1 Energy and Buildings 41 (009) Contents lists available at ScienceDirect Energy and Buildings journal homepage: Modeling solar-driven ejector refrigeration system offering air conditioning for office buildings J. Guo *, H.G. Shen School of Environmental Science and Engineering, Donghua University, 999# North Renmin Road, Shanghai 0160, PR China ARTICLE INFO ABSTRACT Article history: Received 6 June 008 Accepted 18 July 008 Keywords: Solar-driven ejector refrigeration Lumped method Dynamic model COP Solar fraction A lumped method combined with dynamic model is proposed for use in investigating the performance and solar fraction of a solar-driven ejector refrigeration system (SERS) using R134a, for office air conditioning application for buildings in Shanghai, China. Classical hourly outdoor temperature and solar radiation model were used to provide basic data for accurate analysis of the system performance. Results indicate that during the office working-time, i.e., from 9:00 to 17:00, the average COP and the average solar fraction of the system were 0.48 and 0.8 respectively when the operating conditions were: generator temperature (85 8C), evaporator temperature (8 8C) and condenser temperature varying with ambient temperature. Compared with traditional compressor based air conditioner, the system can save upto 80% electric energy when providing the same cooling capacity for office buildings. Hence, the system offers a good energy conservation method for office buildings. ß 008 Elsevier B.V. All rights reserved. 1. Introduction Energy is considered as a major agent in the generation of wealth and an important factor in economic development. With the sharp increase in the cost of the energy and the high energy consumed by the conventional air conditioners, the solar-driven ejector refrigeration system has recently received considerable attention as alternative refrigeration for residential and commercial space cooling application. An ejector driven by solar energy can be used to replace the compressor which makes the refrigeration system to consume much less electric power than traditional compressor based air conditioner. Moreover, the SERS is simple, reliable, and convenient for integration with buildings and can use environmentally friendly working fluid. In addition, they utilize solar energy which is essentially non-hazardous, unlimited and always available. Since the idea of a SERS was advanced in the beginning of 1990s [1 3], a great deal of numerical and experimental works as well as system optimization works have been reported in literatures [4,5]. Various experimental studies [6 11] have examined the effect of the operation conditions such as the generator temperature, evaporator temperature and condenser temperature, the geometrical conditions such as the area ratio (the cross section area ratio of constant area tube to the nozzle throat), the distance of the nozzle exit to the * Corresponding author. address: shuheguo@163.com (J. Guo). inlet of the constant area tube, the system conditions such as refrigerant and collector selections on the performance of the system and presented abundant experimental data for reference during system design. Other researchers [1] have presented numerical methods of simulating the ejector and studied the parametric effect on the system performance. System optimization investigations [13 15] have focused on various combined ejector refrigeration systems for performance improvement. An accurate SERS performance forecasting is an important precondition for the optimal control and energy saving operation of air conditioning systems. Numerous prediction techniques, which mainly include thermodynamic method, dynamic method, lumped method, exergy analysis method and the use of artificial neural network (ANN) have been applied to predict the performance of SERS. Dynamic method is widely accepted as a technique which can describe in details what happens in the ejector while lumped method offers a good way to tackle complex problems in actual situations. The advantage of the dynamic method with respect to other models is its ability to model the choking, shock and mixing phenomena occuring in the ejector and can give detailed information on the mass flow along the ejector. In this paper, the lumped method combined with dynamic model was used to forecast the performance of a solar-driven ejector refrigeration system.. System description The SERS is shown in Fig. 1. It comprises of two loops, one is solar collection loop which is the main energy source of ejector /$ see front matter ß 008 Elsevier B.V. All rights reserved. doi: /j.enbuild

2 176 J. Guo, H.G. Shen / Energy and Buildings 41 (009) Nomenclature A area (m ) COP coefficient of performance Cp specific heat of gas at constant pressure (kj/(kg K)) D diameter (mm) f solar fraction h enthalpy (kj/kg) I solar radiation (W/m ) m mass flow rate (kg/s) M Mach number P pressure (Pa) Q heat (W) R gas constant (kj/(kg K)) T temperature (K) V velocity (m/s) Greek symbols g specific heat ratio h coefficient F m isoentropy coefficient of mixture v entrainment ratio, v = m e /m m Subscripts AS after shock c cooling DO diffuser outlet e entrained fluid HR heat required I calculation step in inlet m motive fluid mt mixture NO nozzle outlet t nozzle throat y section y y 3 constant area tube refrigeration system (ERS) and the other is ejector refrigeration loop which supplies useful cooling to the user. The solar collection loop is composed of collector, a hot water storage tank, an auxiliary heater and a circulating pump. The auxiliary heater is located between the hot water storage tank and the generator of the ejector refrigeration loop. When the hot water temperature in the tank is not high enough to drive the ejector refrigeration loop, the auxiliary heater will start automatically. The ejector refrigeration loop consists of two subsystems: the power subsystem, and the refrigeration subsystem. In the power subsystem, the refrigerant flows through the generator, the ejector, the condenser and the circulating pump, and finally flows back to the generator to supply high pressure motive fluid to the ejector. In the refrigeration subsystem, the refrigerant flows through the ejector, the condenser, the expansion valve, the evaporator, and then back to the suction of the ejector to supply the required cooling capacity. The main part of the ejector refrigeration loop is the ejector (Fig. ), which is composed of a convergent divergent nozzle, suction chamber, mixing chamber and a diffuser. The motive fluid is first accelerated to supersonic velocity in the convergent divergent nozzle, which entrains the evaporated fluid (named entrained fluid hereinafter) from the evaporator and the two fluids mix together in the mixing chamber. In the diffuser, the velocity of the mixed fluid is stepped down and the pressure is lifted to the condenser pressure. 3. Mathematical model Being driven by solar energy, the performance of the SERS is affected not only by geometrical parameters of the ejector, but also by local climatic conditions. Taking these into considerations, a lumped method combined with dynamic model was developed to investigate the performance of the SERS. The environmental friendly refrigerant R134a was used as the working fluid. And the climatic conditions of Shanghai were used for field modeling. The designed cooling capacity of the system was 6 kw with evaporation temperature at 8 8C. A vacuum tube collector of 15 m was employed for analysis Modeling the ejector performance The main geometrical parameters of the designed ejector are shown in Fig.. The dynamic model of ejector performance prediction similar to that given in reference [16] with the outlet of the convergent divergent nozzle located at somewhere in front of the constant area tube was adopted to analyze the system with real gas property derived from NIST REFPROP (Version 6.01) [17]. Suppose two chokes occur for both the motive and the entrained fluids, then the mass flow follows the gas dynamic equations: sffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi m ¼ P ina t gh ðgþ1þ=ðg 1Þ pffiffiffiffiffiffi (1) R g þ 1 A iþ1 A i P i P iþ1 ¼ T in " # ¼ M i 1 þððg 1Þ=ÞMiþ1 ðgþ1þ=ðg 1Þ () M iþ1 1 þððg 1Þ=ÞMi 1 þððr 1Þ=ÞM iþ1 1 þððr 1Þ=ÞM i! r=ðr 1Þ (3) For a given ejector, the area is known, and the Mach number and pressure P NO at convergent divergent nozzle exit can be obtained by Eqs. () and (3). Assuming that the entrained fluid mixed with the motive fluid at section y y, where it forms the dynamic throat for the entrained fluid, i.e., M ey = 1. For a given inlet stagnant pressure P e, the pressure of the entrained fluid (P ey ) at the mixing section can be calculated by Eq. (3). Also, supposing the motive fluid and the entrained fluid mixed at section y y with uniform pressure, i.e. P my = P ey, known the convergent divergent nozzle outlet Mach number and with pressure obtained as mentioned above, the Mach number of the motive fluid at section y y can be calculated by Eq. (3) if P NO > P ey. Otherwise, shock happens at the outlet of the convergent divergent nozzle, and the flow abides by the shock wave theory. Then the cross-section area of the motive fluid core A my at section y y and that of the ejector at section y y A y can be obtained from Eq. () and the geometrical parameter of the ejector, and consequently, the cross-section area of the entrained fluid A y at section y y is given by: A ey ¼ A y A my (4) The mass flow of the entrained fluid m e can be calculated by Eq. (1) and the entrainment ratio is: v ¼ m e m m (5)

