Nearly Zero Energy Building in Lecco Modern technological building compared to an ancient Villa

Size: px
Start display at page:

Download "Nearly Zero Energy Building in Lecco Modern technological building compared to an ancient Villa"

Transcription

1 Nearly Zero Energy Building in Lecco Modern technological building compared to an ancient Villa Matteo BRASCA *, Oscar Luigi PAGANI **, Kanza RAUF*** * partner - AIACE S.r.l. società di ingegneria, contract professor Politecnico di Milano School of Architectural Engineering, Milan, Italy (matteo.brasca@polimi.it) ** partner - AIACE S.r.l. società di ingegneria, contract professor Politecnico di Milano School of Architectural Engineering, Milan, Italy (oscar.pagani@aiace-srl.it) *** student - Politecnico di Milano M.Sc. in Architectural Engineering, Milan, Italy (zk.rauf@gmail.com) Keywords: nearly Zero-energy building, dynamic/static simulation, energy efficiency Field of Interest: Building Design; Topic of Interest: High performance buildings Main paper focus: General Framework; Paper Content Classification: Technical Abstract The building is located in Lecco, Italy, into an industrial area and it hosts offices (600 m 2 ) for a software company. The structure is an extension of an existing building originated as a residential villa. The new headquarter is an example of climate sensitive building, reacting, in an adaptive way, to seasons and different climates. Temperate climate, with cold winter and hot/wet summer has influenced building's shape and different elevations, depending on their orientation. The building is oriented to south, trying to exploit solar gains and balancing them with internal ones. Building's passive envelope minimizes thermal energy dissipation, with strong use of thermal insulation (transmittance from 0.08 to 0.20 W/m 2 K); to the west, a green wall protects offices from solar radiation. Green is watered with raining water, which has been gathered, filtered and stored in underground storage tanks. Photovoltaic panels on the roof (5.5 kwp) and on the south facing facade (6.0 kwp) provide electricity. Building-Envelope technology ensures a quick construction, flexibility, maintainability and possibility to change wall composition, depending on the expected performance. Ventilated rainscreen cladding avoids condensation and overheating; different coatings (fibrecement and copper) cover different volumes. Aluminum frame with thermal break and low-e triple glass give windows an average thermal transmittance U < 1.0 W/m 2 K. Advanced systems have been designed to optimise the contribution of the envelope. A heat pump provides building's heating and cooling through ceiling radiant panels; depending on the external climatic conditions, an efficient air handling unit ensures long free cooling periods. The building has smart thermoregulation and plant s electrical automation. The building uses geothermal and solar energy for heating and cooling. Different energy simulations (performed with different calculation software) show that the building belongs to best Italian energy class (A+ class), with an yearly heating primary energy demand of 2.97 kwh/m 3 y. The result has been obtained through a good integration between building features and installations starting from the design optimization, inspired to nature s efficiency.

2 1. Introduction The building is located in Lecco, Italy, into an industrial area and it hosts offices (600 m 2 ) for a software company. The structure will be an extension of an existing building originated as a residential villa. The new headquarter will be an example of climate sensitive building reacting, in an adaptive way, to the seasons and different climates. Temperate climate, with cold winter and hot/wet summer has influenced building's shape and different elevations, depending on their orientation. The building is oriented to south, trying to exploit solar gains and balancing them with internal ones. Building's passive envelope minimizes thermal energy dissipation, with strong use of thermal insulation (transmittance from 0.08 to 0.20 W/m 2 K); to the west, a green wall protects offices from solar radiation. Green is watered with raining water, which has been gathered, filtered and stored in underground storage tanks. Photovoltaic panels on the roof (5.5 kwp) and on the south facing facade (6.0 kwp) provide electricity. Building-Envelope technology ensures a quick construction, flexibility, maintainability and possibility to change wall composition depending on the expected performance. Ventilated rainscreen cladding avoids condensation and overheating; different coatings (fibrecement and copper) cover different volumes. Aluminium frames with thermal break and low-e triple glass give windows an average thermal transmittance U < 1.0 W/m 2 K. Advanced systems have been designed to optimise the contribution of the envelope. A heat pump provides building's heating and cooling through ceiling radiant panels; depending on the external climatic conditions, an efficient air handling unit ensures long free cooling periods. The building has smart thermoregulation and plant s electrical automation. The building uses geothermal and solar energy for heating and cooling. The building is an example of a good integration between building features and installations starting from the design optimization, inspired to nature s efficiency [1]: it belongs to best Italian energy class (A+ class), with an yearly heating primary energy demand of 2.97 kwh/m 3 y (CENED software, with the contribution of the photovoltaic system). Figure 1 the new Headquarter of GR informatica company 2. Building Models and Simulation Software Two software were chosen to carry out the energy simulations for the GR Informatica Office building: Cened+ 1 and EnergyPlus 2. EnergyPlus is a simulation engine and it was used coupled with Design Builder 3 software for the setting of the calculation model. Energy Plus and Cened+ offer two complementary types of energy calculations. Cened+ is a software that performs steady state simulation along 24 hours under standard conditions 4. Energy Plus performs dynamic simulation better considering the components of the building heat balance and the issues of the plants and, in particular, in this case, it is able to evaluate the influence of the natural ventilation on the internal comfort conditions. These two complementary approaches were used to

3 evaluate the different strategies used in the building. Lastly, the use of two software offered a better chance to validate the building models, to verify the accuracy and reliability of the calculation and to have a reference point for future monitoring of the building. 3. Building Models In order to compare the energy requirements of the designed low energy solution with a usual older construction, the existing building, that have approximately the same volume than the new one, was modelled and simulated to calculate the primary energy demand. The location of the new and existing building is shown in Figure 2. Existing Building New Headquarter Figure 2 Plan of the area in Lecco, Italy Models for the two buildings were created using DesignBuilder with the surrounding site plan to take into account the shadows cast by the surrounding buildings (in this case a very critical point because of the shadows that restrict the use of passive solar strategies). The idea was to compare the energy demand of the existing building with the energy efficient solution just next to it. Simulation models are shown in Figure 3. Figure 3 Design Builder Model of the Existing Building (on the left) and New Building (on the right)

4 Figure 4 Summer (on the Left) and Winter (on the right) Scheme Design 4. Benchmark Models In order to obtain benchmark solutions to compare the results obtained with the dynamic simulations, the software CENED+ was used to create steady state calculation models of the existing building and the new one. At this stage, in order to have comparable results, an EnergyPlus simulation was performed assuming the plant operation for 24 hours a day, both in summer and in winter (without using the natural ventilation) and a fixed comfort temperature. The comparison is shown in Figure 5. Benchmark heating primary energy demand [kwh/m 3 y] Cened Energy Plus 57,00 61,17 Benchmark cooling primary energy demand [kwh/m 3 y] 2,18 2,77 Cened Energy Plus 2,70 2,60 4,84 4,93 New building (without PV system) Existing Building New building (without PV system) Figure 5 Benchmark comparison between Cened+ and EnergyPlus calculation results Existing Building The above graph shows the yearly heating and cooling primary energy demand, calculated (KWh/m 3 y) by Cened+ and EnergyPlus for the existing as well as the new office building (without the contribution of the photovoltaic system). It can be noted that the difference between the results obtained with the two software are almost the same with an error of less than 10%; in the summer season differences obtained are slightly higher. This confirms the reliability of both the models for further analysis. 5. Energy Demand Comparison: Existing and New Office Building The purpose of modelling the existing building was to provide a direct comparison between the primary energy demand of a regular building and a nearly zero-energy building (class A+ CENED). Based on results shown in Figure 5 and Figure 6, we note that the new GR Informatica office building is 10 to 12 lesser energy intensive, compared to the existing building as far as the heating load. The cooling energy demand of the old building, however, is comparable to the new building (Figure 6). The reason is probably that the old building has significant air infiltration and, above all, high-mass walls that

