STUDY OF HEATING AND COOLING SYSTEMS TO DESIGN ZERO ENERGY BUILDINGS

Size: px
Start display at page:

Download "STUDY OF HEATING AND COOLING SYSTEMS TO DESIGN ZERO ENERGY BUILDINGS"

Transcription

1 STUDY OF HEATING AND COOLING SYSTEMS TO DESIGN ZERO ENERGY BUILDINGS ABSTRACT By 2020 all new buildings within the European Union should reach nearly zero energy levels. Their energy needs should be significantly covered by renewable energy sources. As a consequence, it is important to identify which combinations of technologies will be suitable in order to reach such objectives. Climate conditions, final energy and investment costs, technological maturity and stakeholders services quality are key elements for the final choice. This paper presents the first results of a more general survey the purpose of which is to study different combinations of heating - cooling systems integrated in single-family dwellings under the Belgian climate conditions. Eight representative dwellings and one heating system composed of solar collectors and an air-towater heat pump were selected. The dwellings were chosen in such a way that different insulation levels may be studied: we considered houses with an insulation level that just respects the 2008 EPBD legislation (arête du gouvernement wallon, 2008) as well as very low energy houses. The heat pump and solar collectors are connected to a heat storage water tank as well as to a DHW reservoir. A design procedure based on energy needs is proposed and applied to each dwelling-system. The design characteristics of the system are then integrated in a simulation software (TRNSYS 17) to perform a one-year energy performance calculation (Klein, S.A, et al.,2000). The results show that the solar coverage ratio for DHW production ranges from 52% (very low energy buildings) to 76% (EPBD buildings). The solar coverage ratio for space heating ranges from 3% (very low energy buildings) to 9% (EPBD buildings). Whatever the kind of building, the seasonal performance factor of the heat pump is about The total non renewable primary energy that is used is about 57% of the total heat demand. INTRODUCTION Improvement of the energy efficiency is the most cost-effective and fastest way both to increase security of energy supply and to reduce the greenhouse gases emissions responsible for climate change. In the EU, buildings represent about 40% of the final energy consumption. For residential houses, two thirds of this energy consumption is for space heating. Therefore, the reduction of energy consumption and the use of energy from renewable sources in the building sector are important measures for the European Union. In May 2010, the EU recast the directive on the energy performance of buildings. In this directive (Directive 2010/31/EU, 2010), the European Commission proposes that Member States shall ensure that by 2020 all new buildings are Nearly Zero Energy Buildings (NZEB). NZEB means a building that requires a very low amount of energy so that it can be produced, to a very significant extent, by use of renewable sources (produced on-site or nearby the building). Member States shall transpose and precise these definitions in their own legislative system. Further information about the maximum allowable energy demand, the minimum coverage rate by renewable energy is indeed required. Considering the definition proposed by Torcellini, Pless and Deru (Torcelli et al., 2006), a ZEB (Zero Energy Building) produces on site at least as much energy as it uses in a year. There is no technological barrier to conceive a ZEB based on such a definition. However, economic considerations like investment and energy costs as well as climatic conditions and reliability of the stakeholders have to be taken into account at the national level. This is the reason why each Member State may adapt the concept of ZEB to NZEB to its own reality. One of the main questions that arises when defining a NZEB is whether it is better to promote very low energy demand (passive houses) or high coverage by renewable energies in just low energy buildings. Low energy demand should be encouraged before considering efficient and renewable energy

2 production. However, it can be difficult to justify economically the use of complex energy production systems in passive houses due to low absolute energy gains they lead to. Furthermore, the maximum required heat power is often less than a few kw in such dwellings and the heat demand for DHW is often equal to the heat demand for space heating. These particularities require specific solutions (low power heat generators, high efficiency at both low and high production temperatures, new design procedures, adapted control strategy). Obviously, such solutions already exist: the PassivHaus Insitute reports that 33% of high performance buildings use integrated systems for heating and DHW production (Pfuger, 2008). These integrated systems use solar collectors and a water tank to cover the energy needs of the buildings. Nevertheless, it is important that the public sector set clear rules and propose actions to accompagny both citizens and stakeholders in this technological transition. This is even more important in a country which mainly imports existing technologies rather than producing them. These rules and actions are: - To define clear objectives in terms of maximum allowable energy demand and give advice as to the kind of technology to be used for energy production; these recommendations and rules will be based on scientific studies taking into account national specificities; - To support measurement campaigns to validate new concepts of energy production; - To develop and promote knowledge and education programmes for a suitable integration of energy production systems in low energy and passive buildings; - To promote R&D activities in this domain. This paper presents the first results of a more general survey the purpose of which is to study different combinations of heating - cooling systems integrated in one-family dwellings. It is based on simulation rather than on experience. The dwellings were selected in such a way that different insulation levels may be studied: we considered houses with an high level of insulation as well as others that just respect the 2008 legislation (first EPBD rules in Belgium). Sample buildings are representative of what is being constructed now in Belgium on the one hand and in South of France on the other hand. All buildings will be studied under Belgian and South of France climatic conditions so that experience in construction methods may be shared. All combinations of energy production technologies will also be tested in these two climatic conditions except that cooling technologies will not be considered for Belgium. The first technology combinations that are being considered are taken from Annex 38 Task 44 of the HPP and SHC implementing agreements of IEA. Other technologies and their coupling will be considered in a second step of the research programme. The final purpouse is to identify which heatingcooling system in which kind of building is the most appropriate solution to minimize the use of non renewable energy taking into account economic considerations. Conception and sizing rules as well as basic control strategies are also proposed. In this paper we present results for the eight buildings under the Belgian climate conditions. The heating system that is considered is a coupling of a heat pump and solar colectors. METHOD This section presents the strategy for the whole project. It is divided in several steps: - Sample buildings selection; - Simulation of their thermal behaviour; - Results analysis: annual heat demand, maximum required heat power; For each combination of technologies for heating and cooling: - Proposal of design rules for the main components of the heating-cooling system (production, storage and distribution/emission) and application to all buildings; - Simulation of the thermal behaviour of the overall system (building + equipment); - Results analysis (non renewable primary energy consumption; weight of the different technologies in the final energy production); - Sensitivity study (based on design and control strategy parameters) - Economic survey. BUILDINGS MAIN CHARACTERISTICS Single-family houses are the most common residential building type in Belgium. As stated in ESE 2001 study, 76% of the Belgian people live in a single-family dwelling. For the purpouse of this study, eight representative dwellings were selected. All of them have different energy performance, insulation concepts (outside, inside or distributed), structures (wood, brick or concrete) and thermal inertia. However, they all have similarities which allow for a better comparison: all houses have approximately 200m of living space, two floors, and are occupied by a four-person family. The characteristics of these reference buildings are presented in Table