3 J. Guo, H.G. Shen / Energy and Buildings 41 (009) Fig. 1. Schematic diagram of solar-driven ejector refrigeration system. According to gas dynamic equations (6) and (7), the temperature and velocity of motive and entrained fluids are: T in ¼ 1 þ g 1 T y M y (6) V y ¼ M y qffiffiffiffiffiffiffiffiffiffiffi grt y Based on energy and momentum conservation of the motive, entrained and the mixed fluid, and taking the energy loss into consideration, the parameters of the mixture are: F m ½m m V my þ m e V ey Š¼ðm m þ m e ÞV mt (8) m m CpT my þ V! py þ m e CpT ey þ V! ey ¼ðm m þ m e Þ CpT mt þ V mt (9) Call for the database NIST REFPROP (Version 6.01) for the properties of the gas, the cooling capacity, heat required by the (7) generator and the performance of the ERS are: Q c ¼ m e ðh h 6 Þ (10) Q HR ¼ m m ðh 1 h 5 Þ (11) COP ERS ¼ Q c ¼ v h h 6 (1) Q g h 1 h 5 Under the condition that the motive fluid undergoes a shock wave at the outlet of the nozzle, the pressure and Mach number after the shock wave are described by Eqs. (13) and (14). P AS ¼ 1 þ g P NO g þ 1 ðm NO 1Þ (13) M AS ¼ 1 þððg 1Þ=ÞM NO gm NO ððg 1Þ=Þ (14) 3.. Modeling the performance of the system Once the performance of the ejector and its refrigeration system is obtained, the performance of the SERS can be described by: COP SERS ¼ COP ERS h col (15) Fig.. Schematic diagram of ejector geometry.

4 178 J. Guo, H.G. Shen / Energy and Buildings 41 (009) Where, h col is the efficiency of the solar collector, given by: h col ¼ F R ðatþ F R U L T col T a I (16) Where, F R is the heat transfer factor, t and a are the solar incident ratio and absorption, respectively. U L is the total heat loss coefficient of collector, T col is the water temperature of the collector, and T a is the ambient temperature. Then the effective solar energy gain and the solar fraction can be calculated by the following equations: Q col ¼ A col I h col (17) heat geained from solar energy f ¼ heat required for the generator=h ¼ Q col Q HR =h where, A col is the collector area, m, I is solar radiation, W/m. (18) Fig. 3. Schematic schedule of the program.

5 J. Guo, H.G. Shen / Energy and Buildings 41 (009) Fig. 4. Validation of the model. Fig. 6. COP of the ERS under various generator temperature. Based on the assumption that: (1) the power consumed by the circulating pumps and that by the control system is neglectable; () the velocity at the ejector inlet, outlet and evaporator outlet is neglectable; (3) the condenser temperature is 5 8C higher than the ambient temperature; and (4) the collector temperature is 10 8C higher than the generator temperature, then the performance of the system can be predicted by the program descript in Fig Results and discussions 4.1. Performance of the ejector and its refrigeration system For a given ejector, the performance can be calculated based on the mathematical model mentioned in Section 3.1. For validation, the results calculated by the model were compared with the experimental values and also with the one-dimension model by Huang et al. [16], and with that calculated by CFD software package Fluent 6. [18]. The deviations are shown in Fig. 4. The results were found to be in good agreement with experimental values with deviations no more than 10%, which means the model is effective for analysis the performance of the ejector and can be used as basis for performance analysis of the SERS. The entrainment ratio of the ejector used for the system analysis is shown in Fig. 5. For a given ejector, higher generator temperature means higher motive fluid pressure, which leads to a higher velocity at the exit of the convergent divergent nozzle and more fluid from the evaporator is entrained. When the inlet temperature of the motive fluid is higher than the designed temperature, shock wave will happen. With energy loss during the shock wave, the entrainment capacity of the motive fluid after the shock wave is decreased sharply. The COP of the ERS is shown in Fig. 6, and it has a similar trend as the entrainment ratio of the ejector because the performance of the system is greatly affected by the entrainment ratio of the ejector. More refrigerant fluid entrained by the ejector means the system supplies more cooling capacity, with a small increase in heat requirement for heating the motive fluid. Hence, the system offers better performance. Fig. 7 shows the cooling capacity of the designed ejector under critical condenser pressure. The critical cooling capacity of the ejector increases with increasing generator temperature. Under the design condition of generator temperature at 85 8C, the cooling capacity reaches maximum. After that, shock wave happens at the exit of the nozzle which leads to energy loss, consequently, the performance and the cooling capacity of the ERS decrease sharply. Fig. 5. Entrainment ratio of the designed ejector. Fig. 7. Cooling capacity of the ERS under various generator temperature.

6 180 J. Guo, H.G. Shen / Energy and Buildings 41 (009) Fig. 8. Hourly ambient temperature variations in Shanghai (July). Fig. 11. Variation of COP of the SERS with time. Fig. 9. Hourly solar radiation in Shanghai (July). 4.. Performance of the SERS The climate conditions of Shanghai were used for the performance prediction of the SERS. Figs. 8 and 9 show the hourly outdoor ambient temperature and total solar radiation on a typical day in July calculated from the model proposed by Liu and Jordan [19]. Given the performance of the ejector as mentioned above and the climate conditions as shown in Figs. 8 and 9, the hourly performance of the ERS and SERS can be obtained (Figs. 10 and 11). Fig. 10 shows the hourly COP of the ERS with the evaporator temperature at 8 8C and the condenser temperature varying with the ambient temperature. Under fixed inlet pressures of motive fluid and entrained fluid, the mixed fluid is easier to flow through with higher condenser temperature, therefore, more refrigerant fluid can be entrained and the entrainment ratio of the ejector increases, consequently, the cooling capacity and the COP of the ERS also increase. Comparing Figs. 8 10, although the solar radiation reaches maximum at 1:00, the ambient temperature and the entrainment ratio of the ejector reach maximum at 14:00. It indicates that the condenser temperature has greater effect on the performance of the ERS than the generator temperature. As the condenser temperature not only determines the condenser pressure which in turn influences the entrainment ratio and COP of the ERS as mentioned above, but it also influences the heat required by the generator. Under a higher condenser temperature, the ejector entrains more refrigerant and supplies more cooling capacity. Furthermore, a higher condenser temperature causes a decrease in the heat required by the generator when it generates the same quality and quantity of motive fluid. Fig. 10. Variation of COP of ERS with time. Fig. 1. Hourly solar fraction.

