1 FIRE PERFORMANCE OF WOOD: TEST METHODS AND FIRE RETARDANT TREATMENTS Mitchell S. Sweet Fire Safety of Wood Products, USDA Forest Service Forest Products Laboratory 1 One Gifford Pinchot Drive Madison, WI Abstract This report describes the fire performance characteristics of wood and wood products, along with test methods for evaluating the fire properties of these materials. Wood treated with fire retardants may provide a code-approved alternative to noncombustible materials. Fire performance and problems associated with thermal degradation are discussed in terms of the mechanisms of fire retardancy. In: Lewin, Menachem, ed. Recent advances in flame retardancy of polymeric materials. Proceedings of the 4th annual BCC conference on flame retadancy; 1993 May 18 20; Stamford, CT. Norwalk, CT: Business Communications Co. Inc.: [1993]: The Forest Products Laboratory is maintained in cooperation with the University of Wisconsin. This article was written and prepared by U.S. Government employees on official time, and it is therefore in the public domain and not subject to copyright. 36

2 Introduction In 1991 in the United States, approximately 3,800 people died as a result of fire in structures, compared to 7,600 deaths in 1972 (Karter, 1992; NFPA, 1973). Property loss to structural fires amounted to over $8.3 billion in 1991, an increase from $2.4 billion in In the past 20 years, fatalities caused by fires have been reduced by 50%, but even when adjusted for inflation, property losses have increased by 25%. It is generally recognized that the combustible contents of buildings often initiate fires and are usually responsible for fire-related deaths. Nevertheless, building codes place considerable emphasis on wood and wood products, which are used extensively for structural and interior components of buildings. This report describes the fire performance characteristics of wood, methods for evaluating fire properties, and fire performance of fire-retardant treated wood. Ignition Fire Performance of Wood Wood, like other cellulosic materials, undergoes thermal degradation at elevated temperatures. This phenomenon, pyrolysis, follows a low-temperature pathway (below 300 C (570 F)) and a high-temperature pathway (above 300 C) (Shafizadeh, 1984). At low temperatures, the pyrolysis of wood favors the formation of char and evolution of noncombustible gases such as H 2 O and CO 2. At high temperatures, tars and combustible gases are produced. These combustible volatiles combine with oxygen to burn. In the presence of a pilot flame, the volatiles can ignite with a minimum rate of heating of 13 kw/m 2 (1.1 Btu/ft 2 s). When no pilot flame is present, spontaneous ignition can occur, although roughly twice the heat flux is required about 25 kw/m 2 (2.2 Btu/ft 2 s) (Lawson and Simms, 1952). The surface temperature for the rapid spontaneous ignition of wood has been determined to be between 330 and 600 C (626 and 1,112 F) (Beall and Eickner, 1970; Kanury, 1972). Forest Products Laboratory (FPL) is currently using ASTM Test Method E (ASTM, 1990) for measure-merit of both ignition and flame spread. The heat flux of the radiant panel is adjusted until the minimum flux required to ignite the specimen, using piloted ignition, is determined. Fire Resistance Wood has excellent natural fire resistance as a result of low thermal conductivity and the fact that char is formed as wood burns. This layer of char prevents further fire penetration, while the wood beneath the char retains most of its original strength properties. In the standard fire conditions for ASTM E119 (ASTM, 1988), a thick piece of wood is exposed to fire conditions between 815 C and 1,038 C (1,500 F and 1,900 F). The outermost layer of wood is charred, but deeper into the wood, the temperature drops. The active char area is found to correspond to the depth at which the wood temperature reaches 290 C (550 F). Beyond that depth, the temperature drops further; at the depth at which the temperature falls to 175 C (347 F), the wood is no longer darkened. At a depth of 13 mm (0.5 in.) from the active char zone, the wood is only 105 C (220 F). Table I contains some typical 37

3 values of char rates for various softwoods and hardwoods under ASTM E119 testing conditions. Flame Spread Table I Average char rates and flame spread indices for selected wood species Species Char rate (mm/h) a FSI b Softwoods Western hemlock Douglas-fir Engelmann spruce Western redcedar Southern pine Redwood Hardwoods Hard maple Yellow-poplar Red oak Basswood a 1 in. = 25.4 mm. Data from White and Nordheim (1992). b Flame spread index (UL, 1971). Flame spread is the propagation of a flame along the surface of wood. ASTM Test Method E84 (ASTM, 1991) involves exposure of a specimen with dimensions of 7.32 m (24 ft) by 0.51 m (20 in. ) to a gas burner. In the past, red oak was taken to be the standard for the test and was arbitrarily assigned a value of 100. Red oak was used because of its availability and fairly uniform properties. Today, red oak is still used as a calibration material for the test method, with a flame spread index (FSI) near 100. The FSIs are now calculated from the time necessary for the flame front to advance the length of the test specimen. In general, untreated natural wood products (25 mm (1 in.) lumber) have FSIs of ; a few species have flame indices below 75 (western hemlock, western redcedar, redwood) and others have values above 170 (yellow- poplar) (Table I). Building Codes have defined classifications for flame spread from the FSI of a material. Class A or I materials have indices of 0-25; Class B or II, 26-75; and Class C or III, Heat Release Rate The rate of heat release (HRR) can be determined by several approaches, including the sensible heat and oxygen consumption methods. Based on studies performed at FPL (Tran, 1988), the oxygen consumption method was determined to be superior to the thermal method. As a result, only the oxygen method is currently used at FPL. The heat release rate quantifies the amount of heat being 38

4 given off by a specimen exposed to a radiant heat source, It is generally believed that a lower HRR leads to better fire performance. A higher HRR means that a specimen could contribute more energy to a growing fire and produce a larger, hotter fire than a material with a lower HRR. ASTM Test Method E906 (ASTM, 1983) is not used as a basis for ratings or regulatory purposes but rather as a research and development tool. Table II contains some typical values for HRRs of various softwoods and hardwoods. smoke Table II-Average HRR for selected wood species a Species Softwoods Douglas-fir Redwood Hardwoods Red maple Sugar maple Cottonwood Yellow-poplar Red oak White oak Hickory HRR (kw/m 2 ) b afive-minute average HRR at 40 kw/m 2 (3.5 Btu/ft 2 s)) (Tran, 1992). 1 Btu/ft 2 s) = kw/m 2. b Most fire deaths are caused not by flame and heat but by gases and smoke (NFPA, 1986). Since smoke obscures vision and makes egress more difficult, the optical density of smoke is important. The smoke density is measured by light obscuration techniques. ASTM Test Method E662 (ASTM, 1992) is used to determine the specific optical density of smoke by measuring the reduction in intensity of a light beam under flaming or nonflaming conditions. A smokedeveloped index is also determined in ASTM Test Method E84. This index is relative to that of red oak. While the toxicity of smoke is also of interest, currently there is no nationally recognized standardized test method for measuring the toxicological effect of the combustion products of wood products. Mechanisms of Fire Retardancy Browne (1958) wrote a comprehensive literature review of various theories of fire retardancy for wood. The predominant theories are that the fire retardant (1) reduces the flow of heat to prevent further combustion, (2) quenches the flame, or (3) modifies the thermal degradation process. 39