3 Location Structure Insulation principle Inertia Area (m ) Strépy Concrete Outside Medium 160 Epinois Wood Betweenrafter Light 194 Alès Concrete Outside and Medium 186 (France) inside Lobbes Wood Outside Low 138 Château Wood Betweenrafter Light 200 Neuf (France) Chiché Monomur Distributed Low 183 (France) blocks Haine St Brick Outside Heavy 155 Paul Strépy Brick Outside Low 153 Table 1: Sample buildings information The overall heat transfer coefficients (U value) for each building are given in table 2. U_value_wall U_value_roof (W/m.K) (W/m.K) 1 0,084 0, ,100 0, ,154 0, ,335 0, ,21 0, ,292 0, ,265 0, ,312 0,216 Table 2: Overall heat transfer coefficient HEATING SYSTEM DESCRIPTION In the first combination of technologies that is studied, heat is produced by thermal collectors (TC) and by an air-to-water heat pump (HP). Both systems are used for space heating and DHW preparation. Figure 1 presents the complete system when working for space heating: a water tank (B1) is used as heat storage. The thermal solar collectors are connected to this heat storage by a heat exchanger (HX1) whereas the heat pump condenser is directly connected to it. The water tank is also linked to an air-to-water heat exchanger (HX2) which delivers warm air to the building. Whenever possible, thermal solar collectors are used to produce heat and to store it. The heat pump is used only if there is a heat demand from the building and if the temperature at the top of the water tank is below a set temperature. Ambient Air Figure 1: Heat production, storage and emission system (space heating) As shown in Figure 2, a similar configuration is used for domestic hot water preparation: both the heat pump and the solar collectors are connected to another water tank (B2). Whenever possible, the water tank is heated using the solar collectors; the heat pump operates only in case of hot water demand if the required water temperature is not reached at the top of the tank.. Ambient Air (C1) (HP) (TC) (C1) (HP) (TC) (C2) (C2) (HX1) Figure 2: Heat production and hot water storage system (DHW preparation) HEATING SYSTEM : DESIGN RULES AND MAIN CHARACTERISTICS FOR SIMULATION Solar collectors The following solar collectors characteristics are taken for simulation: Orientation: South; Slope : 60 ; No shade; Flat-plate solar collectors : efficiency curve parameters: 0 = , 1 = W/(m K) et 2 = W/(m K ). The total surface area is calculated in such a way that the estimated solar heat production during April, May, September and October may cover the space heating needs during the same period. Such a rule was developed in a first step of the study when only space heating was considered. Heat pump The air-to-water heat pump is selected in such a way that its heat capacity in standard conditions (A -5 C/W35 C) is equal to the building heat loss flow- (B1) (B2) (HX3) (C3) (HX2) DHW (F) Supply water Building

4 rate calculated for an outside temperature of -5 C. The heat pump model consists in a performance map provided by the manufacturer and adapted to the simulation tool requirements (heat capacity and absorbed power as a function of outside temperature and inlet water temperature at the condenser). The same model is used for all buildings but a weighing factor is applied to the thermal heat capacity and absorbed power in order to fit the sizing rule for each building. Water tanks Water tanks are modelled as stratified vertical and cylindrical water tanks with two inlets and two outlets as well as connections to an internal heat exchanger. All stratification nodes of the tank have a uniform size. Low thermal losses (1.2 kj/(m.k.h)) are considered. Volumes are taken equal to 1000 l for B1 and 200 l for B2. Heat exchangers The air-to-water heat exchanger that provides warm air to the building is modelled as a counter-flow fluid-to-fluid heat exchanger with a constant efficiency of 0.7. The surface area of the solar heat exchanger is 0.9 m for DHW production and 1.12 m for space heating. Pumps, fan and flow-rates Mass flow-rates through the different elements are calculated using the following rules: Heat exchanger HX2: the maximum required heat flow-rate must be transferred with air temperatures equal to 35 C (supplied air to the building) and 18 C (return air temperature). Water temperatures and mass flow-rate may be deduced from the heat flowrate and heat exchanger efficiency. HP condenser: the water mass flow-rate through the condenser is calculated considering a temperature difference equal to 5 C between inlet and outlet and the heat flow-rate value used for sizing procedure (A -5 C/W35 C). Solar collectors, HX1 and HX3: the fluid mass flowrate is calculated considering 40 l/(h m 2 of solar collectors). Pressure drops are associated to each fluid loop so that energy requirement for pumps and fan (C1, C2, C3, F) may be calculated. Control strategy The solar collectors are considered as the prior heat generation system. The priority is given to domestic hot water production. If the difference between the temperature downstream the solar collectors and the water temperature inside the water tank (at the node located at HX3 outlet) is higher than 5 C, solar collectors are activated and heat is stored in B2. If such a condition is not respected, heat produced by the solar collectors is stored in the water tank for space heating (B1) provided this operation is possible (same criterion as for DHW production). The heat pump does not take part to the storage process. It is activated only in case of heat demand from the building or in case of hot water demand provided that the set temperature is not reached at the inlet of HX2 for space heating (35 C) or at the top of B2 (45 C) for hot water supply. Warm air circulation through HX2 is allowed when inside ambient temperature is lower than 18 C and is stopped when it is higher than 21 C. Domestic hot water tapping program is inspired from French regulations (Figure 3). It depends on the heated area. Set point temperature ( C) Time (h) Figure 3: Tapping program SIMULATION RESULTS All buildings and equipment are simulated using TRNSYS 17 with a time step of 10 minutes. Components models come from two sources: the TRSNSYS standard models library and the TESS library. The dwellings are modelled using TRNSYS s TYPE 56 with three or four distinct thermal zones. The weather-processing model uses standard TRNSYS TYPE 15 with the climate data file from Uccle. First simulation runs are achieved considering only the building. Results are then used to size the different elements of the heating system. Table 3 presents the annual heat demand, the installed thermal power of the heat pump as well as the solar collectors surface area for each dwelling. Figure 4 present the month heat demand for space heating for buildings 1 and

