EVALUATION OF THE THERMAL PERFORMANCE OF FIVE REFRIGERATED VANS

Size: px
Start display at page:

Download "EVALUATION OF THE THERMAL PERFORMANCE OF FIVE REFRIGERATED VANS"

Transcription

1 EVALUATION OF THE THERMAL PERFORMANCE OF FIVE REFRIGERATED VANS S. ESTRADA-FLORES, A. EDDY and N. SMALE Supply Chain Innovation, Food Science Australia PO Box 52, North Ryde, NSW 7, Australia. Fax: ; S. Estrada-Flores@csiro.au ABSTRACT An experimental evaluation of insulation effectiveness, pull-down times and effectiveness of the mechanical refrigeration unit was performed on five refrigerated panel vans. Additionally, a mapping of temperature variability in the cargo space was carried out during a simulated logistic scenario encompassing several door openings. The temperature variability measured in the vans was neither correlated to the effectiveness of the insulation nor the time required to achieve complete cooling of the cargo space. These criteria are common thermal performance indicators used to evaluate refrigerated vehicles in international standards. The effectiveness of insulation was correlated to the pull-down times, presenting the possibility of calculating the former as a function of the latter. The temperature variability was correlated with the time required for the unit to recover temperature control after a door opening interval and the difference between the maximum and minimum temperatures reached during a door opening cycle. Keywords: thermal performance; vehicles; insulation; temperature; regulation; cooling; refrigerated; 1. INTRODUCTION Thermal performance standards serve as benchmarking instruments to compare refrigerated transport systems and to ensure that these systems provide a minimum level of operating effectiveness. Insulated and refrigerated sea, rail and road freight containers must comply with the international standard ISO (International Organization for Standardization, 1996). In Europe, the specifications for refrigerated vehicles are covered by the International Agreement for the Transport of Perishables (United Nations Economic and Social Council, 23), which has the status of a standard. The Australian Standard for refrigerated vehicles (Standards Australia, 23) defines testing specifications and procedures to evaluate the thermal performance of refrigerated equipment, used to transport perishable goods by road. The equipment covered by the standard includes insulated trailer, truck and van bodies (single or multi-compartment) fitted with any form of refrigeration. Key thermal tests described in AS and relevant to refrigeration plants already fitted to the unit are: (a) Insulation effectiveness (heat leakage) test by the inner heating method: This test determines the effectiveness of the insulated body, measured as a K value, by means of creating a temperature differential of no less than 2 o C between the cargo space and the external environment. The method includes measurement of at least twelve temperatures covering the corners, [all] walls, ceiling and floor of the vehicle. (b) Performance test of the refrigeration system: This test evaluates the ability of the truck to maintain the set-point temperature within the cargo space during hours of uninterrupted operation. The vehicle is tested for a further hours with an additional heat load. The AS specifies an ambient external temperature of 3 o C for this test. Innovative Equipment and Systems for Comfort and Food Preservation, Auckland, NZ, 26

2 (c) In-service (pull-down) test: This assessment measures the time required to cool down the empty truck to the classification temperature. The evaluation of vehicles following the AS and similar standards rely on temperature measurements in selected locations throughout the tested body; however, these locations usually reflect the thermal behaviour of the layers adjacent to the walls of the van, rather than the thermal behaviour of the cargo space. Furthermore, most regulations do not test vehicles under realistic logistics scenarios. For example, vehicles carrying out home delivery operations will have at least three deliveries (i.e. three door openings) per hour (Clancy, 2). Frequent door openings can lead to increased evaporator frosting, thus increasing the need for defrosts, particularly in humid weather conditions. This paper presents the results of thermal performance tests carried out on five refrigerated vans, following the methodology described in the Australian Standard Additionally, a detailed mapping of temperature variability in the cargo space of each van was carried out during an -hour simulated delivery schedule. 2. METHODOLOGY Tests were carried out in Food Science Australia s controlled-environment shipping-container test facility Instrumentation of the vans The characteristics of the vehicles tested are summarised in Table 1. Table 1. Mechanical characteristics of the vehicles tested. VAN MODEL PAYLOAD CAPACITY (m 3 ) 1 Mercedes Sprinter 3CDI SWB 2 Ford Transit/Therma Truck (mid-roof, long wheelbased) 3 Mercedes Sprinter 3CDI SWB Mercedes Sprinter 3CDI SWB 5 Mercedes Sprinter 3CDI LWB High Roof MEAN SURFACE AREA (m 2 ) COOLING PLANT AND CAPACITY AT 2,5 RPM Transfridge chiller model Transfridge chiller model Transfridge chiller model Transfridge chiller model Transfridge chiller model All vehicles were insulated post-production with polyurethane foam.type-t thermocouples (diameter =.5 mm; nominal accuracy ±.2 ºC) were placed in each van, as described below: (a) K value test: Sixteen measurement points in the inside and outside of the vans were used to determine their thermal behaviour. Care was taken to avoid placement of thermocouples on thermal bridges (e.g. metallic fittings, pockets in the insulation). (b) Temperature mapping in the cargo space: The cargo space was divided into five imaginary slices. Each slice had nine thermocouples distributed throughout the van s height and width, in a 3x3 grid. Innovative Equipment and Systems for Comfort and Food Preservation, Auckland, NZ, 26

3 All thermocouples were connected to two 6-channel, battery-powered data loggers Eltek SQ 1 (Eltek Ltd, Cambridge). The measuring systems were previously calibrated with ice slurry, by means of a standard measuring system, encompassing a -wire platinum resistance thermometer sensor connected to a Hart Scientific Instrument Model 152 (system resolution =.1 o C) Heat leakage ( K value ) test Testing was carried out inside the test facility at 1 o C. Once all thermocouples were attached to the van s body, the van was brought to thermal equilibrium with the external air. Two fans and a heater were placed inside the van and connected to an uninterruptible power supply (Powertech, 5kVA). The power consumption of fans and heater were measured during the test, by means of a PM39 multifunction electricity meter (accuracy =.5% of reading; Northern Design Electronics Ltd, UK). Additionally, twenty-five fans were distributed to ensure air velocities between 1 and 2 m s -1 over the external surface of the van. Floor drains, defrost drains and relief valves were functioning as normal. The doors of the van were closed as normal. The heater power was adjusted through a Variac autotransformer (model W2HMT3A -2V 2 VAC) to obtain a temperature difference greater than 2 o C. Temperature data was recorded every minute during the warm-up and the final steady-state -hr period. The data was analysed to obtain the mean air and skin temperatures inside and outside the truck during the steady-state period. The K value was calculated as follows: K value Q = (1) S m ( T T ) ms, i ms, o Therefore, the K value is a reflection of an overall heat transfer coefficient, rather than a formal expression of the thermal conductivity of the van s walls. The K value obtained experimentally reflects: (a) the properties of the van s insulation; (b) the van s design and (c) the van s manufacturing process. An insulated body may be insulated with a highquality, low conductivity material, but due to its design and/or manufacturing process, the body may have significant thermal losses in the form of structural pockets, air gaps incorporated in the foaming process, metallic latches, structural ribs, hinges, rivets or screws. These losses cannot be predicted theoretically without an in-depth knowledge of the dimension and location of the thermal bridges in each body tested Pull-down test Immediately after the K value test, the temperature of the test facility was set to 3 o C and the van s doors were opened to reach thermal equilibrium with the external temperature. Once the external and internal temperatures were within a ±3 o C tolerance band around 3 o C, the doors were closed and the refrigeration unit of the van was turned on. The temperature set-point of the unit was set to 2 C. The unit was left to operate, until the internal temperature was 2 o C, as read by the sensor signalling the start of the normal on/off cycling of the refrigeration unit. The time to achieve this cooling was considered as the pull-down period (t pull-down, hrs). 2.. Effectiveness of the mechanical refrigeration unit in maintaining a specified temperature The pull-down phase was immediately followed by an -hr period of uninterrupted, normal operation at 2 o C. After this first period, the heater inside the cargo space was activated and adjusted to increase the internal heat load. The AS specifies that the extra heat load should be 35% of the infiltration heat load, using the K value calculated with Eq. (1). After the K value test was performed, it was apparent that some of the vans would not be able to maintain temperature control with an extra 35% heat load. Therefore, for the purposes of this paper, it was decided to add only an extra 3% heat load. The extra heat load Q h was calculated as: Innovative Equipment and Systems for Comfort and Food Preservation, Auckland, NZ, 26

