Available online at ScienceDirect. Energy Procedia 101 (2016 )
|
|
- Maurice Barton
- 6 years ago
- Views:
Transcription
1 Available online at ScienceDirect Energy Procedia 101 (2016 ) st Conference of the Italian Thermal Machines Engineering Association, ATI2016, September 2016, Turin, Italy Analysis of the coupling between CHP and EHP in an office building applied to the Italian energy market Sandro Magnani a *, Piero Danti a, Lorenzo Pezzola a a Yanmar R&D Europe, Viale Galileo 3/A, Florence 50125, Italy Abstract The increasing need for energy and cost efficient solutions for thermal and electric supply is giving new life to CHP plants, even for small power sizes. It is renowned that the optimal application of a CHP plant is to satisfy as much as possible both the electricity and the thermal requirements of the loads, but the frequent applicative context, especially for residential and/or tertiary buildings, is unbalanced towards the thermal needs, so that the sizing of the CHP is determined by the electric loads, at least in the Italian tariff structure context, with the consequence that the generator is relatively small and, consequently, the installation costs represent a consistent part of the capital investment. The increasing level of the performance of the electric heat pump can sensitively minimize the former issue: the combination between a CHP and an EHP can led to a larger size of the co-generative unit, whose exceeding power output can feed the heat pump so that to efficiently satisfy most of the thermal loads of the plant. In this paper an application case referred to an office building is presented: the optimal size of the system will be discussed, and the economic results (in terms of PBT and NPV) of the management of the plant compared with other commonly exploited solutions: Conventional supply, with the heat produced by a gas boiler, the cooling from an electric chiller, and the electricity purchased by the grid; Optimal sizing of the CCHP based on the heating loads duration curve, with the engine operated in thermal-led; Optimal sizing of the CCHP based on the electric loads duration curve, with the engine operated in power-led. The environment performance will be discussed as well, focusing on the comparison between the different solutions in terms of equivalent CO 2 emissions and primary energy consumptions The The Authors. Authors. Published Published by by Elsevier Elsevier Ltd. Ltd. This is an open access article under the CC BY-NC-ND license ( Peer-review under responsibility of the Scientific Committee of ATI Peer-review under responsibility of the Scientific Committee of ATI Keywords: CHP; cogeneration; EHP; design optimization; energy efficiency; CO 2 reduction * Corresponding author. Tel.: /5; fax: ;. address: sandro_magnani@yanmar.com The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license ( Peer-review under responsibility of the Scientific Committee of ATI doi: /j.egypro
2 Sandro Magnani et al. / Energy Procedia 101 ( 2016 ) Introduction In recent times, the level of the CO 2 concentration in the atmosphere has increased to a level that may determine remarkable changes in the climate. If no modifications to energy use and production will happen in the next future, this trend is going to become more and more detrimental for human activities: with this focus in mind, the developed and growing Countries are taking measures to minimize the carbon footprint of their activities (e.g. the European policy of the target [1] or the recent results of 2015 Paris Cop21 conference [2]), with interventions spacing in all energy-related fields. Particular attention is payed to the decrease of the energy consumption in buildings, coupled with the increase in the efficiency of their energy supply pieces of equipment: as reported in [3] they are one of the largest voices in the energy consumption in Europe, representing about 27% of the total final use. One of the options to minimize building carbon footprint stands in the adoption of efficient technologies for room conditioning: the spread of micro-combined Heat and Power (CHP) systems (also suggested by the COGEN Europe Response document [4]) and the improvement of the performance of Electric Heat Pumps (EHPs), whose diffusion is remarkably increased in the last years, can give promising results if widely adopted. The correct integration of these two types of devices can enhance the respective benefits, leading to a decrease in the environmental footprint of the households consumptions and in the reduction of the O&M costs of the buildings energy supply systems. In the following, an example of the integration between μ-chp and EHP systems will be analyzed: in paragraph 2 the details of the energy consumptions of the considered case study will be described, as well as the economic conditions applied to the Italian energy market. The results of the performance of the hypothesized configurations, in economic (Pay-Back Time PBT and Net Present Value NPV) and environmental (CO 2 emissions and primary energy consumptions) terms will be presented in part 4, with the main conclusions summarized in paragraph 5. Nomenclature CAR Cogenerazione ad Alto Rendimento CCHP Combined Cooling, Heating and Power CHP Combined Heating and Power COP Coefficient Of Performance EER Energy Efficiency Ratio EHP Electric Heat Pump ELF Electric Load Following ICE Internal Combustion Engine NPV Net Present Value PBT Pay-Back Time PES Primary Energy Saving TEE Titoli di Efficienza Energetica TLF Thermal Load Following 2. Problem definition 2.1. Definition of the case study For the present analysis, an office building is considered as the case study. The load profiles for this context are retrieved by Macchi et. al in [5], giving indications on the energy consumptions during two example days, one for the winter period and the other one for the summer time. The considered data are shown in Fig. 1. The reference day load profiles are furtherly elaborated on both monthly and daily basis to consider the differences in the energy use, especially on heating and cooling, when the environmental conditions are modified and the building has a different use during holiday periods. To assess the typical consumptions during the months of the year, the profiles are shifted on the basis of the monthly energy ratios shown in Table 1, derived from [5]. About holidays, an estimation of working days, pre-holidays, and holidays is carried out for each month, allowing to consider the different consumptions in contexts like offices, where holidays demand is very low, if null. The details of this division are reported in Table 2.
