1 The pros and cons of chilled beams Peter Clackett, Technical Director Skanska Rashleigh Weatherfoil William Booth, Operations Manager BSRIA
2 Agenda Registration Welcome & Introduction - Jo Harris, BSRIA What, Why and How - Peter Clackett, Skanska Description and Application - Peter Clackett, Skanska Performance testing - William Booth, BSRIA Comfort break/coffee Performance testing continued - William Booth, BSRIA The good, the bad and the ugly - Peter Clackett, Skanska and William Booth, BSRIA Q&A - Chaired by Jo Harris, BSRIA Networking Lunch Click on links above to access each presentation At the end of each presentation, click on link Back to Agenda
3
4 What, why, how many?
5 Chilled Beams What are they? They are a cooling device They are different from chilled ceilings These rely solely on radiant cooling (Output 50 to 55 watts per square metre) They are an alternative to both Fan Coil Units and VAV systems There are three kinds of chilled beams Active Chilled Beams can also be used for heating
6 Chilled Beams What are they? 1. Passive No reliance on primary air supply. They work entirely on radiant convection. (Output 130 to 170 watts per linear metre)
7 Chilled Beams What are they? 2. Active These rely on primary air supply to provide the induction required for performance. (Output 850 to 1400 watts per linear metre)
8 Chilled Beams What are they? 3. Multi Service These are active beams with the additional components (smoke detectors, lighting, sprinklers etc.) (Output 850 to 1050 watts per linear metre)
9 Chilled Beams The History Chilled Beams were developed in Norway in 1975 Originally used in Scandinavia Introduced to UK in 1990 s Now used world wide Device of choice for some Clients
10 How many?
11
12
13 ACB UK Market Data Provided by BSRIA s Worldwide Market Intelligence (WMI) Group Data comes from the HEVAC study Annual collection of a/c product sales Managed by BSRIA for a number of years with HEVAC/FETA s endorsement All data to be published in the UK Air conditioning study next month buy from WMI Author David Garwood (available over lunch)
14 Market For Chilled Beams & Ceilings* UK market reduced over last couple of years Many major projects were shelved or put on hold Leading suppliers now seeing signs of improvement Some major projects now moving forward 2012 sales were for universities, hospitals and labs plus a few offices and police stations * Data provided by WMI, BSRIA
15 UK Fan Coil Market* Highly engineered product in UK market But.. Highly price driven Customers of fan coils look at : First price Second thermal performance Third acoustic performance * Data provided by WMI, BSRIA
16 Chilled Beams vs Fan Coil Units Active chilled beams main substitute product for FCUs Conversely, ACB players fighting back against threat of FCU through marketing: Demonstrating how ACB can be a suitable replacement for FCU Placing emphasis on: Energy efficiencies Long life expectancy Low maintenance Occupant comfort * Data provided by WMI, BSRIA
17 Market Data * Item Market ( M) Active Chilled Beams Fan Coils Variable Air Volume Volume ( Units) Active Chilled Beams 34,500 33,400 27,000 Fan Coils 51,500 54,000 46,800 Variable Air Volume 5,500 13,300 13,500 Unit price Active Chilled Beams Fan Coils Variable Air Volume * Data provided by WMI, BSRIA
18 2012 Market Data* 2012 Market Share ( M) Variable Air Volume, 5.3 Active Chilled Beams, 8.0 Variable Air Volume, 13, Market Share (units) Active Chilled Beams, 27,000 Fan Coils, 23.7 Fan Coils, 46, Unit Price Variable Air Volume, 393 Active Chilled Beams, 296 Fan Coils, 506 * Data provided by WMI, BSRIA
19 70% Market 2012 FCU Market Players (Ranked By Value) Ability Projects Diffusion Dunham Bush TEV limited Trox * Data provided by WMI, BSRIA
20 20% Market 80% Market 2012 ACB Market Players (Ranked By Value) Trox Frenger Systems (Lindab) Halton SAS international Krantz Swegon Flaktwoods LTI Advanced systems Technology (Keifer brand) Waterloo Air products Others * Data provided by WMI, BSRIA
21 Back to Agenda
22 Description and application
23 Active Chilled Beams - Considerations Still requires central bulkhead or similar for services (Supply Duct, Extract Duct, Chilled Water Pipework, Controls etc.) Careful control of primary supply air temperature required to prevent perception of cold draughts Chilled water temperature needs accurate control
24 Active Chilled Beams - Considerations Performance of the whole space needs to be evaluated The air patterns are very hard to predict Air distribution throughout the space is load dependent Computer modelling does not give the true air movement answers You MUST understand the product, how it works and how it integrates to its environment
