1 Energy Audit for YWCA 1503 S. Denver Tulsa, Oklahoma 5/18/2010 Performed By 220 E. 8th Street Tulsa, Oklahoma Fax:

2 Table of Contents Cover Page... 1 Table of Contents... 2 Executive Summary... 3 Introduction Situation Report Summary of Property... 3 Current Energy and Utility Usage Potential Improvements Energy/Utility Graphs & Tables Estimated Savings and Simple Payback Analysis YWCA 1503 S. Denver Energy Audit 2

3 Executive Summary This report is the result of an energy audit performed by Crafton Tull Sparks on May 18 th Currently, the total for all yearly utility bills for this facility is $4, The electric bill is the largest at $2,799.45, the natural gas bill is next at $1, and the water bill is the lowest at $ The estimated total yearly savings for all potential improvements is $1, or 42 percent of the current total of yearly utility bills. The total simple payback is 5.3 years. Four of the potential improvements have less than three year paybacks if implemented by themselves. Cap Attic Fan, Insulate Attic, Upgrade Thermostats and Lighting Upgrade together would save $1, per year or 27 percent of the current total of yearly utility bills. The simple payback for these four potential improvements is 1.1 years. Introduction A Certified Energy Manager from Crafton Tull Sparks conducted an energy audit for the YWCA on 1503 S. Denver in Tulsa, Oklahoma. This report recommends potential improvements along with the estimated cost and energy savings from the potential improvements. This report has been kept intentionally brief and non-technical. The information represented in this report is believed to be correct. However, since Crafton Tull Sparks has no control of design and implementation details or use of the building and its components, Crafton Tull Sparks cannot be responsible for any results or lack of results from building changes undertaken following the potential improvements in this report. 1. Situation Report. Summary of Property The YWCA on 1503 S. Denver is a 2,200 square foot facility located in Tulsa, Oklahoma. The facility is office space that is dedicated to eliminating racism, empowering women and promoting peace, justice, freedom and dignity for all. Occupancy of the building is predominantly office space that is used primarily for women s counseling, a kitchenette, a large conference room, and with a unattached carriage house that is used for physical fitness taught by personal trainers. Current Energy and Utility Use The YWCA 1503 S. Denver facility uses electricity for its lighting, air conditioning and powering plug loads such as computers. Electricity is also used to heat the first floor and used to generate domestic hot water for the carriage house. The facility uses natural gas as the energy source for heating of the 2nd floor, carriage house and domestic water heating for the main building. The attached energy and water use tables illustrate the cost and consumption of electricity, natural gas and water for the facility over the past year. Charges reflected are inclusive of any customer fees, and administrative fees assessed to the account. All cost saving calculations are based on an average electric cost of $ per kwh and an average natural gas cost of $6.983 per dekatherm. YWCA 1503 S. Denver Energy Audit 3

4 2. Potential Improvements. 1. Cap Attic Fan: Cap the existing 3-foot by 3-foot attic fan louver in the ceiling of the 2 nd floor of the main building. This fan is no longer used and the louver has been abandoned in place. a. Cost of improvement - $150 b. Average annual savings of $ c. Payback of 2.2 years. 2. Insulate Attic: Blow in fiberglass or cellulose insulation (either one to be formaldehyde free and fire treated) to a level of R-19 (amount and level dependant on manufacturer), additional insulation, in the attic on top of the existing cellulose insulation estimated to be R-11. a. Cost of improvement - $600 b. Average annual savings of $ c. Payback of 0.9 years. 3. Upgrade Thermostats: Replace the two existing manual thermostats with new 7-day programmable thermostats. One thermostat is located on the 1 st floor of the main building. The other thermostat is located in the carriage house. a. Cost of improvement - $200 b. Average annual savings of $ c. Payback of 0.5 years. 4. HVAC Upgrade: Upgrade the heating and air conditioning systems in the 2 nd floor of the main building and in the carriage house. New units to have 95% condensing furnaces and 16 SEER condensing units. a. Cost of improvement - $7,500. b. Average annual savings of $ c. Payback of 7.7 years. 5. Lighting Upgrade: Upgrade Lighting systems (6 fixtures), in conference room and in SE office, from incandescent fixtures at 1,120 watts to (4 fixtures) 2-bulb, T-8 light fixtures at 264 watts with reflectors. a. Cost of improvement $ b. Average annual savings of $ c. Payback of 2.9 years. 6. Replace Doors: Replace double doors in 2 nd floor NE office. Replace single door in 2 nd floor SE kitchenette. Replace double doors in 1 st floor NW conference room. Replace single door in 1 st floor SE office. a. Cost of improvement $1, b. Average annual savings of $ c. Payback of 13.2 years. YWCA 1503 S. Denver Energy Audit 4

5 3. Energy/Utility Graphs & Tables. Electrical Data 12,000 $ Electrical Usage, kwh 10,000 8,000 6,000 4,000 2,000 $ $ $ $ $ $ Electrical Cost Electrical Consumption kwh Electrical Cost 0 May-09 Jun-09 Jul-09 Aug-09 Sep-09 Oct-09 Nov-09 Dec-09 Month Jan-10 Feb-10 Mar-10 Apr-10 $0.00 Outdoor Franchise Energy Fuel Rate Billing Cycle kwh Usage Light Cost Fee Cost Fee Total May-09 1,613 $12.26 $2.28 $ ($17.10) $ Jun-09 3,771 $11.73 $4.97 $ ($48.24) $ Jul-09 4,574 $11.73 $5.91 $ ($58.51) $ Aug-09 3,868 $11.73 $5.08 $ ($49.48) $ Sep-09 2,275 $11.68 $3.18 $ ($29.10) $ Oct-09 1,837 $11.68 $2.67 $ ($23.50) $ Nov-09 1,854 $11.68 $2.28 $ ($23.72) $ Dec-09 4,750 $11.68 $4.90 $ ($33.88) $ Jan-10 11,256 $11.78 $9.11 $ ($181.56) $ Feb-10 6,835 $11.79 $5.90 $ ($110.25) $ Mar-10 3,535 $11.87 $3.55 $ ($57.02) $ Apr-10 1,543 $13.77 $2.61 $ $2.48 $ Year Totals 47,711 2, YWCA 1503 S. Denver Energy Audit 5