5 N Solar collectors surface area (m ) Heat pump thermal power in design conditions (kw) Annual heat demand (space heating) kwh/(y m 2 ) Table 3: Installed surface area of solar collectors, heat pump thermal power and annual heat demand for space heating Buildings 1, 2 and 3 may be considered as very low energy buildings in terms of heat demand. Buildings 4 and 7 have characteristics close to the minimum EPBD requirements in Belgium. Building 8 is representative of what is commonly built in Belgium in Buildings 5 and 6 are close to building 8 whereas they are located in the South of France. Heat demand kwh/(y m2) Building 1 Building 4 Figure 4: Heat demand (space heating) for two buildings Heating system + building behaviour are then simulated. Table 4 shows the main results on an annual base. Energy data are all given per square meter of heated area. Q SH is the annual heat quantity released to the building for space heating. These values are close to the annual heat demand given in Table 3. Slight discrepancies (up to 10 kwh/(y m 2 )) may be observed due to the offset of the control strategy of the heating system. Q DHW is the annual energy quantity in the domestic hot water that is consumed in one year. Q SC and Q HP are respectively the heat quantities produced by the solar collectors on the one hand and by the heat pump on the other hand. Q loss and Q bu are the annual heat losses in the water tanks and the annual heat produced by a back-up system when set temperatures (inside ambient temperature and DHW) may not be reached. It appears that the heat pump is the supply technology with the highest heating contribution for all cases. The proposed design procedure seems to be satisfactory in terms of comfort as the back-up system contribution remains low. OSC, SCSH and SCDHW are respectively the overall solar coverage ratio, the solar coverage ratio for space heating and the solar coverage ratio for DHW production. Solar contribution for space heating remains low for all cases (from 3% to 9%). The lowest values are for very low energy buildings (1, 2 and 3). Their heating demand is already nearly zero during the mid-season which is less the case for the other buildings for which a solar contribution is possible mainly in April, May, September and October. The solar contribution for DHW production ranges from 52% to 76%. Once again, very low energy buildings are characterized by low solar coverage ratios compared to other ones. This is due to the fact that the sizing of the solar collectors surface area is based on the heat demand for space heating. For low energy buildings, the resulting surface area is low, comparable to what is commonly used in Belgium for solar preparation of DHW, leading to typical values of solar coverage ratio of 50 to 60%. For the other buildings, the solar collectors surface area is oversized and higher coverage ratio may be reached. E aux, E HP and SPF are respectively the annual electricity consumption of pumps and fan, the annual electricity consumption of the heat pump and its seasonal performance factor. It can be concluded that the very low energy buildings can be turned into zero energy buildings (when considering only energy requirements for heating and DHW preparation) as the electricity needs to run the heat pump and auxilaries can be produced by PV panels. This will be practically impossible or quite difficult for the other buildings if only the roof surface is considered for PV panels installation. The design procedure and the control strategy allow for low temperature heat production and high values of heat pump seasonal performance factor (around 3.5 for most cases). The renewable contribution of the heat pump is estimated to 29% of its heat production. Solar contribution and heat pumping lead to a ratio E prim /(Q sh +Q DHW +Q loss ) of about 57% (E prim is the non renewable primary energy consumed for space heating and DHW production)

6 Unit Q sh kwh/(y m 2 ) 36,4 29,9 36,3 130,2 72,0 63,8 94,5 75,9 Q DHW kwh/(y m 2 ) 14,6 15,8 15,9 22,3 15,2 16,7 19,8 21,1 Q SC kwh/(y m 2 ) 9,1 11,3 11,3 31,8 14,2 20,5 28,1 29,3 Q HP kwh/(y m 2 ) 43,9 37,1 43,6 131,2 77,1 66,3 95,6 77,9 Q loss kwh/(y m 2 ) 2,9 3,8 3,7 13,0 4,9 8,1 11,7 12,7 Q bu kwh/(y m 2 ) 0,1 0,8 0,1 1,9 0,8 1,6 1,1 0,9 OSC 17,0% 23,0% 21,0% 19,0% 15,0% 23,0% 23,0% 27,0% SCSH 3,0% 6,0% 4,0% 7,0% 3,0% 8,0% 8,0% 9,0% SCDHW 52,0% 54,0% 55,0% 75,0% 65,0% 72,0% 76,0% 76,0% E aux kwh/(y m 2 ) 0,2 0,2 0,2 0,3 0,2 0,2 0,3 0,3 E HP kwh/(y m 2 ) 11,0 10,7 12,6 39,0 22,0 19,0 27,4 22,3 SPF 4,0 3,5 3,5 3,4 3,5 3,5 3,5 3,5 E prim kwh/(y m 2 ) 27,7 28,9 31,9 102,1 56,9 51,4 71,3 58,0 CONCLUSIONS A heating system composed of a heat pump and solar collectors connected to two water tanks (one for heat storage and one for DHW preparation) was tested by simulation in eight single-family dwellings under Belgian climate conditions. Such systems are well known but still not too much used in Belgium. Problems in the design choices and during operation (control strategy) were identified in real such systems installed in Belgium. These problems generally result from a lack of knowledge due to unaivalable information on best practices. The use of a heat pump for space heating and of solar collectors for DHW production (the heat pump is sometimes used as the back-up system) is a more widespread and well handled solution. Our study aimed at testing an integrated system (both technologies are used both for space heating and for DHW preparation) and at proposing design rules for stakeholders. Whatever the building characteristics the integrated system allows for a drastic reduction (43%) of non renewable primary energy use when compared to an hypothetic system with a 100% yield (heat produced/non renewable primary energy). Nevertheless, the sizing procedure and/or the control strategy leads to quite low solar coverage ratio for space heating so that the benefit of using a completely integrated system instead of the most common solution (no heat storage and no solar contribution for space heating) can not be clearly established. This is particularly true for very low energy buildings. For such buildings the low electricity requirement to run the heat pump makes possible the net zero energy target if PV panels are used. Further developments, namely on the sizing procedure (heat storage, solar collectors) are needed as well as an economic survey. These works are undergoing. Table 4: Energy balance ACKNOWLEDGEMENT This study was conducted as part of a research project financed by the company Electrabel GDF SUEZ. REFERENCES Arrêté du Gouvernement wallon déterminant la méthode de calcul et les exigences, les agréments et les sanctions applicables en matière de performance énergétique et de climat intérieur des bâtiments, Moniteur Belge, juillet Klein, S.A, et al., TRNSYS Reference Manual, Solar Energy Laboratory, University of Wisconsin-Madison, Directive 2010/31/EU on the EU Energy Performance of Buildings (Recast), Official Journal of the European Union, May Torcellini, P., Pless, S., Deru, M., Crawley, D., Zero Energy Buildings: A critical look at the definition, June Pfluger, R., Evaluation statistique des systèmes de génération de chaleur en bâtiment passif, Passivhaus Institut, 2008 ESE (Enquête Socio Economique) 2001, Service public fédéral Economie, PME, Classes moyennes et Energie, DGSIE (Direction générale statistique et information économique)