4 ( T T ) Q h.3 K value S m ms, o ms, i = (2) The van was left to operate with the additional heat load for a further -hr period. A pass or fail status was given to each van, depending on its ability to sustain the 2 o C temperature set-point during the -hr steady state period with no extra heat load and the -hr steady state period with extra heat load Temperature mapping during door opening tests This test was conducted in the test facility at a temperature of 3 o C and a relative humidity in the range of 5 to 9%. The relative humidity was kept high, to assess the performance of the vans under extreme ambient conditions. The trial simulated a logistic schedule for an hr working day, encompassing a pull-down of one hour followed by fourteen 1-minute door openings at approximately 3-minute intervals. Only one rear door was opened. Cargo space temperatures were measured every seconds during the whole testing period. The analysis of the temperature variability was performed by means of histograms, showing the frequency temperature distribution of the data collected for each van. The following measures were calculated: (a) Mean temperature T m, represented by the average of all the temperatures measured in the cargo space in each van. (b)total variation, represented by the standard deviation σ. (c) Fraction of temperatures fulfilling the 2 to o C temperature guideline for pharmaceutical products (P x ), calculated as the number of temperature values falling within the aforementioned range divided by the total number of temperature measurements. (d) Recovery time (t recovery ) or the time required for the unit to recover temperature control in the cargo space after a door opening, as measured by the grid of sensors installed inside the van. (e) Amplitude of the mean temperature rise during the door opening cycle (A do ), calculated as the average difference between the peak mean cargo space temperature reached at the end of the door opening, and the minimum temperature reached when temperature control was regained. Once T m, σ, P x, t recovery and A do were calculated, the relationship between these measures and the two parameters obtained from the thermal performance tests (K value and t pull-down ) was investigated by means of a correlation analysis. 3. RESULTS AND DISCUSSION Table 2 summarises the results obtained after testing of the K value, refrigeration performance and pull-down tests. Even though Table 1 shows that Models 1, 3 and have similar mechanical characteristics, their different K values suggest variations in the effect of thermal bridges in these three models, possibly due to different methods used during the foaming of the insulation. Differences in the age of the insulation could have also led to different K values. The K value measured in the five vans ranged from.2 to 1.2 W m -2 o C -1. Models 2 and 3 showed similar values, which were approximately 1.5 times higher than the value found for Model 1. Innovative Equipment and Systems for Comfort and Food Preservation, Auckland, NZ, 26

5 Model Table 2. Summary of results of the K value test, pull-down test and effectiveness of the mechanical refrigeration unit. K value (W m -2 o C -1 ) t pulldown (h) Refrigeration capacity during -hrs, no extra heat load Heat load entering the cargo area (W) Pass/fail criteria Refrigeration capacity during -hrs, extra heat load added Extra heat load added (W) Pass/fail criteria Pass 253 Pass Pass 369 Fail Pass 375 Fail Pass 26 Pass a 1 Fail 75 Fail a The unit failed to achieve a full pull-down (cooling) to +2 o C. Although Models 1 to achieved normal cycling conditions, only Models 1 and continued to operate normally during the period of hours with an additional heat load. These two models also showed the shortest pull-down times and the lowest K value. Model 5 failed to achieve a pull-down, even though its K value was comparable with the values found for Models 2 and 3. Insufficient refrigeration capacity in Model 5 may have produced this result. Figure 1 shows the average temperatures measured in the cargo space during the last 7 hours of the door opening test. Only Model 1 was able to return to a normal cycling temperature operation after each door opening. Although Model performed well during the first three door openings, temperatures below o C were observed after this point, particularly after each door opening. This was possibly due to the control system of the cooling unit attempting to regain temperature control after each opening by excessively lowering the air delivery temperature. Other models showed an initial loss of temperature control due to a slow pull-down period (e.g. Model 2), a gradual loss of control during the test (e.g. Model 3) or a combination of both (e.g. Model 5). Figure 2 shows the frequency distribution charts of the temperature data collected during the 7-hour period for each model, representing around 2, values measured in 5 locations, distributed as explained in Section 2.3. The initial one-hour pull-down period was not included in the analysis. Innovative Equipment and Systems for Comfort and Food Preservation, Auckland, NZ, 26

6 2 Model 1 2 Model Model Model Model Figure 1. Mean cargo space temperatures measured in Models 1 to 5, during the final 7 hours of the door opening test. The dotted lines indicate the temperature set-point (2 o C). Table 3 shows the results obtained for the five temperature variability indicators calculated. The proportion of measured temperatures falling within the required temperature range of 2 to o C, for the logistics operations commonly performed in these vans, ranged from 93% (for Model 1) to 6% (for Model ). Although the latter van achieved a full pull-down and passed the refrigeration performance tests, the van was not capable of complying with the 2 to o C specification. Table 3. Parameters calculated during the door opening test for all models. MODEL T m ( o C) σ P x t recovery A do ( o C) (hrs) Innovative Equipment and Systems for Comfort and Food Preservation, Auckland, NZ, 26

7 25 Model 1 25 Model Model 3 25 Model Model Figure 2. distribution charts encompassing temperature data measured in Models 1 to 5, during the final 7 hours of the door opening test. The dotted lines indicate the recommended temperature range for pharmaceutical products (2 to o C). Table shows the correlation coefficients calculated for the seven performance indicators. As expected, vans that presented T m values close to the targeted temperature mean (5 o C) presented the highest P x values. The strong correlation between K value and t pull-down was not expected, though there is an intuitive relationship between these two parameters (i.e. lower K value should lead to shorter pull-down times). This presents the possibility of predicting a K value as a function of t pull-down, thus decreasing the time and cost of testing procedures. However, further experimental work is required to assess the robustness of this relationship for a wider range of K value and sizes of bodies. Innovative Equipment and Systems for Comfort and Food Preservation, Auckland, NZ, 26

