Energy Performance And Long-Term Evaluation Of Internal Thermal Comfort Of An Office Building With Different Kinds Of Glazing Systems And Window Sizes

Size: px
Start display at page:

Download "Energy Performance And Long-Term Evaluation Of Internal Thermal Comfort Of An Office Building With Different Kinds Of Glazing Systems And Window Sizes"

Transcription

1 Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering Energy Performance And Long-Term Evaluation Of Internal Thermal Comfort Of An Office Building With Different Kinds Of Glazing Systems And Window Sizes Francesca Cappelletti Andrea Gasparella Giovanni Pernigotto Piercarlo Romagnoni Follow this and additional works at: Cappelletti, Francesca; Gasparella, Andrea; Pernigotto, Giovanni; and Romagnoni, Piercarlo, "Energy Performance And Long-Term Evaluation Of Internal Thermal Comfort Of An Office Building With Different Kinds Of Glazing Systems And Window Sizes" (). International High Performance Buildings Conference. Paper 9. This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at Herrick/Events/orderlit.html

2 558, Page Energy Performance And Long-Term Evaluation Of Internal Thermal Comfort Of An Office Building With Different Kinds Of Glazing Systems And Window Sizes Francesca CAPPELLETTI *, Andrea GASPARELLA, Giovanni PERNIGOTTO, Piercarlo ROMAGNONI 4 University IUAV of Venezia, Venezia, Italy Phone , Fax , francesca.cappelletti@iuav.it Free University of Bolzano, Faculty of Science and Technology, Bolzano, Italy Phone , Fax , andrea.gasparella@unibz.it University of Padova, Dept. of Management and Engineering, Vicenza, Italy Phone , Fax , pernigotto@gest.unipd.it University IUAV of Venezia, Venezia, Italy Phone , Fax , piercarlo.romagnoni@iuav.it * Corresponding Author ABSTRACT Although the presence of large window surfaces could be preferable during the heating season when solar gains through the glazed components can overcome heating losses from the same surfaces, during the cooling season more attention has to be paid in order to limit the inlet of solar radiation which causes the increment of cooling load. Generally the optimal tradeoff for energy optimization, as already underlined in a previous paper by the authors, is using low thermal transmittance and high solar factor glazing, even if higher solar transmittance considerably worsens the cooling performance. However, the choice of glazing type and the design of windows on a façade may depend on comfort consideration besides energetic evaluations. Thermal sensation of an individual is mainly related to the whole thermal balance of the human body. Comfort limits can in this case be expressed by two indexes proposed by Fanger in 97: the Predicted Mean Vote, PMV, and the correlated Predicted Percentage of Dissatisfied, PPD. The PMV depends on four environmental parameters (air temperature, air humidity, air velocity and mean radiant temperature) and two variables connected with human being (physical activity and clothing). The air temperature, the air humidity and the air velocity inside a building are directly under the system control. In contrast, the mean radiant temperature is strongly conditioned by the envelope surface temperature, and in particular, by the presence of glazed surfaces whose insulating performance is lower than the opaque components one. In this paper the study of heating and cooling energy needs of an open-space office with different windows characteristics has been carried out controlling the internal comfort conditions with appropriate setpoint of the system. An office module with windows on a single façade, or on opposite façades, oriented towards different orientations has been simulated, varying the glazed area ( sizes), the glazing systems (4 types) and considering three localities of central and southern Europe. The PMV have been calculated for each hour of occupation of the whole year assuming two season as regards the setpoint conditions and clothing level. Calculations have then been repeated considering also the effect of the diffuse and beam solar radiation through the windows directly reaching the occupants. The evaluation of the long-term comfort conditions (on seasonal basis) has been conducted considering some statistical indicators of distribution (the median, minimum, maximum and the interquartile range) and the energy performance of the different glazing solution have been compared accounting for the comfort one. International High Performance Buildings Conference at Purdue, July 6-9,

3 558, Page. INTRODUCTION The contribution of the windows physical properties to the building energy needs and the simultaneous influence of their characteristics on the thermal sensation of occupants has been studied by many authors from different points of view. As regards thermal comfort, Hwang and Shu () investigated the effect of different envelope parameters on thermal comfort. Their analysis compared the cooling energy need of a space controlled by a thermostat with a PMV-based control, implementing the approach of Kang et al. (). According to that concept (Kang et al. ) the occupants will adjust the room temperature when they perceive uncomfortable indoor thermal environments. Therefore the room temperature should be adjusted with respect to the changes in the indoor climate in order to maintain the same PMV level. Recently some authors have underlined the importance of taking into account of adaptation possibilities in order to reduce energy needs (Nicol and Humphreys,, Ferrari and Zanotto, ), although the European Technical Standard EN 55:7 considers this approach only for buildings without mechanical cooling system. Finally many authors have proposed to correct the classical definition of the PMV to take into account the effect of direct and diffuse solar radiation entering through the glazed areas and directly reaching the people (La Gennusa et al., 5, Singh et al., 8, Hwang and Shu, ). As regards the importance of the glazing system in the optimization of energy need both during the heating and the cooling season, Gasparella et al. () underlined the fact that energy optimization does not only depend on the use of insulating glasses, but also on the quantity of solar radiation admitted by the windows. Successively the same authors (Gasparella et al., ) analysed the relation between long-term internal thermal comfort, energy performance, kind of glazing and window size, according to the classical definition of the PMV approach. In this paper different kinds of glazing systems and different windows sizes are compared from energetic point of view, assuming a controlled indoor thermal comfort in an office application. Heating and cooling energy needs have been evaluated through a parametric analysis, considering 96 configurations in three European climates (Rome, Milan and Paris-Trappes). An office module with windows on a single façade, or on opposite façades, oriented towards three different orientations has been simulated, varying the glazed surface entity ( sizes) and the glazing systems (4 types) and considering three localities of central and southern Europe. The analysis has been carried out considering two seasons of six months each (winter from st October till st March and summer from st April till th September). A control logic acting on the air temperature has been simulated to directly limit the operative temperature within the seasonal ranges prescribed in the Annex A of the EN ISO Standard 77:5 for the winter and for the summer season, in consideration of the kind of activity, of the clothing level and for a normal level of expectation (category B). The PMVs have been calculated for each occupational hour of the whole year. Calculations have then been repeated considering also the effect of the diffuse and beam solar radiation through the windows directly reaching the occupants. The evaluation of the long-term comfort conditions (on a seasonal basis) has been conducted considering some statistical indicators of distribution (the median, minimum, maximum and the interquartile range) and the energy performance of the different glazing solution have been compared accounting for the comfort one.. MODEL AND METHOD A simple three-dimensional office model has been considered and a parametric simulation plan has been developed. The base module is an open office box shaped (Figure a), with a square floor of m and an internal height of m. The roof is horizontal and the floor is considered adiabatic, as could be for the top floor of an office building. The four vertical walls are oriented towards the four cardinal directions. Both horizontal and vertical walls are composed by a two-layer structure: the internal layer is a clay block of. m of thickness and the external one is an insulation layer of.5 m. The solar absorptance coefficients have been set to.6 for the floor (internal side) and. for the vertical walls and the roof (both sides). The wall emissivity is.9, both for the internal and the external side. Different kind of glazings, two double glazings and two triple glazings have been considered (Table ). A wooden frame with a thermal transmittance of. W/(m K) and a class- edge correlation have been chosen. Changing each parameter among the kind of glazings, the glazing size, the windows distribution and the climatic conditions, 96 configurations to analyze were obtained (Table ). Hourly climatic data were calculated from average monthly values from the Italian Standard UNI 49:994 for Milan and Rome and from the monthly averages of a TRY weather file (CEC, 985) for Paris (Trappes) using the TRNSYS subroutine Type 54 Weather Data Generator. International High Performance Buildings Conference at Purdue, July 6-9,