3 560 Sandro Magnani et al. / Energy Procedia 101 ( 2016 ) a b Fig. 1. Office building load profiles for the example winter day (a) and summer day (b). Table 1. Energy use correction coefficients for each month of the year. Load Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec Electricity Heating Cooling Table 2. Days type for each month of the year. Day type Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec TOT Working Pre-holiday Holiday The loads for working days are estimated as the same as winter and summer days with the monthly correction factor. Pre-holidays are considered equal as the working days for the first half of the day, while for the second half a base electric load is considered (i.e. the night consumption); in summer the air conditioning system is considered switched off (i.e. the cooling load is null), while the room heating in winter is assumed to be half of the average night demand. For holidays the electric load is assumed to be as the second half of pre-holidays, the cooling loads in summer are always considered null, and the heating demand is considered as the second half of pre-holidays. The summary of the energy consumptions of the considered case study are summarized in Table 3. Table 3. Case study characteristics. Parameter Unit of measurement Value Building volume m 3 6,000 Electricity peak (year) kw e 37.8 Heating peak (winter) kw th 78.0 Cooling peak (summer) kw c 61.8 Yearly electricity request kwh e 137,954 Yearly heating request kwh th 150,447 Yearly cooling request kwh c 35,527 In the analysis, the energy loads are supposed to be satisfied by 4 different plant configurations: BASE: the heating loads are satisfied by a natural gas condensing boiler, while the cooling request is matched by an electric chiller; the power grid connection supplies all the electricity needs; CCHP-TLF: the plant is equipped with a micro-chp system coupled with an absorption chiller, operated with a thermal-led logic (Thermal Load Following, TLF), i.e. trying to satisfy the heating request during winter time and the cooling needs in summer; the mismatching between the output from
4 Sandro Magnani et al. / Energy Procedia 101 ( 2016 ) the tri-generation system and the energy request is satisfied by a natural gas condensing boiler, an electric compression chiller and the external power grid for heating, cooling and electricity respectively; CCHP-ELF: again, a micro-chp coupled with an absorption chiller is considered, with the management logic aiming to satisfy as much as possible the electric requests (Electric Load Following, ELF); the fulfillment of thermal loads is ensured by back-up systems, i.e. a natural gas condensing boiler and an electric compression chiller; additional electric requests are satisfied by the external power grid; CCHP+EHP: a tri-generation system is coupled with an electric heat pump, this latter one providing to close the thermal balance of the plant; the CCHP management considers two different aspects, maximizing the efficiency of the tri-generation system and avoiding the sale of the exceeding electricity to the grid because of the poor remuneration; the CCHP is thus operated in TLF until the electric balance with the grid reach the null value: if the thermal request is not satisfied, the EHP is enabled, with an increase in the electric demand of the building, balanced by an increase of the output of the CCHP, with a larger thermal output; the procedure iteratively considers the two aspects until a perfect balance between the electric and thermal request is reached (see the flow chart in Fig. 2). Fig. 2. CCHP operation strategy for CCHP+EHP configuration. The size of the back-up systems, i.e. of the gas boiler, of the electric chiller, and of the heat pump, is determined by the peak request of the loads and is established once for all the different plant scenarios. The size of the tri-generation system is different for each configuration. For the standards operation strategy for the CCHP system (i.e. TLF and ELF) the method of the maximum rectangle area of the cumulative load curve is considered: all the yearly loads are ordinated from the maximum to the minimum value, and their correspondent time duration is also plotted, determining the loads duration curve; the ideal size of the engine is defined by the power reference of the vertex lying on the curve determining the subscribed rectangle with the largest area possible. By doing so, the number of operating hours of the system at rated power (at the maximum efficiency) is maximized, and a consistent part of the loads with smaller power values can also be covered, as shown in Fig. 3 (a) for the CCHP-TLF case and in Fig. 3 (b) for the CCHP-ELF case. Two different loads are considered for the CCHP-TLF and CCHP-ELF sizing method: the generator power output for the former one is determined by considering the thermal loads, i.e. the heating loads in winter period and the equivalent heating loads for the summer time, by multiplying the cooling loads for a fixed conversion coefficient representing the average conversion efficiency of the absorption chiller; similarly, for the CCHP-ELF case the loads considered are the electric ones. As a consequence, in CCHP-TLF case, the estimated ideal size of the PM results in 15.3 kw th : by the analysis of Yanmar micro-chp catalogue, the closest option is the CP10WE1 model, with a rated electric output of 10 kw e, corresponding to 16.2 kw th. When considering CCHP-ELF configuration, the theoretical best size of the cogeneration system results 31.8 kw e : the Yanmar product with the closest output is the CP35VC model, with a rated power output of 35 kw e and a heat recovery of 52.2 kw th. Both systems are based on a gas-fed Internal Combustion Engine (ICE), with an inverter and capable of a maximum output temperature of 85 C, compliant with the energy characteristics requested by the office building. No general rule exists for the definition of the ideal size of the CHP for the CCHP+EHP configuration. The power output of the tri-generation system is so determined by a simplified consideration by the authors: the sum of the rated thermal output and the conversion of half of the rated power of the ICE (needed for feeding the electric heat pump) shall be as closest as possible to the
5 562 Sandro Magnani et al. / Energy Procedia 101 ( 2016 ) heating peak load. As a consequence the selected option is the Yanmar CP25WE, with a rated electric output of 25.1 kw e and a maximum heat recovery capacity of 38.4 kw th. The size of the generators and their characteristics are reported in Table 4 and Table 5, respectively. a b Fig. 3. (a) equivalent heating loads duration curve for CCHP-TLF sizing; (b) electric loads duration curve for CCHP-ELF sizing. Table 4. Equipment size for the considered configurations. Equipment BASE CCHP - TLF CCHP - ELF CCHP + EHP CHP [kw e] N.A Absorption chiller [kw c] N.A Gas boiler [kw th] N.A. Electric chiller [kw c] N.A. EHP [kw th]/[kw c] N.A. N.A. N.A. 80/70 Table 5. Equipment performance. Equipment Rated output [kw] Min output [kw] Rated efficiency CP10WE1 electric % CP10WE1 heating % CP25WE electric % CP25WE heating % CP35VD electric % CP35VD heating % Gas boiler % Electric chiller (EER) EHP heating (COP) EHP cooling (EER) Absorption chiller (EER) The size of the absorption chiller is determined by considering the rated thermal output of the Yanmar CHPs and multiplying this value for a fixed reference conversion factor for the chiller, estimated in 0.7. The lower output of the Yanmar micro-chp systems is also considered: if the power request is under the technical limit, the system is not run, and the back-up generators (or the power grid) satisfy the requests. The partial load performance of all the generators are considered as well: for Yanmar products, the global efficiency is constant in all the operating range, with the electric efficiency slightly decreasing in favor of the thermal efficiency, like in [6]. The gas boiler is considered with a constant efficiency, due to the negligible loss of efficiency at partial loads; the EHP and chiller partial load behavior is supposed to be as in [7], while for the absorption chiller data in [8] is considered; for sake of simplicity, no dependency of the performance on the external temperature is considered.