5 The first theory has several variations. Afire retardant may work by forming a glaze or foam that serves to insulate the wood surface, such as an intumescent coating. Some fire retardants may actually increase the thermal conductivity of the wood to such an extent that the heat is quickly dissipated, preventing ignition. Another variation of the theory states that the fire retardant may undergo a highly endothermic reaction that absorbs sufficient heat to prevent the surface of the material from igniting. The flame quenching theory proposes that fire retardants release radicals at pyrolytic temperatures that scavenge hydrogen and hydroxyl radicals from the combustion gas mixture, inhibiting the propagation of the flaming combustion. The mechanism of thermal degradation may be modified by the formation of a physical barrier, which prevents oxygen from the atmosphere from reaching the pyrolyzed wood or prevents volatile gases from escaping from the wood. The mechanism of thermal degradation may be modified in a different way. The fire retardant chemicals may lower the temperature at which pyrolysis occurs, forcing a greater proportion of the thermal degradation to follow the lowtemperature pathway. This increases the amount of char and decreases the amount of volatile gases. The effective heat content of the material is therefore lowered as a result of less combustible volatiles. In all probability, fire retardant formulations utilize several of these mechanisms. However, most commercial fire retardants for wood seem to follow the increased char/reduced volatiles theory. The increase in char is due to an acid-catalyzed hydrolysis of the cellulose and hemicellulose, which not only dehydrates the wood but also increases the condensation and cross-linking of the carbon skeleton (Browne, 1958; LeVan, 1984). Within the last few years, much attention has been focused on the strength loss associated with fire-retardant-treated plywood. Strength loss is believed to be a result of the fire retardant lowering the temperature at which pyrolysis is occurring. Instead of catalyzing the acid hydrolysis during actual fire conditions, the polysaccharides in the wood may be dehydrated prematurely in-service, under the influence of solar radiation. The degradation of the polysaccharides appears to manifest itself as a reduction in strength properties of the solid wood (LeVan and others, 1990). Fire Performance of Treated Wood Fire-retardant-treated wood usually increases the temperature at which ignition occurs. Since the fire retardant tends to increase the amount of char formed and decrease the amount of volatile gases evolved, the treated wood resists ignition under the same conditions when compared to untreated wood. When treated wood is exposed to severe fire conditions, the charring rate is not significantly different from that of untreated wood. Southern Pine was treated with a number of different fire retardants and exposed to ASTM E119 fire conditions (Schaffer, 1974). Monoammonium phosphate, zinc chloride, sodium 40

6 chloride, dicyandiamide with phosphoric acid, and tetrakis (hydroxymethyl) phosphonium chloride with urea had no effect on charring rate. Boric acid, borax, ammonium sulfate, monosodium phosphate, potassium carbonate and sodium hydroxide reduced the char rate by about 20 percent. Fire retardants slow down the spread of flame by altering ignition and heat release characteristics, but generally do not improve the fire endurance of wood. The property that shows the greatest improvement with fire-retardant treatment is flame spread. While untreated wood commonly has a FSI of , wood well treated with present commercial formulations has an FSI of < 25. Treating wood with fire retardants can substantially reduce HRR. LeVan and Tran (1990), treated Southern Pine plywood with borax-boric acid and measured HRR according to ASTM E906. The HRR could be lowered from a 5-min. average of 140 kw/m 2 (12.3 Btu/ft 2 s) for untreated plywood to <25 kw/m 2 (2.2 Btu/ft 2 s) for plywood treated at a 15% loading level. While this HRR reduction was only demonstrated for borax-boric acid, it is believed that other fire retardants exhibit similar behaviors. The smoke yield from treated wood is also lower than for untreated material. Brenden (1975) found that treating Douglas-fir plywood with inorganic salt fire retardants decreased smoke yield under nonflaming conditions. Sodium bichromate decreased smoke by as much as 90%. Under flaming conditions, sodium bichromate, boric acid, ammonium sulfate, and borax also reduced the smoke yield. Concluding Remarks Wood and wood products will ignite when a heat flux causes sufficient evolution of flammable gases. It is these flammable volatiles that actually ignite, rather than the wood itself. The wood components that are not volatilized become char. The char will thermally and physically insulate the remaining wood, which gives wood excellent natural fire resistance to fire penetration. Most natural wood products have flame spread properties that give ratings of Class III. Some species of wood with inherently low flame spread have a Class II rating. Fire retardant treatment will greatly improve flame spread, but will not generally improve burnthrough resistance. Many mechanisms of fire retardancy have been proposed over time, and many fire retardants utilize several of these mechanisms. However, most commercial fire retardants for wood function by reducing the amount of flammable gases and increasing the amount to char formed. There is, and will continue to be, a need for building materials that meet a minimum level of fire performance. In many instances, untreated wood and wood products provide that performance. For other uses, a higher level of fire performance is required and can be attained by treating wood with fire retardants. However, the current generation of fire retardants used for wood needs to be improved. New fire retardants that are as inexpensive and effective as the ones used today, but are able to avoid the problems associated with strength degradation, should be able to make great advances on the market. 41

7 References 42

8 on recycled paper 43

Wood Products: Thermal Degradation and Fire

Wood Products: Thermal Degradation and Fire Wood Products: Thermal Degradation and Fire Wood is a thermally degradable and combustible material. Applications range from a biomass providing useful energy to a building material with unique properties.

More information

FIRE AND MATERIALS 98

FIRE AND MATERIALS 98 FIRE AND MATERIALS 98 5th International Conference February 1998 San Antonio Tx, USA White, R. H.; M.A. Dietenberger; and H. Tran. 1998. Comparison of test protocols for standard room/corner tests. p.