SIMULATION MODEL IN TRNSYS OF A SOLAR HOUSE FROM BRAŞOV, ROMANIA

SIMULATION MODEL IN TRNSYS OF A SOLAR HOUSE FROM BRAŞOV, ROMANIA SIMULATION MODEL IN TRNSYS OF A SOLAR HOUSE FROM BRAŞOV, ROMANIA C. Şerban 1, E. Eftimie 1 and L. Coste 1 1 Department of Renewable Energy Systems and Recycling Transilvania University of Braşov B-dul

More information

The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort

The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort Ongun Berk Kazanci, Bjarne W. Olesen 1 1 International Center for Indoor Environment and

More information

NUMERICAL STUDY ON THERMAL DEPLETION OF THE GROUND AROUND A GEOTHERMAL HEAT PUMP S PROBE

NUMERICAL STUDY ON THERMAL DEPLETION OF THE GROUND AROUND A GEOTHERMAL HEAT PUMP S PROBE U.P.B. Sci. Bull., Series C, Vol. 75, Iss. 3, 2013 ISSN 2286-3540 NUMERICAL STUDY ON THERMAL DEPLETION OF THE GROUND AROUND A GEOTHERMAL HEAT PUMP S PROBE Constantin IONESCU 1, Clément MONTANGE 2 Long

More information

PERFORMANCE OF SOLAR COLLECTORS UNDER LOW TEMPERATURE CONDITIONS: Measurements and simulations results

PERFORMANCE OF SOLAR COLLECTORS UNDER LOW TEMPERATURE CONDITIONS: Measurements and simulations results PERFORMANCE OF SOLAR COLLECTORS UNDER LOW TEMPERATURE CONDITIONS: Measurements and simulations results Mircea Bunea *, Sara Eicher, Catherine Hildbrand, Jacques Bony, Bengt Perers 2 and Stéphane Citherlet

More information

Energy consumption and thermal comfort in a passive house built in Romania

Energy consumption and thermal comfort in a passive house built in Romania Chapter 3 - High Performance Sustainable Building Solutions Energy consumption and thermal comfort in a passive house built in Romania Cristina Tanasa, Cristian Sabau, Daniel Dan & Valeriu Stoian Polytechnic

More information

Energy Performance of Buildings Directive and nearly-zero Energy Buildings

Energy Performance of Buildings Directive and nearly-zero Energy Buildings Energy Performance of Buildings Directive and nearly-zero Energy Buildings J.J. BLOEM DG JRC http://ec.europa.eu/dgs/jrc Serving society Stimulating innovation Supporting legislation TOWARDS 2030 Framework

More information

SUMMER THERMAL COMFORT IN TYPICAL FRENCH RESIDENTIAL BUILDINGS: IMPACT ASSESSMENT OF BUILDING ENVELOPE INSULATION ENHANCEMENT

SUMMER THERMAL COMFORT IN TYPICAL FRENCH RESIDENTIAL BUILDINGS: IMPACT ASSESSMENT OF BUILDING ENVELOPE INSULATION ENHANCEMENT 13th Conference of International Building Simulation Association, Chambéry, France, August 26-28 SUMMER THERMAL COMFORT IN TYPICAL FRENCH RESIDENTIAL BUILDINGS: IMPACT ASSESSMENT OF BUILDING ENVELOPE INSULATION

More information

A STUDY ON DESIGN OPTIMIZATION OF A NEAR NET-ZERO ENERGY HOUSE

A STUDY ON DESIGN OPTIMIZATION OF A NEAR NET-ZERO ENERGY HOUSE Int. Journal for Housing Science, Vol.37, No.1 pp.23-31, 2013 Published in the United States A STUDY ON DESIGN OPTIMIZATION OF A NEAR NET-ZERO ENERGY HOUSE Narghes Doust, Gabriele Masera and Marco Imperadori

More information

DESIGN AND RECOMMANDATIONS FOR DECENTRALIZED SOLAR DISTRICT HEATING SYSTEMS IN FRANCE

DESIGN AND RECOMMANDATIONS FOR DECENTRALIZED SOLAR DISTRICT HEATING SYSTEMS IN FRANCE T Proceedings of BS213: DESIGN AND RECOMMANDATIONS FOR DECENTRALIZED SOLAR DISTRICT HEATING SYSTEMS IN FRANCE Philippe Papillon 1, Cédric Paulus 1 1 CEA LITEN, 5 avenue du lac Léman, 73377 Le Bourget du