25 Active Chilled Beams - Considerations Heating application requires careful design It can be counter intuitive Full mock-up of partial areas is the best solution to understand the product
26 Video not available in pdf. format
27 Active Chilled Beams - Advantages Cheaper to buy Low Maintenance One Fix device Does not require secondary ductwork/grilles etc. Only require simple controls On/Off is adequate for cooling Variable Self Limiting Output No condensate drainage required
28 Active Chilled Beams - Advantages Supply conditioned air to the space Large induction ratios Fully mixes the air within the space Very slow air velocities within the occupied zone Multi service beams allows ancillary services to be concealed
29 Active Chilled Beams - Advantages Works well when combined with other cooling sources Requires full scale mock-up testing to ensure that they do not interact Very quiet product Can be visually pleasing
30 Active Chilled Beams - Disadvantages Not liked by letting agents Not flexible enough No energy allowances under Building Regs. (FCU s allowed 0.6w/(l/s) - FAVAV allowed 1.2w/(l/s)) Normally requires higher system static pressures Airflow may be greater than required for occupancy
31 Active Chilled Beams - Disadvantages Poor chilled water temperature control can lead to indoor rain May require sound masking (pink noise) to maintain privacy levels Requires careful co-ordination to get the solution right
32 Back to Agenda
33 Performance testing
34 ACB Definitions Reference temperature: return air onto beam (usually underside in active beams) Mean water temperature: average of water into and out of beam Difference gives indication of cooling potential: no difference means no cooling should happen BS EN 15116:2008 Ventilation in buildings. Chilled beams. Testing and rating of active chilled beams
35 Schematic of test chamber
36 Performance Testing BS EN 15116:2008 Internal heat supply method Heat sources within chamber (DIN men) External heat supply method Heated walls (same concept as radiator test room) General principle of a calorimeter with steady state boundary conditions and 60 min steady state data
37 Performance Testing BS EN 15116:2008 Temperature difference ΔΘ = Θ r θ w Θ r = reference air temperature Θ w = mean cooling water temperature q p = primary air flow rate 3 steady state conditions at ΔΘ = 6, 8 and 10K with constant q p Repeat at ΔΘ = 8K nominal with q p at 80% and 120% to determine influence of primary air on thermal performance Repeat all five at half the nominal water flow rate
38 Performance Testing BS EN 15116:2008 Performance follows the form of P w = P k * ΔΘ m Where P w is waterside cooling capacity P k is specific cooling capacity m is an exponent Alternatively, P k = P w / ΔΘ m Also, P k = A * q p n A is a characteristic constant n is an exponent
39 Example Results
40 Example Results
41 Example Results
42 Water side duty ( W) Water side duty (W) P w (const q p ) Mean Temperature Difference (K) y = x R² = 1 Pw (const qp) Power (Pw (const qp)) P w (var q p ) Primary airflow rate (q p ) (l.s -1 ) y = x R² = Pw (var qp) Power (Pw (var qp))
43 Example graph of Capacity against temperature difference for three water flowrates
44 Same as previous showing passing through zero
45 Different beam same graph shape
46 Airflow vs. flowrate of air
47 Water side pressure drop vs. flowrate
48 Performance Testing Performance follows the form of P k = P w / ΔΘ m P k = A * q p n Report the nominal cooling capacity P N (at ΔΘ n = 8K) Optionally, cooling capacity as fn(globet- Θ w ) or fn(roomt - Θ w ) Selection guides and tables will include throw, noise figures, water and air side pressure drops as well as nozzle selections, heating coil options, etc..
49 Ball Park Numbers mm Waterside Cooling 0.02 to 0.10 l/s C supply with 1-3K rise Waterside Heating ( W/m) 0.01 to 0.04 l/s C inlet with drop of 5 to 15K Airside Cooling/Induction l/s primary air at 18 C for roomt 24 C
50 Back to Agenda
51 System performance testing
52
53 Physical modelling Predicting and measuring real life situations Achieving the correct results first time Prove beforehand that the systems and products will meet the necessary specifications Water supply (from chiller) Conditioned air Client s ventilation system AHU Ceiling void Glass window Viewing chamber Floor tiles/carpet Floor void Chamber wall Adjacent chamber Adjustable walls Control room Insulated floor ( 400 mm)
54 Physical modelling Constructing a full size representation of the proposed design for a specific part of a building interior. Full simulation of external conditions Internal loads Comprising lighting Small power and people Room furnishing and office equipment layout Fully working HVAC system.