More information

Flame Spread Performance of Wood Products Used for Interior Finish

Flame Spread Performance of Wood Products Used for Interior Finish Performance of Wood Products Used for Interior Finish Wood and wood-based products are widely used as interior wall, ceiling, and floor surfaces in all types of buildings. Appearance, acoustical qualities,

More information

FOR A LONG time, evidence has shown that, even when heated at low

FOR A LONG time, evidence has shown that, even when heated at low Smoldering Initiation in Cellulosics under Prolonged Low-Level Heating E. L. SCHAFFER Forest Products Laboratory Forest Service, U.S. Department of Agriculture Scant field information and the difficulty

More information

Fire Performance of the Wood Treated with Inorganic Fire Retardants* 1

Fire Performance of the Wood Treated with Inorganic Fire Retardants* 1 J. Korean Wood Sci. & Tech. 40(5) : 335~342, 2012 http://dx.doi.org/doi : 10.5658/WOOD.2012.40.5.335 Fire Performance of the Wood Treated with Inorganic Fire Retardants* 1 Dong Won Son* 2, Mee Ran Kang*

More information

Effect of fire-retardant treatment on plywood ph and the relationship of ph to strength properties

Effect of fire-retardant treatment on plywood ph and the relationship of ph to strength properties Wood Science and Technology 33 (1999) 285-298 Springer-Verlag 1999 Effect of fire-retardant treatment on plywood ph and the relationship of ph to strength properties S. T. Lebow, J. E. Winandy Summary

More information

EFFECT OF LIGNIN CONTENT AND EXTRACTIVES ON THE HIGHER HEATING VALUE OF WOOD. Robert H. White

EFFECT OF LIGNIN CONTENT AND EXTRACTIVES ON THE HIGHER HEATING VALUE OF WOOD. Robert H. White EFFECT OF LIGNIN CONTENT AND EXTRACTIVES ON THE HIGHER HEATING VALUE OF WOOD Robert H. White Research Forest Products Technologist Forest Products Laboratory, Madison, WI 53705-2398' (Received December

More information

BPVV R7002 Lumber, Treated

BPVV R7002 Lumber, Treated BPVV R7002 HOOVER TREATED WOOD PRODUCTS INC 154 WIRE RD THOMSON, GA 30824 USA R7002 Lumber, impregnated by pressure process to reduce combustibility. Specie Type or Grade PYRO-GUARD Flame Spread Smoke

More information

Robert H. White* and Erik V. Nordheim**

Robert H. White* and Erik V. Nordheim** Robert H. White* and Erik V. Nordheim** Abstract Analytical methods that predict the endurance of structural wood members in a fire are based on the reduction of the cross section of the member caused

More information

Charring rate of intumescent fire protective coated Norway spruce (Picea abies L.)

Charring rate of intumescent fire protective coated Norway spruce (Picea abies L.) Charring rate of intumescent fire protective coated Norway spruce (Picea abies L.) Wilfried Beikircher 1, Paul Hartmann 2, Josef Kögl 3 ABSTRACT: The objective of this study was to determine the combustion

More information

A SIMPLIFIED TEST FOR ADHESIVE BEHAVIOR IN WOOD SECTIONS EXPOSED TO FIRE

A SIMPLIFIED TEST FOR ADHESIVE BEHAVIOR IN WOOD SECTIONS EXPOSED TO FIRE U.S. DEPARTMENT OF AGRICULTURE FOREST SERVICE FOREST PRODUCTS LABORATORY MADISON, WlS. In cooperation with the University of Wisconsin U.S.D.A FOREST SERVICE RESEARCH NOTE FPL-0175 NOVEMBER 1968 A SIMPLIFIED

More information

HEAT OF COMBUSTION OF THE VOLATILE PYROLYSIS PRODUCTS OF FIRE-RETARDANT-TREATED PONDEROSA PINE

HEAT OF COMBUSTION OF THE VOLATILE PYROLYSIS PRODUCTS OF FIRE-RETARDANT-TREATED PONDEROSA PINE U. S. FOREST SERVICE RESEARCH PAPER FPL 19 DECEMBER 1964 HEAT OF COMBUSTION OF THE VOLATILE PYROLYSIS PRODUCTS OF FIRE-RETARDANT-TREATED PONDEROSA PINE U. S. DEPARTMENT OF AGRICULTURE, FOREST SERVICE FOREST

More information

MEASUREMENTS OF HEAT RELEASE RATES ON WOOD PRODUCTS AND AN ASSEMBLY

MEASUREMENTS OF HEAT RELEASE RATES ON WOOD PRODUCTS AND AN ASSEMBLY MEASUREMENTS OF HEAT RELEASE RATES ON WOOD PRODUCTS AND AN ASSEMBLY USDA FOREST SERVICE RESEARCH PAPER FPL 281 1977 U.S. DEPARTMENT OF AGRICULTURE FOREST SERVICE FOREST PRODUCTS LABORATORY MADISON, WIS.

More information

Heat Release Rate of Wood-Plastic Composites

Heat Release Rate of Wood-Plastic Composites Abstract Wood-plastic composites are becoming more important as a material that ful fills recycling needs. In this study, fire performance tests were conducted on several compositions of wood and plastic

More information

Use of Coatings to Improve Fire Resistance of Wood

Use of Coatings to Improve Fire Resistance of Wood Reprint from Standard Technical Publication 826 Robert H. White 1 American Society for Testing and Materials 1916 Race Street, Philadelphia, PA 19103 1984 Use of Coatings to Improve Fire Resistance of

More information

CORRELATION BETWEEN 8-FOOT TUNNEL FURNACES

CORRELATION BETWEEN 8-FOOT TUNNEL FURNACES U.S. DEPARTMENT OF AGRICULTURE FOREST SERVICE FOREST PRODUCTS LABORATORY MADISON, WIS. U.S. FOREST SERVICE RESEARCH NOTE FPL - 058 August 1964 CORRELATION BETWEEN 8-FOOT TUNNEL FURNACES Abstract Flammability

More information

FLAME RETARDANT TREATED WOOD PRODUCTS

FLAME RETARDANT TREATED WOOD PRODUCTS WOOD AND FIRE SAFETY 2000 101 FLAME RETARDANT TREATED WOOD PRODUCTS Ondrej Grexa INTRODUCTION Wood has many good properties from the point of view of processing, physical and mechanical properties, aesthetic,

More information

4. Inorganic Flame Retardants.

4. Inorganic Flame Retardants. 4. Inorganic Flame Retardants. Plastics can be given flame retardant characteristics by introducing elements of organic, inorganic and halogen origin. Such elements include magnesium, aluminium, phosphorous,

More information

FLAME RETARDED. By VAMP TECH

FLAME RETARDED. By VAMP TECH FLAME RETARDED COMPOUNDS By VAMP TECH Foundamental Aspects of the Flame Retardacy 1. Combustion 2. Testing FR Compounds 3. FR Additives 4. FR Mechanisms 5. Advantages and Disadvantages Combustion Step

More information

Construction Fire Mitigation by:

Construction Fire Mitigation by: Construction Fire Mitigation by: Improving Fire Resistance of Wood Products Paul Maxim, Len Garis August 2018 Executive Summary Buildings face the greatest risk from fires during the construction phase.