4 558, Page 7 (,8,.) 8 (5,8,.) 9 (8,8,.) 4 (,5,.) 5 (5,5,.) 6 (8,5,.) (,,.) (5,,.) (8,,.) (a) (b) Figure : (a) Office module (large size windows (S) up and small size down (S)) (b) Coordinates of the positions for the PMV calculations Table : Parameters values varied in the considered configurations and symbols Parameter Values Glazings Double Glazings (D) with high SHGC (H):U gl =.4 W/(m K); SHGC =.68; d =.49 Double Glazings (D) with low SHGC (L): U gl =.99 W/(m K); SHGC =.5; d =.5 Triple Glazings (T) with high SHGC (H): U gl =.6 W/(m K); SHGC =.575; d =.9 Triple Glazings (T) with low SHGC (L): U gl =.6 W/(m K); SHGC =.4; d =.9 Windows Size (S): width = 9 m; height =.5 m; area =.5 m (in each façade with windows) Size Size (S): width = 9 m; height =.5 m; area =.5 m (in each façade with windows) Windows East (E) distribution East + West (E+W) South (S) South + North (S+N) Location Rome: Lat. N /Heating Deg-Days HDD 8 : 4 K d/cooling Deg-Days CDD 8 : 87 K d Milan: Lat. N ; HDD 8 : 49 K d CDD 8 : 686 K d Paris (Trappes); Latitude N ; HDD 8 : 5 K d CDD 8 : 5 K d The office occupation period is from 8: am to the 6: pm, Monday to Friday. Considering an occupancy index of. people/m the estimated number of occupants is. Correspondingly the ventilation rate is set equal to.58 ach/h during the occupation time, in accordance to the Italian technical standard UNI 9:995, and. ach/h, as infiltration, for the rest of the time; the indoor air velocity has been fixed in. m/s. The internal gains, in accordance with the EN ISO 79:8, are W/m during the occupation time, and W/m otherwise, a half convective and a half radiant. The vapor flow rate due to occupants have been estimated in.5 kg/h per person and the indoor humidity is not controlled by the system. The whole year has been considered as divided in two main seasons: the winter from st October till st March and the summer from st April till th September. The heating and the cooling system have two different set-points depending on the season. The temperature ranges were fixed considering the category B (which should allow a PMV within ±.5 and a PPD under %), as defined in the Annex A of EN ISO 77:5, that means for an open office, an operative temperature range from C to 4 C for the winter season (clothing index ) and from C to 6 C for summer season (with clothing index.5). This way the energy needs of the different configurations can be compared for similar internal comfort performance. The system operates from 6: a.m. to 6: pm during the week-day. During the week-end and the un-occupancy time the heating set-point is 5 C while there isn t any cooling set-point. The occupants are assumed with a sedentary activity corresponding to. met (EN ISO 77:5) and a clothing level of clo in winter and of.5 clo in summer. The hourly predicted mean vote PMV un has been calculated according to EN ISO 77:5 for 9 positions in the room, as in Figure b, each one at. m from the floor level. However the results are given only for the position due to the limited variability with respect to the position and for the below reasons. International High Performance Buildings Conference at Purdue, July 6-9,

5 558, Page 4 Besides the PMV un, the PMV irr has been calculated only for the position of Figure b, which is particularly critical, considering the mean radiant temperature which includes the effect of solar radiation that directly reaches the occupant (La Gennusa et al., 7). This parameter has been calculated considering a mean radiant temperature calculated as in Equation : N M 4 C 4 dn in in in T r,irr F S iti irr,d FS jid, j CS irr,b f pibn () i j The diffuse irradiation entering through the windows, I in d, has been calculated from the external diffuse irradiation considering the hemispherical transmission coefficients given by WINDOW 6. for the four types of glazings (table ), as in Equation : I in out d = I d d () Similarly, the beam radiation entering through the glazed surfaces has been calculated considering the external beam radiation on the oriented façade and the hourly optical transmission coefficient of the glazing which depends on the incidence angle, as in Equation : I in out b = I b b () To calculate b a polynomial function was extrapolated from the optical characteristics given by WINDOW 6. for a step of of the incidence angles. The expression used is reported in equation 4 and the coefficients j for the calculation are reported in Table : 5 j cos (4) b j j The beam solar radiation reaching the considered point has been determined considering the position of the sun with an hourly time step and comparing the azimuth and the altitude angle with the maximum angles for the geometry of the windows. The calculation of energy needs were performed in TRNSYS 7. which enables D modeling of the ambient radiation exchanges. The determination of the hourly variables for the calculation of the PMV un and PMV irr was implemented in a specific spreadsheet. Table : Coefficient for the calculation of the optical transmittance of the glazed surface as function of the index j in Equation 4. j 4 5 Glazings DH DL TH TL RESULTS The simulations results have been represented in terms of PMV un (Figures and, for winter and summer respectively) and PMV irr (Figure 4) distribution, both only for the position number, indicating minimum and maximum, the median and the interquartile range IQR for each configuration, and referring only to the occupancy period. With this representation the distribution of the values is particularly evidenced as each individuated range comprises 5% of the occurrences. Due to the control strategy the conventional PMV un should result in the range of the comfort category B (±.5) as would be required to compare the heating and cooling energy needs (represented in the same Figures and ) of the different configurations under equivalent (if not the same) comfort conditions. Even if this is not completely verified, for a given locality the PMV un lays in an almost constant range allowing this evaluation at least location by location. In the next two sections the results will be discussed starting from the winter season and moving to the summer season.. Rome, Milan and Paris - Winter As regards Rome, the mean values and the dispersion of the PMV un values change when the windows size (Figure ), the windows orientation and the solar heat gain coefficient of the glasses change. Anyhow, the PMV un vary from the minimum of.6 to the maximum of.8 in all cases, and the IQRs generally are always between ±.5. The wider and higher IQRs are given for the larger windows area and in East+West, South and South+North orientations. Comparing the glazing systems, it is noticeable that negligible differences appear for the PMV un International High Performance Buildings Conference at Purdue, July 6-9,

6 International High Performance Buildings Conference at Purdue, July 6-9, 558, Page 5 distribution of glazings with the same Solar Heat Gain Coefficient (SHGC). Moreover the high SHGC reduces the differences in the distribution of PMV un with respect to the increase of the windows size. This is true for all the orientation except for the East one. Moving to the energy needs analysis, for a given kind of glazing, the larger size S of the windows reduces the heating energy needs in all the orientations except for the East one, where enhanced solar gains are balanced by enhanced dispersion. Adding windows on the opposite side of the room, when the increased area is North exposed, increases the heating energy needs for all the glazing systems except for triple glazing and for wider size windows S: in that case the energy need is the same as with window only on the south façade. Comparing the glazing systems the most convenient way to reduce heating needs is to adopt the triple glazing with high SHGC for all the situations. However the double glazing with high SHGC gives similar energy needs. Winter cooling needs become significant when increasing the window area only for the orientation East+West, South and South+North, but only for the high SHGC solutions. However, when the solar radiation entering through the windows and hitting a person is accounted, the higher SHGC values present some drawbacks. Looking to the PMV irr distributions (Figure 4), the glazing systems with high SHGC presents the highest maximum values (about.4 for East and East+West orientation, and well above the full scale value of for South and South+North orientation) determining, even if temporarily, very bad thermal indoor conditions. Except for this extreme condition the mean value is still in the comfort category B which, according to the ISO 77:5, includes PMV values between the range ±.5. Nevertheless the third quartile overcome the upper limit of +.5. Also in Milan, the PMV un distributions (Figure ) range between.6 and.8, but with narrower IQRs and mean values much more aligned than in Rome. In all the cases the 5% of the PMV un values are under the zero and between. and.4, that means that the thermal sensation is a little cooler than the neutrality. For each type of glazing increasing the size of the windows generally reduces the heating energy needs, except for the East orientation and double glazing with high SHGC and for the South orientation and double glazing with high SHGC. Adding windows on the opposite side is ineffective or slightly penalizing when the increased area is North exposed otherwise it has positive effect in energy saving. For the same type of glazing, the orientation and size combination which leads to the lower heating need is the South with the larger size of window S. Comparing the glazing systems, the most convenient to reduce heating needs is again the triple glazing with high SHGC for all the situations. The double glazing with high SHGC gives similar needs only for east orientation. Winter cooling needs are almost null for low SHGC glazings and are between and GJ in the other cases. When considering the solar radiation through the windows hitting the person (Figure 4), the maximum PMV irr values overcome the value of.7 (which is the upper limit for the comfort category C of EN ISO 77:5) in all cases, and for the high SHGC glazing they largely overpasses the full scale for South and South+North orientation. Nevertheless as it happens for Rome climate, the IQRs never overcome +.5. In the climate of Paris the PMV un distributions (Figure ) show minimum and the maximum ranging from.6 to.6 for all the orientation except for the East one, for which minimum is (smaller windows) or. (larger windows). The IQRs are very narrow (between. and.4) for all cases and the mean values are aligned to.4. Even in this case, as for Milan, the generally thermal sensation is slightly cooler than the neutrality. Increasing the size of the windows for each type of glazing does not affect so much the heating energy needs and in some cases it slightly increases the heating need. As for Milan and for Rome, adding windows on the opposite side is ineffective or slightly penalizing when the increased area is north exposed otherwise it has positive effect in energy saving. For the same type of glazing, the orientation and the size combination which lead to the lower heating need is South and larger size (S). Comparing the glazing systems the most convenient to reduce heating needs is still the triple glazing with high SHGC for all the situations. Winter cooling needs are almost always null. The interquartile ranges the distributions of PMV irr (Figure 4) are very narrow as for the PMV un with the only exceptions for the South and South+North orientations and for double high and triple high SHGC glazings where the IRQ amplitude swings from.5 to.8. In general, the presence of solar radiation hitting the person seems to improve in average the thermal sensation, but could leads to some extreme situations of discomfort as it happens for Rome and Milan for double and triple glazing with high SHGC and for South and South+North orientation.. Rome, Milan and Paris - Summer In the climate of Rome, the PMV un ranges between.8 and.6 in almost all the cases (Figure ). The mean values swing from. (just few cases) to.4. The IQRs are narrower than in the winter case and between and.4, widely in the range of the thermal comfort category B. The wider IQRs are for the glazings with low SHGC. Almost no heating needs are present in summer. Concerning the cooling needs, for each type of glazing and for each orientation, increasing the size of the windows strongly increases the cooling energy needs. For the same glazing

