PERCEIVED AIR QUALITY, THERMAL COMFORT, AND SBS SYMPTOMS AT LOW AIR TEMPERATURE AND INCREASED RADIANT TEMPERATURE
|
|
- Gary Turner
- 6 years ago
- Views:
Transcription
1 PERCEIVED AIR QUALITY, THERMAL COMFORT, AND SBS SYMPTOMS AT LOW AIR TEMPERATURE AND INCREASED RADIANT TEMPERATURE J Toftum *, G Reimann, P Foldbjerg, G Clausen and PO Fanger International Centre for Indoor Environment and Energy, Technical University of Denmark ABSTRACT This study investigated if low air temperature, which is known to improve the perception of air quality, also can reduce the intensity of some SBS symptoms. In a low-polluting office, human subjects were exposed to air at two temperatures 23 o C and 18 o C both with and without a pollution source present at the low temperature. To maintain overall thermal neutrality, the low air temperature was partly compensated for by individually controlled radiant heating, and partly by allowing subjects to modify clothing insulation. A reduction of the air temperature from 23 C to 18 C suggested an improvement of the perceived air quality, while no systematic effect on symptom intensity was observed. The overall indoor environment was evaluated equally acceptable at both temperatures due to local thermal discomfort at the low air temperature. INDEX TERMS Low air temperature, radiant heating, thermal comfort, perceived air quality, SBS symptoms INTRODUCTION The perception of indoor air quality depends not only on the chemical composition of the air, but also on its psychrometric properties: cool and dry air is perceived as less stuffy and more acceptable than warm and moist air (Berglund and Cain 1989, Fang et al. 1998, Toftum et al. 1998). It has been suggested that perceived air quality may influence the intensity of some SBS symptoms (Wyon 1998, Wargocki et al. 1999). Therefore, the consequences of low air temperature may not only be improved perceived air quality, but also a reduction of the intensity of SBS symptoms. Fang et al. (1999) showed that a decrease in the outdoor air supply rate from 1 L/s per person to 3.5 L/s per person could be compensated for by decreasing indoor air enthalpy from 45 kj/kg to 35 kj/kg, so as to avoid deteriorating perceived air quality. Thus, indoor air of low enthalpy could permit lower ventilation rates and in some climatic regions contribute substantially to energy conservation in buildings. To avoid compromising thermal comfort, low air temperature needs to be compensated for, e.g. by means of radiant or contact heating, preferably under individual control to accommodate inter-individual differences. The objective of this study was to determine whether indoor air at low temperature, which is known to improve perceived air quality, can also reduce SBS symptom intensity. METHODS Human subjects in a state of thermal neutrality were exposed to air at two temperatures 23 C and 18 C. To maintain overall thermal neutrality, the reduced air temperature was partly compensated for by radiant heating, controlled individually according to subjects expressed thermal sensation, and partly by allowing subjects to modify clothing insulation. At 18 o C * Contact author jt@mek.dtu.dk 267
2 experiments were conducted with and without an additional pollution source present in the office. Thermal sensation and comfort, perceived air quality and the intensity of a range of typical SBS symptoms were compared between experimental conditions. METHODS Subjects were exposed to the three experimental conditions shown in Table 1. Table 1. Experimental conditions. Condition 1 Condition 2 Condition 3 (reference) Air temperature ( C) Operative temp. ( C) Clothing insul. (clo) Radiant heating not used used used Pollution source absent absent present Experiments were conducted in an ordinary, low-polluting office space (6 x 6 m 2 ) located at the Technical University of Denmark. The office was equipped with a ventilation and airconditioning system hidden for the subjects behind a screen (Figure 1). Under all experimental conditions, the ventilation rate was kept constant at 6 h -1 corresponding to 45 L/(s person) and the humidity ratio was.42 kg/kg. The duration of all experimental sessions was three hours. Four workstations were installed in the occupied zone of the office, each consisting of a desk, a chair and a PCmonitor (PC s were located outside the office). As shown in Figure 1, the workstations were equipped with electrical radiant heating panels at each side and behind the subject's chair. An additional panel to prevent cold legs was mounted under the desk. The surface temperature of the radiant panels, and thus the operative temperature, was controlled individually for each workstation, based on the subject's thermal sensation vote. The surface temperature of the three vertical panels at each workstation was jointly controlled, whereas the horizontal panel was Figure 1. Experimental set-up in the office. controlled separately. Subjects were not aware that the surface temperature of the heating panels was adjusted. The pollution source was 8 m 2 of 2-years-old tufted bouclé carpet with 1% polyamid fibres and latex backing, which had been removed from a building with a history of indoor environment complaints. The carpet was cut into 2 x.2 m 2 pieces that were attached back-toback and hung on a mobile stainless steel rack. Mixing fans located at different positions ensured full mixing of the air in the office. 268