6 Natural Gas Data $ $ Natural Gas Usage, Dekatherm Apr-09 May-09 Jun-09 Jul-09 Aug-09 Sep-09 Oct-09 Month Nov-09 Dec-09 Jan-10 Feb-10 Mar-10 $ $ $ $ $50.00 $0.00 Natrual Gas Cost Gas Consumption Dekatherm Natural Gas Cost Billing Dekatherm Cost of Energy ONG Late Cycle Usage Mcf Service Cost Franchise fee Fee Total Apr $33.00 $12.18 $1.40 $0.00 $46.58 May $32.77 $9.45 $1.31 $0.70 $44.23 Jun $34.19 $9.38 $1.35 $0.66 $45.58 Jul $34.19 $9.40 $1.35 $0.00 $44.94 Aug $34.06 $7.85 $1.29 $0.00 $43.20 Sep $34.40 $14.21 $1.50 $0.00 $50.11 Oct $35.61 $24.20 $1.85 $0.00 $61.66 Nov $43.94 $ $4.97 $0.92 $ Dec $44.08 $ $9.22 $0.00 $ Jan $43.05 $ $7.05 $0.00 $ Feb $42.41 $ $5.38 $0.00 $ Mar $41.39 $47.90 $2.76 $2.69 $94.74 Year Totals $ 4.97 $1, YWCA 1503 S. Denver Energy Audit 6

7 Water Data $30.00 Water Usage, 1000 gallons May-09 Jun-09 Jul-09 Aug-09 Sep-09 Oct-09 Nov-09 Dec-09 Month Jan-10 Feb-10 Mar-10 Apr-10 $25.00 $20.00 $15.00 $10.00 $5.00 $0.00 Water Cost Water Consumption, 1000 gallons Water Cost 1000 gallon 1000 gallon Refuse Water Sewer Storm Billing Cycle Usage Sewer Fees Charge Cost Cost Water Total May $8.16 $2.38 $7.88 $12.66 $15.81 $46.89 Jun $8.16 $2.38 $25.61 $41.15 $15.81 $93.11 Jul $8.16 $2.38 $5.91 $9.50 $15.81 $41.76 Aug $8.16 $2.38 $7.88 $12.66 $15.81 $46.89 Sep $8.16 $2.38 $7.88 $12.66 $15.81 $46.89 Oct $8.70 $2.38 $6.09 $10.47 $16.29 $43.93 Nov $8.70 $2.38 $6.09 $10.47 $16.29 $43.93 Dec $8.70 $2.38 $4.06 $6.98 $16.29 $38.41 Jan $8.70 $2.38 $2.03 $3.49 $16.29 $32.89 Feb $8.70 $7.14 $0.00 $0.00 $16.29 $32.13 Mar $8.70 $4.76 $4.06 $6.98 $16.29 $40.79 Apr $8.70 $4.76 $6.09 $10.47 $16.29 $46.31 Year Totals 42.0 $ YWCA 1503 S. Denver Energy Audit 7

8 4. Estimated Savings and Simple Payback Analysis. Cap Attic Fan Estimated Current HVAC Electrical Usage 29,711 kwh Size of estimated openings for attic fan 135 In 2 Electrical Energy lost from openings 630 kwh Estimated $ Savings from Electrical $42.71 Estimated Current HVAC Gas Usage 103 dekatherm Size of estimated openings for attic fan 2,700 In 2 Natural gas energy lost from openings 3.53 dekatherm Estimated $ Savings from Gas usage $24.65 Total Estimated Savings from cap attic fan $67.36 Cost of improvement $150 Simple Payback 2.23 yrs Insulate Attic Estimated Current HVAC Electrical Usage 29,711 kwh Effective area of 2 nd floor ceiling 1300 ft 2 Electrical Energy lost (R-11 exist, R-30 new) 7, kwh Estimated $ Savings from Electrical $ Estimated Current HVAC Gas Usage 103 dekatherm Effective area of 2 nd floor ceiling 1300 ft 2 Natural gas energy lost (R-11 exist, R-30 new) dekatherm Estimated $ Savings from Gas usage $ Total Estimated savings from insulate attic $ Cost of improvement $600 Simple Payback 0.9 yrs (or 11 Months) YWCA 1503 S. Denver Energy Audit 8

9 Upgrade Thermostats Estimated Current HVAC Electrical Usage 29,711 kwh Run-time saved for programmable stats 13.5 % Estimated Electrical Savings from new stats 4,011 kwh Estimated $ Savings from Electrical $ Estimated Current HVAC Gas Usage 103 dekatherm Run-time saved for programmable stats 20 % Estimated Natural gas savings from new stats 20.6 dekatherm Estimated $ Savings from Gas usage $ Total Estimated $ Savings from thermostats $ Cost of improvement $200 Simple Payback 0.48 yrs (or 5.8 Months) YWCA 1503 S. Denver Energy Audit 9

10 HVAC Upgrade Estimated Current HVAC Electrical Usage 29,711 kwh Amount estimated for two units to be replaced 14,855.5 kwh Current HVAC EER 10 Proposed HVAC EER 16 Energy Eff. Improvement 60% Estimate Electrical Savings from Eff. Imp. 8,913.3 kwh Run-time saved for programmable stats 20% Estimate Electrical Savings from new stats 1, kwh Estimate of Total Electrical Savings HVAC 10, kwh Estimated $ Savings from Electrical $ Estimated Current HVAC Gas Usage 103 dekatherm Amount estimated for two units to be replaced 103 dekatherm Current HVAC EFF 76 Proposed HVAC EFF 95 Energy Eff. Improvement 25% Estimate Natural Gas Savings dekatherm Run-time saved for programmable stats 20% Estimate Gas Savings from new stats dekatherm Estimate of Total Gas Savings HVAC 41.2 dekatherm Estimated $ Savings from Natural Gas $ Total Estimated $ Savings from HVAC $ Cost of improvement $7,500 Simple Payback 7.7 yrs YWCA 1503 S. Denver Energy Audit 10

11 Lighting Upgrade Existing Lights 1,120 Watt New Lights (including ballasts) 264 Watt Current Light Operation 9 hrs/day Days per Week 5 Existing number of Lights 6 Proposed number of Lights 4 Current Energy Usage kwh/day 2,620.8 kwh/yr New Energy Usage kwh/day kwh/yr Energy Reduction 2, kwh/yr Estimated $ Savings from lighting upgrade $ Cost of improvement $400 Simple Payback 2.95 yrs Replace Doors Estimated Current HVAC Electrical Usage 29,711 kwh Effective area of doors to be replaced 126 ft 2 Estimated electrical Energy lost 1, kwh Estimated $ Savings from Electrical $ Estimated Current HVAC Gas Usage 103 dekatherm Estimated natural gas energy lost 5.15 dekatherm Estimated $ Savings from Gas usage $35.96 Total Estimated savings from insulate attic $ Cost of improvement $1,800 Simple Payback yrs YWCA 1503 S. Denver Energy Audit 11

Farm Energy IQ. Future. Tom Manning, New Jersey Agricultural Experiment Station

Farm Energy IQ. Future. Tom Manning, New Jersey Agricultural Experiment Station Farm Energy IQ Farms Farm Today Energy Securing Audits Our Energy Future Tom Manning, New Jersey Agricultural Experiment Station An energy audit is the process of determining energy consumption of a building

More information

Establishing a Baseline, Energy Audits and Energy Star s Portfolio Manager

Establishing a Baseline, Energy Audits and Energy Star s Portfolio Manager Establishing a Baseline, Energy Audits and Energy Star s Portfolio Manager Glenn Barnes Environmental Finance Center University of North Carolina at Chapel Hill 919-962-2789 glennbarnes@sog.unc.edu Energy

More information

ENERGY MANAGEMENT PLAN - HEADQUARTERS. ABC Winery 123 1st Street Franklin, NJ 12345

ENERGY MANAGEMENT PLAN - HEADQUARTERS. ABC Winery 123 1st Street Franklin, NJ 12345 ENERGY MANAGEMENT PLAN - HEADQUARTERS ABC Winery 123 1st Street Franklin, NJ 12345 TABLE OF CONTENTS Executive Summary 3 Background and Site Information 3 Summary 3 Energy Conservation Opportunities 4

More information

ENERGY AUDIT. 123 Main Street Mississauga, Ontario. January 1, Report To: Mr. John Smith Smith Printing Company.