6 Sandro Magnani et al. / Energy Procedia 101 ( 2016 ) Definition of the energy market context The economic analysis results are strongly affected by the energy market context. In this particular case, the Italian scenario is selected as the reference one. The purchase of the electricity from the grid is characterized by three different markets: the so called Mercato di maggior tutela, whose tariffs are defined and updated by the Italian Authority for Electricity, Natural Gas and Hydric System (AEEGSI, Autorità per l Energia Elettrica, il Gas ed il Sistema Idrico), the Mercato libero, whose tariffs are directly negotiated with the electric companies on the basis of different contracts (the only possible for large customers and optional for small and medium consumer), and the Mercato di salvaguardia, to which each customer not belonging to the others refer to. In this case, the most common one is selected, the Mercato di maggior tutela, with different electricity prices on the basis of the time of the day and of the day of the week. Three segments are individuated: F1 from Monday to Friday from 8 AM to 7 PM; F2 from Monday to Friday from 7 AM to 8 AM and from 7 PM to 11 PM, and on Saturdays from 7 AM to 11 PM; F3 from Monday to Friday from midnight to 7 AM and from 11 PM to midnight, and on all Sundays. In addition to consumptions variable costs, fixed costs are also due, comprehensive of the connection charge (based on the maximum power supply), of the system operation charges and of taxes: these latter contributions represent between 50% and 70% of the total electric bill. Also the natural gas market can be divided into 3 types, but in this case the prices are flat during all the day and week. Again, other charges are due, with the pure energy component being from 40% to 60% of the total amount. For the presented case study, subsidies for CHP are also due to be considered, defined as Cogenerazione ad Alto Rendimento (CAR, high efficiency cogeneration) and whose reference is in [9]: Italian laws allow a reduction on taxes for natural gas if the operation of co-generator achieves two different thresholds: the global efficiency of the systems, that for micro-chps (< 50 kw e ) shall be larger than 75%, and the Primary Energy Saving (PES), that shall be at least 0 (an advantage in terms of primary energy use is achieved compared to the separated production). If both parameters are satisfied, a reduction of the natural gas price of about 33% is experienced. In addition, CHPs also benefit of the Titoli di Efficienza Energetica TEE (energy efficiency certifications): the system is assigned of 1 TEE when 1 MWh of primary energy is saved by the system. At present their value is about 100, but their future is not clear and their contribution is so neglected. 4. Results and discussion In addition to the energy market considerations in paragraph 2, for the economic and environmental estimation the considered additional parameters are summarized in Table 6. From the energy side, in winter period the cogeneration system can cover almost completely the energy needs in case of CCHP-ELF configuration (also wasting part of the recovered heat), while the percentage are reduced to about 44% of the electric needs and to a percentage variable from 55% to more than 70% of the heating demand for the CCHP-TLF and CCHP+EHP scenarios. A similar behavior is also experienced during the summer period, when CP25WE and CP35VD are installed, while the CP10WE1 shows a remarkable reduction in the total energy supply, covering about 1/4 of the electric load and 1/3 of the cooling one, due to the small rated output. All the details are shown in Table 7, with an estimation of both the equivalent and effective operating hours of the CHPs in the year. In terms of economic results, the configuration CCHP+EHP shows the better performance during most of the year, except than in mid-season months, when the CCHP-TLF is preferable. This may be attributable to the lower thermal request characterizing the mentioned periods: for supplying the loads the CP25WE shall operate in partial load conditions with a limited electric efficiency, while the CP10WE1 is close to the rated output, with a lower gas need and a larger electric production, with two beneficial effects: a saving both in natural gas and electricity from the grid. The details of the economic results for each month are shown in Table 8 for all the plant configurations. The CCHP-ELF is preferable than the CCHP-TLF during the periods with a larger thermal request: the possibility to supply much of the thermal load and to minimize the purchase from the grid determine this result, even if in some cases part of the heat is wasted and the natural gas cost can no longer benefit of the fiscal discount. In all the other periods the strategy for the CP35VD is not convenient compared to the other CCHP solutions, because the higher natural gas price due to the heat waste (causing the non-achievement of the efficiency and PES thresholds for the fiscal benefit) is not balanced by the larger electric production.
7 564 Sandro Magnani et al. / Energy Procedia 101 ( 2016 ) Table 6. Economic and environmental calculation parameters. \ Value Parameter Value Electricity price F1 [ /kwh e] EHP reference cost [ /kw c] 450 Electricity price F2 [ /kwh e] Gas boiler reference cost [ /kw th] 150 Electricity price F3 [ /kwh e] Electric chiller reference cost [ /kw c] 300 Electricity selling price [ /kwh e] 0.03 CHP maintenance cost [ /h ON] (absorption chiller included) 0.30 (CP10WE1) 0.40 (CP25WE) 0.50 (CP35VD) Natural gas price [ /Sm 3 ] 0.78 EHP maintenance cost [ /h] 0.10 Italian power grid reference efficiency [%] 46 Gas boiler maintenance cost [ /h] 0.07 Natural gas CO2 emission factor [kg/sm 3 ] Electric chiller maintenance cost [ /h] 0.07 Italian grid CO2 emission factor [ /kwh e] Installation cost [ ] 7,000 (3,000 for BASE) CHP reference cost [ /kw e] 1,500 Rate of interest [%] 3.0 Absorption chiller reference cost [ /kw c] 700 Inflation rate [%] 1.0 Table 7. Yearly energy performance of the considered plant configurations. Plant layout Winter Summer E el CHP E th CHP E el backup h eq CHP h CHP E el CHP E th CHP E el backup h eq CHP h CHP CCHP-ELF 98.3 % % n.a. 3,310 5, % % 5.5 % 1,519 1,864 CCHP-TLF 44.7 % 55.9 % n.a. 5,266 5, % 39.2 % 23.6 % 1,631 1,788 CCHP+EHP 43.2 % 72.4 % 9.9 % 2,338 3, % 70.2 % 7.5 % 1,293 1,446 Table 8. Monthly and yearly economic performance of the considered plant configurations (all values in ). Plant layout Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec TOT BASE 3,895 4,117 3,734 3,393 3,093 3,194 3,865 1,768 3,094 3,489 3,763 4,262 41,667 CCHP-ELF 2,905 3,131 3,287 3,193 2,964 2,305 2,708 1,215 2,939 3,192 3,077 3,177 34,091 CCHP-TLF 3,235 3,421 3,009 2,805 2,569 3,193 3,538 1,708 2,918 2,797 3,042 3,558 35,795 CCHP+EHP 2,252 2,581 3,163 3,012 2,814 2,275 2,314 1,115 2,465 2,999 2,732 2,616 30,339 The NPV for all the hypothesized configurations, considering as reference the configuration BASE, is shown in Fig. 4. Due to the uncertainty on the future perspective of the presence and value of the TEE, their contribution is neglected in the yearly evaluations. By the analysis of the results, an evaluation of the more suitable installation based on the PBT only would bring to misleading results, because both solutions CCHP+EHP and CCHP-TLF present the return of the investment in the same period (about 5 years), but remarkably higher investment costs. The larger economic saving of the previous one compared to the other brings to a larger advantage during the rest of the life span of the tri-generation system, estimated in 15 years. On the other side, the CCHP-ELF solution would determine a longer PBT, with the NPV value becoming positive after about 11 years, a time period too large for the suitability of the investment. The analysis of the environmental footprint, in terms of equivalent CO 2 emissions and primary energy consumption, of the proposed plant layouts partially confirms the economic results, as shown in Fig. 5. The cleanest solution is the CCHP+EHP with the CCHP-TLF ranked as second, with a decrease of 10% and 9.7% in CO 2 and primary energy respectively for the former one (more than 9 t of CO 2 and 45 MWh per year), while the advantage for the other is respectively 6.5% and 6.2% (a decrease of about 6 t of CO 2 and 28 MWh). The CCHP-ELF presents the worst emissions and the largest primary energy consumption of the analyzed layouts, also worse than the BASE solution. This behavior may be attributable to the large amount of wasted heat, due to the CCHP management logic, giving advantages from the economic but not from the environmental point of view.