7 J. Guo, H.G. Shen / Energy and Buildings 41 (009) Considering the efficiency of the solar collector, heat loss of the storage tank and pipes as well as the heat transfer efficiency in the generator, the hourly overall performance of the SERS is as shown in Fig. 11. From 8:00. to 16:00, the system worked under steady performance between 0.43 and 0.53 with cooling capacity of 6 kw. During other times, the solar radiation intensity weakens and the ambient temperature drops, therefore, the overall COP of the system decreases sharply. From the view of this character, the system exerts its best performance when being used in daytime. Therefore, it s appropriate for the system to supply air conditioning for office buildings. The hourly solar fraction of the system is shown in Fig. 1. With more solar energy gain from 10:00 to 13:00, the solar fraction during this period is more than 1.0, which means no additional electric energy is needed (except that used for the instrument and circulation pumps) for the system to supply air conditioning. During other hours at daytime, the solar fraction of the system is between except at 17:00, the solar fraction drops to as low as When the system is equipped in office buildings, and the office time is from 9:00 to 17:00, the average solar fraction of the system is 0.8. That is to say, only 18% electric energy is needed to provide the same cooling capacity. Compared with traditional compressed air conditioning system, the SERS can conserve more than 75% of electric energy. 5. Conclusions In this study, the lumped method combined with dynamic model for performance prediction of solar-driven ejector refrigeration system for providing air conditioning to office buildings was investigated. The results of the mathematical simulation have demonstrated that the solar-driven ejector refrigeration system can be designed to meet the cooling requirements of air conditioning for office buildings. The following conclusions were obtained: (1) For the studied case, the condenser temperature influences more on the performance of the SERS than the generator temperature. () From 9:00 to 17:00, on typical clear sky days, the average COP of the system is 0.48 with most of the daytime remaining steady between , except at 17:00, when it drops as low as 0.9. The average solar fraction is 0.8. (3) Compared with traditional compressor based air conditioner, the SERS conserves more than 75% of electric energy when it is used to supply air conditioning during daytime for office buildings. (4) The system offers a good energy conservation method for air conditioning of office buildings. References [1] Srinivasa Murthy, R. Balasubramanian, M.V. Krishna Murthy, Experiments on vapour jet refrigeration system suitable for solar energy applications, Renewable Energy 1 (5/6) (1991) [] M. Sokolov, D. Hershgal, Optimal coupling and feasibility of a solar-powered yearround ejector air conditioner, Solar Energy 50 (6) (1993) [3] M. Sokolov, D. Hershgal, Solar-powered compression-enhanced ejector air conditioner, Solar Energy 51 (3) (1993) [4] B. Zhang, S.Q. Shen, Development of solar ejector refrigeration system, in: Proceedings of the 1st International Conference on Sustainable Energy Technologies, 00. [5] K. Chunnanond, S. Aphornratana, Ejectors: applications in refrigeration technology, Renewable and Sustainable Energy Reviews 8 (004) [6] S. Aphornratana, I.W. Eames, A small capacity steam-ejector refrigerator: experimental investigation of a system using ejector with movable primary nozzle, International Journal of Refrigeration 0 (5) (1997) [7] I.W. Eames, A.E. Ablwaifa, V. Petrenko, Results of an experimental study of an advanced jet-pump refrigerator operating with R45fa, Applied Thermal Engineering 7 (007) [8] A. Selvaraju, A. Mani, Experimental investigation on R134a vapour ejector refrigeration system, International Journal of Refrigeration 9 (006) [9] T. Sankarlal, A. Mani, Experimental investigations on ejector refrigeration system with ammonia, Renewable Energy 3 (007) [10] B.J. Huang, V.A. Petrenko, I.Y.A. Samofatov, N.A. Shchetinina, Collector selection for solar ejector cooling system, Solar Energy 71 (4) (001) [11] A. Selvaraju, A. Mani, Analysis of an ejector with environment friendly refrigerants, Applied Thermal Engineering 4 (004) [1] E.D. Rogdakis, G.K. Alexis, Design and parametric investigation of an ejector in an air-conditioning system, Applied Thermal Engineering 0 (000) [13] A. Arbel, M. Sokolov, Rvisiting solar-powered ejector air conditioner the greener the better, Solar Energy 77 (004) [14] X.J. Zhang, R.Z. Wang, A new combined adsorption-ejector refrigeration and heating hybrid system powered by solar energy, Applied Thermal Engineering (00) [15] J.L. Yu, Y.F. Ren, H. Chen, Y.Z. Li, Applying mechanical subcooling to ejector refrigeration cycle for improving the coefficient of performance, Energy Conversion and Management 48 (007) [16] B.J. Huang, J.M. Chang, C.P. Wang, V.A. Petrenko, A 1-D analysis of ejector performance, International Journal of Refrigeration (1999) [17] NIST Standard Reference Database 3, NIST Thermodynamics and Transport Properties of Refrigerants and Refrigerant Mixtures, REFPROP, Version 6.01, [18] E. Rusly, Ejector cooling with reference to combined ejector-vapour compression system, Ph.D. Thesis, University of Melbourne, 004. [19] Y.H. Benjamin Liu, C. Richard Jordan, The interrelationship and characteristic distribution of direct, diffuse and total solar radiation, Solar Energy 4 (3) (1960) 1 19.

Supersonic Nozzle Flow in the Two-Phase Ejector as Water Refrigeration System by Using Waste Heat

Supersonic Nozzle Flow in the Two-Phase Ejector as Water Refrigeration System by Using Waste Heat HEFAT2012 9 th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics 16 18 July 2012 Malta Supersonic Nozzle Flow in the Two-Phase Ejector as Water Refrigeration System by Using

More information

Enhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis

Enhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Enhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis Elias

More information

Effect of Generator, Condenser and Evaporator Temperature on the Performance of Ejector Refrigeration System (ERS)

Effect of Generator, Condenser and Evaporator Temperature on the Performance of Ejector Refrigeration System (ERS) Journal of Basic and Applied Engineering Research pp. 4-9 Krishi Sanskriti Publications http://www.krishisanskriti.org/jbaer.html Effect of Generator, Condenser and Evaporator Temperature on the Performance

More information

Experimental investigation of solar-driven double ejector refrigeration system

Experimental investigation of solar-driven double ejector refrigeration system Experimental investigation of solar-driven double ejector refrigeration system Jedsada Visedmanee a *, Anan Pongtornkulpanich a, Sakda Somkun a and Ananchai U-kaew b a Thermal Energy Research Unit, School

More information

COEFFICIENT OF PERFORMANCE OF TWO PHASE CONDENSING EJECTOR REFRIGERATION SYSTEM WITH R-22

COEFFICIENT OF PERFORMANCE OF TWO PHASE CONDENSING EJECTOR REFRIGERATION SYSTEM WITH R-22 INTERNATIONAL JOURNAL OF RESEARCH IN COMPUTER APPLICATIONS AND ROBOTICS ISSN 2320-7345 COEFFICIENT OF PERFORMANCE OF TWO PHASE CONDENSING EJECTOR REFRIGERATION SYSTEM WITH R-22 Kuldip Kumar 1, Anjani Kumar

More information

3d Analysis on Supersonic Ejector

3d Analysis on Supersonic Ejector 3d Analysis on Supersonic Ejector Arun K R 1, Abraham Antony 2, Eldhose Kurian 3, Frenosh K Francis 4 1,2,3, 4 Assistant Professor Department of Mechanical Engineering, Viswajyothi College of Engineering,

More information

Numerical Investigation of the Flow Dynamics of a Supersonic Fluid Ejector

Numerical Investigation of the Flow Dynamics of a Supersonic Fluid Ejector Proceedings of the International Conference on Heat Transfer and Fluid Flow Prague, Czech Republic, August 11-12, 2014 Paper No. 171 Numerical Investigation of the Flow Dynamics of a Supersonic Fluid Ejector

More information

Revue des Energies Renouvelables Spécial ICT3-MENA Bou Ismail (2015) Numerical study of a single effect ejector-absorption cooling system

Revue des Energies Renouvelables Spécial ICT3-MENA Bou Ismail (2015) Numerical study of a single effect ejector-absorption cooling system Revue des Energies Renouvelables Spécial ICT3-MENA Bou Ismail (2015) 71-77 Numerical study of a single effect ejector-absorption cooling system D. Sioud 1*, M. Bourouis 2 et A. Bellagi 1 1 Unité de Recherche

More information

Computational Analysis Of Ejector With Oscillating Nozzle

Computational Analysis Of Ejector With Oscillating Nozzle Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2018 Computational Analysis Of Ejector With Oscillating Nozzle Arun Kodamkayath

More information

Study on Ejector - Vapor Compression Hybrid Air Conditioning System Using Solar Energy

Study on Ejector - Vapor Compression Hybrid Air Conditioning System Using Solar Energy Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 202 Study on Ejector - Vapor Compression Hybrid Air Conditioning System Using

More information

Solar Cooling Using Variable Geometry Ejectors

Solar Cooling Using Variable Geometry Ejectors Solar Cooling Using Variable Geometry Ejectors M. Dennis Centre for Sustainable Energy Systems Department of Engineering The Australian National University Canberra, ACT 2 AUSTRALIA E-mail:Mike.Dennis@anu.edu.au