ENERGY AUDIT. 123 Main Street Mississauga, Ontario. January 1, Report To: Mr. John Smith Smith Printing Company. Report To: Mr. John Smith Smith Printing Company ENERGY AUDIT 123 Main Street Mississauga, Ontario January 1, 2009 120 Carlton Street, Suite 212 Toronto, Ontario M5A 4K2 Tel 416-964-3246 Toll Free 1-866-964-3246

More information

PV Generation Potential 17.1 kbtu/ft2/yr 15.4

PV Generation Potential 17.1 kbtu/ft2/yr 15.4 TOWNHOME PROTOTYPE HIGH PERFORMANCE 60 kbtu/sf/yr 50 kbtu/sf/yr 40 kbtu/sf/yr 30 kbtu/sf/yr 20 kbtu/sf/yr 10 kbtu/sf/yr 0 kbtu/sf/yr 54.4 Baseline 21.8 kbtu/ 2/yr 15 MMBtu 12 MMBtu 9 MMBtu 6 MMBtu 3 MMBtu

More information

2/17/2017. Energy Accounting & Education. Topics (Electricity) Creating Electricity

2/17/2017. Energy Accounting & Education. Topics (Electricity) Creating Electricity Energy Accounting & Education Energy Managers Kermit King School District of La Crosse John Daily School District of Holmen 1 Topics (Electricity) Creating electricity Defining degree days Customer charges

More information

PV Generation Potential 17.1 kbtu/ft2/yr 15.4

PV Generation Potential 17.1 kbtu/ft2/yr 15.4 TOWNHOME PROTOTYPE BASELINE 60 kbtu/sf/yr 50 kbtu/sf/yr 40 kbtu/sf/yr 30 kbtu/sf/yr 20 kbtu/sf/yr 10 kbtu/sf/yr 0 kbtu/sf/yr 54.4 Baseline 54.4 kbtu/ 2/yr 21.8 High Performance 18.2 PHIUS - IES 60 MMBtu

More information

LOW-RISE APARTMENT BUILDING PROTOTYPE HIGH PERFORMANCE PV Genera on Poten al 17.9 kbtu/ 2/yr

LOW-RISE APARTMENT BUILDING PROTOTYPE HIGH PERFORMANCE PV Genera on Poten al 17.9 kbtu/ 2/yr LOW-RISE APARTMENT BUILDING PROTOTYPE HIGH PERFORMANCE 40 kbtu/sf/yr 35 kbtu/sf/yr 30 kbtu/sf/yr 25 kbtu/sf/yr 20 kbtu/sf/yr 15 kbtu/sf/yr 10 kbtu/sf/yr 5 kbtu/sf/yr 0 kbtu/sf/yr 11.9 kbtu/ft2/yr 36.0

More information

MID-RISE APARTMENT BUILDING PROTOTYPE HIGH PERFORMANCE PV Genera on Poten al 10.8 kbtu/ 2/yr

MID-RISE APARTMENT BUILDING PROTOTYPE HIGH PERFORMANCE PV Genera on Poten al 10.8 kbtu/ 2/yr MID-RISE APARTMENT BUILDING PROTOTYPE HIGH PERFORMANCE 50 kbtu/sf/yr 45.1 PROJECT INFORMATION 40 kbtu/sf/yr 30 kbtu/sf/yr 20 kbtu/sf/yr 10 kbtu/sf/yr 0 kbtu/sf/yr 13.0 kbtu/ft2/yr Baseline 10.8 kbtu/ft2/yr

More information

Pharmaceutical Sustainability Initiatives

Pharmaceutical Sustainability Initiatives Pharmaceutical Sustainability Initiatives Duane Hagen, CEA Energy and Systems Optimization Steam and Condensate System Specialist Technical Training Instructor Primary Energy Sources Conversion of Energy

More information

National Indian Gaming Association 2005 Certification: Energy Management for Cost Savings Larry Kinney Synertech Systems Corporation On behalf of

National Indian Gaming Association 2005 Certification: Energy Management for Cost Savings Larry Kinney Synertech Systems Corporation On behalf of National Indian Gaming Association 2005 Certification: Energy Management for Cost Savings Larry Kinney Synertech Systems Corporation On behalf of CERT Wild Horse Casino in Umatilla Country, Oregon Dancing

More information

Energy Usage Reduction Program

Energy Usage Reduction Program Energy Usage Reduction Program Presented By: Samuel R. Day Earth Recycle Image Source: http://www.pfbsustainability.com/objectives.html Columbus Castings History First batch of steel melted from Parsons

More information

Comprehensive Energy Audit For Sleetmute Water Treatment Plant

Comprehensive Energy Audit For Sleetmute Water Treatment Plant Comprehensive Energy Audit For Sleetmute Water Treatment Plant Prepared For Sleetmute Traditional Council August 1, 2011 Prepared By: ANTHC-DEHE Energy Projects Group 1901 Bragaw, Suite 200 Anchorage,

More information

Comprehensive Energy Audit For Pitkas Point Tribal Office

Comprehensive Energy Audit For Pitkas Point Tribal Office Comprehensive Energy Audit For Pitkas Point Tribal Office Prepared For Native Village of Pitkas Point March 7, 2013 Prepared By: ANTHC DEHE 3900 Ambassador Drive, Suite 301 Anchorage, AK 99508 1 Table

More information

Powering Michigan Agriculture with Renewable Energy

Powering Michigan Agriculture with Renewable Energy Powering Michigan Agriculture with Renewable Energy ENERGY AUDIT & RENEWABLE ENERGY ASSESSMENT ENERGY PYRAMID MICHIGAN STATE UNIVERSITY MI Agricultural Energy Use Significant MI Dairy Farms Energy Use

More information

Greening Your Business Energy Efficiency in Buildings

Greening Your Business Energy Efficiency in Buildings Greening Your Business Energy Efficiency in Buildings Ben J. Sliwinski Building Research Council School of Architecture University of Illinois at Urbana-Champaign Overview Introduction Where is the Money?