3 A total of 28 subjects (14 females and 14 males) participated in the experiments as paid volunteers. Each subject was supposed to participate in the three experimental sessions and a prior training session, but only 23 subjects participated in the experiment with the pollution source present in the office. At each workstation, thermistors were used to measure the air temperature in the breathing zone of the subjects and the surface temperature of the radiant panels. Air velocity was measured once under each experimental condition. Air humidity and temperature were measured at the centre of the office and used as input to the control system. The ventilation rate was measured prior to or after each experiment by means of tracer gas. During the 18 min exposure, subjects were activated by simulated office work and were regularly asked to assess the air quality, overall and local thermal sensation and comfort. After 9 min of exposure, the subjects evaluated the intensity of symptoms and perceptions, including nose, throat, and eye dryness, headache, etc. on visual analogue scales (Kildesø et al. 1999). After entering the office, the subjects assessed the air quality and then began the office tasks (multiplication, proof reading, addition, and text typing), which were interrupted every min to fill in a questionnaire. To maintain an average activity level of around 1.2 met, subjects performed a short stepping exercise after 4 min and again after 13 min. At the beginning of the 18 C sessions, subjects were asked to add a fleece jacket and leg warmers to their clothing ensemble. They were instructed to keep these garments on for at least 3 min and subsequently to adjust their clothing during the remaining period to attain and maintain a neutral thermal sensation. RESULTS Physical measurements performed under each of the three experimental conditions are summarized in Table 2. Table 2. Results of physical measurements (average ± std.). Parameter 23 C Source absent Experimental condition 18 C Source absent 18 C Source present Air temp. in breathing zone ( C) 23.1 ± ± ±.5 Operative temp. ( C) 22.4 ± ± ±.8 Enthalpy (kj/kg) 36 ± 1 29 ± 1 28 ± 1 Ventilation rate (h -1 ) 5.8 ± ± ±.3 Under all experimental conditions, the physical parameters were close to the desired values. At two of the workstations, the air temperature in the breathing zone on average was.2-.3 C lower than the desired value and at the other two workstations around.3 C higher. However, this temperature difference was too modest to reveal any systematic impact on subject responses. Figure 2 shows that it was possible after 6 min to attain and maintain an average thermal sensation for the body as a whole around neutral. The thermal acceptability decreased significantly when the air temperature was reduced from 23 C to 18 C (p <.4), despite 269
4 thermal sensation being almost the same at both temperatures. Local thermal sensation votes showed that particularly hands, face and feet were perceived as colder at 18 C than at 23 C. In addition, draught, caused by too high air velocities at 18 C, resulted in local thermal discomfort being more pronounced at the low temperature (p <.8). Both these factors contributed to a decrease of thermal acceptability. Thermal sensation (7-pt) C, source absent 18 C, source absent 18 C, source present Time (min) Clearly 1 acceptable Thermal acceptability 23 C, source absent 18 C, source absent 18 C, source present Clearly -1 unacceptable Time (min) Figure 2. Average overall thermal sensation votes and average thermal acceptability votes. Figure 3 shows the acceptability of the air just after entry to the office, as an average of six assessments made during the experiment, and when re-entering after refreshing the olfactory senses outside the experimental office after 18 min. The figure indicates that with no pollution source present in the office, air at 18 C was perceived as being more acceptable than air at 23 C. With the pollution source present, the perceived air quality at 18 C was approximately the same as at 23 o C without the source, except when subjects re-entered the office. At 18ºC, the overall indoor environment was evaluated as being significantly better without the source in the office than when the source was present (p <.3) (Figure 4). Without the source present, air temperature had no influence on the evaluation of the overall indoor environment. 1 1 Acceptability C, source absent 18 C, source absent 18 C, source present Entry Average Re-entry Acceptability of overall environment C, source absent 18 C, source absent 18 C, source present Figure 3. Perceived air quality at first entry, as an average of six assessments during the experiment and at re-entry after refreshing olfactory senses (average ± std.). T exposure is shown in Figure 5. Generally, sympt symptoms varied systematically between condi Figure 4. Acceptability of the overall indoor environment (average ± std.). he average intensity of selected symptoms as expressed by subjects after 9 minutes of om intensity was modest, and none of the tions. The figure indicates that the highest 27
5 symptom intensity was observed when subjects were exposed to air at 18 C and when the pollution source was present in the office. During the experiments, subjects were activated by different typical office tasks, which also provided a measure of their mental performance. No significant differences between conditions in the speed with which the subjects completed the tasks or in the error ratio could be detected. 23 C, source absent 18 C, source absent 18 C, source present Sleepy Difficult to concentrate Tired Awake Easy to concentrate Rested Dizzy Difficult to think Strong headache Not dizzy Easy to think No headache Figure 5. Average symptom intensity (error bars show standard deviations). DISCUSSION The results of the current study suggested an improvement of the perceived air quality when the air temperature was reduced from 23 C to 18 C corresponding to the results of several earlier studies (Fang et al. 1998, 1999; Toftum et al. 1998). However, a reduction of the air temperature had no systematic effect on symptom intensity. Due to the relatively high heat load generated by the radiant heating panels, a ventilation rate of 45 L/(s pers) was needed to sustain the temperature in the low-polluting office. This ventilation rate was much higher than the minimum recommended by current standards, such as e.g. ASHRAE 62 (1996) and CR 1752 (1998). Thus, with no pollution source in the office, the comfort and health effects of reducing the air temperature were studied by further improvement of an already acceptable perceived air quality, and it is possible that more pronounced effects would appear if the reference condition was of a poorer quality. Under all experimental conditions, the total exposure time was 18 min and symptom intensity was evaluated after 9 minutes. This may have been too short for symptoms to develop, particularly in an environment that on average was perceived as acceptable by the subjects. Yet, subjects' assessments indicated that the introduction of a pollution source resulted in slightly higher symptom intensity at 18 C. While overall thermal neutrality was attained both at 23ºC and at 18ºC, thermal acceptability differed between temperatures due to local thermal discomfort caused by unwanted cooling of some body parts, including hands, feet and face. Without the pollution source present in the office, overall acceptability of the indoor environment was nearly the same at 23ºC and at 18ºC, indicating that the expected positive effects of improved perceived air quality may have been moderated by decreased thermal acceptability when subjects assessed the overall indoor environment. Introducing a pollution source significantly reduced the acceptability of the overall indoor environment. 271