55 Validation process Room air movement Gas tracer tests Salt tests Supply Chamber Ceiling Ceiling void Smoke tests Fans/Air conditioning system Ceiling tiles Wall Floor tiles Adjacent chamber CFD Floor extract Back passage Extract Floor void Control room Airtightness Mock-up construction Design
56 Full size mock-ups Mock-ups of any ventilation system; chilled beam configuration, offices, hospital rooms, cold cabinet testing Thermal comfort analysis Temperature and humidity readings Airtightness tests Heat load simulation (Small load, occupancy, solar load) Anemometry readings ( air speed and temperatures) Gas tracer tests Special components commissioning (pressure stabilisers, ventilation grilles, floor grilles) Thermal imaging Smoke tests
57 Offices Data centres Libraries Chilled beams Cold cabinets Hospitals
58 Real site vs mock-up
59 Job A
60 Job A
61 Job A
62 Animation Animation not available in pdf. format
63 Smoke test Video not available in pdf. format
64 Job B
65 Example of discharge profile
66 Job C
67 Example of ductwork and ceiling
68 Calc Induced Flow (l/s) Example of Pressure test Full pressure test - Beam 1 type 2 (16 Sep 05) y = x R 2 = y = x R 2 = Primary Flow (l/s) Calc Ind Flow Ratio Linear (Calc Ind Flow) Linear (Ratio)
69 Example of average parameters A PARAMETER REQUESTED VALUE AVERAGE DURING TEST SUPPLIED VALUE Water supply temperature ( C) Water return temperature ( C) To be recorded 15.9 Water flow rate (l.s -1 per beam) Water flow rate (l.s -1 all beams) N/A Cooling duty (10 beams) (W) N/A 2958 Fresh air supply temperature at point of entry to the test rig ( C) Extract temperature ( C) To be recorded 23.5 Air flow rate (l.s -1 ) Fresh air cooling duty (W) N/A 583 Total cooling (W) N/A 3541 Electrical load (W) Start End Solar load simulated with wall mounted heated mats Occupancy (6 DIN Men simulating 7.5 people) Small power gain Lighting gain Total electrical load Total electrical load (Average) Imbalance (W) 169
70 Example of parameters PARAMETER VALUE Fresh air supply volume 60 l.s -1 Fresh air supply temperature 19.0 C Beam chilled water supply l.s -1 volume for perimeter test Beam chilled water supply l.s -1 volume for core test Chilled water supply 14.0 C temperature Illuminance As produced by integral lighting system
71 Example of average parameters B PARAMETER AVERAGE SUPPLIED VALUE REQUESTED VALUE Fresh air flowrate 64.1 l.s l.s -1 Extract flowrate 62.6 l.s l.s -1 Fresh air supply temperature 19.0 C 19.0 C Extract temperature 23.4 C N/A Altrium roof load emitted into room (simulated with 3 wall mounted heat mats) 510 W 525 W Core people gain (simulated with W 600 W standard DIN men) Core small power gain (simulated with 1.69 kw kw 4 standard PCs and 7 floor heat mats) Lighting gain 905 W As produced by integral lighting system Total heating gain (perimeter, core and lighting) kw kw plus lighting gain Chilled beam water flow temperature 13.9 C 14 C Chilled beam water return 16.4 C N/A temperature Chilled beam water flowrate 0.28 l.s l.s -1
72 Parameter Average cooling during Test 3 (kw) Chilled beam cooling effect 2.93 Air cooling effect 0.34 TOTAL COOLING 3.27 kw
73 Back to Agenda
74 Ugly Duckling or Hidden Swan?
75 Chilled Beams - Advantages Cheap to Buy and Maintain Simple principals Simple Controls Give a well conditioned space Very adaptable Quiet Energy Efficient
76 Chilled Beams - Disadvantages Not always popular Lack of application knowledge can restrict use Low noise may be an issue Integration into environment may not be as simple as it seems - Can be hard to get right
77 Questions and answers
78 Q&A Session Adaptive temperature theory Turbulent water flow Uneven load distribution Load location fighting the beam Windows impinging on active beam lengths Control strategy
79 Back to Agenda
ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS
ANSI/ASHRAE STANDARD 200-2015, METHODS OF TESTING CHILLED BEAMS NEMIC 2017 Agenda 1. Foreword 2. Purpose & Scope 3. Definitions 4. Instrumentation & Facilities 5. Test Methods 6. Reporting 7. Normative
More informationChilled Beams. The new system of choice?
Chilled Beams The new system of choice? Presented By: Kevin M. Pope P.E. Jason Leffingwell Hammel Green And Abrahamson, Inc. and Ken Bauer, P.E., LEED AP Butters-Fetting Co., Inc. History of Chilled Beams
More informationSustainable Chilled Beam Design
MAIJA VIRTA HARRI ITKONEN PANU MUSTAKALLIO MIKA RUPONEN RISTO KOSONEN 1 - Halton Oy ABSTRACT Chilled beam technology is seen as a very sustainable technology providing both excellent indoor conditions
More informationACBC Floor Mounted Active Beam
Floor Mounted Active Beam The Price Floor Mounted Active Beam,, is designed for occupant comfort. It provides high cooling and heating capacities while simultaneously supplying ventilation air from a DOAS
More informationFEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF
FEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF Oliver Baumann 1, and Claudius Reiser 1/2 1 Ebert & Baumann Consulting Engineers, Washington, D.C. 2 Ebert-Ingenieure GmbH &Co. KG, Munich,
More informationDEMAND CONTROLLED VENTILATION (DCV) SYSTEMS
DEMAND CONTROLLED VENTILATION (DCV) SYSTEMS Mari-Liis Maripuu, PhD CIT Energy mari-liis.maripuu@cit.chalmers.se Swegon Air Academy, Portugal, 27 May 211 Outline Introduction Concept of a DCV system Adapting
More informationAchieving acoustical standards in the classroom Study of HVAC systems and classroom acoustics