More information

For Point. Prepared For City of Nunapitchuk. June 14, 2012 ANTHC DEHE

For Point. Prepared For City of Nunapitchuk. June 14, 2012 ANTHC DEHE Comprehensive Energy Audit For West Watering Point Prepared For City of Nunapitchuk June 14, 2012 Prepared By: ANTHC DEHE 1901 Bragaw Street, Suite 200 Anchorage, AK 99508 1 Table of Contents 1. EXECUTIVE

More information

LIBRARY ENERGY WALK- THROUGH. Andy Robinson, Training and Education, SEDAC

LIBRARY ENERGY WALK- THROUGH. Andy Robinson, Training and Education, SEDAC LIBRARY ENERGY WALK- THROUGH Andy Robinson, Training and Education, SEDAC ILLINOIS ENERGY NOW University of Illinois 360 Energy Group 2 WHAT WE DO SEDAC Free Services Outreach and Training Energy Assistance

More information

Allstream Centre Energy Performance Report

Allstream Centre Energy Performance Report Allstream Centre Energy Performance Report 2012 2014 TABLE OF CONTENTS INTRODUCTION... 1 ELECTRICAL CONSUMPTION... 2 ELECTRICAL ENERGY DISTRIBUTION... 3 BUILDING POWER AND SYSTEMS... 4 FACTORS CONTRIBUTING

More information

A Key Component of Environmental Sustainability Efforts and a Source of Substantial Cost Savings for FCGU. Dr. Simeon Komisar

A Key Component of Environmental Sustainability Efforts and a Source of Substantial Cost Savings for FCGU. Dr. Simeon Komisar ENERGY EFFICIENCY : A Key Component of Environmental Sustainability Efforts and a Source of Substantial Cost Savings for FCGU Dr. Simeon Komisar Environmental Sustainability Committee Member Associate

More information

PacifiCorp Annual Review of DSM Programs California

PacifiCorp Annual Review of DSM Programs California PacifiCorp 2009 Annual Review of DSM Programs California PacifiCorp Demand Side Management Team 3/15/2010 Table of Contents Introduction... 2 2009 Performance and Activity... 3 Stakeholder Meetings, Communications

More information

Results and Recommendations from Energy Audit of Shageluk. For VEEP Grants Village of Shageluk, Alaska

Results and Recommendations from Energy Audit of Shageluk. For VEEP Grants Village of Shageluk, Alaska ENERGY AUDIT POST INSTALLATION REPORT Results and Recommendations from Energy Audit of Shageluk For VEEP Grants Village of Shageluk, Alaska June 21, 2012 Prepared By:, Inc. 6643 Brayton Drive Anchorage,

More information

WAKE TECHNICAL COMMUNITY COLLEGE SUSTAINABLE ENERGY PLAN. Energy Plan

WAKE TECHNICAL COMMUNITY COLLEGE SUSTAINABLE ENERGY PLAN. Energy Plan Energy Plan 1 EXECUTIVE SUMMARY SCORECARD RESULTS An assessment of current energy management efforts was performed; current performance falls into all categories on the SEP-Performance Scorecard (Appendix

More information

Comprehensive Energy Audit For. Savoonga Water Treatment Plant

Comprehensive Energy Audit For. Savoonga Water Treatment Plant Comprehensive Energy Audit For Savoonga Water Treatment Plant Prepared For: City of Savoonga August 30, 2010 Prepared By: ANTHC-DEHE Energy Projects Group 1901 Bragaw St. Suite 200 Anchorage, AK 99508

More information

Xavier University of Louisiana

Xavier University of Louisiana Annual Savings Report Year 2 May 1, 2012 to April 30, 2013 July 2013 For Marion Bracy Vice President Xavier University Facilities Planning 1 Drexel Drive New Orleans LA 70125 (504) 520 1056 Submitted By

More information

BRICK TOWNSHIP BOARD OF EDUCATION EMMA HAVENS YOUNG ELEMENTARY SCHOOL 43 DRUM POINT ROAD BRICK, NJ FACILITY ENERGY REPORT

BRICK TOWNSHIP BOARD OF EDUCATION EMMA HAVENS YOUNG ELEMENTARY SCHOOL 43 DRUM POINT ROAD BRICK, NJ FACILITY ENERGY REPORT BRICK TOWNSHIP BOARD OF EDUCATION EMMA HAVENS YOUNG ELEMENTARY SCHOOL 43 DRUM POINT ROAD BRICK, NJ 08723 FACILITY ENERGY REPORT TABLE OF CONTENTS I. HISTORIC ENERGY CONSUMPTION/COST... 2 II. FACILITY DESCRIPTION...

More information

Electric Forward Market Report

Electric Forward Market Report Mar-01 Mar-02 Jun-02 Sep-02 Dec-02 Mar-03 Jun-03 Sep-03 Dec-03 Mar-04 Jun-04 Sep-04 Dec-04 Mar-05 May-05 Aug-05 Nov-05 Feb-06 Jun-06 Sep-06 Dec-06 Mar-07 Jun-07 Sep-07 Dec-07 Apr-08 Jun-08 Sep-08 Dec-08

More information

Comprehensive Energy Audit For Chevak Vacuum Plant

Comprehensive Energy Audit For Chevak Vacuum Plant Comprehensive Energy Audit For Chevak Vacuum Plant Prepared For City of Chevak March 30, 2013 Prepared By: ANTHC-DEHE 3900 Ambassador Drive, Suite 301 Anchorage, AK 99508 1 Table of Contents 1. EXECUTIVE

More information

NWC District Energy Campus Energy - RFQ Supporting Documentation. April 25, 2018

NWC District Energy Campus Energy - RFQ Supporting Documentation. April 25, 2018 NWC District Energy Campus Energy - RFQ Supporting Documentation April 25, 2018 ESTIMATED ENERGY DEMAND BY BUILDING Facility Name Area Energy Use Intensity Goal Estimated Total Energy Total Average Peak

More information

A New Type of Hybrid Groundwater Energy System

A New Type of Hybrid Groundwater Energy System This case-history is about: A New Type of Hybrid Groundwater Energy System by Todd Giddings, Ph.D., P.G. My 10,000 square foot office building Located in State College, PA (5,600 hdd s) Constructed in

More information

Green Buildings Make Cents

Green Buildings Make Cents Green Buildings Make Cents Jay Moore, Vice President, AIA Carrie Webster, Environmental Analyst, LEED AP Virginia Association of Counties Annual Conference November 10, 2008 PERCEPTION REALITY Third Creek

More information

Comprehensive Energy Audit For Kongiganak Health Clinic

Comprehensive Energy Audit For Kongiganak Health Clinic Comprehensive Energy Audit For Kongiganak Health Clinic Prepared For Native Village of Kongiganak September 15, 2011 Prepared By: ANTHC DEHE Energy Projects Group Anchorage, Alaska 99508 1 Table of Contents

