A Field Study of the Thermal Environment in Residential Buildings in Harbin

Size: px
Start display at page:

Download "A Field Study of the Thermal Environment in Residential Buildings in Harbin"

Transcription

1 KC (4664) A Field Study of the Thermal Environment in Residential Buildings in Harbin Zhao-Jun Wang, Ph.D. Gang Wang Le-Ming Lian ABSTRACT This paper presents the main findings of Project HIT supported by the Scientific Research Foundation of Harbin Institute of Technology, a field study of indoor climates and occupant comfort in 66 residential buildings in Harbin, located in northeastern China. One hundred and twenty sets of questionnaire responses were provided from 120 subjects for winter, each accompanied by a full set of physical indoor climatic measurements with an indoor climate analyzer and a thermal comfort meter, which met ASHRAE Standard and ISO Standard 7726 (1985) for accuracy, duration of sample, and response time. Only 77.5% of the indoor measurements fell within the ASHRAE Standard and ISO Standard 7730 (1994) winter comfort zone of 16.5~22.5 C (corresponding to the average clothing, 1.37 clo); 91.7% of the occupants considered their thermal conditions acceptable. The operative temperature corresponding to the accepted thermal environment by 80% of the occupants is 18.0~25.5 C. Thermal neutrality, according to responses on the ASHRAE seven-point sensation scale, occurred at 21.5 C in winter. The preferred temperature is 21.9 C. Over 80% of the occupants felt dry at a relative humidity of 20%~30% in the comfort zone and over 40% at a relative humidity of 30%~55%. INTRODUCTION Current thermal comfort standards, such as ASHRAE and ISO 7730, are based almost exclusively on data from climate chamber experiments performed in mid-latitude climatic regions of North America and northern Europe. These standards are suitable for static, uniformly thermal conditions. But real people live in changeable, inconsistent environments. This poses potential problems when the standards are applied to residents living in real-world situations (McIntyre 1980; Schiller 1990; Benton et al. 1990). A large number of field studies have been performed around the world (Humphreys 1976; Dedear and Auliciems 1985; Schiller et al. 1988; Dedear and Fountain 1994; Howell and Kennedy 1979; Howell and Stramler 1981; Fishman and Pimbert 1979; Busch 1990; Xia et al. 1999; Cena and Dedear 1999; de Paula, Xavier, and Roberto 2000), but most of these were carried out in tropical and temperate climatic zones except Donnini et al. (1996), which was conducted in a cold climate in Montreal, Canada. The results of such field studies indicate that there is not perfect harmony between the expression of thermal comfort proposed by ASHRAE and ISO 7730 (ISO 1994) and the sensations that people are really feeling. This paper presents the main findings of Project HIT supported by the Scientific Research Foundation of Harbin Institute of Technology, a field study of indoor climates and occupant comfort in 66 residential buildings in Harbin, located in northeastern China. AIMS The current study was performed in Harbin, which has a cold and arid climate. The objectives of this project are as follows: To develop a database of the thermal environments and subjective responses of occupants in existing residential buildings in a cold, dry climate. To determine both the neutral and preferred operative temperature for occupancy as well as the range of thermal conditions found to be acceptable by the occupants. These findings are to be compared to the conditions required by ASHRAE and ISO To investigate the influence of relative humidity and vertical temperature difference. Zhao-Jun Wang is an associate professor, Gang Wang is a doctoral candidate, and Le-Ming Lian is a professor in the School of Municipal and Environmental Engineering, Harbin Institute of Technology, Harbin, China ASHRAE. THIS PREPRINT MAY NOT BE DISTRIBUTED IN PAPER OR DIGITAL FORM IN WHOLE OR IN PART. IT IS FOR DISCUSSION PURPOSES ONLY AT THE 2003 ASHRAE ANNUAL MEETING. The archival version of this paper along with comments and author responses will be published in ASHRAE Transactions, Volume 109, Part 2. ASHRAE must receive written questions or comments regarding this paper by July 11, 2003, if they are to be included in Transactions.

2 TABLE 1 Summary of the Samples of Residence Occupants Sample size 120 Gender Male 59 (49.2%) Age (year) Length of time living in Harbin (years) To investigate potential acclimation effects and the adapted measures taken by occupants. METHOD Female 61 (50.8%) Mean 46.4 Standard deviation Maximum 80.0 Minimum 14.0 Mean 33.6 Standard deviation Maximum 67.0 Minimum 0.25 Outdoor Climatic Environment Harbin is situated in the northeast of China (at the latitude of north of the equator and longitude of east). The winter climate in Harbin is very cold and dry. The current experiment was conducted during the winter of (from December 2000 to January 2001). The mean daily temperature during this period was 15.5 C to 29.5 C, which is the lowest temperature in the past 30 years. Subjects We visited 66 families in two residential districts in Harbin. The samples were chosen equally in different living conditions, such as location of floor, area of the house, as well as the gender of subjects. A total of 120 participants provided 120 sets of data and subjective responses. The subjects participating in the study were composed of 61 females (50.8%) and 59 males (49.2%). The average age of all subjects is 46.4 years with a range of 14 to 80. A summary of the background characteristics of the subjects is presented in Table 1. Measurement of Indoor Climates An indoor climate analyzer and a thermal comfort meter made in Denmark were used to collect measurements of the indoor climates. 1. The physical data include air temperature, relative humidity, radiant asymmetry, air velocity, and predicted mean vote (PMV) and predicted percentage dissatisfied (PPD) indices. These were collected in accordance with the global database presented by Dedear and Brager (1998). Air temperature and air velocity were measured at the 0.1, 0.6, and 1.1 meter heights, representing the immediate environment of the seated person s ankles, mid-body, and neck, respectively. Relative humidity, radiant asymmetry, and PMV-PPD indices were measured at the 1.1 meter height. 2. All accuracies (manufacturer s specifications and the results of the calibration in an Instruments Testing Station in Heilongjiang Province) of the instruments used in the current field study meet the ASHRAE and ISO 7726 (ISO 1985) standards for accuracy, duration of sample, and response time. The air temperature transducer is based on a platinum resistance temperature sensing element with accuracy within 0.2 C and response time of 50 s to 90% of step change in still air. The humidity transducer is a dew-point transducer. Dew-point temperature is registered by a chilled mirror with total accuracy of ±0.5 C at 25 C, and relative humidity is measured directly. Air velocity is measured on the constant temperature anemometer principle with accuracy of ±5% at ±0.05 m/s in the measurement range of 0.05 to 1.0 m/s and response time of 0.2 s to 90% of step change. The radiant temperature asymmetry transducer consists of two identical faces (A and B), which independently measure incident radiation on each plane surface with total accuracy of ±0.5 C at 15 C and response time of 60 s to 90% of step change. Questionnaires The subjective questionnaires include the following: 1. Background survey The background survey form covered name, gender, age, and length of time living in Harbin for demographic characteristics of the sample. 2. Clothing and activity checklists 3. Thermal sensation, thermal preference, and thermal acceptability survey The thermal sensation scale is the ASHRAE seven-point scale of warmth ranging from cold (-3) to hot (+3) with neutral (0) in the middle. The McIntyre scale focuses more directly on thermal satisfaction by probing the subjects judgments of whether they would prefer the conditions to be different. The subject responds to three choices: I want to be: warmer, no change, cooler (McIntyre and Gonzalez 1976). These data are then encoded as +1, 0, and -1, respectively, for subsequent analysis. The thermal acceptability scale asked on a two-point scale whether the subjects would accept the thermal environment. Possible answers are yes and no, encoded as 1 and 0, respectively. 4. Thermal comfort and air condition survey The thermal comfort scale uses a five-point scale to rate the participants immediate impressions of comfort with regard to airflow, relative humidity, and general comfort. The five-point scale is very uncomfortable ( 2), slightly 2 KC (4664)