8 Sandro Magnani et al. / Energy Procedia 101 ( 2016 ) Fig. 4. NPV results for the considered plant configurations. a b Fig. 5. (a) yearly CO 2 emission results; (b) yearly primary energy consumptions. 5. Conclusions The reduction of energy consumptions and the increase of efficiency in buildings are the focus of the next future for developed and growing Countries: the use of micro-chp and EHP systems can help to achieve these targets. Considering an office building as the case study in the Italian energy market scenario, 4 different solutions for supplying the energy request are analyzed: the conventional layout with the heat supplied by a gas boiler, the cooling by an electric chiller and the power from the external distribution grid; three different micro-cchp based solutions, the first one with the CCHP sized on thermal demand and managed with a thermal-led strategy, the second one with the CCHP sized on the electric loads and with the engine managed in power-led, and the combination of a CCHP with and EHP, managed so that to avoid the selling of electricity from the ICE to the grid. This last configuration shows the most promising results, in terms of both economic merit and environmental performance, with a decrease in the O&M costs of more than 25%, and an increase in the environmental performance (CO 2 emissions and energy consumptions) of about 10%. These results are mainly determined by the sizing of the CCHP, implying an integrated design between the two elements, and by the operation strategy of the engine, which does not allow the waste of the heat and avoids the power selling to the distribution grid, due to the low remuneration from the entity in charge of purchasing the exceeds of the distributed local electric generators. References [1] [2] [3] [4] [5] Macchi E, Campanari S, Silva P. La microcogenerazione a gas naturale. Polipress; In Italian [6] [7] In S, Cho K, Lim B, Lee C. Partial load performance test of residential heat pump system with low-gwp refrigerants. Applied Thermal Engineering 2015; pp , vol.85. [8] [9] In Italian.
Energy Audit Summary Report. Manufacture of cosmetics
Energy Audit Summary Report Audit No. 22 - FR03 Manufacture of cosmetics energyxperts.net Berlin (Germany) / Barcelona (Spain) December 2011 With the collaboration of the Chamber of Commerce and Industry
More informationAvailable online at ScienceDirect. Energy Procedia 78 (2015 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (215 ) 1859 1864 6th International Building Physics Conference, IBPC 215 An evaluation of distributed solar thermal "net metering"
More informationStrategies for energy efficiency improvement in residential and office buildings: their role at building and country scale
The Future Role of Energy Storage in South Eastern Europe Enlargement and Integration Action Workshop Strategies for energy efficiency improvement in residential and office buildings: their role at building
More informationEvaluation of Solar PV and Wind Alternatives for Self Renewable Energy Supply: Case Study of Shrimp Cultivation
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 88 (2016 ) 462 469 CUE2015-Applied Energy Symposium and Summit 2015: Low carbon cities and urban energy systems Evaluation of Solar
More informationPOTENTIAL FOR THE ENERGY EFFICIENCY ADVANCEMENT IN DISTRICT HEATING AND COOLING PLANT BY RENOVATION
Eleventh International IBPSA Conference Glasgow, Scotland July 27-30, 2009 POTENTIAL FOR THE ENERGY EFFICIENCY ADVANCEMENT IN DISTRICT HEATING AND COOLING PLANT BY RENOVATION Yoshiyuki Shimoda, Yoshitaka
More informationAvailable online at ScienceDirect. Energy Procedia 78 (2015 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 2663 2668 6th International Building Physics Conference, IBPC 2015 The daylighting contribution in the electric lighting
More informationA CHCP System Constituted by Microturbine and Exhaust Absorption Chiller
A CHCP System Constituted by Microturbine and Exhaust Absorption Chiller G. Caruso, L. De Santoli, F. Giamminuti, P. Sodani University of Rome "La Sapienza" - SAE Servizio di Ateneo per l Energia P.le
More informationCHP Case Studies. Midwest CHP Application Center (MAC) .org (312) University of Illinois at Chicago Energy Resources Center UIC
CHP Case Studies Midwest CHP Application Center (MAC) www.chpcentermw.org.org (312)413-5448 University of Illinois at Chicago Energy Resources Center CHP Case Studies Elgin Community College Presbyterian
More informationScienceDirect. Simulation based mixed mode building design
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 00 (2016) 000 000 www.elsevier.com/locate/procedia 5th International Conference on Advances in Energy Research, ICAER 2015, 15-17
More informationAvailable online at ScienceDirect. Energy Procedia 78 (2015 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 1147 1152 6th International Building Physics Conference, IBPC 2015 Design of borehole heat exchangers for ground source
More informationOptimum sizing of residential cogeneration for prefeasibility estimations. An analytical approach
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (2015 ) 993 998 The 7 th International Conference on Applied Energy ICAE2015 Optimum sizing of residential cogeneration for prefeasibility
More informationEvaluation of Distributed Generation Technologies in Luxury Hotels Marco Gambini, Michela Vellini
Evaluation of Distributed Generation Technologies in Luxury Hotels Marco Gambini, Michela Vellini Abstract The paper aims to examine the capabilities of the application of distributed generation technologies
More informationCogeneration in a Hospital: a case Study
Cogeneration in a Hospital: a case Study C. J. Renedo, A. Ortiz, D. Silió, M. Mañana, S. Pérez and J. Carcedo Department of Electric and Energy Engineering ESTI Industriales y Telecomunicación, University
More informationAvailable online at ScienceDirect. Energy Procedia 81 (2015 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 81 (215 ) 17 69th Conference of the Italian Thermal Engineering Association, ATI 214 Climate influence on seasonal performances of
More informationElectric Forward Market Report
Mar-01 Mar-02 Jun-02 Sep-02 Dec-02 Mar-03 Jun-03 Sep-03 Dec-03 Mar-04 Jun-04 Sep-04 Dec-04 Mar-05 May-05 Aug-05 Nov-05 Feb-06 Jun-06 Sep-06 Dec-06 Mar-07 Jun-07 Sep-07 Dec-07 Apr-08 Jun-08 Sep-08 Dec-08
More informationEnergy and environmental evaluation of combined cooling heating and power system
