1 Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering Energy Performance And Long-Term Evaluation Of Internal Thermal Comfort Of An Office Building With Different Kinds Of Glazing Systems And Window Sizes Francesca Cappelletti Andrea Gasparella Giovanni Pernigotto Piercarlo Romagnoni Follow this and additional works at: Cappelletti, Francesca; Gasparella, Andrea; Pernigotto, Giovanni; and Romagnoni, Piercarlo, "Energy Performance And Long-Term Evaluation Of Internal Thermal Comfort Of An Office Building With Different Kinds Of Glazing Systems And Window Sizes" (). International High Performance Buildings Conference. Paper 9. This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at Herrick/Events/orderlit.html
2 558, Page Energy Performance And Long-Term Evaluation Of Internal Thermal Comfort Of An Office Building With Different Kinds Of Glazing Systems And Window Sizes Francesca CAPPELLETTI *, Andrea GASPARELLA, Giovanni PERNIGOTTO, Piercarlo ROMAGNONI 4 University IUAV of Venezia, Venezia, Italy Phone , Fax , francesca.cappelletti@iuav.it Free University of Bolzano, Faculty of Science and Technology, Bolzano, Italy Phone , Fax , andrea.gasparella@unibz.it University of Padova, Dept. of Management and Engineering, Vicenza, Italy Phone , Fax , pernigotto@gest.unipd.it University IUAV of Venezia, Venezia, Italy Phone , Fax , piercarlo.romagnoni@iuav.it * Corresponding Author ABSTRACT Although the presence of large window surfaces could be preferable during the heating season when solar gains through the glazed components can overcome heating losses from the same surfaces, during the cooling season more attention has to be paid in order to limit the inlet of solar radiation which causes the increment of cooling load. Generally the optimal tradeoff for energy optimization, as already underlined in a previous paper by the authors, is using low thermal transmittance and high solar factor glazing, even if higher solar transmittance considerably worsens the cooling performance. However, the choice of glazing type and the design of windows on a façade may depend on comfort consideration besides energetic evaluations. Thermal sensation of an individual is mainly related to the whole thermal balance of the human body. Comfort limits can in this case be expressed by two indexes proposed by Fanger in 97: the Predicted Mean Vote, PMV, and the correlated Predicted Percentage of Dissatisfied, PPD. The PMV depends on four environmental parameters (air temperature, air humidity, air velocity and mean radiant temperature) and two variables connected with human being (physical activity and clothing). The air temperature, the air humidity and the air velocity inside a building are directly under the system control. In contrast, the mean radiant temperature is strongly conditioned by the envelope surface temperature, and in particular, by the presence of glazed surfaces whose insulating performance is lower than the opaque components one. In this paper the study of heating and cooling energy needs of an open-space office with different windows characteristics has been carried out controlling the internal comfort conditions with appropriate setpoint of the system. An office module with windows on a single façade, or on opposite façades, oriented towards different orientations has been simulated, varying the glazed area ( sizes), the glazing systems (4 types) and considering three localities of central and southern Europe. The PMV have been calculated for each hour of occupation of the whole year assuming two season as regards the setpoint conditions and clothing level. Calculations have then been repeated considering also the effect of the diffuse and beam solar radiation through the windows directly reaching the occupants. The evaluation of the long-term comfort conditions (on seasonal basis) has been conducted considering some statistical indicators of distribution (the median, minimum, maximum and the interquartile range) and the energy performance of the different glazing solution have been compared accounting for the comfort one. International High Performance Buildings Conference at Purdue, July 6-9,
3 558, Page. INTRODUCTION The contribution of the windows physical properties to the building energy needs and the simultaneous influence of their characteristics on the thermal sensation of occupants has been studied by many authors from different points of view. As regards thermal comfort, Hwang and Shu () investigated the effect of different envelope parameters on thermal comfort. Their analysis compared the cooling energy need of a space controlled by a thermostat with a PMV-based control, implementing the approach of Kang et al. (). According to that concept (Kang et al. ) the occupants will adjust the room temperature when they perceive uncomfortable indoor thermal environments. Therefore the room temperature should be adjusted with respect to the changes in the indoor climate in order to maintain the same PMV level. Recently some authors have underlined the importance of taking into account of adaptation possibilities in order to reduce energy needs (Nicol and Humphreys,, Ferrari and Zanotto, ), although the European Technical Standard EN 55:7 considers this approach only for buildings without mechanical cooling system. Finally many authors have proposed to correct the classical definition of the PMV to take into account the effect of direct and diffuse solar radiation entering through the glazed areas and directly reaching the people (La Gennusa et al., 5, Singh et al., 8, Hwang and Shu, ). As regards the importance of the glazing system in the optimization of energy need both during the heating and the cooling season, Gasparella et al. () underlined the fact that energy optimization does not only depend on the use of insulating glasses, but also on the quantity of solar radiation admitted by the windows. Successively the same authors (Gasparella et al., ) analysed the relation between long-term internal thermal comfort, energy performance, kind of glazing and window size, according to the classical definition of the PMV approach. In this paper different kinds of glazing systems and different windows sizes are compared from energetic point of view, assuming a controlled indoor thermal comfort in an office application. Heating and cooling energy needs have been evaluated through a parametric analysis, considering 96 configurations in three European climates (Rome, Milan and Paris-Trappes). An office module with windows on a single façade, or on opposite façades, oriented towards three different orientations has been simulated, varying the glazed surface entity ( sizes) and the glazing systems (4 types) and considering three localities of central and southern Europe. The analysis has been carried out considering two seasons of six months each (winter from st October till st March and summer from st April till th September). A control logic acting on the air temperature has been simulated to directly limit the operative temperature within the seasonal ranges prescribed in the Annex A of the EN ISO Standard 77:5 for the winter and for the summer season, in consideration of the kind of activity, of the clothing level and for a normal level of expectation (category B). The PMVs have been calculated for each occupational hour of the whole year. Calculations have then been repeated considering also the effect of the diffuse and beam solar radiation through the windows directly reaching the occupants. The evaluation of the long-term comfort conditions (on a seasonal basis) has been conducted considering some statistical indicators of distribution (the median, minimum, maximum and the interquartile range) and the energy performance of the