Achieving acoustical standards in the classroom Study of HVAC systems and classroom acoustics Trane believes the facts and suggestions presented here to be accurate. However, final design and application
More informationAIRCOOL VENTILATORS FURTHER INFORMATION
.................................................. CI/SfB (57.7) Xy Uniclass L7563 January 2015 FURTHER INFORMATION................................................................... Services Passivent
More informationDemonstration of modeling of radiant cooling system in design builder. Prashant Bhanware & Bharath Reddy
Demonstration of modeling of radiant cooling system in design builder Prashant Bhanware & Bharath Reddy CONTENTS Introduction to Design Builder Building Energy Simulation Modeling procedure Making a model
More informationMilwaukee, WI. Darron Rempel
Application of Hydronic Radiant and Beam Systems ASHRAE Region IV Conference Milwaukee, WI May 14, 2010 Darron Rempel darronr@price hvac hvac.comcom Introduction Topics covered: o Theory of using water
More informationAsset Energy Calculator Guidance
Asset Energy Calculator Guidance Introduction This section has been produced to give BREEAM In-Use assessors further guidance on the workings of the asset energy calculator so it is clear how any improvements
More informationDEVELOPMENT AND CONSTRUCTION OF BIOCLIMATIC DOUBLE SKIN ACTIVE FACADE FOR HOT AND HUMID CLIMATE OF UAE
DEVELOPMENT AND CONSTRUCTION OF BIOCLIMATIC DOUBLE SKIN ACTIVE FACADE FOR HOT AND HUMID CLIMATE OF UAE Eng. Ray Karbor MSc. Director Engenius Green Technology FZE RAK, UAE & Ex-Sustainability Manager Reem
More informationEADQUARTERS. Thesis Revised Proposal. Stephanie Kunkel Mechanical Option
EADQUARTERS 707 N. Calvert St. Mechanical System Renovation Construction Management & Lighting/Electrical Breadths Stephanie Kunkel www.engr.psu.edu/ae/thesis/portfolios/2011/slk5061 Mechanical Option
More informationARPAN JOHARI. Architect. 13/08/10 AW Design. Ahmedabad
ARPAN JOHARI. Architect THERMAL MASS Thermal mass (or thermal capacitance) is defined as the ability of a body to store heat THERMAL MASS Thermal mass is also known as Fabric Energy Storage, FES (The Concrete
More informationDISPLACEMENT VENTILATION
DISPLACEMENT VENTILATION D3 OVERVIEW The fundamental approach to displacement ventilation utilizes the natural buoyancy forces created by the convective flows from heat sources in the space. As supply
More informationApplication of Advanced Energy Technologies
GLOBALCON 2002 Philadelphia, Pennsylvania March 27, 2002 Application of Advanced Energy Technologies Michael K. West, Ph.D., P.E. Building Systems Scientist Advantek Consulting, Inc. www.advantekinc.com
More informationHourly Analysis Program v.4.1 Page 1 of 1
Air System Design Load Summary for Zona 11 DESIGN COOLING DESIGN HEATING COOLING DATA AT Dec 1700 HEATING DATA AT DES HTG COOLING OA DB / WB 33.1 C / 23.5 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible
More informationAir Conditioning Inspections for Buildings Assessing Equipment Sizing
Air Conditioning Inspections for Buildings Assessing Equipment Sizing PRESENTED BY NIRAJ MISTRY aircon@stroma.com Size V s Load Regulation 22 of EPB Regulations The inspection report must include an assessment
More informationAn experimental investigation of a passive chilled beam system in subtropical
An experimental inestigation of a passie chilled beam system in subtropical conditions Alex Hole 1, Risto Kosonen 2 1 Arup, Sydney - Australia 2 Halton, Kausala - Finland Corresponding email: alex.hole@arup.com.au
More informationACBC Floor Mounted Active Beam
Floor Mounted Active Beam The Price Floor Mounted Active Beam,, is designed for occupant comfort. It provides high cooling and heating capacities while simultaneously supplying ventilation air from a DOAS
More informationCOMMERCIAL LOAD ESTIMATING. Load Estimating Level 3: Block and Zone Loads. Technical Development Program
COMMERCIAL LOAD ESTIMATING Load Estimating Level 3: Block and Zone Loads Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design,
More informationBUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY. Dr Mirek Piechowski 1, Adrian Rowe 1
BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY Dr Mirek Piechowski 1, Adrian Rowe 1 Meinhardt Building Science Group, Meinhardt Australia 1 Level 12, 501
More information35% reduction in water use below code maximum 83% 88% 49% reduction in lighting power density 12%
Science Center Cabot Library Project LEED CI v4.0 1 Oxford Street, Cambridge, ma LEED Certified Project Profile December 2017 The Science Center Cabot Library project was comprised of renovating the entry,
More informationHourly Analysis Program v.4.1 Page 1 of 1
Air System Design Load Summary for Zona 8 DESIGN COOLING DESIGN HEATING COOLING DATA AT Dec 1700 HEATING DATA AT DES HTG COOLING OA DB / WB 33.1 C / 23.5 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible Latent
More informationOptimizing Indoor Environments for Occupant Satisfaction. Presented by: Kelli Goldstone April 2016
Optimizing Indoor Environments for Occupant Satisfaction Presented by: Kelli Goldstone April 2016 Outline Function of HVAC Thermal Comfort Air Distribution Radiant Heating / Cooling Case Study Function
More informationAll panels can be supplied in a range of styles, to suit the applications pictured below.