Energy and environmental evaluation of combined cooling heating and power system Andrzej Bugaj 1,* 1 Wroclaw University of Science and Technology, Faculty of Environmental Engineering, ul. Norwida 4/6,
More informationAvailable online at ScienceDirect. Energy Procedia 78 (2015 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 1513 1518 6th International Building Physics Conference, IBPC 2015 Assessment of natural ventilation within buildings
More informationOptimal Unit Sizing of Biogas-Fuelled Micro Gas Turbine Cogeneration Systems in a Sewage Treatment Plant
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (2015 ) 1052 1058 The 7 th International Conference on Applied Energy ICAE2015 Optimal Unit Sizing of Biogas-Fuelled Micro Gas
More informationAvailable online at ScienceDirect. Energy Procedia 70 (2015 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 70 (2015 ) 480 485 International Conference on Solar Heating and Cooling for Buildings and Industry, SHC 2014 Novel approach for
More informationDimensioning a small-sized PTC solar field for heating and cooling of a hotel in Almería (Spain)
Available online at www.sciencedirect.com Energy Procedia 30 (2012 ) 967 973 SHC 2012 Dimensioning a small-sized PTC solar field for heating and cooling of a hotel in Almería (Spain) Manuel Quirante a,
More informationHeating the University of Glasgow with river sourced heat pumps. Adam McConkey Andrew Poon-King Zhibin Yu
Heating the University of Glasgow with river sourced heat pumps Adam McConkey Andrew Poon-King Zhibin Yu Opportunity - Reduce Glasgow University s 1.9 m gas bill - The University is set to upgrade its
More informationPeter Randall Solar Kingdom Ltd
Peter Randall Solar Kingdom Ltd How is Solar Doing? How is Solar Doing? Now an Established Industry How is Solar Doing? Now an Established Industry UK a Major Market Estimated Total installed capacity
More informationPortland General Electric Company First Revision of Sheet No P.U.C. Oregon No. E-18 Canceling Original Sheet No. 26-1
First Revision of Sheet No. 26-1 P.U.C. Oregon No. E-18 Canceling Original Sheet No. 26-1 PURPOSE SCHEDULE 26 NONRESIDENTIAL DEMAND RESPONSE PILOT PROGRAM This schedule is an optional supplemental service
More informationEfficient utilization of energy sources
Efficient utilization of energy sources Perspectives for the reduction of fossil primary energy utilization in urban areas March 28 Using the energy content the most efficient way is using COMBINED HEAT
More informationAvailable online at ScienceDirect. Energy Procedia 110 (2017 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 110 (2017 ) 504 509 1st International Conference on Energy and Power, ICEP2016, 14-16 December 2016, RMIT University, Melbourne,
More informationDharam V. Punwani Avalon Consulting, Inc. Tom L. Pierson Turbine Air Systems, Ltd.
Turbine Inlet Air Cooling: A Great Strategy for Maximizing the Potential of Combustion Turbines and Addressing the Needs of Restructuring Energy Market Dharam V. Punwani Avalon Consulting, Inc. Tom L.
More informationIntegrating Standby Power and Steam Turbine Chillers for Better Resiliency at UNC Chapel Hill
Integrating Standby Power and Steam Turbine Chillers for Better Resiliency at UNC Chapel Hill IDEA 28 th Annual Campus Energy Conference Denver, Colorado Philip Barner, P.E. Director of Energy Services
More informationCalifornia Independent System Operator Corporation. California ISO. Import resource adequacy. Department of Market Monitoring
k California Independent System Operator Corporation California ISO Import resource adequacy September 10, 2018 Department of Market Monitoring Summary This report provides an update of analysis and trends
More informationREPLACEMENT OF AN OLD CHP FOR A NEW ONE ON THE TOURISTIC SECTOR: ENERGETIC AND ECONOMIC ANALISYS
Proceedings of the 6th International Conference on Mechanics and Materials in Design, Editors: J.F. Silva Gomes & S.A. Meguid, P.Delgada/Azores, 26-30 July 2015 PAPER REF: 5386 REPLACEMENT OF AN OLD CHP
More informationBiomass combustion with ORC for decentralized bioenergy applications: A techno-economic approach
Biomass combustion with ORC for decentralized bioenergy applications: A techno-economic approach A. Rentizelas a *, S. Karellas b **, E. Kakaras b, I. Tatsiopoulos a a Sector of Industrial Management and
More informationAvailable online at ScienceDirect. Energy Procedia 75 (2015 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (2015 ) 1172 1177 The 7 th International Conference on Applied Energy ICAE2015 Limiting the effect of ambient temperature on micro
More informationEnergy Savings Analysis Generated by a Real Time Energy Management System for Water Distribution
Energy Savings Analysis Generated by a Real Time Energy Management System for Water Distribution Sarah Thorstensen Derceto Ltd, Auckland, New Zealand sthorstensen@derceto.com Abstract Washington Suburban
More informationEnergy Audit Summary Report Audit No. 21. Pharmaceutical Industry
Energy Audit Summary Report Audit No. 21 Pharmaceutical Industry energyxperts.net Berlin (Germany) / Barcelona (Spain) November 2011 With the collaboration of the Chamber of Commerce and Industry of Madrid
More informationSolar Power Realities
Solar Power Realities Supply-Demand Characteristics, Storage and Capital Costs by Peter Lang Abstract This paper provides a simple analysis of the capital cost of solar power and energy storage sufficient
More informationBEYOND COMBINED HEAT AND POWER: POLIGENERATIVE SMALL SCALE RENEWABLE PLANT
Massimo Benenati (MassimoB) BEYOND COMBINED HEAT AND POWER: POLIGENERATIVE SMALL SCALE RENEWABLE 31 March 2018 L. Pezzola, V. Magalotti, R. Mussi 1, A. Bellissima 1, M. Colaiemma 2, M. Benenati 2, T. Tolda
More informationScienceDirect. High Efficiency Cogeneration: Electricity from cogeneration in CHP Plants
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 81 (2015 ) 430 439 69th Conference of the Italian Thermal Engineering Association, ATI 2014 High Efficiency Cogeneration: Electricity
More informationUrban Greening and the UHI: Seasonal Trade-offs in Heating and Cooling Energy Consumption in Manchester, UK
Urban Greening and the UHI: Seasonal Trade-offs in Heating and Cooling Energy Consumption in Manchester, UK T H E R E S E A R C H E R S C y n t h i a S k e l h o r n PhD Physical Geography Post-Doctoral
More informationMulti-objective approach in thermoenvironomic optimization of a Small-scale CCHP system with risk