7 International High Performance Buildings Conference at Purdue, July 6-9, 558, Page 6 type and for the same window size, the largest cooling needs are found for orientation South if windows are present only on one façade and for the East-West orientation when windows are present on the opposite façades. It is noticeable that in the first case the difference in cooling needs from South and East orientation are not so relevant, while the cooling needs is greatly higher for East+West orientation than for the South+North especially for high SHGC. Comparing the different glazing types, the double and the triple with low SHGC give the lowest cooling needs and their values are very similar. The SHGC appears to be the only relevant parameter in this climate, in which the thermal losses have modest impact on the building heat balance, and this consideration is in accordance with the findings of some previous works (Gasparella et al. ). The presence of the solar radiation entering through the windows generally doesn t affect the mean value of the PMV nor the third quartile value (Figure 4). For the double and triple glazings with high SHGC the maximum values of PMV irr reaches values of about. for South and South+North orientation, but reaches the value of about for East and East+West orientation. For the other two types of glazing the maximum values are reached for the East and the East+West orientation but it doesn t overcome the value of.. As regards Milan, the PMV un values ranges between.8 and.6 in almost all the cases; the only exceptions are for low SHGC glazings and East orientation for which the maximum PMV un values is.7. The mean PMV un value is about. and the IQRs are wider than for Rome especially for the low SHGC glazings, but don t overcome the amplitude of.4. Almost no heating needs are present. Again increasing the size of the windows strongly increases the cooling energy needs. The cooling needs for orientation East do not prevail over the South orientation, as it occurs in Rome but still have the most important sensitivity to the addition of windows on the opposite side (East+West) and still this last orientation gives the greatest level of cooling need for all the type of glazings. As regards the type of glazing, the differences between double and triple glazings with similar SHGCs are negligible, either considering the energy needs or the PMV un values. Glazings with low SHGC give the lowest cooling needs when given the other conditions. Considering the PMV irr the considerations are quite similar to the ones for Rome. The solar irradiation increases slightly the median of about. but just for some orientation. Maximum values increases very much for glazing with high SHGC especially for East and East+West orientation approaching the value of. The interquartile ranges have negligible differences from the unirradiated cases. For the glazings with low SHGC the maximum values of PMV irr is about for East and East+West orientation and of.8 for other orientation. However, the IQR for the PMV irr is always inside the interval of the B category of indoor environment (±.5). Finally as regards Paris, the PMV un ranges, similarly to the other localities, from the minimum value of -.8 to the maximum value of.6. The mean value has a discrete variability for the same glazing type increasing when the window size increases and, for high SHGC glazing, it reaches the values of for the larger size of window for orientation East+West, South and North+South. The distribution of PMV irr is similar to the one of PMV un except for the maximum values as it happens for Rome and Milan. Heating needs prevail over cooling needs in all the cases when the glazing has low SHGC and in some cases, such as for east and south orientation in other cases. Considering the cooling needs again increasing the size of the windows strongly increases the cooling energy needs. East+West orientation gives the greatest level of cooling need for all the type of glazings. As in Milan and in Rome also in Paris the cooling needs are driven by the SHGC coefficient and the differences between the double and the triple glazing with the same SHGC are negligible. Maximum PMV irr swings from to for high SHGC glazings, depending on the orientation and the size of the window: this behavior is quite different from the other localities. For the low SHGC glazings the maximum values are quite constant at.6 for East and East+West orientation and they vary from.7 to.9 for the other orientations. Also in this climate the IQR is kept inside the thermal comfort range of ± CONCLUSIONS In the present paper the energy performance of different kinds of glazing systems have been evaluated for given comfort conditions, in order to identify the importance of the thermal transmittance and of the SHGC in relation to different orientations, window size and envelope insulation for three European climatic conditions. The results confirmed that for equivalent interquartile distribution of the PMV un there is a strong influence of the SHGC also on the winter energy needs, as already found in some previous works. In particular double glazings with high SHGC tend to have at least as good winter performance as triple with low SHGC. Low SHGC double or triple glazings are preferable in summer in particular for East orientation. Concerning the comfort conditions, the SHGC again is the controlling parameter, in particular in winter, when evaluating the effect on the PMV un distribution. Low SHGC leads to narrower IQRs in winter with small and

8 558, Page 7 different effects in summer. However, when the solar radiation hitting the occupant is considered, PMV irr maximum value with high SHGC are dramatically increased in particular for South and South+North orientation in winter and for the Southern climates. Minor effects are seen for East and East+West orientation in summer. In conclusion high SHGC triple glazings appear to be slightly preferable to double glazings in Rome, Milan and Paris, providing suitable moveable shading devices especially for the South orientations for winter comfort and for the East and East+West for summer energy performance. NOMENCLATURE T r,irr Mean radiant temperature including entering solar radiation (K) T i Temperature of surface i (K) F S i, j Angle factor between the window and the person (-) C dn Day-night coefficient (-) in I d Intensity of the inner diffuse solar radiation (W m - ) in I bn Intensity of the indoor beam solar radiation on a surface orthogonal to solar ray direction (W m - ) out I b Intensity of the external beam solar radiation (W m - ) out I d Intensity of the external diffuse solar radiation (W m - ) in C S Inner building shading coefficient (-) HDD 8 Heating degree days with respect to an internal reference temperature of 8 C (K d) CDD 8 Cooling degree days with respect to an internal reference temperature of 8 C (K d) SHGC Solar heat gain coefficient (-) U gl Glazing thermal transmittance (W m - K - ) Greek Symbols d, b Absorption coefficient of the subject referring to the diffuse or beam solar radiation (-) Emissivity of the subject (-) Angle between the direction of the solar rays and the normal to the glass ( ) Stephan- Boltzmann constant ( ) (W m - K -4 ) d, b Optical transmittance of the glass for the diffuse or the beam component (-) REFERENCES CEC (Commission of the European Communities), 985, Test Reference Years TRY, weather data sets for computer simulations of solar energy systems and energy consumption in buildings, Brussels, Belgium. Ferrari, S., Zanotto, V.,, Adaptive comfort: Analysis and application of the main indices, Build. Environ., vol. 49: p. 5-. Gasparella, A., Pernigotto, G., Cappelletti, F., Romagnoni, P., Baggio, P.,, Analysis and modeling of window and glazing systems energy performance for a well-insulated residential building, Energy Build., vol. 4, no. 4: p. -7. Gasparella, A., Cappelletti, F., Pernigotto, G., Romagnoni, P.,, Long-term Evaluation of Internal Thermal Comfort with Different Kinds of Glazing Systems and Window Sizes: from Energetic Considerations to Users Comfort, Proceedings of Ashrae Annual Conference, San Antonio, TX, USA, rd 7 th June Hwang, R.L., Shu, S.Y.,, Building envelope regulations on thermal comfort in glass facade buildings and energy-saving potential for PMV-based comfort control, Build. Environ., vol. 46: p Kang, D.H., Mo, P.H., Choi, D.H., Song, S.Y., Yeo, M.S., Kim, K.W.,, Effect of MRT variation on the energy consumption in a PMV-controlled office. Build. Environ., vol. 45: p La Gennusa, M., Nucara, A., Pietrafesa, M., Rizzo, G., 7, A model for managing and evaluating solar radiation for indoor thermal comfort, Sol. Energy, vol. 8: p Nicol, J.F., Humphreys, M.A.,, Adaptive thermal comfort and sustainable thermal standards for buildings, Energy Build., vol. 4: p Singh, M.C., Garg, S.N., Jha, R., 8, Different glazing systems and their impact on human thermal comfort - Indian scenario, Build. Environ., vol. 4: p International High Performance Buildings Conference at Purdue, July 6-9,