5 allow to shift the heat wave at night. Another aspect is the presence of the ventilated roof that protects from summer solar radiation the office spaces. Comparison Old and New Buildings Yearly Primary Energy demand (kwh/m 3 y) 70,0 60,0 50,0 40,0 30,0 20,0 10,0 2,77 4,93 2,60 61,17 Cooling Heating 0,0 New building (without PV system) Existing Building Figure 6 Comparing between Existing and New Building primary energy demand 6. Sensitivity Analysis of the New Building Energy Demand After the benchmark models have confirmed the reliability of the building model, the actual use of offices and plant was simulated, in order to estimate the effective primary energy demand of the building. Till now, any analysis were carried out on the basis of continuous operation for 24 hours of the building, the additional simulations assume the actual use of the office, that is from 08:00 to 18:00 with the weekend off. At the same time, various situations were simulated to analyse the impact of each option on the energy demand of the building. Condition 5 window trasmittance U floor = 1.80 W/m 2 K 4,96 86,3% 1,59 69,3% Condition 6 with window shading devices 4,57 71,8% 1,35 43,6% Table 1 Sensitivity analysis of the New Building Primary Energy Demand 6,00 CASES Sensitivity Analysis of the New Building Primary Energy Demand 5,49 Prim.En. Heating demand Difference Prim.En. Cooling demand Difference [kwh/m 3 y] [kwh/m 3 y] Condition 0 final desing with PV panels 2,66 0,0% 0,94 0,0% Condition 1 final desing without PV panels 4,47 68,0% 1,58 68,0% Condition 2 wall trasmittance U wall = 0.27 W/m 2 K 5,49 106,6% 1,57 66,7% Condition 3 roof trasmittance U roof = 0.24 W/m 2 K 4,68 76,1% 1,63 73,1% Condition 4 floor trasmittance U floor = 0.30 W/m 2 K 4,47 68,0% 1,59 69,1% Yearly Primary Energy Demand [kwh/m 3 y] 5,00 4,00 3,00 2,00 1,00 2,66 0,94 4,96 4,68 4,47 4,47 1,58 1,57 1,63 1,59 1,59 4,57 1,35 Heating Cooling 0,00 Condition 0 Condition 1 Condition 2 Condition 3 Condition 4 Condition 5 Condition 6

6 Figure 7 Sensitivity analysis of the New Building Primary Energy Demand Firstly, the benchmark model of the building was simulated for actual working hours, as mentioned above. The first calculation option (condition 0) has been analysed taking into account the energy production of the photovoltaic panels provided for the building. In this case we used the value of energy production for photovoltaic panels calculated with the software CENED +. The next step was to modify the thermal conductivity (U-Value) of each building component one by one, that is, walls (cond. 2), roofs (cond. 3), floors (cond. 4), and windows (cond. 5), while keeping the other elements unchanged. The components performance assumed, in any case, respect the values of thermal conductivity as required by Law. Results of the parametric study are shown in Table 1 and in Figure 7. Based on the results shown in Figure 7, in the case of heating primary energy, the maximum increase is achieved by increasing the U-value of the walls, up to the minimum requirement of Regulations. This is because a large portion of the building fabric is opaque and walls affect a lot the overall conduction losses through the envelope. This is also the reason why there is a high increase in heating primary energy by reducing the performance of the windows: the percentage of openings is quite low and most of them face south-east or north. From the results, it can be deduced that, by increasing the design transmittance to those required by Regulations, the influence of the roof (from U = 0.19 W/m 2 K to U = 0.24 W/m 2 K, difference +88%) and the floor (from U = 0.16 W/m 2 K to U = 0.30 W/m 2 K, difference +88%) on the heating primary energy are lower than the influence of walls: the reason is mainly due to the articulated shape of the building (high S/V ratio) but also to the better thermal performance which characterizes the vertical envelope (U = 0.10 W/m 2 K compared to U = 0.27 W/m 2 K, difference +170%). The variation of the cooling primary energy demand follows variations of the heating demand too: considerable differences, that can be seen, are the greater influence of the roof (the solar heat load is greater in summer, neglecting the shading effect of photovoltaic panels). 7. Simulating the Performance of the Building Envelope The final step in our analysis was to understand the efficiency of the building without the support of an HVAC system for the thermal treatment of the space inside. Figure 8 and Figure 9 show a comparison of the average monthly inside operative temperature, in comparison with the outside dry-bulb temperatures, with plant and without plant situation. The natural ventilation is kept at 0.8 ach with 0.3 ach as infiltration. Monthly Average Temperatures With Heating and Cooling Plant Temperature ( C) 17,7 17,7 18,0 6,2 19,1 10,9 21,5 15,5 22,8 19,0 24,1 23,9 21,7 20,2 22,7 17,8 19,5 11,6 18,1 17,6 6,3 0,0 2,3 1, Months of the Year Operative Temperature C Outside Dry Bulb Temperature C Figure 8 Comparison between outside air temperature and operative temperature with plant contribution

7 It can be noted here that the average monthly temperature during the heating season is around 18 C. This is because the HVAC system was allowed to set back from 20 C, during the working hours, to 18 C, during the night. Monthly Average Temperatures Without HVAC Plant 27,2 26,6 23,7 23,6 20,9 Temperature ( C) 4,0 5,2 9,4 6,2 15,7 10,9 15,5 19,0 21,7 20,2 17,8 17,9 11,6 11,8 6,3 5,5 2,3 1,7 0, Months of the year Operative Temperature C Outside Dry Bulb Temperature C Figure 9 Comparison between outside air temperature and operative temperature without plant contribution In Figure 9, only the natural ventilation is used, and thus results are a direct depiction of the performance of the building envelope elements, in the absence of any HVAC equipment. With the assistance of the plant a temperature gradient of about 15 C is kept but even the envelope alone is able to maintain a constant temperature gradient of 5 C. The two yellow boxes indicate the year period when inside comfort can be attained even without the use of HVAC equipment, for the months of May, June, August and September. This result can be obtained using the adaptive comfort temperature with the following comfort expression proposed by de Dear and Brager [2]: T 0.31 T, 17.8 [1] 35 T comf 20%PPD T comf 10%PPD T daily avrg Jan 11 Jan 21 Jan 31 Jan 10 Feb 20 Feb 1 Mar T [ C] 11 Mar 21 Mar 31 Mar 10 Apr 20 Apr 30 Apr 10 May 20 May 30 May 9 Jun 19 Jun 29 Jun 9 Jul 19 Jul 29 Jul 8 Aug 18 Aug 28 Aug 7 Sep 17 Sep 27 Sep 7 Oct 17 Oct 27 Oct 6 Nov 16 Nov 26 Nov 6 Dec 16 Dec 26 Dec Figure 10 Outside Temperature Variation During the Year and adaptive comfort temperature Figure 11 Inside Operative Temperature Variation During the Year Figure 10 shows the comfort temperatures for 10% and 20% perception of discomfort conditions by the occupants and it can be used as a reference for assessing comfort feeling in a given month [3]. It can be seen that summer months have a comfort condition at about 25 C.