More information

Standardized 3-part specifications D-Blaze FRTW CSI 3-part and Canadian CSC architectural specs are available at

Standardized 3-part specifications D-Blaze FRTW CSI 3-part and Canadian CSC architectural specs are available at How to specify D-Blaze FRT lumber and plywood To assure structural integrity in roof areas of high temperature and humidity, D-Blaze span and strength design adjustment factors have been determined by

More information

FIRE-RETARDANT TREATMENTS FOR WOOD 1

FIRE-RETARDANT TREATMENTS FOR WOOD 1 FIRE-RETARDANT TREATMENTS FOR WOOD 1 By 2 Forest Products Laboratory, Forest Service U. S. Department of Agriculture --- From ancient times, man has associated wood with fire. He has become imbued with

More information

DECOMPOSITION OF ORGANIC MATTER IN SOIL

DECOMPOSITION OF ORGANIC MATTER IN SOIL DECOMPOSITION OF ORGANIC MATTER IN SOIL The rapidity with which a given organic amendment is decomposed depends on temperature, the supply of oxygen, moisture, and available minerals, the C/N ratio of

More information

WOOD & FIRE SAFETY. 3 rd International Scientific Conference

WOOD & FIRE SAFETY. 3 rd International Scientific Conference WOOD & FIRE SAFETY 3 rd International Scientific Conference The High Tatras, Hotel Patria SLOVAK REPUBLIC FUNDAMENTAL THERMOPHYSICAL PROPERTIES OF MATERIALS DERIVED FROM THE CONE CALORIMETER MEASUREMENTS

More information

THERMOGRAVIMETRIC ANALYSIS OF FIRE RETARDANT TREATED PARTICLEBOARDS

THERMOGRAVIMETRIC ANALYSIS OF FIRE RETARDANT TREATED PARTICLEBOARDS WOOD AND FIRE SAFETY 2000 385 THERMOGRAVIMETRIC ANALYSIS OF FIRE RETARDANT TREATED PARTICLEBOARDS P. S. Karastergiou - J. L. Philippou Abstract In this work the thermogravimetric analysis (TGA) of particleboards

More information

Prevent fire naturally. Eco-efficient flame retardants

Prevent fire naturally. Eco-efficient flame retardants Prevent fire naturally Eco-efficient flame retardants Save lives without endangering health and nature Eliminating bio-accumulative, toxic, potentially carcinogenic and definitely non-renewable flame retardants

More information

Surface Flammability, Smoke and Toxic Gas Generation of "3M Polyurethane Adhesive Sealant 560"

Surface Flammability, Smoke and Toxic Gas Generation of 3M Polyurethane Adhesive Sealant 560 ELECTRONIC COPY Surface Flammability, Smoke and Toxic Gas Generation of "3M Polyurethane Adhesive Sealant 560" A Report To: 3M Center Industrial and Transportation Division 3M Center, Building 223-1N-14

More information

FIRE-RETARDANT-TREATED STRANDBOARD: PROPERTIES AND FIRE PERFORMANCE. Jerrold E. Winandy* Qingwen Wang. Robert H. White

FIRE-RETARDANT-TREATED STRANDBOARD: PROPERTIES AND FIRE PERFORMANCE. Jerrold E. Winandy* Qingwen Wang. Robert H. White FIRE-RETARDANT-TREATED STRANDBOARD: PROPERTIES AND FIRE PERFORMANCE Jerrold E. Winandy* Research Wood Scientist USDA Forest Service, Forest Products Laboratory One Gifford Pinchot Drive Madison, WI 53726-2398

More information

Jerrold E. Winandy 1 and William McNamara 2

Jerrold E. Winandy 1 and William McNamara 2 Journal of Testing and Evaluation, Vol. 31, No. 2 Paper ID JTE11060_312 Available online at: www.astm.org Jerrold E. Winandy 1 and William McNamara 2 Evaluation of a Boron-Nitrogen, Phosphate-Free Fire-Retardant

More information

Fire Retardants and Truss Design. Overview

Fire Retardants and Truss Design. Overview Fire Retardants and Truss Design Overview Introduction Fire retardant treatments (FRT) were developed to be applied to building materials, such as dimension lumber (FRTW) and plywood, to reduce the ability

More information

Keywords: Dolomite; Melamine; Particleboard; Combustion properties; Fire retardants

Keywords: Dolomite; Melamine; Particleboard; Combustion properties; Fire retardants Investigation of the Effect of Some Fire Retardant Chemicals and Mineral Materials Used in Surface Coating on Combustion Performance of Particleboard Ferhat Özdemir,* Zehra Odabaş Serin, and Ahmet Tutuş

More information

Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings. John Buddy Showalter, PE VP, Technology Transfer American Wood Council

Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings. John Buddy Showalter, PE VP, Technology Transfer American Wood Council Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings John Buddy Showalter, PE VP, Technology Transfer American Wood Council Copyright This presentation is protected by US and International

More information

Dricon FRT Wood Specification

Dricon FRT Wood Specification PART 1 GENERAL Dricon FRT Wood Specification 1.01 SUMMARY A. Section includes: Fire retardant treatment for wood, including framing, decking, sheathing and other wood construction, not exposed to weather.

