ASSESSMENT OF AIR CHANGE RATE AND CONTRIBUTION RATIO IN IDEALIZED URBAN CANOPY LAYERS BY TRACER GAS SIMULATIONS

Size: px
Start display at page:

Download "ASSESSMENT OF AIR CHANGE RATE AND CONTRIBUTION RATIO IN IDEALIZED URBAN CANOPY LAYERS BY TRACER GAS SIMULATIONS"

Transcription

1 Topic B4: Ventilation ASSESSMENT OF AIR CHANGE RATE AND CONTRIBUTION RATIO IN IDEALIZED URBAN CANOPY LAYERS BY TRACER GAS SIMULATIONS Qun WANG 1, Mats SANDBERG 2, Jian HANG 1* 1 Department of Atmospheric Sciences, School of Environmental Science and Engineering of Sun Yat-Sen University, Guangzhou, P. R. China 2 Laboratory of Ventilation and Air Quality, University of Gävle, SE Gävle, Sweden *Corresponding hangj3@mail.sysu.edu.cn Keywords: Air change rate per hour (ACH), Concentration decay method, Urban canopy layer (UCL), Contribution ratio, Computational fluid dynamics (CFD) simulations SUMMARY This paper first performed CFD simulations with the concentration decay method to investigate air change rate per hour in entire urban canopy layers (UCL) under neutral atmospheric condition (building packing density p =0.25, frontal area density f =0.25, aspect ratio H/W=1). Two approaches are included. One is the normal way (ACH 1 ), the other (ACH 2 ) fixes concentration out of the UCL volume to be zero in CFD, i.e. no tracer gas reentry. ACH 2 with a quicker concentration decay always exceeds ACH 1. With a parallel approaching wind (θ=0 o ), the larger urban size (Lx=390m to 2940m), the lower ACH is. For 5-row and 5-column UCL model (Lx=Ly=270m), θ=0 o attains greater ACH than θ=15 o, 30 o, 45 o. Both ACH 1 and ACH 2 are less than the sum of ACH induced by mean flows and turbulence across UCL boundaries. Then the contribution ratio was numerically predicted to quantify the transfer of pollutants between different urban spaces of a UCL. INTRODUCTION Besides pollutant source control, urban canopy layer (UCL) ventilation by rural/ marine/mountain wind can help reducing urban air pollution and urban heat island intensity. Tracer gas techniques have been widely used to measure ventilation indices in indoor environments(chen, 2009) to evaluate how external air enters a room and ventilates it. How to quantify UCL ventilation? In recent years, researchers have started to apply similar tracer gas simulations to estimate UCL ventilation, including volumetric flow rate and air change rate per hour (Liu et al., 2005; Hang and Li, 2010), pollutant retention time and purging flow rate (Bady et al., 2008), age of air and air exchange efficiency (Hang et al., 2009) etc. The application of these

2 ventilation indices assumes that the surrounding air is relatively clean and cool, which can be transported into UCL to help pollutant dilution and heat removal. Air change rate per hour (ACH) is one of the key ventilation indexes, which represents the volumetric air exchange rate of the entire UCL volume per hour. It was initially used for 2D street canyon ventilation (Liu et al.,2005), then was extended for 3D UCL ventilation (Hang and Li, 2010). These literatures confirmed that both mean flows and turbulence across UCL boundaries contribute to UCL ventilation, and ACH index induced by them are usually calculated separately. It is still unclear that, how to calculate ACH index produced by the net effect of both mean flows and turbulence. The concentration decay method has been widely used to measure air change rate in rooms(etheridge and Sandberg, 1996; Chen, 2009). Thus this paper aims to introduce this tracer gas technique into CFD simulations and numerically predict air change rates in various UCL models. Another question is how to quantify the pollutant transport and correlation of air pollution between different urban spaces within a UCL. Thus the contribution ratio between different urban spaces is analyzed by using CFD simulations, in which a uniform pollutant source is defined within a given urban space and the mass fraction of pollutants entering other spaces was analyzed. METHODOLOGIES We define the urban canopy layer (UCL) as the air volume surrounded by street openings and street roofs. In CFD simulations, full-scale UCL models are investigated in which building width (B), building height (H) and street width (W) are the same constant of 30m (see Fig. 1). Key urban parameters include building area density p =0.25, frontal area density f =0.25, street aspect ratio H/W=1. Two groups of UCL models are investigated. As summarized in Table 1, all test cases are named as Case "[row number-column number, wind direction θ]". The row and column numbers are referred to the numbers of the main and secondary streets. For Group I (see Table 1 and Fig. 1a), the approaching wind (θ=0 o ) is parallel to the main streets with a length of Lx and the column number is defined as "N", which denotes that the lateral urban size (Ly) is sufficiently large to disregard the influence of lateral boundaries of UCL models. For Group II (see Table 1 and Fig. 1b), the lateral UCL boundaries are taken into account under a neutral atmospheric condition with parallel (0 ) or non-parallel (θ=15,30,45 ) approaching winds. The CFD code FLUENT 6.3 was used to solve the steady-state isothermal flow field. The standard k-ε model was used to simulate the turbulence effects. All transport equations were discretized by the second order upwind scheme. The hexahedral cells of 1.0 to 2.9 million are produced, and the minimum of grid size is 0.5m near street ground and building surfaces with an expansion ratio of 1.15 toward the surrounding. The SIMPLE scheme was used for the pressure and velocity coupling. To quantify UCL ventilation performance, the concentration decay method is applied to calculate volumetric air exchange rate per hour (ACH) in the entire UCL, in which a uniform

3 Y(m) y (m) UCL initial pollutant concentration is defined at time t=0s (C(0)=10-5 kg/kg or 10 ppm, see Fig. 1), then its decay history (C(t)/C(0)) is analyzed. The time step is 1s. The decay duration of all test cases is nearly 400s. Two CFD setups are defined in the decay method. One is the normal way (ACH 1 ) to solve concentration field without the above assumption, thus tracer gas concentration is not zero outside UCL volume and tracer gas reentry into UCL volume occurs; The other (ACH 2 ) fixes tracer gas concentration out of the UCL volume to be always zero in CFD, assuming that tracer gas leaving UCL volume never come back (i.e. no tracer gas reentry). To quantify the correlation of pollutant transport between different urban units within a UCL(see Fig. 1c), a uniform tracer gas source with an emission rate of 10-5 kg m -3 s -1 is defined in only one unit (for example, unit B11), then the mass fraction of tracer gas in each unit is calculated as contribution ratio. ( ) 3.0( z U ) 0 z H 0.16 y z x H B W=B B H=W=B=30 m in full-scale CFD simulation of Case [7-N, 0] W=B Pollutant concentration within entire urban canopy layer is C(0)=10-7 kg/kg at initial state (t=0 s). Concentration decay method is used to calculate ACH 300 Stream-wise urban size Lx = 270 m 250 θ o (c) Figure 1. CFD model and definition of initial state in concentration decay method Table 1 Test cases investigated ( p = f =0.25, H/W=1) Case name (Group I) Number of rows /total length Lx Number of columns /total length in Ly [7-N,0] 7 row, Lx=390m N or Ly is sufficiently large [14-N, 0] 14 row, Lx=810m to neglect the lateral [21-N, 0] 21 row, Lx=1230m boundary effect as the [28-N,0] [35-N,0] 28 row, Lx=1650m 35 row, Lx=2070m approaching wind is parallel to main streets [42-N,0] [49-N,0] 42 row, Lx=2490m 49 row, Lx=2910m X(m) x(m) Uniform source B11 (emission rate 10-5 kg/m 3 -s) [5-5,0] [5-5,15] 5 rows 5 columns 15 o [5-5,30] Lx=270m Ly=270m 30 o [5-5,45] 45 o θ o B14 B24 B34 B13 B12 B11 B23 B22 B21 B33 B32 B31 B44 B43 B42 B41 Wind direction 0 o 0 o Lateral urban size Ly = 270 m