3 TABLE 2 Statistical Summary of Physical Data Mean Standard Deviation Maximum Minimum Air temperature ( C) Relative humidity (%) Air velocity (m/s) Radiant temperature ( C) Operative temperature ( C) PMV (%) PPD (%) Clothing (clo) Figure 1 Frequency of operative temperature. Figure 2 Frequency of air velocity. uncomfortable ( 1), comfortable (0), slightly comfortable (+1), and very comfortable (+2). The air condition assessment is collected from the subjects responses to the question: The air that you feel in the room is: muggy, fresh, dry, damp. 5. Adapted measures survey The adapted measures used by the occupants include electric heater, humidifier, openable window, curtain, and others. Figure 3 Frequency of relative humidity. RESULTS Indoor Climates Table 2 provides statistical summaries of the indoor climate measurements for the winter samples in Harbin. Air temperatures (t a ) (averaged across the three heights of 0.1, 0.6, and 1.1 m) fell within 12 C and 25.6 C, with a mean of 20.1 C. Mean radiant temperature (t r ) (mean of four directions) is 21.6 C. Operative temperatures (t o ) (average of t a and t r ) ranged between 12.1 C and 29.4 C, with a mean of 20.8 C. Relative humidities (RH) ranged from 22% to 53%. Air velocities (mean of three heights) are very low in winter, with a mean of 0.06 m/s. Figure 1 to Figure 3 give the frequency of operative temperature, air velocity, and relative humidity, respectively. From Figure 1, we see that 70.0% of the operative temperature measurements ranged between 18 C and 22.5 C. From Figure 2, we find that 95.8% of the air velocities are not more than 0.15 m/s. Personal Comfort Variables The insulation of clothes (clo) is obtained from tables (ISO 1994). On average, the chair insulation increment amounts to 0.15 clo (McCullough et al. 1994). Based on activity checklists referring to the hour just prior to sitting down to fill in the questionnaire, metabolic rates (met) of the subjects are estimated to be, on average, 1.2 met (70 W/m 2 ). Thermal insulation, including the insulation of the chairs on which subjects were sitting when they completed the questionnaire, is listed in Table 2. KC (4664) 3

4 Figure 4 Frequency of thermal sensation vote. Figure 5 Calculation of neutral temperature. Thermal Sensation The frequency distribution of thermal sensation votes is given in Figure 4. The strength of association and sensitivity of thermal sensation votes to temperature variations can be quantified using linear regression techniques. The data are binned into 0.5 C intervals. Mean thermal sensation votes and predicted mean vote for each half-degree operative temperature bin have been plotted in Figure 5. The linear regression equations are fitted for these binned thermal sensations against operative temperature: Mean thermal sensation = t o (1) Predicted mean vote = t o (2) Figure 6 Calculation of preferred temperature. The regression coefficient between the mean thermal sensation and the operative temperature is The regression coefficient between predicted mean vote and the operative temperature is The neutrality is derived by solving the equation for a mean sensation of zero, and the neutral operative temperature is 21.5 C, which is about equal to the mean operative temperature. The results are in accord with the ones that Dedear and Brager gave in 1998, proving that the adaptation of occupants to thermal environments is established. Thermal Preference Preferred temperature is assessed directly according to the answers of the question: At this point in time, would you prefer to feel warmer, cooler, or no change? Separate probit models are fitted to the want warmer and want cooler percentages within each half-degree operative temperature bin. Preferred temperature is obtained from the intersection of the two fitted probit lines in Figure 6 and the value is 21.9 C. From this we know that the preferred operative temperature is higher than the neutral operative temperature in cold area. The results are in accord with the ones given by McIntyre (1980); Figure 7 Calculation of thermal acceptability. Humphreys (1976); Dedear and Fountain (1994); Dedear and Brager (1998). Thermal Acceptability Thermal acceptability can be quantified simply as the percentage of the sample of the occupants who answered acceptable to the questionnaires on whether the thermal conditions were acceptable: 91.7% of occupants considered their thermal environments to be acceptable. ASHRAE and ISO 7730 comfort zone 20~24 C is only for ~1 clo. The average clothing in this study is 1.37 clo. This corresponds to a comfort range (PPD < 10%, PMV< ±0.5) from 16.5 C to 22.5 C, and 77.5% of the thermal conditions fell within the comfort zone 16.5 ~ 22.5 C. The acceptable temperature range is determined as follows: All persons voting +3, +2, 2, 4 KC (4664)

5 and 3 are considered as uncomfortable, while people voting 1, 0, and +1 are considered as comfortable. Percentage of dissatisfied is calculated for each half-degree operative temperature bin. The operative temperatures at which 80% of the occupants felt comfortable are the acceptable temperatures. In the current study, the acceptable temperature range is 18.0~25.5 C in Figure 7. Adaptation Measures The acceptable temperature range is very wide and it indicates that the adaptation of people to thermal environment is very important. The main measure taken by occupants is clothing adjustments. The insulation of clothes is 0.81~2.08 clo. DISCUSSION Comparisons Between Observed Comfort Data and the Standards Description of Comfort Standards ASHRAE In the winter, operative temperature and humidity limits are defined by a comfort zone on the psychrometric chart having the following coordinates: t o =19.5~23.0 C at 16.7 C T dp (dew point) and t o = 20.2~24.6 C at 1.7 C T dp. The two slanted sides are defined by the new effective temperature (ET * ). The winter limits are ET * = 20.0 and 23.6 C. The maximum limit for mean air velocity is 0.15 m/s in the winter. The vertical air temperature difference between the 0.1 and 1.7 meter levels shall not exceed 3 C. ISO The ISO standard is very similar to the ASHRAE standard with a few minor exceptions. It does not specify humidity limits, resulting in a comfort zone defined strictly in terms of operative temperature limits: t o shall be between 20~24 C in the winter. The maximum allowable air velocity is 0.15 m/s. The maximum acceptable vertical air temperature difference is the same, but it is taken between the 0.1 and 1.1 meter levels. Due to the similarity of the ASHRAE and ISO comfort standards and because the calculating of ET * is difficult, we only compare the results to the ISO standard and calculate the index of t o instead of ET *. Comparisons with Thermal Comfort Standards Humidity on Human Comfort. According to the comfort standard, the influence of relative humidities at 22% to 53% all fell within the comfort zones. But in fact, 81.1% of the occupants felt dry at relative humidity of 20% to 30%, while 18.9% people thought it acceptable. When relative humidity was 30% to 40%, 40.5% persons felt dry, 14.3% people felt damp, 42.9% occupants thought it acceptable, and the other 2.3% felt muggy. The feeling of the subjects at relative humidity of 40% to 55% was almost the same with that of ones at relative humidity of 30% to 40%. In winter, people living in northeastern China often complain that the air is too dry to feel comfortable in their throats. The comfort standard for humidity seems too wide to be applied in Harbin. Vertical Air Temperature Difference on Human Comfort. In 17.5% of the samples, people were not satisfied with ISO 7730 comfort standard on air temperature gradient. But 52.4% of the persons felt comfortable among these occupants. Only 47.6% of the people felt slightly cool at their feet when the operative temperature at the 0.1 meter level was lower than 16 C. So we think that vertical air temperature difference is not the main cause that can influence human comfort, but the operative temperature at the 0.1 meter level is the key to the question. The lowest limit of 16 C at 0.1meter level is suggested. Comparisons with Previous Thermal Comfort Field Studies Harbin subjects are as sensitive to temperature variations as the San Francisco and Pekin subjects and less sensitive to temperature variations than the Townsville and Montreal subjects. A gradient of one sensation unit per 3 C is found in the Harbin, San Francisco, and Pekin studies, while a gradient of one sensation unit per 2 C was found in both the Townsville and Montreal studies. In this study, the neutral operative temperature (21.5 C) is lower than that of Montreal (23.1 C) while higher than that of Kalgoorlie (20.3 C) in winter. The preferred operative temperature is found to be 21.9 C, which is similar to that of the Montreal study (22.0 C). Eighty percent of the occupants can accept the operative temperature range at 18.0~25.5 C, and the upper limit of accepted temperature is similar to that of the Montreal study (21.5~25.5 C) and the minimum temperature is lower than that of the Montreal study. CONCLUSION 1. According to the ASHRAE and ISO 7730 comfort standards, only 77.5% of the thermal conditions fall within the comfort zone of 16.5~22.5 C; 91.7% of the occupants considered their thermal environments to be acceptable due to adaptability measures taken by occupants. 2. Eighty percent of the occupants can accept the operative temperature range at 18.0~25.5 C. It is higher than the winter comfort zone of 16.5~22.5 C. 3. Neutral operative temperature is 21.5 C. Preferred operative temperature is 21.9 C. 4. Some 81.1% of the occupants felt dry at relative humidity of 20% to 30%, while over 40% of the persons felt dry at relative humidity of 30% to 55%. The lowest limit of relative humidity shall be 30% instead of the 20% recommended in comfort standards. 5. Only 47.6% of the people felt slightly cool at their feet when the vertical air temperature difference between 1.1 and the 0.1 meter heights was over 3 C and the operative temperature at 0.1 meter level was lower than 16 C. So we think that vertical air temperature difference is not the main KC (4664) 5