6 CONCLUSIONS A reduction of the air temperature from 23 C to 18 C suggested an improvement of the perceived air quality, while no systematic effect on symptom intensity was observed after 9 min of exposure. The overall indoor environment was evaluated equally acceptable at both temperatures due to local thermal discomfort at the low air temperature. The combination of low air temperature and local heating of the body was expected to promote improved perception of the indoor environment and to result in fewer health symptoms. However, at low air temperature, local thermal discomfort problems need to be addressed in order to optimize simultaneously thermal comfort, perceived air quality and symptom intensity. ACKNOWLEDGEMENT This study was supported by the Danish Technical Research Council (STVF) as part of the research programme of the International Centre for Indoor Environment and Energy established at the Technical University of Denmark for the period REFERENCES Berglund, L.G., Cain, W., 1989: Perceived air quality and the thermal environment. Proc. IAQ 89, San Diego, pp BSR/ASHRAE Standard : Ventilation for acceptable air quality. American Society for Heating, Ventilating, and Air-Conditioning Engineers, Inc. CEN CR : Ventilation for buildings Design criteria for the indoor environment. European Committee for Standardization. Fang, L., Clausen, G., Fanger, P.O., 1998: Impact of temperature and humidity on the perception of indoor air quality. Indoor Air, 8(2), 8-9. Fang, L., Wargocki, P., Witterseh, T., Clausen, G., Fanger, P.O., 1999: Field study on the impact of temperature, humidity and ventilation on perceived air quality. Proc. of Indoor Air '99, Edinburgh, Vol. 2, pp Kildesø, J., Wyon, D., Skov, T., Schneider, T., 1999: Visual analogue scales for detecting changes in symptoms of the sick building syndrome in an intervention study. Scandinavian Journal of Work, Environment & Health, 25, Pejtersen, J., Brohus, H., Hyldgaard, C.E., Bach Nielsen, J., Valbjørn, O., Hauschildt, P., Kjærgaard, S.K., Wolkoff, P., 21: Effect of renovating an office building on occupants' comfort and health. Indoor Air, 11, Toftum, J., Jørgensen, A.S., Fanger, P.O., 1998: Upper limit for air humidity for preventing warm respiratory discomfort. Energy and Buildings, 28( 3), Wargocki, P., Wyon, D.P., Baik, Y.K., Clausen, G., Fanger, P.O., 1999: Perceived air quality, Sick Building Syndrome (SBS) symptoms and productivity in an office with two different pollution loads. Indoor Air, 9, Wyon, D.P., 1998: Documented indoor environmental effects on productivity. Presented at Danvac conference "Green Buildings", Copenhagen, 5 November. 272
SICK BUILDING SYNDROME SYMPTOMS AND PERFORMANCE IN A FIELD LABORATORY STUDY AT DIFFERENT LEVELS OF TEMPERATURE AND HUMIDITY
SICK BUILDING SYNDROME SYMPTOMS AND PERFORMANCE IN A FIELD LABORATORY STUDY AT DIFFERENT LEVELS OF TEMPERATURE AND HUMIDITY L Fang, DP Wyon, G Clausen and PO Fanger International Centre for Indoor Environment
More informationPersonal Ventilation: from research to practical use
Personal Ventilation: from research to practical use Arsen Melikov 1*, Henning Grønbæk 2, Jan Bach Nielsen 3 1 International Centre for Indoor Environment and Energy, Department of Mechanical Engineering,
More informationUse of local convective and radiant cooling at warm environment
Downloaded from orbit.dtu.dk on: Nov 01, 2018 Use of local convective and radiant cooling at warm environment Melikov, Arsen Krikor; Krejcirikova, Barbora; Kaczmarczyk, Jan; Duszyk, Marcin; Sakoi, Tomonori
More informationStandards for Ventilation, IAQ, and Thermal Comfort EVALUATION OF THE INDOOR ENVIRONMENT THERMAL ENVIRONMENT INDOOR ENVIRONMENT.
Standards for Ventilation, IAQ, and Thermal Comfort Bjarne W. Olesen, PhD. Wirsbo-Velta, Germany Adjunct professor, Technical University Denmark Chair ISO/TC159/SC5/WG1 Ergonomics of the thermal environment
More informationThermal comfort assessment of Danish occupants exposed to warm environments and preferred local air movement
Downloaded from orbit.dtu.dk on: Mar 08, 2019 Thermal comfort assessment of Danish occupants exposed to warm environments and preferred local air movement Simone, Angela; Yu, Juan ; Levorato, Gabriele
More informationThermal and air quality effects on the performance of office work
Thermal and air quality effects on the performance of office work David P. Wyon International Centre for Indoor Environment and Energy (DTU) Swegon Air Academy Stockholm 2014-11-21 ICIEE - International
More informationPERSONAL COMPUTERS POLLUTE INDOOR AIR: EFFECTS ON PERCEIVED AIR QUALITY, SBS SYMPTOMS AND PRODUCTIVITY IN OFFICES
PERSONAL COMPUTERS POLLUTE INDOOR AIR: EFFECTS ON PERCEIVED AIR QUALITY, SBS SYMPTOMS AND PRODUCTIVITY IN OFFICES Zs Bakó-Biró 1,2, P Wargocki 1, C. Weschler 1,3 and P. Ole Fanger 1 1 International Centre
More informationPRACTICAL APPLICATION OF A NEW METHOD FOR THE ASSESSMENT OF COMFORT, HEALTH AND PRODUCTIVITY IN OFFICES PAOLA M.LEARDINI, JØRN TOFTUM
SB07 New Zealand Page 1 of 10 PRACTICAL APPLICATION OF A NEW METHOD FOR THE ASSESSMENT OF COMFORT, HEALTH AND PRODUCTIVITY IN OFFICES PAOLA M.LEARDINI, JØRN TOFTUM School of Architecture and Planning,
More informationAir Movement Preference and Thermal Comfort A survey in classrooms during summer season in Brazil
Air Movement Preference and Thermal Comfort A survey in classrooms during summer season in Brazil CHRISTHINA CÂNDIDO 1,4, RICHARD DE DEAR, ROBERTO LAMBERTS 1, LEONARDO BITTENCOURT 3 1 Federal University
More informationTHE EFFECT OF USING LOW-POLLUTING BUILDING MATERIALS ON VENTILATION REQUIREMENTS AND ENERGY USE IN BUILDINGS