More information

SOLAR XXI: A Portuguese Office Building towards Net Zero-Energy Building

SOLAR XXI: A Portuguese Office Building towards Net Zero-Energy Building SOLAR XXI: A Portuguese Office Building towards Net Zero-Energy Building Helder Gonçalves PhD, Director of the Energy Laboratory, National Energy and Geology Laboratory, Portugal email: helder.goncalves@lneg.pt

More information

Chapter Six{ TC "Chapter Six" \l 1 } System Simulation

Chapter Six{ TC Chapter Six \l 1 } System Simulation Chapter Six{ TC "Chapter Six" \l 1 } System Simulation In the previous chapters models of the components of the cooling cycle and of the power plant were introduced. The TRNSYS model of the power plant

More information

European Energy Policy and Standardization Buildings and Building Components

European Energy Policy and Standardization Buildings and Building Components European Energy Policy and Standardization Buildings and Building Components J.J. BLOEM DG JRC http://ec.europa.eu/dgs/jrc Serving society Stimulating innovation Supporting legislation TOWARDS 2030 framework

More information

NEW GENERATION OF A HIGHLY COMPACT SOLAR HEAT PUMP SYSTEM WITH BOOSTED ENERGETIC EFFICIENCY

NEW GENERATION OF A HIGHLY COMPACT SOLAR HEAT PUMP SYSTEM WITH BOOSTED ENERGETIC EFFICIENCY NEW GENERATION OF A HIGHLY COMPACT SOLAR HEAT PUMP SYSTEM WITH BOOSTED ENERGETIC EFFICIENCY I. Mojic 1 ; M.Y. Haller 1 ; B. Thissen 2 ; F. Hengel 3, A. Heinz 3 1: Institute for Solar Technology SPF, HSR

More information

FLOWRATE DEPENDENT HEAT-PUMP MODEL

FLOWRATE DEPENDENT HEAT-PUMP MODEL Poster P.4.10-1 - FLOWRATE DEPENDENT HEAT-PUMP MODEL Andreas, Genkinger, dipl. Phys., Research Associate, University of Applied Sciences and Arts Northwestern Switzerland, School of Architecture, Civil

More information

The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating

The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating Stephen Harrison Ph.D., P. Eng., Solar Calorimetry, Dept. of Mechanical and Materials Engineering, Queen s University,

More information

1/58 Components of solar systems

1/58 Components of solar systems 1/58 Components of solar systems storage heat exchangers safety and protection devices air vents, check valve control & measurement Thermosiphon circulation system 2/58 circulation induced by buoyancy

More information

Thermal insulation of buildings and cooling demand

Thermal insulation of buildings and cooling demand 411 Thermal insulation of buildings and cooling demand C. Hamans Rockwool International S.A.,The Netherlands ABSTRACT Thermal insulation in the warm climate can reduce the energy demand for cooling in

More information

Reference System, Germany Solar domestic hot water system, single-family house

Reference System, Germany Solar domestic hot water system, single-family house Description: Definition of the reference system for solar domestic hot water (SDHW) preparation in a single-family house, Germany Date: 14.09.207, last revision 12.11.2017 Authors: Download possible at:

More information

EVALUATION OF A HIGH TEMPERATURE SOLAR THERMAL SEASONAL BOREHOLE STORAGE

EVALUATION OF A HIGH TEMPERATURE SOLAR THERMAL SEASONAL BOREHOLE STORAGE EVALUATION OF A HIGH TEMPERATURE SOLAR THERMAL SEASONAL BOREHOLE STORAGE Johan Heier 1, Chris Bales 1, Artem Sotnikov 2 and Ganna Ponomarova 2 1 Solar Energy Research Center (SERC), Dalarna University,

More information

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Available online at  ScienceDirect. Procedia Engineering 121 (2015 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 121 (2015 ) 1413 1419 9th International Symposium on Heating, Ventilation and Air Conditioning (ISHVAC) and the 3rd International

More information

Unit 7 Overview of Solar Thermal Applications

Unit 7 Overview of Solar Thermal Applications ELTR 1223 Survey of Renewable Energy Technology Unit 7 Overview of Solar Thermal Applications REEC 120 Sustainability and Renewable Energy Source: Use Policy This material was developed by Timothy J. Wilhelm,

More information

Net Zero Energy Solar Buildings SHC Position Paper

Net Zero Energy Solar Buildings SHC Position Paper Task 40 (EBC Annex 52) Towards Net Zero Energy Solar Buildings Net Zero Energy Solar Buildings SHC Position Paper June 2015 Table of Contents Aim of Position Paper... 3 Executive Summary... 3 Introduction

More information

Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France

Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France Sylvain Boulet 1, Stéphanie Armand-Decker 2, FCBA Technological Institute I2M-TREFLE laboratory -

More information

Investigations of Intelligent Solar Heating Systems for Single Family House

Investigations of Intelligent Solar Heating Systems for Single Family House Downloaded from orbit.dtu.dk on: May 08, 2018 Investigations of Intelligent Solar Heating Systems for Single Family House Andersen, Elsa; Chen, Ziqian; Fan, Jianhua; Furbo, Simon; Perers, Bengt Published

More information

Swedish development of Energy-efficient buildings

Swedish development of Energy-efficient buildings Melbourne Forum September 2011 Swedish development of Energy-efficient buildings From reduction of energy use to increased use of renewable energy Maria Wall Energy and Building Design Lund University,

More information

Modeling and analyzing solar cooling systems in Polysun

Modeling and analyzing solar cooling systems in Polysun Modeling and analyzing solar cooling systems in Polysun Seyed H. Rezaei (seyed.rezaei@velasolaris.com) 1 Andreas Witzig (andreas.witzig@velasolaris.com) 1 Michael Pfeiffer (michael.pfeiffer@velasolaris.com)