different glazing solution have been compared accounting for the comfort one.. MODEL AND METHOD A simple three-dimensional office model has been considered and a parametric simulation plan has been developed. The base module is an open office box shaped (Figure a), with a square floor of m and an internal height of m. The roof is horizontal and the floor is considered adiabatic, as could be for the top floor of an office building. The four vertical walls are oriented towards the four cardinal directions. Both horizontal and vertical walls are composed by a two-layer structure: the internal layer is a clay block of. m of thickness and the external one is an insulation layer of.5 m. The solar absorptance coefficients have been set to.6 for the floor (internal side) and. for the vertical walls and the roof (both sides). The wall emissivity is.9, both for the internal and the external side. Different kind of glazings, two double glazings and two triple glazings have been considered (Table ). A wooden frame with a thermal transmittance of. W/(m K) and a class- edge correlation have been chosen. Changing each parameter among the kind of glazings, the glazing size, the windows distribution and the climatic conditions, 96 configurations to analyze were obtained (Table ). Hourly climatic data were calculated from average monthly values from the Italian Standard UNI 49:994 for Milan and Rome and from the monthly averages of a TRY weather file (CEC, 985) for Paris (Trappes) using the TRNSYS subroutine Type 54 Weather Data Generator. International High Performance Buildings Conference at Purdue, July 6-9,
4 558, Page 7 (,8,.) 8 (5,8,.) 9 (8,8,.) 4 (,5,.) 5 (5,5,.) 6 (8,5,.) (,,.) (5,,.) (8,,.) (a) (b) Figure : (a) Office module (large size windows (S) up and small size down (S)) (b) Coordinates of the positions for the PMV calculations Table : Parameters values varied in the considered configurations and symbols Parameter Values Glazings Double Glazings (D) with high SHGC (H):U gl =.4 W/(m K); SHGC =.68; d =.49 Double Glazings (D) with low SHGC (L): U gl =.99 W/(m K); SHGC =.5; d =.5 Triple Glazings (T) with high SHGC (H): U gl =.6 W/(m K); SHGC =.575; d =.9 Triple Glazings (T) with low SHGC (L): U gl =.6 W/(m K); SHGC =.4; d =.9 Windows Size (S): width = 9 m; height =.5 m; area =.5 m (in each façade with windows) Size Size (S): width = 9 m; height =.5 m; area =.5 m (in each façade with windows) Windows East (E) distribution East + West (E+W) South (S) South + North (S+N) Location Rome: Lat. N /Heating Deg-Days HDD 8 : 4 K d/cooling Deg-Days CDD 8 : 87 K d Milan: Lat. N ; HDD 8 : 49 K d CDD 8 : 686 K d Paris (Trappes); Latitude N ; HDD 8 : 5 K d CDD 8 : 5 K d The office occupation period is from 8: am to the 6: pm, Monday to Friday. Considering an occupancy index of. people/m the estimated number of occupants is. Correspondingly the ventilation rate is set equal to.58 ach/h during the occupation time, in accordance to the Italian technical standard UNI 9:995, and. ach/h, as infiltration, for the rest of the time; the indoor air velocity has been fixed in. m/s. The internal gains, in accordance with the EN ISO 79:8, are W/m during the occupation time, and W/m otherwise, a half convective and a half radiant. The vapor flow rate due to occupants have been estimated in.5 kg/h per person and the indoor humidity is not controlled by the system. The whole year has been considered as divided in two main seasons: the winter from st October till st March and the summer from st April till th September. The heating and the cooling system have two different set-points depending on the season. The temperature ranges were fixed considering the category B (which should allow a PMV within ±.5 and a PPD under %), as defined in the Annex A of EN ISO 77:5, that means for an open office, an operative temperature range from C to 4 C for the winter season (clothing index ) and from C to 6 C for summer season (with clothing index.5). This way the energy needs of the different configurations can be compared for similar internal comfort performance. The system operates from 6: a.m. to 6: pm during the week-day. During the week-end and the un-occupancy time the heating set-point is 5 C while there isn t any cooling set-point. The occupants are assumed with a sedentary activity corresponding to. met (EN ISO 77:5) and a clothing level of clo in winter and of.5 clo in summer. The hourly predicted mean vote PMV un has been calculated according to EN ISO 77:5 for 9 positions in the room, as in Figure b, each one at. m from the floor level. However the results are given only for the position due to the limited variability with respect to the position and for the below reasons. International High Performance Buildings Conference at Purdue, July 6-9,
5 558, Page 4 Besides the PMV un, the PMV irr has been calculated only for the position of Figure b, which is particularly critical, considering the mean radiant temperature which includes the effect of solar radiation that directly reaches the occupant (La Gennusa et al., 7). This parameter has been calculated considering a mean radiant temperature calculated as in Equation : N M 4 C 4 dn in in in T r,irr F S iti irr,d FS jid, j CS irr,b f pibn () i j The diffuse irradiation entering through the windows, I in d, has been calculated from the external diffuse irradiation considering the hemispherical transmission coefficients given by WINDOW 6. for the four types of glazings (table ), as in Equation : I in out d = I d d () Similarly, the beam radiation entering through the glazed surfaces has been calculated considering the external beam radiation on the oriented façade and the hourly optical transmission coefficient of the glazing which depends on the incidence angle, as in Equation : I in out b = I b b () To calculate b a polynomial function was extrapolated from the optical characteristics given by WINDOW 6. for a step of of the incidence angles. The expression used is reported in equation 4 and the coefficients j for the calculation are reported in Table : 5 j cos (4) b j j The beam solar radiation reaching the considered point has been determined considering the position of the sun with an hourly time step and comparing the azimuth and the altitude angle with the maximum angles for the geometry of the windows. The calculation of energy needs were performed in TRNSYS 7. which enables D modeling of the ambient radiation exchanges. The determination of the hourly variables for the calculation of the PMV un and PMV irr was implemented in a specific spreadsheet. Table : Coefficient for the calculation of the optical transmittance of the glazed surface as function of the index j in Equation 4. j 4 5 Glazings DH DL TH TL RESULTS The simulations results have been represented in terms of PMV un (Figures and, for winter and summer respectively) and PMV irr (Figure 4) distribution, both only for the position number, indicating minimum and maximum, the median and the interquartile range IQR for each configuration, and referring only to the occupancy period. With this representation the distribution of the values is particularly evidenced as each individuated range comprises 5% of the occurrences. Due to the control strategy the conventional PMV un should result in the range of the comfort category B (±.5) as would be required to compare the heating and cooling energy needs (represented in the same Figures and ) of the different configurations under equivalent (if not the same) comfort conditions. Even if this is not completely verified, for a given locality the PMV un lays in an almost constant range allowing this evaluation at least location by location. In the next two sections the results will be discussed starting from the winter season and moving to the summer season.. Rome, Milan and Paris - Winter As regards Rome, the mean values and the dispersion of the PMV un values change when the windows size (Figure ), the windows orientation and the solar heat gain coefficient of the glasses change. Anyhow, the PMV un vary from the minimum of.6 to the maximum of.8 in all cases, and the IQRs generally are always between ±.5. The wider and higher IQRs are given for the larger windows area and in East+West, South and South+North orientations. Comparing the glazing systems, it is noticeable that negligible differences appear for the PMV un International High Performance Buildings Conference at Purdue, July 6-9,