THE EFFECT OF USING LOW-POLLUTING BUILDING MATERIALS ON VENTILATION REQUIREMENTS AND ENERGY USE IN BUILDINGS Pawel Wargocki, Henrik N. Knudsen 2, and Monika Frontczak International Centre for Indoor Environment
More informationHuman Response to Ductless Personalized Ventilation with Local Air Cleaning: Air Quality and Prevalence of SBS Symptoms
Downloaded from orbit.dtu.dk on: Dec 20, 2017 Human Response to Ductless Personalized Ventilation with Local Air Cleaning: Air Quality and Prevalence of SBS Symptoms Dalewski, Mariusz; Bivolarova, Maria
More informationIMPROVING INDOOR AIR QUALITY IMPROVES THE PERFORMANCE OF OFFICE WORK AND SCHOOLWORK
IMPROVING INDOOR AIR QUALITY IMPROVES THE PERFORMANCE OF OFFICE WORK AND SCHOOLWORK Pawel Wargocki International Centre for Indoor Environment and Energy, Department of Mechanical Engineering, Technical
More informationHuman response to individually controlled micro environment generated with localized chilled beam
Downloaded from orbit.dtu.dk on: Jan 31, 2019 Human response to individually controlled micro environment generated with localized chilled beam Uth, Simon C. ; Nygaard, Linette; Bolashikov, Zhecho Dimitrov;
More informationPREDICTION OF THERMAL SENSATION IN NON-AIR- CONDITIONED BUILDINGS IN WARM CLIMATES
PREDICTION OF THERMAL SENSATION IN NON-AIR- CONDITIONED BUILDINGS IN WARM CLIMATES PO Fanger and J Toftum * International Centre for Indoor Environment and Energy, Technical University of Denmark ABSTRACT
More informationSTUDIES ON THERMAL COMFORT AND ENERGY CONSUMPTION OF HVAC SYSTEM
STUDIES ON THERMAL COMFORT AND ENERGY CONSUMPTION OF HVAC SYSTEM B Liu,*, N Zhu 2, RQ Zhang.Dep. Of Refrigeration, Tianjin University of Commerce, 334, lbtjcu@tjcu.edu.cn 2.Environment School, Tianjin
More informationHuman Response to Ductless Personalised Ventilation: Impact of Air Movement, Temperature and Cleanness on Eye Symptoms
Downloaded from orbit.dtu.dk on: Dec 31, 2019 Human Response to Ductless Personalised Ventilation: Impact of Air Movement, Temperature and Cleanness on Eye Symptoms Dalewski, Mariusz; Fillon, Maelys ;
More informationThermal comfort recent challenges
Thermal comfort recent challenges Quality and compliance - Thermal comfort and indoor air quality 19 November 2013 Bjarne OLESEN International Centre for Indoor Environment and Energy Technical University
More informationFindings of Field Survey for Thermal Comfort and Ventilation in US Office Buildings
Findings of Field Survey for Thermal Comfort and Ventilation in US Office Buildings Liangcai Tan 1, Samir Moujaes, HDR Inc. University of Nevada Las Vegas SUMMARY This paper presents the measured data
More informationPerformance of Ductless Personalized Ventilation in Open-Plan Office - Field Survey
Downloaded from orbit.dtu.dk on: Dec 31, 2019 Performance of Ductless Personalized Ventilation in Open-Plan Office - Field Survey Dalewski, Mariusz; Ezzat Khalifa, H. ; Melikov, Arsen Krikor Published
More informationAir heating of passive house office buildings in cold climates how high supply temperature is acceptable?
Air heating of passive house office buildings in cold climates how high supply temperature is acceptable? Axel Cablé *1, Mads Mysen 1,2, Hugo Lewi Hammer 2 and Kari Thunshelle 1 1 SINTEF Forskningsveien
More informationTaking flexibility into account in designing beam systems
Taking flexibility into account in designing beam systems Risto Kosonen and Maija Virta Halton Oy Corresponding email: risto.kosonen@halton.com SUMMARY In a modern office environment, balance is sought
More informationRadiant Floor Cooling Combined with Mixing Ventilation in a Residential Room Thermal Comfort and Ventilation Effectiveness
Downloaded from orbit.dtu.dk on: Apr 09, 2019 Radiant Floor Cooling Combined with Mixing Ventilation in a Residential Room Thermal Comfort and Ventilation Effectiveness Krajcik, Michal; Simone, Angela;
More informationHow does low relative humidity affect perceived air quality, thermal comfort and symptoms in modern office buildings in cold climates?
How does low relative humidity affect perceived air quality, thermal comfort and symptoms in modern office buildings in cold climates? Merethe Lind 1, Sverre Holøs 2*[0000-0003-1405-8724], Kari Thunshelle
More informationOptimizing Indoor Environments for Occupant Satisfaction. Presented by: Kelli Goldstone April 2016
Optimizing Indoor Environments for Occupant Satisfaction Presented by: Kelli Goldstone April 2016 Outline Function of HVAC Thermal Comfort Air Distribution Radiant Heating / Cooling Case Study Function
More informationImpact of Temperature and Humidity on the Perception of Indoor Air Quality
Indoor Air 1998; 8: 80 90 Copyright c Munksgaard 1998 Printed in Denmark. All rights reserved INDOOR AIR ISSN 0905-6947 Impact of Temperature and Humidity on the Perception of Indoor Air Quality L. FANG
More informationINVESTIGATING THE EFFECT OF CO 2 CONCENTRATION ON REPORTED THERMAL COMFORT
INVESTIGATING THE EFFECT OF CO 2 CONCENTRATION ON REPORTED THERMAL COMFORT S. Gauthier 1 ; B. Liu 2 ; G. Huebner 2 ; D. Shipworth 2 1: University of Southampton, Highfield, Southampton, SO17 1BJ, UK. 2:
More informationREDEFINING APPROPRIATE THERMAL COMFORT STANDARD FOR NATURALLY VENTILATED BUILDINGS IN TROPICS (SINGAPORE AND INDONESIA PERSPECTIVE)
REDEFINING APPROPRIATE THERMAL COMFORT STANDARD FOR NATURALLY VENTILATED BUILDINGS IN TROPICS (SINGAPORE AND INDONESIA PERSPECTIVE) H Feriadi, NH Wong *, S Chandra, KW Cheong, KW Tham Department of Building,
More informationPerformance of radiant cooling ceiling combined with personalized ventilation in an office room: identification of thermal conditions
Downloaded from orbit.dtu.dk on: Oct 29, 2018 Performance of radiant cooling ceiling combined with personalized ventilation in an office room: identification of thermal conditions Lipczynska, Aleksandra
More informationIndoor comfort and air quality in spaces equipped with eco-ventilation systems
ICUC9-9 th International Conference on Urban Climate jointly with th Symposium on the Urban Environment Indoor comfort and air quality in spaces equipped with eco-ventilation systems Eusébio Z. E. Conceição,
More informationA Comparison of Calculated and Subjective Thermal Comfort Sensation in Home and Office Environment
Proceedings of Conference: People and Buildings held at the offices of Arup UK, 23rd September 2011. London: Network for Comfort and Energy Use in Buildings, http://nceub.org.uk A Comparison of Calculated