4 z / H z / H RESULTS AND DISCUSSION Validation of CFD Simulations using Wind Tunnel Data Brown et al. (2001) performed a detailed wind-tunnel experiment of 7-row and 11-column cube array with a parallel approaching wind (see Fig. 2a, B=H=W=15cm, Lx=13H, Ly=21H). The scale ratio to full-scale model is 1:200. Point Vi represents the centre point of the secondary street No i for the middle column (see Fig. 2a). Vertical profiles of mean stream-wise velocity uz, ( ) mean vertical velocity wz () at these points were measured. Hang and Li (2010) confirmed that the lateral urban boundaries hardly affect airflows in the middle column (see Fig. 2a) since the lateral size is sufficiently large (Ly=21H). Using similar technique, this paper uses these wind tunnel data to estimate the accuracy of CFD simulations. All CFD arrangements on domain sizes, grid sizes and boundary conditions fulfill the major requirements as recommended by Tominaga et al. (2008). Fig.2b shows uz ( ) and wz () at V1 as two examples. Obviously standard k model predicts mean flows better than RNG k model. Thus standard k model is selected for the following CFD simulations Vertical profiles at Point V1(x/H=1.5) Wind tunnel data CFD results using Standard k- model RNG k- model y W H=B=15cm B W=B uz ( ) V1 V2 V3 V4 V5 V6 0.5 Wind V1 x Wind x/h 0.0 x/h= Stream-wise velocity (m/s) 3.0 Vertical profiles at Point V1(x/H=1.5) Wind tunnel data 2.5 CFD results using Standard k- model RNG k- model Wind V0 V1 V2 V3 V4 V5 V wz () x/h=-0.5 x/h=1.5 x/h=3.5 x/h=5.5 x/h=7.5 x/h=9.5 x/h=11.5 x Vertical velocity (m/s) Figure 2. Wind tunnel model description and vertical profiles of CFD results and experimental data at Point V1. Characteristics of flow pattern and concentration decay process The decaying concentration is associated with turbulent airflow pattern. To verify this correlation, Fig. 3 shows 3D streamline and concentration field at time of 38s and 138s in Case [5-5, 0]. The flow is channeled toward downstream regions, and 3D

5 vortices and helical flows exist behind each buildings. Across the lateral boundary of cube array (at y=135m), there are lateral helical airflows leaving or re-entering across lateral UCL boundary. Thus tracer gas concentration decreases more quickly in upstream regions than downstream regions, and that near lateral boundary than near urban centre regions. It shows that the downstream and urban centre regions experience a worse ventilation performance. Two concentration decay methods are compared, including the normal way (ACH 1, see Fig. 3a-3b) with tracer gas reentry, and the second method (ACH 2, see Fig. 3c-3d) assuming that tracer gas leaving UCL volume never comes back. Obviously the second one (see Fig. 3c-3d) attains a quicker concentration decay process than the first (see Fig. 3a-3b). (c) (d) (e) Figure 3. Concentration field at time of 38s,138s in Case [5-5, 0]: (a-b) the method for ACH 1, (c-d) the method for ACH 2 without tracer gas reentry, (e) 3D streamline.

6 Air change rate per hour (ACH) Analysis of air change rates by various methods Air change rate per hour (ACH) is used to quantify the volumetric air exchange rate of the entire UCL volume per hour. ACH was initially used for 2D street canyon ventilation (Liu et al.,2005), then was extended for 3D UCL ventilation (Hang and Li, 2010). Both mean flows and turbulence contribute to UCL ventilation. In Eq. (1), ACH calculated by total mean flow rates (Q T ), by effective flow rated induced by turbulence fluctuations across street roofs (Q roof (turb)) are defined as below. ACH T =3600Q T /Vol ACH turb =3600Q roof (turb)/vol (1a) (1b) where Vol is the entire UCL volume. Fig. 4a shows air change rates calculated by flow rates across UCL boundaries (ACH T, ACH turb ), and by the concentration decay methods (ACH 1, ACH 2 ) in Case [5-5, θ] (θ=0,15,30,45 ). Here we pay more concern about the difference with and without tracer gas reentry. Note that, for ACH 2, the tracer gas concentration out of UCL volume is set as 0 ppm without tracer gas reentry. ACH 2 is found a little greater than ACH 1 with tracer gas re-entry. To investigated the effect of urban size under a parallel approaching wind, Fig. 4b shows air change rates in test cases of Case [i-n,0] (i=7,14,21,28,35,49, urban size Lx=390 to 2910m) with a parallel wind. Obviously as urban size rises, ACH T, ACH 1, ACH 2 all decrease, but ACH turb change little. ACH 2 still exceeds ACH 1 with tracer gas re-entry. Finally both Fig. 4a and 4b confirm that, ACH 1 and ACH 2 are always less than the sum of ACH T and ACH turb. It verifies that there is an issue of ventilation efficiency by mean flows and turbulence. Air change rate per hour (ACH) In Case [5-5, o ] 'air change rate per hour (ACH)' Calculated by flow rates across UCL boundaries ACH T ACH roof (turb) Calculated by concentration decay method ACH 1 (with tracer gas reentry) ACH 2 θ o Urban size in x direction Lx (N rows) Ly (M columns) Wind direction of o ACH turb ACH T ACH 2 ACH 1 with re-entry Total street length Lx ACH roof (turb) ACH2 ACH1 5 In Case [i-n,0] (i=7,14,21,28,35,49) ACH T ACH roof (turb) ACH T ACH 0 1 with tracer gas re-entry ACH Total street length or urban size Lx (m) Figure 4. Air change rate in test cases of Case [5-5, θ], Case [i-n,0]. Analysis of Contribution Ratio in the Example Case As an example, Fig. 5a shows 3D streamline and concentration field in z=1.5m in Case [5-5, 15] as tracer gas source unit is B11. 3D vortices and helical flow also exist.

7 Thus turbulent airflows transport pollutant to the neighbor units and toward downstream. The concentration in source B11 unit and its neighbor units are much higher than that far downstream. Then Fig. 5b-5g display contribution ratio in Case [5-5, 15] and Case [5-5, 45] with source units of B11, B44. With the upstream source unit of B11(see Fig. 5b-5c), tracer gas concentration in B11 unit itself is relatively low (ratio of 26.97% and 23.71%) due to better ventilation in B11 unit, but tracer gas disperses to many other units with considerable contribution ratios. With a downstream source unit (B44), the contribution ratio is small in its upstream unit, and tracer gas is dispersed to a limited number of urban units, however contribution ratio in the source unit itself is large (79.84%-82.24%) because the downstream unit has a worse ventilation performance locally. Tracer gas concentration (ppm) in z=1.5 m in Case [5-5, 15] 15 Uniform source in B %% 1.53%% % 1.20% 5.16% 6.46% 1.02%% 3.59%% 5.36%% 1.24% 6.39% 8.82% 4.69% 3.23% 8.13%% 7.9%% 7.89%% 9.13% 13.48% 6.01% 1.03% 26.97% 16.43%% 8.89%% 5.93%% 23.71% 9.04% 1.16%% 0.12% Source B11 (c) 0.19% 79.84% 0.38% 82.24% 0.74% 0.36% (d) (e) Figure 5. 3D streamline and concentration in z=1.5m in Case [5-5, 15], (b-e) Contribution ratio with source units of B11, B44 in Case [5-5, 15] and Case [5-5, 45]. CONCLUSIONS This paper applied some tracer gas techniques into CFD simulations to predict air