6 International High Performance Buildings Conference at Purdue, July 6-9, 558, Page 5 distribution of glazings with the same Solar Heat Gain Coefficient (SHGC). Moreover the high SHGC reduces the differences in the distribution of PMV un with respect to the increase of the windows size. This is true for all the orientation except for the East one. Moving to the energy needs analysis, for a given kind of glazing, the larger size S of the windows reduces the heating energy needs in all the orientations except for the East one, where enhanced solar gains are balanced by enhanced dispersion. Adding windows on the opposite side of the room, when the increased area is North exposed, increases the heating energy needs for all the glazing systems except for triple glazing and for wider size windows S: in that case the energy need is the same as with window only on the south façade. Comparing the glazing systems the most convenient way to reduce heating needs is to adopt the triple glazing with high SHGC for all the situations. However the double glazing with high SHGC gives similar energy needs. Winter cooling needs become significant when increasing the window area only for the orientation East+West, South and South+North, but only for the high SHGC solutions. However, when the solar radiation entering through the windows and hitting a person is accounted, the higher SHGC values present some drawbacks. Looking to the PMV irr distributions (Figure 4), the glazing systems with high SHGC presents the highest maximum values (about.4 for East and East+West orientation, and well above the full scale value of for South and South+North orientation) determining, even if temporarily, very bad thermal indoor conditions. Except for this extreme condition the mean value is still in the comfort category B which, according to the ISO 77:5, includes PMV values between the range ±.5. Nevertheless the third quartile overcome the upper limit of +.5. Also in Milan, the PMV un distributions (Figure ) range between.6 and.8, but with narrower IQRs and mean values much more aligned than in Rome. In all the cases the 5% of the PMV un values are under the zero and between. and.4, that means that the thermal sensation is a little cooler than the neutrality. For each type of glazing increasing the size of the windows generally reduces the heating energy needs, except for the East orientation and double glazing with high SHGC and for the South orientation and double glazing with high SHGC. Adding windows on the opposite side is ineffective or slightly penalizing when the increased area is North exposed otherwise it has positive effect in energy saving. For the same type of glazing, the orientation and size combination which leads to the lower heating need is the South with the larger size of window S. Comparing the glazing systems, the most convenient to reduce heating needs is again the triple glazing with high SHGC for all the situations. The double glazing with high SHGC gives similar needs only for east orientation. Winter cooling needs are almost null for low SHGC glazings and are between and GJ in the other cases. When considering the solar radiation through the windows hitting the person (Figure 4), the maximum PMV irr values overcome the value of.7 (which is the upper limit for the comfort category C of EN ISO 77:5) in all cases, and for the high SHGC glazing they largely overpasses the full scale for South and South+North orientation. Nevertheless as it happens for Rome climate, the IQRs never overcome +.5. In the climate of Paris the PMV un distributions (Figure ) show minimum and the maximum ranging from.6 to.6 for all the orientation except for the East one, for which minimum is (smaller windows) or. (larger windows). The IQRs are very narrow (between. and.4) for all cases and the mean values are aligned to.4. Even in this case, as for Milan, the generally thermal sensation is slightly cooler than the neutrality. Increasing the size of the windows for each type of glazing does not affect so much the heating energy needs and in some cases it slightly increases the heating need. As for Milan and for Rome, adding windows on the opposite side is ineffective or slightly penalizing when the increased area is north exposed otherwise it has positive effect in energy saving. For the same type of glazing, the orientation and the size combination which lead to the lower heating need is South and larger size (S). Comparing the glazing systems the most convenient to reduce heating needs is still the triple glazing with high SHGC for all the situations. Winter cooling needs are almost always null. The interquartile ranges the distributions of PMV irr (Figure 4) are very narrow as for the PMV un with the only exceptions for the South and South+North orientations and for double high and triple high SHGC glazings where the IRQ amplitude swings from.5 to.8. In general, the presence of solar radiation hitting the person seems to improve in average the thermal sensation, but could leads to some extreme situations of discomfort as it happens for Rome and Milan for double and triple glazing with high SHGC and for South and South+North orientation.. Rome, Milan and Paris - Summer In the climate of Rome, the PMV un ranges between.8 and.6 in almost all the cases (Figure ). The mean values swing from. (just few cases) to.4. The IQRs are narrower than in the winter case and between and.4, widely in the range of the thermal comfort category B. The wider IQRs are for the glazings with low SHGC. Almost no heating needs are present in summer. Concerning the cooling needs, for each type of glazing and for each orientation, increasing the size of the windows strongly increases the cooling energy needs. For the same glazing
7 International High Performance Buildings Conference at Purdue, July 6-9, 558, Page 6 type and for the same window size, the largest cooling needs are found for orientation South if windows are present only on one façade and for the East-West orientation when windows are present on the opposite façades. It is noticeable that in the first case the difference in cooling needs from South and East orientation are not so relevant, while the cooling needs is greatly higher for East+West orientation than for the South+North especially for high SHGC. Comparing the different glazing types, the double and the triple with low SHGC give the lowest cooling needs and their values are very similar. The SHGC appears to be the only relevant parameter in this climate, in which the thermal losses have modest impact on the building heat balance, and this consideration is in accordance with the findings of some previous works (Gasparella et al. ). The presence of the solar radiation entering through the windows generally doesn t affect the mean value of the PMV nor the third quartile value (Figure 4). For the double and triple glazings with high SHGC the maximum values of PMV irr reaches values of about. for South and South+North orientation, but reaches the value of about for East and East+West orientation. For the other two