8 Table. Correlation coefficients between thermal performance indicators and capability indices T m σ P x K value t pull-down t recovery A do T m 1 σ.1 1 P x K value t pull-down t recovery A do K value correlated poorly with the five parameters describing the temperature variability in the cargo space. However, the correlation of σ (which represents the total temperature variation within the cargo space) with respect to t recovery and A do was strong. This suggests that (a) the most significant factor affecting temperature variability during in-transit conditions is the management of door openings; (b) K value influences the initial cooling rate of the van, but not the cargo space temperature during typical working conditions.. CONCLUSIONS The temperature variability of the cargo space measured in five refrigerated panel vans, when subjected to realistic logistics scenarios, was neither correlated to the effectiveness of the insulation (measured as an overall heat transfer coefficient) nor the time required to achieve complete cooling of the cargo space (measured as a pull-down time, which is in turn an indication of the available refrigeration power). Effectiveness of insulation and pull-down time are common thermal performance indicators used to evaluate refrigerated vehicles in international standards. The effectiveness of insulation was correlated to the pull-down time, presenting the possibility of calculating the former as a function of the latter, thus decreasing the time and cost of the testing procedures. The temperature variability during a simulated delivery schedule, encompassing several door openings, was correlated with the time required for the unit to recover temperature control after a door opening and the difference between the maximum and minimum temperatures reached during a door opening cycle. ACKNOWLEDGEMENTS The authors gratefully acknowledge the support of Mr Robert Itaoui and Mr Micheal Gammon during the development of this project. NOMENCLATURE A do amplitude of mean temperature during the door opening cycle ( o C) K value overall heat transfer coefficient (W m -2 o C -1 ) P x fraction of temperatures fulfilling the 2 to o C temperature guideline for pharmaceutical products Q electrical power dissipated inside the body by the heaters and fans (W) Q h total heat load during the final -hr period in the refrigeration capacity test (W) S m mean surface area of the body (m 2 ) T m mean temperature ( o C) Innovative Equipment and Systems for Comfort and Food Preservation, Auckland, NZ, 26

9 T ms arithmetic mean of skin temperature ( o C) t pull-down pull-down time (h) recovery time (h) t recovery Greek letters σ standard deviation Subscripts o outside, external i inside, internal REFERENCES 1. Clancy, S. 2. Small vehicles, great expectations. E-logistics magazine. Issue 2, May. From website: 2. International Organization for Standardization ISO E. Series 1 Freight Containers Specification and testing Part 2: Thermal containers. 51 pp. 3. Standards Australia. 23. AS 92-23: Thermal performance of refrigerated transport equipment Specification and testing. 5 pp.. United Nations Economic and Social Council. Economic Commission for Europe. 23. Agreement on the International Carriage of Perishable Foodstuffs and on the Special Equipment to be used for such Carriage.United Nations. Geneva, including amendments thereto up to Sept pp. Innovative Equipment and Systems for Comfort and Food Preservation, Auckland, NZ, 26

THE USE OF THERMOGRAPHY TO AID DESIGN OF REFRIGERATED ROAD VEHICLES

THE USE OF THERMOGRAPHY TO AID DESIGN OF REFRIGERATED ROAD VEHICLES THE USE OF THERMOGRAPHY TO AID DESIGN OF REFRIGERATED ROAD VEHICLES S. ESTRADA-FLORES and A. EDDY Supply Chain Innovation, Fax: +61 02 94908530; Email: S. Estrada-Flores@csiro.au; Food Science Australia

More information

Tectainers. Special Purpose Containers. Comtainer Options Pty Limited Cnr Pine & Loftus Roads, Yennora P O Box 1011 Fairfield NSW 1860

Tectainers. Special Purpose Containers. Comtainer Options Pty Limited Cnr Pine & Loftus Roads, Yennora P O Box 1011 Fairfield NSW 1860 Tectainers TM Special Purpose Containers Comtainer Options Pty Limited Cnr Pine & Loftus Roads, Yennora P O Box 1011 Fairfield NSW 1860 Tel: +61 (2) 9892 2822 Fax: +61 (2) 9892 2522 E-mail: sales@containeroptions.com.au

More information

Monitoring thermal conditions during transport of racing pigeons on a vehicle equipped with controlled ventilation

Monitoring thermal conditions during transport of racing pigeons on a vehicle equipped with controlled ventilation Monitoring thermal conditions during transport of racing pigeons on a vehicle equipped with controlled ventilation The vehicle A novel vehicle has been designed and constructed to ensure optimal conditions

More information

DETAILED PROCEDURE AND GUIDELINES TEMPERATURE MAPPING STUDY & QUALIFICATION OF COLD ROOMS, WAREHOUSES, VANS, TRUCKS, REEFERS, REFRIGERATORS & BOXES

DETAILED PROCEDURE AND GUIDELINES TEMPERATURE MAPPING STUDY & QUALIFICATION OF COLD ROOMS, WAREHOUSES, VANS, TRUCKS, REEFERS, REFRIGERATORS & BOXES DETAILED PROCEDURE AND GUIDELINES ON TEMPERATURE MAPPING STUDY & QUALIFICATION OF COLD ROOMS, WAREHOUSES, VANS, TRUCKS, REEFERS, REFRIGERATORS & BOXES FOR PHARMACEUTICAL INDUSTRY Revision History: Revision

More information

International Cold Chain Technology

International Cold Chain Technology INTERNATIONAL COLD CHAIN TECHNOLOGY 140 Newmarket Road, Cambridge CB5 8HE Tel: +44 1223 365101 Fax: +44 1223 461522 Email: icct@crtech.co.uk ICCT ICCT guidelines on Cargo Temperature Maintenance CONTENTS

More information

Refrigerated Road Rail Distribution Link Project

Refrigerated Road Rail Distribution Link Project AIRAH Food for Thought Refrigerated Road Rail Distribution Link Project Ray Clarke M.AIRAH Ray Clarke, Director ISECO Consulting Services Pty Ltd Hawthorn Vic Refrigerated Logistics Refrigerated Logistics

More information

A Modified Heat Pump Air-Conditioning System for Electric Vehicle

A Modified Heat Pump Air-Conditioning System for Electric Vehicle A Modified Heat Pump Air-Conditioning System for Electric Vehicle Po-Hsu Lin a and Kuang-Ting Cheng b Automotive Research & Testing Center, No.6, Lugong S. 7 th Rd., Lugang, Changhua county 50544, Taiwan

More information

Available online at ScienceDirect. Transportation Research Procedia 14 (2016 )

Available online at  ScienceDirect. Transportation Research Procedia 14 (2016 ) Available online at www.sciencedirect.com ScienceDirect Transportation Research Procedia 14 (2016 ) 1080 1086 6th Transport Research Arena April 18-21, 2016 New heating system development working with

More information

CAC/RCP 8 Page 1 of 19 RECOMMENDED INTERNATIONAL CODE OF PRACTICE FOR THE PROCESSING AND HANDLING OF QUICK FROZEN FOODS CAC/RCP