8 change rates and contribution ratio in urban spaces. Results show that the approaches are effective tools to evaluate the effect of urban morphologies on overall ventilation capacity and to quantify the pollutant flux between different urban spaces within the UCL. The normal concentration decay method (ACH 1 ) attains smaller air change rates than the other (ACH 2 ) without tracer gas reentry which fixes concentration out of UCL volume to be zero. Moreover ACH calculated by concentration decay methods are always less than the sum of ACH calculated by flow rates induced by mean flows and turbulence across UCL boundaries. It verifies that further investigations are still required to analyze ventilation efficiency by mean flows and turbulence. With a parallel approaching wind (θ=0 o ), larger urban sizes experience smaller ACH (Lx= 390m to 2940m). For the 5-row and 5-column UCL model (Lx=Ly=270m), the parallel wind obtains greater ACH than non-parallel winds (θ=15 o, 30 o, 45 o ). Finally the contribution ratio approach is effective to quantify the transfer of pollutants between different urban spaces of a UCL, and it is worth being applied if urban planners select an urban site to place heavy pollutant sources. ACKNOWLEDGEMENT This work was funded by the National Natural Science Foundation of China (Grant No ). REFERENCES Bady M, Kato S, Huang H (2008) Towards the application of indoor ventilation efficiency indices to evaluate the air quality of urban areas. Building and Environment, 43, Brown MJ, Lawson RE, Decroix DS et al (2001) Comparison of centerline velocity measurements obtained around 2D and 3D buildings arrays in a wind tunnel, Report LA-UR , Los Alamos National Laboratory, Los Alamos,pp.7. Chen Q (2009) Ventilation performance prediction for buildings: a method overview and recent applications. Building and Environment, 44, Etheridge D and Sandberg M (1996) Building Ventilation Theory and Measurement. John Wiley & Sons, Chichester, UK. Hang J, Sandberg M, Li Y (2009) Age of air and air exchange efficiency in idealized city models. Building and Environment, 44(8), Hang J, Li Y (2010) Wind conditions in idealized building clusters macroscopic simulations using a porous turbulence model. Boundary-Layer Meteorology, 136(1), Liu CH, Leung DYC, Barth MC (2005) On the prediction of air and pollutant exchange rates in street canyons of different aspect ratio using large-eddy simulation. Atmospheric Environment, 39, Tominaga Y, Mochida A, Yoshie R, et al (2008) AIJ guidelines for practical applications of CFD to pedestrian wind environment around buildings. Journal of Wind Engineering and Industrial Aerodynamics, 96,

Riccardo Buccolieri 1, Mats Sandberg 2

Riccardo Buccolieri 1, Mats Sandberg 2 STUDY OF TE EFFECTS OF BUILDING DENSITY AND OVERALL SAPE OF A CITY ON POLLUTANT DISPERSION BY COMBINATION OF WIND TUNNEL EXPERIMENTS AND CFD SIMULATIONS Riccardo Buccolieri 1, Mats Sandberg 2 1 Dipartimento

More information

Numerical simulation of inter-flat pollutant dispersion routes and cross-contamination risk in high-rise residential buildings Di Mu, Naiping Gao* Ins

Numerical simulation of inter-flat pollutant dispersion routes and cross-contamination risk in high-rise residential buildings Di Mu, Naiping Gao* Ins Numerical simulation of inter-flat pollutant dispersion routes and cross-contamination risk in high-rise residential buildings Di Mu, Naiping Gao* Institute of Thermal and Environment Engineering, School

More information

Natural ventilation assessment in typical open an semi open urban environments under various wind directions

Natural ventilation assessment in typical open an semi open urban environments under various wind directions Natural ventilation assessment in typical open an semi open urban environments under various wind directions Article Accepted Version Hang, J., Luo, Z., Sandberg, M. and Jian, G. (2013) Natural ventilation

More information

H POLLUTANT DISPERSION OVER TWO-DIMENSIONAL IDEALIZED STREET CANYONS: A LARGE-EDDY SIMULATION APPROACH. Colman C.C. Wong and Chun-Ho Liu*

H POLLUTANT DISPERSION OVER TWO-DIMENSIONAL IDEALIZED STREET CANYONS: A LARGE-EDDY SIMULATION APPROACH. Colman C.C. Wong and Chun-Ho Liu* H14-117 POLLUTANT DISPERSION OVER TWO-DIMENSIONAL IDEALIZED STREET CANYONS: A LARGE-EDDY SIMULATION APPROACH Colman C.C. Wong and Chun-Ho Liu* Department of Mechanical Engineering, The University of Hong

More information

u and Yoshie (2013) investigate the effect of building geometry and they revealed that the ventilation efficiency strongly depended on the level of bu

u and Yoshie (2013) investigate the effect of building geometry and they revealed that the ventilation efficiency strongly depended on the level of bu Effect of upstream building arrangement and setback distance on air flow around idealized cubical building arrays A. Abd Razak 1*, R.. usam 1, T. Liyana 1, S. A. Zaki 2 and A. F. Mohammad 2 1 Faculty of

More information

On the performance of the Stravent ventilation system in an office space Numerical and experimental investigations

On the performance of the Stravent ventilation system in an office space Numerical and experimental investigations On the performance of the Stravent ventilation system in an office space Numerical and experimental investigations S. Janbakhsh 1, 2 and.b. Moshfegh 1, 2 1 Division of Energy and Mechanical Engineering,

More information

putational domain contained 8 blocks surrounding the central one. All 9 blocks had the same arrangement. Each block comprised a total of 72 residentia

putational domain contained 8 blocks surrounding the central one. All 9 blocks had the same arrangement. Each block comprised a total of 72 residentia The Seventh International Colloquium on Bluff Body Aerodynamics and Applications (BBAA7) Shanghai, China; September 2-6, 2012 Ventilation efficiency indices for evaluating ventilation performance of newly-built

More information

Fluctuating Inlet Flow Conditions for Use in Urban Air Quality CFD Studies

Fluctuating Inlet Flow Conditions for Use in Urban Air Quality CFD Studies Proceedings of the World Congress on Engineering Vol II, WCE, July -,, London, U.K. Fluctuating Inlet Flow Conditions for Use in Urban Air Quality CFD Studies S. M. Kwa, S. M. Salim Abstract Fluctuating

More information

On The Effect Of Various Design Factors On Wind-Induced Natural Ventilation Of Residential Buildings In Malaysia M. F. Mohamad 1,2*, A. Hagishima 2, J

On The Effect Of Various Design Factors On Wind-Induced Natural Ventilation Of Residential Buildings In Malaysia M. F. Mohamad 1,2*, A. Hagishima 2, J On The Effect Of Various Design Factors On Wind-Induced Natural Ventilation Of Residential Buildings In Malaysia M. F. Mohamad 1,2*, A. Hagishima 2, J. Tanimoto 2, N. Ikegaya 2, and A. R. Omar 1 1 Faculty

More information

CFD Modeling of Reactive Pollutants in an Urban Street Canyon using Different Chemical Mechanisms

CFD Modeling of Reactive Pollutants in an Urban Street Canyon using Different Chemical Mechanisms CFD Modeling of Reactive Pollutants in an Urban Street Canyon using Different Chemical Mechanisms B Sanchez a,b, JL Santiago a, A Martilli a, M Palacios a, F Kirchner c a Center for Energy, Environment

More information

Modelling urban pollution dispersion by using MISKAM

Modelling urban pollution dispersion by using MISKAM Modelling urban pollution dispersion by using MISKAM Márton Balczó 1, Tamás Faragó 2, Tamás Lajos 3 PhD Student 1, Student 2, Professor 3 Budapest University of Technology and Economics, Department of

More information

SCIENCE & TECHNOLOGY

SCIENCE & TECHNOLOGY Pertanika J. Sci. & Technol. 25 (S): 277-286 (2017) SCIENCE & TECHNOLOGY Journal homepage: http://www.pertanika.upm.edu.my/ Effect of Upstream Building Configurations on Mean Wind Speed Ratio at Urban

More information

CFD/FEM Based Analysis Framework for Wind Effects on Tall Buildings in Urban Areas

CFD/FEM Based Analysis Framework for Wind Effects on Tall Buildings in Urban Areas 2017 2nd International Conference on Industrial Aerodynamics (ICIA 2017) ISBN: 978-1-60595-481-3 CFD/FEM Based Analysis Framework for Wind Effects on Tall Buildings in Urban Areas Qiao Yan, Dalong Li,

More information

On the performance of confluent jets ventilation system in office space

On the performance of confluent jets ventilation system in office space On the performance of confluent jets ventilation system in office space T. Karimipanah 1 and B. Moshfegh 1, 2 1 Division of Energy and Mechanical Engineering, Department of Technology and Built Environment,