types of glazing the maximum values are reached for the East and the East+West orientation but it doesn t overcome the value of.. As regards Milan, the PMV un values ranges between.8 and.6 in almost all the cases; the only exceptions are for low SHGC glazings and East orientation for which the maximum PMV un values is.7. The mean PMV un value is about. and the IQRs are wider than for Rome especially for the low SHGC glazings, but don t overcome the amplitude of.4. Almost no heating needs are present. Again increasing the size of the windows strongly increases the cooling energy needs. The cooling needs for orientation East do not prevail over the South orientation, as it occurs in Rome but still have the most important sensitivity to the addition of windows on the opposite side (East+West) and still this last orientation gives the greatest level of cooling need for all the type of glazings. As regards the type of glazing, the differences between double and triple glazings with similar SHGCs are negligible, either considering the energy needs or the PMV un values. Glazings with low SHGC give the lowest cooling needs when given the other conditions. Considering the PMV irr the considerations are quite similar to the ones for Rome. The solar irradiation increases slightly the median of about. but just for some orientation. Maximum values increases very much for glazing with high SHGC especially for East and East+West orientation approaching the value of. The interquartile ranges have negligible differences from the unirradiated cases. For the glazings with low SHGC the maximum values of PMV irr is about for East and East+West orientation and of.8 for other orientation. However, the IQR for the PMV irr is always inside the interval of the B category of indoor environment (±.5). Finally as regards Paris, the PMV un ranges, similarly to the other localities, from the minimum value of -.8 to the maximum value of.6. The mean value has a discrete variability for the same glazing type increasing when the window size increases and, for high SHGC glazing, it reaches the values of for the larger size of window for orientation East+West, South and North+South. The distribution of PMV irr is similar to the one of PMV un except for the maximum values as it happens for Rome and Milan. Heating needs prevail over cooling needs in all the cases when the glazing has low SHGC and in some cases, such as for east and south orientation in other cases. Considering the cooling needs again increasing the size of the windows strongly increases the cooling energy needs. East+West orientation gives the greatest level of cooling need for all the type of glazings. As in Milan and in Rome also in Paris the cooling needs are driven by the SHGC coefficient and the differences between the double and the triple glazing with the same SHGC are negligible. Maximum PMV irr swings from to for high SHGC glazings, depending on the orientation and the size of the window: this behavior is quite different from the other localities. For the low SHGC glazings the maximum values are quite constant at.6 for East and East+West orientation and they vary from.7 to.9 for the other orientations. Also in this climate the IQR is kept inside the thermal comfort range of ± CONCLUSIONS In the present paper the energy performance of different kinds of glazing systems have been evaluated for given comfort conditions, in order to identify the importance of the thermal transmittance and of the SHGC in relation to different orientations, window size and envelope insulation for three European climatic conditions. The results confirmed that for equivalent interquartile distribution of the PMV un there is a strong influence of the SHGC also on the winter energy needs, as already found in some previous works. In particular double glazings with high SHGC tend to have at least as good winter performance as triple with low SHGC. Low SHGC double or triple glazings are preferable in summer in particular for East orientation. Concerning the comfort conditions, the SHGC again is the controlling parameter, in particular in winter, when evaluating the effect on the PMV un distribution. Low SHGC leads to narrower IQRs in winter with small and
8 558, Page 7 different effects in summer. However, when the solar radiation hitting the occupant is considered, PMV irr maximum value with high SHGC are dramatically increased in particular for South and South+North orientation in winter and for the Southern climates. Minor effects are seen for East and East+West orientation in summer. In conclusion high SHGC triple glazings appear to be slightly preferable to double glazings in Rome, Milan and Paris, providing suitable moveable shading devices especially for the South orientations for winter comfort and for the East and East+West for summer energy performance. NOMENCLATURE T r,irr Mean radiant temperature including entering solar radiation (K) T i Temperature of surface i (K) F S i, j Angle factor between the window and the person (-) C dn Day-night coefficient (-) in I d Intensity of the inner diffuse solar radiation (W m - ) in I bn Intensity of the indoor beam solar radiation on a surface orthogonal to solar ray direction (W m - ) out I b Intensity of the external beam solar radiation (W m - ) out I d Intensity of the external diffuse solar radiation (W m - ) in C S Inner building shading coefficient (-) HDD 8 Heating degree days with respect to an internal reference temperature of 8 C (K d) CDD 8 Cooling degree days with respect to an internal reference temperature of 8 C (K d) SHGC Solar heat gain coefficient (-) U gl Glazing thermal transmittance (W m - K - ) Greek Symbols d, b Absorption coefficient of the subject referring to the diffuse or beam solar radiation (-) Emissivity of the subject (-) Angle between the direction of the solar rays and the normal to the glass ( ) Stephan- Boltzmann constant ( ) (W m - K -4 ) d, b Optical transmittance of the glass for the diffuse or the beam component (-) REFERENCES CEC (Commission of the European Communities), 985, Test Reference Years TRY, weather data sets for computer simulations of solar energy systems and energy consumption in buildings, Brussels, Belgium. Ferrari, S., Zanotto, V.,, Adaptive comfort: Analysis and application of the main indices, Build. Environ., vol. 49: p. 5-. Gasparella, A., Pernigotto, G., Cappelletti, F., Romagnoni, P., Baggio, P.,, Analysis and modeling of window and glazing systems energy performance for a well-insulated residential building, Energy Build., vol. 4, no. 4: p. -7. Gasparella, A., Cappelletti, F., Pernigotto, G., Romagnoni, P.,, Long-term Evaluation of Internal Thermal Comfort with Different Kinds of Glazing Systems and Window Sizes: from Energetic Considerations to Users Comfort, Proceedings of Ashrae Annual Conference, San Antonio, TX, USA, rd 7 th June Hwang, R.L., Shu, S.Y.,, Building envelope regulations on thermal comfort in glass facade buildings and energy-saving potential for PMV-based comfort control, Build. Environ., vol. 46: p Kang, D.H., Mo, P.H., Choi, D.H., Song, S.Y., Yeo, M.S., Kim, K.W.,, Effect of MRT variation on the energy consumption in a PMV-controlled office. Build. Environ., vol. 45: p La Gennusa, M., Nucara, A., Pietrafesa, M., Rizzo, G., 7, A model for managing and evaluating solar radiation for indoor thermal comfort, Sol. Energy, vol. 8: p Nicol, J.F., Humphreys, M.A.,, Adaptive thermal comfort and sustainable thermal standards for buildings, Energy Build., vol. 4: p Singh, M.C., Garg, S.N., Jha, R., 8, Different glazing systems and their impact on human thermal comfort - Indian scenario, Build. Environ., vol. 4: p International High Performance Buildings Conference at Purdue, July 6-9,