CAC/RCP 8 Page 1 of 19 RECOMMENDED INTERNATIONAL CODE OF PRACTICE FOR THE PROCESSING AND HANDLING OF QUICK FROZEN FOODS CAC/RCP CAC/RCP 8 Page 1 of 19 RECOMMENDED INTERNATIONAL CODE OF PRACTICE FOR THE PROCESSING AND HANDLING OF QUICK FROZEN FOODS CAC/RCP 8-1976 CAC/RCP 8 Page 2 of 19 TABLE OF CONTENTS PAGE INTRODUCTION... 3 CODES

More information

FACT SHEET 6 Transport Refrigeration

FACT SHEET 6 Transport Refrigeration FACT SHEET 6 Transport Refrigeration UNEP Ozone Secretariat Workshop on HFC management: technical issues UNEP Ozone Secretariat Background Material for HFC Workshop, 2015 Bangkok, 20 and 21 April 2015

More information

Relevant parameters on the energy efficiency of closed refrigerated multideck display cases

Relevant parameters on the energy efficiency of closed refrigerated multideck display cases nd This paper is part of the Proceedings of the 2 International Conference on Energy Production and Management (EQ 2016) www.witconferences.com Relevant parameters on the energy efficiency of closed refrigerated

More information

A STUDY OF WALL SURFACE TEMPERATURE VARIATIONS FOR HOUSING IN MODERATE CLIMATES

A STUDY OF WALL SURFACE TEMPERATURE VARIATIONS FOR HOUSING IN MODERATE CLIMATES Florianópolis Brazil 212 A STUDY OF WALL SURFACE TEMPERATURE VARIATIONS FOR HOUSING IN MODERATE CLIMATES Alterman, Dariusz 1 ; Page, Adrian 2 ; Hands, Stuart 3 ; Moffiet, Trevor 4 ; Moghtaderi, Behdad

More information

CARRIAGE OF INTEGRAL REFRIGERATED CONTAINERS ON BOARD SHIPS

CARRIAGE OF INTEGRAL REFRIGERATED CONTAINERS ON BOARD SHIPS Guide for Carriage of Integral Refrigerated Containers on Board Ships GUIDE FOR CARRIAGE OF INTEGRAL REFRIGERATED CONTAINERS ON BOARD SHIPS MAY 2017 American Bureau of Shipping Incorporated by Act of Legislature

More information

Energy Efficiency in Building Active Design Part II

Energy Efficiency in Building Active Design Part II Energy Efficiency in Building Active Design Part II Presented by: CK Tang BSEEP Component 4 Manager Veritas Enviornment Sdn Bhd ck.tang@veritas.com.my Air Conditioning System System Sizing 1 Current Industry

More information

General Plan OXYGEN SERVICE CONTAINER 2005 Version 1.02

General Plan OXYGEN SERVICE CONTAINER 2005 Version 1.02 - 1 - General Plan OXYGEN SERVICE CONTAINER 2005 Version 1.02 Laser Gas Author: Rauno Hakala Distribution: Printed: Document s state: version 1.02 Edited: 07.12.2003 - 2 - i) Version history Version Date

More information

Chapter 6. Space heating load

Chapter 6. Space heating load Chapter 6 Space heating load 1 Outdoor Design Conditions Heating systems should provide just enough heat to match the heat loss from the structure. Local knowledge should be obtained for design conditions.

More information

8. Appendix F Acoustic Assessment

8. Appendix F Acoustic Assessment 8. Appendix F Acoustic Assessment HFT Ltd 06-Jun-2017 Assessment of Noise Effects Mixed Industrial Development at 28 Inlet Road, Takanini Mixed Industrial Development at 28 Inlet Road, Takanini Client:

More information

REAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS. Galway, Ireland

REAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS. Galway, Ireland REAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS Magdalena Hajdukiewicz 1,2,3, Padraig O Connor 1, Colin O Neill 1, Daniel Coakley 1,2,3, Marcus M. Keane 1,2,3, Eoghan Clifford 1,2,3 1 Department

More information

Thermal comfort study of a hawker center in Singapore

Thermal comfort study of a hawker center in Singapore September 004 Page of 6 Thermal comfort study of a hawker center in Singapore Song Jiafang, Wong Nyuk Hien, Agustinus Djoko Istiadji Department of Building, School of Design and Environment, National University

More information

Proceedings of BS2013: 13th Conference of International Building Performance Simulation Association, Chambéry, France, August 26-28

Proceedings of BS2013: 13th Conference of International Building Performance Simulation Association, Chambéry, France, August 26-28 HVAC CONTROL SIMULATION STUDY FOR AUSTRALIAN OFFICE BUILDINGS Hongsen Zhang and Paul Bannister Exergy Australia Pty Ltd, Canberra, Australia hongsen@xgl.com.au; paul@xgl.com.au ABSTRACT This paper presents

More information

MIR COOLED INCUBATORS

MIR COOLED INCUBATORS MIR COOLED INCUBATORS Model Range: MIR Cooled Incubators PHCbi s Cooled Incubators have been recognised as exceptional units suitable for a wide range of applications. These incubators offer precise, repeatable

More information

Special edition paper Research on Utilizing Air Thermal Energy for Railway Facilities

Special edition paper Research on Utilizing Air Thermal Energy for Railway Facilities Research on Utilizing Air Thermal Energy for Railway Facilities Keisuke Yamaguchi* Setsuo Fuda* Naoyuki Tanita** Masafumi Sato*** To utilize air thermal energy for railway facilities, experiments were

More information

Technical supplement to WHO Technical Report Series, No. 961, 2011

Technical supplement to WHO Technical Report Series, No. 961, 2011 Supplement 11 Qualification of refrigerated road vehicles Technical supplement to WHO Technical Report Series, No. 961, 2011 Annex 9: Model guidance for the storage and transport of time- and temperature-sensitive

More information

Flow Patterns and Thermal Behaviour in a Large Refrigerated Store

Flow Patterns and Thermal Behaviour in a Large Refrigerated Store IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-issn: 2278-1684,p-ISSN: 2320-334X, Volume 13, Issue 2 Ver. III (Mar- Apr. 2016), PP 81-92 www.iosrjournals.org Flow Patterns and Thermal Behaviour

More information

CHAPTER 4 EXPERIMENTATION

CHAPTER 4 EXPERIMENTATION CHAPTER 4 EXPERIMENTATION The performance of the considered alternative refrigerant mixtures is experimentally studied in comparison with R134a and HC mixture (50%R290/50%R600a) in the visi cooler of conventional

More information

Amvic Building System Warehouse Energy Study. Presented to: Gary Brown. File: Dolphin Ave Kelowna, BC V1Y 9S4.