Evolution Radiant panel system LPHW up to 90 C Suspended ceiling grid or soffit mounting Vertical wall surface mounting Standard widths 150mm to 900mm 1 Description Introduction Evolution by Dunham-Bush
More informationPrinciples of Ventilation and Air Conditioning Design & Installation
Unit 10: Unit code Principles of Ventilation and Air Conditioning Design & Installation D/615/1926 Unit level 4 Credit value 15 Introduction The demands of modern living as well as the potential impact
More informationENGINEERING UPDATE WHITE PAPER: BUILDING PERFORMANCE METRICS. price-hvac.com. May 2013 Vol. 10
ENGINEERING UPDATE May 2013 Vol. 10 WHITE PAPER: BUILDING PERFORMANCE METRICS By Hugh Crowther P. Eng. Executive Vice President, Product Management and Technology There is a steady and determined march
More informationThe Art of Thermal Mass Modeling for Energy Conservation in Buildings, Part 2
The Art of Thermal Mass Modeling for Energy Conservation in Buildings, Part 2 Linda Lam is a Project Engineer at Transsolar, Inc. She has a traditional mechanical engineering background with an energetic
More informationSCHOOL OF MUSIC UNIVERSITY OF IOWA IOWA CITY, IOWA
Project Data Total Project $150,000,000 Construction $115,000,000 MEP Const $28,000,000 Owner University of Iowa Rodney P. Lehnertz Director, Planning, Design & Const 319.353.3325 rodney-lehnertz@uiowa.edu
More informationCeiling Radiant Cooling Panels
2006, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc (wwwashraeorg) Published in ASHE Journal Vol 48, Oct 2006 For personal use only Additional reproduction, distribution,
More informationDesigning Air-Distribution Systems To Maximize Comfort
Designing Air-Distribution Systems To Maximize Comfort By David A. John, P.E., Member ASHRAE An air-distribution system that provides occupant thermal comfort can be a complicated system to predict and
More informationModelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates
Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates Kittitach Pichatwatana, and Fan Wang Abstract This paper examines the TAS computer
More informationThese systems are offered an alternative to overhead, mixing ventilation (MV), systems. Due to their potential advantages which are [1]:
Prediction of thermal comfort, IAQ, and Energy consumption in a dense occupancy environment with the under floor air distribution system Ghassem Heidarinejad 1, Mohammad Hassan Fathollahzadeh 2, Hadi Pasdarshahri
More informationThe optimization of the mechanical night cooling system in the office building
The optimization of the mechanical night cooling system in the office building Milos Lain 1, Jan Hensen 2 1 Department of Environmental Engineering, Faculty of Mechanical Engineering, Czech Technical University
More informationVarennes Net-Zero Library City of Varennes
Varennes Net-Zero Library City of Varennes 2016 Canadian Consulting Engineering Awards 2016 Canadian Consulting Engineering Awards Varennes Net-Zero Library 1 ii 2016 Canadian Consulting Engineering Awards
More informationThe Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma
LEED Green Building Certification The purpose of the LEED Green Building Rating is to provide a national standard that aims to improve environmental, health and economic performance of buildings using
More informationUsing CFD to Wring Out Energy Efficiency in Laboratory Settings
Using CFD to Wring Out Energy Efficiency in Laboratory Settings Energy Conservation Strategies for Cornell University Laboratories Primary focus is on controls to reduce outside air use Occupancy sensors
More informationCitation (APA) Bluyssen, P. M. (2017). SenseLab: a genuine playground for the senses. Rehva Journal, 54(2),
Delft University of Technology SenseLab a genuine playground for the senses Bluyssen, P.M. Publication date 2017 Document Version Final published version Published in Rehva Journal Citation (APA) Bluyssen,
More informationCentre for Sustainability of the Built Environment
Case Study Report Indoor air quality of a demandcontrolled air-conditioning system Mayfield House Lecture Theatre, Falmer Campus, University of Brighton European Regional Development Fund Executive summary
More informationApplied Noise Control. D. W. Herrin, Ph.D., P.E. University of Kentucky Department of Mechanical Engineering
D. W. Herrin, Ph.D., P.E. Department of Mechanical Engineering Outline of Topics 1. Introduction 2. Noise Control at Source 3. Noise Control of Transmission Path 4. Protection at Receiver 5. Summary 2
More informationTHERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE
S447 THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE by Bojan V. ANDJELKOVIĆ *,a, Branislav V. STOJANOVIĆ b, Mladen M. STOJILJKOVIĆ b, Jelena N. JANEVSKI
More informationCOMFORT-PRODUCTIVITY Building costs COMFORT-PERFORMANCE. Radiant Heating and Cooling Systems for Better Comfort and Energy Efficiency INDOOR - OUTDOOR
Radiant Heating and Cooling Systems for Better Comfort and Energy Efficiency Professor Bjarne W. Olesen, PhD Director International Centre for Indoor Environment and Energy Department of Civil Engineering
More informationTHERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE
Andjelković, V., B.et. al.: Thermal Mass Impact on Energy Performance of A Low, Medium and Heavy S507 THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM AND HEAVY MASS BUILDING IN BELGRADE by Bojan
More informationArticles. Figure 2. Typical set-up of personalized ventilation system.
Revision of 15251: ndoor Environmental Criteria Abstract: 15251 specifies indoor environmental input parameters for design and assessment of energy performance of buildings addressing indoor air quality,
More informationCan we feel safe in this building?