More information

Comprehensive Energy Audit For Eek Tribal Office/City Office

Comprehensive Energy Audit For Eek Tribal Office/City Office Comprehensive Energy Audit For Eek Tribal Office/City Office Prepared For: Native Village of Eek And City of Eek August 5, 2011 Prepared By: ANTHC-DEHE Energy Projects Group 1901 Bragaw St. Suite 200 Anchorage,

More information

Findings through Nov. 2016

Findings through Nov. 2016 BUILDING ENERGY SAVING ORDINANCE (BESO) DECEMBER 7, 2016 Findings through Nov. 2016 BESO Basics Update to RECO/CECO requiring tailored energy assessment at time of sale or periodically, based on building

More information

Lawrence Township Municipal Building / EMS Garage 357 Main Street Cedarville, NJ 08311

Lawrence Township Municipal Building / EMS Garage 357 Main Street Cedarville, NJ 08311 Steven Winter Associates, Inc. 293 Route 18 South, Suite 330 Telephone: (866) 676-1972 Architects and Engineers East Brunswick, NJ 08816 E-mail:swinter@swinter.com www.swinter.com March 18 th, 2010 Local

More information

2011 Residential Environmental Program Series

2011 Residential Environmental Program Series 2011 Residential Environmental Program Series Feb. 16 Creating a collaborative community March 2 The complete home energy angler March 16 Xeriscape: beyond the basics March 23 Energy and water efficient

More information

BB&E GREENHOUSE GAS EMISSIONS INVENTORY. Prepared For: General Services Administration (GSA) Joint Base Andrews, Maryland.

BB&E GREENHOUSE GAS EMISSIONS INVENTORY. Prepared For: General Services Administration (GSA) Joint Base Andrews, Maryland. BB&E GREENHOUSE GAS EMISSIONS INVENTORY Prepared For: General Services Administration (GSA) Joint Base Andrews, Maryland Prepared By: BB&E, Inc. July 2014 This Greenhouse Gas (GHG) Emissions Inventory

More information

Timmins and District Hospital

Timmins and District Hospital Opportunity Assessment Timmins and District Hospital Draft Report December 10 th 2013 Submitted to: Tim Prokopetz, Manager, Materials - Biomedical Engineering Timmins and District Hospital Submitted by:

More information

Campus Annual Energy Use Report

Campus Annual Energy Use Report 2017 2018 Campus Annual Energy Use Report Macalester College 2017 2018 Energy Report Contents Year at a Glance... 3 Executive Summary... 3 Fuel Consumption & Cost... 4 Campus Fuel Consumption... 4 Campus

More information

Administration Division Public Works Department Anchorage: Performance. Value. Results.

Administration Division Public Works Department Anchorage: Performance. Value. Results. Administration Division Anchorage: Performance. Value. Results. Mission Provide administrative, budgetary, fiscal, and personnel support to ensure departmental compliance with Municipal policies and procedures,

More information

Hamilton Way - Case Study of a High Performance Community in a Cold Climate

Hamilton Way - Case Study of a High Performance Community in a Cold Climate March 11, 2010 Northeast Sustainable Energy Association Conference Peter Baker, P.Eng. Building Science Corporation Chris Nelson Nelson Construction Hamilton Way - Case Study of a High Performance Community

More information

FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION. Florida Department of Business and Professional Regulation - Residential Performance Method

FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION. Florida Department of Business and Professional Regulation - Residential Performance Method FORM R405-204 FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: Merryplace Homes Type III

More information

FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION. Florida Department of Business and Professional Regulation - Residential Performance Method

FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION. Florida Department of Business and Professional Regulation - Residential Performance Method FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance Method Project Name: Merryplace Homes Type II Builder Name:

More information

Solar Energy Case Study Webinar

Solar Energy Case Study Webinar Solar Energy Case Study 2010 Webinar JOE FICALORA FICALORA & ASSOCIATES & ASSOCIATES 1 What is this? The 7 Keys to DFSS Success 1. Active NPD Phase Gate Process 2. Linkage to Growth Strategy 3. Mind-Meld

More information

equest Home Energy Model ME 514 ~ HVAC Sean Rosin University of Idaho/Boise State University Spring 2016

equest Home Energy Model ME 514 ~ HVAC Sean Rosin University of Idaho/Boise State University Spring 2016 equest Home Energy Model ME 514 ~ HVAC Sean Rosin University of Idaho/Boise State University Spring 2016 ABSTRACT There is a growing need for energy modeling as commercial buildings get more and more complex.

More information

Streamlining Utility Billing Analysis and Reporting

Streamlining Utility Billing Analysis and Reporting Streamlining Utility Billing Analysis and Reporting Marlene Zacarias Rosenboom, Utility Analyst Dagoberto Rodriguez, Energy Manager The University of Texas at San Antonio Abstract The University of Texas

More information

Condenser Water Heat Recovery"

Condenser Water Heat Recovery PLEASE MUTE CELL PHONES Condenser Water Heat Recovery" Julian de Bullet ASHRAE Distinguished Lecturer Director of Industry Relations McQuay International 703-395-5054 1 What Is Sustainability? sustainable

More information

Sample Reports. for. HAP v4.80 Example Problem

Sample Reports. for. HAP v4.80 Example Problem Sample Reports for HAP v4.80 Example Problem October, 2013 Carrier Software Systems Copyright 2013 Carrier Corporation, All Rights Reserved Introduction This document contains reports generated using the

More information

Hotels: Water and Energy

Hotels: Water and Energy Hotels: Water and Energy Agenda 01 Introduction 05 Hotel System Options 02 Company Overview 06 Hotel Energy Conservation 03 Hotel Energy & Water Use 07 Hotel Project Examples 04 Design Philosophy Introduction

More information

Low-Hanging Fruit Simple Steps Toward Energy Effective Building Operations

Low-Hanging Fruit Simple Steps Toward Energy Effective Building Operations Low-Hanging Fruit Simple Steps Toward Energy Effective Building Operations Roger Ebbage Northwest Water / Energy Education Institute Lane Community College May 7-9 Enzian Inn - Leavenworth, Washington

More information

Pennsylvania Watt Watchers. Business Programs

Pennsylvania Watt Watchers. Business Programs Pennsylvania Watt Watchers Business Programs Why does a utility company want me to reduce electricity usage? Pennsylvania Act 129 Signed into law by Governor Rendell - October 2008. Establishes new requirements

More information

Hamilton Board of Education Greenwood Elementary School Hamilton, NJ 08610

Hamilton Board of Education Greenwood Elementary School Hamilton, NJ 08610 Steven Winter Associates, Inc. 50 Washington Street Telephone (203) 857-0200 Architects and Engineers Norwalk, CT 06854 Facsimile (203) 852-0741 www.swinter.com E-mail: swinter@swinter.com July 17, 2009

More information

For Newtok. Prepared For. March 16, 2012 ANTHC DEHE

For Newtok. Prepared For. March 16, 2012 ANTHC DEHE Comprehensive Energy Audit For Newtok Triball Court Prepared For Newtok Village March 16, 2012 Prepared By: ANTHC DEHE 1901 Bragaw Suite 200 Anchorage, Alaska 99508 1 Table of Contents 1. EXECUTIVE SUMMARY...