More information

WIND FLOW IN THE RECESSED CAVITIES OF A TALL

WIND FLOW IN THE RECESSED CAVITIES OF A TALL The Seventh Asia-Pacific Conference on Wind Engineering, November 8-12, 2009, Taipei, Taiwan WIND FLOW IN THE RECESSED CAVITIES OF A TALL BUILDING Charles C.K. Cheng 1, K.M. Lam 2 and Andrew Y.T. Leung

More information

Numerical analysis of CO concentration distribution on extraction ventilation type tunnel Tao Guo 1,a, Jun Zhou 2,b, Xiaonan Liu 3,c and Bo Shang 4

Numerical analysis of CO concentration distribution on extraction ventilation type tunnel Tao Guo 1,a, Jun Zhou 2,b, Xiaonan Liu 3,c and Bo Shang 4 Applied Mechanics and Materials Online: 2013-10-15 ISSN: 1662-7482, Vols. 444-445, pp 277-280 doi:10.4028/www.scientific.net/amm.444-445.277 2014 Trans Tech Publications, Switzerland Numerical analysis

More information

Performance of a Vertical Axis Wind Turbine under Accelerating and Decelerating Flows

Performance of a Vertical Axis Wind Turbine under Accelerating and Decelerating Flows Performance of a Vertical Axis Wind Turbine under Accelerating and Decelerating Flows Atif Shahzad, Taimoor Asim*, Rakesh Mishra, Achilleos Paris School of Computing & Engineering, University of Huddersfield,

More information

Numerical Simulation of Airflow Organization and Temperature Distribution in Bulk Curing Barn Yong-qiao WANG, Yan-qiong LI, Yan ZHAO

Numerical Simulation of Airflow Organization and Temperature Distribution in Bulk Curing Barn Yong-qiao WANG, Yan-qiong LI, Yan ZHAO 5th International Conference on Advanced Materials and Computer Science (ICAMCS 2016) Numerical Simulation of Airflow Organization and Temperature Distribution in Bulk Curing Barn Yong-qiao WANG, Yan-qiong

More information

Comparison of RANS, URANS and LES in the Prediction of Airflow and Pollutant Dispersion

Comparison of RANS, URANS and LES in the Prediction of Airflow and Pollutant Dispersion Comparison of RANS, URANS and LES in the Prediction of Airflow and Pollutant Dispersion S. M. Salim, K. C. Ong, S. C. Cheah Abstract The performance of three different numerical techniques, i.e. RANS,

More information

CFD Study on Inter-Action between NonIsothermal Airflow and Buoyancy Plume in an AirConditioned Space

CFD Study on Inter-Action between NonIsothermal Airflow and Buoyancy Plume in an AirConditioned Space Wang et al. CFD Letters www.cfdl.issres.net Vol. 2(3) 2010 Vol. 2(3) September 2010 CFD Study on Inter-Action between NonIsothermal Airflow and Buoyancy Plume in an AirConditioned Space Xin. Wang1C and

More information

PERFORMANCE EVALUATION OF TWO AIR DISTRIBUTION SYSTEMS. T Karimipanah 1 and H B Awbi 2

PERFORMANCE EVALUATION OF TWO AIR DISTRIBUTION SYSTEMS. T Karimipanah 1 and H B Awbi 2 PERFORMANCE EVALUATION OF TWO AIR DISTRIBUTION SYSTEMS T Karimipanah 1 and H B Awbi 2 1 Air Innovation AB, Sweden 2 University of Reading, UK ABSTRACT This paper focuses on evaluating the performance of

More information

On Plume Dispersion over Two-Dimensional Urban-like Idealized Roughness Elements with Height Variation

On Plume Dispersion over Two-Dimensional Urban-like Idealized Roughness Elements with Height Variation On Plume Dispersion over Two-Dimensional Urban-like Idealized Roughness Elements with Height Variation Colman C.C. Wong and Chun-Ho Liu Department of Mechanical Engineering, The University of Hong Kong,

More information

A Modelling-Mapping Approach for Fine-Scale Natural Ventilation Evaluation in High Density Cities

A Modelling-Mapping Approach for Fine-Scale Natural Ventilation Evaluation in High Density Cities A Modelling-Mapping Approach for Fine-Scale Natural Ventilation Evaluation in High Density Cities Chao Yuan 1, 2, Leslie Norford 3, Rex Britter 4, Steve Yim 5, Edward Ng 6, 1 Massachusetts Institute of

More information

Numerical Simulation of an Express Freight Train and a High-Speed Train Meeting in a Tunnel

Numerical Simulation of an Express Freight Train and a High-Speed Train Meeting in a Tunnel 2017 2nd International Conference on Industrial Aerodynamics (ICIA 2017) ISBN: 978-1-60595-481-3 Numerical Simulation of an Express Freight Train and a High-Speed Train Meeting in a Tunnel Kan He, Guang-Jun

More information

Numerical Simulation of the Flue Gas Desulfurization in the Sieve Tray Tower

Numerical Simulation of the Flue Gas Desulfurization in the Sieve Tray Tower 52 China Steel Technical Report, No. Numerical 28, pp.52-57, Simulation (2015) of the Flue Gas Desulfurization in the Sieve Tray Tower Numerical Simulation of the Flue Gas Desulfurization in the Sieve

More information

Numerical Modeling of Buoyancy-driven Natural Ventilation in a Simple Three Storey Atrium Building

Numerical Modeling of Buoyancy-driven Natural Ventilation in a Simple Three Storey Atrium Building Numerical Modeling of Buoyancy-driven Natural Ventilation in a Simple Three Storey Atrium Building Shafqat Hussain and Patrick H. Oosthuizen Department of Mechanical and Materials Engineering, Queen s

More information

Modelling of air pollution on urban buildings: a wind tunnel study

Modelling of air pollution on urban buildings: a wind tunnel study Modelling of air pollution on urban buildings: a wind tunnel study A. M. Mfula 1,2, V. Kukadia 1, R. F. Griffiths 2 & D. J. Hall 3 1 Building Research Establishment Ltd (BRE), UK 2 Environmental Technology

More information

XVII th World Congress of the International Commission of Agricultural and Biosystems Engineering (CIGR)

XVII th World Congress of the International Commission of Agricultural and Biosystems Engineering (CIGR) XVII th World Congress of the International Commission of Agricultural and Biosystems Engineering (CIGR) Hosted by the Canadian Society for Bioengineering (CSBE/SCGAB) Québec City, Canada June 13-17, 2010

More information

Scott Reynolds, PE M/E Engineering Syracuse NY

Scott Reynolds, PE M/E Engineering Syracuse NY Scott Reynolds, PE M/E Engineering Syracuse NY What is Wind Modeling? Wind modeling studies are used to determine: The flow of pollutants from exhaust stacks on buildings. The determination of pollutant

More information

CFD and Wind Tunnel Study of the Performance of a Multi- Directional Wind Tower with Heat Transfer Devices

CFD and Wind Tunnel Study of the Performance of a Multi- Directional Wind Tower with Heat Transfer Devices Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (2015 ) 1692 1697 The 7 th International Conference on Applied Energy ICAE2015 CFD and Wind Tunnel Study of the Performance of

More information

A Sensitivity Analysis on Mixing Energy Loss in Air-Conditioned Rooms by Using CFD

A Sensitivity Analysis on Mixing Energy Loss in Air-Conditioned Rooms by Using CFD A Sensitivity Analysis on Mixing Energy Loss in Air-Conditioned Rooms by Using CFD S. Iizuka 1, S. Shiba 1,*, M. Sasaki 1, M. Okumiya 1 1 Nagoya University, Nagoya, Japan ABSTRACT In some office buildings,

More information

Indoor Air 2005, Beijing, China Effectiveness of confluent jets ventilation system for classrooms

Indoor Air 2005, Beijing, China Effectiveness of confluent jets ventilation system for classrooms Effectiveness of confluent jets ventilation system for classrooms T. Karimipanah 1, H.B. Awbi 2, C. Blomqvist 3 and M. Sandberg 3 ABSTRACT 1 Fresh AB, Sweden, taghi.k@comhem.se 2 University of Reading,

More information

Performance Improvement Analysis for a Negative-pressurized Biosafety Level Laboratory

Performance Improvement Analysis for a Negative-pressurized Biosafety Level Laboratory Performance Improvement Analysis for a Negative-pressurized Biosafety Level Laboratory F.J. Wang* and J.S. Huang 1 Department of Refrigeration, Air Conditioning and Energy Engineering, National Chin-Yi

More information

-3025 SPATIAL VARIABILITY OF MEAN FLOW AND TURBULENCE FIELDS IN STREET CANYONS LA-UR-00 -

-3025 SPATIAL VARIABILITY OF MEAN FLOW AND TURBULENCE FIELDS IN STREET CANYONS LA-UR-00 - Q... > LA-UR-00 - -3025 Title: SPATIAL VARIABILITY OF MEAN FLOW AND TURBULENCE FIELDS IN STREET CANYONS Authoc P. Kastner-Klein, Institute for C/hnate Research, Swiss Federal Institute of Technology M.