9 Energy needs [GJ] PMV un - Paris PMV un - Milan PMV un - Rome 558, Page 8 Double H Double L Triple H Triple L E E+W S S+N E E+W S S+N E E+W S S+N E E+W S S+N S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S Trappes cooling Milano cooling Roma cooling Trappes heating Milano heating Roma heating Figure : Rome, Milan and Paris Winter PMV un distributions (the upper dot represents the maximum, the intermediate the median, the under dot the minimum and the box the interquartile range) and winter Energy Needs. International High Performance Buildings Conference at Purdue, July 6-9,

10 Energy needs [GJ] PMV un - Paris PMV un - Milan PMV un - Rome 558, Page 9 Double H Double L Triple H Triple L E E+W S S+N E E+W S S+N E E+W S S+N E E+W S S+N S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S Trappes cooling Milano cooling Roma cooling Trappes heating Milano heating Roma heating Figure : Rome, Milan and Paris Summer PMV un distributions (the upper dot represents the maximum, the intermediate the median, the under dot the minimum and the box the interquartile range) and summer Energy Needs. International High Performance Buildings Conference at Purdue, July 6-9,

11 PMV irr - Paris SUMMER WINTER PMV irr - Milan PMV irr - Rome PMV irr - Paris PMV irr - Milan PMV irr - Rome 558, Page Double H Double L Triple H Triple L E E+W S S+N E E+W S S+N E E+W S S+N E E+W S S+N S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S Figure 4: Rome, Milan and Paris Winter (above) and Summer (under) PMV with solar irradiation statistical distributions. International High Performance Buildings Conference at Purdue, July 6-9,

DYNAMIC ANALYSIS OF ENERGY PERFORMANCE OF DIFFERENT ROOF SYSTEMS DURING THE COOLING SEASON

DYNAMIC ANALYSIS OF ENERGY PERFORMANCE OF DIFFERENT ROOF SYSTEMS DURING THE COOLING SEASON Proceedings of Building Simulation : DYNAMIC ANALYSIS OF ENERGY PERFORMANCE OF DIFFERENT ROOF SYSTEMS DURING THE COOLING SEASON Francesca Cappelletti, Andrea Gasparella, Giovanni Pernigotto and Piercarlo

More information

Evaluation methods for indoor environmental quality assessment according to EN15251

Evaluation methods for indoor environmental quality assessment according to EN15251 Summary of this article was published in the REHVA European HVAC Journal Vol 49, Issue 4 (August), 2012, pages 14-19, available at http://www.rehva.eu/en/rehva-european-hvac-journal. Evaluation methods

More information

BUILDING DESIGN AND THERMAL INERTIA: WHEN, WHY, WHERE

BUILDING DESIGN AND THERMAL INERTIA: WHEN, WHY, WHERE Int. Journal for Housing Science, Vol.34, No.4 pp. 221-231, 2010 Published in the United States BUILDING DESIGN AND THERMAL INERTIA: WHEN, WHY, WHERE R. Albatici, S. Penasa Department of Civil and Environmental

More information

Assessment Of Long-Term Visual And Thermal Comfort And Energy Performance In Open-Space Offices With Different Shading Devices

Assessment Of Long-Term Visual And Thermal Comfort And Energy Performance In Open-Space Offices With Different Shading Devices Purdue University Purdue e-pubs International High Performance Buildings Conference chool of Mechanical Engineering 214 Assessment Of Long-Term Visual And Thermal Comfort And Energy Performance In Open-pace

More information

ADVANCED FAÇADES AND HVAC SYSTEMS: PRELIMINARY RESULTS OF FULL-SCALE MONITORING

ADVANCED FAÇADES AND HVAC SYSTEMS: PRELIMINARY RESULTS OF FULL-SCALE MONITORING ADVANCED FAÇADES AND HVAC SYSTEMS: PRELIMINARY RESULTS OF FULL-SCALE MONITORING M. Kragh, M. Colombari and M. Zobec Permasteelisa Group, Research & Engineering, 31020 San Vendemiano (TV), Italy www.permasteelisa.com,

More information

Solar gains in the glazing systems with sun-shading

Solar gains in the glazing systems with sun-shading 729 Solar gains in the glazing systems with sun-shading G. Oliveti, N. Arcuri, R. Bruno, M. De Simone University of Calabria, Italy ABSTRACT This paper presents the optical and thermal performances of

More information

Thermal comfort study of naturally ventilated office

Thermal comfort study of naturally ventilated office Thermal comfort study of naturally ventilated office Marta Laska 1,* 1 Wroclaw University of Science and Technology, Faculty of Environmental Engineering, Wybrz. Wyspianskiego 27, 50-370 Wroclaw, Poland

More information

SUMMER THERMAL COMFORT IN TYPICAL FRENCH RESIDENTIAL BUILDINGS: IMPACT ASSESSMENT OF BUILDING ENVELOPE INSULATION ENHANCEMENT

SUMMER THERMAL COMFORT IN TYPICAL FRENCH RESIDENTIAL BUILDINGS: IMPACT ASSESSMENT OF BUILDING ENVELOPE INSULATION ENHANCEMENT 13th Conference of International Building Simulation Association, Chambéry, France, August 26-28 SUMMER THERMAL COMFORT IN TYPICAL FRENCH RESIDENTIAL BUILDINGS: IMPACT ASSESSMENT OF BUILDING ENVELOPE INSULATION

More information

SKYLIGHT DESIGN PERFORMANCE EVALUATION METHOD DEVELOPMENT WITH THERMAL AND DAYLIGHT SIMULATION

SKYLIGHT DESIGN PERFORMANCE EVALUATION METHOD DEVELOPMENT WITH THERMAL AND DAYLIGHT SIMULATION SKYLIGHT DESIGN PERFORMANCE EVALUATION METHOD DEVELOPMENT WITH THERMAL AND DAYLIGHT SIMULATION Xianou Li, Frederick Wong, and Yihan Li Arup International Consultants (Shanghai) Co Ltd ABSTRACT This paper

More information

Buildings with large glazed surfaces: optimization of solar control strategies in relation to the building's thermal inertia

Buildings with large glazed surfaces: optimization of solar control strategies in relation to the building's thermal inertia Buildings with large glazed surfaces: optimization of solar control strategies in relation to the building's thermal inertia Antonio Carbonari 1 1 Department of Design and Planning in Complex Environments,

More information

Analysis of different shading strategies on energy demand and operating cost of office building

Analysis of different shading strategies on energy demand and operating cost of office building Analysis of different shading strategies on energy demand and operating cost of office building Kwiatkowski, J 1,2 ; Rucińska, J 1,2 ; Panek, A 1,2 1 Warsaw University of Technology, Faculty of Environmental

More information

IMPACT OF USING DIFFERENT MODELS IN PRACTICE A CASE STUDY WITH THE SIMPLIFIED METHODS OF ISO STANDARD AND DETAILED MODELLING PROGRAMS

IMPACT OF USING DIFFERENT MODELS IN PRACTICE A CASE STUDY WITH THE SIMPLIFIED METHODS OF ISO STANDARD AND DETAILED MODELLING PROGRAMS IMPACT OF USING DIFFERENT MODELS IN PRACTICE A CASE STUDY WITH THE SIMPLIFIED METHODS OF ISO 13790 STANDARD AND DETAILED MODELLING PROGRAMS Kokogiannakis Georgios 1, Clarke Joe 1, Strachan Paul 1 1 Energy