Room Control and Indoor Air Quality Benefits and Environmental Impacts Can we reduce our building expenses? Can we decrease our absenteeism rate? Can we feel safe in this building? How green are our buildings?
More informationENERGY CALCULATOR & MODELLING PROTOCOL
Green Star SA Retail Centre v1 ENERGY CALCULATOR & MODELLING PROTOCOL GUIDE VERSION 1.1 Last Update: 17 June 2010 1 Executive Summary The Green Star SA Retail Centre v1 rating tool has been developed to
More informationCOUPLING STRATEGY OF HVAC SYSTEM SIMULATION AND CFD PART 2: STUDY ON MIXING ENERGY LOSS IN AN AIR-CONDITIONED ROOM
12th Conference of International Building Performance Simulation Association, Sdne, 14-16 November. COUPLING STRATEGY OF HVAC SYSTEM SIMULATION AND CFD PART 2: STUDY ON MIXING ENERGY LOSS IN AN AIR-CONDITIONED
More informationPRODUCT MODELS AND LIFE CYCLE DATA MANAGEMENT IN REAL PROJECTS
PRODUCT MODELS AND LIFE CYCLE DATA MANAGEMENT IN REAL PROJECTS Reijo Hänninen, Olof Granlund Oy (reijo.hanninen@granlund.fi) Tuomas Laine, Olof Granlund Oy (tuomas.laine@granlund.fi) Summary Building project,
More informationCorporate Environments
Acoustics and the Impact on Corporate Environments falconproducts.com Achieving High-Quality Acoustics in Corporate Settings Knowledge is power. Here s what you need to know about sound, noise and creating
More informationSarawak Energy s New Low Energy HQ And first green building in Sarawak
Sarawak Energy s New Low Energy HQ And first green building in Sarawak Presented on behalf of the design team by: Gregers Reimann, MD IEN Consultants www.ien.com.my 1 October 2012 [Slides by IEN Consultants
More informationclimatic responsive tall buildings a sustainable & practical design approach
climatic responsive tall buildings a sustainable & practical design approach presented by vince ugarów director, hilson moran swegon air academy seminarium helsinki helsingfors 10 may 2012 introduction
More informationPRODUCT RANGE OF GRILLES, DIFFUSERS, LOUVRES AND DAMPERS
Monodraught are the recognised market leaders in ultra-low carbon, low energy solutions for Natural Ventilation, Natural Cooling and Natural Lighting. WINDCATCHER, SUNPIPE and COOL-PHASE brands are synonymous
More informationThe Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort
The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort Ongun Berk Kazanci, Bjarne W. Olesen 1 1 International Center for Indoor Environment and
More informationInformation Delivery Manual (IDM)
Piping Engineering - Confluence http://idm.buildingsmart.no/confluence/display/idm/piping+engineering?decorator=printable 1 af 2 11-09-2011 19:21 Information Delivery Manual (IDM) Added by Jeffrey Wix,
More informationAssessor Name: Membership number: Reference: Level of assessment: L3 L4 New Post code:
Project /Survey Details Address: Assessor Name: Membership number: Reference: Level of assessment: L3 L4 New Post code: Building Age: Weather : Conservation status: Building plans available: Yes No Date
More informationLindabPlexus. Supply air beam. lindab we simplify construction
Lindab 11.2017 Lindab Ventilation. All forms of reproduction without written permission are forbidden. is the registered trademark of Lindab AB. Lindab's products, systems, product and product group designations
More informationUnderf loor For Schools
The following article was published in ASHRAE Journal, May 2008. Copyright 2008 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes
More informationUC Berkeley HVAC Systems
UC Berkeley HVAC Systems Title Simplified calculation method for design cooling loads in underfloor air distribution (UFAD) systems Permalink https://escholarship.org/uc/item/5w53c7kr Authors Schiavon,
More information2001 National Workshop on State Building Energy Codes July th, 2001 Burlington, Vermont
2001 National Workshop on State Building Energy Codes July 16-19 th, 2001 Burlington, Vermont A Systems Engineering Approach to the Design of Energy and Resource Efficient Homes Presented By: Mark LaLiberte
More informationVentilative Cooling potential tool
Ventilative Cooling potential tool User guide Version 1.0 IEA EBC Programme Annex 62 Ventilative Cooling AUTHORS: ANNAMARIA BELLERI EURAC RESEARCH Institute for renewable energy Druso 1 39100 Bolzano Italy
More informationGreat Ocean Rd Ice Creamery
Great Ocean Rd Ice Creamery BCA Section J - JV3 Compliance Report Revision: 01 Job No: 2171 Date: 7 July 2015 ADP Consulting Pty Ltd Level 10, 10 Queens Rd, Melbourne Vic 3004 www.adpconsulting.com.au
More informationIMPACT OF COLUMNS AND BEAMS ON THE THERMAL RESISTANCE OF THE BUILDING ENVELOPE
IMPACT OF COLUMNS AND BEAMS ON THE THERMAL RESISTANCE OF THE BUILDING ENVELOPE Dr. Essam Al-Sayed Omar Department Manager Kuwait Institute for Scientific Research Kuwait ABSTRACT This paper addresses the
More informationStudent Modeling Competition
Student Modeling Competition Design and Simulation of a Laboratory Building Building Simulation 2017 Briefing Document Zahraa Saiyed Ben Brannon Anna Brannon Christina Hopfe Gerhard Zweifel Student Modeling
More informationPDHengineer.com Course M-3020