More informationA Field Study of the Thermal Environment in Residential Buildings in Harbin
KC-03-13-4 (4664) A Field Study of the Thermal Environment in Residential Buildings in Harbin Zhao-Jun Wang, Ph.D. Gang Wang Le-Ming Lian ABSTRACT This paper presents the main findings of Project HIT.2000.25
More informationShifting Comfort Zone for Hot-Humid Environments
PLEA6 - The rd Conference on Passive and Low Energy Architecture, Geneva, Switzerland, 6-8 September 6 Shifting Comfort Zone for Hot-Humid Environments Kitchai Jitkhajornwanich Faculty of Architecture,
More informationIndividually controlled localized chilled beam in conjunction with chilled ceiling: Part 2 Human response
Downloaded from orbit.dtu.dk on: Dec 09, 2018 Individually controlled localized chilled beam in conjunction with chilled ceiling: Part 2 Human response Arghand, Taha; Pastuszka, Zuzanna ; Bolashikov, Zhecho
More informationIMPACT OF VENTILATION RATE, OZONE AND LIMONENE ON PERCEIVED AIR QUALITY IN OFFICES
Proceedings: Indoor Air 22 IMPACT OF VENTILATION RATE, OZONE AND LIMONENE ON PERCEIVED AIR QUALITY IN OFFICES HN Knudsen 1*, A Afshari 1, L Ekberg 2,4 and B Lundgren 3,4 1 Energy and Indoor Climate Division,
More informationIndoor Air Quality and Thermal Environment in Classrooms with Different Ventilation Systems
Indoor Air Quality and Thermal Environment in Classrooms with Different Ventilation Systems a International Centre for Indoor Environment and Energy, Department of Civil Engineering, Technical University
More informationOPTIMIZATION OF VENTILATION SYSTEMS IN OFFICE ENVIRONMENT, PART I: METHODOLOGY
OPTIMIZATION OF VENTILATION SYSTEMS IN OFFICE ENVIRONMENT, PART I: METHODOLOGY Liang Zhou, and Fariborz Haghighat Department of Building, Civil and Environmental Engineering Concordia University, Montreal,
More informationPrediction of Thermal Comfort. mech14.weebly.com
Prediction of Thermal Comfort Thermal Sensation Scale (Rohles & Nevins, 1974) Fanger s Thermal Comfort Model (1982) Steady state model, applicable for M 3 met and a large group of people Fanger s Thermal
More informationDesigning Air-Distribution Systems To Maximize Comfort
Designing Air-Distribution Systems To Maximize Comfort By David A. John, P.E., Member ASHRAE An air-distribution system that provides occupant thermal comfort can be a complicated system to predict and
More informationAN ASSESSMENT OF THERMAL COMFORT IN NATURALLY VENTILATED ARCHITECTURAL STUDIO IN ABIA STATE UNIVERSITY, UTURU
International Journal of Advance Studies in Engineering and Scientific Inventions Volume 3 Number 1, JULY 2015. ISSN (Print): 1741-8763 ISSN (Online):1741-8771 AN ASSESSMENT OF THERMAL COMFORT IN NATURALLY
More informationTHERMAL COMFORT IN LECTURE HALLS IN THE TROPICS
Topic 2. Indoor environment THERMAL COMFORT IN LECTURE HALLS IN THE TROPICS Yat Huang Yau *, Bee Teng Chew, Aza Saifullah Department of Mechanical Engineering, University of Malaya, 50603 Kuala Lumpur,
More informationEffect of using low-polluting building materials and increasing ventilation on perceived indoor air quality
Effect of using low-polluting building materials and increasing ventilation on perceived indoor air quality Pawel Wargocki, Henrik N. Knudsen 2, and Pawel Zuczek International Centre for Indoor Environment
More informationThese systems are offered an alternative to overhead, mixing ventilation (MV), systems. Due to their potential advantages which are [1]:
Prediction of thermal comfort, IAQ, and Energy consumption in a dense occupancy environment with the under floor air distribution system Ghassem Heidarinejad 1, Mohammad Hassan Fathollahzadeh 2, Hadi Pasdarshahri
More informationEnvironmental and human factors influencing thermal comfort of office occupants in hot-humid and hot-arid climates
Loughborough University Institutional Repository Environmental and human factors influencing thermal comfort of office occupants in hot-humid and hot-arid climates This item was submitted to Loughborough
More informationThe current study investigates the impact of
Evaluation of indoor environment and energy consumption in dwellings before and after their refurbishment HANA BUKOVIANSKA PUSTAYOVÁ Slovak University of Technology in Bratislava Faculty of Civil Engineering
More informationWindow use in single person offices: do occupants control personal ventilation to provide adequate IAQ? Adorkor Bruce-Konuah 1 University Of Sheffield
Window use in single person offices: do occupants control personal ventilation to provide adequate IAQ? Adorkor Bruce-Konuah 1 University Of Sheffield SUMMARY Tests with participants in controlled environments
More informationAn Employee Thermal Comfort Model for Semiconductor Manufacturing
An Employee Thermal Comfort Model for Semiconductor Manufacturing Author Information Robbie Walls Corporate Ergonomist Intel Corporation MS CH10-22 5000 W. Chandler Blvd. Chandler, AZ 85226 Phone: (480)
More informationImplementation of a Multi-phase Approach for Investigating and Remedying a Thermal Comfort Problem in an Office Building
Original Paper Indoor and Built Indoor Built Environ 8;;:1 14 Accepted: September, 8 Environment Implementation of a Multi-phase Approach for Investigating and Remedying a Thermal Comfort Problem in an
More informationHumidification and perceived indoor air quality in
322 Environmental Epidemiology Unit, Department of Public Health, University of Helsinki, Finland L M Reinikainen J J K Jaakkola Technical Reseach Centre of Finland L Aunela-Tapola Laboratory of Heating,
More informationAdaptive thermal comfort explained by PMV
Adaptive thermal comfort explained by PMV Willemijne van der Linden, Marcel Loomans * and Jan Hensen Eindhoven University of Technology, Department of Architecture Building and Planning, Unit Building
More informationIEA/ECBCS Annex 41 Glasgow Meeting HUMIDITY CONDITIONS IN FLATS OF A CORUÑA (SPAIN)
HUMIDITY CONDITIONS IN FLATS OF A CORUÑA (SPAIN) 1 Rodríguez Suárez, E.; 2 Saiz Jabardo, J.Mª.; 1 Orosa García, J. A; 1 Baaliña Insua, A.; 1 Vázquez Martínez, A. Universidade da Coruña. 1 Escuela Técnica
More informationExamples of IEQ factors. Healthy IEQ and energy efficiency. What type of system is the best? Ideas and concepts from research and reality.