6 factor influencing human comfort, but the operative temperature at 0.1 meter level is the key to the question. The lowest limit of 16 C at 0.1 meter level is suggested. REFERENCES ASHRAE ANSI/ASHRAE Standard , Thermal environmental conditions for human occupancy. Atlanta: American Society of Heating, Refrigerating and Air Conditioning Engineers, Inc. Benton, C.C, F.S. Bauman, and M.E. Fountain A field measurement system for the study of thermal comfort. ASHRAE Transactions 96(1): Busch, J.F Thermal responses to the THAI office environment. ASHRAE Transactions 96(1): Cena, K, and R.J. Dedear Field study of occupant comfort and office thermal environments in a hot, arid climate. ASHRAE Transactions 105(2): Dedear, R.J, and A. Auliciems Validation of the predicted mean vote model of thermal comfort in six Australian field studies. ASHRAE Transactions 91(2B): Dedear, R.J, and G.S. Brager Developing an adaptive model of thermal comfort and preference. ASHRAE Transactions 104(1): Dedear, R.J, and M.E. Fountain Field experiments on occupant comfort and office thermal environments in a hot-humid climate. ASHRAE Transactions 100(2): de Paula Xavier, A.A, and L. Roberto Indices of thermal comfort developed from field survey in Brazil. ASHRAE Transactions 106(1): Donnini, G., J. Molina, C. Martello, et al Field study of occupant comfort and office thermal environments in a cold climate. ASHRAE Transactions 103(2): Fishman, D.S, and S.L. Pimbert Survey of the subjective responses to the thermal environment in offices. In Indoor climate, P.O. Fanger and O. Valbjorn, pp Copenhagen: Danish Building Research Institute. Humphreys, M.A Field studies of thermal comfort compared and applied. Building Services Engineer 44: Howell, W.C, and P.A. Kennedy Field validation of the Fanger thermal comfort model. Human Factors 21(2): Howell, W.C, and C.S. Stramler The contribution of psychological variables to the prediction of thermal comfort judgments in real world settings. ASHRAE Transactions 87(1): ISO International Standard Thermal environments Specifications relating to appliances and methods for measuring physical characteristics of the environment. Geneva: International Standard Organization. ISO International Standard Moderate thermal environment Determination of the PMV and PPD indices and the specification of conditions for thermal comfort. Geneva: International Standard Organization. McIntyre, D.A., and R.R. Gonzalez Man s thermal sensitivity during temperature changes at two levels of clothing insulation and activity. ASHRAE Transactions 82(2). McIntyre, D.A Indoor Climate. London: Applied Science Published LTD. McCullough, E.A, B.W. Olesen, and S. Hong Thermal insulation provided by chairs. ASHRAE Transactions 100(1): Schiller, G.E A comparison of measured and predicted comfort in office buildings. ASHRAE Transactions 96(1): Schiller, G.E, E.A. Arens, F.S. Bauman, et al A field study of thermal environment in office buildings. ASHRAE Transactions 94(2): Xia, Y.Z., R.Y. Zhao, and Y. Jiang Thermal comfort in naturally ventilated houses in Beijing. HV&AC 29(2): KC (4664)

Field Studies of Subjective Effects on Thermal Comfort in a University. Classroom

Field Studies of Subjective Effects on Thermal Comfort in a University. Classroom Field Studies of Subjective Effects on Thermal Comfort in a University Classroom Jian Wang Zhaojun Wang Master Associate Candidate Professor School of Municipal & Environmental Engineering, Harbin Institute

More information

PREDICTION OF THERMAL SENSATION IN NON-AIR- CONDITIONED BUILDINGS IN WARM CLIMATES

PREDICTION OF THERMAL SENSATION IN NON-AIR- CONDITIONED BUILDINGS IN WARM CLIMATES PREDICTION OF THERMAL SENSATION IN NON-AIR- CONDITIONED BUILDINGS IN WARM CLIMATES PO Fanger and J Toftum * International Centre for Indoor Environment and Energy, Technical University of Denmark ABSTRACT

More information

A Comparison of Calculated and Subjective Thermal Comfort Sensation in Home and Office Environment

A Comparison of Calculated and Subjective Thermal Comfort Sensation in Home and Office Environment Proceedings of Conference: People and Buildings held at the offices of Arup UK, 23rd September 2011. London: Network for Comfort and Energy Use in Buildings, http://nceub.org.uk A Comparison of Calculated

More information

A PRELIMINARY THERMAL COMFORT STUDY IN TROPICAL BUILDINGS LOCATED IN MALAYSIA

A PRELIMINARY THERMAL COMFORT STUDY IN TROPICAL BUILDINGS LOCATED IN MALAYSIA International Journal of Mechanical and Materials Engineering (IJMME), Vol. 3 (2008), No.2, 119-126. A PRELIMINARY THERMAL COMFORT STUDY IN TROPICAL BUILDINGS LOCATED IN MALAYSIA Y.H. Yau Department of

More information

A Field Study of Thermal Comfort in Open-plan Office Buildings during Transition Seasons in Harbin. Yunsong Han 1, 2, Huixuan Sun 1, 2, Cheng Sun 1, 2

A Field Study of Thermal Comfort in Open-plan Office Buildings during Transition Seasons in Harbin. Yunsong Han 1, 2, Huixuan Sun 1, 2, Cheng Sun 1, 2 A Field Study of Thermal Comfort in Open-plan Office Buildings during Transition Seasons in Harbin Yunsong Han 1, 2, Huixuan Sun 1, 2, Cheng Sun 1, 2 1 School of Architecture, Harbin Institute of Technology,

More information

REDEFINING APPROPRIATE THERMAL COMFORT STANDARD FOR NATURALLY VENTILATED BUILDINGS IN TROPICS (SINGAPORE AND INDONESIA PERSPECTIVE)

REDEFINING APPROPRIATE THERMAL COMFORT STANDARD FOR NATURALLY VENTILATED BUILDINGS IN TROPICS (SINGAPORE AND INDONESIA PERSPECTIVE) REDEFINING APPROPRIATE THERMAL COMFORT STANDARD FOR NATURALLY VENTILATED BUILDINGS IN TROPICS (SINGAPORE AND INDONESIA PERSPECTIVE) H Feriadi, NH Wong *, S Chandra, KW Cheong, KW Tham Department of Building,