More information

EFFECT OF THE NOZZLE EXIT POSITION ON THE EFFICIENCY OF EJECTOR COOLING SYSTEM USING R134A

EFFECT OF THE NOZZLE EXIT POSITION ON THE EFFICIENCY OF EJECTOR COOLING SYSTEM USING R134A EFFECT OF THE NOZZLE EXIT POSITION ON THE EFFICIENCY OF EJECTOR COOLING SYSTEM USING R134A K. Sopian 1, B. Elhub 1, Sohif Mat 1, A. N. Al-Shamani 1, AM Elbreki 1, Azher M. Abed 1, Husam Abdulrasool Hasan

More information

DEVELOPMENT OF SOLAR THERMAL HEATING AND COOLING SYSTEMS USING THE JET PUMP CYCLE

DEVELOPMENT OF SOLAR THERMAL HEATING AND COOLING SYSTEMS USING THE JET PUMP CYCLE DEVELOPMENT OF SOLAR THERMAL HEATING AND COOLING SYSTEMS USING THE JET PUMP CYCLE R.FENTON (a), S.KNOWLES, I.W.EAMES, G.MAIDMENT (a) Industrial Design Consultancy Ltd, Unit 13 The Portland Business Centre,

More information

A review on Present development in refrigeration jet ejector system

A review on Present development in refrigeration jet ejector system Volume: 03 Issue: 0 May-201 wwwirjetnet p-issn: 239-0072 A review on Present development in refrigeration jet ejector system Abstract: This paper focuses and gives idea on the development of ejector cooling

More information

ANALYSIS OF STEAM EJECTOR BY USING COMPUTATIONAL FLUID DYNAMICS

ANALYSIS OF STEAM EJECTOR BY USING COMPUTATIONAL FLUID DYNAMICS , pp.41~51 Thomson Reuters ID: L-5236-2015 ANALYSIS OF STEAM EJECTOR BY USING COMPUTATIONAL FLUID DYNAMICS Dr.I Satyanarayana 1 Pricipal &Professor of Mechanical Engineering,Sri Indu Institute of Engineering

More information

France Marie M. Orden and Menandro S. Berana. Proceedings of the World Congress on Engineering 2017 Vol II WCE 2017, July 5-7, 2017, London, U.K.

France Marie M. Orden and Menandro S. Berana. Proceedings of the World Congress on Engineering 2017 Vol II WCE 2017, July 5-7, 2017, London, U.K. , July 5-7, 2017, London, U.K. Design and Analysis of Incorporating Two Ejectors for Compression Recovery in the Inlet and Outlet Points of the Compressor in a Vapor Compression System France Marie M.

More information

Compound ejectors with improved off-design performance

Compound ejectors with improved off-design performance Compound ejectors with improved off-design performance Dr M. Dennis 1, Dr K. Garzoli 2 1,2 Centre for Sustainable Energy Systems School of Engineering The Australian National University Canberra, ACT 0200

More information

Design of a Solar-Driven Ejector Cooling System

Design of a Solar-Driven Ejector Cooling System Design of a Solar-Driven Ejector Cooling System S. du Clou and M.J. Brooks University of KwaZulu-Natal, Durban, 44, South Africa Centre for Renewable and Sustainable Energy Studies Abstract The Pulse Refrigeration

More information

Three-dimensional Numerical Investigations on Ejector of Vapour Jet Refrigeration System

Three-dimensional Numerical Investigations on Ejector of Vapour Jet Refrigeration System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Three-dimensional Numerical Investigations on Ejector of Vapour Jet Refrigeration

More information

Solar Absorption Aqua-Ammonia Absorption system simulation base on Climate of Malaysia

Solar Absorption Aqua-Ammonia Absorption system simulation base on Climate of Malaysia Solar Absorption Aqua-Ammonia Absorption system simulation base on Climate of Malaysia POORYA OOSHAKSARAEI 1, SOHIF MAT 1, M. YAHYA 1, AHMAD MAHIR RAZALI 1, AZAMI ZAHARIM 2, K. SOPIAN 3 1 Solar Energy

More information

Study on Performance Enhancement of Solar Ejector Cooling System

Study on Performance Enhancement of Solar Ejector Cooling System International Refereed Journal of Engineering and Science (IRJES) ISSN (Online) 2319-183X, (Print) 2319-1821 Volume 6, Issue 8 (August 2017), PP.01-06 Study on Performance Enhancement of Solar Ejector

More information

ANALYSIS OF REFRIGERATION CYCLE PERFORMANCE WITH AN EJECTOR

ANALYSIS OF REFRIGERATION CYCLE PERFORMANCE WITH AN EJECTOR 000 (06) DOI:.5/ matecconf/067000 ICMER 05 ANALYSIS OF REFRIGERATION CYCLE PERFORMANCE WITH AN EJECTOR Wani J. R., Aklilu T. Baheta,a, Abraham D. Woldeyohannes, and Suhaimi Hassan Department of Mechanical

More information

COMPARATIVE ANALYSES OF TWO IMPROVED CO 2 COMBINED COOLING, HEATING, AND POWER SYSTEMS DRIVEN BY SOLAR ENERGY

COMPARATIVE ANALYSES OF TWO IMPROVED CO 2 COMBINED COOLING, HEATING, AND POWER SYSTEMS DRIVEN BY SOLAR ENERGY S93 Introduction COMPARATIVE ANALYSES OF TWO IMPROVED CO 2 COMBINED COOLING, HEATING, AND POWER SYSTEMS DRIVEN BY SOLAR ENERGY by Wanjin BAI a* and Xiaoxiao XU b a School of Mechanical and Vehicle Engineering,

More information

Parametric Study of a Vapor Compression Refrigeration Cycle Using a Two-Phase Constant Area Ejector

Parametric Study of a Vapor Compression Refrigeration Cycle Using a Two-Phase Constant Area Ejector Vol:7, No:, 01 Parametric Study of a Vapor Compression Refrigeration Cycle Using a Two-Phase Constant Area Ejector E. Elgendy International Science Index, Mechanical and Mechatronics Engineering Vol:7,

More information

CFD ANALYSIS OF STEAM EJECTOR WITH DIFFERENT NOZZLE DIAMETER

CFD ANALYSIS OF STEAM EJECTOR WITH DIFFERENT NOZZLE DIAMETER CFD ANALYSIS OF STEAM EJECTOR WITH DIFFERENT NOZZLE DIAMETER G.Saidulu 1, A.Purender reddy 2, Shreenivas 3 1 Student,Mech Dept,Sphoorthy Engineering College, Hyderabad,(India) 2 Assistant professor,mech

More information

Readdressing working fluid selection with a view to designing a variable geometry ejector

Readdressing working fluid selection with a view to designing a variable geometry ejector International Journal of Low-Carbon Technologies Advance Access published May 2, 2013 *Corresponding author: szabolcs@fe.up.pt Readdressing working fluid selection with a view to designing a variable geometry

More information

CFD ANALYSIS OF STEAM EJECTOR WITH DIFFERENT NOZZLE DIAMETER

CFD ANALYSIS OF STEAM EJECTOR WITH DIFFERENT NOZZLE DIAMETER CFD ANALYSIS OF STEAM EJECTOR WITH DIFFERENT NOZZLE DIAMETER 1 B. Sampath 2 Dr.A.Raveendra 1 M.Tech, Thermal Engineering student, Department of Mechanical Engineering, Malla Reddy Engineering College (Autonomous),

More information

Application of Two Stage Ejector Cooling System in a Bus

Application of Two Stage Ejector Cooling System in a Bus Available online at www.sciencedirect.com Energy rocedia 14 (01 187 197 Conference Title Application of Two Stage Ejector Cooling System in a Bus Tawatchai Jaruwongwittaya, Guangming Chen* a nstitute of

More information

Research Article A Numerical Study on the Supersonic Steam Ejector Use in Steam Turbine System

Research Article A Numerical Study on the Supersonic Steam Ejector Use in Steam Turbine System Mathematical Problems in Engineering Volume 13, Article ID 65183, 9 pages http://dx.doi.org/1.1155/13/65183 Research Article A Numerical Study on the Supersonic Steam Ejector Use in Steam Turbine System

More information

CERTIFICATES OF COMPETENCY IN THE MERCHANT NAVY MARINE ENGINEER OFFICER

CERTIFICATES OF COMPETENCY IN THE MERCHANT NAVY MARINE ENGINEER OFFICER CERTIFICATES OF COMPETENCY IN THE MERCHANT NAVY MARINE ENGINEER OFFICER EXAMINATIONS ADMINISTERED BY THE SCOTTISH QUALIFICATIONS AUTHORITY ON BEHALF OF THE MARITIME AND COASTGUARD AGENCY STCW 95 CHIEF

More information

This document is downloaded from DR-NTU, Nanyang Technological University Library, Singapore.