More information

ANNUAL ENERGY PERFORMANCE OF SOLAR THERMAL SYSTEMS IN BRAŞOV, ROMANIA

ANNUAL ENERGY PERFORMANCE OF SOLAR THERMAL SYSTEMS IN BRAŞOV, ROMANIA Bulletin of the Transilvania University of Braşov Series I: Engineering Sciences Vol. 5 (54) No. 2-212 ANNUAL ENERGY PERFORMANCE OF SOLAR THERMAL SYSTEMS IN BRAŞOV, ROMANIA C. ŞERBAN 1 E. EFTIMIE 1 Abstract:

More information

Modelling Solar Thermal Systems

Modelling Solar Thermal Systems Modelling Solar Thermal Systems Michaël Kummert Energy Systems Research Unit Modelling Renewables Workshop SESG, 24 January 2007 Outline Who am I? Solar thermal systems Different tools for different purposes

More information

Energy Audit of two Apartment Buildings in Cagliari using Energy Simulation

Energy Audit of two Apartment Buildings in Cagliari using Energy Simulation Energy Audit of two Apartment Buildings in Cagliari using Energy Simulation Graduation Thesis by Carla Vargiu and Luisa Zedda, Master in Green Building and Energy Efficiency This thesis focuses on the

More information

Overview of national applications of the Nearly Zero- Energy Building (NZEB) definition

Overview of national applications of the Nearly Zero- Energy Building (NZEB) definition Hans Erhorn Heike Erhorn-Kluttig Overview of national applications of the Nearly Zero- Energy Building (NZEB) definition Detailed report April 2015 www.epbd-ca.eu Overv iew of national applications of

More information

SIMULATION AND MODEL CALIBRATION OF A LARGE-SCALE SOLAR SEASONAL STORAGE SYSTEM

SIMULATION AND MODEL CALIBRATION OF A LARGE-SCALE SOLAR SEASONAL STORAGE SYSTEM July August 1, SIMULATION AND MODEL CALIBRATION OF A LARGE-SCALE SOLAR SEASONAL STORAGE SYSTEM Timothy P. McDowell and Jeff W. Thornton Thermal Energy System Specialists, LLC, Madison, WI ABSTRACT The

More information

MULTI-SOURCE HEAT PUMP COUPLED WITH A PHOTOVOLTAIC THERMAL (PVT) HYBRID SOLAR COLLECTORS TECHNOLOGY: A CASE STUDY IN RESIDENTIAL APPLICATION

MULTI-SOURCE HEAT PUMP COUPLED WITH A PHOTOVOLTAIC THERMAL (PVT) HYBRID SOLAR COLLECTORS TECHNOLOGY: A CASE STUDY IN RESIDENTIAL APPLICATION G. Emmi, et al., Int. J. of Energy Prod. & Mgmt., Vol. 1, No. 4 (2016) 382-392 MULTI-SOURCE HEAT PUMP COUPLED WITH A PHOTOVOLTAIC THERMAL (PVT) HYBRID SOLAR COLLECTORS TECHNOLOGY: A CASE STUDY IN RESIDENTIAL

More information

Single family house in Herselt BE

Single family house in Herselt BE Single family house in Herselt BE PROJECT SUMMARY Retrofit of a century old countryhouse into a low energy house. SPECIAL FEATURES House meets Universal Design criteria. ARCHITECT S. Corten OWNER Verbruggen-Jennes

More information

STATUS IN DECEMBER Current status of Implementation of the EPBD I. ENERGY PERFORMANCE REQUIREMENTS

STATUS IN DECEMBER Current status of Implementation of the EPBD I. ENERGY PERFORMANCE REQUIREMENTS Implementation of the EPBD in Portugal STATUS IN DECEMBER 2014 1. Introduction The national implementation of the Energy Performance of Buildings Directive (Directive 2010/31/EU EPBD) started in 2007,

More information

Design of Experiment for Solar Water Heater Performance Analysis

Design of Experiment for Solar Water Heater Performance Analysis Design of Experiment for Solar Water Heater Performance Analysis Mr. M.V. Kulkarni 1, Dr. D. S Deshmukh 2, 1 Asst. Professor, Department of Mechanical Engineering, SSBT'S COLLEGE OF ENGINEERING AND TECHNOLOGY,

More information

A NET ZERO ENERGY BUILDING IN ITALY: DESIGN STUDIES TO REACH THE NET ZERO ENERGY TARGET

A NET ZERO ENERGY BUILDING IN ITALY: DESIGN STUDIES TO REACH THE NET ZERO ENERGY TARGET Proceedings of Building Simulation 2011: A NET ZERO ENERGY BUILDING IN ITALY: DESIGN STUDIES TO REACH THE NET ZERO ENERGY TARGET Maurizio Cellura1, Lucia Campanella1, Giuseppina Ciulla1, Francesco Guarino1

More information

Passive Houses Worlswide: International Developments

Passive Houses Worlswide: International Developments Passive Houses Worlswide: International Developments Henk Kaan, ECN Energy Research Centre of the Netherlands, P.O. Box 1, 1755 ZG Petten, The Netherlands, Isolda Strom, DHV Building and Industry, P.O.

More information

Authors. Towards 2020 OVERVIEW AND OUTCOMES. 1. General information. 2. Objectives

Authors. Towards 2020 OVERVIEW AND OUTCOMES. 1. General information. 2. Objectives Towards 2020 OVERVIEW AND OUTCOMES 1. General information To support EU Member States (MS) in the task of implementing Directive 2002/91/EC on the Energy Performance of Buildings (EPBD), the Concerted

More information

Promoting nzeb through Cost Optimality. Stefano Paolo Corgnati TEBE Research Group, Department of Energy, Politecnico di Torino REHVA President

Promoting nzeb through Cost Optimality. Stefano Paolo Corgnati TEBE Research Group, Department of Energy, Politecnico di Torino REHVA President Promoting nzeb through Cost Optimality Stefano Paolo Corgnati TEBE Research Group, Department of Energy, Politecnico di Torino REHVA President Why do we talk about nzeb? 1997:Kyoto Protocol 2008: EU Climate