9 Energy needs [GJ] PMV un - Paris PMV un - Milan PMV un - Rome 558, Page 8 Double H Double L Triple H Triple L E E+W S S+N E E+W S S+N E E+W S S+N E E+W S S+N S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S Trappes cooling Milano cooling Roma cooling Trappes heating Milano heating Roma heating Figure : Rome, Milan and Paris Winter PMV un distributions (the upper dot represents the maximum, the intermediate the median, the under dot the minimum and the box the interquartile range) and winter Energy Needs. International High Performance Buildings Conference at Purdue, July 6-9,
10 Energy needs [GJ] PMV un - Paris PMV un - Milan PMV un - Rome 558, Page 9 Double H Double L Triple H Triple L E E+W S S+N E E+W S S+N E E+W S S+N E E+W S S+N S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S Trappes cooling Milano cooling Roma cooling Trappes heating Milano heating Roma heating Figure : Rome, Milan and Paris Summer PMV un distributions (the upper dot represents the maximum, the intermediate the median, the under dot the minimum and the box the interquartile range) and summer Energy Needs. International High Performance Buildings Conference at Purdue, July 6-9,
11 PMV irr - Paris SUMMER WINTER PMV irr - Milan PMV irr - Rome PMV irr - Paris PMV irr - Milan PMV irr - Rome 558, Page Double H Double L Triple H Triple L E E+W S S+N E E+W S S+N E E+W S S+N E E+W S S+N S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S S Figure 4: Rome, Milan and Paris Winter (above) and Summer (under) PMV with solar irradiation statistical distributions. International High Performance Buildings Conference at Purdue, July 6-9,
DYNAMIC ANALYSIS OF ENERGY PERFORMANCE OF DIFFERENT ROOF SYSTEMS DURING THE COOLING SEASON
Proceedings of Building Simulation : DYNAMIC ANALYSIS OF ENERGY PERFORMANCE OF DIFFERENT ROOF SYSTEMS DURING THE COOLING SEASON Francesca Cappelletti, Andrea Gasparella, Giovanni Pernigotto and Piercarlo
More informationEvaluation methods for indoor environmental quality assessment according to EN15251
Summary of this article was published in the REHVA European HVAC Journal Vol 49, Issue 4 (August), 2012, pages 14-19, available at http://www.rehva.eu/en/rehva-european-hvac-journal. Evaluation methods
More informationBUILDING DESIGN AND THERMAL INERTIA: WHEN, WHY, WHERE
Int. Journal for Housing Science, Vol.34, No.4 pp. 221-231, 2010 Published in the United States BUILDING DESIGN AND THERMAL INERTIA: WHEN, WHY, WHERE R. Albatici, S. Penasa Department of Civil and Environmental
More informationAssessment Of Long-Term Visual And Thermal Comfort And Energy Performance In Open-Space Offices With Different Shading Devices
Purdue University Purdue e-pubs International High Performance Buildings Conference chool of Mechanical Engineering 214 Assessment Of Long-Term Visual And Thermal Comfort And Energy Performance In Open-pace
More informationADVANCED FAÇADES AND HVAC SYSTEMS: PRELIMINARY RESULTS OF FULL-SCALE MONITORING
ADVANCED FAÇADES AND HVAC SYSTEMS: PRELIMINARY RESULTS OF FULL-SCALE MONITORING M. Kragh, M. Colombari and M. Zobec Permasteelisa Group, Research & Engineering, 31020 San Vendemiano (TV), Italy www.permasteelisa.com,
More informationSolar gains in the glazing systems with sun-shading
729 Solar gains in the glazing systems with sun-shading G. Oliveti, N. Arcuri, R. Bruno, M. De Simone University of Calabria, Italy ABSTRACT This paper presents the optical and thermal performances of
More informationThermal comfort study of naturally ventilated office
Thermal comfort study of naturally ventilated office Marta Laska 1,* 1 Wroclaw University of Science and Technology, Faculty of Environmental Engineering, Wybrz. Wyspianskiego 27, 50-370 Wroclaw, Poland
More informationSUMMER THERMAL COMFORT IN TYPICAL FRENCH RESIDENTIAL BUILDINGS: IMPACT ASSESSMENT OF BUILDING ENVELOPE INSULATION ENHANCEMENT
13th Conference of International Building Simulation Association, Chambéry, France, August 26-28 SUMMER THERMAL COMFORT IN TYPICAL FRENCH RESIDENTIAL BUILDINGS: IMPACT ASSESSMENT OF BUILDING ENVELOPE INSULATION
More informationSKYLIGHT DESIGN PERFORMANCE EVALUATION METHOD DEVELOPMENT WITH THERMAL AND DAYLIGHT SIMULATION
SKYLIGHT DESIGN PERFORMANCE EVALUATION METHOD DEVELOPMENT WITH THERMAL AND DAYLIGHT SIMULATION Xianou Li, Frederick Wong, and Yihan Li Arup International Consultants (Shanghai) Co Ltd ABSTRACT This paper
More informationBuildings with large glazed surfaces: optimization of solar control strategies in relation to the building's thermal inertia
Buildings with large glazed surfaces: optimization of solar control strategies in relation to the building's thermal inertia Antonio Carbonari 1 1 Department of Design and Planning in Complex Environments,
More informationAnalysis of different shading strategies on energy demand and operating cost of office building
Analysis of different shading strategies on energy demand and operating cost of office building Kwiatkowski, J 1,2 ; Rucińska, J 1,2 ; Panek, A 1,2 1 Warsaw University of Technology, Faculty of Environmental
More informationIMPACT OF USING DIFFERENT MODELS IN PRACTICE A CASE STUDY WITH THE SIMPLIFIED METHODS OF ISO STANDARD AND DETAILED MODELLING PROGRAMS
IMPACT OF USING DIFFERENT MODELS IN PRACTICE A CASE STUDY WITH THE SIMPLIFIED METHODS OF ISO 13790 STANDARD AND DETAILED MODELLING PROGRAMS Kokogiannakis Georgios 1, Clarke Joe 1, Strachan Paul 1 1 Energy
More informationA PARAMETRIC STUDY ON WINDOW-TO-FLOOR RATIO OF THREE WINDOW TYPES USING DYNAMIC SIMULATION
A PARAMETRIC STUDY ON WINDOW-TO-FLOOR RATIO OF THREE WINDOW TYPES USING DYNAMIC SIMULATION Energy for Sustainability 2015 Sustainable Cities: Designing for People and the Planet Coimbra, 14-15 May, 2015
More informationThe Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort
The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort Ongun Berk Kazanci, Bjarne W. Olesen 1 1 International Center for Indoor Environment and
More informationPrediction of Thermal Comfort. mech14.weebly.com
Prediction of Thermal Comfort Thermal Sensation Scale (Rohles & Nevins, 1974) Fanger s Thermal Comfort Model (1982) Steady state model, applicable for M 3 met and a large group of people Fanger s Thermal
More informationREAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS. Galway, Ireland
REAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS Magdalena Hajdukiewicz 1,2,3, Padraig O Connor 1, Colin O Neill 1, Daniel Coakley 1,2,3, Marcus M. Keane 1,2,3, Eoghan Clifford 1,2,3 1 Department
More informationOpportunities and Limitations of Building Precooling
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 1994 Opportunities and Limitations of Building Precooling K. R. Keeney Purdue
More informationSTEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS
STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS 1. ABSTRACT In modern architecture the buildings are often designed with large glass facades or windows. Due to these
More informationOPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS
OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS Bjarne W. Olesen Ph. D, International Centre for Indoor Environment and Energy, Department of Mechanical Engineering, Technical
More informationOptimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models
L. Pagliano et al, I: Optimization of air tightness and night ventilation for Passive houses in Italian climates... 1 Optimization of air tightness and night ventilation for Passive houses in Italian climates
More informationAssessment of thermal comfort near a glazed exterior wall
Assessment of thermal comfort near a glazed exterior wall Timothy Anderson 1, Mark Luther 2 and Tim Brain 3 1 School of Engineering, Auckland University of Technology, Auckland 1142, New Zealand 2 School