Healthy IEQ and energy efficiency Ideas and concepts from research and reality Lars Ekberg Energy Management AB A Chalmers Industriteknik Company 1 Examples of IEQ factors Thermal climate -operative temp.
More informationPERSONAL COOLING USING THERMAL CONDUCTION ON THE DESK
PERSONAL COOLING USING THERMAL CONDUCTION ON THE DESK J. Verhaart 1 ; R. Keune 1 ; M. Veselý 1 ; R. Li 1, W. Zeiler 1. 1: Dep. of the Built Environment, Rondom 70, 5612 AP, P.O. Box 513, 5600 MB Eindhoven,
More informationA Field Study of Thermal Comfort in Open-plan Office Buildings during Transition Seasons in Harbin. Yunsong Han 1, 2, Huixuan Sun 1, 2, Cheng Sun 1, 2
A Field Study of Thermal Comfort in Open-plan Office Buildings during Transition Seasons in Harbin Yunsong Han 1, 2, Huixuan Sun 1, 2, Cheng Sun 1, 2 1 School of Architecture, Harbin Institute of Technology,
More informationM.Sc. Thesis Assessment of occupant productivity as a result of indoor climate quality for in-use office buildings
M.Sc. Thesis Assessment of occupant productivity as a result of indoor climate quality for in-use office buildings A field study research on the effects of indoor climate parameters Date: February 2018
More informationEvaluation methods for indoor environmental quality assessment according to EN15251
Summary of this article was published in the REHVA European HVAC Journal Vol 49, Issue 4 (August), 2012, pages 14-19, available at http://www.rehva.eu/en/rehva-european-hvac-journal. Evaluation methods
More informationInformation paper 17. Prepared by: David Clark. book:
Information paper 17 Thermal comfort standards Prepared by: David Clark A paper referenced in the book: Cundall Johnston & Partners LLP. 2013 Issue 1.0: 29 July 2013 This information paper is one of a
More informationPublished in: Proceedings of the 7th International Conference on Healthy Buildings 2003, Singapore, December 2003, Vol. 2
Aalborg Universitet Design Methods for Air Distribution Systems and Comparison Between Mixing Ventilation and Displacement Ventilation Nielsen, Peter Vilhelm; Larsen, Tine Steen; Topp, Claus Published
More informationCASE STUDY ON THE THERMAL COMFORT IN A SERIES OF STORES
CASE STUDY ON THE THERMAL COMFORT IN A SERIES OF STORES G. Verbeeck, H. Hens K.U.Leuven, Department of Civil Engineering Laboratory of Building Physics, Celestijnenlaan 131, B-3001 Leuven 0. INTRODUCTION
More informationEnergy and indoor temperature consequences of adaptive thermal comfort standards
Energy and indoor temperature consequences of adaptive thermal comfort standards L. Centnerova and J.L.M. Hensen Czech Technical University in Prague, Czech Republic (lada@tzb.fsv.cvut.cz) Technische Universiteit
More informationRADIANT SLAB COOLING: A FIELD STUDY OF OCCUPANT THERMAL COMFORT. Zhen Tian 1, James A. Love 2
Second National IBPSA-USA Conference Cambridge, MA August 2-4, 2006 RADIANT SLAB COOLING: A FIELD STUDY OF OCCUPANT THERMAL COMFORT Zhen Tian 1, James A. Love 2 1 Ph. D. Candidate, Faculty of Environmental
More informationIndoor Climate and Ventilation in Finnish Schools Air Distribution and Temperature Control in Classrooms
Indoor Climate and Ventilation in Finnish Schools Air Distribution and Temperature Control in Classrooms Abstract Finland is a country without a debate on natural ventilation. In such a cold climate, it
More informationREAL-LIFE OPERATION OF SOLUS SYSTEM: A FOCUS ON THERMAL COMFORT 11 A P R I L D A N VA K D A G E N
REAL-LIFE OPERATION OF SOLUS SYSTEM: A FOCUS ON THERMAL COMFORT 11 A P R I L 2 0 1 8 D A N VA K D A G E N A L E S S A N D R O M A C C A R I N I, P O S T D O C Agenda Concept behind the SOLUS system Energy
More informationThermal Environment evaluation in Commercial kitchens: Procedure of data collection
Thermal Environment evaluation in Commercial kitchens: Procedure of data collection Angela Simone *, Bjarne W. Olesen ICIEE-BYG, Technical University of Denmark, Kgs. Lyngby, Denmark * email: asi@byg.dtu.dk
More informationRoom-side Low-e Coating: As Good As It Sounds?