8 from Figure 11 too, showing the daily temperature distribution, it can be seen that as the blue line changes quite frequently (showing the dry bulb temperature), the green line showing the operative temperature remains quite constant and this is due to good performance of the envelope. 8. Night Cycle of Natural Ventilation The last step of the natural ventilation analysis was to introduce the concept of night ventilation during three months, namely: April, June and September. Some results are shown in Figure 12. Three analysis were carried out for each of the three months changing the ach (air changes per hour) from Temperature Vs. ach for July Temperature Vs. ach for September Operative Temperature Hourly Readings from to ach 2 ach 3 ach Operative Temperature 25, , , , ,5 Hourly Changes from to ach 2 ach 3 ach Figure 12 Inside Operative Temperature Variation During the Year depending on night ventilation rate Based on of the graphs obtained, it can be concluded that, when ach are increased from 1.0 to 2.0 for a given month, the internal temperatures decrease; however, after further increase of ach from 2.0 to 3.0 no significant change can be seen in operative temperatures. Thus, the most interesting situation is the one with night ventilation introduced into the building with a maximum of 2.0 ach. It is important to note that 2.0 ach is the maximum value of natural ventilation activated only during the night, while a constant value of 0.8 ach is kept during office working hours. Results depicted in Figure 12 are show the effect of night ventilation on operative temperatures of the building. Comparing the operating temperature for 2 ACH cases, it can be noted that, increasing the degree of natural ventilation at night, better indoor temperatures can be attained throughout the day. Thus it can be concluded that better indoor comfort conditions can be attained by natural ventilation if an appropriate amount of night ventilation strategy is put in place. 9. List of References [1] Cursio, V.; Ghilardi, G. Nearly zero energy office building in Lecco, Proceedings of Verso gli edifici ad energia quasi zero : le tecnologie disponibili conference, Milan, October [2] De Dear, R.J.; Brager, G.S. Thermal comfort in naturally ventilated buildings. Revisions to ASHRAE Standard 55, in Energy and Buildings, Vol. 34 (2002), pp [3] Pagani O.L.; Bonomi M. The Ve.L.E. approach: Energy saving and summer overheating control. Proceedings of ISES Solar World Congress 2005, Orlando, U.S.A, August From Lombardy Region: 2 From National Renewable Energy Laboratory: 3 DesignBuilder Software Ltd: 4 Comfort temperature constant and continuous running of the plants.

Verified net Zero Energy Building with air source heat pumps for SME

Verified net Zero Energy Building with air source heat pumps for SME Verified net Zero Energy Building with air source heat pumps for SME Field measurements were conducted on a net zero energy building designed for small to medium enterprises (SMEs). Energy flow and comfort

More information

ScienceDirect. Simulation based mixed mode building design

ScienceDirect. Simulation based mixed mode building design Available online at www.sciencedirect.com ScienceDirect Energy Procedia 00 (2016) 000 000 www.elsevier.com/locate/procedia 5th International Conference on Advances in Energy Research, ICAER 2015, 15-17

More information

Zero Energy House in Japan: Actual results and future target. Isamu Ohta Misawa Homes Institute of Research & Development CO., LTD.

Zero Energy House in Japan: Actual results and future target. Isamu Ohta Misawa Homes Institute of Research & Development CO., LTD. Zero Energy House in Japan: Actual results and future target Isamu Ohta Misawa Homes Institute of Research & Development CO., LTD. Energy consumption of Japanese houses Japanese government has announced

More information

PLANNING SUSTAINABLE IN CHINESE CITIES: DWELLING TYPES AS A MEANS TO ACCESSING POTENTIAL IMPROVEMENTS IN ENERGY EFFICIENCY

PLANNING SUSTAINABLE IN CHINESE CITIES: DWELLING TYPES AS A MEANS TO ACCESSING POTENTIAL IMPROVEMENTS IN ENERGY EFFICIENCY PLANNING SUSTAINABLE IN CHINESE CITIES: DWELLING TYPES AS A MEANS TO ACCESSING POTENTIAL IMPROVEMENTS IN ENERGY EFFICIENCY Qian Li 1, Phil Jones 1, and Simon Lannon 1 Welsh School of Architecture, Cardiff

More information

Passive Strategies and Low-Carbon Technologies: Evaluating the Energy Performance and Thermal Comfort of a Passive House Design

Passive Strategies and Low-Carbon Technologies: Evaluating the Energy Performance and Thermal Comfort of a Passive House Design Proceedings of the 2 nd ICAUD International Conference in Architecture and Urban Design Epoka University, Tirana, Albania, 8- May 14 Paper No. 128 Passive Strategies and Low-Carbon Technologies: Evaluating

More information

Thermal Performance of Retrofitted Envelopes with Internal Insulation: A Comparative Analysis

Thermal Performance of Retrofitted Envelopes with Internal Insulation: A Comparative Analysis PLEA2013-29th Conference, Sustainable Architecture for a Renewable Future, Munich, Germany 10-12 September 2013 Thermal Performance of Retrofitted Envelopes with Internal Insulation: A Comparative Analysis

More information

Case study of an ECBC Compliant, Energy Efficient Building: Aranya Bhawan, Jaipur

Case study of an ECBC Compliant, Energy Efficient Building: Aranya Bhawan, Jaipur Case study of an ECBC Compliant, Energy Efficient Building: Aranya Bhawan, Jaipur Prashant Bhanware (BEEP) 2 nd REGIONAL WORKSHOP ON ECBC IMPLEMENTATION IN STATES March 15 & 16, 2017 Hyatt, Ahmedabad Outline

More information

546: High Altitude Design, Optimising Residential Architecture in the Alborz Mountains, Iran

546: High Altitude Design, Optimising Residential Architecture in the Alborz Mountains, Iran 546: High Altitude Design, Optimising Residential Architecture in the Alborz Mountains, Iran Yasamin Arbabi Architectural Association, Graduate School Abstract Darbandsar is a village located in the Alborz

More information

Ventilative Cooling potential tool

Ventilative Cooling potential tool Ventilative Cooling potential tool User guide Version 1.0 IEA EBC Programme Annex 62 Ventilative Cooling AUTHORS: ANNAMARIA BELLERI EURAC RESEARCH Institute for renewable energy Druso 1 39100 Bolzano Italy

More information

An investigation into potential of passive solar. features to realise net zero carbon housing