More information

International Journal on Engineering Performance-Based Fire Codes, Volume 5, Number 4, p , 2003

International Journal on Engineering Performance-Based Fire Codes, Volume 5, Number 4, p , 2003 , Volume 5, Number 4, p.158-162, 2003 FIRE SAFE FURNITURE S.S. Han Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Many big building fires were

More information

Thermal stability of cotton cellulose modified with gadolinium. complexes

Thermal stability of cotton cellulose modified with gadolinium. complexes 3rd International onference on Mechatronics and Information Technology (IMIT 216) Thermal stability of cotton cellulose modified with gadolinium complexes Guifen LI1,a, Ming GAO 1,b 1 School of Environmental

More information

FUTURE OF FIRE-RESISTIVE COATINGS IN WOOD CONSTRUCTION

FUTURE OF FIRE-RESISTIVE COATINGS IN WOOD CONSTRUCTION FUTURE OF FIRE-RESISTIVE COATINGS IN WOOD CONSTRUCTION ROBERT H. WHITE Forest Products Laboratory U.S. Department of Agriculture, Forest Service Madison, Wisconsin INTRODUCTION The wood industry is currently

More information

A Review of Thermal and Ignition Barrier Requirements for Spray Foam Insulation

A Review of Thermal and Ignition Barrier Requirements for Spray Foam Insulation A Review of Thermal and Ignition Barrier Requirements for Spray Foam Insulation Agenda Why Do Codes Require Thermal or Ignition Barriers? What is a Thermal Barrier? Where is it required? What is an Ignition

More information

Inspecta-Shield Fire Retardant

Inspecta-Shield Fire Retardant Inspecta-Shield Fire Retardant Inspecta-ShieldTM is a versatile, broad spectrum, odorless, colorless, multi-use, penetrating, Class "A" fire retardant (For interior use only). Our pre-mixed product is

More information

PRO LIGNO Vol. 13 N pp

PRO LIGNO Vol. 13 N pp EVALUATION OF ORIENTED STRAND BOARD BEHAVIOR ON FIRE Octavia ZELENIUC Transilvania University of Brasov, Faculty of Wood Engineering Str. Universitatii nr. 1, 500068 Brasov, Romania E-mail: zoctavia@unitbv.ro

More information

Mark A. Dietenberger USDA Forest Service, Forest Products Laboratory Madison, Wisconsin

Mark A. Dietenberger USDA Forest Service, Forest Products Laboratory Madison, Wisconsin Foam Core Particleboards with Intumescent FRT Veneer: Cone Calorimeter Testing With Varying Adhesives, Surface Layer Thicknesses, and Processing Conditions Mark A. Dietenberger USDA Forest Service, Forest

More information

Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings

Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings Michelle Kam-Biron, PE, SE, SECB Senior Director, Education American Wood Council Copyright This presentation is protected

More information

Analysis of Glulam Timber Beams with Mechanically Graded (E-rated) Outer Laminations

Analysis of Glulam Timber Beams with Mechanically Graded (E-rated) Outer Laminations In: Gopu, Vijaya K.A., ed. Proceedings of the international wood engineering conference; 1996 October 28-31; New Orleans, LA. Baton Rouge, LA: Louisiana State University: Vol. 1: 144-150 Analysis of Glulam

More information

WITH FIRE RETARDANT TREATED

WITH FIRE RETARDANT TREATED PROBLEMS WITH FIRE RETARDANT TREATED (FRT) WOOD E X T E N D B E L O W R O O F T H E D E C K Figure 1: Checking parallel to grain. THE PROBLEM Fire Retardant Treatment (FRT) is applied to building materials

More information

FIRE RATINGS. European Oak

FIRE RATINGS. European Oak FIRE RATINGS European Oak Report On Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source As Determined By ASTM E 648 Test Method PREPARED FOR: DuChateau Floors San Diego,

More information

Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings

Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings Code Compliance for Fire Resistance-Rated Assemblies in Light-Frame Buildings Michelle Kam-Biron, PE, SE, SECB Senior Director, Education American Wood Council Copyright This presentation is protected

More information

Surface Flammability, Smoke and Toxic Gas Generation of "3M Polyurethane Adhesive Sealant 550 Fast Cure"

Surface Flammability, Smoke and Toxic Gas Generation of 3M Polyurethane Adhesive Sealant 550 Fast Cure UNCONTROLLED ELECTRONIC COPY Surface Flammability, Smoke and Toxic Gas Generation of "3M Polyurethane Adhesive Sealant 550 Fast Cure" A Report To: 3M Center Industrial and Transportation Division 3M Center,

More information

Surface Flammability, Smoke and Toxic Gas Generation of "3M Scotch-Weld Acrylic Adhesive DP8410NS Green"

Surface Flammability, Smoke and Toxic Gas Generation of 3M Scotch-Weld Acrylic Adhesive DP8410NS Green UNCONTROLLED ELECTRONIC COPY Surface Flammability, Smoke and Toxic Gas Generation of "3M Scotch-Weld Acrylic Adhesive DP8410NS Green" A Report To: 3M Industrial Adhesives and Tapes Division 3M Center,

More information

CORRELATION OF ASTM EXPOSURE TESTS FOR EVALUATING DURABILITY OF FIRE-RETARDANT TREATMENT OF WOOD

CORRELATION OF ASTM EXPOSURE TESTS FOR EVALUATING DURABILITY OF FIRE-RETARDANT TREATMENT OF WOOD SUMMARY A cooperative study was carried out to determine the equivalency of two alternate methods of exposure testing described in ASTM Standard D 2898-70T, Tentative Methods of Test for Durability of

More information

Bending Properties from Laboratory and Field Exposures of FRT Plywood

Bending Properties from Laboratory and Field Exposures of FRT Plywood Bending Properties from Laboratory and Field Exposures of FRT Plywood H. M. Barnes M. G. Sanders G. B. Lindsey Department of Forest Products Mississippi State University J. E. Winandy Winandy & Associates,

More information

Montmorillonite as Flame Retardant for Flexible Poly (Vinyl Chloride)

Montmorillonite as Flame Retardant for Flexible Poly (Vinyl Chloride) 3rd International Conference on Mechatronics and Information Technology (ICMIT 216) Montmorillonite as Flame Retardant for Flexible Poly (Vinyl Chloride) Ying-juan Sun 1,a, Chun-guang Song 1,b, Yin-qiu

More information

Effect of Heating in Water on the Strength Properties of Wood 1

Effect of Heating in Water on the Strength Properties of Wood 1 AMERICAN WOOD-PRESERVERS ASSOCIATION 1954 Effect of Heating in Water on the Strength Properties of Wood 1 Engineer Emeritus, Forest Products Laboratory, 2 J. D. MacLean Forest Service, U. S. Department

