCIAL INLETS ON THIS CRITERIA S. J. Hoff, C. G. Wu ABSTRACT. Four commercially available

More information

CFD Validation of Carbon monoxide diffusion within a ship vehicle garage

CFD Validation of Carbon monoxide diffusion within a ship vehicle garage CFD Validation of Carbon monoxide diffusion within a ship vehicle garage Presented by: Dr. Nasr Abdelrahman Nasr MAY 2013 Presentation Layout: Introduction. Field measurement and analysis. Mathematical

More information

CFD ASSESSMENTS WITHIN STRONGLY TRANSIENT DOMAINS. Aizaz Samuel, Jon Hand Energy Systems Research Unit University of Strathclyde, Glasgow, Scotland

CFD ASSESSMENTS WITHIN STRONGLY TRANSIENT DOMAINS. Aizaz Samuel, Jon Hand Energy Systems Research Unit University of Strathclyde, Glasgow, Scotland CFD ASSESSMENTS WITHIN STRONGLY TRANSIENT DOMAINS Aizaz Samuel, Jon Hand Energy Systems Research Unit University of Strathclyde, Glasgow, Scotland ABSTRACT Assessments based on CFD snapshots of stable

More information

Application of CFD to Predict and Control Chemical and Biological Agent Dispersion in Buildings

Application of CFD to Predict and Control Chemical and Biological Agent Dispersion in Buildings Zhai, Z., Srebric, J., and Chen, Q. 2003. Application of CFD to predict and control chemical and biological agent dispersion in buildings, International Journal of Ventilation, 2(3), 25-26. Application

More information

Examples of IEQ factors. Healthy IEQ and energy efficiency. What type of system is the best? Ideas and concepts from research and reality.

Examples of IEQ factors. Healthy IEQ and energy efficiency. What type of system is the best? Ideas and concepts from research and reality. Healthy IEQ and energy efficiency Ideas and concepts from research and reality Lars Ekberg Energy Management AB A Chalmers Industriteknik Company 1 Examples of IEQ factors Thermal climate -operative temp.

More information

EFEECT OF HYDROGEN ADDITION ON METHANE COMBUSTION IN A CAN TYPE COMBUSTOR

EFEECT OF HYDROGEN ADDITION ON METHANE COMBUSTION IN A CAN TYPE COMBUSTOR EFEECT OF HYDROGEN ADDITION ON METHANE COMBUSTION IN A CAN TYPE COMBUSTOR Ramesh E (Roll No. 10105144) Abstract The effects of hydrogen addition on lean methane combustion was numerically investigated

More information

A study of single-sided ventilation and provision of balconies in the context of high-rise residential buildings

A study of single-sided ventilation and provision of balconies in the context of high-rise residential buildings A study of single-sided ventilation and provision of balconies in the context of high-rise residential buildings Mohamed M. F. 1,2,*, King S. 2, Behnia M. 3, Prasad D. 2 1 Faculty of Engineering and Built

More information

Infiltration simulation in a detached house empirical model validation

Infiltration simulation in a detached house empirical model validation Infiltration simulation in a detached house empirical model validation Juha Jokisalo¹, Targo Kalamees¹, Jarek Kurnitski¹, Lari Eskola¹, Kai Jokiranta¹ and Juha Vinha² ¹Helsinki University of Technology,

More information

Numerical Simulation of Airflow Organization and Temperature Distribution in Bulk Curing Barn Yong-qiao WANG, Yan-qiong LI, Yan ZHAO

Numerical Simulation of Airflow Organization and Temperature Distribution in Bulk Curing Barn Yong-qiao WANG, Yan-qiong LI, Yan ZHAO 5th International Conference on Advanced Materials and Computer Science (ICAMCS 2016) Numerical Simulation of Airflow Organization and Temperature Distribution in Bulk Curing Barn Yong-qiao WANG, Yan-qiong

More information

In-vehicle / Out-vehicle air quality and commuter s exposure to pollutants

In-vehicle / Out-vehicle air quality and commuter s exposure to pollutants In-vehicle / Out-vehicle air quality and commuter s exposure to pollutants Andrew Chan School of Chemical and Environmental Engineering University of Nottingham Malaysia Campus Jalan Broga, 5 Semenyih,

More information

Comparison of airflow and contaminant distributions in rooms with traditional displacement ventilation and under-floor air distribution systems

Comparison of airflow and contaminant distributions in rooms with traditional displacement ventilation and under-floor air distribution systems Lee, K.S., Zhang, T., Jiang, Z., and Chen, Q. 2009. Comparison of airflow and contaminant distributions in rooms with traditional displacement ventilation and under-floor air distribution systems, ASRAE

More information