An investigation into potential of passive solar. features to realise net zero carbon housing Department of Mechanical and Aerospace Engineering An investigation into potential of passive solar features to realise net zero carbon housing Author: Swapnil Sunil Kulkarni Supervisor: Professor Joe

More information

Assessment of Climate Change Robustness of a Deep Energy Retrofit Design of an Existing Day Care Centre

Assessment of Climate Change Robustness of a Deep Energy Retrofit Design of an Existing Day Care Centre Assessment of Climate Change Robustness of a Deep Energy Retrofit Design of an Existing Day Care Centre Amin Moazami, Salvatore Carlucci, Stig Geving Faculty of Engineering Science and Technology Department

More information

OPTIMIZATION OF THE REFURBISHMENT OF THE ENVELOPE THROUGHOUT ITS LIFE CYCLE

OPTIMIZATION OF THE REFURBISHMENT OF THE ENVELOPE THROUGHOUT ITS LIFE CYCLE OPTIMIZATION OF THE REFURBISHMENT OF THE ENVELOPE THROUGHOUT ITS LIFE CYCLE Xabat OREGI ISASI Tecnalia Energy and Environment Division, Área Anardi Azpeitia, Spain, xabat.oregi@tecnalia.com Patxi HERNANDEZ

More information

Evaluating the Building Performance of the Center for Promotion of Science in Block 39 in Belgrade, Serbia

Evaluating the Building Performance of the Center for Promotion of Science in Block 39 in Belgrade, Serbia Evaluating the Building Performance of the Center for Promotion of Science in Block 39 in Belgrade, Serbia Berrak Balci Abstract This paper presents the evaluation of the building performance of the previously

More information

Sustainable Building Façade and Advanced Fenestration Systems

Sustainable Building Façade and Advanced Fenestration Systems Workshop on Potential Technological Developments for Zero Carbon Buildings 16-17 Oct 2013 Sustainable Building Façade and Advanced Fenestration Systems Tin-Tai Chow Building Energy & Environmental Technology

More information

COMPARATIVE SUMMER THERMAL AND COOLING LOAD PERFORMANCE OF NATURAL VENTILATION OF CAVITY ROOF UNDER THREE DIFFERENT CLIMATE ZONES

COMPARATIVE SUMMER THERMAL AND COOLING LOAD PERFORMANCE OF NATURAL VENTILATION OF CAVITY ROOF UNDER THREE DIFFERENT CLIMATE ZONES COMPARATIVE SUMMER THERMAL AND COOLING LOAD PERFORMANCE OF NATURAL VENTILATION OF CAVITY ROOF UNDER THREE DIFFERENT CLIMATE ZONES Lusi Susanti 1, Hiroshi Matsumoto 2, and Hiroshi Homma 2 1 Department of

More information

Near zero energy building with steel solutions case study. Jyrki Kesti, Technology Director, Ruukki Construction

Near zero energy building with steel solutions case study. Jyrki Kesti, Technology Director, Ruukki Construction Near zero energy building with steel solutions case study, Technology Director, Ruukki Construction SSAB & Ruukki SSAB Special Steels SSAB Europe SSAB Americas Global steel and service partner in value-added

More information

Nocturnal natural ventilation for low and zero energy office buildings in Central Chile

Nocturnal natural ventilation for low and zero energy office buildings in Central Chile SET2009-8 th International Conference on Sustainable Energy Technologies,.Aachen, Germany. August 31 st to 3 rd September 2009 Page 1 of 6 Nocturnal natural ventilation for low and zero energy office buildings

More information

Indo-Swiss Building Energy Efficiency Project. Case Study: Aranya Bhawan, Jaipur

Indo-Swiss Building Energy Efficiency Project. Case Study: Aranya Bhawan, Jaipur Indo-Swiss Building Energy Efficiency Project Case Study: Aranya Bhawan, Jaipur OVERVIEW Aranya Bhawan, the office building of the Rajasthan Forest Department in Jaipur, was one of the first projects selected

More information

A STUDY ON DESIGN OPTIMIZATION OF A NEAR NET-ZERO ENERGY HOUSE

A STUDY ON DESIGN OPTIMIZATION OF A NEAR NET-ZERO ENERGY HOUSE Int. Journal for Housing Science, Vol.37, No.1 pp.23-31, 2013 Published in the United States A STUDY ON DESIGN OPTIMIZATION OF A NEAR NET-ZERO ENERGY HOUSE Narghes Doust, Gabriele Masera and Marco Imperadori

More information

Strategies for energy efficiency improvement in residential and office buildings: their role at building and country scale

Strategies for energy efficiency improvement in residential and office buildings: their role at building and country scale The Future Role of Energy Storage in South Eastern Europe Enlargement and Integration Action Workshop Strategies for energy efficiency improvement in residential and office buildings: their role at building

More information

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models L. Pagliano et al, I: Optimization of air tightness and night ventilation for Passive houses in Italian climates... 1 Optimization of air tightness and night ventilation for Passive houses in Italian climates

More information

BUILDING DESIGN AND THERMAL INERTIA: WHEN, WHY, WHERE

BUILDING DESIGN AND THERMAL INERTIA: WHEN, WHY, WHERE Int. Journal for Housing Science, Vol.34, No.4 pp. 221-231, 2010 Published in the United States BUILDING DESIGN AND THERMAL INERTIA: WHEN, WHY, WHERE R. Albatici, S. Penasa Department of Civil and Environmental

More information

AN ADVANCED GLAZING CASE STUDY FROM THE IMAGE PROJECT

AN ADVANCED GLAZING CASE STUDY FROM THE IMAGE PROJECT AN ADVANCED GLAZING CASE STUDY FROM THE IMAGE PROJECT J Clarke and M Janak University of Strathclyde, Energy Systems Research Unit, James Weir Building, Glasgow G1 1XJ P Ruyssevelt, R Cohen and J Bates

More information

Procedia - Social and Behavioral Sciences 216 ( 2016 )

Procedia - Social and Behavioral Sciences 216 ( 2016 ) Available online at www.sciencedirect.com ScienceDirect Procedia - Social and Behavioral Sciences 216 ( 2016 ) 655 661 Urban Planning and Architecture Design for Sustainable Development, UPADSD 14-16 October

More information

Cost-Benefit Analysis of Dwelling Retrofit Options

Cost-Benefit Analysis of Dwelling Retrofit Options Cost-Benefit Analysis of Dwelling Retrofit Options The objective was to study the thermal behaviour of the existing house and suggest cost effective improvements. Over recent years the energy efficiency

More information

This is an Open Access document downloaded from ORCA, Cardiff University's institutional repository:

This is an Open Access document downloaded from ORCA, Cardiff University's institutional repository: This is an Open Access document downloaded from ORCA, Cardiff University's institutional repository: http://orca.cf.ac.uk/95141/ This is the author s version of a work that was submitted to / accepted

More information

Ventilated facade design in hot and humid climate. Ventilated facade design in hot and humid climate

Ventilated facade design in hot and humid climate. Ventilated facade design in hot and humid climate Ventilated facade design in hot and humid climate Matthias Haase Dr. Alex Amato Department of Architecture Faculty of Architecture The Hong Kong University Pokfulam Road, HK, China September 2006 Ventilated

More information

Analysis 2: Alternative Thermal Window Design

Analysis 2: Alternative Thermal Window Design Analysis 2: Alternative Thermal Window Design (8.1) Problem Statement: In the first analysis, the cost and environmental impacts of the addition of solar PV panels to the roof of GrandView was determined.