Multi-objective approach in thermoenvironomic optimization of a Small-scale CCHP system with risk Gholamhossein Abdollahi (mr_abdollahy@yahoo.com) Hoseyn Sayyaadi (sayyaadi@kntu.ac.ir) Mechanical Engineering
More informationScienceDirect. Energy and environmental monitoring of a school building deep energy renovation in Italy
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 3318 3323 6th International Building Physics Conference, IBPC 2015 Energy and environmental monitoring of a school building
More informationResearch on integrated solar and geothermal energy engineering design in hot summer and cold winter area
Available online at www.sciencedirect.com Procedia Engineering 21 (2011) 648 655 2011 International Conference on Green Buildings and Sustainable Cities Research on integrated solar and geothermal energy
More informationUncertainty and Sustainable Energy Investments
Uncertainty and Sustainable Energy Investments Michael J. Kelleher Executive Director Energy and Sustainability SUNY College Of Environmental Science and Forestry mkellehe@esf.edu Energy Inelastic Demand
More informationScienceDirect. Model based optimization of a combined biomass-solar thermal system
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 48 (2014 ) 681 688 SHC 2013, International Conference on Solar Heating and Cooling for Buildings and Industry September 23-25, 2013,
More informationFOR RELEASE: 10:00 A.M. (MADRID TIME), WEDNESDAY, APRIL 16, 2014
FOR RELEASE: 10:00 A.M. (MADRID TIME), WEDNESDAY, APRIL 16, 2014 The Conference Board Spain Business Cycle Indicators SM THE CONFERENCE BOARD LEADING ECONOMIC INDEX (LEI) FOR SPAIN AND RELATED COMPOSITE
More informationAn Engineering Approach to the Optimal Design of Distributed Energy Systems in China
An Engineering Approach to the Optimal Design of Distributed Energy Systems in China Sustainable Thermal Energy Management in the Process Industries International Conference (SusTEM2011), October 25 th
More informationA HYBRID MONITORING-MODELING PROCEDURE FOR ANALYZING THE PERFORMANCE OF LARGE CENTRAL CHILLING PLANTS
A HYBRID MONITORING-MODELING PROCEDURE FOR ANALYZING THE PERFORMANCE OF LARGE CENTRAL CHILLING PLANTS Ricardo Troncoso, P.E. Senior Engineer ACR Engineering, Incorporated 97 South Congress Avenue Austin,
More informationIntegration of -SOFC generator and ZEBRA batteries for domestic application and comparison with other -CHP technologies
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (215 ) 999 14 The 7 th International Conference on Applied Energy ICAE215 Integration of - generator and ZEBRA batteries for domestic
More informationEVALUATION OF THE IMPACT OF NEW RESIDENTIAL WATER HEATER DISSEMINATION BY A RESIDENTIAL ENERGY END-USE MODEL
Proceedings of BS15: 14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 15. EVALUATION OF THE IMPACT OF NEW RESIDENTIAL WATER HEATER DISSEMINATION
More information4-C Foods CHP Plant NYSERDA Demonstration Project June 24, William Cristofaro P.E. Energy Concepts Engineering PC Rochester, NY
4-C Foods CHP Plant NYSERDA Demonstration Project June 24, 24 William Cristofaro P.E. Energy Concepts Engineering PC Rochester, NY 585-272-4650 www.nrg-concepts.com Project Summary: Modular 380 Kw CHP
More informationDiffusion of motor systems energy efficiency measures: an empirical study within Italian manufacturing SMEs
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (2015 ) 2569 2574 The 7 th International Conference on Applied Energy ICAE2015 Diffusion of motor systems energy efficiency measures:
More informationA New Type of Hybrid Groundwater Energy System
This case-history is about: A New Type of Hybrid Groundwater Energy System by Todd Giddings, Ph.D., P.G. My 10,000 square foot office building Located in State College, PA (5,600 hdd s) Constructed in
More informationPJM ENERGY PRICES 2005 Response to Howard M. Spinner Paper
PJM ENERGY PRICES 2005 Response to Howard M. Spinner Paper Joseph Bowring PJM Market Monitor Response to Howard M. Spinner Paper Re: PJM Energy Prices 2005 A March 13, 2006 paper ( Spinner paper ) by Howard
More informationAchieving a cost optimal balance between heat supply efficiency and moderation of demand
Achieving a cost optimal balance between heat supply efficiency and moderation of demand Dr. Christian Friebe Thüga Aktiengesellschaft COGEN Europe, 25th of February 560 cities and towns, 100 companies
More informationERCOT Public LTRA Probabilistic Reliability Assessment. Final Report
ERCOT Public 2016 LTRA Probabilistic Reliability Assessment Final Report November 21, 2016 Contents Summary... 1 Software Model Description... 3 Demand Modeling... 3 Controllable Capacity Demand Response
More informationFuture European Heat. Renewable heating comparisons
Document number Future European Heat Renewable heating comparisons Tuesday, 28 May 2013 By: Melahn Parker (Melahn.Parker@dnvkema.com) DNV KEMA Energy & Sustainability DNV KEMA serves the entire energy
More informationModeling and analyzing solar cooling systems in Polysun
Modeling and analyzing solar cooling systems in Polysun Seyed H. Rezaei (seyed.rezaei@velasolaris.com) 1 Andreas Witzig (andreas.witzig@velasolaris.com) 1 Michael Pfeiffer (michael.pfeiffer@velasolaris.com)
More informationAvailable online at ScienceDirect. Energy Procedia 61 (2014 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 61 (2014 ) 2201 2205 The 6 th International Conference on Applied Energy ICAE2014 Economic Feasibility of Pipe Storage and Underground
More informationUniversity of Michigan Eco-Driving Index (EDI) Latest data: August 2017
University of Michigan Eco-Driving Index () http://www.ecodrivingindex.org Latest data: August 2017 Developed and issued monthly by Michael Sivak and Brandon Schoettle Sustainable Worldwide Transportation
More informationCASE STUDY. Combined Heat and Power System Installation at Atrium II Condominium, 65 Spring Garden Avenue, Toronto
CASE STUDY Combined Heat and Power System Installation at Atrium II Condominium, 65 Spring Garden Avenue, Toronto 2 ATRIUM II COMBINED HEAT & POWER- CASE STUDY Contents 1. Executive Summary...4 2. Project
More informationHéctor Rubio Plana Gas Natural, SDG S.A. 18th. June 2009
1 Héctor Rubio Plana Gas Natural, SDG S.A. 18th. June 2009 Table of contents 1. Introduction 2. How does it work? 3. Experiences 4. Conclusions and future scenario 5. Future previsions 2 3 Solar Cooling
More informationAvailable online at ScienceDirect. Energy Procedia 91 (2016 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 91 (2016 ) 190 196 SHC 2015, International Conference on Solar Heating and Cooling for Buildings and Industry Retrofit of a solar