Amvic Building System Warehouse Energy Study. Presented to: Gary Brown. File: Dolphin Ave Kelowna, BC V1Y 9S4. Amvic Building System Warehouse Energy Study Presented to: Gary Brown Amvic Building System File: 112120108 300 1708 Dolphin Ave Kelowna, BC V1Y 9S4 October, 2006 Contact: Shane Lapp, EIT Amvic Building

More information

CLCF Climate Changer for comfort applications. Next generation air handling performance from Trane

CLCF Climate Changer for comfort applications. Next generation air handling performance from Trane CLCF Climate Changer for comfort applications Next generation air handling performance from Trane Customized performance and maximum comfort at minimum cost For many years Trane has been a global leader

More information

guarantee successful solutions. of which 7000 are covered, today Framec Truck is a through a wide range of highly sophisticated

guarantee successful solutions. of which 7000 are covered, today Framec Truck is a through a wide range of highly sophisticated Green AppeAl 2 About us Our mission MISSION of Eutectic System Refrigerated Bodies for the distribution of ice cream and frozen food. The mission of Framec Truck is to make the proximity service of foodstuff

More information

Temperature Prediction Software for Refrigerated Container Cargoes

Temperature Prediction Software for Refrigerated Container Cargoes Temperature Prediction Software for Refrigerated Container Cargoes by J Frith, Member (Cambridge Refrigeration Technology) (Session 2003-2004) Presented before the Institute of Refrigeration at the Institute

More information

Remote Condition Monitoring systems and products

Remote Condition Monitoring systems and products Remote Condition Monitoring systems and products Operational benefits from improved performance Suitable for new and retrofit installations Leading edge technology Networking products together to provide

More information

POST OCCUPANCY DESIGN INERVENTION TO IMPROVE COMFORT AND ENERGY PERFORMANCE IN A DESERT HOUSE

POST OCCUPANCY DESIGN INERVENTION TO IMPROVE COMFORT AND ENERGY PERFORMANCE IN A DESERT HOUSE POST OCCUPANCY DESIGN INERVENTION TO IMPROVE COMFORT AND ENERGY PERFORMANCE IN A DESERT HOUSE Vidar Lerum Arizona State University P O Box 871605, Tempe, AZ, 85287-1605, USA vidar.lerum@asu.edu Venkata

More information

A Case Study of Energy Demand in Housing Units

A Case Study of Energy Demand in Housing Units A Case Study of Energy Demand in Housing Units Contributors: Niket Kumar 1, Former Graduate Student Dr. Sudhir Misra 1, Professor Dr. Naveen Tiwari 2, Associate Professor 1 Department of Civil Engineering,

More information

The BIG Energy Upgrade Energy Innovation for Retrofitting Deprived Community Housing in the UK

The BIG Energy Upgrade Energy Innovation for Retrofitting Deprived Community Housing in the UK The BIG Energy Upgrade Energy Innovation for Retrofitting Deprived Community Housing in the UK Dr. Hasim Altan Lecturer in Sustainable Environmental Design Director of BEAU Research Centre, School of Architecture

More information

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya (vahid.vakiloroaya@engineer.com) ABSTRACT: The overall attainable reduction in energy consumption and enhancement of

More information

Controlled Environments. KS1100 CS Data Sheet. Controlled Environment Panels. Insulated Panels

Controlled Environments. KS1100 CS Data Sheet. Controlled Environment Panels. Insulated Panels Controlled Environments KS1 CS Data Sheet Controlled Environment Panels Insulated Panels KS1 CS Technical Data Product Overview Kingspan Controlled Environment panels are designed for use within temperature

More information

TEST REPORT. B&W International GmbH Junkendiek Ibbenbühren

TEST REPORT. B&W International GmbH Junkendiek Ibbenbühren 1 Cover Sheet TEST REPORT Project-No.: 17-8981 Test Specimen: Shipping Unit - - Client: B&W International GmbH Junkendiek 5 49479 Ibbenbühren Responsible Persons: Waldemar Masur (B&W International GmbH)

More information

Airflow and temperature modelling of sustainable buildings at the design stage can prevent unintended consequences of passive features

Airflow and temperature modelling of sustainable buildings at the design stage can prevent unintended consequences of passive features Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 00 (2017) 000 000 www.elsevier.com/locate/procedia International High- Performance Built Environment Conference A Sustainable

More information

Performance Considerations of the Thermal Envelope Moderator: Mike Adkins, United States Cold Storage

Performance Considerations of the Thermal Envelope Moderator: Mike Adkins, United States Cold Storage Performance Considerations of the Thermal Envelope Moderator: Mike Adkins, United States Cold Storage Panelists: Andy Bowser, Team Group Larry Gilliland, SubZero Constructors Jay Smith, Metl-Span Recommended

More information

In alliance with. Green AppeAl

In alliance with. Green AppeAl In alliance with Green AppeAl About us of Eutectic System Refrigerated Bodies for the distribution of ice cream and frozen food. Founded in 1950, when Franger Group decided to start a new business: the

More information

Thermally operated mobile air-conditioning system

Thermally operated mobile air-conditioning system Thermally operated mobile air-conditioning system Development and test of a laboratory prototype R. de Boer S.F. Smeding Paper to be presented on the International Sorption Heat Pump Conference 2008, Seoul,

More information

Combined heat, moisture and CFD modelling to assess the impact of climate control on local climates near cultural objects in a museum exhibition room

Combined heat, moisture and CFD modelling to assess the impact of climate control on local climates near cultural objects in a museum exhibition room Combined heat, moisture and CFD modelling to assess the impact of climate control on local climates near cultural objects in a museum exhibition room K. Kompatscher *1, S. Kochen 1, A.W.M. van Schijndel

More information

SANDEN. Leading hot water technology

SANDEN. Leading hot water technology SANDEN. Leading hot water technology Why consider an Air-Sourced Hot Water Heat Pump System? An air-sourced heat pump absorbs heat from the air and transfers it to heat water. It consumes minimal electricity,

More information

A COMPARATIVE STUDY OF THE THERMAL PERFORMANCE OF CAVITY AND BRICK VENEER CONSTRUCTION

A COMPARATIVE STUDY OF THE THERMAL PERFORMANCE OF CAVITY AND BRICK VENEER CONSTRUCTION 13 th International Brick and Block Masonry Conference Amsterdam, July 4-7, 2004 A COMPARATIVE STUDY OF THE THERMAL PERFORMANCE OF CAVITY AND BRICK VENEER CONSTRUCTION H.O. Sugo 1, A.W. Page 2, B. Moghtaderi

More information

Trane Water-Source Variable Refrigerant Flow

Trane Water-Source Variable Refrigerant Flow Trane Water-Source Variable Refrigerant Flow Trane Water-Source Variable Refrigerant Flow Energy Efficiency Meets Expertise TRANE IS THE GLOBAL LEADER IN HVAC EQUIPMENT, SYSTEMS, AND SERVICES, PROVIDING

More information

Live Transportation Research and Improvement Initiatives

Live Transportation Research and Improvement Initiatives Live Transportation Research and Improvement Initiatives MLF Transport Working Committee As a major chicken processor in Canada, MLF recognizes the critical need to identify improved live bird transportation

More information

This article will address the test methods used to determine R-values and their relative degree of accuracy.