This document is downloaded from DR-NTU, Nanyang Technological University Library, Singapore. This document is downloaded from DR-NTU, Nanyang Technological University Library, Singapore. Title Experimentation and cycle performance prediction of hybrid A/C system using automobile exhaust waste

More information

Energy and Exergy Analysis of Combined Ejector-Absorption Refrigeration System

Energy and Exergy Analysis of Combined Ejector-Absorption Refrigeration System Energy and Exergy Analysis of Combined Ejector- Seyed Reza Fakheri 1, Hadi Kargar Sharif Abad 2, Hossein Sakhaii Nia 3 1 M.A Student, Azad University of Science and Research of Semnan, Mechanics College,

More information

High-Efficiency Joule-Thomson Cryocoolers Incorporating an Ejector

High-Efficiency Joule-Thomson Cryocoolers Incorporating an Ejector 1 High-Efficiency Joule-Thomson Cryocoolers Incorporating an Ejector H.S. Cao 1, S. Vanapalli 1, H.J. Holland 1, C.H. Vermeer 2, T. Tirolien 3, H.J.M. ter Brake 1 1 University of Twente, 7500 AE, Enschede,

More information

A Validated Numerical Experimental Design Methodology for a Movable Supersonic Ejector Compressor for Waste Heat Recovery

A Validated Numerical Experimental Design Methodology for a Movable Supersonic Ejector Compressor for Waste Heat Recovery A Validated Numerical Experimental Design Methodology for a Movable Supersonic Ejector Compressor for Waste Heat Recovery Sajad Alimohammadi 1*, Tim Persoons 1, Darina B. Murray 1, Mohamadreza S. Tehrani

More information

CFD Study of a Variable Flow Geometry Radial Ejector

CFD Study of a Variable Flow Geometry Radial Ejector Proceedings of the 4 th International Conference of Fluid Flow, Heat and Mass Transfer (FFHMT'17) Toronto, Canada August 21 23, 2017 Paper No. 123 DOI: 10.11159/ffhmt17.123 CFD Study of a Variable Flow

More information

CFD study of variable geometry ejector using R600a to detect optimal geometry for ejector refrigeration system

CFD study of variable geometry ejector using R600a to detect optimal geometry for ejector refrigeration system 77 mmemodaresacir Downloaded from mmemodaresacir at : IRDT on Sunday August 6th 8 R6a * ghazikhani@ferdowsiumacir 9779 89 9 : 9 : : R6a + 8 9mm * + CFD study of variable geometry ejector using R6a to detect

More information

Effects of Operating Conditions on the Ejector Characteristics and Heat Exchanger Size of Refrigeration System

Effects of Operating Conditions on the Ejector Characteristics and Heat Exchanger Size of Refrigeration System Engineering and Physical Sciences Effects of Operating Conditions on the Ejector Characteristics and Heat Exchanger Size of Refrigeration System Chayarnon SAENGMANEE, Kulachate PIANTHONG *, Wirapan SEEHANAM

More information

Ejectors in a Compressible Network for Gas Turbine Extended Operability

Ejectors in a Compressible Network for Gas Turbine Extended Operability Ejectors in a Compressible Network for Gas Turbine Extended Operability Stefano Rossin, Debora Sassetti GE Oil & Gas, Via Felice Matteucci 2, Florence, Italy Email: stefano.rossin@ge.com; debora.sassetti@ge.com

More information

Development of Terry Turbine Analytical Models for RCIC Off-Design Operation Conditions

Development of Terry Turbine Analytical Models for RCIC Off-Design Operation Conditions Development of Terry Turbine Analytical Models for RCIC Off-Design Operation Conditions Hongbin Zhang Idaho National Laboratory Power Plant Simulation Conference 2019 January 20 23, 2019 Outline Background

More information

CHAPTER 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES

CHAPTER 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES Thermodynamics: An Engineering Approach 8th Edition in SI Units Yunus A. Ç engel, Michael A. Boles McGraw-Hill, 2015 CHAPTER 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES Objectives Develop the conservation

More information

Energy Conversion and Management

Energy Conversion and Management Energy Conversion and Management 50 (2009) 567 575 Contents lists available at ScienceDirect Energy Conversion and Management journal homepage: www.elsevier.com/locate/enconman A combined power cycle utilizing

More information

Copyright 2012 Neal D. Lawrence

Copyright 2012 Neal D. Lawrence Copyright 2012 Neal D. Lawrence ANALYTICAL AND EXPERIMENTAL INVESTIGATION OF TWO-PHASE EJECTOR CYCLES USING LOW-PRESSURE REFRIGERANTS BY NEAL D. LAWRENCE THESIS Submitted in partial fulfillment of the

More information

Eng Thermodynamics I: Sample Final Exam Questions 1

Eng Thermodynamics I: Sample Final Exam Questions 1 Eng3901 - Thermodynamics I: Sample Final Exam Questions 1 The final exam in Eng3901 - Thermodynamics I consists of four questions: (1) 1st Law analysis of a steam power cycle, or a vapour compression refrigeration

More information

CFD analysis of flow phenomena inside thermo vapor compressor influenced by operating conditions and converging duct angles

CFD analysis of flow phenomena inside thermo vapor compressor influenced by operating conditions and converging duct angles Journal of Mechanical Science and Technology 23 (2009) 2366~2375 Journal of Mechanical Science and Technology www.springerlink.com/content/1738-494x DOI 10.1007/s12206-009-0626-7 CFD analysis of flow phenomena

More information

Development of an ejector cooling system with thermal pumping effect

Development of an ejector cooling system with thermal pumping effect International Journal of Refrigeration 29 (2006) 476 484 www.elsevier.com/locate/ijrefrig Development of an ejector cooling system with thermal pumping effect B.J. Huang*, S.S. Hu, S.H. Lee Department

More information

Article Numerical Investigation of Miniature Ejector Refrigeration System Embedded with a Capillary Pump Loop

Article Numerical Investigation of Miniature Ejector Refrigeration System Embedded with a Capillary Pump Loop Article Numerical Investigation of Miniature Ejector Refrigeration System Embedded with a Capillary Pump Loop Jing-Ming Dong *, He Song *, Meng-Qi Yu, Wei-Ning Wang and Xin-Xiang Pan Institute of Marine

More information

Scientific Journal Impact Factor: (ISRA), Impact Factor: [Son, 3(10): October, 2014] ISSN:

Scientific Journal Impact Factor: (ISRA), Impact Factor: [Son, 3(10): October, 2014] ISSN: IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY Performance Characteristics of the R404A Indirect Refrigeration System Using CO2 as a Secondary Refrigerant Jung-In Yoon*, Kwang-Hwan

More information

Effect of Throat Length on Steam Ejector Critical Back Pressure

Effect of Throat Length on Steam Ejector Critical Back Pressure VOL. 61, 2017 CHEMICAL ENGINEERING TRANSACTIONS Guest Editors: Petar S Varbanov, Rongxin Su, Hon Loong Lam, Xia Liu, Jiří J Klemeš Copyright 2017, AIDIC Servizi S.r.l. ISBN 978-88-95608-51-8; ISSN 2283-9216