More information

Solar and Internal Gains in Low-Energy and Passive Houses

Solar and Internal Gains in Low-Energy and Passive Houses Solar and Internal Gains in Low-Energy and Passive ouses GEOFFREY VAN MOESEKE 1 1 Architecture et Climat, Université catholique de Louvain, Louvain-la-Neuve, Belgium ABSTRACT: The increasing energy efficiency

More information

Available online at ScienceDirect. Energy Procedia 91 (2016 ) 20 26

Available online at  ScienceDirect. Energy Procedia 91 (2016 ) 20 26 Available online at www.sciencedirect.com ScienceDirect Energy Procedia 91 (2016 ) 20 26 SHC 2015, International Conference on Solar Heating and Cooling for Buildings and Industry Evaluating the thermal

More information

Evaluation of a versatile energy auditing tool

Evaluation of a versatile energy auditing tool Evaluation of a versatile energy auditing tool Georgios Dermentzis 1, Marcus Gustafsson 2,3,*, Fabian Ochs 1, Sture Holmberg 3, Wolfgang Feist 1,4, Toni Calabrese 1, Philipp Oberrauch 1 1 University of

More information

ScienceDirect. Appraising the effect of the primary systems on the cost optimal design of nzeb: A case study in two different climates

ScienceDirect. Appraising the effect of the primary systems on the cost optimal design of nzeb: A case study in two different climates Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 2028 2033 6th International Building Physics Conference, IBPC 2015 Appraising the effect of the primary systems on the

More information

Bifluid Geothermal System New Generation

Bifluid Geothermal System New Generation Bifluid Geothermal System New Generation The Geothermal Energy - from the Greek roots geo, meaning earth, and thermos, meaning heat - ie the thermal energy stored in the underground of our planet, and

More information

THE INFLUENCE OF ENVELOPING ON ENERGETIC AND ECOLOGICAL EFFICIENCY OF PASSIVE HOUSES

THE INFLUENCE OF ENVELOPING ON ENERGETIC AND ECOLOGICAL EFFICIENCY OF PASSIVE HOUSES INTERNATIONAL SCIENTIFIC CONFERENCE CIBV 14 7-8 November 14, Braşov THE INFLUENCE OF ENVELOPING ON ENERGETIC AND ECOLOGICAL EFFICIENCY OF PASSIVE HOUSES R. MOLDOVAN 1 G. DRAGOȘ 1 Abstract: Within the European

More information

Simulation of a solar collector array consisting of two types of solar collectors, with and without convection barrier

Simulation of a solar collector array consisting of two types of solar collectors, with and without convection barrier Available online at www.sciencedirect.com ScienceDirect Energy Procedia 00 (2015) 000 000 www.elsevier.com/locate/procedia International Conference on Solar Heating and Cooling for Buildings and Industry,

More information

WP Future opportunities for geothermal and energy system integrated

WP Future opportunities for geothermal and energy system integrated WP 2018-2020 Future opportunities for geothermal and energy system integrated Horizon 2020 WP 2018-2020 Horizon 2020 WP 2018-2020 Many opportunities for geothermal h&c projects Horizon 2020 WP 2018-2020

More information

Marjana Šijanec Zavrl, Erik Potočar,

Marjana Šijanec Zavrl, Erik Potočar, Practical Implementation of the Cost- Optimal Regulation for establishing nation Minimum Requirements in Slovenia Marjana Šijanec Zavrl, Marta Skubic, Andraž Rakušček, Henrik Gjerkeš, Building and Civil

More information

BUILDINGS & OFFICE SPACES INDUSTRIAL SOLUTIONS. Combined production of Heat and Power. Waste Heat Recovery Bottoming Cycle

BUILDINGS & OFFICE SPACES INDUSTRIAL SOLUTIONS. Combined production of Heat and Power. Waste Heat Recovery Bottoming Cycle BUILDINGS & OFFICE SPACES Combined production of Heat and Power INDUSTRIAL SOLUTIONS Waste Heat Recovery Bottoming Cycle The ENEFCOGEN GREEN line of products is designed for applications of Combined Heat

More information

A COMPARISON OF THE UK STANDARD ASSESSMENT PROCEDURE (SAP) AND DETAILED SIMULATION OF BUILDING-INTEGRATED RENEWABLE ENERGY SYSTEMS

A COMPARISON OF THE UK STANDARD ASSESSMENT PROCEDURE (SAP) AND DETAILED SIMULATION OF BUILDING-INTEGRATED RENEWABLE ENERGY SYSTEMS Eleventh International IBPSA Conference Glasgow, Scotland July 27-30, 2009 A COMPARISON OF THE UK STANDARD ASSESSMENT PROCEDURE () AND DETAILED SIMULATION OF BUILDING-INTEGRATED RENEWABLE ENERGY SYSTEMS

More information

SOLAR ENGINEERING OF THERMAL PROCESSES

SOLAR ENGINEERING OF THERMAL PROCESSES SOLAR ENGINEERING OF THERMAL PROCESSES Second Edition JOHN A. DUFFIE Emeritus Professor of Chemical Engineering WILLIAM A. BECKMAN Professor of Mechanical Engineering Solar Energy Laboratory University

More information

Experimental analysis of heat-pump integrated with solar energy

Experimental analysis of heat-pump integrated with solar energy Experimental analysis of heat-pump integrated with solar energy André Ricardo Quinteros Panesi 1 Abstract: The objective of the present work is to analyze the performance of an equipment used in water

More information

NREL Commercial Buildings Research

NREL Commercial Buildings Research NREL Commercial Buildings Research Adam Hirsch NREL Commercial Buildings Research Group Boulder Green Building Guild Conference Boulder, CO April, 2010 NREL is a national laboratory of the U.S. Department

More information

Renewable Energy for Indoor Agriculture

Renewable Energy for Indoor Agriculture Renewable Energy for Indoor Agriculture Lucas Semple 1, Rupp Carriveau 2,3,4, David S.K. Ting 2,3,4 1 Engineering Manager, UnderSun Acres 2 Environmental Energy Institute 3 Turbulence and Energy Lab 4

More information

IEA HPT Annex 40 Heat pump concepts for nearly Zero Energy Buildings Introduction