More information

CEE ENVIRONMENTAL QUALITY ENGINEERING PROBLEM SET #5

CEE ENVIRONMENTAL QUALITY ENGINEERING PROBLEM SET #5 CEE 3510 -- ENVIRONMENTAL UALITY ENGINEERING PROBLEM SET #5 Problem 1. (adapted from Water uality by Tchobanoglous and Schroeder) A stream has a nearly uniform cross section, although it passes through

More information

P. Rohdin 1, M. Johansson 2, J. Löfberg 3, M. Ottosson 4. Abstract

P. Rohdin 1, M. Johansson 2, J. Löfberg 3, M. Ottosson 4. Abstract ENERGY EFFICIENT PROCESS VENTILATION IN PAINT SHOPS IN THE CAR INDUSTRY EXPERIENCES AND AN EVALUATION OF A FULL SCALE IMPLEMENTATION AT SAAB AUTOMOBILE IN SWEDEN P. Rohdin 1, M. Johansson 2, J. Löfberg

More information

Volume 7 - Number 12 - November 2011 (29-34) Numerical Modeling of Wind Effect on Plume Dispersion from a Point Source around Buildings

Volume 7 - Number 12 - November 2011 (29-34) Numerical Modeling of Wind Effect on Plume Dispersion from a Point Source around Buildings ISESCO JOURNAL of Science and Technology Volume 7 - Number 12 - November 2011 (29-34) Abstract Dispersion from the polluted point source within the atmosphere is the major concern in the urban areas. The

More information

Investigation of air quality, comfort parameters and effectiveness for two floor level air supply systems in classrooms

Investigation of air quality, comfort parameters and effectiveness for two floor level air supply systems in classrooms Investigation of air quality, comfort parameters and effectiveness for two floor level air supply systems in classrooms T. Karimipanah 1,2,3, H.B. Awbi 2, M. Sandberg 3 and C. Blomqvist 3 1 Fresh AB, Sweden,

More information

Published in: CleanTech for Sustainable Buildings: From Nano to Urban Scale (CISBAT), Lausanne, September 2011

Published in: CleanTech for Sustainable Buildings: From Nano to Urban Scale (CISBAT), Lausanne, September 2011 Evaluation of wind-driven ventilation in building energy simulation: sensitivity to pressure coefficients Ramponi, R.; Costola, D.; Angelotti, A.; Blocken, B.; Hensen, J.L.M. Published in: CleanTech for

More information

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Available online at   ScienceDirect. Energy Procedia 78 (2015 ) Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (5 ) 549 555 6th International Building Physics Conference, IBPC 5 Modeling of the impact of different window types on single-sided

More information

APPLYING COMPUTATIONAL FLUID DYNAMICS TO ARCHITEC- TURAL DESIGN DEVELOPMENT

APPLYING COMPUTATIONAL FLUID DYNAMICS TO ARCHITEC- TURAL DESIGN DEVELOPMENT APPLYING COMPUTATIONAL FLUID DYNAMICS TO ARCHITEC- TURAL DESIGN DEVELOPMENT Strategy and Implementation JIN-YEU TSOU Department of Architecture, Chinese University of Hong Kong Sha Tin, New Territories,

More information

Thermal Management of Densely-packed EV Battery Set

Thermal Management of Densely-packed EV Battery Set EVS28 KINTEX, Korea, May 3-6, 2015 Thermal Management of Densely-packed EV Battery Set Abstract Z. Lu 1, X.Z. Meng 1, W.Y. Hu 2, L.C. Wei 3, L.Y. Zhang 1, L.W. Jin 1* 1 Building Environment and Equipment

More information

Effects of shaft supporting structure on performance test of axial flow fan

Effects of shaft supporting structure on performance test of axial flow fan IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Effects of shaft supporting structure on performance test of axial flow fan To cite this article: R Ma et al 2016 IOP Conf. Ser.:

More information

CODASC: A DATABASE FOR THE VALIDATION OF STREET CANYON DISPERSION MODELS. Christof Gromke

CODASC: A DATABASE FOR THE VALIDATION OF STREET CANYON DISPERSION MODELS. Christof Gromke CODASC: A DATABASE FOR THE VALIDATION OF STREET CANYON DISPERSION MODELS Christof Gromke Building Physics and Services, Department of the Built Environment, Eindhoven University of Technology, Eindhoven,

More information

ACCEPTED MANUSCRIPT NUMERICAL MODELLING OF THE PASSIVE CONTROL OF AIR POLLUTION IN ASYMMETRICAL URBAN STREET CANYONS USING REFINED MESH

ACCEPTED MANUSCRIPT NUMERICAL MODELLING OF THE PASSIVE CONTROL OF AIR POLLUTION IN ASYMMETRICAL URBAN STREET CANYONS USING REFINED MESH Accepted Manuscript Numerical modelling of the passive control of air pollution in asymmetrical urban street canyons using refined mesh discretization schemes J. Gallagher, L.W. Gill, A. McNabola PII:

More information

Numerical Simulation of the Aerodynamic Performance of a H-type Wind Turbine during Self-Starting

Numerical Simulation of the Aerodynamic Performance of a H-type Wind Turbine during Self-Starting Numerical Simulation of the Aerodynamic Performance of a H-type Wind Turbine during Self-Starting Wei Zuo a, Shun Kang b Key Laboratory of Condition Monitoring and Control for Power Plant Equipment, Ministry

More information

Validation of a Coupled Multizone and CFD Program for Building Airflow and Contaminant Transport Simulations

Validation of a Coupled Multizone and CFD Program for Building Airflow and Contaminant Transport Simulations Wang, L. and Chen, Q. 2007. Validation of a coupled multizone and CFD program for building airflow and contaminant transport simulations, HVAC&R Research, 13(2), 267-281. Validation of a Coupled Multizone

More information

Analysis of Uniformity and Energy Consumption in. Supermarket installed DurkeeSox Air Dispersion System. with PE Air Dispersion Model

Analysis of Uniformity and Energy Consumption in. Supermarket installed DurkeeSox Air Dispersion System. with PE Air Dispersion Model Analysis of Uniformity and Energy Consumption in Supermarket installed DurkeeSox Air Dispersion System with PE Air Dispersion Model Summary: Taking partial area of a large supermarket for example, to simulate

More information

Computational Parametric Study to Improve Air Quality in High-Density Cities

Computational Parametric Study to Improve Air Quality in High-Density Cities Computational Parametric Study to Improve Air Quality in High-Density Cities Chao Yuan1.2, Edward Ng3, Leslie Norford4 1 Massachusetts Institute of Technology, 77 Mass. Ave, Cambridge, MA, US. yuanc@mit.edu

More information

A study of single-sided ventilation and provision of balconies in the context of high-rise residential buildings

A study of single-sided ventilation and provision of balconies in the context of high-rise residential buildings A study of single-sided ventilation and provision of balconies in the context of high-rise residential buildings Mohamed M. F. 1,2,*, King S. 2, Behnia M. 3, Prasad D. 2 1 Faculty of Engineering and Built

More information

THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING. Gang Wang, Yafeng Hu, and Songtao Hu

THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING. Gang Wang, Yafeng Hu, and Songtao Hu THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING Gang Wang, Yafeng Hu, and Songtao Hu School of Environmental & Municipal Engineering, Qingdao Technological University, Qingdao

More information

Single-sided natural ventilation through a centre-pivot roof window Iqbal, Ahsan; Nielsen, Peter Vilhelm; Gunner, Amalie; Afshari, Alireza

Single-sided natural ventilation through a centre-pivot roof window Iqbal, Ahsan; Nielsen, Peter Vilhelm; Gunner, Amalie; Afshari, Alireza Aalborg Universitet Single-sided natural ventilation through a centre-pivot roof window Iqbal, Ahsan; Nielsen, Peter Vilhelm; Gunner, Amalie; Afshari, Alireza Published in: Proceedings Indoor Air 214 Publication

More information

Causes of Urban Heat Island in Singapore: An investigation using computational fluid dynamics (CFD)

Causes of Urban Heat Island in Singapore: An investigation using computational fluid dynamics (CFD) Causes of Urban Heat Island in Singapore: An investigation using computational fluid dynamics (CFD) RAJAGOPALAN PRIYADARSINI 1, WONG NYUK HIEN 2 1 School of Architecture & Building, Deakin University,

More information

Technical Feasibility Study of Hybrid Ventilation for a High-rise Office Building in Shanghai

Technical Feasibility Study of Hybrid Ventilation for a High-rise Office Building in Shanghai Topic 2. Ventilation and Sustainable Development Technical Feasibility Study of Hybrid Ventilation for a High-rise Office Building in Shanghai Yiqun PAN 1,*, Sen HUANG 2, Jiachen MAO 1 1 College of Mechanical

More information

ADVANCES in NATURAL and APPLIED SCIENCES

ADVANCES in NATURAL and APPLIED SCIENCES ADVANCES in NATURAL and APPLIED SCIENCES ISSN: 1995-0772 Published BYAENSI Publication EISSN: 1998-1090 http://www.aensiweb.com/anas 2017 May 11(7): pages 910-918 Open Access Journal Analysis Of Ventilation

More information

COMPARISON OF WIND TUNNEL MEASUREMENT AND NUMERICAL SIMULATION OF DISPERSION OF POLLUTANTS IN URBAN ENVIRONMENT

COMPARISON OF WIND TUNNEL MEASUREMENT AND NUMERICAL SIMULATION OF DISPERSION OF POLLUTANTS IN URBAN ENVIRONMENT COMPARISON OF WIND TUNNEL MEASUREMENT AND NUMERICAL SIMULATION OF DISPERSION OF POLLUTANTS IN URBAN ENVIRONMENT I. Goricsán Department of Fluid Mechanics Budapest University of Technology and Economics

More information

INVESTIGATION OF FLOW CHARACTERISTICS OF HELLER-TYPE COOLING TOWERS WITH DIFFERENT COOLING DELTA ANGLES

INVESTIGATION OF FLOW CHARACTERISTICS OF HELLER-TYPE COOLING TOWERS WITH DIFFERENT COOLING DELTA ANGLES PERIODICA POLYTECHNICA SER. MECH. ENG. VOL. 47, NO. 2, PP. 143 150 (2003) INVESTIGATION OF FLOW CHARACTERISTICS OF HELLER-TYPE COOLING TOWERS WITH DIFFERENT COOLING DELTA ANGLES Nimród KAPÁS Department

More information

Project Background (long term goals)

Project Background (long term goals) ANNUAL REPORT 2012 UIUC, August 16, 2012 Modeling Heat Transfer in SEN during Preheating & Cool-down Yonghui Li (Ph.D. Student) Department of Mechanical Science and Engineering University of Illinois at

More information

A study on the effect of the airflow rate of the ceiling type air-conditioner on the ventilation performance

A study on the effect of the airflow rate of the ceiling type air-conditioner on the ventilation performance A study on the effect of the airflow rate of the ceiling type air-conditioner on the ventilation performance Kwang-Chul Noh 1, Chang-Woo Han 2 and Myung-Do Oh 2 1 Institute of Industrial Technology, University

More information

Wind driven flow through building openings

Wind driven flow through building openings International Conference Passive and Low Energy Cooling 427 for the Built Environment, May 25, Santorini, Greece Wind driven flow through building openings P. Karava, T. Stathopoulos and A.K. Athienitis

More information

Ecole Centrale de Lyon. Laboratoire de Mécanique des Fluides et d'acoustique

Ecole Centrale de Lyon. Laboratoire de Mécanique des Fluides et d'acoustique Ecole Centrale de Lyon Laboratoire de Mécanique des Fluides et d'acoustique Pollutant dispersion through an obstacle array: numerical modelling and experimental investigation Soulhac L., Rios I., Garbero

More information

Critical Review of the Building Downwash Algorithms in AERMOD

Critical Review of the Building Downwash Algorithms in AERMOD Critical Review of the Building Downwash Algorithms in AERMOD Paper #34 Presented at the conference: Guideline on Air Quality Models: The New Path April 12-14, 2016 Chapel Hill, NC Ron L. Petersen, 1 Sergio

More information

INVESTIGATIONS ON PERFORMANCE OF A SAVONIUS HYDROKINETIC TURBINE

INVESTIGATIONS ON PERFORMANCE OF A SAVONIUS HYDROKINETIC TURBINE INVESTIGATIONS ON PERFORMANCE OF A SAVONIUS HYDROKINETIC TURBINE Ph.D. THESIS by ANUJ KUMAR ALTERNATE HYDRO ENERGY CENTRE INDIAN INSTITUTE OF TECHNOLOGY ROORKEE ROORKEE-247667 (INDIA) AUGUST, 2017 INVESTIGATIONS

More information

HEAT EXCHANGER THERMAL STRATIFICATION MODEL

HEAT EXCHANGER THERMAL STRATIFICATION MODEL HEAT EXCHANGER THERMAL STRATIFICATION MODEL Celso Yukio Nakashima*, Luiz Tobaldini Neto*,1 *Embraer Keywords: cross flow, heat exchanger, thermal stratification, modeling, bleed Abstract Compact cross-flow

More information

Numerical analysis of indoor thermal comfort in a cross-ventilated space with top-hung windows

Numerical analysis of indoor thermal comfort in a cross-ventilated space with top-hung windows University of Wollongong Research Online Faculty of Engineering and Information Sciences - Papers: Part B Faculty of Engineering and Information Sciences 2017 Numerical analysis of indoor thermal comfort

More information

Performance Evaluation of Natural Ventilation Devices to Improve Thermal Comfort of a Computer Lab of University Building Using CFD as a Tool

Performance Evaluation of Natural Ventilation Devices to Improve Thermal Comfort of a Computer Lab of University Building Using CFD as a Tool From the SelectedWorks of Innovative Research Publications IRP India Spring March 1, 2015 Performance Evaluation of Natural Ventilation Devices to Improve Thermal Comfort of a Computer Lab of University

More information

Current Studies on Air Distributions in Commercial Airliner Cabins

Current Studies on Air Distributions in Commercial Airliner Cabins Liu, W. and Chen, Q. 2013. Current studies on air distributions in commercial airliner cabins. Accepted by Theoretical & Applied Mechanics Letters. Current Studies on Air Distributions in Commercial Airliner

More information

Evaluation of Gaussian Plume Model against CFD Simulations through the Estimation of CO and NO Concentrations in an Urban Area

Evaluation of Gaussian Plume Model against CFD Simulations through the Estimation of CO and NO Concentrations in an Urban Area American Journal of Environmental Sciences Original Research Paper Evaluation of Gaussian Plume Model against CFD Simulations through the Estimation of CO and NO Concentrations in an Urban Area 1,2 Mahmoud

More information

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Available online at   ScienceDirect. Procedia Engineering 121 (2015 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 121 (2015 ) 225 231 9th International Symposium on Heating, Ventilation and Air Conditioning (ISHVAC) and the 3rd International

More information

TREES IN URBAN STREET CANYONS AND THEIR IMPACT ON THE DISPERSION OF AUTOMOBILE EXHAUSTS. Christof Gromke*, Bodo Ruck

TREES IN URBAN STREET CANYONS AND THEIR IMPACT ON THE DISPERSION OF AUTOMOBILE EXHAUSTS. Christof Gromke*, Bodo Ruck TREES IN URBAN STREET CANYONS AND THEIR IMPACT ON THE DISPERSION OF AUTOMOBILE EXHAUSTS Christof Gromke*, Bodo Ruck Laboratory of Building- and Environmental Aerodynamics Institute for Hydromechanics,

More information

Sensitivity Analysis of Personal Exposure Assessment Using a Computer Simulated Person Brohus, Henrik; Jensen, H. K.