PDHengineer.com Course M-3020 Ductwork Exterior Exposed To receive credit for this course This document is the course text. You may review this material at your leisure either before or after you purchase
More informationCOMPARISON OF THE STANDARDIZED REQUIREMENTS FOR INDOOR CLIMATE IN OFFICE BUILDINGS
Kazderko Mikhail COMPARISON OF THE STANDARDIZED REQUIREMENTS FOR INDOOR CLIMATE IN OFFICE BUILDINGS Bachelor s Thesis Building Services Engineering December 2012 DESCRIPTION Date of the bachelor's thesis
More informationIntegrated Solution PARTNERS
Integrated Solution PARTNERS PERFECT Integration We take great pride in creating time for our customers through pre-engineered solutions and integrated partnerships. The result a wide range of compatible
More informationTrends and drivers in the Finnish ventilation and AC market
Trends and drivers in the Finnish ventilation and AC market Jarek Kurnitski, D.Sc. Docent Helsinki University of Technology Finnish Society of Indoor Air Quality and Climate, FiSIAQ 1 Contents Indoor climate
More informationBaffled Openings at Chain Link Fencing: Design shall consist of two end-posts set 4 feet apart, and a 10 foot wide chain-link fence panel equal in height as the adjacent fence. Chain link fence panel shall
More informationI. Khoo, BEng(Hons), G.J. Levermore, BSc, ARCS, PhD, DIC, CEng, FCIBSE, MASHRAE, MInstE, K.M. Letherman, BSc, MSc, PhD, CEng, FIEE, FCIBSE.
Duct Loops and VAV Modelling and Control I. Khoo, BEng(Hons), G.J. Levermore, BSc, ARCS, PhD, DIC, CEng, FCIBSE, MASHRAE, MInstE, K.M. Letherman, BSc, MSc, PhD, CEng, FIEE, FCIBSE. Abstracts This paper
More informationTrane Engineers Newsletter Live. Specifying Quality Sound Presenters: Dave Guckelberger, Brian Reynolds, Art Hallstrom
Trane Engineers Newsletter Live Presenters: Dave Guckelberger, Brian Reynolds, Art Hallstrom Agenda Trane Engineers Newsletter Live Series Abstract After viewing this program you will understand how product
More informationRENOVATIONS & REFURBISHMENTS
RENOVATIONS & REFURBISHMENTS This Activity received funding from the Department of Industry as part of the Energy Efficiency Information Grants Program The nature of the tourism and hospitality industries
More informationEnergy Savers: Air-Source Heat Pumps
1 of 5 4/25/2009 8:55 AM U.S. Department of Energy - Energy Efficiency and Renewable Energy Energy Savers Air-Source Heat Pumps An air-source heat pump can provide efficient heating and cooling for your
More informationASHRAE Chapter Meeting HVAC Noise & Vibration Control Specifications & Best Practices
ASHRAE Chapter Meeting HVAC Noise & Vibration Control Specifications & Best Practices Industrial Presented By OEM Architectural Noise & Vibration Control, Inc. 610-863-6300 www.brd-nonoise.com HVAC Marine
More informationNoise Control. Commercial, Industrial, and Environmental Products and Solutions.
Noise Control Commercial, Industrial, and Environmental Products and Solutions www.kineticsnoise.com Commercial Duct Silencers Kinetics Noise Control offers the design and engineering assistance to integrate
More informationGeneral Specifications for HVAC System Cleaning
General Specifications for HVAC System Cleaning Part 1 Special Provisions 1.01 Qualification of the HVAC System Cleaning Contractor (A) Membership: The HVAC system cleaning contractor shall be a member
More informationBuilding & Ductwork Airtightness Standards
Building & Ductwork Airtightness Standards Version 1.02, August 2013 Standard Reference Technical Body Title ICS (International Classification for Standards) Scope Door and Windows EN 12207:1999 Windows
More informationTate Laboratory of Physics Building Analysis
Tate Laboratory of Physics Building Analysis Adam Lapacz, Andrew Olson, Daniel Greuel, Indira Manandhar, Kyle Snyder, Mark Kelly, Molly McClung, Stefanie Perez, Tony Palmer Built: 1927 Located: East Bank
More informationLTG Air Diffusers. Product Overview. Outstanding technique for highest demands. Unique in comfort, acoustics and design.
The Innovation Company LTG Incorporated Product Overview LTG Air Diffusers Outstanding technique for highest demands. Unique in comfort, acoustics and design. LTG Incorporated 1 LTG Air Technology Solutions
More informationEnergy-Efficient Passive House using thermal mass to achieve high thermal comfort
Energy-Efficient Passive House using thermal mass to achieve high thermal comfort Loa Andersson Managing Director RLI Byggdata AB rli@termodeck.com Alexander Engström Technical Director RLI Byggdata AB
More informationBuilding Envelope Commissioning and Building Diagnostic Test: Case Studies Course Number: CXENERGY1506
AABC Commissioning Group AIA Provider Number: 50111116 Building Envelope Commissioning and Building Diagnostic Test: Case Studies Course Number: CXENERGY1506 Dan Adam, RA, CxA, Facility Commissioning Group
More informationASTATT1 Prepare to carry out air tightness testing
ASTATT1 Prepare to carry out air tightness testing Overview This standard is for those who carry out air tightness and/or air change rate testing of buildings of any size or complexity. It covers those
More informationCanada Published online: 28 Feb 2011.