This article will address the test methods used to determine R-values and their relative degree of accuracy. Insulation R-value, What does it really mean? Every designer knows that the R-value of a material is important in specifying insulation products. Regulations abound that require minimum R-values for wall,

More information

Deakin University gratefully acknowledges permission of the Australian and New Zealand Solar Energy Society to publish these papers

Deakin University gratefully acknowledges permission of the Australian and New Zealand Solar Energy Society to publish these papers Deakin Research Online Deakin University s institutional research repository DDeakin Research Online Research Online This is the published version (version of record) of:, P. and Luther, M. B. 2001, Evaluating

More information

MONITORING THE COOL CHAIN Maximizing Shelf Life for Safer Food

MONITORING THE COOL CHAIN Maximizing Shelf Life for Safer Food MONITORING THE COOL CHAIN Maximizing Shelf Life for Safer Food Dr. Noel P. Greis Director, Center for Logistics and Digital Strategy Co-Driector, UNC-Tsinghua Center for Logistics and Enterprise Development

More information

MOISTURE CONDITIONS IN WALLS AND CEILINGS OF A SIMULATED OLDER HOME DURING WINTER

MOISTURE CONDITIONS IN WALLS AND CEILINGS OF A SIMULATED OLDER HOME DURING WINTER MOISTURE CONDITIONS IN WALLS AND CEILINGS OF A SIMULATED OLDER HOME DURING WINTER USDA FOREST SERVICE RESEARCH PAPER FPL 290 1977 U.S. DEPARTMENT OF AGRICULTURE FOREST SERVICE FOREST PRODUCTS LABORATORY

More information

Rooftops High performance, proven reliability and easy installation

Rooftops High performance, proven reliability and easy installation Rooftops High performance, proven reliability and easy installation 1 Airfinity Rooftops Comfort and economy When it comes to installing and maintaining an HVAC system, every cent counts. From your initial

More information

THE EFFECT OF WINDOW-WALL INTERFACE DETAILS ON WINDOW CONDENSATION POTENTIAL

THE EFFECT OF WINDOW-WALL INTERFACE DETAILS ON WINDOW CONDENSATION POTENTIAL THE EFFECT OF WINDOW-WALL INTERFACE DETAILS ON WINDOW CONDENSATION POTENTIAL W. Maref 1, N. Van Den Bossche 2, M. Armstrong 1, M.A. Lacasse 1, H. Elmahdy 1 and R. Glazer 1 1-National Research Council Canada,

More information

CSIRO Energy Centre Newcastle, New South Wales, Australia

CSIRO Energy Centre Newcastle, New South Wales, Australia CSIRO Energy Centre Newcastle, New South Wales, Australia Trevor Moody BE, BEc Commonwealth Scientific and Industrial Research Organisation (CSIRO), Australia. PO Box 227 Dickson ACT 2602 Australia. Telephone:

More information

Re: Proposed revisions to USP General Chapter <1079> Good Storage and Distribution Practices For Drug Products

Re: Proposed revisions to USP General Chapter <1079> Good Storage and Distribution Practices For Drug Products 30 September 2011 Scientific Liaison (PS05) Packaging and Storage Expert Committee US Pharmacopeia 12601 Twinbrook Pkwy Rockville MD 20852-1790 Re: Proposed revisions to USP General Chapter Good

More information

Understanding Extrusion

Understanding Extrusion Chris Rauwendaal Understanding Extrusion 2nd Edition Sample Chapter 2: Instrumentation and Control ISBNs 978-1-56990-453-4 1-56990-453-7 HANSER Hanser Publishers, Munich Hanser Publications, Cincinnati

More information

Thermal comfort evaluation of natural ventilation mode: case study of a high-rise residential building

Thermal comfort evaluation of natural ventilation mode: case study of a high-rise residential building J. Zuo, L. Daniel, V. Soebarto (eds.), Fifty years later: Revisiting the role of architectural science in design and practice: 50 th International Conference of the Architectural Science Association 2016,

More information

Experimental Performance Analyses of a Heat Recovery System for Mechanical Ventilation in Buildings

Experimental Performance Analyses of a Heat Recovery System for Mechanical Ventilation in Buildings Available online at www.sciencedirect.com ScienceDirect Energy Procedia 82 (2015 ) 465 471 ATI 2015-70th Conference of the ATI Engineering Association Experimental Performance Analyses of a Heat Recovery

More information

Assessment of thermal comfort near a glazed exterior wall

Assessment of thermal comfort near a glazed exterior wall Assessment of thermal comfort near a glazed exterior wall Timothy Anderson 1, Mark Luther 2 and Tim Brain 3 1 School of Engineering, Auckland University of Technology, Auckland 1142, New Zealand 2 School

More information

DIGITAL AND ENVIRONMENTAL SKILLS FOR FACILITIES MANAGEMENT

DIGITAL AND ENVIRONMENTAL SKILLS FOR FACILITIES MANAGEMENT DIGITAL AND ENVIRONMENTAL SKILLS FOR FACILITIES MANAGEMENT O3 A1 Learning unit 2 Energy efficiency and energy management in buildings Project Start Date - October 1st, 2016 Project End Date - March 31,

More information

Proceedings of Clima 2007 WellBeing Indoors

Proceedings of Clima 2007 WellBeing Indoors Experimental Study of Thermal Environment and Comfort in an Office Room with a Variable Air Volume (VAV) System under Low Supply Air Temperature Conditions Mari-Liis Maripuu Chalmers University of Technology,

More information

IMPROVING THE DURABILITY OF FLAT ROOF CONSTRUCTIONS Durability of flat roof construction

IMPROVING THE DURABILITY OF FLAT ROOF CONSTRUCTIONS Durability of flat roof construction IMPROVING THE DURABILITY OF FLAT ROOF CONSTRUCTIONS Durability of flat roof construction C. RUDBECK, S. SVENDSEN Technical University of Denmark, Department of Buildings and Energy, Lyngby, Denmark Durability

More information

MAGNUM PLUS. Container refrigeration. Fresh or frozen: faster is better.

MAGNUM PLUS. Container refrigeration. Fresh or frozen: faster is better. MAGNUM PLUS Container refrigeration. Fresh or frozen: faster is better. Premium performance. No compromise. Premium performance. No compromise. Thermo King is committed to engineering innovative products

More information

ASTM C 1363 Thermal Performance Test Report

ASTM C 1363 Thermal Performance Test Report ASTM C 1363 Thermal Performance Test Report Test Number: 2010-50 Sponsor: Butler Research Center Liner System R-25 + R-11 Membrane liner system, R-25 fiberglass insulation between the purlins, R-11 fiberglass

More information

Compound ejectors with improved off-design performance

Compound ejectors with improved off-design performance Compound ejectors with improved off-design performance Dr M. Dennis 1, Dr K. Garzoli 2 1,2 Centre for Sustainable Energy Systems School of Engineering The Australian National University Canberra, ACT 0200

More information

Modular Coldroom Installation Manual

Modular Coldroom Installation Manual Modular Coldroom Installation Manual May 2005 Disclaimer: The information contained in this installation guide is provided "as is". Bromic Pty Ltd does not warrant the accuracy, adequacy or completeness