More information

Energy Savings Progress

Energy Savings Progress Energy Savings Progress Woodbine & West Union Main Street Districts Woodbine and West Union, designated as Main Street Iowa communities by the Iowa Economic Development Authority (IEDA), were selected

More information

HOWELL TOWNSHIP SCHOOLS TAUNTON ELEMENTARY SCHOOL FACILITY ENERGY REPORT 4 TAUNTON DR HOWELL, NJ 07731

HOWELL TOWNSHIP SCHOOLS TAUNTON ELEMENTARY SCHOOL FACILITY ENERGY REPORT 4 TAUNTON DR HOWELL, NJ 07731 HOWELL TOWNSHIP SCHOOLS TAUNTON ELEMENTARY SCHOOL 4 TAUNTON DR HOWELL, NJ 07731 FACILITY ENERGY REPORT TABLE OF CONTENTS I. HISTORIC ENERGY CONSUMPTION/COST... 2 II. FACILITY DESCRIPTION... 7 III. MAJOR

More information

EAST ORANGE SCHOOL DISTRICT DIONNE WARWICK INSTITUTE FACILITY ENERGY REPORT 120 CENTRAL AVENUE EAST ORANGE, NEW JERSEY 07017

EAST ORANGE SCHOOL DISTRICT DIONNE WARWICK INSTITUTE FACILITY ENERGY REPORT 120 CENTRAL AVENUE EAST ORANGE, NEW JERSEY 07017 EAST ORANGE SCHOOL DISTRICT DIONNE WARWICK INSTITUTE 120 CENTRAL AVENUE EAST ORANGE, NEW JERSEY 07017 FACILITY ENERGY REPORT East Orange School District Dionne Warwick Institute TABLE OF CONTENTS I. HISTORIC

More information

Hamilton Board of Education Robinson Elementary School Hamilton, NJ 08610

Hamilton Board of Education Robinson Elementary School Hamilton, NJ 08610 Steven Winter Associates, Inc. 50 Washington Street Telephone (203) 857-0200 Architects and Engineers Norwalk, CT 06854 Facsimile (203) 852-0741 www.swinter.com E-mail: swinter@swinter.com July 17, 2009

More information

PERFORMANCE REPORT. Building Performance Partnership. January 2011 U.S. GREEN BUILDING COUNCIL

PERFORMANCE REPORT. Building Performance Partnership. January 2011 U.S. GREEN BUILDING COUNCIL 2010 PERFORMANCE REPORT Building Performance Partnership January 2011 U.S. GREEN BUILDING COUNCIL Introduction USGBC would like to thank you for partnering with us to raise awareness of the importance

More information

Natural Gas. April Click on each slide to proceed to the next one.

Natural Gas. April Click on each slide to proceed to the next one. Natural Gas April 2008 Click on each slide to proceed to the next one. Physical Flow of Natural Gas before Deregulation [ Producers] [ 4 Pipelines] [ Homes & Businesses] [ Washington Gas] More Market Participants

More information

For. Prepared For ANTHC DEHE

For. Prepared For ANTHC DEHE Comprehensive Energy Audit For Tuluksakk Health Clinic Prepared For Tuluksak Native Community February 7, 20122 Prepared By: ANTHC DEHE 1901 Bragaw, Suite 200 Anchorage, AK 99508 1 Table of Contents 1.

More information

Using Renewable Energy in Dairy Production. Brad Heins West Central Research and Outreach Center Morris, MN

Using Renewable Energy in Dairy Production. Brad Heins West Central Research and Outreach Center Morris, MN Using Renewable Energy in Dairy Production Brad Heins West Central Research and Outreach Center Morris, MN WCROC Dairy Herds Organic herd 130 cows 40 lbs milk, 4.4% fat, 3.5% protein, 265 SCC Milk price:

More information

August 19, Building Science. Corporation August 19,

August 19, Building Science. Corporation August 19, August 19, 28 Effects of Air Conditioner Sizing on Energy Consumption and Peak Demand in a Hot Dry Climate ACEEE Summer Study on Energy Efficiency in Buildings Aaron Townsend and Kohta Ueno I Am Not the

More information

Comprehensive Energy Audit For Sleetmute Tribal Office

Comprehensive Energy Audit For Sleetmute Tribal Office Comprehensive Energy Audit For Sleetmute Tribal Office Prepared For Traditional Council of Sleetmute August 17, 2011 Prepared By: ANTHC Energy Projects Group 1901 Bragaw St. Suite 200 Anchorage, AK 99508

More information

TUR Continuing Education Conference November 20, 2008 PHILIPS

TUR Continuing Education Conference November 20, 2008 PHILIPS TUR Continuing Education Conference November 20, 2008 1. Who we are and what we do 2. The process we used for Asset Selection 3. Resource Conservation Plan for Water and Expected Change in Facility Wide

More information

MAYWOOD BOARD OF EDUCATION MEMORIAL ELEMENTARY SCHOOL ENERGY ASSESSMENT. For NEW JERSEY BOARD OF PUBLIC UTILITIES CHA PROJECT NO.

MAYWOOD BOARD OF EDUCATION MEMORIAL ELEMENTARY SCHOOL ENERGY ASSESSMENT. For NEW JERSEY BOARD OF PUBLIC UTILITIES CHA PROJECT NO. MAYWOOD BOARD OF EDUCATION MEMORIAL ELEMENTARY SCHOOL ENERGY ASSESSMENT For NEW JERSEY BOARD OF PUBLIC UTILITIES CHA PROJECT NO. 24473 September 2012 Prepared by: 6 Campus Drive Parsippany, NJ 07054 (973)

More information

Deep Dive Into Process Efficiency AEP November 14, 2017

Deep Dive Into Process Efficiency AEP November 14, 2017 Deep Dive Into Process Efficiency AEP November 14, 2017 Kelly Kissock Ph.D., P.E. Department of Mechanical and Aerospace Engineering / Renewable and Clean Energy University of Dayton, Dayton Ohio, U.S.A.