Room-side Low-e Coating: As Good As It Sounds? Alejandra Menchaca, PhD, LEED AP Senior Building Scientist Associate Lynn Petermann, AIA, LEED AP Architect Vera Baranova, Assoc. AIA Designer NESEA Building
More informationIMPLICATIONS OF CLIMATE CHANGE AND OCCUPANT BEHAVIOUR ON FUTURE ENERGY DEMAND IN A ZERO CARBON HOUSE
IMPLICATIONS OF CLIMATE CHANGE AND OCCUPANT BEHAVIOUR ON FUTURE ENERGY DEMAND IN A ZERO CARBON HOUSE Halla Huws and Ljubomir Jankovic Birmingham School of Architecture Birmingham Institute of Art and Design,
More informationRaise the standards within Ventilation
lindab we simplify construction Raise the standards within Ventilation Background Today the normal standards of duct systems for ventilation are air tightness class A or B. How does this correspond with
More informationField Studies of Subjective Effects on Thermal Comfort in a University. Classroom
Field Studies of Subjective Effects on Thermal Comfort in a University Classroom Jian Wang Zhaojun Wang Master Associate Candidate Professor School of Municipal & Environmental Engineering, Harbin Institute
More informationRefurbishment of Ventilation in Respect of Indoor Environment Quality and Energy Efficiency
Refurbishment of Ventilation in Respect of Indoor Environment Quality and Energy Efficiency VIRTA MAIJA, M.Sc.(Eng.), Vice-president of REHVA, maija.virta@halton.com 1 BACKGROUD FOR SUSTAINABLE INDOOR
More informationIndividually controlled localized chilled beam in conjunction with chilled ceiling: Part 1 Physical environment
Downloaded from orbit.dtu.dk on: Dec 18, 2017 Individually controlled localized chilled beam in conjunction with chilled ceiling: Part 1 Physical environment Arghand, Taha; Bolashikov, Zhecho Dimitrov;
More informationIncorporating comfort in the design of low energy buildings
NCEUB Autumn Meeting, Edinburgh 2009 Incorporating comfort in the design of low energy buildings Atze Boerstra BBA Binnenmilieu & Eindhoven University of Technology, Faculty of Architecture, Building Physics
More informationInvestigation and Analysis of Winter Classroom Thermal Environment. In Chongqing
ESL-IC-61-8 ICEBO26, Shenzhen, China Investigation and Analysis of Winter Classroom Thermal Environment In Chongqing Jing Liu Baizhan Li Runming Yao Postgraduate Ph.D Ph.D Professor Senior researcher Chongqing,
More informationDETERMINATION OF VOLATILE ORGANIC COMPOUNDS IN THE BUILDING OF PRINTING COMPANY
Proceedings of the 14 th International Conference on Environmental Science and Technology Rhodes, Greece, 3-5 September 2015 DETERMINATION OF VOLATILE ORGANIC COMPOUNDS IN THE BUILDING OF PRINTING COMPANY
More informationEnhancing Productivity While Reducing Energy Use in Buildings
233 Enhancing Productivity While Reducing Energy Use in Buildings David P. Wyon 1 Adjunct Professor, International Centre for Indoor Environment & Energy, Technical University of Denmark; Research Fellow,
More informationREAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS. Galway, Ireland
REAL-TIME CONTROL OF OCCUPANTS THERMAL COMFORT IN BUILDINGS Magdalena Hajdukiewicz 1,2,3, Padraig O Connor 1, Colin O Neill 1, Daniel Coakley 1,2,3, Marcus M. Keane 1,2,3, Eoghan Clifford 1,2,3 1 Department
More informationProceedings of Clima 2007 WellBeing Indoors
Experimental Study of Thermal Environment and Comfort in an Office Room with a Variable Air Volume (VAV) System under Low Supply Air Temperature Conditions Mari-Liis Maripuu Chalmers University of Technology,
More informationEvaluation of Occupant Perception and Satisfaction in Two New Office Buildings
in Two New Office Buildings Lu Aye 1, W. W. S. Charters 2, M. Chiazor 3,1 and J. R. W. Robinson 3 1 International Technologies Centre (IDTC), Dept. of Civil and Environmental Engineering 2 Department of
More informationAir distribution and temperature control in classrooms
Air distribution and temperature control in classrooms Jarek Kurnitski D.Sc., Docent HELSINKI UNIVERSITY OF TECHNOLOGY Laboratory of Heating, Ventilation and Air Conditioning Swegon Air Academy 11.6.2008
More informationUniversity of Rochester Environmental Health & Safety Indoor Air Quality Program March 23, 2005
University of Rochester Environmental Health & Safety Indoor Air Quality Program March 23, 2005 1. Purpose: The purpose of this program is to inform the University community about indoor air quality (IAQ).
More informationPerformance Investigation of Building Ventilation System by Calculating Comfort Criteria through HVAC Simulation
IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) ISSN: 2278-1684Volume 3, Issue 6 (Nov. - Dec. 2012), PP 07-12 Performance Investigation of Building Ventilation System by Calculating Comfort
More informationSome methodological aspects of sensory testing of indoor air quality Wargocki, Pawel; Knudsen, Henrik N.; Krzyzanowska, Justyna
Aalborg Universitet Some methodological aspects of sensory testing of indoor air quality Wargocki, Pawel; Knudsen, Henrik N.; Krzyzanowska, Justyna Published in: Clima 2010, 9-12 May, Antalya Publication
More informationASHRAE Region VI CRC Track III: Session 1 Ventilation & IAQ Fundamentals. Steven T. Taylor, PE Principal Taylor Engineering
ASHRAE Region VI CRC Track III: Session 1 Ventilation & IAQ Fundamentals Steven T. Taylor, PE Principal Taylor Engineering This program is registered with the AIA/CES for continuing professional education.