This article was downloaded by: [Bibliothèque ÉTS] On: 21 July 2015, At: 04:30 Publisher: Taylor & Francis Informa Ltd Registered in England and Wales Registered Number: 1072954 Registered office: 5 Howick
More informationEcolibrium. Positive step Embedding health in design. THE OFFICIAL JOURNAL OF AIRAH MARCH 2017 VOLUME 16.2 RRP $14.95
THE OFFICIAL JOURNAL OF AIRAH MARCH 2017 VOLUME 16.2 Ecolibrium RRP $14.95 Positive step Embedding health in design. PRINT POST APPROVAL NUMBER PP352532/00001 The heart of the matter The Sydney home of
More informationBCA Section J Compliance Report. Alterations & Additions to Cottage at St Johns College 10 Missenden Road Camperdown
BCA Section J Compliance Report Alterations & Additions to Cottage at St Johns College 10 Missenden Road Camperdown Prepared by: Gradwell Consulting ABN 68 872 791 784 Sustainability Consultants PO Box
More informationIntelliPak Ton and IntelliPak II Ton Rooftops
IntelliPak 20-130 Ton and IntelliPak II 90-150 Ton Rooftops Subject: Indoor Sound Issued by: Clarksville Large Commercial Unitary June 2008 RT-PRB022-EN Table of Contents Engineering Bulletin....................................................
More informationPlanning for Biomed Facility Puts Energy Efficiency Under Microscope
Planning for Biomed Facility Puts Energy Efficiency Under Microscope Chilled beams, runaround-loop ERV system included May 19, 2014 By DAN VASTYAN, Common Ground, Manheim, Pa. HPAC Engineering Constructing
More informationABSTRACT I. INTRODUCTION II. METHODS AND MATERIAL
2017 IJSRSET Volume 3 Issue 2 Print ISSN: 2395-1990 Online ISSN : 2394-4099 Themed Section: Engineering and Technology Chiller and AHU Design for A commercial Usage S M Azfar Hashmi, Mirza Muneer Baig,
More informationSenior Design Project for UNO. Design of the International Studies Building: An Environmental Analysis
Senior Design Project for UNO Design of the International Studies Building: An Environmental Analysis Design Intent Implement Passive & Active design strategies in order to make the building: More Energy
More informationHeat Rejection using Cooling Towers
MEBS6006 Environmental Services I http://www.hku.hk/bse/mebs6006 Heat Rejection using Cooling Towers Dr. Benjamin P.L. Ho (beplho@yahoo.com.hk) Part-time Lecturer Department of Mechanical Engineering The
More informationNASA Langley Research Center Administration Office Building One Hampton, VA. Project Proposal. Introduction to Proposed Design Alternatives Revision 1
NASA Langley Research Center Administration Office Building One Hampton, VA Project Proposal Introduction to Proposed Design Alternatives Revision 1 Valerie Miller Mechanical Dr. Freihaut Revised 01/16/2015
More informationLindabCarat. Chilled beam. lindab we simplify construction
lindab we simplify construction Lindab 08.2016 Lindab Ventilation. All forms of reproduction without written permission are forbidden. is the registered trademark of Lindab AB. Lindab's products, systems,
More informationGeneral guidelines for using thermal mass in concrete buildings
General guidelines for using thermal mass in concrete buildings 1 THERMAL MASS - BEST PRACTICE GUIDELINES FOR HOUSING In warm climates, the thermal mass in concrete and masonry helps provide a comfortable
More informationEarth, Wind & Fire Natural Airconditioning [1] Research objectives and Methods
Earth, Wind & Fire Natural Airconditioning [1] Research objectives and Methods Ben Bronsema Department of Architectural Engineering, Faculty of Architecture, Delft University of Technology, The Netherlands
More informationMSC Guidelines for Review of Ventilation System Plans
K. B. FERRIE, CDR, Chief, Hull Division Purpose: This Plan Review Guideline (PRG) explains the requirements for seeking plan approval of ventilation systems from the Marine Safety Center (MSC) for most
More informationPRODUCT BROCHURE. Fixed Helical Swirl Diffuser HSC-FD HSC-FD : smartemp.com
PRODUCT BROCHURE Fixed Helical Swirl Diffuser HSC-FD HSC-FD : 07 smartemp.com DESCRIPTION The SMARTEMP Fixed Helical Swirl Diffuser, type HSC-FD, produces highly inductive swirl discharge, diffusing the
More informationHeat Load Calculation for the Design of Environmental Control System of a Light Transport Aircraft
International Journal of Scientific & Engineering Research, Volume 7, Issue 5, May-2016 249 Heat Load Calculation for the Design of Environmental Control System of a Light Transport Aircraft Rahul Mohan.P1,
More information