More information

RADIANT SLAB COOLING: A FIELD STUDY OF OCCUPANT THERMAL COMFORT. Zhen Tian 1, James A. Love 2

RADIANT SLAB COOLING: A FIELD STUDY OF OCCUPANT THERMAL COMFORT. Zhen Tian 1, James A. Love 2 Second National IBPSA-USA Conference Cambridge, MA August 2-4, 2006 RADIANT SLAB COOLING: A FIELD STUDY OF OCCUPANT THERMAL COMFORT Zhen Tian 1, James A. Love 2 1 Ph. D. Candidate, Faculty of Environmental

More information

Energy and indoor temperature consequences of adaptive thermal comfort standards

Energy and indoor temperature consequences of adaptive thermal comfort standards Energy and indoor temperature consequences of adaptive thermal comfort standards L. Centnerova and J.L.M. Hensen Czech Technical University in Prague, Czech Republic (lada@tzb.fsv.cvut.cz) Technische Universiteit

More information

Environmental and human factors influencing thermal comfort of office occupants in hot-humid and hot-arid climates

Environmental and human factors influencing thermal comfort of office occupants in hot-humid and hot-arid climates Loughborough University Institutional Repository Environmental and human factors influencing thermal comfort of office occupants in hot-humid and hot-arid climates This item was submitted to Loughborough

More information

SUBJECTIVE AND MEASURED THERMAL COMFORT IN ITALIAN UNIVERSITY CLASSROOMS IN HEATED AND FREE RUNNING CONDITIONS

SUBJECTIVE AND MEASURED THERMAL COMFORT IN ITALIAN UNIVERSITY CLASSROOMS IN HEATED AND FREE RUNNING CONDITIONS SUBJECTIVE AND MEASURED THERMAL COMFORT IN ITALIAN UNIVERSITY CLASSROOMS IN HEATED AND FREE RUNNING CONDITIONS Stefano Corgnati, Roberta Ansaldi, and Marco Filippi Department of Energy (DENER), Politecnico

More information

Investigation and Analysis of Winter Classroom Thermal Environment. In Chongqing

Investigation and Analysis of Winter Classroom Thermal Environment. In Chongqing ESL-IC-61-8 ICEBO26, Shenzhen, China Investigation and Analysis of Winter Classroom Thermal Environment In Chongqing Jing Liu Baizhan Li Runming Yao Postgraduate Ph.D Ph.D Professor Senior researcher Chongqing,

More information

Shifting Comfort Zone for Hot-Humid Environments

Shifting Comfort Zone for Hot-Humid Environments PLEA6 - The rd Conference on Passive and Low Energy Architecture, Geneva, Switzerland, 6-8 September 6 Shifting Comfort Zone for Hot-Humid Environments Kitchai Jitkhajornwanich Faculty of Architecture,

More information

Findings of Field Survey for Thermal Comfort and Ventilation in US Office Buildings

Findings of Field Survey for Thermal Comfort and Ventilation in US Office Buildings Findings of Field Survey for Thermal Comfort and Ventilation in US Office Buildings Liangcai Tan 1, Samir Moujaes, HDR Inc. University of Nevada Las Vegas SUMMARY This paper presents the measured data

More information

Thermal environment and thermal comfort in a passive residential building in the severe cold area of China

Thermal environment and thermal comfort in a passive residential building in the severe cold area of China Thermal environment and thermal comfort in a passive residential Yuchen Ji Ph D. Candidate Harbin Institute of Technology China 15B927029@hit.edu.cn Professor, Zhaojun Wang, Harbin Institute of Technology,

More information

Thermal Environment evaluation in commercial kitchens

Thermal Environment evaluation in commercial kitchens Downloaded from orbit.dtu.dk on: Nov 11, 2018 Thermal Environment evaluation in commercial kitchens Simone, Angela; Olesen, Bjarne W. Publication date: 2013 Link back to DTU Orbit Citation (APA): Simone,

More information

Air Movement Preference and Thermal Comfort A survey in classrooms during summer season in Brazil

Air Movement Preference and Thermal Comfort A survey in classrooms during summer season in Brazil Air Movement Preference and Thermal Comfort A survey in classrooms during summer season in Brazil CHRISTHINA CÂNDIDO 1,4, RICHARD DE DEAR, ROBERTO LAMBERTS 1, LEONARDO BITTENCOURT 3 1 Federal University

More information

REAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS. Galway, Ireland

REAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS. Galway, Ireland REAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS Magdalena Hajdukiewicz 1,2,3, Padraig O Connor 1, Colin O Neill 1, Daniel Coakley 1,2,3, Marcus M. Keane 1,2,3, Eoghan Clifford 1,2,3 1 Department

More information

The applicability of the ISO 7730 (Fanger's comfort model) and the adaptive model of thermal comfort in Jakarta, Indonesia.

The applicability of the ISO 7730 (Fanger's comfort model) and the adaptive model of thermal comfort in Jakarta, Indonesia. The applicability of the ISO 7730 (Fanger's comfort model) and the adaptive model of thermal comfort in Jakarta, Indonesia Tri Harso Karyono Agency for the Assessment and Application of Technology, Republic

More information

Thermal Comfort Zone for Thai People

Thermal Comfort Zone for Thai People Engineering, 013, 5, 55-59 http://dx.doi.org/10.436/eng.013.5506 Published Online May 013 (http://www.scirp.org/journal/eng) Thermal Comfort Zone for Thai People Juntakan Taweekun *, Ar-U-Wat Tantiwichien

More information

Thermal comfort assessment of Danish occupants exposed to warm environments and preferred local air movement

Thermal comfort assessment of Danish occupants exposed to warm environments and preferred local air movement Downloaded from orbit.dtu.dk on: Mar 08, 2019 Thermal comfort assessment of Danish occupants exposed to warm environments and preferred local air movement Simone, Angela; Yu, Juan ; Levorato, Gabriele

More information

Energy simulation of traditional vs. adaptive thermal comfort for two

Energy simulation of traditional vs. adaptive thermal comfort for two Hensen, J.L.M. & Centnerova, L. (2001). Energy simulation of traditional vs. adaptive thermal comfort for two moderate climate regions. Proceedings of the International conference "Moving Thermal Comfort

More information

BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY. Dr Mirek Piechowski 1, Adrian Rowe 1

BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY. Dr Mirek Piechowski 1, Adrian Rowe 1 BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY Dr Mirek Piechowski 1, Adrian Rowe 1 Meinhardt Building Science Group, Meinhardt Australia 1 Level 12, 501

More information

Energy and Buildings

Energy and Buildings Energy and Buildings 41 (2009) 139 145 Contents lists available at ScienceDirect Energy and Buildings journal homepage: www.elsevier.com/locate/enbuild A comparative analysis of urban and rural residential

More information

ATBU, Journal of Science, Technology & Education (JOSTE); Vol. 3 (4), December, 2015 ISSN:

ATBU, Journal of Science, Technology & Education (JOSTE); Vol. 3 (4), December, 2015 ISSN: THERMAL COMFORT ASSESSMENT OF ENGINEERING WORKSHOP: A CASE STUDY OF UNIVERSITY OF MAIDUGURI By S. Shodiya 1 *, M.B. Oumarou 1, A.T Quadri 2, and A.B. Muhammed 1 1 Department of Mechanical Engineering,

More information

Thermal Environment evaluation in Commercial kitchens: Procedure of data collection