More informationJOTUN Cool Shades. Impact of the TSR Value on the Users Comfort and the Energy Performance of Buildings. ai³ Werner Jager
JOTUN Cool Shades Impact of the TSR Value on the Users Comfort and the Energy Performance of Buildings ai³ Werner Jager Exclusion of warranty: All tables, graphical charts and results presented within
More informationQuantifying Comfort to Assist in the Window Selection Process
Quantifying Comfort to Assist in the Window Selection Process Kerry Haglund, Efficient Windows Collaborative Jim Larsen, Cardinal Glass Industries June 18, 2015 WDMA Technical & Manufacturing Conference
More informationAttaining Thermal Comfort in. Buildings with Predominantly. Glazed Facades. presented to: ANSYS Boston Regional Conference
Attaining Thermal Comfort in Buildings with Predominantly Glazed Facades presented to: ANSYS Boston Regional Conference September 14, 2011 Case Study Background High floor to ceiling windows Large skylight
More informationModeling Energy Consumption Effects of Glazing
Modeling Energy Consumption Effects of Glazing Daniel Lu 12/7/2012 Table of Contents Introduction... 3 Design Options... 5 Option 1... 5 Option 2... 5 Preliminary Energy Simulation... 7 Objectives... 7
More informationScienceDirect. Influence of the balcony glazing construction on thermal comfort of apartments in retrofitted large panel buildings
Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 108 (2015 ) 481 487 7th Scientific-Technical Conference Material Problems in Civil Engineering (MATBUD 2015) Influence of the
More informationHVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya
HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya (vahid.vakiloroaya@engineer.com) ABSTRACT: The overall attainable reduction in energy consumption and enhancement of
More informationUtilizing Heat Dump Capacity of a Small Pond Attached to Infloor Slab of a Net-Zero Energy House
Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2010 Utilizing Heat Dump Capacity of a Small Pond Attached to Infloor Slab of a Net-Zero
More informationLong term evaluation of building energy performance: comparison of the test reference year and historical data series in the North Italian climates
Long term evaluation of building energy performance: comparison of the test reference year and historical data series in the North Italian climates Giovanni Pernigotto University of Padova, Vicenza, Italy
More informationA Case Study on the Daylighting and Thermal Effects of Fixed and Motorized Light Louvers
A Case Study on the Daylighting and Thermal Effects of Fixed and Motorized Light Louvers Yuxiang Chen 1, Samson Yip 1, Andreas Athienitis 1 1 Building, Civil and Environmental Engineering, Concordia University,
More informationDesigning Air-Distribution Systems To Maximize Comfort
Designing Air-Distribution Systems To Maximize Comfort By David A. John, P.E., Member ASHRAE An air-distribution system that provides occupant thermal comfort can be a complicated system to predict and
More informationCOMPARATIVE SUMMER THERMAL AND COOLING LOAD PERFORMANCE OF NATURAL VENTILATION OF CAVITY ROOF UNDER THREE DIFFERENT CLIMATE ZONES
COMPARATIVE SUMMER THERMAL AND COOLING LOAD PERFORMANCE OF NATURAL VENTILATION OF CAVITY ROOF UNDER THREE DIFFERENT CLIMATE ZONES Lusi Susanti 1, Hiroshi Matsumoto 2, and Hiroshi Homma 2 1 Department of
More informationThermal comfort evaluation of natural ventilation mode: case study of a high-rise residential building
J. Zuo, L. Daniel, V. Soebarto (eds.), Fifty years later: Revisiting the role of architectural science in design and practice: 50 th International Conference of the Architectural Science Association 2016,
More informationThermal Characteristics of a Vernacular Building Envelope
Thermal Characteristics of a Vernacular Building Envelope Priyanka Dhar, M.Tech. Department of Energy, Tezpur University, Tezpur, 784028, Assam, India Pallavi Borah, M.Tech. Department of Energy, Tezpur
More informationDesigning for thermal comfort near a glazed exterior wall. * School of Engineering, Auckland University of Technology, Auckland, New Zealand
Designing for thermal comfort near a glazed exterior wall T.N. Anderson ǂ *, M.B. Luther ** * School of Engineering, Auckland University of Technology, Auckland, New Zealand ** School of Architecture and
More informationInfluence Of Building Zoning On Annual Energy Demand
Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Influence Of Building Zoning On Annual Energy Demand Lisa Rivalin Mines ParisTech,
More informationNearly Zero Energy Building in Lecco Modern technological building compared to an ancient Villa
Nearly Zero Energy Building in Lecco Modern technological building compared to an ancient Villa Matteo BRASCA *, Oscar Luigi PAGANI **, Kanza RAUF*** * partner - AIACE S.r.l. società di ingegneria, contract
More informationIMPACT OF SOLAR IRRADIATION MODELS ON BUILDING REFURBISHMENT MEASURES FROM MULTI-OBJECTIVE OPTIMIZATION
IMPACT OF SOLAR IRRADIATION MODELS ON BUILDING REFURBISHMENT MEASURES FROM MULTI-OBJECTIVE OPTIMIZATION Alessandro Prada 1, Giovanni Pernigotto 2, Francesca Cappelletti 3, Andrea Gasparella 1 1 Free University
More informationFree University of Bolzano/Bozen, Faculty of Science and Technology, Bolzano, Italy -
Comparison of Different Glare Indices through Metrics for Long Term and Zonal Visual Comfort Assessment Anna Maria Atzeri 1, Francesca Cappelletti 2, Andrea Gasparella 1 1 Free University of Bolzano/Bozen,
More informationAssessing the energy performance of modern glass facade systems
Assessing the energy performance of modern glass facade systems Abdelsalam Aldawoud * Architectural Engineering Department, University of Sharjah Sharjah, United Arab Emirates Abstract. The design and
More informationSimplified methods to evaluate energy use for space cooling in the energy certification
Simplified methods to evaluate energy use for space cooling in the energy certification Alessio Gastaldello and Luigi Schibuola University IUAV of Venice, Italy Corresponding email: luigi.schibuola@iuav.it
More informationVentilative Cooling potential tool
Ventilative Cooling potential tool User guide Version 1.0 IEA EBC Programme Annex 62 Ventilative Cooling AUTHORS: ANNAMARIA BELLERI EURAC RESEARCH Institute for renewable energy Druso 1 39100 Bolzano Italy
More informationModelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates
Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates Kittitach Pichatwatana, and Fan Wang Abstract This paper examines the TAS computer
More informationLOCAL VENTILATION SYSTEMS: SOME INVESTIGATIONS ABOUT COMFORT LEVELS AND ENERGY DEMANDS
LOCAL VENTILATION SYSTEMS: SOME INVESTIGATIONS ABOUT COMFORT LEVELS AND ENERGY DEMANDS Elena Buchberger - ebuch@iuav.it Luca Porciani, porciani@iuav.it Fabio Peron, fperon@iuav.it Universita IUAV di Venezia,
More informationAn enhancement of the daylighting from side-window using two-section venetian blind
An enhancement of the daylighting from side-window using two-section venetian blind Vichuda Mettanant 1,2, Pipat Chaiwiwatworakul 1,2,*, Pattana Rakkwamsuk 3 1 The Joint Graduate School of Energy and Environment,
More informationEffects of Fixed and Motorized Window Louvers on the Daylighting and Thermal Performance of Open-Plan Office Buildings
Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 214 Effects of Fixed and Motorized Window Louvers on the Daylighting and Thermal Performance
More informationA Field Study of Thermal Comfort in Open-plan Office Buildings during Transition Seasons in Harbin. Yunsong Han 1, 2, Huixuan Sun 1, 2, Cheng Sun 1, 2
A Field Study of Thermal Comfort in Open-plan Office Buildings during Transition Seasons in Harbin Yunsong Han 1, 2, Huixuan Sun 1, 2, Cheng Sun 1, 2 1 School of Architecture, Harbin Institute of Technology,