Sensitivity Analysis of Personal Exposure Assessment Using a Computer Simulated Person Brohus, Henrik; Jensen, H. K. Aalborg Universitet Sensitivity Analysis of Personal Exposure Assessment Using a Computer Simulated Person Brohus, Henrik; Jensen, H. K. Published in: Healthy Buildings 2009 Publication date: 2009 Document

More information

Evaluation of a CFD modeling approach by means of an intensive experimental campaign using passive samplers in an urban area of Madrid

Evaluation of a CFD modeling approach by means of an intensive experimental campaign using passive samplers in an urban area of Madrid Evaluation of a CFD modeling approach by means of an intensive experimental campaign using passive samplers in an urban area of Madrid Jose Luis Santiago 1, Rafael Borge 2, Fernando Martin 1, David de

More information

CFD Modelling and Analysis of Different Plate Heat Exchangers

CFD Modelling and Analysis of Different Plate Heat Exchangers CFD Modelling and Analysis of Different Plate Heat Exchangers Ahmed Y Taha Al-Zubaydi a *, Guang Hong b and W. John Dartnall c Faculty of Engineering and Information Technology, UTS, Sydney, Australia

More information

By Kimbal A. Hall, PE. Submitted to: WESTFALL MANUFACTURING COMPANY. May ALDEN RESEARCH LABORATORY, INC. 30 Shrewsbury Street Holden, MA 01520

By Kimbal A. Hall, PE. Submitted to: WESTFALL MANUFACTURING COMPANY. May ALDEN RESEARCH LABORATORY, INC. 30 Shrewsbury Street Holden, MA 01520 COMPUTATIONAL FLOW MODEL OF WESTFALL'S 36 3050 THREE STAGE MIXER TO BE INSTALLED IN THE PERCHLORATE BLENDING STATION FOR THE CITY OF REDLANDS, CALIFORNIA GFS-411507-1R2 By Kimbal A. Hall, PE Submitted

More information

EasyChair Preprint. Resolving the Non-Productive Periods of Solar Chimney by Integrating with Waste-to-Energy Plant

EasyChair Preprint. Resolving the Non-Productive Periods of Solar Chimney by Integrating with Waste-to-Energy Plant EasyChair Preprint 159 Resolving the Non-Productive Periods of Solar Chimney by Integrating with Waste-to-Energy Plant Ali Habibollahzade, Ehsan Houshfar, Amir Mohammad Behzadi, Ehsan Gholamian and Mehdi

More information

NUMERICAL STUDY ON AIRFLOW IN AN OFFICE ROOM WITH A DISPLACEMENT VENTILATION SYSTEM Yukihiro Hashimoto 1 1

NUMERICAL STUDY ON AIRFLOW IN AN OFFICE ROOM WITH A DISPLACEMENT VENTILATION SYSTEM Yukihiro Hashimoto 1 1 Ninth International IBPSA Conference Montréal, Canada August 5-8, 5 NUMERICAL STUDY ON AIRFLOW IN AN OFFICE ROOM WITH A DISPLACEMENT VENTILATION SYSTEM Yukihiro Hashimoto Polytechnic University, Dept.

More information

Analysis on the influence of rotational speed to aerodynamic performance of vertical axis wind turbine

Analysis on the influence of rotational speed to aerodynamic performance of vertical axis wind turbine Available online at www.sciencedirect.com Procedia Engineering 31 (2012) 245 250 International Conference on Advances in Computational Modeling and Simulation Analysis on the influence of rotational speed

More information

Roof Mounted Wind Turbines: The influence of roof shape, building height and urban location on wind speed

Roof Mounted Wind Turbines: The influence of roof shape, building height and urban location on wind speed Roof Mounted Wind Turbines: The influence of roof shape, building height and urban location on wind speed ISLAM ABOHELA 1, STEVEN DUDEK 1 and NEVEEN HAMZA 1 1 School of Architecture, Planning and Landscape,

More information

IDENTIFICATION OF VENTILATION PROBLEMS IN AN UNDERGROUND BUS TERMINAL IN KOREA

IDENTIFICATION OF VENTILATION PROBLEMS IN AN UNDERGROUND BUS TERMINAL IN KOREA IDENTIFICATION OF VENTILATION PROBLEMS IN AN UNDERGROUND BUS TERMINAL IN KOREA H Han 1* and Y-I Kwon 2 1 Dept. Of Mechanical Engineering, Kookmin University, Korea 2 Dept. Of Building Mechanical Engineering,

More information

Influence of Building Aspect Ratio and Traffic Volume on Reactive Pollutant Dispersion in Urban-like Street Canyons during Direct Ground Heating

Influence of Building Aspect Ratio and Traffic Volume on Reactive Pollutant Dispersion in Urban-like Street Canyons during Direct Ground Heating Department of Mechanical Engineering University of Hong Kong Influence of Building Aspect Ratio and Traffic Volume on Reactive Pollutant Dispersion in Urban-like Street Canyons during Direct Ground Heating

More information

ADVANCES in NATURAL and APPLIED SCIENCES

ADVANCES in NATURAL and APPLIED SCIENCES ADVANCES in NATURAL and APPLIED SCIENCES ISSN: 1995-0772 Published BY AENSI Publication EISSN: 1998-1090 http://www.aensiweb.com/anas 2016 Special 10(6): pages 72-78 Open Access Journal Cfd Analysis Of

More information

THE EFFECTS OF URBAN HEAT ISLAND MITIGATION STRATEGIES ON THE OUTDOOR THERMAL ENVIRONMENT IN CENTRAL TOKYO A NUMERICAL SIMULATION

THE EFFECTS OF URBAN HEAT ISLAND MITIGATION STRATEGIES ON THE OUTDOOR THERMAL ENVIRONMENT IN CENTRAL TOKYO A NUMERICAL SIMULATION The Seventh Asia-Pacific Conference on Wind Engineering, November 8-12, 2009, Taipei, Taiwan THE EFFECTS OF URBAN HEAT ISLAND MITIGATION STRATEGIES ON THE OUTDOOR THERMAL ENVIRONMENT IN CENTRAL TOKYO A

More information

An Evaluation of Heat Transfer Coefficient in an Independent Zonal Temperature Controls with CFD

An Evaluation of Heat Transfer Coefficient in an Independent Zonal Temperature Controls with CFD An Evaluation of Heat Transfer Coefficient in an Independent Zonal Temperature Controls with CFD ZHOU, Pei; WANG, Junqi; HUANG, Gongsheng Published in: Energy Procedia Published: 01/05/2017 Document Version:

More information

CFD evaluation of natural ventilation of indoor environments. by the concentration decay method: CO 2 gas dispersion. from a semi-enclosed stadium

CFD evaluation of natural ventilation of indoor environments. by the concentration decay method: CO 2 gas dispersion. from a semi-enclosed stadium van Hooff T, Blocken B, 2013. CFD evaluation of natural ventilation of indoor environments by the concentration decay method: CO 2 gas dispersion from a semi-enclosed stadium. Building and Environment

More information

MODELLING THE URBAN MICROCLIMATE AND ITS INFLUENCE ON BUILDING ENERGY DEMANDS OF AN URBAN NEIGHBOURHOOD

MODELLING THE URBAN MICROCLIMATE AND ITS INFLUENCE ON BUILDING ENERGY DEMANDS OF AN URBAN NEIGHBOURHOOD MODELLING THE URBAN MICROCLIMATE AND ITS INFLUENCE ON BUILDING ENERGY DEMANDS OF AN URBAN NEIGHBOURHOOD J. Allegrini 1,2 ; J. Kämpf 3 ; V. Dorer 1 ; J. Carmeliet 1,2 1: Empa, Laboratory for Building Science