More information

CMA CGM CONTAINERS CHOOSING THE RIGHT EQUIPMENT TO SHIP YOUR CARGO

CMA CGM CONTAINERS CHOOSING THE RIGHT EQUIPMENT TO SHIP YOUR CARGO CMA CGM CONTAINERS CHOOSING THE RIGHT EQUIPMENT TO SHIP YOUR CARGO SELECTING A CONTAINER NEEDS CONTAINER TYPE GENERAL PURPOSE CONTAINERS Boxes, cartons, cases, sacks, bales, pallets, drums 7 REEFER CONTAINERS

More information

Attachment 1 Amendment 6 - IS6/IAS6: Section 3.8: Amended New Zealand Standard for Spray Chilling Large Mammals and Large Birds

Attachment 1 Amendment 6 - IS6/IAS6: Section 3.8: Amended New Zealand Standard for Spray Chilling Large Mammals and Large Birds Attachment 1 Amendment 6 - IS6/IAS6: Section 3.8: Amended New Zealand Standard for Spray Chilling Large Mammals and Large Birds February 2008 Contents 1 Scope... 2 2 Background... 2 3 Definitions... 3

More information

FRESH OR FROZEN. FASTER IS BETTER.

FRESH OR FROZEN. FASTER IS BETTER. FRESH OR FROZEN. FASTER IS BETTER. 3 PREMIUM PERFORMANCE. NO COMPROMISE. PREMIUM PERFORMANCE. NO COMPROMISE. Thermo King is committed to engineering innovative products and technologies to provide ever-increasing

More information

GREAT DANE S NEW i-van IS A VERSATILE TRAILER DESIGNED AND ENGINEERED TO OFFER SEMI-INSULATED PROPERTIES IN CONJUNCTION WITH THE STRENGTH AND

GREAT DANE S NEW i-van IS A VERSATILE TRAILER DESIGNED AND ENGINEERED TO OFFER SEMI-INSULATED PROPERTIES IN CONJUNCTION WITH THE STRENGTH AND GREAT DANE S NEW i-van IS A VERSATILE TRAILER DESIGNED AND ENGINEERED TO OFFER SEMI-INSULATED PROPERTIES IN CONJUNCTION WITH THE STRENGTH AND DURABILITY OF THE CLASSIC DRY FREIGHT VAN. i-van REPRESENTS

More information

Thermal Comfort Measurements in a Hybrid Ventilated Office Room

Thermal Comfort Measurements in a Hybrid Ventilated Office Room Eawag 5237 Thermal Comfort Measurements in a Hybrid Ventilated Office Room Thomas Frank 1), Herbert Güttinger 2) and Stefan van Velsen 3) 1 Swiss Federal Laboratories for Materials Testing and Research

More information

EXPERIMENT AND NUMBERICAL ANALYSIS OF THE DISCONTINUOUS OPERATION FOR GROUND HEAT EXCHANGERS

EXPERIMENT AND NUMBERICAL ANALYSIS OF THE DISCONTINUOUS OPERATION FOR GROUND HEAT EXCHANGERS EXPERIMENT AND NUMBERICAL ANALYSIS OF THE DISCONTINUOUS OPERATION FOR GROUND HEAT EXCHANGERS Gao Qing, Li Ming, Jiang Yan, Yu Ming, Qiao Guang Jilin University Changchun,JiLin 130025, China Tel: 86-431-5095897

More information

EXTRA DURABILITY BY DESIGN TO LOWER YOUR LIFECYCLE COST

EXTRA DURABILITY BY DESIGN TO LOWER YOUR LIFECYCLE COST EXTRA DURABILITY BY DESIGN TO LOWER YOUR LIFECYCLE COST With maximized strength-to-weight ratio, Kidron s Emperor G2 trailer introduces a new generation of food service distribution advantages, uniquely

More information

In 2011, Auckland Council commissioned a report to identify how the City could reduce its Carbon emissions. The top 6 recommendations for the built

In 2011, Auckland Council commissioned a report to identify how the City could reduce its Carbon emissions. The top 6 recommendations for the built In 2011, Auckland Council commissioned a report to identify how the City could reduce its Carbon emissions. The top 6 recommendations for the built environment included: compact growth, electric vehicles,

More information

The case for research

The case for research The case for research In recent years there has been growing world-wide concern for energy conservation, the reduction of greenhouse gases and sustainability. In Australia, it is estimated that 39% of

More information

973 Dew Point Mirror. Portable Industrial Chilled Mirror Hygrometer. Typical applications: REFLECTING YOUR STANDARDS

973 Dew Point Mirror. Portable Industrial Chilled Mirror Hygrometer. Typical applications: REFLECTING YOUR STANDARDS Portable Industrial Chilled Mirror Hygrometer Fundamental drift free humidity measurement Integral frost/dew point measuring head Internal sample pump Optimal Response Injection System for fast measurement

More information

Performance Evaluation of an Integrated Hybrid Photovoltaic/Thermal (PV/T) Greenhouse

Performance Evaluation of an Integrated Hybrid Photovoltaic/Thermal (PV/T) Greenhouse 12 EAAS & ARF. All rights reserved Performance Evaluation of an Integrated Hybrid Photovoltaic/Thermal (PV/T) Greenhouse Shahana Parveen 1, Dr. Qamar Parvez Rana 2 Jamia Hamdard, India Shahanaparveen_amu@gmail.com

More information

The benchmark in cold chain. 30+ years experience in cold chain

The benchmark in cold chain. 30+ years experience in cold chain The benchmark in cold chain 30+ years experience in cold chain Why Temperature Controlled Transportation? A drug that has been temperature abused is every bit as dangerous as one that is not authentic

More information

UR-Smart by Unipart Rail

UR-Smart by Unipart Rail UR-Smart by Unipart Rail Remote Condition Monitoring systems and products Operational benefits from improved performance Suitable for new and retrofit installations Leading edge technology Networking products

More information

Temperature Mapping Report

Temperature Mapping Report Document Status: Page: 1 of 13 Temperature Mapping Report Company Name & Site Warehouse Start Date: DD Month YYYY End Date: DD Month YYYY Document Status: Page: 2 of 13 Table of Contents 1 Approvals...