More informationAccording to our research and study most occupant complaints relating to IAQ are attributable to the following factors:
Report pertaining to the Duct Cleaning of ICU! &ICU2 at Hospital 5 th & 6 th Floor. The IAQ Report documents by Photograph (at random) photo shots of the various ducting systems & AHU Systems for work
More informationThermal Environment evaluation in commercial kitchens
Downloaded from orbit.dtu.dk on: Nov 11, 2018 Thermal Environment evaluation in commercial kitchens Simone, Angela; Olesen, Bjarne W. Publication date: 2013 Link back to DTU Orbit Citation (APA): Simone,
More informationThermal Comfort Evaluation of HDB flats
Thermal Comfort Evaluation of HDB flats Objective Measurements For this study, empirical data on the thermal comfort parameters (i.e. room space temperature, velocity and relative humidity) was collected
More informationAssessment of Indoor Environments
Assessment of Indoor Environments Edward Arens University of California, Berkeley e-mail: earens@berkeley.edu I. INTRODUCTION The energy and environmental consequences of conditioning buildings are immense,
More informationAalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016
Aalborg Universitet CLIMA 2016 - proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols Publication date: 2016 Document Version Publisher's PDF, also known as Version of record Link to publication
More informationAssessment of Thermal Comfort: A Study at Closed and Ventilated Call Centre
American Journal of Applied Sciences 7 (3): 02-07, 2010 ISSN 156-9239 2010Science Publications Assessment of Thermal Comfort: A Study at Closed and Ventilated Call Centre 1 A.R. Ismail, 2 N. Jusoh, 2 N.K.
More informationSaving energy for ventilation by careful selection of building materials Wargocki, Pawel; Knudsen, Henrik N.
Aalborg Universitet Saving energy for ventilation by careful selection of building materials Wargocki, Pawel; Knudsen, Henrik N. Published in: Proceedings of the 8th Symposium on Building Physics in the
More informationEnergy and Thermal Comfort Management in a Kindergarten School Building in the South of Portugal in Winter Conditions
4th IASME/WSEAS International Conference on ENERGY, ENVIRONMENT, ECOSYSTEMS and SUSTAINABLE DEVELOPMENT (EEESD'8) Algarve, Portugal, June 11-13, 8 Energy and Thermal Comfort Management in a Kindergarten
More informationA Field Study on Thermal Comfort of Occupants at a Library Using Natural Ventilation and Air-Conditioning System in Brazil
International Journal of Science and Engineering Investigations vol. 7, issue 74, March 2018 ISSN: 2251-8843 A Field Study on Thermal Comfort of Occupants at a Library Using Natural Ventilation and Air-Conditioning
More informationWork Package 2: Performance of naturally ventilated buildings
Work Package 2: Performance of naturally ventilated buildings Detailed Monitoring Report The architectural office of Malmö (SE1) Åke Blomsterberg, Charlotte Svensson J&W Consulting Engineers Building Physics,
More informationThermal comfort under transient seasonal conditions of a bioclimatic building in Greece
54 2nd PALENC Conference and 28th AIVC Conference on Building Low Energy Cooling and Thermal comfort under transient seasonal conditions of a bioclimatic building in Greece A. Androutsopoulos Centre for
More informationSensitivity Analysis of Personal Exposure Assessment Using a Computer Simulated Person Brohus, Henrik; Jensen, H. K.
Aalborg Universitet Sensitivity Analysis of Personal Exposure Assessment Using a Computer Simulated Person Brohus, Henrik; Jensen, H. K. Published in: Healthy Buildings 2009 Publication date: 2009 Document
More informationThermal environment and thermal comfort in a passive residential building in the severe cold area of China
Thermal environment and thermal comfort in a passive residential Yuchen Ji Ph D. Candidate Harbin Institute of Technology China 15B927029@hit.edu.cn Professor, Zhaojun Wang, Harbin Institute of Technology,
More informationSET. An analysis of thermal comfort in primary schools in Vietnam BOLOGNA. Thi Ho Vi LE 1, Mark GILLOTT 2, Lucelia RODRIGUES 3
SET 2017 BOLOGNA An analysis of thermal comfort in primary schools in Vietnam Thi Ho Vi LE 1, Mark GILLOTT 2, Lucelia RODRIGUES 3 1 University of Nottingham, Nottingham, United Kingdom, vi.le@nottingham.ac.uk
More informationPractical Guide Comfort level measurement in the workplace :32. PMV PPD measurement protocol Default Point Graphic Date/Time
05.05.2015 16:32 PMV PPD measurement protocol Default Point Graphic Date/Time 04.05.2015 10:51 Practical Guide Comfort level measurement in the workplace 1 Introduction. Several hundred million people
More informationThe Response of Human Thermal Perception and Skin Temperature to Step-Changed Activity Level
The Response of Human Thermal Perception and Skin Temperature to StepChanged Activity Level Diyi Tan, Hong Liu, and Yuxin Wu Abstract Considerable researches have been conducted on human thermal comfort
More informationIMPACT OF THE AIRFLOW INTERACTION ON OCCUPANTS THERMAL COMFORT IN ROOMS WITH ACTIVE CHILLED BEAMS
IMPACT OF THE AIRFLO INTERACTION ON OCCUPANTS THERMAL COMFORT IN ROOMS ITH ACTIVE CHILLED BEAMS Arsen Melikov 1, Boryana Yordanova 1, Lyuben Bozkhov 1, Viktor Zboril 1,2, and Risto Kosonen 3 1 International
More informationCOUPLING OUTER-BODY AIRFLOW AND INNER-BODY THERMOREGULATION MODELS TO PREDICT THERMAL COMFORT IN NON- UNIFORM ENVIRONMENTS
Eleventh International IBPSA Conference Glasgow, Scotland July 27-30, 2009 COUPLING OUTER-BODY AIRFLOW AND INNER-BODY THERMOREGULATION MODELS TO PREDICT THERMAL COMFORT IN NON- UNIFORM ENVIRONMENTS Gao
More informationWork Package 2: Performance of naturally ventilated buildings
Work Package 2: Performance of naturally ventilated buildings Detailed Monitoring Report The Pfizer Building (NO2) Peter Blom The Norwegian Building Research Institute Technical division Table of contents
More information