More information

A PARAMETRIC STUDY ON WINDOW-TO-FLOOR RATIO OF THREE WINDOW TYPES USING DYNAMIC SIMULATION

A PARAMETRIC STUDY ON WINDOW-TO-FLOOR RATIO OF THREE WINDOW TYPES USING DYNAMIC SIMULATION A PARAMETRIC STUDY ON WINDOW-TO-FLOOR RATIO OF THREE WINDOW TYPES USING DYNAMIC SIMULATION Energy for Sustainability 2015 Sustainable Cities: Designing for People and the Planet Coimbra, 14-15 May, 2015

More information

The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort

The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort Ongun Berk Kazanci, Bjarne W. Olesen 1 1 International Center for Indoor Environment and

More information

Prediction of Thermal Comfort. mech14.weebly.com

Prediction of Thermal Comfort. mech14.weebly.com Prediction of Thermal Comfort Thermal Sensation Scale (Rohles & Nevins, 1974) Fanger s Thermal Comfort Model (1982) Steady state model, applicable for M 3 met and a large group of people Fanger s Thermal

More information

REAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS. Galway, Ireland

REAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS. Galway, Ireland REAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS Magdalena Hajdukiewicz 1,2,3, Padraig O Connor 1, Colin O Neill 1, Daniel Coakley 1,2,3, Marcus M. Keane 1,2,3, Eoghan Clifford 1,2,3 1 Department

More information

Opportunities and Limitations of Building Precooling

Opportunities and Limitations of Building Precooling Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 1994 Opportunities and Limitations of Building Precooling K. R. Keeney Purdue

More information

STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS

STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS 1. ABSTRACT In modern architecture the buildings are often designed with large glass facades or windows. Due to these

More information

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS Bjarne W. Olesen Ph. D, International Centre for Indoor Environment and Energy, Department of Mechanical Engineering, Technical

More information

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models L. Pagliano et al, I: Optimization of air tightness and night ventilation for Passive houses in Italian climates... 1 Optimization of air tightness and night ventilation for Passive houses in Italian climates

More information

Assessment of thermal comfort near a glazed exterior wall

Assessment of thermal comfort near a glazed exterior wall Assessment of thermal comfort near a glazed exterior wall Timothy Anderson 1, Mark Luther 2 and Tim Brain 3 1 School of Engineering, Auckland University of Technology, Auckland 1142, New Zealand 2 School

More information

JOTUN Cool Shades. Impact of the TSR Value on the Users Comfort and the Energy Performance of Buildings. ai³ Werner Jager

JOTUN Cool Shades. Impact of the TSR Value on the Users Comfort and the Energy Performance of Buildings. ai³ Werner Jager JOTUN Cool Shades Impact of the TSR Value on the Users Comfort and the Energy Performance of Buildings ai³ Werner Jager Exclusion of warranty: All tables, graphical charts and results presented within

More information

Quantifying Comfort to Assist in the Window Selection Process

Quantifying Comfort to Assist in the Window Selection Process Quantifying Comfort to Assist in the Window Selection Process Kerry Haglund, Efficient Windows Collaborative Jim Larsen, Cardinal Glass Industries June 18, 2015 WDMA Technical & Manufacturing Conference

More information

Attaining Thermal Comfort in. Buildings with Predominantly. Glazed Facades. presented to: ANSYS Boston Regional Conference

Attaining Thermal Comfort in. Buildings with Predominantly. Glazed Facades. presented to: ANSYS Boston Regional Conference Attaining Thermal Comfort in Buildings with Predominantly Glazed Facades presented to: ANSYS Boston Regional Conference September 14, 2011 Case Study Background High floor to ceiling windows Large skylight

More information

Modeling Energy Consumption Effects of Glazing

Modeling Energy Consumption Effects of Glazing Modeling Energy Consumption Effects of Glazing Daniel Lu 12/7/2012 Table of Contents Introduction... 3 Design Options... 5 Option 1... 5 Option 2... 5 Preliminary Energy Simulation... 7 Objectives... 7

More information

ScienceDirect. Influence of the balcony glazing construction on thermal comfort of apartments in retrofitted large panel buildings

ScienceDirect. Influence of the balcony glazing construction on thermal comfort of apartments in retrofitted large panel buildings Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 108 (2015 ) 481 487 7th Scientific-Technical Conference Material Problems in Civil Engineering (MATBUD 2015) Influence of the

More information

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya (vahid.vakiloroaya@engineer.com) ABSTRACT: The overall attainable reduction in energy consumption and enhancement of

More information

Utilizing Heat Dump Capacity of a Small Pond Attached to Infloor Slab of a Net-Zero Energy House

Utilizing Heat Dump Capacity of a Small Pond Attached to Infloor Slab of a Net-Zero Energy House Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2010 Utilizing Heat Dump Capacity of a Small Pond Attached to Infloor Slab of a Net-Zero

More information

Long term evaluation of building energy performance: comparison of the test reference year and historical data series in the North Italian climates

Long term evaluation of building energy performance: comparison of the test reference year and historical data series in the North Italian climates Long term evaluation of building energy performance: comparison of the test reference year and historical data series in the North Italian climates Giovanni Pernigotto University of Padova, Vicenza, Italy

More information

A Case Study on the Daylighting and Thermal Effects of Fixed and Motorized Light Louvers

A Case Study on the Daylighting and Thermal Effects of Fixed and Motorized Light Louvers A Case Study on the Daylighting and Thermal Effects of Fixed and Motorized Light Louvers Yuxiang Chen 1, Samson Yip 1, Andreas Athienitis 1 1 Building, Civil and Environmental Engineering, Concordia University,

More information

Designing Air-Distribution Systems To Maximize Comfort

Designing Air-Distribution Systems To Maximize Comfort Designing Air-Distribution Systems To Maximize Comfort By David A. John, P.E., Member ASHRAE An air-distribution system that provides occupant thermal comfort can be a complicated system to predict and

More information

COMPARATIVE SUMMER THERMAL AND COOLING LOAD PERFORMANCE OF NATURAL VENTILATION OF CAVITY ROOF UNDER THREE DIFFERENT CLIMATE ZONES

COMPARATIVE SUMMER THERMAL AND COOLING LOAD PERFORMANCE OF NATURAL VENTILATION OF CAVITY ROOF UNDER THREE DIFFERENT CLIMATE ZONES COMPARATIVE SUMMER THERMAL AND COOLING LOAD PERFORMANCE OF NATURAL VENTILATION OF CAVITY ROOF UNDER THREE DIFFERENT CLIMATE ZONES Lusi Susanti 1, Hiroshi Matsumoto 2, and Hiroshi Homma 2 1 Department of

More information

Thermal comfort evaluation of natural ventilation mode: case study of a high-rise residential building

Thermal comfort evaluation of natural ventilation mode: case study of a high-rise residential building J. Zuo, L. Daniel, V. Soebarto (eds.), Fifty years later: Revisiting the role of architectural science in design and practice: 50 th International Conference of the Architectural Science Association 2016,

More information

Thermal Characteristics of a Vernacular Building Envelope

Thermal Characteristics of a Vernacular Building Envelope Thermal Characteristics of a Vernacular Building Envelope Priyanka Dhar, M.Tech. Department of Energy, Tezpur University, Tezpur, 784028, Assam, India Pallavi Borah, M.Tech. Department of Energy, Tezpur

More information

Designing for thermal comfort near a glazed exterior wall. * School of Engineering, Auckland University of Technology, Auckland, New Zealand

Designing for thermal comfort near a glazed exterior wall. * School of Engineering, Auckland University of Technology, Auckland, New Zealand Designing for thermal comfort near a glazed exterior wall T.N. Anderson ǂ *, M.B. Luther ** * School of Engineering, Auckland University of Technology, Auckland, New Zealand ** School of Architecture and

More information

Influence Of Building Zoning On Annual Energy Demand

Influence Of Building Zoning On Annual Energy Demand Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Influence Of Building Zoning On Annual Energy Demand Lisa Rivalin Mines ParisTech,

More information

Nearly Zero Energy Building in Lecco Modern technological building compared to an ancient Villa

Nearly Zero Energy Building in Lecco Modern technological building compared to an ancient Villa Nearly Zero Energy Building in Lecco Modern technological building compared to an ancient Villa Matteo BRASCA *, Oscar Luigi PAGANI **, Kanza RAUF*** * partner - AIACE S.r.l. società di ingegneria, contract