More information

CHARACTERISTICS OF PRESSURE RECOVERY IN TWO-PHASE EJECTOR APPLIED TO CARBON DIOXIDE HEAT PUMP CYCLE

CHARACTERISTICS OF PRESSURE RECOVERY IN TWO-PHASE EJECTOR APPLIED TO CARBON DIOXIDE HEAT PUMP CYCLE - 1 - CHARACTERISTICS OF PRESSURE RECOVERY IN TWO-PHASE EJECTOR APPLIED TO CARBON DIOXIDE HEAT PUMP CYCLE Satoshi Akagi, Chaobin Dang and Eiji Hihara* Division of Environmental Studies, Graduate School

More information

Dual Source Solar Powered Combined-Cycle Multi-Temperature Refrigeration System for Cold Production in the Context of Off-Grid and Rural Energy Access

Dual Source Solar Powered Combined-Cycle Multi-Temperature Refrigeration System for Cold Production in the Context of Off-Grid and Rural Energy Access International Journal of Thermal Technologies E-ISSN 2277 4114 2017 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijtt/ Research Article Dual Source Solar Powered Combined-Cycle

More information

Code No: RR Set No. 1

Code No: RR Set No. 1 Code No: RR310303 Set No. 1 III B.Tech I Semester Regular Examinations, November 2006 THERMAL ENGINEERING-II (Mechanical Engineering) Time: 3 hours Max Marks: 80 Answer any FIVE Questions All Questions

More information

Study of Performance Improvement of Air Conditioning using Various Heat Recovery Techniques

Study of Performance Improvement of Air Conditioning using Various Heat Recovery Techniques Study of Performance Improvement of Air Conditioning using Various Heat Recovery Techniques Poonpong Swatdepan *, Umphisak Teeboonma and Chawalit Thinvongpituk Department of Mechanical Engineering, Faculty

More information

Performance evaluation of a solar ejector-vapour compression cycle for cooling application

Performance evaluation of a solar ejector-vapour compression cycle for cooling application Journal of Physics: Conference Series OPEN ACCESS Performance evaluation of a solar ejector-vapour compression cycle for cooling application To cite this article: K Megdouli et al 2015 J. Phys.: Conf.

More information

Review Questions for the FE Examination

Review Questions for the FE Examination 110 THE FIRST LAW OF THERMODYNAMICS [CHAP. 4 4.1FE Review Questions for the FE Examination Select a correct statement of the first law if kinetic and potential energy changes are negligible. (A) Heat transfer

More information

*Corresponding authors. Tel.: x415, address: (N. Zhu)

*Corresponding authors. Tel.: x415,  address: (N. Zhu) Optimal design of ground source heat pump system integrated with phase change cooling storage tank in an office building Na Zhu *, Yu Lei, Pingfang Hu, Linghong Xu, Zhangning Jiang Department of Building

More information

MODELING THERMODYNAMIC ANALYSIS AND SIMULATION OF ORGANIC RANKINE CYCLE USING GEOTHERMAL ENERGY AS HEAT SOURCE

MODELING THERMODYNAMIC ANALYSIS AND SIMULATION OF ORGANIC RANKINE CYCLE USING GEOTHERMAL ENERGY AS HEAT SOURCE MODELING THERMODYNAMIC ANALYSIS AND SIMULATION OF ORGANIC RANKINE CYCLE USING GEOTHERMAL ENERGY AS HEAT SOURCE Colak L.* and Bahadir T. *Author for correspondence Department of Mechanical Engineering,

More information

K.S. Rawat 1, H. Khulve 2, A.K. Pratihar 3 1,3 Department of Mechanical Engineering, GBPUAT, Pantnagar , India

K.S. Rawat 1, H. Khulve 2, A.K. Pratihar 3 1,3 Department of Mechanical Engineering, GBPUAT, Pantnagar , India Thermodynamic Analysis of Combined ORC-VCR System Using Low Grade Thermal Energy K.S. Rawat 1, H. Khulve 2, A.K. Pratihar 3 1,3 Department of Mechanical Engineering, GBPUAT, Pantnagar-263145, India 2 Department

More information

Thermodynamic analysis of a direct expansion solar assisted heat pump water heater

Thermodynamic analysis of a direct expansion solar assisted heat pump water heater Thermodynamic analysis of a direct expansion solar assisted heat pump water heater Masoud Yousefi Misagh Moradali Mechanical Engineering Department, South Tehran Branch, Islamic Azad University, Tehran,

More information

Applied Thermal Engineering

Applied Thermal Engineering Applied hermal Engineering 29 (29) 194 1912 Contents lists available at ScienceDirect Applied hermal Engineering journal homepage: www.elsevier.com/locate/apthermeng Performance of ejector cooling system

More information

DESIGN OF VAPOUR ABSORPTION REFRIGERATION SYSTEM OF 1.5TR CAPACITY BY WASTE HEAT RECOVERY PROCESS

DESIGN OF VAPOUR ABSORPTION REFRIGERATION SYSTEM OF 1.5TR CAPACITY BY WASTE HEAT RECOVERY PROCESS Volume 115 No. 7 2017, 613-619 ISSN: 1311-8080 (printed version); ISSN: 1314-3395 (on-line version) url: http://www.ijpam.eu ijpam.eu DESIGN OF VAPOUR ABSORPTION REFRIGERATION SYSTEM OF 1.5TR CAPACITY

More information

Second Law Analysis of a Carbon Dioxide Transcritical Power System in Low-grade Heat Source Recovery

Second Law Analysis of a Carbon Dioxide Transcritical Power System in Low-grade Heat Source Recovery Second Law Analysis of a Carbon Dioxide Transcritical Power System in Low-grade Heat Source Recovery Y. Chen, Almaz Bitew Workie, Per Lundqvist Div. of Applied Thermodynamics and Refrigeration, Department

More information

Ejector Expansion Refrigeration Systems

Ejector Expansion Refrigeration Systems Research Inventy: International Journal Of Engineering And Science Vol.5, Issue 2 (February 2015), PP 25-29 Issn (e): 2278-4721, Issn (p):2319-6483, www.researchinventy.com Ejector Expansion Refrigeration

More information

Performance study on solar assisted heat pump water heater using CO 2 in a transcritical cycle

Performance study on solar assisted heat pump water heater using CO 2 in a transcritical cycle European Association for the Development of Renewable Energies, Environment and Power Quality (EA4EPQ) International Conference on Renewable Energies and Power Quality (ICREPQ 12) Santiago de Compostela

More information

Effect of Suction Nozzle Pressure Drop on the Performance of an Ejector-Expansion Transcritical CO 2 Refrigeration Cycle

Effect of Suction Nozzle Pressure Drop on the Performance of an Ejector-Expansion Transcritical CO 2 Refrigeration Cycle Entropy 2014, 16, 4309-4321; doi:10.3390/e16084309 Article OPEN ACCESS entropy ISSN 1099-4300 www.mdpi.com/journal/entropy Effect of Suction Nozzle Pressure Drop on the Performance of an Ejector-Expansion

More information

UNIVERSITY OF TORONTO FACULTY OF APPLIED SCIENCE AND ENGINEERING FINAL EXAMINATION, DECEMBER 2008 MIE 411H1 F - THERMAL ENERGY CONVERSION

UNIVERSITY OF TORONTO FACULTY OF APPLIED SCIENCE AND ENGINEERING FINAL EXAMINATION, DECEMBER 2008 MIE 411H1 F - THERMAL ENERGY CONVERSION UNIVERSITY OF TORONTO FACULTY OF APPLIED SCIENCE AND ENGINEERING FINAL EXAMINATION, DECEMBER 2008 MIE 411H1 F - THERMAL ENERGY CONVERSION Exam Type: X Examiner: J.S. Wallace You may use your copy of the

More information

A Review on Performance of Air Conditioning System using Two Phase Ejector

A Review on Performance of Air Conditioning System using Two Phase Ejector International Journal of Current Engineering and Technology E-ISSN 2277 4106, P-ISSN 2347 5161 2016 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article A Review