More information

Great Ocean Rd Ice Creamery

Great Ocean Rd Ice Creamery Great Ocean Rd Ice Creamery BCA Section J - JV3 Compliance Report Revision: 01 Job No: 2171 Date: 7 July 2015 ADP Consulting Pty Ltd Level 10, 10 Queens Rd, Melbourne Vic 3004 www.adpconsulting.com.au

More information

ADAPTIVE FACADE SYSTEM BASED ON PHASE CHANGE MATERIALS

ADAPTIVE FACADE SYSTEM BASED ON PHASE CHANGE MATERIALS ADAPTIVE FACADE SYSTEM BASED ON PHASE CHANGE MATERIALS MSc Thesis 2016-2017 TU Delft - Faculty of Architecture - MSc Building Technology Maria Alexiou _ 4504003 Mentors: Main supervisor: dr.ir. MSc.Arch

More information

Intelligent tall building envelope technologies and design alternatives for comfort and energy efficiency in hot, arid climate

Intelligent tall building envelope technologies and design alternatives for comfort and energy efficiency in hot, arid climate Intelligent tall building envelope technologies and design alternatives for comfort and energy efficiency in hot, arid climate Sameh Monna, Building Environment Science & Technology Department, Polytechnic

More information

COMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING

COMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING COMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING ABSTRACT F. Bagheri 1, M. Fakoor 1, B. Young 1, C. Cranswick 1 1 BC Building Science Ltd. 611 Bent

More information

Chapter 9 Integration of BSA tools in building design tools 909

Chapter 9 Integration of BSA tools in building design tools 909 Chapter 9 Integration of BSA tools in building design tools 99 Integrated Approach for Intelligent Envelope Design: Simulation performance of building envelope design strategies and technologies during

More information

ANNUAL ENERGY PERFORMANCE OF SOLAR THERMAL SYSTEMS IN BRAŞOV, ROMANIA

ANNUAL ENERGY PERFORMANCE OF SOLAR THERMAL SYSTEMS IN BRAŞOV, ROMANIA Bulletin of the Transilvania University of Braşov Series I: Engineering Sciences Vol. 5 (54) No. 2-212 ANNUAL ENERGY PERFORMANCE OF SOLAR THERMAL SYSTEMS IN BRAŞOV, ROMANIA C. ŞERBAN 1 E. EFTIMIE 1 Abstract:

More information

Performance-Risk Methodology for the Design of High-Performance Affordable Homes

Performance-Risk Methodology for the Design of High-Performance Affordable Homes April 3 rd, 2012 1 Performance-Risk Methodology for the Design of High-Performance Affordable Homes Building Enclosure Science & Technology Conference BEST3, Atlanta Rodrigo Mora, British Columbia Institute

More information

State Of The Art Office Building & Campus For Maharashtra Energy Development Agency(MEDA) At AUNDH, PUNE

State Of The Art Office Building & Campus For Maharashtra Energy Development Agency(MEDA) At AUNDH, PUNE State Of The Art Office Building & Campus For Maharashtra Energy Development Agency(MEDA) At AUNDH, PUNE Architectural Design Basis: 2 o The sole motive and mission of MEDA is to Promote Energy Conservation,

More information

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Available online at   ScienceDirect. Energy Procedia 78 (2015 ) Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 1513 1518 6th International Building Physics Conference, IBPC 2015 Assessment of natural ventilation within buildings

More information

ECO-RETROFITTING VERY OLD DWELLINGS: CURRENT AND FUTURE ENERGY AND CARBON PERFORMANCE FOR TWO UK CITIES

ECO-RETROFITTING VERY OLD DWELLINGS: CURRENT AND FUTURE ENERGY AND CARBON PERFORMANCE FOR TWO UK CITIES ECO-RETROFITTING VERY OLD DWELLINGS: CURRENT AND FUTURE ENERGY AND CARBON PERFORMANCE FOR TWO UK CITIES HANIYEH MOHAMMADPOURKARBASI, STEVE SHARPLES School of Architecture, University of Liverpool, Liverpool,

More information

SOPHARMA AND LITEX TOWERS Hi-tech intelligent building where light, architecture and sustainability meet business

SOPHARMA AND LITEX TOWERS Hi-tech intelligent building where light, architecture and sustainability meet business European Nearly Zero Energy Buildings Conference 28 February 1.March 13, Wels/Austria Summary SOPHARMA AND LITEX TOWERS Hi-tech intelligent building where light, architecture and sustainability meet business

More information

Passive systems for energy savings of buildings in tropical climate

Passive systems for energy savings of buildings in tropical climate Passive systems for energy savings of buildings in tropical climate Institut Teknologi Bandung 20/01/2018 Dr. Lídia Rincón Contents Bioclimatic architecture Passive design in hot climates 2 1. Introduction

More information

MULTIDISCIPLINARY DESIGN PROCESS: URBAN, ARCHITECTURAL AND TECHNOLOGICAL ANALYSES FOR ENERGY-EFFICIENT RESIDENTIAL BUILDINGS IN NORTHERN ITALY

MULTIDISCIPLINARY DESIGN PROCESS: URBAN, ARCHITECTURAL AND TECHNOLOGICAL ANALYSES FOR ENERGY-EFFICIENT RESIDENTIAL BUILDINGS IN NORTHERN ITALY Int. Journal for Housing Science, Vol.35, No.1 pp. 11-21, 2011 Published in the United States MULTIDISCIPLINARY DESIGN PROCESS: URBAN, ARCHITECTURAL AND TECHNOLOGICAL ANALYSES FOR ENERGY-EFFICIENT RESIDENTIAL

More information

THE IMPACT OF GLAZING SELECTION ON DAYLIGHTING AND ENERGY PERFORMANCE FOR AN OFFICE BUILDING IN CANBERRA

THE IMPACT OF GLAZING SELECTION ON DAYLIGHTING AND ENERGY PERFORMANCE FOR AN OFFICE BUILDING IN CANBERRA THE IMPACT OF GLAZING SELECTION ON DAYLIGHTING AND ENERGY PERFORMANCE FOR AN OFFICE BUILDING IN CANBERRA Peter Taylor, Hélène Duponchel, and Paul Bannister Exergy Australia Pty Ltd PO Box 546 Belconnen

More information

Green Building Parameters & Case Studies

Green Building Parameters & Case Studies Green Building Parameters & Case Studies 14 th March, 2015 Mumbai Abdullah Nisar Siddiqui abdullah.nisar.siddiqui@undp.org Presentation Coverage 1. Energy Scenario in the Country 2. Green / Energy Efiicient

More information

Design guidelines for direct ground cooling systems in different climates

Design guidelines for direct ground cooling systems in different climates Design guidelines for direct ground cooling systems in different climates Adriana Angelotti and Giulio Solaini Dipartimento BEST, Politecnico di Milano, Milano, Italy ABSTRACT: Direct ground cooling systems