More information

FIRE ISSUES IN ENGINEERED WOOD COMPOSITES FOR NAVAL WATERFRONT FACILITIES 1

FIRE ISSUES IN ENGINEERED WOOD COMPOSITES FOR NAVAL WATERFRONT FACILITIES 1 46th International SAMPE Symposium and Exhibition Long Beach, CA, May 2001 FIRE ISSUES IN ENGINEERED WOOD COMPOSITES FOR NAVAL WATERFRONT FACILITIES 1 L. Javier Malvar 1, Robert Tichy 2, David E. Pendleton

More information

WOOD USE IN NONCOMBUSTIBLE BUILDINGS

WOOD USE IN NONCOMBUSTIBLE BUILDINGS INTRODUCTION The National Building Code of Canada (NBCC) 1 requires that some buildings be of noncombustible construction under its prescriptive requirements. Its use in certain types of buildings such

More information

Responsibilities: Effective Date: November Revision Date: January 27, VP, Facilities and Construction Management

Responsibilities: Effective Date: November Revision Date: January 27, VP, Facilities and Construction Management Title: Fire Safety Requirements for Interior Finish Materials Procedure Effective Date: November 2005 Revision Date: January 27, 2017 Issuing Authority: Responsible Officer: VP, Facilities and Construction

More information

Charring rate determination of wood pine profiles submitted to high temperatures

Charring rate determination of wood pine profiles submitted to high temperatures Safety and Security Engineering III 449 Charring rate determination of wood pine profiles submitted to high temperatures E. M. M. Fonseca & L. M. S. Barreira Polytechnic Institute of Bragança, Portugal

More information

High Tg Bromine-free Laminates for PWB Applications

High Tg Bromine-free Laminates for PWB Applications Presented at IPC Printed Circuits EXPO www.ipcprintedcircuitexpo.org High Tg Bromine-free Laminates for PWB Applications Marty Choate Isola Abstract The development of halogen free materials has been a

More information

PYROLYSIS OF TROPICAL HARDWOOD UNDER LONG-TERM AND LOW-TEMPERATURE CONDITIONS

PYROLYSIS OF TROPICAL HARDWOOD UNDER LONG-TERM AND LOW-TEMPERATURE CONDITIONS , Volume 8, Number 1, p.17-27, 2011 PYROLYSIS OF TROPICAL HARDWOOD UNDER LONG-TERM AND LOW-TEMPERATURE CONDITIONS M.Y.L. Chew, Ngoc Quynh An Hoang and Long Shi Department of Building, National University

More information

Flammability studies of impregnated paper sheets

Flammability studies of impregnated paper sheets J Therm Anal Calorim (2012) 107:519-526 DOI 10.1007/s10973-011-1690-7 Flammability studies of impregnated paper sheets Ivan Šimkovic Robert H. White Anne M. Fuller Received: 27 January 2011 /Accepted:

More information

Should Whole-Tree Chips for Fuel Be Dried Before Storage?

Should Whole-Tree Chips for Fuel Be Dried Before Storage? United States Department of Agriculture Forest Service Forest Products Laboratory 1 Research Note FPL-0241 Should Whole-Tree Chips for Fuel Be Dried Before Storage? By Edward L. Springer Abstract Whole-tree

More information

Defining Forests. forestry hardwood log native forest old-growth forest. E-unit: Defining Forests Page 1

Defining Forests. forestry hardwood log native forest old-growth forest. E-unit: Defining Forests Page 1 Defining Forests W HEN WE use the tree respectfully and economically, we have one of the greatest resources on the earth, said Frank Lloyd Wright. Clearly Mr. Wright placed value on trees and had sustainability

More information

ESR-2645 Reissued October 1, 2013 This report is subject to renewal November 1, 2014.

ESR-2645 Reissued October 1, 2013 This report is subject to renewal November 1, 2014. ICC-ES Evaluation Report ESR-64 Reissued October, 0 This report is subject to renewal November, 04. www.icc-es.org (800) 4-68 (6) 699-04 A Subsidiary of the International Code Council DIVISION: 06 00 00

More information

ASTM E 648 Test Method. 5/8" Walnut Engineered Wood Flooring

ASTM E 648 Test Method. 5/8 Walnut Engineered Wood Flooring FIRE RATINGS Walnut Report On Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source As Determined By ASTM E 648 Test Method PREPARED FOR: DuChateau Floors San Diego,CA TEST

More information

Phosphorus Flame Retardants for Textiles. Novecare 18/06/2006 CHALLENGING BOUNDARIES

Phosphorus Flame Retardants for Textiles. Novecare 18/06/2006 CHALLENGING BOUNDARIES Phosphorus Flame Retardants for Textiles Summary Introduction How Do Textiles Burn? The Action of a Phosphorus Flame Retardant Flame Retardant Selection Classification of Textile Flame Retardants Inherent

More information

ASTM E 1354 Caloric Content Determination of "3M Polyurethane Adhesive Sealant 550 Fast Cure + AC63"

ASTM E 1354 Caloric Content Determination of 3M Polyurethane Adhesive Sealant 550 Fast Cure + AC63 UNCONTROLLED ELECTRONIC COPY ASTM E 1354 Caloric Content Determination of "3M Polyurethane Adhesive Sealant 550 Fast Cure + AC63" A Report To: 3M Center Industrial and Transportation Division 3M Center,

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: FIRE RETARDANT WOOD TREATMENT REPORT HOLDER: VIANCE, LLC

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: FIRE RETARDANT WOOD TREATMENT REPORT HOLDER: VIANCE, LLC 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2645 Reissued 11/2017 This report is subject to renewal 11/2018. DIVISION: 06 00

More information

Predicting the Burning of Wood Using an Integral Model

Predicting the Burning of Wood Using an Integral Model Predicting the Burning of Wood Using an Integral Model M. J. SPEARPOINT* and J. G. QUINTIERE Department of Fire Protection Engineering, University of Maryland, College Park, MD 20742 This paper experimentally

More information

EFFECT OF HIGH TEMPERATURE DRYING ON MOISTURE CONTENT DETERMINATION WITH ELECTRONIC METERS

EFFECT OF HIGH TEMPERATURE DRYING ON MOISTURE CONTENT DETERMINATION WITH ELECTRONIC METERS EFFECT OF HIGH TEMPERATURE DRYING ON MOISTURE CONTENT DETERMINATION WITH ELECTRONIC METERS William B. Smith, Associate Professor SUNY College of Environmental Science & Forestry Syracuse, NY Hee-Suk Jung,