Thermal Environment evaluation in Commercial kitchens: Procedure of data collection Thermal Environment evaluation in Commercial kitchens: Procedure of data collection Angela Simone *, Bjarne W. Olesen ICIEE-BYG, Technical University of Denmark, Kgs. Lyngby, Denmark * email: asi@byg.dtu.dk

More information

Thermal comfort evaluation of natural ventilation mode: case study of a high-rise residential building

Thermal comfort evaluation of natural ventilation mode: case study of a high-rise residential building J. Zuo, L. Daniel, V. Soebarto (eds.), Fifty years later: Revisiting the role of architectural science in design and practice: 50 th International Conference of the Architectural Science Association 2016,

More information

COMFORT MODEL FOR LOCAL COOLING. Yufeng Zhang 1 and Rongyi Zhao 2. Beijing, , P.R. China

COMFORT MODEL FOR LOCAL COOLING. Yufeng Zhang 1 and Rongyi Zhao 2. Beijing, , P.R. China COMFORT MODEL FOR LOCAL COOLING Yufeng Zhang 1 and Rongyi Zhao 2 1 Building Environment Energy Laboratory (BEEL), State Key Laboratory of Subtropical Building Science, South China University of Technology,

More information

STUDIES ON THERMAL COMFORT AND ENERGY CONSUMPTION OF HVAC SYSTEM

STUDIES ON THERMAL COMFORT AND ENERGY CONSUMPTION OF HVAC SYSTEM STUDIES ON THERMAL COMFORT AND ENERGY CONSUMPTION OF HVAC SYSTEM B Liu,*, N Zhu 2, RQ Zhang.Dep. Of Refrigeration, Tianjin University of Commerce, 334, lbtjcu@tjcu.edu.cn 2.Environment School, Tianjin

More information

Energy simulation of traditional vs. adaptive thermal comfort for two moderate climate regions Hensen, J.L.M.; Hensen Centnerová, L.

Energy simulation of traditional vs. adaptive thermal comfort for two moderate climate regions Hensen, J.L.M.; Hensen Centnerová, L. Energy simulation of traditional vs. adaptive thermal comfort for two moderate climate regions Hensen, J.L.M.; Hensen Centnerová, L. Published in: Proceedings int. conf. "Moving Thermal Comfort Standards

More information

Prediction of Thermal Comfort. mech14.weebly.com

Prediction of Thermal Comfort. mech14.weebly.com Prediction of Thermal Comfort Thermal Sensation Scale (Rohles & Nevins, 1974) Fanger s Thermal Comfort Model (1982) Steady state model, applicable for M 3 met and a large group of people Fanger s Thermal

More information

Assessment of thermal comfort in shopping centre transitional spaces

Assessment of thermal comfort in shopping centre transitional spaces Assessment of thermal comfort in shopping centre transitional spaces Marta Avantaggiato 1,2 *, Annamaria Belleri 1, Spencer M. Dutton 3, Wilmer Pasut 1 and Roberto Lollini 1 1 EURAC Research, Institute

More information

AN ASSESSMENT OF THERMAL COMFORT IN NATURALLY VENTILATED ARCHITECTURAL STUDIO IN ABIA STATE UNIVERSITY, UTURU

AN ASSESSMENT OF THERMAL COMFORT IN NATURALLY VENTILATED ARCHITECTURAL STUDIO IN ABIA STATE UNIVERSITY, UTURU International Journal of Advance Studies in Engineering and Scientific Inventions Volume 3 Number 1, JULY 2015. ISSN (Print): 1741-8763 ISSN (Online):1741-8771 AN ASSESSMENT OF THERMAL COMFORT IN NATURALLY

More information

Optimizing Indoor Environments for Occupant Satisfaction. Presented by: Kelli Goldstone April 2016

Optimizing Indoor Environments for Occupant Satisfaction. Presented by: Kelli Goldstone April 2016 Optimizing Indoor Environments for Occupant Satisfaction Presented by: Kelli Goldstone April 2016 Outline Function of HVAC Thermal Comfort Air Distribution Radiant Heating / Cooling Case Study Function

More information

UC Berkeley Indoor Environmental Quality (IEQ)

UC Berkeley Indoor Environmental Quality (IEQ) UC Berkeley Indoor Environmental Quality (IEQ) Title Developing an adaptive model of thermal comfort and preference Permalink https://escholarship.org/uc/item/4qq2p9c6 Authors de Dear, Richard Brager,

More information

Assessing the ability of PMV model in predicting thermal sensation in naturally ventilated buildings in UK

Assessing the ability of PMV model in predicting thermal sensation in naturally ventilated buildings in UK Loughborough University Institutional Repository Assessing the ability of PMV model in predicting thermal sensation in naturally ventilated buildings in UK This item was submitted to Loughborough University's

More information

THERMAL COMFORT OF A COURTYARD IN GUANGZHOU IN SUMMER

THERMAL COMFORT OF A COURTYARD IN GUANGZHOU IN SUMMER THERMAL COMFORT OF A COURTYARD IN GUANGZHOU IN SUMMER L Jin 1,*, QL Meng 1 and LH Zhao 1 1 Building Environment Energy Laboratory, South China University of Technology, Guangzhou 510640, China Engineering

More information

Comparison between thermal comfort predictive models and subjective responses in Italian university classrooms

Comparison between thermal comfort predictive models and subjective responses in Italian university classrooms Comparison between thermal comfort predictive models and subjective responses in Italian university classrooms Roberta Ansaldi 1, Stefano Paolo Corgnati 1 and Marco Filippi 1 1 Department of Energy (DENER),

More information

An Assessment of Thermal Comfort in Hot and Dry Season (A Case Study of 4 Theaters at Bayero University Kano)

An Assessment of Thermal Comfort in Hot and Dry Season (A Case Study of 4 Theaters at Bayero University Kano) International Journal of Multidisciplinary and Current Research Research Article ISSN: - Available at: http://ijmcr.com An Assessment of Thermal Comfort in Hot and Dry Season (A Case Study of Theaters

More information

Available online at ScienceDirect. Procedia Engineering 169 (2016 )

Available online at   ScienceDirect. Procedia Engineering 169 (2016 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 169 (2016 ) 158 165 4th International Conference on Countermeasures to Urban Heat Island (UHI) 2016 Indoor Thermal Comfort Assessment

More information

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Available online at   ScienceDirect. Procedia Engineering 121 (2015 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 121 (2015 ) 1990 1997 9th International Symposium on Heating, Ventilation and Air Conditioning (ISHVAC) and the 3rd International

More information

Designing Air-Distribution Systems To Maximize Comfort

Designing Air-Distribution Systems To Maximize Comfort Designing Air-Distribution Systems To Maximize Comfort By David A. John, P.E., Member ASHRAE An air-distribution system that provides occupant thermal comfort can be a complicated system to predict and

More information

Evaluation methods for indoor environmental quality assessment according to EN15251

Evaluation methods for indoor environmental quality assessment according to EN15251 Summary of this article was published in the REHVA European HVAC Journal Vol 49, Issue 4 (August), 2012, pages 14-19, available at http://www.rehva.eu/en/rehva-european-hvac-journal. Evaluation methods

More information

Allowing for Thermal Comfort in Free-running Buildings in the New European Standard EN15251

Allowing for Thermal Comfort in Free-running Buildings in the New European Standard EN15251 Allowing for Thermal Comfort in Free-running Buildings in the New European Standard EN15251 Fergus Nicol, Low Energy Architecture Research Unit (LEARN), School of Architecture, London Metropolitan University,