More information

IMPACT OF SOLAR IRRADIATION MODELS ON BUILDING REFURBISHMENT MEASURES FROM MULTI-OBJECTIVE OPTIMIZATION

IMPACT OF SOLAR IRRADIATION MODELS ON BUILDING REFURBISHMENT MEASURES FROM MULTI-OBJECTIVE OPTIMIZATION IMPACT OF SOLAR IRRADIATION MODELS ON BUILDING REFURBISHMENT MEASURES FROM MULTI-OBJECTIVE OPTIMIZATION Alessandro Prada 1, Giovanni Pernigotto 2, Francesca Cappelletti 3, Andrea Gasparella 1 1 Free University

More information

Free University of Bolzano/Bozen, Faculty of Science and Technology, Bolzano, Italy -

Free University of Bolzano/Bozen, Faculty of Science and Technology, Bolzano, Italy - Comparison of Different Glare Indices through Metrics for Long Term and Zonal Visual Comfort Assessment Anna Maria Atzeri 1, Francesca Cappelletti 2, Andrea Gasparella 1 1 Free University of Bolzano/Bozen,

More information

Assessing the energy performance of modern glass facade systems

Assessing the energy performance of modern glass facade systems Assessing the energy performance of modern glass facade systems Abdelsalam Aldawoud * Architectural Engineering Department, University of Sharjah Sharjah, United Arab Emirates Abstract. The design and

More information

Simplified methods to evaluate energy use for space cooling in the energy certification

Simplified methods to evaluate energy use for space cooling in the energy certification Simplified methods to evaluate energy use for space cooling in the energy certification Alessio Gastaldello and Luigi Schibuola University IUAV of Venice, Italy Corresponding email: luigi.schibuola@iuav.it

More information

Ventilative Cooling potential tool

Ventilative Cooling potential tool Ventilative Cooling potential tool User guide Version 1.0 IEA EBC Programme Annex 62 Ventilative Cooling AUTHORS: ANNAMARIA BELLERI EURAC RESEARCH Institute for renewable energy Druso 1 39100 Bolzano Italy

More information

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates Kittitach Pichatwatana, and Fan Wang Abstract This paper examines the TAS computer

More information

LOCAL VENTILATION SYSTEMS: SOME INVESTIGATIONS ABOUT COMFORT LEVELS AND ENERGY DEMANDS

LOCAL VENTILATION SYSTEMS: SOME INVESTIGATIONS ABOUT COMFORT LEVELS AND ENERGY DEMANDS LOCAL VENTILATION SYSTEMS: SOME INVESTIGATIONS ABOUT COMFORT LEVELS AND ENERGY DEMANDS Elena Buchberger - ebuch@iuav.it Luca Porciani, porciani@iuav.it Fabio Peron, fperon@iuav.it Universita IUAV di Venezia,

More information

An enhancement of the daylighting from side-window using two-section venetian blind

An enhancement of the daylighting from side-window using two-section venetian blind An enhancement of the daylighting from side-window using two-section venetian blind Vichuda Mettanant 1,2, Pipat Chaiwiwatworakul 1,2,*, Pattana Rakkwamsuk 3 1 The Joint Graduate School of Energy and Environment,

More information

Effects of Fixed and Motorized Window Louvers on the Daylighting and Thermal Performance of Open-Plan Office Buildings

Effects of Fixed and Motorized Window Louvers on the Daylighting and Thermal Performance of Open-Plan Office Buildings Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 214 Effects of Fixed and Motorized Window Louvers on the Daylighting and Thermal Performance

More information

A Field Study of Thermal Comfort in Open-plan Office Buildings during Transition Seasons in Harbin. Yunsong Han 1, 2, Huixuan Sun 1, 2, Cheng Sun 1, 2

A Field Study of Thermal Comfort in Open-plan Office Buildings during Transition Seasons in Harbin. Yunsong Han 1, 2, Huixuan Sun 1, 2, Cheng Sun 1, 2 A Field Study of Thermal Comfort in Open-plan Office Buildings during Transition Seasons in Harbin Yunsong Han 1, 2, Huixuan Sun 1, 2, Cheng Sun 1, 2 1 School of Architecture, Harbin Institute of Technology,

More information

Thermal Characteristics and Energy Performance of Double Skin. Façade System in the Hot Summer and Cold Winter Zone

Thermal Characteristics and Energy Performance of Double Skin. Façade System in the Hot Summer and Cold Winter Zone Thermal Characteristics and Energy Performance of Double Skin Façade System in the Hot Summer and Cold Winter Zone L.F. Shu 1, G.Q. He 1,*, S.M. Zhang 1 and Q.A. Bai 2 1 College of Civil Engineering and

More information

Characterization and performance evaluation of solar shading devices

Characterization and performance evaluation of solar shading devices Characterization and performance evaluation of solar shading devices Inês P. Santos, Research Assistant, Department of Civil Engineering, Technical University of Denmark; isa@byg.dtu.dk, www.byg.dtu.dk

More information

COMPARISON OF THERMAL PERFORMANCE OF DIFFERENT WALL STRUCTURES

COMPARISON OF THERMAL PERFORMANCE OF DIFFERENT WALL STRUCTURES HEFAT2012 9 th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics 16 18 July 2012 Malta COMPARISON OF THERMAL PERFORMANCE OF DIFFERENT WALL STRUCTURES Ozel M.* and Ozel C. *Author

More information

Allowing for Thermal Comfort in Free-running Buildings in the New European Standard EN15251

Allowing for Thermal Comfort in Free-running Buildings in the New European Standard EN15251 Allowing for Thermal Comfort in Free-running Buildings in the New European Standard EN15251 Fergus Nicol, Low Energy Architecture Research Unit (LEARN), School of Architecture, London Metropolitan University,

More information

Towards nzeb buildings: a historical building case study

Towards nzeb buildings: a historical building case study Towards nzeb buildings: a historical building case study The recast of EU Directive 2010/31 introduced the concept of (nearly) zero energy building (NZEB). In Italy this challenge is remarkable: existing

More information

Assessing thermal comfort of dwellings in summer using EnergyPlus

Assessing thermal comfort of dwellings in summer using EnergyPlus Assessing thermal comfort of dwellings in summer using EnergyPlus Irina Bliuc, Rodica Rotberg and Laura Dumitrescu Gh. Asachi Technical University of Iasi, Romania Corresponding email: irina_bliuc@yahoo.com

More information

Young Cities Research Briefs 07 Architectural Energy Efficiency

Young Cities Research Briefs 07 Architectural Energy Efficiency Young Cities Research Briefs 7 Architectural Energy Efficiency Farshad Nasrollahi 1 Introduction Decreasing the energy demand of buildings by applying cost-intensive measures (such as the addition of insulation

More information

Passive house optimization for Southern Italy based on the New Passivhaus Standard

Passive house optimization for Southern Italy based on the New Passivhaus Standard Passive house optimization for Southern Italy based on the New Passivhaus Standard Paolo Zangheri end-use Effi ciency Research Group, Dipartimento di Energia Politecnico di Milano, Italy paolo.zangheri@polimi.it

More information

Deliverable D.3.3 Common computer tool for building simulations -Manual- English version July 2006

Deliverable D.3.3 Common computer tool for building simulations -Manual- English version July 2006 Contract No. EIE-2003-RURASU-223 Deliverable D.3.3 Common computer tool for building simulations -Manual- English version July 2006 Prepared by: Kostas Pavlou University of Athens, Physics Department (IASA

More information

An Assessment in the Heat Gain and Loss Through Opaque Elements in Commercial Buildings in Brazil

An Assessment in the Heat Gain and Loss Through Opaque Elements in Commercial Buildings in Brazil Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 212 An Assessment in the Heat Gain and Loss Through Opaque Elements in Commercial Buildings

More information

Design guidelines for direct ground cooling systems in different climates

Design guidelines for direct ground cooling systems in different climates Design guidelines for direct ground cooling systems in different climates Adriana Angelotti and Giulio Solaini Dipartimento BEST, Politecnico di Milano, Milano, Italy ABSTRACT: Direct ground cooling systems

More information

OPENING DESIGN TO IMPROVE THE NATURAL VENTILATION PERFORMANCE OF HIGH-RISE RESIDENTIAL BUILDINGS

OPENING DESIGN TO IMPROVE THE NATURAL VENTILATION PERFORMANCE OF HIGH-RISE RESIDENTIAL BUILDINGS OPENING DESIGN TO IMPROVE THE NATURAL VENTILATION PERFORMANCE OF HIGH-RISE RESIDENTIAL BUILDINGS Cho Rong Kim 1, Ga Young Cho 1, Sun Woo Lee 1, Myoung Souk Yeo 2, and Kwang Woo Kim 2 1 Department of Architecture,