More information

Evaluation methods for indoor environmental quality assessment according to EN15251

Evaluation methods for indoor environmental quality assessment according to EN15251 Summary of this article was published in the REHVA European HVAC Journal Vol 49, Issue 4 (August), 2012, pages 14-19, available at http://www.rehva.eu/en/rehva-european-hvac-journal. Evaluation methods

More information

SOLCER HOUSE ENERGY POSITIVE - LOW CARBON - LOW COST

SOLCER HOUSE ENERGY POSITIVE - LOW CARBON - LOW COST SOLCER HOUSE ENERGY POSITIVE - LOW CARBON - LOW COST BACKGROUND The Welsh School of Architecture has designed and built Wales first low cost energy positive house. The Solcer House is capable of exporting

More information

Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France

Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France Sylvain Boulet 1, Stéphanie Armand-Decker 2, FCBA Technological Institute I2M-TREFLE laboratory -

More information

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates Kittitach Pichatwatana, and Fan Wang Abstract This paper examines the TAS computer

More information

Urban Greening and the UHI: Seasonal Trade-offs in Heating and Cooling Energy Consumption in Manchester, UK

Urban Greening and the UHI: Seasonal Trade-offs in Heating and Cooling Energy Consumption in Manchester, UK Urban Greening and the UHI: Seasonal Trade-offs in Heating and Cooling Energy Consumption in Manchester, UK T H E R E S E A R C H E R S C y n t h i a S k e l h o r n PhD Physical Geography Post-Doctoral

More information

Thermal Comfort Measurements in a Hybrid Ventilated Office Room

Thermal Comfort Measurements in a Hybrid Ventilated Office Room Eawag 5237 Thermal Comfort Measurements in a Hybrid Ventilated Office Room Thomas Frank 1), Herbert Güttinger 2) and Stefan van Velsen 3) 1 Swiss Federal Laboratories for Materials Testing and Research

More information

Reducing energy demand in non-domestic buildings: integrating smart facades, ventilation, and surface heating and cooling

Reducing energy demand in non-domestic buildings: integrating smart facades, ventilation, and surface heating and cooling Reducing energy demand in non-domestic buildings: integrating smart facades, ventilation, and surface heating and cooling Phil Jones, Shan Shan Hou and XiaoJun Li Welsh School of Architecture, Cardiff

More information

IMPACT OF USING DIFFERENT MODELS IN PRACTICE A CASE STUDY WITH THE SIMPLIFIED METHODS OF ISO STANDARD AND DETAILED MODELLING PROGRAMS

IMPACT OF USING DIFFERENT MODELS IN PRACTICE A CASE STUDY WITH THE SIMPLIFIED METHODS OF ISO STANDARD AND DETAILED MODELLING PROGRAMS IMPACT OF USING DIFFERENT MODELS IN PRACTICE A CASE STUDY WITH THE SIMPLIFIED METHODS OF ISO 13790 STANDARD AND DETAILED MODELLING PROGRAMS Kokogiannakis Georgios 1, Clarke Joe 1, Strachan Paul 1 1 Energy

More information

Simulation based façade control implemented as a responsive building element

Simulation based façade control implemented as a responsive building element Simulation based façade control implemented as a responsive building element Axel Seerig, Carina Sagerschnig Gruner AG, Basel, Switzerland Smart and Efficient Energy Council (SEEC 2009) 1 Trento / Italy,

More information

Passive House in Canada: Case Studies on a Near EnerPHit Retrofit and Post-Occupancy Research

Passive House in Canada: Case Studies on a Near EnerPHit Retrofit and Post-Occupancy Research Passive House in Canada: Case Studies on a Near EnerPHit Retrofit and Post-Occupancy Research Brittany Coughlin, RDH Building Science Inc. 224 W 8 th Ave, Vancouver, BC Canada Phone: +011 604 873 1181;

More information

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort Energy-Efficient Passive House using thermal mass to achieve high thermal comfort Loa Andersson Managing Director RLI Byggdata AB rli@termodeck.com Alexander Engström Technical Director RLI Byggdata AB

More information

STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS

STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS 1. ABSTRACT In modern architecture the buildings are often designed with large glass facades or windows. Due to these

More information

How to Design Zero Emission Buildings

How to Design Zero Emission Buildings Federico Butera, Politecnico di Milano Energy end uses Europe 2004 (Source: Eurostat Yearbook 2006-2007) EU Targets: Reduction of greenhouse gas emissions by 20% and ensure 20% of renewable energy sources

More information

ENERGETIC MONITORING AND OPTIMIZATION OF A SOLAR HOUSE

ENERGETIC MONITORING AND OPTIMIZATION OF A SOLAR HOUSE Bulletin of the Transilvania University of Braşov Vol. 3 (52) - 2010 Series I: Engineering Sciences ENERGETIC MONITORING AND OPTIMIZATION OF A SOLAR HOUSE M. MOLDOVAN 1 I. VIŞA 1 A. DUŢĂ 1 Abstract: Into

More information

ADAPTIVE THERMAL COMFORT - AN EXTENDED APPROACH FOR CONDITIONED INDOOR ENVIRONMENT USING COMPUTATIONAL FLUID DYNAMICS

ADAPTIVE THERMAL COMFORT - AN EXTENDED APPROACH FOR CONDITIONED INDOOR ENVIRONMENT USING COMPUTATIONAL FLUID DYNAMICS 16 th International Conference on Clean Energy (ICCE-2018) 9-11 May 2018, Famagusta, N. Cyprus ADAPTIVE THERMAL COMFORT - AN EXTENDED APPROACH FOR CONDITIONED INDOOR ENVIRONMENT USING COMPUTATIONAL FLUID

More information

Analysis of different shading strategies on energy demand and operating cost of office building

Analysis of different shading strategies on energy demand and operating cost of office building Analysis of different shading strategies on energy demand and operating cost of office building Kwiatkowski, J 1,2 ; Rucińska, J 1,2 ; Panek, A 1,2 1 Warsaw University of Technology, Faculty of Environmental

More information

The Elithis Tower is an experimental and demonstration. Elithis Tower in Dijon, France. nzeb case studies

The Elithis Tower is an experimental and demonstration. Elithis Tower in Dijon, France. nzeb case studies COM Elithis Tower in Dijon, France Elithis Tower, located in Dijon, France, provides strong evidence that net zero energy office buildings are achievable in near future. The building, which was designed

More information

A CASE STUDY OF LOW-ENERGY HOUSES IN NORTHERN ITALY

A CASE STUDY OF LOW-ENERGY HOUSES IN NORTHERN ITALY A CASE STUDY OF LOW-ENERGY HOUSES IN NORTHERN ITALY G. Salvalai Politecnico di Milano, Milan, Italy, graziano.salvalai@mail.polimi.it E. Zambelli Politecnico di Milano, Milan, Italy, ettore.zambelli@polimi.it

More information

USE OF COOL ROOF TO REDUCE THE ENERGY DEMAND AND CONSUMPTION OF COMMERCIAL BUILDINGS AT MEDITERRANEAN LATITUDES

USE OF COOL ROOF TO REDUCE THE ENERGY DEMAND AND CONSUMPTION OF COMMERCIAL BUILDINGS AT MEDITERRANEAN LATITUDES USE OF COOL ROOF TO REDUCE THE ENERGY DEMAND AND CONSUMPTION OF COMMERCIAL BUILDINGS AT MEDITERRANEAN LATITUDES Michele ZINZI Ph.D. 1 Aldo FANCHIOTTI Prof. 2 Gaetano FASANO Arc. Gabriele DE ROSSI Dr.Eng.