More information

Results and Recommendations from Energy Audit of Koyukuk. For VEEP Grants. City of Koyukuk, Alaska

Results and Recommendations from Energy Audit of Koyukuk. For VEEP Grants. City of Koyukuk, Alaska ENERGY AUDIT POST INSTALLATION REPORT Results and Recommendations from Energy Audit of Koyukuk For VEEP Grants City of Koyukuk, Alaska June 20, 2012 Prepared By:, Inc. 6643 Brayton Drive Anchorage, AK

More information

Comprehensive Energy Audit For Community Building

Comprehensive Energy Audit For Community Building Comprehensive Energy Audit For Community Building Prepared For Hooper Bay Tribal Council June 29, 2012 Prepared By: ANTHC 1901 Bragaw St. Suite 200 Anchorage, AK 99508 1 Table of Contents 1. EXECUTIVE

More information

ENERGY EFFICIENT RETROFIT OF A HIGH-RISE MULTIFAMILY BUILDING

ENERGY EFFICIENT RETROFIT OF A HIGH-RISE MULTIFAMILY BUILDING ENERGY EFFICIENT RETROFIT OF A HIGH-RISE MULTIFAMILY BUILDING Brittany Hanam 1, Lorne Ricketts 2, Andrew Pape-Salmon 3 ABSTRACT The National Institute of Building Sciences estimates that over 70% of the

More information

Energy 10/19/2011. Inc. New. Castle, DEE. Image. By: Skanska

Energy 10/19/2011. Inc. New. Castle, DEE. Image. By: Skanska Technical Report Two Building, Plant Energy and Emission Analysis Report 10/19/ New Castle Center for Delaware Hospice, Inc. New Castle, DEE Image By: Skanska Pennn State University Architectural Engineering

More information

For. Prepared For. June 11, 2012 ANTHC DEHE

For. Prepared For. June 11, 2012 ANTHC DEHE Comprehensive Energy Audit For Tununak Tribal Police Office Prepared For Native Village of Tununak June 11, 2012 Prepared By: ANTHC DEHE 1901 Bragaw Suite, Suite 200 Anchorage, AK 99508 1 Table of Contents

More information

Whitemarsh Township Municipal Building

Whitemarsh Township Municipal Building Whitemarsh Township Municipal Building 616 Germantown Pike, Lafayette Hill, PA 19444 Prepared For: Whitemarsh Township practical energy solutions 101 e. evans street, suite 2, west chester, pa 19380 t.610.430.1382

More information

Sound HVAC Choices for Sustainable Design. Julian de Bullet

Sound HVAC Choices for Sustainable Design. Julian de Bullet PLEASE MUTE CELL PHONES Sound HVAC Choices for Sustainable Design Julian de Bullet Director of Industry Relations McQuay International ASHRAE Distinguished Lecturer 703-395-5054 1 2 Rising?? What Is Sustainability?

More information

CHERRY HILL TOWNSHIP SCHOOLS CHERRY HILL HIGH SCHOOL EAST 1750 KRESSON ROAD CHERRY HILL, NJ FACILITY ENERGY REPORT

CHERRY HILL TOWNSHIP SCHOOLS CHERRY HILL HIGH SCHOOL EAST 1750 KRESSON ROAD CHERRY HILL, NJ FACILITY ENERGY REPORT CHERRY HILL TOWNSHIP SCHOOLS CHERRY HILL HIGH SCHOOL EAST 1750 KRESSON ROAD CHERRY HILL, NJ 08003 FACILITY ENERGY REPORT TABLE OF CONTENTS I. HISTORIC ENERGY CONSUMPTION/COST... 2 II. FACILITY DESCRIPTION...

More information

Comprehensive Energy Audit For Buckland Washeteria

Comprehensive Energy Audit For Buckland Washeteria Comprehensive Energy Audit For Buckland Washeteria Prepared For City of Buckland May 12, 2017 Prepared By: Bailey Gamble Alaska Native Tribal Health Consortium 4500 Diplomacy Dr., Suite 454 Anchorage,

More information

Using Renewable Energy in Dairy Production. Brad Heins West Central Research and Outreach Center Morris, MN

Using Renewable Energy in Dairy Production. Brad Heins West Central Research and Outreach Center Morris, MN Using Renewable Energy in Dairy Production Brad Heins West Central Research and Outreach Center Morris, MN WCROC Dairy Herds Organic herd 130 cows 40 lbs milk, 4.4% fat, 3.5% protein, 265 SCC Milk price:

More information

Water & Energy Conservation. Topics Covered

Water & Energy Conservation. Topics Covered Water & Energy Conservation Relationships & Opportunities Tony T. Gregg, P.E. Manager Water Conservation Program Austin Water Utility City of Austin, Texas Topics Covered 1. Basic Relationships Water/Energy

More information

Comprehensive Energy Audit For Akiak Health Clinic

Comprehensive Energy Audit For Akiak Health Clinic Comprehensive Energy Audit For Akiak Health Clinic Prepared For Akiak Native Community October 19, 2011 Prepared By: ANTHC-DEHE Energy Projects Group Anchorage, Alaska 99508 1 Table of Contents 1. EXECUTIVE

More information

Hamilton Board of Education Morgan Elementary School Hamilton, NJ 08619

Hamilton Board of Education Morgan Elementary School Hamilton, NJ 08619 Steven Winter Associates, Inc. 50 Washington Street Telephone (203) 857-0200 Architects and Engineers Norwalk, CT 06854 Facsimile (203) 852-0741 www.swinter.com E-mail: swinter@swinter.com July 17, 2009

More information

Rainwater tank study of new homes

Rainwater tank study of new homes Rainwater tank study of new homes Helena Amaro UWSRA Science & Stakeholder Engagement Forum #4 The objectives Determine the quantity of water savings from rainwater tanks Identify opportunities to improve

More information

Woking. q business confidence report

Woking. q business confidence report Woking q1 business confidence report Woking q1 report headlines saw a new record in company registrations in Woking when compared to any previous. was a record quarter for company registrations in Woking

More information

Puget Sound Green Infrastructure Summit 2017

Puget Sound Green Infrastructure Summit 2017 * 130,000 SF office building 5 stories above-grade * Mixed use, including 15,000 SF retail space * City of Seattle Deep Green Pilot Program Stone34 Project Overview Matt Nielsen 2017-02-13 Seattle Deep

More information

University of Michigan Eco-Driving Index (EDI) Latest data: August 2017

University of Michigan Eco-Driving Index (EDI)   Latest data: August 2017 University of Michigan Eco-Driving Index () http://www.ecodrivingindex.org Latest data: August 2017 Developed and issued monthly by Michael Sivak and Brandon Schoettle Sustainable Worldwide Transportation

More information

White Paper. HVLS Fans and Energy Savings. Dubai Case Study. Featuring Altra-Air Fans with WhalePower Technology from Envira-North Systems

White Paper. HVLS Fans and Energy Savings. Dubai Case Study. Featuring Altra-Air Fans with WhalePower Technology from Envira-North Systems HVLS Fans and Energy Savings Dubai Case Study White Paper This paper is designed to provide insight into a case study of a manufacturing facility in Dubai, UAE. At the 2,500m² air conditioned site, one