More information

Consider the wide array of batteries used in today s portable electronics. Photograph 1 displays a sampling of the their many shapes and sizes:

Consider the wide array of batteries used in today s portable electronics. Photograph 1 displays a sampling of the their many shapes and sizes: Flame Retardant Label Materials.. What s it all about? Dr. Jim Williams, CTO Polyonics, Inc. Flame retardant fabrics for curtains, bedding and other home use makes sense. Obviously flame retardant fabrics

More information

Adhesive Polyester Polyols with inherent Flame Retardancy

Adhesive Polyester Polyols with inherent Flame Retardancy placeholder title visual Adhesive Polyester Polyols with inherent Flame Retardancy Gabriele Brenner, Dr. Christina Diehl, Sabine Thüner Izmir, 2013-09-13 Outline 1. Motivation and Targets 2. Polymer Design

More information

Burtin Polymer Laboratories 2 SwRI Project No e[1]

Burtin Polymer Laboratories 2 SwRI Project No e[1] INTRODUCTION This report presents the results of a fire performance evaluation performed in accordance with AC377, Appendix X, Alternate Testing for Use in Attics and Crawl Spaces without a Code- Prescribed

More information

Report on First Revision June 2014 NFPA 5000

Report on First Revision June 2014 NFPA 5000 5000 FR520 BLD-FUR (10.1 and 10.2) 10.1* General. 10.1.1 Application. Interior finish for buildings shall comply with this chapter. 10.1.2 Automatic Sprinkler Systems. Where another provision of this chapter

More information

An Introduction to Spray Foam Insulation

An Introduction to Spray Foam Insulation An Introduction to Spray Foam Insulation Program Registration BNP Media is a registered provider with The American Institute of Architects Continuing Education System. Credit(s) earned upon completion

More information

Forensic Fire investigation

Forensic Fire investigation Forensic Fire investigation Arson? When investigating a fire one of the questions asked is, Was this arson? This question is difficult to answer based on evidence present at a fire, which is very little.

More information

WANG WOOD FIRE RETARDANT

WANG WOOD FIRE RETARDANT WANG WOOD FIRE RETARDANT Information Reviewed and Reaffirmed March 1956 FOREST RESEARCH C LIBRARY No. 1760 111 1 111 1 11i 11111Hil Iiri _ FOREST PRODUCTS LABORATORY MADISON 5, WISCONSIN UNITED STATES

More information

LECTURE #21: Wild Fires: The Science & History

LECTURE #21: Wild Fires: The Science & History GEOL 0820 Ramsey Natural Disasters Spring, 2018 LECTURE #21: Wild Fires: The Science & History Date: 4 April 2018 I. Wild Fires very important hazard to understand! one of the largest and most expensive

More information

1.3 Energy transfer and the stages of combustion

1.3 Energy transfer and the stages of combustion 1.3 Energy transfer and the stages of combustion Understanding the principles of combustion, can we begin to see how fires initiate and spread? To complete the fire triangle, energy must move through space

More information

REPORT NUMBER: SAT-001A ORIGINAL ISSUE DATE: March 13, 2013 REVISED DATE:

REPORT NUMBER: SAT-001A ORIGINAL ISSUE DATE: March 13, 2013 REVISED DATE: Page 1 of 9 REPORT NUMBER: 101095500SAT-001A ORIGINAL ISSUE DATE: March 13, 2013 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Road Elmendorf, TX 78112 TEST REPORT

More information

Redwood. Redwood Empire. The Environmental Advice A Division of Pacific States Industries, Inc.

Redwood. Redwood Empire. The Environmental Advice A Division of Pacific States Industries, Inc. Redwood The Environmental Advice Redwood Empire A Division of Pacific States Industries, Inc. 1-800-862-4657 www.buyredwood.com Dimensional Stability of California Redwood Redwood is much less subject

More information

DATA SIZE * S O L D * C U T * CLASS CLASS DESCRIPTION SALES VOLUME-MBF VALUE VOLUME-MBF VALUE

DATA SIZE * S O L D * C U T * CLASS CLASS DESCRIPTION SALES VOLUME-MBF VALUE VOLUME-MBF VALUE DATE: 02/11/04 TCS004 TIMBER CUT AND SOLD ON NATIONAL FORESTS SERVICE-WIDE PAGE 1 DATA SIZE * S O L D * C U T * CLASS CLASS DESCRIPTION SALES VOLUME-MBF VALUE VOLUME-MBF VALUE 2 1 NON-CONVERTIBLE 183,360.00

More information

INTERIOR FINISHES CHAPTER 8 SECTION 801 GENERAL

INTERIOR FINISHES CHAPTER 8 SECTION 801 GENERAL CHAPTER 8 INTERIOR FINISHES SECTION 801 GENERAL 801.1 Scope. Provisions of this chapter shall govern the use of materials used as interior finishes, trim and decorative materials. 801.1.1 Interior finishes.

More information

Huber s Unique Vertex 100 Series: Surface-Treated Magnesium Hydroxides. Outstanding Fire Retardant Performance in Wire and Cable Jacketing Compounds

Huber s Unique Vertex 100 Series: Surface-Treated Magnesium Hydroxides. Outstanding Fire Retardant Performance in Wire and Cable Jacketing Compounds Huber s Unique Vertex Series: Surface-Treated Magnesium Hydroxides Outstanding Fire Retardant Performance in Wire and Cable Jacketing Compounds Vertex SP and Vertex SV surface-treated magnesium hydroxides

More information

Introduction to Fire Protection Systems

Introduction to Fire Protection Systems PDHonline Course M110 (4 PDH) Introduction to Fire Protection Systems Instructor: Lawrence J. Marchetti, P.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088

More information

Applications of Wood Materials for Innovative Bridge Systems

Applications of Wood Materials for Innovative Bridge Systems In: Suprenant, Bruce S., ed. Serviceability and durability of construction materials: Proceedings of 1st materials engineering congress; 1990 August 13-15; Denver, CO. New York: American Society of Civil

More information

Effect of Fire-Retardant Treatment and Redrying on the Mechanical Properties of Douglas-Fir and Aspen Plywood

Effect of Fire-Retardant Treatment and Redrying on the Mechanical Properties of Douglas-Fir and Aspen Plywood United States Department of Agriculture Forest Service Forest Products Laboratory Research Paper FPL-RP-485 Effect of Fire-Retardant Treatment and Redrying on the Mechanical Properties of Douglas-Fir and