More information

Experimental Studies on a Solar Assisted Heat Pump Working with R22: An Exergy Point of View

Experimental Studies on a Solar Assisted Heat Pump Working with R22: An Exergy Point of View Journal of Advanced Engineering Research ISSN: 2393-8447 Volume 4, Issue 2, 2017, pp94-98 Experimental Studies on a Solar Assisted Heat Pump Working with R22: An Exergy Point of View Lokesh Paradeshi 1,

More information

Analysis of a Two Phase Flow Ejector for the Transcritical CO 2 Cycle

Analysis of a Two Phase Flow Ejector for the Transcritical CO 2 Cycle 3, Page Analysis of a Two Phase Flow Ejector for the Transcritical CO Cycle Fang LIU *, Eckhard A. GROLL Purdue University, School of Mechanical Engineering, West Lafayette, IN, USA Tel: 765-494-03, Fax:

More information

OPTIMIZATION OF PCM NUMBER IN HOT WATER TANK FOR THE APPLICATION OF SOLAR DRIVEN ADSORPTION CHILLER IN TROPICAL CLIMATE

OPTIMIZATION OF PCM NUMBER IN HOT WATER TANK FOR THE APPLICATION OF SOLAR DRIVEN ADSORPTION CHILLER IN TROPICAL CLIMATE OPTIMIZATION OF PCM NUMBER IN HOT WATER TANK FOR THE APPLICATION OF SOLAR DRIVEN ADSORPTION CHILLER IN TROPICAL CLIMATE 1 NASRUDDIN, 2 LEMINGTON, 3 M. IDRUS ALHAMID 1,3 Department of Mechanical Engineering,

More information

The Benefit of Variable-Speed Turbine Operation for Low Temperature Thermal Energy Power Recovery

The Benefit of Variable-Speed Turbine Operation for Low Temperature Thermal Energy Power Recovery Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2014 The Benefit of Variable-Speed Turbine Operation for Low Temperature Thermal Energy

More information

Performance Evaluation of Solar Assisted Heat Pump Water Heating System

Performance Evaluation of Solar Assisted Heat Pump Water Heating System IOSR Journal of Engineering (IOSRJEN) e-issn: 50-301, p-issn: 78-8719 Vol. 3, Issue 4 (April. 013), V PP 1-17 Performance Evaluation of Solar Assisted Heat Pump Water Heating System Kokila. R.N 1, Rajakumar.S

More information

Stefan Elbel Pega Hrnjak University of Illinois at Urbana-Champaign

Stefan Elbel Pega Hrnjak University of Illinois at Urbana-Champaign Experimental Validation of a CO 2 Prototype Ejector with Integrated High-Side Pressure Control Stefan Elbel (elbel@uiuc.edu), Pega Hrnjak (pega@uiuc.edu) University of Illinois at Urbana-Champaign Saalfelden,

More information

Chapter 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES

Chapter 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES Thermodynamics: An Engineering Approach Seventh Edition Yunus A. Cengel, Michael A. Boles McGraw-Hill, 2011 Chapter 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES Copyright The McGraw-Hill Companies, Inc.

More information

Enhancement on the Performance of Refrigeration System Using the Nano-Refrigerant

Enhancement on the Performance of Refrigeration System Using the Nano-Refrigerant Journal of Energy and Power Engineering 11 (2017) 237-243 doi: 10.17265/1934-8975/2017.04.004 D DAVID PUBLISHING Enhancement on the Performance of Refrigeration System Using the Nano-Refrigerant Qasim

More information

NUMERICAL INVESTIGATION OF AN R744 LIQUID EJECTOR FOR SUPERMARKET REFRIGERATION SYSTEMS

NUMERICAL INVESTIGATION OF AN R744 LIQUID EJECTOR FOR SUPERMARKET REFRIGERATION SYSTEMS THERMAL SCIENCE: Year 2016, Vol. 20, No. 4, pp. 1259-1269 1259 NUMERICAL INVESTIGATION OF AN R744 LIQUID EJECTOR FOR SUPERMARKET REFRIGERATION SYSTEMS by Michal HAIDA a, Jacek SMOLKA a*, Michal PALACZ

More information

Exergy analysis of a flat plate solar collector

Exergy analysis of a flat plate solar collector Exergy analysis of a flat plate solar collector Sunil Chamoli GRDIMT Dehradun, Uttarakhand, India Abstract In this study, exergetic performance analysis of flat plate solar collector has been carried out

More information

PARAMETRIC STUDY OF GAS TURBINE CYCLE COUPLED WITH VAPOR COMPRESSION REFRIGERATION CYCLE FOR INTAKE AIR COOLING

PARAMETRIC STUDY OF GAS TURBINE CYCLE COUPLED WITH VAPOR COMPRESSION REFRIGERATION CYCLE FOR INTAKE AIR COOLING International Journal of Mechanical Engineering and Technology (IJMET) Volume 9, Issue 9, September 2018, pp. 248 261, Article ID: IJMET_09_09_029 Available online at http://www.iaeme.com/ijmet/issues.asp?jtype=ijmet&vtype=9&itype=9

More information

Mechanical Engineering Journal

Mechanical Engineering Journal Bulletin of the JSME Mechanical Engineering Journal Vol.3, No.6, 2016 Experimental study on the behavior of the two phase flow shock waves occurring in the ejector refrigeration cycle Haruyuki NISHIJIMA*,

More information

ENERGY AND EXERGY ANALYSIS OF HEAT PUMP USING R744/R32 REFRIGERANT MIXTURE

ENERGY AND EXERGY ANALYSIS OF HEAT PUMP USING R744/R32 REFRIGERANT MIXTURE THERMAL SCIENCE, Year 2014, Vol. 18, No. 5, pp. 1649-1654 1649 ENERGY AND EXERGY ANALYSIS OF HEAT PUMP USING R744/R32 REFRIGERANT MIXTURE by Fang WANG, Xiao-Wei FAN, Jie CHEN, and Zhi-Wei LIAN School of

More information

PERFORMANCE EVALUATION OF HEAT PUMP SYSTEM USING R744/R161 MIXTURE REFRIGERANT

PERFORMANCE EVALUATION OF HEAT PUMP SYSTEM USING R744/R161 MIXTURE REFRIGERANT THERMAL SCIENCE, Year 2014, Vol. 18, No. 5, pp. 1673-1677 1673 PERFORMANCE EVALUATION OF HEAT PUMP SYSTEM USING R744/R161 MIXTURE REFRIGERANT by Xian-Ping ZHANG a,b, Xin-Li WEI b, Xiao-Wei FAN c*, Fu-Jun

More information

semester + ME6404 THERMAL ENGINEERING UNIT III NOZZLES, TURBINES & STEAM POWER CYCLES UNIT-III

semester + ME6404 THERMAL ENGINEERING UNIT III NOZZLES, TURBINES & STEAM POWER CYCLES UNIT-III ME6404 THERMAL ENGINEERING UNIT III NOZZLES, TURBINES & STEAM POWER CYCLES UNIT-III 3. 1 CONTENTS 3.1 Flow of steam through nozzles: 3.2 Continuity and steady flow energy equations 3.3 Types of Nozzles

More information

Efficiency enhancement of the ocean thermal energy conversion system with a vapor vapor ejector

Efficiency enhancement of the ocean thermal energy conversion system with a vapor vapor ejector Special Issue Article Efficiency enhancement of the ocean thermal energy conversion system with a vapor vapor ejector Advances in Mechanical Engineering 1 10 Ó The Author(s) 2015 DOI: 10.1177/1687814015571036

More information

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Available online at   ScienceDirect. Procedia Engineering 121 (2015 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 121 (1 ) 1880 1886 9th International Symposium on Heating, Ventilation and Air Conditioning (ISHVAC) and the 3rd International