More information

Borough of Bogota Municipal Complex 375 Larch Avenue Bogota, NJ 07603

Borough of Bogota Municipal Complex 375 Larch Avenue Bogota, NJ 07603 307 7 th Avenue, Suite 1701 Telephone (866) 676-1972 Improving the Built Environment Since 1972 New York City, NY 10001 Facsimile (203) 852-0741 www.swinter.com June 4, 2012 Local Government Energy Program

More information

June 11, Local Government Energy Program Energy Audit Final Report. Franklin Lakes Ambulance Corps 1 Bender Court, Franklin Lakes, NJ 07417

June 11, Local Government Energy Program Energy Audit Final Report. Franklin Lakes Ambulance Corps 1 Bender Court, Franklin Lakes, NJ 07417 Steven Winter Associates, Inc. 293 Route 18 South, Suite #330 Telephone: (866) 676-1962 Architects and Engineers East Brunswick, NJ 08816 Web: www.swinter.com E-mail: swinter@swinter.com June 11, 2010

More information

Duke Energy Corporation

Duke Energy Corporation Commercial Audit for Account: 12345-56789 Thank you for completing the Duke Energy Corporation Business Energy Check. We hope the information and recommendations provided will assist you in managing your

More information

CONCORD ENGINEERING GROUP 520 SOUTH BURNT MILL ROAD VOORHEES, NJ TELEPHONE: (856) FACSIMILE: (856)

CONCORD ENGINEERING GROUP 520 SOUTH BURNT MILL ROAD VOORHEES, NJ TELEPHONE: (856) FACSIMILE: (856) ENERGY AUDIT FINAL REPORT BRICK TOWNSHIP M.U.A. WASTEWATER PUMPING STATIONS BRICK, NJ 08724 ATTN: MR. JAY DELANEY PROJECT MANAGER CEG PROJECT NO. CONCORD ENGINEERING GROUP 520 SOUTH BURNT MILL ROAD VOORHEES,

More information

CHP Case Studies. Midwest CHP Application Center (MAC) .org (312) University of Illinois at Chicago Energy Resources Center UIC

CHP Case Studies. Midwest CHP Application Center (MAC) .org (312) University of Illinois at Chicago Energy Resources Center UIC CHP Case Studies Midwest CHP Application Center (MAC) www.chpcentermw.org.org (312)413-5448 University of Illinois at Chicago Energy Resources Center CHP Case Studies Elgin Community College Presbyterian

More information

Energy Audit. Project: ENergy Efficiency and Renewables SUPporting Policies in Local level for EnergY (ENER-SUPPLY) Work Package 4

Energy Audit. Project: ENergy Efficiency and Renewables SUPporting Policies in Local level for EnergY (ENER-SUPPLY) Work Package 4 Project: ENergy Efficiency and Renewables SUPporting Policies in Local level for EnergY (ENER-SUPPLY) Work Package 4 Energy Audit Date: Country: SERBIA Partner: University of Novi Sad (UNS) Building: Health

More information

Renewables. Vacuum Tube Solar Systems. Solar Energy to the Power of

Renewables. Vacuum Tube Solar Systems. Solar Energy to the Power of Renewables Vacuum Tube Solar Systems Solar Energy to the Power of FREE HOT WATER FROM DAWN TO DUSK AND THROUGHOUT THE YEAR WITH Thermomax advanced vacuum tube solar systems provide hot water in all seasons.

More information

South River Appleby Avenue Firehouse South River, NJ 08882

South River Appleby Avenue Firehouse South River, NJ 08882 Steven Winter Associates, Inc. 293 Route 18 South, Suite 330 Telephone: (866) 676-1972 Architects and Engineers East Brunswick, NJ 08816 E-mail: swinter@swinter.com www.swinter.com April 30, 2010 Local

More information

Comprehensive Energy Audit For. Old Harbor Water Treatment Plant

Comprehensive Energy Audit For. Old Harbor Water Treatment Plant Comprehensive Energy Audit For Old Harbor Water Treatment Plant Prepared For City of Old Harbor August 9, 2016 Prepared By: ANTHC-DEHE 4500 Diplomacy Dr. Anchorage, AK 99508 1 Table of Contents PREFACE...

More information

June 11, Local Government Energy Program Energy Audit Report Final

June 11, Local Government Energy Program Energy Audit Report Final Steven Winter Associates, Inc. 293 Route 18 South, Suite #330 Telephone: (866) 676-1972 Architects and Engineers East Brunswick, NJ 08816 Web: www.swinter.com E-mail: swinter@swinter.com June 11, 2010

More information

Borough of Chatham Public Works and Water Plant 446 Main Street Chatham, NJ 07928

Borough of Chatham Public Works and Water Plant 446 Main Street Chatham, NJ 07928 Steven Winter Associates, Inc. 293 Route 18, Suite 330 Telephone (866) 676-1972 Building Systems Consultants East Brunswick, NJ 08816 Facsimile (203) 852-0741 www.swinter.com June 28, 2010 Local Government

More information

Premium Sample Reports

Premium Sample Reports Premium Sample Reports Under the WegoWise Premium subscription, we deliver the following reports in pdf format to present actionable information and answers to common questions property managers and owners

More information

Strategies for energy efficiency improvement in residential and office buildings: their role at building and country scale

Strategies for energy efficiency improvement in residential and office buildings: their role at building and country scale The Future Role of Energy Storage in South Eastern Europe Enlargement and Integration Action Workshop Strategies for energy efficiency improvement in residential and office buildings: their role at building

More information

Sample Reports. for. HAP v4.90 Example Problem

Sample Reports. for. HAP v4.90 Example Problem Sample Reports for HAP v4.90 Example Problem December, 2014 Carrier Software Systems Copyright 2014 Carrier Corporation, All Rights Reserved Introduction This document contains reports generated using

More information

Results and Recommendations from Energy Audit of Pilot Station. For VEEP Grants City of Pilot Station, Alaska

Results and Recommendations from Energy Audit of Pilot Station. For VEEP Grants City of Pilot Station, Alaska ENERGY AUDIT POST INSTALLATION REPORT Results and Recommendations from Energy Audit of Pilot Station For VEEP Grants City of Pilot Station, Alaska June 20, 2012 Prepared By:, Inc. 6643 Brayton Drive Anchorage,

More information

AMERICAN PSYCHOLOGICAL ASSOCIATION BUILDING 750 FIRST STREET, NE WASHINGTON, DC G Place Limited Partnership.

AMERICAN PSYCHOLOGICAL ASSOCIATION BUILDING 750 FIRST STREET, NE WASHINGTON, DC G Place Limited Partnership. AMERICAN PSYCHOLOGICAL ASSOCIATION BUILDING 750 FIRST STREET, NE WASHINGTON, DC 20001 OWner: Submitter: ~ Description: G Place Limited Partnership. Michael R. McCormick Director of Engineering Services

More information