More informationThermal Characteristics and Energy Performance of Double Skin. Façade System in the Hot Summer and Cold Winter Zone
Thermal Characteristics and Energy Performance of Double Skin Façade System in the Hot Summer and Cold Winter Zone L.F. Shu 1, G.Q. He 1,*, S.M. Zhang 1 and Q.A. Bai 2 1 College of Civil Engineering and
More informationCharacterization and performance evaluation of solar shading devices
Characterization and performance evaluation of solar shading devices Inês P. Santos, Research Assistant, Department of Civil Engineering, Technical University of Denmark; isa@byg.dtu.dk, www.byg.dtu.dk
More informationCOMPARISON OF THERMAL PERFORMANCE OF DIFFERENT WALL STRUCTURES
HEFAT2012 9 th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics 16 18 July 2012 Malta COMPARISON OF THERMAL PERFORMANCE OF DIFFERENT WALL STRUCTURES Ozel M.* and Ozel C. *Author
More informationAllowing for Thermal Comfort in Free-running Buildings in the New European Standard EN15251
Allowing for Thermal Comfort in Free-running Buildings in the New European Standard EN15251 Fergus Nicol, Low Energy Architecture Research Unit (LEARN), School of Architecture, London Metropolitan University,
More informationTowards nzeb buildings: a historical building case study
Towards nzeb buildings: a historical building case study The recast of EU Directive 2010/31 introduced the concept of (nearly) zero energy building (NZEB). In Italy this challenge is remarkable: existing
More informationAssessing thermal comfort of dwellings in summer using EnergyPlus
Assessing thermal comfort of dwellings in summer using EnergyPlus Irina Bliuc, Rodica Rotberg and Laura Dumitrescu Gh. Asachi Technical University of Iasi, Romania Corresponding email: irina_bliuc@yahoo.com
More informationYoung Cities Research Briefs 07 Architectural Energy Efficiency
Young Cities Research Briefs 7 Architectural Energy Efficiency Farshad Nasrollahi 1 Introduction Decreasing the energy demand of buildings by applying cost-intensive measures (such as the addition of insulation
More informationPassive house optimization for Southern Italy based on the New Passivhaus Standard
Passive house optimization for Southern Italy based on the New Passivhaus Standard Paolo Zangheri end-use Effi ciency Research Group, Dipartimento di Energia Politecnico di Milano, Italy paolo.zangheri@polimi.it
More informationDeliverable D.3.3 Common computer tool for building simulations -Manual- English version July 2006
Contract No. EIE-2003-RURASU-223 Deliverable D.3.3 Common computer tool for building simulations -Manual- English version July 2006 Prepared by: Kostas Pavlou University of Athens, Physics Department (IASA
More informationAn Assessment in the Heat Gain and Loss Through Opaque Elements in Commercial Buildings in Brazil
Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 212 An Assessment in the Heat Gain and Loss Through Opaque Elements in Commercial Buildings
More informationDesign guidelines for direct ground cooling systems in different climates
Design guidelines for direct ground cooling systems in different climates Adriana Angelotti and Giulio Solaini Dipartimento BEST, Politecnico di Milano, Milano, Italy ABSTRACT: Direct ground cooling systems
More informationOPENING DESIGN TO IMPROVE THE NATURAL VENTILATION PERFORMANCE OF HIGH-RISE RESIDENTIAL BUILDINGS
OPENING DESIGN TO IMPROVE THE NATURAL VENTILATION PERFORMANCE OF HIGH-RISE RESIDENTIAL BUILDINGS Cho Rong Kim 1, Ga Young Cho 1, Sun Woo Lee 1, Myoung Souk Yeo 2, and Kwang Woo Kim 2 1 Department of Architecture,
More informationInternational Journal of Civil and Environmental Engineering 3:2 2011
Investigating the Effectiveness of Self-Shading Strategy on Overall Thermal Transfer Value and Window Size in High Rise Buildings Mansour Nikpour, Mohd Zin kandar, Mohammad Ghomeshi, Nima Moeinzadeh, Mohsen
More informationIntroduction to basics of energy efficient building design
Introduction to basics of energy efficient building design Pierre Jaboyedoff Seminar on Energy Efficient & Thermally Comfortable Buildings in Amravati For CRDA, Andhra Pradesh May 2 nd 2017 Indo-Swiss
More informationModule 3: Simulation and Data Analysis
INSTRUCTIONAL MODULES DEMONSTRATING BUILDING ENERGY ANALYSIS USING A BUILDING INFORMATION MODEL Christian Daniel Douglass Industrial and Enterprise Systems Engineering December 1, 2010 Module Summary In
More informationSolar cooling design: a case study
Eco-Architecture IV 399 Solar cooling design: a case study S. Grignaffini & M. Romagna Department of Astronautic, Electric and Energetic Engineering, Sapienza, University of Rome, Italy Abstract Throughout
More informationInformation paper 17. Prepared by: David Clark. book:
Information paper 17 Thermal comfort standards Prepared by: David Clark A paper referenced in the book: Cundall Johnston & Partners LLP. 2013 Issue 1.0: 29 July 2013 This information paper is one of a
More informationENERGY DEMAND ANALYSIS AND ENERGY LABELLING OF NEW RESIDENTIAL BUILDINGS IN TUSCANY (ITALY)
ENERGY DEMAND ANALYSIS AND ENERGY LABELLING OF NEW RESIDENTIAL BUILDINGS IN TUSCANY (ITALY) F. Fantozzi, F. Leccese, G. Salvadori, G. Tuoni Department of Energy L. Poggi Faculty of Engineering, University
More informationInnovative Systems for Energy Efficient Building Envelopes Applications at middle latitudes (temperate/mesothermal climates)
Innovative Systems for Energy Efficient Building Envelopes Applications at middle latitudes (temperate/mesothermal climates) MONICA ROSSI 1 1 Facoltà di Architettura - Dipartimento DPUU, Università degli
More informationEnergy and Thermal Comfort Management in a Kindergarten School Building in the South of Portugal in Winter Conditions
4th IASME/WSEAS International Conference on ENERGY, ENVIRONMENT, ECOSYSTEMS and SUSTAINABLE DEVELOPMENT (EEESD'8) Algarve, Portugal, June 11-13, 8 Energy and Thermal Comfort Management in a Kindergarten
More informationStudy of the energy performance of a retrofitting office
Study of the energy performance of a retrofitting office Paolo Valdiserri CIRI Edilizia Costruzioni, Università di Bologna paolo.valdiserri@unibo.it Abstract Building retrofitting is the most feasible
More informationATBU, Journal of Science, Technology & Education (JOSTE); Vol. 3 (4), December, 2015 ISSN:
THERMAL COMFORT ASSESSMENT OF ENGINEERING WORKSHOP: A CASE STUDY OF UNIVERSITY OF MAIDUGURI By S. Shodiya 1 *, M.B. Oumarou 1, A.T Quadri 2, and A.B. Muhammed 1 1 Department of Mechanical Engineering,
More informationSolar-Assisted Space Heating of a Highly Insulated Energy Efficient House
Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2010 Solar-Assisted Space Heating of a Highly Insulated Energy Efficient House Toktam
More informationSimulation Before Design? A New Software Program for Introductory Design Studios
SIMULATION BEFORE DESIGN? 1 Simulation Before Design? A New Software Program for Introductory Design Studios TROY NOLAN PETERS California Polytechnic State University INTRODUCTION The 2010 Imperative states:
More informationADAPTIVE THERMAL COMFORT - AN EXTENDED APPROACH FOR CONDITIONED INDOOR ENVIRONMENT USING COMPUTATIONAL FLUID DYNAMICS
16 th International Conference on Clean Energy (ICCE-2018) 9-11 May 2018, Famagusta, N. Cyprus ADAPTIVE THERMAL COMFORT - AN EXTENDED APPROACH FOR CONDITIONED INDOOR ENVIRONMENT USING COMPUTATIONAL FLUID
More informationEnhancing the Energy and Non-Energy Performance of Existing Buildings: a Multi- Objective Approach
Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Enhancing the Energy and Non-Energy Performance of Existing Buildings: a Multi-
More informationA STUDY ON DESIGN OPTIMIZATION OF A NEAR NET-ZERO ENERGY HOUSE