More information

The Double Glass Skin Façade: a sustainable option for the Curtain Wall in Mediterranean Climate Countries?

The Double Glass Skin Façade: a sustainable option for the Curtain Wall in Mediterranean Climate Countries? 1 The Double Glass Skin Façade: a sustainable option for the Curtain Wall in Mediterranean Climate Countries? Pere Alavedra¹, Mauricio Torres², Amado Guzmán³, Samantha Gallowayº, Daniel Alavedra" Department

More information

The effect of shading design and control on building cooling demand

The effect of shading design and control on building cooling demand International Conference Passive and Low Energy Cooling 953 for the Built Environment, May 25, Santorini, Greece The effect of shading design and control on building cooling demand A. Tzempelikos and A.K.

More information

Quantifying the impact of passive design on high rise buildings

Quantifying the impact of passive design on high rise buildings Quantifying the impact of passive design on high rise buildings Mohamed A. M. Krem 1, Simi T. Hoque 2,Sanjay R. Arwade 3 1 Department of Civil Engineering, Al-Mergeb University, Al-Khoms, Libya 2 Department

More information

Hamilton Way - Case Study of a High Performance Community in a Cold Climate

Hamilton Way - Case Study of a High Performance Community in a Cold Climate March 11, 2010 Northeast Sustainable Energy Association Conference Peter Baker, P.Eng. Building Science Corporation Chris Nelson Nelson Construction Hamilton Way - Case Study of a High Performance Community

More information

Zero Energy Building Example in Estonia. Tõnu Mauring

Zero Energy Building Example in Estonia. Tõnu Mauring Zero Energy Building Example in Estonia Tõnu Mauring University of Tartu, Estonia Jan 22 2014, Riga Site location Põlva, Estonia (58 N, 27 E) Long-term average dry bulb temperature for inland part of Estonia

More information

AIC TECH 2015 Sustainability in Practice Turning Ideas into Reality Jan 16, 2015 FUTURE & NET ZERO BUILDINGS

AIC TECH 2015 Sustainability in Practice Turning Ideas into Reality Jan 16, 2015 FUTURE & NET ZERO BUILDINGS AIC TECH 2015 Sustainability in Practice Turning Ideas into Reality Jan 16, 2015 FUTURE & NET ZERO BUILDINGS CONTENTS Introduction to Net Zero Can we get to Net Zero? Pathway to Net Zero Energy Buildings

More information

Parametric Louver Design System Based On Direct Solar Radiation Control Performance

Parametric Louver Design System Based On Direct Solar Radiation Control Performance Parametric Louver Design System Based On Direct Solar Radiation Control Performance Jaepil Choi 1, Taekyoung Lee* 2, Euisoon Ahn 2 and Gensong Piao 2 1 Professor, Department of Architecture, Seoul National

More information

Project Description. Projected build start date 03 May 2010 Projected date of occupation 06 Aug

Project Description. Projected build start date 03 May 2010 Projected date of occupation 06 Aug http://lowenergybuildings.org.uk Project name Retrofit - Appledore, Ashford Project summary The key project approach is to develop a solution that uses complementary technologies and techniques, and primarily

More information

Solar cooling design: a case study

Solar cooling design: a case study Eco-Architecture IV 399 Solar cooling design: a case study S. Grignaffini & M. Romagna Department of Astronautic, Electric and Energetic Engineering, Sapienza, University of Rome, Italy Abstract Throughout

More information

ADAPTIVE LOW-E DOUBLE GLAZING WINDOW

ADAPTIVE LOW-E DOUBLE GLAZING WINDOW ADAPTIVE LOW-E DOUBLE GLAZING WINDOW Hussein Abaza 1 and Ihab Sa ad 2 ABSTRACT This paper investigates the thermal performance of a new adaptive window which is seasonally reversible. The new window is

More information

ENERGY EFFICIENT RETROFIT OF A HIGH-RISE MULTIFAMILY BUILDING

ENERGY EFFICIENT RETROFIT OF A HIGH-RISE MULTIFAMILY BUILDING ENERGY EFFICIENT RETROFIT OF A HIGH-RISE MULTIFAMILY BUILDING Brittany Hanam 1, Lorne Ricketts 2, Andrew Pape-Salmon 3 ABSTRACT The National Institute of Building Sciences estimates that over 70% of the

More information

The energy benefits of View Dynamic Glass

The energy benefits of View Dynamic Glass Workplace demonstration Energy monitoring over a period of 12 months resulted in the commercial office room installed with View Dynamic Glass saving 39 percent of the total energy consumed compared to

More information

Effect of passive cooling strategies on overheating in low energy residential buildings for Danish climate

Effect of passive cooling strategies on overheating in low energy residential buildings for Danish climate Proceedings of 8 th Windsor Conference: Counting the Cost of Comfort in a changing world Cumberland Lodge, Windsor, UK, 10-13 April 2014. London: Network for Comfort and Energy Use in Buildings, http://nceub.org.uk

More information

Preservation of cultural heritage: the design of low-energy archival storage

Preservation of cultural heritage: the design of low-energy archival storage Preservation of cultural heritage: the design of low-energy archival storage Dr Tim Taylor a,b* a Atkins, Woodcote Grove, Ashley Road, Epsom, Surrey KT18 5BW, United Kingdom b Cardiff Metropolitan University,

More information

Redesigning of building envelope: tree bark as a biomimicry concept

Redesigning of building envelope: tree bark as a biomimicry concept Sustainable Development and Planning VII 1019 Redesigning of building envelope: tree bark as a biomimicry concept E. Alkhateeb & H. Taleb Sustainable Design of Built Environment, British University of

More information

Student Modeling Competition

Student Modeling Competition Student Modeling Competition Design and Simulation of a Near-zero Energy Building Building Simulation 2013 Apoorv Goyal agoyal@gsd.harvard.edu Arta Yazdanseta ayazdans@gsd.harvard.edu Keojin Jin kjin@gsd.harvard.edu

More information

Future tree planting on the two acre lot will offset remaining lifetime carbon emissions.