More information

Air Pollutant Dispersion from a Large Semi- Enclosed Stadium in an Urban Area: High- Resolution CFD Modeling versus Full-Scale Measurements

Air Pollutant Dispersion from a Large Semi- Enclosed Stadium in an Urban Area: High- Resolution CFD Modeling versus Full-Scale Measurements International Congress on Environmental Modelling and Software Brigham Young University BYU ScholarsArchive 6th International Congress on Environmental Modelling and Software - Leipzig, Germany - July

More information

EFFECT OF COMBINED HOLE CONFIGURATION ON FILM COOLING WITH AND WITHOUT MIST INJECTION

EFFECT OF COMBINED HOLE CONFIGURATION ON FILM COOLING WITH AND WITHOUT MIST INJECTION THERMAL SCIENCE: Year 2018, Vol. 22, No. 5, pp. 1923-1931 1923 EFFECT OF COMBINED HOLE CONFIGURATION ON FILM COOLING WITH AND WITHOUT MIST INJECTION by Ke TIAN a, Jin WANG a*, Chao LIU a, Jakov BALETA

More information

ON THE ENERGY CONSUMPTION OF HIGH- AND LOW-LEVEL AIR SUPPLIES

ON THE ENERGY CONSUMPTION OF HIGH- AND LOW-LEVEL AIR SUPPLIES ON THE ENERGY CONSUMPTION OF HIGH- AND LOW-LEVEL AIR SUPPLIES T. Karimipanah 1, H. B. Awbi 2 and B. Moshfegh 1 1 University of Gävle, Sweden 2 University of Reading, UK Email: taghi.k@comhem.se, h.b.awbi@rdg.ac.uk,

More information

Verification and Validation of Preliminarily Result of CFD of Electrostatic Precipitator Mr.Dharmendra Dekate 1 Mr.K.M.Narkar 2

Verification and Validation of Preliminarily Result of CFD of Electrostatic Precipitator Mr.Dharmendra Dekate 1 Mr.K.M.Narkar 2 IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 01, 015 ISSN (online): 31-013 Verification and Validation of Preliminarily Result of CFD of Electrostatic Precipitator

More information

Dr. J. Wolters. FZJ-ZAT-379 January Forschungszentrum Jülich GmbH, FZJ

Dr. J. Wolters. FZJ-ZAT-379 January Forschungszentrum Jülich GmbH, FZJ Forschungszentrum Jülich GmbH, FZJ ZAT-Report FZJ-ZAT-379 January 2003 Benchmark Activity on Natural Convection Heat Transfer Enhancement in Mercury with Gas Injection authors Dr. J. Wolters abstract A

More information

consumption. As the first step of calculating indoor energy consumption, this study investigated the net radiation heat gain of building exterior surf

consumption. As the first step of calculating indoor energy consumption, this study investigated the net radiation heat gain of building exterior surf Analysis of the Net Radiation Heat Gain of Buildings by Changing Building Distance in Guangzhou and Sendai J. HU 1,*, Y. XUAN 2, and A. MOCHIDA 1 1 Graduate School of Engineering, Tohoku University, Sendai,

More information

H AIR QUALITY MODELLING OF ROAD PROJECTS USING A 3D COMPUTATIONAL FLUID DYNAMICS (CFD) MODEL. Malo Le Guellec, Lobnat Ait Hamou, Amita Tripathi

H AIR QUALITY MODELLING OF ROAD PROJECTS USING A 3D COMPUTATIONAL FLUID DYNAMICS (CFD) MODEL. Malo Le Guellec, Lobnat Ait Hamou, Amita Tripathi H13-198 AIR QUALITY MODELLING OF ROAD PROJECTS USING A 3D COMPUTATIONAL FLUID DYNAMICS (CFD) MODEL Malo Le Guellec, Lobnat Ait Hamou, Amita Tripathi FLUIDYN France, Saint-Denis, France Abstract: The air

More information

Systematic comparison of the influence of cool wall versus cool roof adoption

Systematic comparison of the influence of cool wall versus cool roof adoption Systematic comparison of the influence of cool wall versus cool roof adoption on urban climate in the Los Angeles basin Jiachen Zhang 1, Arash Mohegh 1, Yun Li 1, Ronnen Levinson 2, George Ban-Weiss 1,*

More information

Document Version Publisher s PDF, also known as Version of Record (includes final page, issue and volume numbers)

Document Version Publisher s PDF, also known as Version of Record (includes final page, issue and volume numbers) Air pollutant dispersion from a large semi-enclosed stadium in an urban area: high-resolution CFD modeling versus full-scale measurements van Hooff, T.; Blocken, B. Published in: Proceedings of the International

More information

Investigation on Core Downward Flow by a Passive Residual Heat Removal System of Research Reactor

Investigation on Core Downward Flow by a Passive Residual Heat Removal System of Research Reactor Investigation on Core Downward Flow by a Passive Residual Heat Removal System of Research Reactor W.K. Lee 1, S.J. Kim 1, D.Y. Lee 1, W.K. Hwang 1, K.Y. Lee 1 1) Department of Mechanical and Control Engineering,

More information

CFD Simulation in Township Planning A Case Study

CFD Simulation in Township Planning A Case Study International Journal Of Computational Engineering Research (ijceronline.com) Vol. 3 Issue. 3 CFD Simulation in Township Planning A Case Study 1, Nilesh S. Varkute, 2, R.S. Maurya 1 Sardar Patel College

More information

A COMPARATIVE STUDY OF DIFFERENT AIR DISTRIBUTION SYSTEMS IN A CLASSROOM

A COMPARATIVE STUDY OF DIFFERENT AIR DISTRIBUTION SYSTEMS IN A CLASSROOM ROOMVENT 2000, Vol. 2, pp. 1013-1018, Reading, UK, 9-12 July 2000. A COMPARATIVE STUDY OF DIFFERENT AIR DISTRIBUTION SYSTEMS IN A CLASSROOM T. Karimipanah 1, M. Sandberg 2, and H.B. Awbi 3 1 Air Innovation

More information

MODELLING COMBUSTION AND THERMAL NO X FORMATION IN ELECTRIC ARC FURNACES FOR THE PRODUCTION OF FERRO-SILICON AND SILICON-METAL

MODELLING COMBUSTION AND THERMAL NO X FORMATION IN ELECTRIC ARC FURNACES FOR THE PRODUCTION OF FERRO-SILICON AND SILICON-METAL MODELLING COMBUSTION AND THERMAL NO X FORMATION IN ELECTRIC ARC FURNACES FOR THE PRODUCTION OF FERRO-SILICON AND SILICON-METAL B. Ravary, C. Colomb 1 and S. T. Johansen 2 ERAMET Norway AS, c/o SINTEF Materials,

More information

Research on Ventilation Ontology of Wind Power Vehicle Bai-lin FAN 1,*, Wen-ping XIN 1, Guo-jun DING 2, Jia-qing HUANG 3 and Zeng-hui HUANG 4

Research on Ventilation Ontology of Wind Power Vehicle Bai-lin FAN 1,*, Wen-ping XIN 1, Guo-jun DING 2, Jia-qing HUANG 3 and Zeng-hui HUANG 4 2017 2nd International Conference on Environmental Science and Energy Engineering (ICESEE 2017) ISBN: 978-1-60595-417-2 Research on Ventilation Ontology of Wind Power Vehicle Bai-lin FAN 1,*, Wen-ping

More information

caused by subjective factors such as oversimplified modeling for simulation, nonuniform calculation methods, casual input parameters and boundary cond

caused by subjective factors such as oversimplified modeling for simulation, nonuniform calculation methods, casual input parameters and boundary cond Study of Standardization In The Use of Simulation Tools For Optimization and Evaluation of Green Building Performance In China Fan Lu 1, Borong Lin 1,*, and Bo Peng 1 1 Institute of Building Technology,

More information