Int. Journal for Housing Science, Vol.37, No.1 pp.23-31, 2013 Published in the United States A STUDY ON DESIGN OPTIMIZATION OF A NEAR NET-ZERO ENERGY HOUSE Narghes Doust, Gabriele Masera and Marco Imperadori
More informationFindings of Field Survey for Thermal Comfort and Ventilation in US Office Buildings
Findings of Field Survey for Thermal Comfort and Ventilation in US Office Buildings Liangcai Tan 1, Samir Moujaes, HDR Inc. University of Nevada Las Vegas SUMMARY This paper presents the measured data
More informationANALYSIS AND MITIGATION OF THERMAL EFFECTS ON A LARGE FACADE-MOUNTED PV ARRAY
ANALYSIS AND MITIGATION OF THERMAL EFFECTS ON A LARGE FACADE-MOUNTED PV ARRAY A. Driesse 1, S. J. Harrison 2, Q. Lin 2 1 Queen's University, Integrated Learning Center, Kingston, ON, Canada; 2 Queen's
More informationAvailable online at ScienceDirect. Energy Procedia 78 (2015 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 1093 1098 6th International Building Physics Conference, IBPC 2015 Verifying a need of artificial cooling - a simplified
More informationLecture 3: Utilization of Passive Solar Technology
Lecture 3: Utilization of Passive Solar Technology http://www.cs.kumamoto-u.ac.jp/epslab/apsf/ Lecturers: Syafaruddin & Takashi Hiyama syafa@st.eecs.kumamoto-u.ac.jp hiyama@cs.kumamoto-u.ac.jp Time and
More informationHUMAN-BEHAVIOR ORIENTED CONTROL STRATEGIES FOR NATURAL VENTILATION IN OFFICE BUILDINGS
HUMAN-BEHAVIOR ORIENTED CONTROL STRATEGIES FOR NATURAL VENTILATION IN OFFICE BUILDINGS Haojie Wang 1, Qingyan Chen 1,2* 1 School of Mechanical Engineering, Purdue University, West Lafayette, IN 47907 2
More informationRECENT CZECH BUILDING ENERGY SIMULATION CASE STUDIES
RECENT CZECH BUILDING ENERGY SIMULATION CASE STUDIES )'UNDO7'XQRYVND01HX]LO96NUODQW &]HFK7HFKQLFDO8QLYHUVLW\LQ3UDJXH )DFXOW\RI0HFKDQLFDO(QJLQHHULQJ 7HFKQLFND 3UDJXH&]HFK5HSXEOLF $%675$&7 By describing
More informationcarbon-neutral architectural design Pablo La Roche CRC Press Taylor & Francis Croup Boca Raton London NewYork CRC Press is an imprint of the
carbon-neutral architectural design Pablo La Roche CRC Press Taylor & Francis Croup Boca Raton London NewYork CRC Press is an imprint of the Taylor fit Francis Group, an informs business Contents Preface
More informationFEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF
FEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF Oliver Baumann 1, and Claudius Reiser 1/2 1 Ebert & Baumann Consulting Engineers, Washington, D.C. 2 Ebert-Ingenieure GmbH &Co. KG, Munich,
More informationAvailable online at ScienceDirect. Energy Procedia 78 (2015 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 2857 2862 6th International Building Physics Conference, IBPC 2015 Optimized Blind Control Method to minimize Heating,
More informationPhase-Change Wallboard and Mechanical Night Ventilation in Commercial Buildings: Potential for HVAC System Downsizing
Phase-Change Wallboard and Mechanical Night Ventilation in Commercial Buildings: Potential for HVAC System Downsizing Corina Stetiu Helmut E. Feustel Lawrence Berkeley National Laboratory, Berkeley, CA
More informationThermal Comfort and Energy Consumption according to the Indoor Control Logic
Thermal Comfort and Energy Consumption according to the Indoor Control Logic S. Kim 1 and D. Song 2 1 Department of Civil and Environmental System Engineering Sungkyunkwan University, Suwon-si, Gyeonggi-do
More informationChapter 7. Passive Solar Contents
Chapter 7. Passive Solar Contents 7.1 Introduction 7.2 Types of Passive Solar Systems 7.3 Advantages and Disadvantages 7.4 General Design Principles 7.5 Design Information for Direct System 7.6 Design
More informationPerformance Evaluation Of Thermally Activated Glass Fibre Reinforced Gypsum Building Equipped With Desiccant System
Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering July 2018 Performance Evaluation Of Thermally Activated Glass Fibre Reinforced Gypsum
More informationSUBJECTIVE AND MEASURED THERMAL COMFORT IN ITALIAN UNIVERSITY CLASSROOMS IN HEATED AND FREE RUNNING CONDITIONS
SUBJECTIVE AND MEASURED THERMAL COMFORT IN ITALIAN UNIVERSITY CLASSROOMS IN HEATED AND FREE RUNNING CONDITIONS Stefano Corgnati, Roberta Ansaldi, and Marco Filippi Department of Energy (DENER), Politecnico
More informationPerformance Evaluation of a Passive Chilled Beam System and Comparison with a Conventional Air System
Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2016 Performance Evaluation of a Passive Chilled Beam System and Comparison with a Conventional
More informationDEVELOPMENT OF A DESIGN TOOL TO SIMULATE THE THERMAL PERFORMANCE OF DIRECT GAIN PASSIVE SOLAR SYSTEMS USING TMY3 DATA
DEVELOPMENT OF A DESIGN TOOL TO SIMULATE THE THERMAL PERFORMANCE OF DIRECT GAIN PASSIVE SOLAR SYSTEMS USING TMY3 DATA Alfredo Fernández-González University of Nevada, Las Vegas 4505 Maryland Parkway, Box
More informationObservation of Liquid-filled Window without Presence of Liquid in Test Chamber
SSP - JOURNAL OF CIVIL ENGINEERING Vol. 11, Issue 2, 2016 DOI: 10.1515/sspjce-2016-0020 Observation of Liquid-filled Window without Presence of Liquid in Test Chamber Ján Lojkovics Technical University
More informationQ-Air unique selling propositions in detail
Q-Air unique selling propositions in detail Afraid of sitting at the window in winter? Q-Air offers a U value so low that there can be no perceptible cold air movement at the panoramic window even in coldest
More informationThermal Comfort Assessment Based on Measurement and Questionnaire Surveys in a Large Mechanically Ventilated Space
Thermal Comfort Assessment Based on Measurement and Questionnaire Surveys in a Large Mechanically Ventilated Space Ali Alzaid 1, Maria Kolokotroni 1, Hazim Awbi 2 1 Mechanical Engineering, Brunel University
More informationPOST OCCUPANCY DESIGN INERVENTION TO IMPROVE COMFORT AND ENERGY PERFORMANCE IN A DESERT HOUSE
POST OCCUPANCY DESIGN INERVENTION TO IMPROVE COMFORT AND ENERGY PERFORMANCE IN A DESERT HOUSE Vidar Lerum Arizona State University P O Box 871605, Tempe, AZ, 85287-1605, USA vidar.lerum@asu.edu Venkata
More informationBuilding Envelope and Fabric Load Tests performed on ApacheSim in accordance with ANSI/ASHRAE Standard
Building Envelope and Fabric Load Tests performed on ApacheSim in accordance with ANSI/ASHRAE Standard 140-2007 ApacheSim Version 6.0.4 February 2010 Integrated Environmental Solutions www.iesve.com BOSTON,
More informationAvailable online at ScienceDirect. Procedia Engineering 145 (2016 ) 18 25
Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 145 (2016 ) 18 25 International Conference on Sustainable Design, Engineering and Construction Applicability of Radiant Heating-Cooling
More informationA Method for Driving the Solar Control Mechanism Selection
A Method for Driving the Solar Control Mechanism Selection Christopher Nilsson & Vitaliya Mokhava Master thesis in Energy-efficient and Environmental Buildings Faculty of Engineering Lund University Lund
More informationCost-Benefit Analysis of Dwelling Retrofit Options
Cost-Benefit Analysis of Dwelling Retrofit Options The objective was to study the thermal behaviour of the existing house and suggest cost effective improvements. Over recent years the energy efficiency
More informationSolar-Protective Glazing for Cold Climates
Lund University Sweden Lund Institute of Technology Department of Building Science Report TABK--98/3053 Solar-Protective Glazing for Cold Climates A Parametric Study of Energy Use in Offices Marie-Claude
More informationPassive Thermal Control for Window Insulation
Passive Thermal Control for Window Insulation E. Konroyd-Bolden 1, Dr. Z. Liao 1, 1 Ryerson University; Dept. of Architectural Science *Corresponding Author: 392 Pine Avenue, Unit 602, Oakville, Ontario,
More information