More information

International Journal of Civil and Environmental Engineering 3:2 2011

International Journal of Civil and Environmental Engineering 3:2 2011 Investigating the Effectiveness of Self-Shading Strategy on Overall Thermal Transfer Value and Window Size in High Rise Buildings Mansour Nikpour, Mohd Zin kandar, Mohammad Ghomeshi, Nima Moeinzadeh, Mohsen

More information

Introduction to basics of energy efficient building design

Introduction to basics of energy efficient building design Introduction to basics of energy efficient building design Pierre Jaboyedoff Seminar on Energy Efficient & Thermally Comfortable Buildings in Amravati For CRDA, Andhra Pradesh May 2 nd 2017 Indo-Swiss

More information

Module 3: Simulation and Data Analysis

Module 3: Simulation and Data Analysis INSTRUCTIONAL MODULES DEMONSTRATING BUILDING ENERGY ANALYSIS USING A BUILDING INFORMATION MODEL Christian Daniel Douglass Industrial and Enterprise Systems Engineering December 1, 2010 Module Summary In

More information

Solar cooling design: a case study

Solar cooling design: a case study Eco-Architecture IV 399 Solar cooling design: a case study S. Grignaffini & M. Romagna Department of Astronautic, Electric and Energetic Engineering, Sapienza, University of Rome, Italy Abstract Throughout

More information

Information paper 17. Prepared by: David Clark. book:

Information paper 17. Prepared by: David Clark. book: Information paper 17 Thermal comfort standards Prepared by: David Clark A paper referenced in the book: Cundall Johnston & Partners LLP. 2013 Issue 1.0: 29 July 2013 This information paper is one of a

More information

ENERGY DEMAND ANALYSIS AND ENERGY LABELLING OF NEW RESIDENTIAL BUILDINGS IN TUSCANY (ITALY)

ENERGY DEMAND ANALYSIS AND ENERGY LABELLING OF NEW RESIDENTIAL BUILDINGS IN TUSCANY (ITALY) ENERGY DEMAND ANALYSIS AND ENERGY LABELLING OF NEW RESIDENTIAL BUILDINGS IN TUSCANY (ITALY) F. Fantozzi, F. Leccese, G. Salvadori, G. Tuoni Department of Energy L. Poggi Faculty of Engineering, University

More information

Innovative Systems for Energy Efficient Building Envelopes Applications at middle latitudes (temperate/mesothermal climates)

Innovative Systems for Energy Efficient Building Envelopes Applications at middle latitudes (temperate/mesothermal climates) Innovative Systems for Energy Efficient Building Envelopes Applications at middle latitudes (temperate/mesothermal climates) MONICA ROSSI 1 1 Facoltà di Architettura - Dipartimento DPUU, Università degli

More information

Energy and Thermal Comfort Management in a Kindergarten School Building in the South of Portugal in Winter Conditions

Energy and Thermal Comfort Management in a Kindergarten School Building in the South of Portugal in Winter Conditions 4th IASME/WSEAS International Conference on ENERGY, ENVIRONMENT, ECOSYSTEMS and SUSTAINABLE DEVELOPMENT (EEESD'8) Algarve, Portugal, June 11-13, 8 Energy and Thermal Comfort Management in a Kindergarten

More information

Study of the energy performance of a retrofitting office

Study of the energy performance of a retrofitting office Study of the energy performance of a retrofitting office Paolo Valdiserri CIRI Edilizia Costruzioni, Università di Bologna paolo.valdiserri@unibo.it Abstract Building retrofitting is the most feasible

More information

ATBU, Journal of Science, Technology & Education (JOSTE); Vol. 3 (4), December, 2015 ISSN:

ATBU, Journal of Science, Technology & Education (JOSTE); Vol. 3 (4), December, 2015 ISSN: THERMAL COMFORT ASSESSMENT OF ENGINEERING WORKSHOP: A CASE STUDY OF UNIVERSITY OF MAIDUGURI By S. Shodiya 1 *, M.B. Oumarou 1, A.T Quadri 2, and A.B. Muhammed 1 1 Department of Mechanical Engineering,

More information

Solar-Assisted Space Heating of a Highly Insulated Energy Efficient House

Solar-Assisted Space Heating of a Highly Insulated Energy Efficient House Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2010 Solar-Assisted Space Heating of a Highly Insulated Energy Efficient House Toktam

More information

Simulation Before Design? A New Software Program for Introductory Design Studios

Simulation Before Design? A New Software Program for Introductory Design Studios SIMULATION BEFORE DESIGN? 1 Simulation Before Design? A New Software Program for Introductory Design Studios TROY NOLAN PETERS California Polytechnic State University INTRODUCTION The 2010 Imperative states:

More information

ADAPTIVE THERMAL COMFORT - AN EXTENDED APPROACH FOR CONDITIONED INDOOR ENVIRONMENT USING COMPUTATIONAL FLUID DYNAMICS

ADAPTIVE THERMAL COMFORT - AN EXTENDED APPROACH FOR CONDITIONED INDOOR ENVIRONMENT USING COMPUTATIONAL FLUID DYNAMICS 16 th International Conference on Clean Energy (ICCE-2018) 9-11 May 2018, Famagusta, N. Cyprus ADAPTIVE THERMAL COMFORT - AN EXTENDED APPROACH FOR CONDITIONED INDOOR ENVIRONMENT USING COMPUTATIONAL FLUID

More information

Enhancing the Energy and Non-Energy Performance of Existing Buildings: a Multi- Objective Approach

Enhancing the Energy and Non-Energy Performance of Existing Buildings: a Multi- Objective Approach Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Enhancing the Energy and Non-Energy Performance of Existing Buildings: a Multi-

More information

A STUDY ON DESIGN OPTIMIZATION OF A NEAR NET-ZERO ENERGY HOUSE

A STUDY ON DESIGN OPTIMIZATION OF A NEAR NET-ZERO ENERGY HOUSE Int. Journal for Housing Science, Vol.37, No.1 pp.23-31, 2013 Published in the United States A STUDY ON DESIGN OPTIMIZATION OF A NEAR NET-ZERO ENERGY HOUSE Narghes Doust, Gabriele Masera and Marco Imperadori

More information

Findings of Field Survey for Thermal Comfort and Ventilation in US Office Buildings

Findings of Field Survey for Thermal Comfort and Ventilation in US Office Buildings Findings of Field Survey for Thermal Comfort and Ventilation in US Office Buildings Liangcai Tan 1, Samir Moujaes, HDR Inc. University of Nevada Las Vegas SUMMARY This paper presents the measured data

More information

ANALYSIS AND MITIGATION OF THERMAL EFFECTS ON A LARGE FACADE-MOUNTED PV ARRAY

ANALYSIS AND MITIGATION OF THERMAL EFFECTS ON A LARGE FACADE-MOUNTED PV ARRAY ANALYSIS AND MITIGATION OF THERMAL EFFECTS ON A LARGE FACADE-MOUNTED PV ARRAY A. Driesse 1, S. J. Harrison 2, Q. Lin 2 1 Queen's University, Integrated Learning Center, Kingston, ON, Canada; 2 Queen's

More information

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Available online at  ScienceDirect. Energy Procedia 78 (2015 ) Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 1093 1098 6th International Building Physics Conference, IBPC 2015 Verifying a need of artificial cooling - a simplified

More information

Lecture 3: Utilization of Passive Solar Technology

Lecture 3: Utilization of Passive Solar Technology Lecture 3: Utilization of Passive Solar Technology http://www.cs.kumamoto-u.ac.jp/epslab/apsf/ Lecturers: Syafaruddin & Takashi Hiyama syafa@st.eecs.kumamoto-u.ac.jp hiyama@cs.kumamoto-u.ac.jp Time and

More information

HUMAN-BEHAVIOR ORIENTED CONTROL STRATEGIES FOR NATURAL VENTILATION IN OFFICE BUILDINGS

HUMAN-BEHAVIOR ORIENTED CONTROL STRATEGIES FOR NATURAL VENTILATION IN OFFICE BUILDINGS HUMAN-BEHAVIOR ORIENTED CONTROL STRATEGIES FOR NATURAL VENTILATION IN OFFICE BUILDINGS Haojie Wang 1, Qingyan Chen 1,2* 1 School of Mechanical Engineering, Purdue University, West Lafayette, IN 47907 2