More information

OPTIMIZATION OF PARAMETERS FOR HEAT RECOVERY STEAM GENERATOR (HRSG) IN COMBINED CYCLE PLANTS

OPTIMIZATION OF PARAMETERS FOR HEAT RECOVERY STEAM GENERATOR (HRSG) IN COMBINED CYCLE PLANTS OPTIMIZATION OF PARAMETERS FOR HEAT RECOVERY STEAM GENERATOR (HRSG) IN COMBINED CYCLE PLANTS Muammer Alus, Milan V. Petrovic University of Belgrade-Faculty of Mechanical Engineering, Laboratory of Thermal

More information

ENHANCEMENT OF COEFFICIENT OF PERFORMANCE IN VAPOUR COMPRESSION REFRIGERATION CYCLE

ENHANCEMENT OF COEFFICIENT OF PERFORMANCE IN VAPOUR COMPRESSION REFRIGERATION CYCLE ENHANCEMENT OF COEFFICIENT OF PERFORMANCE IN VAPOUR COMPRESSION REFRIGERATION CYCLE Dr Venkata Ramana Reddy Mula 1, H.V.Harish 2 1 Professor and Head, Department of Aeronautical Engineering NMIT BANGALORE

More information

CONTROL VOLUME ANALYSIS USING ENERGY. By Ertanto Vetra

CONTROL VOLUME ANALYSIS USING ENERGY. By Ertanto Vetra CONTROL VOLUME ANALYSIS USING ENERGY 1 By Ertanto Vetra Outlines Mass Balance Energy Balance Steady State and Transient Analysis Applications 2 Conservation of mass Conservation of mass is one of the most

More information

Vapor injected heat pump using non-azeotropic mixture R32/R1234ze(E) for low temperature ambient

Vapor injected heat pump using non-azeotropic mixture R32/R1234ze(E) for low temperature ambient Abstract Vapor injected heat pump using non-azeotropic mixture R32/R1234ze(E) for low temperature ambient Zuo Cheng, Wenxing Shi, Baolong Wang * Beijing Key Laboratory of Indoor Air Quality Evaluation

More information

R13 SET - 1 '' ''' '' ' '''' Code No: RT31035

R13 SET - 1 '' ''' '' ' '''' Code No: RT31035 R13 SET - 1 III B. Tech I Semester Regular/Supplementary Examinations, October/November - 2016 THERMAL ENGINEERING II (Mechanical Engineering) Time: 3 hours Max. Marks: 70 Note: 1. Question Paper consists

More information

AREN 2110: Thermodynamics Spring 2010 Homework 7: Due Friday, March 12, 6 PM

AREN 2110: Thermodynamics Spring 2010 Homework 7: Due Friday, March 12, 6 PM AREN 2110: Thermodynamics Spring 2010 Homework 7: Due Friday, March 12, 6 PM 1. Answer the following by circling the BEST answer. 1) The boundary work associated with a constant volume process is always

More information

- 2 - SME Q1. (a) Briefly explain how the following methods used in a gas-turbine power plant increase the thermal efficiency:

- 2 - SME Q1. (a) Briefly explain how the following methods used in a gas-turbine power plant increase the thermal efficiency: - 2 - Q1. (a) Briefly explain how the following methods used in a gas-turbine power plant increase the thermal efficiency: i) regenerator ii) intercooling between compressors (6 marks) (b) Air enters a

More information

Thermodynamics: An Engineering Approach, 6 th Edition Yunus A. Cengel, Michael A. Boles McGraw-Hill, 2008

Thermodynamics: An Engineering Approach, 6 th Edition Yunus A. Cengel, Michael A. Boles McGraw-Hill, 2008 Thermodynamics: An Engineering Approach, 6 th Edition Yunus A. Cengel, Michael A. Boles McGraw-Hill, 2008 Chapter 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES SUMMARY 1 CONSERVATION OF MASS Conservation

More information

Chapter 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES

Chapter 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES Thermodynamics: An Engineering Approach Seventh Edition in SI Units Yunus A. Cengel, Michael A. Boles McGraw-Hill, 2011 Chapter 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES Copyright The McGraw-Hill Companies,

More information

OPTIMIZING THE GENERATOR AND ABSORBER THERMAL LOAD OF COMBINED ABSORPTION-EJECTOR REFRIGERATION SYSTEM

OPTIMIZING THE GENERATOR AND ABSORBER THERMAL LOAD OF COMBINED ABSORPTION-EJECTOR REFRIGERATION SYSTEM OPTIMIZING THE GENERATOR AND ABSORBER THERMAL LOAD OF COMBINED ABSORPTION-EJECTOR REFRIGERATION SYSTEM Azher M.Abed,,, M.A.Alghoul,, Ali Najah Al-Shamani,,K. Sopian, Solar Energy Research Institute (SERI),

More information

CHAPTER 1 BASIC CONCEPTS

CHAPTER 1 BASIC CONCEPTS GTU Paper Analysis CHAPTER 1 BASIC CONCEPTS Sr. No. Questions Jan 15 Jun 15 Dec 15 May 16 Jan 17 Jun 17 Nov 17 May 18 Differentiate between the followings; 1) Intensive properties and extensive properties,

More information

Theoretical investigations on combined power and ejector cooling system powered by low-grade energy source

Theoretical investigations on combined power and ejector cooling system powered by low-grade energy source Theoretical investigations on combined power and ejector cooling system powered by low-grade energy source... Xiangjie Chen *, Yuehong Su, Siddig Omer and Saffa Riffat Department of Architecture and Built

More information

ASSESSMENT OF R290 AS A POSSIBLE ALTERNATIVE TO R22 IN DIRECT EXPANSION SOLAR ASSISTED HEAT PUMPS

ASSESSMENT OF R290 AS A POSSIBLE ALTERNATIVE TO R22 IN DIRECT EXPANSION SOLAR ASSISTED HEAT PUMPS Paradeshi, L., et al.: Assesment of R290 as a Possible Alternative to R22 in S369 ASSESSMENT OF R290 AS A POSSIBLE ALTERNATIVE TO R22 IN DIRECT EXPANSION SOLAR ASSISTED HEAT PUMPS by Lokesh PARADESHI *,

More information

Solar Powered Vapour Absorption Refrigeration (SPVAR) System as a rural microenterprise

Solar Powered Vapour Absorption Refrigeration (SPVAR) System as a rural microenterprise Solar Powered Vapour Absorption Refrigeration (SPVAR) System as a rural microenterprise Anurag Mudgal, Pandit Deendayal Petroleum University, India Jatin Kumar Patel, Pandit Deendayal Petroleum University,

More information

THEORETICAL STUDY OF HEAT PUMP SYSTEM USING CO 2 /DIMETHYLETHER AS REFRIGERANT

THEORETICAL STUDY OF HEAT PUMP SYSTEM USING CO 2 /DIMETHYLETHER AS REFRIGERANT THERMAL SCIENCE, Year 2013, Vol. 17, No. 5, pp. 1261-1268 1261 THEORETICAL STUDY OF HEAT PUMP SYSTEM USING CO 2 /DIMETHYLETHER AS REFRIGERANT by Xiao-Wei FAN a*, Xian-Ping ZHANG b,c, Fu-Jun JU a, and Fang

More information

Empirical correlation for ejector design

Empirical correlation for ejector design International Journal of Refrigeration 22 (1999) 379 388 Empirical correlation for ejector design B.J. Huang*, J.M. Chang Department of Mechanical Engineering, National Taiwan University, Taipei, Taiwan

More information

BINARY BLEND OF CARBON DIOXIDE AND FLUORO ETHANE AS WORKING FLUID IN TRANSCRITICAL HEAT PUMP SYSTEMS

BINARY BLEND OF CARBON DIOXIDE AND FLUORO ETHANE AS WORKING FLUID IN TRANSCRITICAL HEAT PUMP SYSTEMS THERMAL SCIENCE, Year 2015, Vol. 19, No. 4, pp. 1317-1321 1317 Introduction BINARY BLEND OF CARBON DIOXIDE AND FLUORO ETHANE AS WORKING FLUID IN TRANSCRITICAL HEAT PUMP SYSTEMS by Xian-Ping ZHANG a*, Fang

More information