More information

INVESTIGATING THE EFFECT OF CO 2 CONCENTRATION ON REPORTED THERMAL COMFORT

INVESTIGATING THE EFFECT OF CO 2 CONCENTRATION ON REPORTED THERMAL COMFORT INVESTIGATING THE EFFECT OF CO 2 CONCENTRATION ON REPORTED THERMAL COMFORT S. Gauthier 1 ; B. Liu 2 ; G. Huebner 2 ; D. Shipworth 2 1: University of Southampton, Highfield, Southampton, SO17 1BJ, UK. 2:

More information

Thermal comfort recent challenges

Thermal comfort recent challenges Thermal comfort recent challenges Quality and compliance - Thermal comfort and indoor air quality 19 November 2013 Bjarne OLESEN International Centre for Indoor Environment and Energy Technical University

More information

An Employee Thermal Comfort Model for Semiconductor Manufacturing

An Employee Thermal Comfort Model for Semiconductor Manufacturing An Employee Thermal Comfort Model for Semiconductor Manufacturing Author Information Robbie Walls Corporate Ergonomist Intel Corporation MS CH10-22 5000 W. Chandler Blvd. Chandler, AZ 85226 Phone: (480)

More information

Radiant Floor Cooling Combined with Mixing Ventilation in a Residential Room Thermal Comfort and Ventilation Effectiveness

Radiant Floor Cooling Combined with Mixing Ventilation in a Residential Room Thermal Comfort and Ventilation Effectiveness Downloaded from orbit.dtu.dk on: Apr 09, 2019 Radiant Floor Cooling Combined with Mixing Ventilation in a Residential Room Thermal Comfort and Ventilation Effectiveness Krajcik, Michal; Simone, Angela;

More information

Assessment of thermal comfort near a glazed exterior wall

Assessment of thermal comfort near a glazed exterior wall Assessment of thermal comfort near a glazed exterior wall Timothy Anderson 1, Mark Luther 2 and Tim Brain 3 1 School of Engineering, Auckland University of Technology, Auckland 1142, New Zealand 2 School

More information

Micheal Okpara University of Agriculture Umudike. Abstract

Micheal Okpara University of Agriculture Umudike. Abstract International Journal of Scientific & Engineering Research, Volume 6, Issue 10, October-2015 1531 IMPACT OF AIR TEMPERATURE IN THERMAL COMFORT OF INDOORS OF RESIDENTIAL BUILDINGS IN UMUAHIA URBAN ABIA

More information

FIELD MEASUREMENT OF A RESIDENTIAL FLOOR COOLING SYSTEM AND EVALUATION OF HUMAN THERMAL COMFORT

FIELD MEASUREMENT OF A RESIDENTIAL FLOOR COOLING SYSTEM AND EVALUATION OF HUMAN THERMAL COMFORT Engineering Review, Vol. 35, Issue 1, 69-79, 015. 69 FIELD MEASUREMENT OF A RESIDENTIAL FLOOR COOLING SYSTEM AND EVALUATION OF HUMAN THERMAL COMFORT X. M. Sui 1* X. Zhang 1 School of Environmental Science

More information

Thermal Comfort Evaluation of HDB flats

Thermal Comfort Evaluation of HDB flats Thermal Comfort Evaluation of HDB flats Objective Measurements For this study, empirical data on the thermal comfort parameters (i.e. room space temperature, velocity and relative humidity) was collected

More information

A Thermal Comfort Investigation of a Facility Department of a Hospital in Hot-Humid Climate: Correlation between Objective and Subjective Measurements

A Thermal Comfort Investigation of a Facility Department of a Hospital in Hot-Humid Climate: Correlation between Objective and Subjective Measurements Case Study Paper Indoor and Built Indoor Built Environ 2013;22;5:836 845 Accepted: August 12, 2012 Environment A Thermal Comfort Investigation of a Facility Department of a Hospital in Hot-Humid Climate:

More information

Thermal comfort and occupant adaptive behaviour in university offices with cooling and free running modes

Thermal comfort and occupant adaptive behaviour in university offices with cooling and free running modes Thermal comfort and occupant adaptive behaviour in university offices with cooling and free running modes Mohd Sabri Mustapa 1, Sheikh Ahmad Zaki Shaikh Salim 2, Aya Hagishima 3 and Mohamed Sukri Mat Ali

More information

Research of Thermal Comfort for Side Air Supply Pattern in Office

Research of Thermal Comfort for Side Air Supply Pattern in Office IOP Conference Series: Earth and Environmental Science PAPER OPEN ACCESS Research of Thermal Comfort for Side Air Supply Pattern in Office To cite this article: Wenhong Yu et al 2018 IOP Conf. Ser.: Earth

More information

GREEN CONCEPT OF THERMAL COMFORT DESIGN FOR SUSTAINABLE HOUSING IN THE TROPICS: Learning from Thermal Comfort in School Buildings 1 INTRODUCTION

GREEN CONCEPT OF THERMAL COMFORT DESIGN FOR SUSTAINABLE HOUSING IN THE TROPICS: Learning from Thermal Comfort in School Buildings 1 INTRODUCTION Abstract GREEN CONCEPT OF THERMAL COMFORT DESIGN FOR SUSTAINABLE HOUSING IN THE TROPICS: Learning from Thermal Comfort in School Buildings Baharuddin Hamzah Department of Architecture, Hasanuddin University,

More information

Adaptive Thermal Comfort in Warm Dry Climate: Economical dwellings in Mexico

Adaptive Thermal Comfort in Warm Dry Climate: Economical dwellings in Mexico Adaptive Thermal Comfort in Warm Dry Climate: Economical dwellings in Mexico MARINCIC, I. 1 ; OCHOA, J. M. 1 ; ALPUCHE, M.G. 1 AND GÓMEZ-AZPEITIA, G. 2 1 Dpt. Architecture, University of Sonora, Hermosillo,

More information

Comfort models as applied to buildings

Comfort models as applied to buildings R.H. Crawford and A. Stephan (eds.), Living and Learning: Research for a Better Built Environment: 49 th International Conference of the Architectural Science Association 2015, pp.1087 1096. 2015, The

More information

Thermal Comfort Assessment Based on Measurement and Questionnaire Surveys in a Large Mechanically Ventilated Space

Thermal Comfort Assessment Based on Measurement and Questionnaire Surveys in a Large Mechanically Ventilated Space Thermal Comfort Assessment Based on Measurement and Questionnaire Surveys in a Large Mechanically Ventilated Space Ali Alzaid 1, Maria Kolokotroni 1, Hazim Awbi 2 1 Mechanical Engineering, Brunel University

More information

Adaptive thermal comfort explained by PMV

Adaptive thermal comfort explained by PMV Adaptive thermal comfort explained by PMV Willemijne van der Linden, Marcel Loomans * and Jan Hensen Eindhoven University of Technology, Department of Architecture Building and Planning, Unit Building

More information

COMFORT IN AUSTRALIAN OFFICES

COMFORT IN AUSTRALIAN OFFICES F. Madeo and M. A. Schnabel (eds.), Across: Architectural Research through to Practice: 48 th International Conference of the Architectural Science Association 2014, pp. 643 653. 2014, The Architectural

More information

THERMAL COMFORT IN LECTURE HALLS IN THE TROPICS

THERMAL COMFORT IN LECTURE HALLS IN THE TROPICS Topic 2. Indoor environment THERMAL COMFORT IN LECTURE HALLS IN THE TROPICS Yat Huang Yau *, Bee Teng Chew, Aza Saifullah Department of Mechanical Engineering, University of Malaya, 50603 Kuala Lumpur,

More information

Numerical Investigation on Ventilation Strategy for Laboratories: A Novel Approach to Control Thermal Comfort Using Cooling Panels

Numerical Investigation on Ventilation Strategy for Laboratories: A Novel Approach to Control Thermal Comfort Using Cooling Panels Numerical Investigation on Ventilation Strategy for Laboratories: A Novel Approach to Control Thermal Comfort Using Cooling Panels Farhad Memarzadeh 1, Andy Manning 2 and Zheng Jiang 2 1 National Institutes