More informationSOLAR COOLING: STATE OF THE ART, TECHNICAL ANALYSIS AND FIRSTS APPLICATIONS
SOLAR COOLING: STATE OF THE ART, TECHNICAL ANALYSIS AND FIRSTS APPLICATIONS F. Asdrubali, G. Baldinelli, A. Presciutti, M. Caporali University of Perugia - Industrial Engineering Department, Via G. Duranti
More informationENERGY MANAGEMENT IN A CHILLED WATER PLANT USING THERMAL STORAGE
ENERGY MANAGEMENT IN A CHILLED WATER PLANT USING THERMAL STORAGE The Tenth International Conference on Thermal Energy Storage ECOSTOCK 2006 Stephane Bilodeau,, PE, Ph.D. sbilodeau@groupeenerstat.com Scope
More informationEconomic Estimation of Heat Storage Type Geothermal Source Heat Pump System Applied in K-Ward Office Building
Economic Estimation of Heat Storage Type Geothermal Source Heat Pump System Applied in K-Ward Office Building Myung Jin Ko 1, a, Yong Shik Kim 2, b, Yong In Kim 3, c, Eun Taek Lee 4, d, Joong Heon Kim
More informationTechniques for quasi-static operating optimization of CHP plants. Mario Nervi Università di Genova (Italy)
Techniques for quasi-static operating optimization of CHP plants Mario Nervi Università di Genova (Italy) PolyCity Workshop, 25 th of May 2007, Turin, ITALY 1 Mario Nervi Associate professor of Fundamentals
More informationEnergiewende in Germany
Unintended Consequences for District Energy/CHP IDEA Seattle, June, 9 th 214 Werner R. Lutsch, Managing Director/CEO of AGFW and Vice President of Euroheat & Power Seattle, June 214 Energiewende in Germany
More informationEvaluation of reduced energy use resulting from a DHC network in the Shinjuku DHC area
Evaluation of reduced energy use resulting from a DHC network in the Shinjuku DHC area Hashidate D 1 ; Nakajima Y 2 1 Graduate School Kogakuin University, Tokyo, Japan 2 Associate Professor Kogakuin University,
More informationMaking the move to cogeneration
Making the move to cogeneration > Decision factors for facility managers In theory, almost any facility with a simultaneous need for both electric and thermal energy is a potential candidate for the energy-saving
More informationA New Absorption Machine for Both Cooling and Heating
A New Absorption Machine for Both Cooling and Heating Giuseppe Corallo Institute of Thermal-Fluid Dynamics, ENEA C.R. Casaccia, Rome, Italy e-mail corallo@casaccia.enea.it Abstract. The paper, in very
More informationCost Optimal Retrofitting Of Shopping Malls In Europe
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 2058 2063 6th International Building Physics Conference, IBPC 2015 Cost Optimal Retrofitting Of Shopping Malls In Europe
More informationDoc. CEN/TC 228 N541 CEN/TC 228
Doc. CEN/TC 228 N541 CEN/TC 228 Date: 2006-08 CEN/TC 228 WI 026 CEN/TC 228 Secretariat: DS Heating systems in buildings Method for calculation of system energy requirements and system efficiencies Part
More informationSOFC Micro-CHP integration in residential buildings
PROCEEDINGS OF ECOS 212 - THE 25TH INTERNATIONAL CONFERENCEON EFFICIENCY, COST, OPTIMIZATION, SIMULATION AND ENVIRONMENTAL IMPACT OF ENERGY SYSTEMS JUNE 26-29, 212, PERUGIA, ITALY SOFC Micro-CHP integration
More informationEnergy Upgrade Screening Study
Energy Upgrade Screening Study Prepared for: The University of Maine Orono, ME Prepared by: R.G. Vanderweil Engineers, LLP 274 Summer Street Boston, MA 02210 Vanderweil Project No.: 28471.00 October 28,
More informationTHE CONFERENCE BOARD LEADING ECONOMIC INDEX (LEI) FOR THE EURO AREA AND RELATED COMPOSITE ECONOMIC INDEXES FOR APRIL
FOR RELEASE: 9:30 A.M. (ET), THURSDAY, MAY 28, 2015 The Conference Board Euro Area Business Cycle Indicators SM THE CONFERENCE BOARD LEADING ECONOMIC INDEX (LEI) FOR THE EURO AREA AND RELATED COMPOSITE
More informationEnergy Audit Summary Report Audit No GER08. DIN Building Berlin, Germany. Offices
Energy Audit Summary Report Audit No. 61 - GER08 DIN Building Berlin, Germany Offices energyxperts.net Berlin (Germany) / Barcelona (Spain) June 2012 This energy audit has been carried out with cofunding
More informationDesign and optimization of solar water heating system for a five star hotel in Varanasi
Design and optimization of solar water heating system for a five star hotel in Varanasi Mahesh Vipradas & Amit Kumar Tata Energy Research Institute, Darbari Seth Block, Habitat Place, Lodhi Road, New Delhi
More informationENERGY EVALUATION BY SIMULATION FOR EFFECTIVE USE OF SEWAGE HEAT
Proceedings of BS213: ENERGY EVALUATION BY SIMULATION FOR EFFECTIVE USE OF SEWAGE HEAT Toshihiko Sudo 1,Ryoichi Kajiya 2, Koji Sakai 2 1 Nikken Sekkei Research Institute, Japan 2 School of Science and
More informationLife Cycle Assessment performance comparison of small solar thermal cooling systems with conventional plants assisted with photovoltaics
Available online at www.sciencedirect.com Energy Procedia 30 (2012 ) 893 903 SHC 2012 Life Cycle Assessment performance comparison of small solar thermal cooling systems with conventional plants assisted
More informationPre-Feasibility Study of Cogeneration in a Paper Recycling Mill in Bangladesh
CMU. Journal (2003) Vol. 2(1) 27 Pre-Feasibility Study of Cogeneration in a Paper Recycling Mill in Bangladesh Md. Ehsan, M.A.R. Sarkar*, Md. Obaidullah and M. A. Islam Bangladesh University of Engineering
More informationGas Natural, SDG S.A. 18th. June 2009
Héctor Rubio Gas Natural, SDG S.A. 18th. June 2009 1 Table of contents 1. Introduction 2. How does it work? 3. Experiences 4. Conclusions and future scenario 2 3 Introduction Fitting demand to solar energy
More informationAORA SOLAR S TULIP SYSTEM A HYBRID SOLAR THERMAL SOLUTION
AORA SOLAR S TULIP SYSTEM A HYBRID SOLAR THERMAL SOLUTION COMPANY PROFILE COMPANY PROFILE AORA SOLAR commercializes its own solar thermal technology the TULIP system, based on a solar receiver heating
More informationSOLAR THERMAL IT S HOT AGAIN! Solar Water Heating and Solar Thermal Energy Solutions
SOLAR THERMAL IT S HOT AGAIN! Solar Water Heating and Solar Thermal Energy Solutions Solar Water Heating and Solar Thermal Energy Solutions Bill Guiney Program Manager Renewable Energy Solutions Great
More informationAvailable online at ScienceDirect. Energy Procedia 91 (2016 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 91 (2016 ) 824 831 SHC 2015, International Conference on Solar Heating and Cooling for Buildings and Industry LEED Platinum awarded
More informationCHAPTER THREE. Load Curves The curve showing the variation of load on the power station (power plant) with reference to time is known as load curve.