More information

Charring rate determination of wood pine profiles submitted to high temperatures

Charring rate determination of wood pine profiles submitted to high temperatures Charring rate determination of wood pine profiles submitted to high temperatures Fonseca, E.M.M. 1 and Barreira, L.M.S. 1 1 Polytechnic Institute of Bragança, Portugal Abstract The wood material presents

More information

Copyright is owned by the Author of the thesis. Permission is given for a copy to be downloaded by an individual for the purpose of research and

Copyright is owned by the Author of the thesis. Permission is given for a copy to be downloaded by an individual for the purpose of research and Copyright is owned by the Author of the thesis. Permission is given for a copy to be downloaded by an individual for the purpose of research and private study only. The thesis may not be reproduced elsewhere

More information

PLYWOOD- OAK-COTTONWOOD MINIMUM CURE TIME USDA FOREST SERVICE RESEARCH PAPER FPL

PLYWOOD- OAK-COTTONWOOD MINIMUM CURE TIME USDA FOREST SERVICE RESEARCH PAPER FPL OAK-COTTONWOOD PLYWOOD- MINIMUM CURE TIME USDA FOREST SERVICE RESEARCH PAPER FPL 231 1974 U.S. DEPARTMENT OF AGRICULTURE FOREST SERVICE FOREST PRODUCTS LABORATORY MADISON, WIS. ABSTRACT In bonding oak-cottonwood

More information

Pallets: A Growing Source of Recycled Wood

Pallets: A Growing Source of Recycled Wood Pallets: A Growing Source of Recycled Wood Robert J. Bush Vijay S. Reddy Philip A. Araman Abstract Considerable volumes of solid hardwoods, solid softwoods, and wood panels are used to manufacture pallets

More information

Assessment of the Treatability of Small-Diameter Grand Fir Posts

Assessment of the Treatability of Small-Diameter Grand Fir Posts 2 United States Department of Agriculture Forest Service Forest Products Laboratory Research Note FPL RN 0285 Assessment of the Treatability of Small-Diameter Grand Fir Posts Stan Lebow Susan L. LeVan

More information

Development of the New Halogen-Free Flame Retardant System by Nanoencapsulation

Development of the New Halogen-Free Flame Retardant System by Nanoencapsulation Special Issue Polymer Materials Technology Development of the New Halogen-Free Flame Retardant System by Nanoencapsulation Jae-Kyung Kim*, Hirofumi Kawanaka* A large amount of flame retardant is required

More information

FIRE RESISTANCE OF WOOD MEMBERS WITH DIRECTLY APPLIED PROTECTION

FIRE RESISTANCE OF WOOD MEMBERS WITH DIRECTLY APPLIED PROTECTION FIRE RESISTANCE OF WOOD MEMBERS WITH DIRECTLY APPLIED PROTECTION Robert H. White U.S. Forest Service, Forest Products Laboratory Madison, Wisconsin, U.S.A. ABSTRACT Fire-resistive wood construction is

More information

Update for Combustion Properties of Wood Components

Update for Combustion Properties of Wood Components FIRE AND MATERIALS Fire Mater 2002; 26: 255-267 (DOI: 101002/fam807) Update for Combustion Properties of Wood Components Mark Dietenberger* USDA Forest Service, Forest Products Laboratory, One Gifford

More information

EXPOSED TO FIRE RATE OF HEAT RELEASE FROM WOOD-BASE BUILDING MATERIALS EQUIPMENT INTRODUCTION

EXPOSED TO FIRE RATE OF HEAT RELEASE FROM WOOD-BASE BUILDING MATERIALS EQUIPMENT INTRODUCTION SUMMARY Data on the potential total heat release or on the rate of heat release has been suggested as means of defining combustibility of materials in building code regulations, and would replace the present

More information

Ron Blank & Associates, Inc Viance 200 E Woodlawn Rd, Ste 350 Charlotte, NC

Ron Blank & Associates, Inc Viance 200 E Woodlawn Rd, Ste 350 Charlotte, NC Ron Blank & Associates, Inc. 2012 Viance 200 E Woodlawn Rd, Ste 350 Charlotte, NC 28217 800-421-8661 productinfo@viance.net Fire Retardant Treated Wood (FRTW) For Commercial and Residential Structures

More information

Fire triangle. Contents. Fire tetrahedron

Fire triangle. Contents. Fire tetrahedron Fire triangle From Wikipedia, the free encyclopedia The fire triangle or combustion triangle is a simple model for understanding the ingredients necessary for most fires. [1] The triangle illustrates a

More information

FM APPROVED. FIRE PERFORMANCE Differences Between Elastomeric and Polyethylene/Polyolefin Insulations

FM APPROVED. FIRE PERFORMANCE Differences Between Elastomeric and Polyethylene/Polyolefin Insulations FIRE PERFORMANCE Differences Between Elastomeric and Polyethylene/Polyolefin Insulations Why a 5/50 rating alone does not assure fire safety FM APPROVED FIRE PERFORMANCE: A 5/50 RATING DOES NOT ASSURE

More information

FIRE SAFETY CONCERN FOR TIMBER PARTITION IN THE FAR EAST

FIRE SAFETY CONCERN FOR TIMBER PARTITION IN THE FAR EAST , Volume 7, Number 4, p.148-154, 25 FIRE SAFETY CONCERN FOR TIMBER PARTITION IN THE FAR EAST W.K. Chow Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China

More information

ANALYTICAL METHODS FOR DETERMINING FIRE RESISTANCE OF TIMBER MEMBERS

ANALYTICAL METHODS FOR DETERMINING FIRE RESISTANCE OF TIMBER MEMBERS In: The SFPE handbook of fire protection engineering. 2d ed. Boston, MA: Society of Fire Protection Engineers: 4-217-4-229; 1995. Chapter 11. Section 4/Chapter 11 ANALYTICAL METHODS FOR DETERMINING FIRE

More information

ESR-1826 Reissued May 1, 2009 This report is subject to re-examination in one year.

ESR-1826 Reissued May 1, 2009 This report is subject to re-examination in one year. ICC-ES Evaluation Report ESR-1826 Reissued May 1, 2009 This report is subject to re-examination in one year. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council

More information

INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS

INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS CHAPTER 8 INTERIOR FINISH, DECORATIVE MATERIALS AND FURNISHINGS SECTION 801 GENERAL 801.1 Scope. The provisions of this chapter shall govern interior finish, interior trim, furniture, furnishings, decorative

More information