More information

Thermal Comfort in Architecture

Thermal Comfort in Architecture Thermal Comfort in Architecture Ommid Saberi [1], Parisa Saneei [2] Amir Javanbakht [3] 1. Ph.D. Student (Architecture & Energy) in Shahid Beheshti Uni. Tehran Iran e: omid_saberi@yahoo.com 2. Architect

More information

Thermal comfort under transient seasonal conditions of a bioclimatic building in Greece

Thermal comfort under transient seasonal conditions of a bioclimatic building in Greece 54 2nd PALENC Conference and 28th AIVC Conference on Building Low Energy Cooling and Thermal comfort under transient seasonal conditions of a bioclimatic building in Greece A. Androutsopoulos Centre for

More information

Human response to individually controlled micro environment generated with localized chilled beam

Human response to individually controlled micro environment generated with localized chilled beam Downloaded from orbit.dtu.dk on: Jan 31, 2019 Human response to individually controlled micro environment generated with localized chilled beam Uth, Simon C. ; Nygaard, Linette; Bolashikov, Zhecho Dimitrov;

More information

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya (vahid.vakiloroaya@engineer.com) ABSTRACT: The overall attainable reduction in energy consumption and enhancement of

More information

Impacts of Indoor Temperature and Velocity on Human Physiology in Hot Summer and Cold Winter Climate in China

Impacts of Indoor Temperature and Velocity on Human Physiology in Hot Summer and Cold Winter Climate in China Impacts of Indoor Temperature and Velocity on Human Physiology in Hot Summer and Cold Winter Climate in China Hong Liu 1, Baizhan Li 1, Liang Chen 1, Lu Chen 1, Jing Wu 1, Jie Zheng 1, Wenjie Li 1, Runming

More information

Indoor comfort and air quality in spaces equipped with eco-ventilation systems

Indoor comfort and air quality in spaces equipped with eco-ventilation systems ICUC9-9 th International Conference on Urban Climate jointly with th Symposium on the Urban Environment Indoor comfort and air quality in spaces equipped with eco-ventilation systems Eusébio Z. E. Conceição,

More information

Retrofitting Adaptive Comfort Strategies into Conventionally Air Conditioned Commercial Buildings

Retrofitting Adaptive Comfort Strategies into Conventionally Air Conditioned Commercial Buildings Retrofitting Adaptive Comfort Strategies into Conventionally Air Conditioned Commercial Buildings Hisham Allam 1 The University Of Sydney SUMMARY Reducing the temperature difference between indoor HVAC

More information

Towards Adaptive PMV/PPD Indices for European Climates

Towards Adaptive PMV/PPD Indices for European Climates Towards Adaptive PMV/PPD Indices for European Climates Laurent Grignon-Massé, Jérôme Adnot, and Philippe Rivière, Ecole des Mines de Paris ABSTRACT There are currently two main standards relative to indoor

More information

PERSONAL COOLING USING THERMAL CONDUCTION ON THE DESK

PERSONAL COOLING USING THERMAL CONDUCTION ON THE DESK PERSONAL COOLING USING THERMAL CONDUCTION ON THE DESK J. Verhaart 1 ; R. Keune 1 ; M. Veselý 1 ; R. Li 1, W. Zeiler 1. 1: Dep. of the Built Environment, Rondom 70, 5612 AP, P.O. Box 513, 5600 MB Eindhoven,

More information

Perception of Thermal Comfort for Naturally Ventilated High School Classrooms in San Rafael, CA

Perception of Thermal Comfort for Naturally Ventilated High School Classrooms in San Rafael, CA Perception of Thermal Comfort for Naturally Ventilated High School Classrooms in San Rafael, CA GWENEDD MURRAY 1 1 Architectural Association, Inc., London, United Kingdom ABSTRACT: The primary intention

More information

Experimental investigation on a ceiling capillary radiant heating system

Experimental investigation on a ceiling capillary radiant heating system Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (2015 ) 1380 1386 The 7 th International Conference on Applied Energy ICAE2015 Experimental investigation on a ceiling capillary

More information

Thermal Comfort and Energy Consumption according to the Indoor Control Logic

Thermal Comfort and Energy Consumption according to the Indoor Control Logic Thermal Comfort and Energy Consumption according to the Indoor Control Logic S. Kim 1 and D. Song 2 1 Department of Civil and Environmental System Engineering Sungkyunkwan University, Suwon-si, Gyeonggi-do

More information

IMPACT OF THE AIRFLOW INTERACTION ON OCCUPANTS THERMAL COMFORT IN ROOMS WITH ACTIVE CHILLED BEAMS

IMPACT OF THE AIRFLOW INTERACTION ON OCCUPANTS THERMAL COMFORT IN ROOMS WITH ACTIVE CHILLED BEAMS IMPACT OF THE AIRFLO INTERACTION ON OCCUPANTS THERMAL COMFORT IN ROOMS ITH ACTIVE CHILLED BEAMS Arsen Melikov 1, Boryana Yordanova 1, Lyuben Bozkhov 1, Viktor Zboril 1,2, and Risto Kosonen 3 1 International

More information

Neutral humidity in low cost dwellings in arid climate

Neutral humidity in low cost dwellings in arid climate PLEA0-8th Conference, Opportunities, Limits & Needs Towards an environmentally responsible architecture Lima, Perú -9 November 0 Neutral humidity in low cost dwellings in arid climate LUIS CARLOS HERRERA,

More information

Artificial Neural Network Models Using Thermal Sensations and Occupants Behavior for Predicting Thermal Comfort

Artificial Neural Network Models Using Thermal Sensations and Occupants Behavior for Predicting Thermal Comfort Deng, Z. and Chen, Q. 2018. Artificial neural network models using thermal sensations and occupants behavior for predicting thermal comfort, Energy and Buildings. 174: 587-602. 1 2 3 4 5 6 7 8 9 10 11

More information

Analysis of the Window Side Thermal Environment Formed by Air Barrier. Technique in Winter Conditions and Its Economy

Analysis of the Window Side Thermal Environment Formed by Air Barrier. Technique in Winter Conditions and Its Economy Analysis of the Window Side Thermal Environment Formed by Air Barrier Technique in Winter Conditions and Its Economy Chen Huang 1 Yufeng Jia 1 Lan Liu 2 Xin Wang 1 Professor Post Graduate Senior Engineer

More information

Performance Investigation of Building Ventilation System by Calculating Comfort Criteria through HVAC Simulation

Performance Investigation of Building Ventilation System by Calculating Comfort Criteria through HVAC Simulation IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) ISSN: 2278-1684Volume 3, Issue 6 (Nov. - Dec. 2012), PP 07-12 Performance Investigation of Building Ventilation System by Calculating Comfort

More information

CLIMATE CONTROL: INTENT/CRITERIA

CLIMATE CONTROL: INTENT/CRITERIA CLIMATE CONTROL: INTENT/CRITERIA This lecture is a review/restatement of information from ARCH 273. Thermal comfort and indoor air quality (coming up) are critical foundations for HVAC system design. Ball

More information

Bio Climatic Analysis of Bhubaneswar-An Investigation to Arrive Human Comfort through Natural Ventilation

Bio Climatic Analysis of Bhubaneswar-An Investigation to Arrive Human Comfort through Natural Ventilation International Journal of Scientific and Research Publications, Volume 6, Issue 5, May 2016 557 Bio Climatic Analysis of Bhubaneswar-An Investigation to Arrive Human Comfort through Natural Ventilation

More information

VARIABILITY OF THERMAL STRATIFICATION IN NATURALLY VENTILATED RESIDENTIAL BUILDINGS. Stephanie Gauthier 1, David Shipworth 1