More information

RECENT CZECH BUILDING ENERGY SIMULATION CASE STUDIES

RECENT CZECH BUILDING ENERGY SIMULATION CASE STUDIES RECENT CZECH BUILDING ENERGY SIMULATION CASE STUDIES )'UNDO7'XQRYVND01HX]LO96NUODQW &]HFK7HFKQLFDO8QLYHUVLW\LQ3UDJXH )DFXOW\RI0HFKDQLFDO(QJLQHHULQJ 7HFKQLFND 3UDJXH&]HFK5HSXEOLF $%675$&7 By describing

More information

carbon-neutral architectural design Pablo La Roche CRC Press Taylor & Francis Croup Boca Raton London NewYork CRC Press is an imprint of the

carbon-neutral architectural design Pablo La Roche CRC Press Taylor & Francis Croup Boca Raton London NewYork CRC Press is an imprint of the carbon-neutral architectural design Pablo La Roche CRC Press Taylor & Francis Croup Boca Raton London NewYork CRC Press is an imprint of the Taylor fit Francis Group, an informs business Contents Preface

More information

FEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF

FEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF FEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF Oliver Baumann 1, and Claudius Reiser 1/2 1 Ebert & Baumann Consulting Engineers, Washington, D.C. 2 Ebert-Ingenieure GmbH &Co. KG, Munich,

More information

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Available online at   ScienceDirect. Energy Procedia 78 (2015 ) Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 2857 2862 6th International Building Physics Conference, IBPC 2015 Optimized Blind Control Method to minimize Heating,

More information

Phase-Change Wallboard and Mechanical Night Ventilation in Commercial Buildings: Potential for HVAC System Downsizing

Phase-Change Wallboard and Mechanical Night Ventilation in Commercial Buildings: Potential for HVAC System Downsizing Phase-Change Wallboard and Mechanical Night Ventilation in Commercial Buildings: Potential for HVAC System Downsizing Corina Stetiu Helmut E. Feustel Lawrence Berkeley National Laboratory, Berkeley, CA

More information

Thermal Comfort and Energy Consumption according to the Indoor Control Logic

Thermal Comfort and Energy Consumption according to the Indoor Control Logic Thermal Comfort and Energy Consumption according to the Indoor Control Logic S. Kim 1 and D. Song 2 1 Department of Civil and Environmental System Engineering Sungkyunkwan University, Suwon-si, Gyeonggi-do

More information

Chapter 7. Passive Solar Contents

Chapter 7. Passive Solar Contents Chapter 7. Passive Solar Contents 7.1 Introduction 7.2 Types of Passive Solar Systems 7.3 Advantages and Disadvantages 7.4 General Design Principles 7.5 Design Information for Direct System 7.6 Design

More information

Performance Evaluation Of Thermally Activated Glass Fibre Reinforced Gypsum Building Equipped With Desiccant System

Performance Evaluation Of Thermally Activated Glass Fibre Reinforced Gypsum Building Equipped With Desiccant System Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering July 2018 Performance Evaluation Of Thermally Activated Glass Fibre Reinforced Gypsum

More information

SUBJECTIVE AND MEASURED THERMAL COMFORT IN ITALIAN UNIVERSITY CLASSROOMS IN HEATED AND FREE RUNNING CONDITIONS

SUBJECTIVE AND MEASURED THERMAL COMFORT IN ITALIAN UNIVERSITY CLASSROOMS IN HEATED AND FREE RUNNING CONDITIONS SUBJECTIVE AND MEASURED THERMAL COMFORT IN ITALIAN UNIVERSITY CLASSROOMS IN HEATED AND FREE RUNNING CONDITIONS Stefano Corgnati, Roberta Ansaldi, and Marco Filippi Department of Energy (DENER), Politecnico

More information

Performance Evaluation of a Passive Chilled Beam System and Comparison with a Conventional Air System

Performance Evaluation of a Passive Chilled Beam System and Comparison with a Conventional Air System Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2016 Performance Evaluation of a Passive Chilled Beam System and Comparison with a Conventional

More information

DEVELOPMENT OF A DESIGN TOOL TO SIMULATE THE THERMAL PERFORMANCE OF DIRECT GAIN PASSIVE SOLAR SYSTEMS USING TMY3 DATA

DEVELOPMENT OF A DESIGN TOOL TO SIMULATE THE THERMAL PERFORMANCE OF DIRECT GAIN PASSIVE SOLAR SYSTEMS USING TMY3 DATA DEVELOPMENT OF A DESIGN TOOL TO SIMULATE THE THERMAL PERFORMANCE OF DIRECT GAIN PASSIVE SOLAR SYSTEMS USING TMY3 DATA Alfredo Fernández-González University of Nevada, Las Vegas 4505 Maryland Parkway, Box

More information

Observation of Liquid-filled Window without Presence of Liquid in Test Chamber

Observation of Liquid-filled Window without Presence of Liquid in Test Chamber SSP - JOURNAL OF CIVIL ENGINEERING Vol. 11, Issue 2, 2016 DOI: 10.1515/sspjce-2016-0020 Observation of Liquid-filled Window without Presence of Liquid in Test Chamber Ján Lojkovics Technical University

More information

Q-Air unique selling propositions in detail

Q-Air unique selling propositions in detail Q-Air unique selling propositions in detail Afraid of sitting at the window in winter? Q-Air offers a U value so low that there can be no perceptible cold air movement at the panoramic window even in coldest

More information

Thermal Comfort Assessment Based on Measurement and Questionnaire Surveys in a Large Mechanically Ventilated Space

Thermal Comfort Assessment Based on Measurement and Questionnaire Surveys in a Large Mechanically Ventilated Space Thermal Comfort Assessment Based on Measurement and Questionnaire Surveys in a Large Mechanically Ventilated Space Ali Alzaid 1, Maria Kolokotroni 1, Hazim Awbi 2 1 Mechanical Engineering, Brunel University

More information

POST OCCUPANCY DESIGN INERVENTION TO IMPROVE COMFORT AND ENERGY PERFORMANCE IN A DESERT HOUSE

POST OCCUPANCY DESIGN INERVENTION TO IMPROVE COMFORT AND ENERGY PERFORMANCE IN A DESERT HOUSE POST OCCUPANCY DESIGN INERVENTION TO IMPROVE COMFORT AND ENERGY PERFORMANCE IN A DESERT HOUSE Vidar Lerum Arizona State University P O Box 871605, Tempe, AZ, 85287-1605, USA vidar.lerum@asu.edu Venkata

More information

Building Envelope and Fabric Load Tests performed on ApacheSim in accordance with ANSI/ASHRAE Standard

Building Envelope and Fabric Load Tests performed on ApacheSim in accordance with ANSI/ASHRAE Standard Building Envelope and Fabric Load Tests performed on ApacheSim in accordance with ANSI/ASHRAE Standard 140-2007 ApacheSim Version 6.0.4 February 2010 Integrated Environmental Solutions www.iesve.com BOSTON,

More information

Available online at ScienceDirect. Procedia Engineering 145 (2016 ) 18 25

Available online at  ScienceDirect. Procedia Engineering 145 (2016 ) 18 25 Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 145 (2016 ) 18 25 International Conference on Sustainable Design, Engineering and Construction Applicability of Radiant Heating-Cooling

More information

A Method for Driving the Solar Control Mechanism Selection

A Method for Driving the Solar Control Mechanism Selection A Method for Driving the Solar Control Mechanism Selection Christopher Nilsson & Vitaliya Mokhava Master thesis in Energy-efficient and Environmental Buildings Faculty of Engineering Lund University Lund

More information

Cost-Benefit Analysis of Dwelling Retrofit Options

Cost-Benefit Analysis of Dwelling Retrofit Options Cost-Benefit Analysis of Dwelling Retrofit Options The objective was to study the thermal behaviour of the existing house and suggest cost effective improvements. Over recent years the energy efficiency

More information

Solar-Protective Glazing for Cold Climates

Solar-Protective Glazing for Cold Climates Lund University Sweden Lund Institute of Technology Department of Building Science Report TABK--98/3053 Solar-Protective Glazing for Cold Climates A Parametric Study of Energy Use in Offices Marie-Claude

More information

Passive Thermal Control for Window Insulation

Passive Thermal Control for Window Insulation Passive Thermal Control for Window Insulation E. Konroyd-Bolden 1, Dr. Z. Liao 1, 1 Ryerson University; Dept. of Architectural Science *Corresponding Author: 392 Pine Avenue, Unit 602, Oakville, Ontario,

More information