CHAPTER THREE Load Curves The curve showing the variation of load on the power station (power plant) with reference to time is known as load curve. Daily Load Curve Maximum Load (Peak Load) It represents
More informationClean Energy Extension
Clean Energy Extension ag.umass.edu/energy The Clean Energy Extension is an Affiliate of the UMass Amherst Center for Agriculture, Food and the Environment 209 Agricultural Engineering Building University
More informationF. Kabus, G. Möllmann, F. Hoffmann and J. Bartels
TWO-YEAR EXPERIENCE IN THE OPERATION OF AN AQUIFER THERMAL ENERGY STORE BASED ON SURPLUS HEAT ARISING FROM A GAS AND STEAM COGENERATION PLANT AT NEUBRANDENBURG / NE GERMANY F. Kabus, G. Möllmann, F. Hoffmann
More informationEnergy Management :: 2007/2008
:: 2007/2008 Class # 3P Energy Prices João Parente joao.parente@dem.ist.utl.pt Energy transformation PROBLEM 01 Consider a Combined Heat and Power Plant (CHP), based on a micro gas turbine recuperated
More informationBuilding Operator Certification Level I
Building Operator Certification Level I A Partnership of the CUNY Institute for Urban Systems Building Performance Lab, the CUNY School of Professional Studies, and the New York State Energy Research &
More informationDESIGN SUSTAINABLE BUILDING WITH OPTIMIZED COMBINED HEATING, COOLING, AND POWER (CHCP) SYSTEM
DESIGN SUSTAINABLE BUILDING WITH OPTIMIZED COMBINED HEATING, COOLING, AND POWER (CHCP) SYSTEM Saeed Karimi Alavijeh 1* and Omid Zeinali 2 National Iranian Gas Company (NIGC), Assaluyeh, Bushehr, Iran 1*
More informationSTUDY ON TESTING FEASIBILITY OF SOLAR ENERGY IN THE PALESTINIAN TERRITORIES
STUDY ON TESTING FEASIBILITY OF SOLAR ENERGY IN THE PALESTINIAN TERRITORIES FALLING WITHIN THE FRAMEWORK OF THE EXTRAORDINARY FINANCIAL ASSISTANCE OF THE CZECH REPUBLIC TO THE PALESTINIAN TERRITORIES FOLLOWING
More informationAvailable online at ScienceDirect. Energy Procedia 81 (2015 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 81 (2015 ) 1171 1183 69th Conference of the Italian Thermal Engineering Association, ATI 2014 Dynamic simulation and performance
More informationTwinning project Bulgaria
Twinning project Bulgaria PROJECT TWINNING BULGARIA Institutional Building at the Energy Efficiency Agency (EEA) Seminar Industrial Energy Audits Energy efficiency case studies Sofia February 20th 2007
More informationSolar, Wind and Market Power in the New Zealand Electricity Market (and hydro lake dynamics) Mina Bahrami Gholami and Stephen Poletti
Solar, Wind and Market Power in the New Zealand Electricity Market (and hydro lake dynamics) Mina Bahrami Gholami and Stephen Poletti University of Auckland Economic Paradox Energy Only Markets. Low-carbon
More informationENERGY AND ENVIRONMENTAL EVALUATION OF MICRO-COGENERATION SYSTEM FOR CONVENIENCE STORES IN THAILAND
American Journal of Environmental Sciences 10 (3): 312-323, 2014 ISSN: 1553-345X 2014 Science Publication doi:10.3844/ajessp.2014.312.323 Published Online 10 (3) 2014 (http://www.thescipub.com/ajes.toc)
More informationBuilding performance based on measured data
Building performance based on measured data S. Andersson 1,*, J-U Sjögren 2, R. Östin 1 and T.Olofsson 1 1. Department of applied physics and electronics, Umeå, Sweden 2. NCC Ltd, Stockholm, Sweden * Corresponding
More informationCO₂emission of FC which is the most commercialized type of household fuel cell and gas fired boiler. Therefore, energy saving effect and carbon emissi
Applicability of a fuel cell for primary energy saving in a liquid desiccant and evaporative cooling assisted 100% outdoor air system Su-Young Jo 1, Joon-Young Park 1, Jae-Weon Jeong 1,* 1 Division of
More informationNORTH AMERICAN MONITORING OF A HOTEL WITH ROOM SIZE GSHPS
NORTH AMERICAN MONITORING OF A HOTEL WITH ROOM SIZE GSHPS Hugh I. Henderson, Jr. P.E.*, Steven W. Carlson, P.E., and Adam C. Walburger CDH Energy Corp. Cazenovia, NY USA ABSTRACT This paper presents the
More informationAvailable online at ScienceDirect. Procedia Technology 24 (2016 ) Tahira Bano a,*, K.V.S. Rao a
Available online at www.sciencedirect.com ScienceDirect Procedia Technology 24 (2016 ) 505 512 International Conference on Emerging Trends in Engineering, Science and Technology (ICETEST - 2015) Levelized
More informationOPTIMAL OPERATING METHOD FOR A HEAT SOURCE SYSTEM CONSIST OF CENTRIFUGAL CHILLERS
Numbers of Abstract/Session (given by NOC) - 1 - OPTIMAL OPERATING METHOD FOR A HEAT SOURCE SYSTEM CONSIST OF CENTRIFUGAL CHILLERS Satoshi, Nikaido, Centrifugal & Absorption Chiller Department, Air-Conditioning
More information6 Cost Analysis. Table 6.1 Initial System Costs
6.1 Considerations 6 Analysis There are two parts that need to be considered when looking into a cost analysis. The first is determining the initial cost of the system to determine whether or not a simple
More informationTechnical Report Two: Building and Plant Energy Analysis Report
The American Swedish Institute Minneapolis, MN Technical Report Two: Building and Plant Energy Analysis Report Name: Option: Mechanical Advisor: Stephen Treado Date: 10.19.11 Table of Contents Executive
More information