More information

Title: Food Supplier Guideline Issued by: Food & Health Department

Title: Food Supplier Guideline Issued by: Food & Health Department Guideline No.: FH/001 Issue Date: 29/04/2010 Title: Food Supplier Guideline Issued by: Food & Health Department 1.0 INTRODUCTION The key to keeping food safe during transportation is to keep it out of

More information

CARRIAGE OF PERISHABLE FOODSTUFFS

CARRIAGE OF PERISHABLE FOODSTUFFS CARRIAGE OF PERISHABLE FOODSTUFFS Peter PIALA, Andrej DAVID 1 Introduction Perishable foodstuffs are transported for short and long distances in the different climatic conditions. This transport is not

More information

PERFORMANCE OF AN AUXILIARY NATURAL VENTILATION SYSTEM

PERFORMANCE OF AN AUXILIARY NATURAL VENTILATION SYSTEM PERFORMANCE OF AN AUXILIARY NATURAL VENTILATION SYSTEM A.W. Rofail and L.J.Aurelius 1.0 INTRODUCTION A comprehensive wind tunnel study has been carried out by Windtech Consultants Pty Ltd to establish

More information

(904) FAX (904) The Intermodal Hardware Specialists. Therm-Cool

(904) FAX (904) The Intermodal Hardware Specialists. Therm-Cool (904) 696-0010 FAX (904) 696-0019 e-mail sales@buffersusa.com The Intermodal Hardware Specialists BUFFERS USA, INC. 10180 New Berlin Rd. Jacksonville, FL. 32226 Therm-Cool Thermal Insulated Bulkhead Product

More information

Study of the Electric Vehicle Heat Pump Air-conditioning System

Study of the Electric Vehicle Heat Pump Air-conditioning System AVEC 1 Study of the Electric Vehicle Heat Pump Air-conditioning System Po-Hsu Lin, Automotive esearch & Testing Center No.6, Lugong S. 7th d., Lukang, Changhua County, 50544, Taiwan(.O.C) Phone: 886-4-7811

More information

Design Evolution for HVAC Systems

Design Evolution for HVAC Systems Design Evolution for HVAC Systems What We Know Ductless Heat Pumps Reliable Efficient Having my DHP installed was as easy as falling off a log! Energy saving Can be aesthetically pleasing Give homeowners

More information

Clean Cool Energy. Harnessing the power of liquid nitrogen for zero emission power and cooling.

Clean Cool Energy. Harnessing the power of liquid nitrogen for zero emission power and cooling. Clean Cool Energy Harnessing the power of liquid nitrogen for zero emission power and cooling Dearman s vision is to deliver clean, sustainable cold and power to help address global challenges of climate

More information

Window Labelling Program for India

Window Labelling Program for India Window Labelling Program for India Stakeholder consultation meeting : October 13, 2012, New Delhi Centre for Advanced Research in Building Science and Energy, CEPT University, Ahmedabad INDIA Rajan Rawal,

More information

Monitoring climate in the storage of pharmaceutical goods with testo 175.

Monitoring climate in the storage of pharmaceutical goods with testo 175. Testo Solution Application example Monitoring climate in the storage of pharmaceutical goods with testo 175. Pharmaceutical goods whether APIs or end products must be stored at defined and constant ambient

More information

Code of Hygienic Practice for Processing and Handling of Quick Frozen Foods

Code of Hygienic Practice for Processing and Handling of Quick Frozen Foods 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 Table of Contents 1 Scope and objective... 2 2 Terms and definitions... 3 3 Prerequisite Program... 4 3.1 Establishment:

More information

Module 3 Slabbing, Skimming, Dry Lining and Floors UNIT: 2 Skimming to Plasterboard

Module 3 Slabbing, Skimming, Dry Lining and Floors UNIT: 2 Skimming to Plasterboard TRADE OF PLASTERING PHASE 2 Module 3 Slabbing, Skimming, Dry Lining and Floors UNIT: 2 Produced by In cooperation with subject matter expert: Terry Egan Some images & text courtesy of Gypsum Industries

More information

Design and retrofitting of a hybrid building in Athens

Design and retrofitting of a hybrid building in Athens International Conference Passive and Low Energy Cooling 597 Design and retrofitting of a hybrid building in Athens A. Gavalas Gavalas Architects, Athens ABSTRACT This paper s aim is to present a building

More information

FACT SHEET. Thermally Efficient Design with Precast. making precast easy

FACT SHEET. Thermally Efficient Design with Precast. making precast easy Thermally Efficient Design with Precast What is thermal efficiency? Thermal efficiency is part of energy efficiency and energy efficiency is one part of sustainability. Sustainability includes not only

More information

Smart Integration of Thermal Management Systems for Electronics Cooling

Smart Integration of Thermal Management Systems for Electronics Cooling Smart Integration of Thermal Management Systems for Electronics Cooling Dr. Ir. Wessel W. Wits, University of Twente, Faculty of Engineering Technology, Laboratory of Design, Production and Management,

More information

ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS

ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS ANSI/ASHRAE STANDARD 200-2015, METHODS OF TESTING CHILLED BEAMS NEMIC 2017 Agenda 1. Foreword 2. Purpose & Scope 3. Definitions 4. Instrumentation & Facilities 5. Test Methods 6. Reporting 7. Normative

More information

Cold Rooms Kide

Cold Rooms Kide COLD ROOMS Cold Rooms 2 Cold under control KIDE it is a business Group manufacturer of cold-rooms, insulation panels, insulated doors, refrigeration units and drying units, offering integral solutions

More information

St Loyes Extra Care Facility PHPP Pre-Assessment Report

St Loyes Extra Care Facility PHPP Pre-Assessment Report St Loyes Extra Care Facility PHPP Pre-Assessment Report Gale & Snowden Architects & Engineers July 2011 Gale & Snowden Architects St Loyes Extra Care Facility PHPP Pre-Assessment Report Page 2 of 10 St

More information

TR Test Report Verification Testing RKN e1 Container (+5 C) Worst Case Load Version: 01 Page: 2 (26)

TR Test Report Verification Testing RKN e1 Container (+5 C) Worst Case Load Version: 01 Page: 2 (26) TR120013-01 Test Report Verification Testing RKN e1 Container (+5 C) Worst Case Load Version: 01 Page: 2 (26) Document History Version Date of issue Revision(s) Issued by 01 20FEB2012 N/A (First version

More information

Report on thermal cooling system implementation and performance

Report on thermal cooling system implementation and performance SUSTAINABLE ENERGY SYSTEMS Report on thermal cooling system implementation and performance Organisation name of lead contractor for this deliverable: ATC POLYCITY DD 2C.1 TREN/05FP6EN/S07.43964/513481

More information

Handling Units. Air. D-AHU Professional AIR FLOW RATE 1, ,000m 3 /h DAME

Handling Units. Air. D-AHU Professional AIR FLOW RATE 1, ,000m 3 /h DAME Air Handling Units The present leaflet is drawn up by way of information only and does not constitute an offer binding upon Daikin. Daikin has compiled the content of this leaflet to the best of its knowledge.

More information

Kingspan Day-Lite Kapture Data Sheet

Kingspan Day-Lite Kapture Data Sheet Light + Air UK & Republic of Ireland Kingspan Day-Lite Data Sheet KS700DLK, KS1400DLK, KS0DLK 2 Kingspan Day-Lite KS700DLK, KS1400DLK, KS0DLK Application KS700DLK, KS1400DLK, KS0DLK & KS2750DLK rooflights

More information

Green Data Center CRYOGEL Ice Ball Thermal Storage

Green Data Center CRYOGEL Ice Ball Thermal Storage Green Data Center CRYOGEL Ice Ball Thermal Storage Victor J. Ott, P.E. CRYOGEL, San Diego, CA Tuesday, March 1, 2011 4:30 5:30 PM, ACC, Room 207B Copyright Cryogel 2001 Telephone (858) 457-1837 Email:

More information