Future tree planting on the two acre lot will offset remaining lifetime carbon emissions. Luxury Net-Zero Home by Rockwood Custom Homes 47 Grandview Place, Calgary AB T3Z A8 by Grant Bremner A Net-Zero Emissions (NZE) home is carbon neutral where carbon credits fully offset emissions. An NZE

More information

The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort

The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort Ongun Berk Kazanci, Bjarne W. Olesen 1 1 International Center for Indoor Environment and

More information

Introduction to basics of energy efficient building design

Introduction to basics of energy efficient building design Introduction to basics of energy efficient building design Pierre Jaboyedoff Seminar on Energy Efficient & Thermally Comfortable Buildings in Amravati For CRDA, Andhra Pradesh May 2 nd 2017 Indo-Swiss

More information

Achieving a cost optimal balance between heat supply efficiency and moderation of demand

Achieving a cost optimal balance between heat supply efficiency and moderation of demand Achieving a cost optimal balance between heat supply efficiency and moderation of demand Dr. Christian Friebe Thüga Aktiengesellschaft COGEN Europe, 25th of February 560 cities and towns, 100 companies

More information

Assessing the energy performance of modern glass facade systems

Assessing the energy performance of modern glass facade systems Assessing the energy performance of modern glass facade systems Abdelsalam Aldawoud * Architectural Engineering Department, University of Sharjah Sharjah, United Arab Emirates Abstract. The design and

More information

The Net-Zero building Solar 2002

The Net-Zero building Solar 2002 The Net-Zero building Solar 2002 Learning from an early example Koen Claes (1), Ralf Klein (3), Guido Henri De Couvreur (2), Alexis Versele (3), Hilde Breesch (3) (1) Hogeschool voor Wetenschap & Kunst,

More information

Effects of the use of DIN on the energetic assessment of residential buildings reflection on the calculation

Effects of the use of DIN on the energetic assessment of residential buildings reflection on the calculation Abstract Effects of the use of DIN 18599 on the energetic assessment of residential buildings reflection on the calculation approaches The research report was financially supported by the research initiative

More information

Introduction and utilizing of natural energy in Net ZEB practice

Introduction and utilizing of natural energy in Net ZEB practice Introduction and utilizing of natural energy in Net ZEB practice Takenaka Corporation Higashi-kanto Branch Office 2018.10.5 Renewable Energy Institute / Green Building Symposium Takenaka Corporation Hiroaki

More information

JOTUN Cool Shades. Impact of the TSR Value on the Users Comfort and the Energy Performance of Buildings. ai³ Werner Jager

JOTUN Cool Shades. Impact of the TSR Value on the Users Comfort and the Energy Performance of Buildings. ai³ Werner Jager JOTUN Cool Shades Impact of the TSR Value on the Users Comfort and the Energy Performance of Buildings ai³ Werner Jager Exclusion of warranty: All tables, graphical charts and results presented within

More information

ENERGY SELF SUFFICIENCY WITH RENEWABLE SOURCES BIOMASS AND WIND IN THE REHABILITATION PROJECTOF AN OLD RURAL BUILDING COMPLEX IN SICILY (ITALY)

ENERGY SELF SUFFICIENCY WITH RENEWABLE SOURCES BIOMASS AND WIND IN THE REHABILITATION PROJECTOF AN OLD RURAL BUILDING COMPLEX IN SICILY (ITALY) ENERGY SELF SUFFICIENCY WITH RENEWABLE SOURCES BIOMASS AND WIND IN THE REHABILITATION PROJECTOF AN OLD RURAL BUILDING COMPLEX IN SICILY (ITALY) Paola Caputo paola.caputo@polimi.it Politecnico di Milano,

More information

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016 Aalborg Universitet CLIMA 2016 - proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols Publication date: 2016 Document Version Publisher's PDF, also known as Version of record Link to publication

More information

Twenty-first Century Building Design: Getting to Net-Zero Energy?

Twenty-first Century Building Design: Getting to Net-Zero Energy? Twenty-first Century Building Design: Getting to Net-Zero Energy? National Conference of State Legislators Paul A. Torcellini, Ph.D., PE June 23, 2009 www.highperformancebuildings.gov NREL is a national

More information

A prototype architecture for passive and plus energy building in Estonia

A prototype architecture for passive and plus energy building in Estonia A prototype architecture for passive and plus energy building in Estonia Tõnu Mauring, Jaanus Hallik, Margus Valge, Kristo Kalbe University of Tartu, Institute of Technology Georg W. Reinberg, Architekturbüro

More information

Towards nzeb buildings: a historical building case study

Towards nzeb buildings: a historical building case study Towards nzeb buildings: a historical building case study The recast of EU Directive 2010/31 introduced the concept of (nearly) zero energy building (NZEB). In Italy this challenge is remarkable: existing

More information

Progress of Nordic Built project_nb13339 Low temperature heating and high temperature cooling in refurbishments and new construction of buildings

Progress of Nordic Built project_nb13339 Low temperature heating and high temperature cooling in refurbishments and new construction of buildings Progress of Nordic Built project_nb13339 Low temperature heating and high temperature cooling in refurbishments and new construction of buildings Low temperature heating (LTH) group: Sture Holmberg, Professor,

More information

Impact of Distributed Solar Generation in Low Energy Housing on the Electrical Grid

Impact of Distributed Solar Generation in Low Energy Housing on the Electrical Grid Impact of Distributed Solar Generation in Low Energy Housing on the Electrical Grid Wasim Saman, David Whaley and Lachlan Mudge Barbara Hardy Institute University of South Australia - Mawson Lakes SA,

More information

Modeling and analyzing solar cooling systems in Polysun

Modeling and analyzing solar cooling systems in Polysun Modeling and analyzing solar cooling systems in Polysun Seyed H. Rezaei (seyed.rezaei@velasolaris.com) 1 Andreas Witzig (andreas.witzig@velasolaris.com) 1 Michael Pfeiffer (michael.pfeiffer@velasolaris.com)

More information

Energy Audit of two Apartment Buildings in Cagliari using Energy Simulation

Energy Audit of two Apartment Buildings in Cagliari using Energy Simulation Energy Audit of two Apartment Buildings in Cagliari using Energy Simulation Graduation Thesis by Carla Vargiu and Luisa Zedda, Master in Green Building and Energy Efficiency This thesis focuses on the

More information

COST - EFFECTIVE DESIGN FOR AIR-CONDITIONED OFFICE SPACE : TRANSPORT CORPORATION OF INDIA LTD. ASHOK B. LALL ARCHITECTS, NEW DELHI

COST - EFFECTIVE DESIGN FOR AIR-CONDITIONED OFFICE SPACE : TRANSPORT CORPORATION OF INDIA LTD. ASHOK B. LALL ARCHITECTS, NEW DELHI COST - EFFECTIVE DESIGN FOR AIR-CONDITIONED OFFICE SPACE : TRANSPORT CORPORATION OF INDIA LTD. ASHOK B. LALL ARCHITECTS, NEW DELHI TCI HOUSE is a modern office building with a high level of environmental

More information

Imp ementation Case:

Imp ementation Case: ZEMedS: Implementation Implementation Case: IPCT Bonifazi, Recanati, Italy General data 3 Name of the School Type of school IPCT Recanati High School High School Number of students Owner 277 public Location

More information

Summer season temperature control in Finnish apartment buildings

Summer season temperature control in Finnish apartment buildings Summer season temperature control in Finnish apartment buildings Jarek Kurnitski, Pasi Tauru and Jari Palonen Helsinki University of Technology, Finland Corresponding email: jarek.kurnitski@tkk.fi SUMMARY

More information