VARIABILITY OF THERMAL STRATIFICATION IN NATURALLY VENTILATED RESIDENTIAL BUILDINGS. Stephanie Gauthier 1, David Shipworth 1 1 2 3 4 5 6 7 8 9 10 VARIABILITY OF THERMAL STRATIFICATION IN NATURALLY VENTILATED RESIDENTIAL BUILDINGS ABSTRACT Stephanie Gauthier 1, David Shipworth 1 1 UCL Energy Institute, London, United-Kingdom

More information

Work environment. Microclimate - definition. Main microclimate elements. Core temperature. Microclimate

Work environment. Microclimate - definition. Main microclimate elements. Core temperature. Microclimate Microclimate - definition Work environment Microclimate A local atmospheric zone where the climate differs from the surrounding area A small-scale site of special conditions within a larger climate Can

More information

ADAPTIVE THERMAL COMFORT IN THE WET TROPICS FOR HOUSING DESIGN WITH PASSIVE COOLING

ADAPTIVE THERMAL COMFORT IN THE WET TROPICS FOR HOUSING DESIGN WITH PASSIVE COOLING 74 International Journal on Design and Manufacturing Technologies, Vol.2, No.1, July 2008 ADAPTIVE THERMAL COMFORT IN THE WET TROPICS FOR HOUSING DESIGN WITH PASSIVE COOLING 1 2 3 Djamila Harimi, Narayanan

More information

Field Study of Air Conditioning and Thermal Comfort in Residential Buildings

Field Study of Air Conditioning and Thermal Comfort in Residential Buildings Proceedings of 9 th Windsor Conference: Making Comfort Relevant Cumberland Lodge, Windsor, UK, 7-10 April 2016. Network for Comfort and Energy Use in Buildings, http://nceub.org.uk Field Study of Air Conditioning

More information

Thermal Comfort Evaluation of a Heat Pump System using Induced-air Supply Unit

Thermal Comfort Evaluation of a Heat Pump System using Induced-air Supply Unit Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Thermal Comfort Evaluation of a Heat Pump System using Induced-air Supply

More information

Assessment of thermal comfort inside primary governmental classrooms in hot-dry climates Part II a case study from Egypt

Assessment of thermal comfort inside primary governmental classrooms in hot-dry climates Part II a case study from Egypt Assessment of thermal comfort inside primary governmental classrooms in hot-dry climates Part II a case study from Egypt Tamer Gado 1, Mady Mohamed 2 1 University of Dundee, UK 2 Zagazig University, Egypt

More information

Sustainable Designed Air-Conditioned Mosque For Thermal Comfort

Sustainable Designed Air-Conditioned Mosque For Thermal Comfort Sustainable Designed Air-Conditioned Mosque For Thermal Comfort Presented by Prof. Dr. Essam E. Khalil, Fellow ASHRAE, Fellow ASME, Fellow AIAA Professor of Mechanical Power Engineering Prepared by Redhwan

More information

Thermal Comfort Model for Educational Institutions in Kerala

Thermal Comfort Model for Educational Institutions in Kerala IJIRST International Journal for Innovative Research in Science & Technology Volume 3 Issue 11 April 2017 ISSN (online): 2349-6010 Thermal Comfort Model for Educational Institutions in Kerala Vishal T.

More information

CLIMATE CONTROL: OPR

CLIMATE CONTROL: OPR CLIMATE CONTROL: OPR A review/restatement of information from ARCH 273. Thermal comfort and indoor air quality (coming up) are critical foundations for active climate control (HVAC system) design. OPR

More information

Thermal Comfort Survey in Office Buildings in Bandung, Indonesia

Thermal Comfort Survey in Office Buildings in Bandung, Indonesia Thermal Comfort Survey in Office Buildings in Bandung, Indonesia S.A. Damiati 1, S.A. Zaki 2*, S. Wonorahardjo 3, M.S. Mat Ali 2, H.B. Rijal 4 1 Malaysia-Japan International Institute of Technology, Universiti

More information

Evaluation of Thermal Comfort of Men and Women in Food Courts

Evaluation of Thermal Comfort of Men and Women in Food Courts International Journal of Science and Engineering Investigations vol. 6, issue 65, June 2017 ISSN: 2251-8843 Evaluation of Thermal Comfort of Men and Women in Food Courts ejane MartinsViegas 1, Wagner Augusto

More information

ADAPTIVE THERMAL COMFORT - AN EXTENDED APPROACH FOR CONDITIONED INDOOR ENVIRONMENT USING COMPUTATIONAL FLUID DYNAMICS

ADAPTIVE THERMAL COMFORT - AN EXTENDED APPROACH FOR CONDITIONED INDOOR ENVIRONMENT USING COMPUTATIONAL FLUID DYNAMICS 16 th International Conference on Clean Energy (ICCE-2018) 9-11 May 2018, Famagusta, N. Cyprus ADAPTIVE THERMAL COMFORT - AN EXTENDED APPROACH FOR CONDITIONED INDOOR ENVIRONMENT USING COMPUTATIONAL FLUID

More information

UC Berkeley Indoor Environmental Quality (IEQ)

UC Berkeley Indoor Environmental Quality (IEQ) UC Berkeley Indoor Environmental Quality (IEQ) Title Percentage of commercial buildings showing at least 80% occupant satisfied with their thermal comfort Permalink https://escholarship.org/uc/item/89m0z34x

More information

Field Investigation of Comfort Temperature and Adaptive Model in Japanese Houses

Field Investigation of Comfort Temperature and Adaptive Model in Japanese Houses PLEA2013-29th Conference, Sustainable Architecture for a Renewable Future, Munich, Germany 10-12 September 2013 Field Investigation of Comfort Temperature and Adaptive Model in Japanese Houses HOM BAHADUR

More information

Indoor climate The adaptive approach to thermal comfort

Indoor climate The adaptive approach to thermal comfort Bachelor of Architectural technology and Construction management Indoor climate The adaptive approach to thermal comfort 7 th semester dissertation academic report Author : Tudor Mihai Panaitescu Consultant:

More information

COMPUTER MODELING OF UNDERFLOOR AIR SUPPLY SYSTEM

COMPUTER MODELING OF UNDERFLOOR AIR SUPPLY SYSTEM COMPUTER MODELING OF UNDERFLOOR AIR SUPPLY SYSTEM JJ Kim, JD Chang, and JC Park Taubman College of Architecture and Urban Planning, University of Michigan, Ann Arbor, MI, USA ABSTRACT An underfloor air

More information

Designing for thermal comfort near a glazed exterior wall. * School of Engineering, Auckland University of Technology, Auckland, New Zealand

Designing for thermal comfort near a glazed exterior wall. * School of Engineering, Auckland University of Technology, Auckland, New Zealand Designing for thermal comfort near a glazed exterior wall T.N. Anderson ǂ *, M.B. Luther ** * School of Engineering, Auckland University of Technology, Auckland, New Zealand ** School of Architecture and

More information

Assessment of Indoor Climate: Learning from Buildings

Assessment of Indoor Climate: Learning from Buildings Roomvent 27: 1 th International Conference on Helsinki, June 1-15, 27 Assessment of Indoor Climate: Learning from Buildings Outdoor climate Edward Arens Center for the Built Environment UC Berkeley Indoor

More information

Development of the adaptive model for thermal comfort in Japanese houses

Development of the adaptive model for thermal comfort in Japanese houses Proceedings of 8 th Windsor Conference: Counting the Cost of Comfort in a changing world Cumberland Lodge, Windsor, UK, 10-13 April 2014. London: Network for Comfort and Energy Use in Buildings, http://nceub.org.uk

More information