IEA HPT Annex 40 Heat pump concepts for nearly Zero Energy Buildings Introduction IEA Heat Pumping Technologies Implementing Agreement IEA HPT Annex 40 Heat pump concepts for nearly Zero Energy Buildings Introduction Carsten Wemhoener HSR University of Applied Sciences Rapperswil IEA

More information

ZEBRA2020: NEARLY ZERO-ENERGY BUILDING STRATEGY 2020

ZEBRA2020: NEARLY ZERO-ENERGY BUILDING STRATEGY 2020 ZEBRA2020: NEARLY ZERO-ENERGY BUILDING STRATEGY 2020 Deliverable 5.1: Nearly Zero-Energy Building (nzeb) technology solutions, cost assessment and performance Technical References Project Acronym Zebra2020

More information

Ventilation in residential buildings: A comparison of different calculation methodologies in the context of the EPBD

Ventilation in residential buildings: A comparison of different calculation methodologies in the context of the EPBD S. Wössner et al, D: Ventilation in residential buildings: A comparison of different calculation... 1 Ventilation in residential buildings: A comparison of different calculation methodologies in the context

More information

Project Description. Projected build start date 01 Mar 2010 Projected date of occupation 31 May Aberdare, Rhondda Cynon Taff, Wales

Project Description. Projected build start date 01 Mar 2010 Projected date of occupation 31 May Aberdare, Rhondda Cynon Taff, Wales http://lowenergybuildings.org.uk Project name Self Heating Social Housing- the zero carbon retrofit Project summary The target for this project is to create the first UK PassivHaus retrofit using low/zero

More information

The Renewable Heat Incentive

The Renewable Heat Incentive The Renewable Heat Incentive Heating RHI Expected Outcome Non-Domestic Ground Source Heat Pumps Air Source and Ground Source Heat Pumps Increased tariffs for Air and Ground Source RHI First Announcement

More information

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Available online at  ScienceDirect. Energy Procedia 78 (2015 ) Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (215 ) 1859 1864 6th International Building Physics Conference, IBPC 215 An evaluation of distributed solar thermal "net metering"

More information

Neil Eccles June SBED TSC Technology

Neil Eccles June SBED TSC Technology Neil Eccles June 2013 SBED TSC Technology The drivers Buildings account for 40% of energy use and CO 2 emissions. In Northern Europe one half of the above is used for space heating/cooling. Reduction in

More information

Heat pump system control: the potential improvement based on perfect prediction of weather forecast and user occupancy

Heat pump system control: the potential improvement based on perfect prediction of weather forecast and user occupancy Heat pump system control: the potential improvement based on perfect prediction of weather forecast and user occupancy D. Rolando, H. Madani, G. Braida, R. Tomasetig, Z. Mohammadi Project Smart control

More information

Building Regulations Part L 2013 For England. Ant Wilson Director/AECOM Fellow Building Engineering AECOM

Building Regulations Part L 2013 For England. Ant Wilson Director/AECOM Fellow Building Engineering AECOM Building Regulations Part L 2013 For England Ant Wilson Director/AECOM Fellow Building Engineering AECOM 1 st May 2014 2 Building Byelaws Thermal Insulation 3 Bringing in Part L 2002 Working With DETR

More information

An innovative HCP/T collector and its potential SHC applications

An innovative HCP/T collector and its potential SHC applications NEW GENERATION OF SOLAR COOLING AND HEATING SYSTEMS DRIVEN BY PHOTOVOLTAIC OR SOLAR THERMAL ENERGY An innovative HCP/T collector and its potential SHC applications Filippo Paredes Idea Srl fparedes@ideasrl.it

More information

Reference System, Austria Solar domestic hot water system for single- family house

Reference System, Austria Solar domestic hot water system for single- family house Description: Date: 30.11.2016 Authors: Download possible at: Definition of the reference solar domestic hot water (SDHW) system for single- family house (SFH), Austria Thomas Ramschak, François Veynandt

More information

Side by side tests of two SDHW systems with solar collectors with and without antireflection treatment

Side by side tests of two SDHW systems with solar collectors with and without antireflection treatment Downloaded from orbit.dtu.dk on: Mar 31, 2018 Side by side tests of two SDHW systems with solar collectors with and without antireflection treatment Kong, Weiqiang; Han, Jiangong; Perers, Bengt; Furbo,

More information

The challenges, dynamics and activities in the building sector and its energy demand in France

The challenges, dynamics and activities in the building sector and its energy demand in France The challenges, dynamics and activities in the building sector and its energy demand in France D2.1 of WP2 from Entranze Project Written by: Bruno Lapillonne, Carine Sebi and Nicolas Mairet Enerdata, with

More information

Zero Energy Building (ZEB) definitions A literature review. 1. Introduction. Anna Joanna Marszal 1 and Per Heiselberg 1

Zero Energy Building (ZEB) definitions A literature review. 1. Introduction. Anna Joanna Marszal 1 and Per Heiselberg 1 Zero Energy Building (ZEB) definitions A literature review Anna Joanna Marszal 1 and Per Heiselberg 1 1 Department of Civil Engineering Aalborg University Sohngaardsholmsvej 57 DK-9000 Aalborg, Denmark

More information

Reference System, Austria Solar domestic hot water preparation for multi- family house

Reference System, Austria Solar domestic hot water preparation for multi- family house Description: Date: 30.11.2016 Authors: Download possible at: Definition of the reference solar domestic hot water (SDHW) system for multifamily house (MFH), Austria Thomas Ramschak, François Veynandt http://task54.iea-

More information

LOW-ENERGY HOUSING ESTATE SUNDAYS

LOW-ENERGY HOUSING ESTATE SUNDAYS LOW-ENERGY HOUSING ESTATE SUNDAYS Werner Weiß Christian Fink Alexander Thür AEE - Arbeitsgemeinschaft ERNEUERBARE ENERGIE Feldgasse 19 A-8 Gleisdorf AUSTRIA Tel.: +43-311 - 5886 Fax.: +43-311 5886-18

More information

Nikolaos Taousanidis 1* and Elisavet Amanatidou 2

Nikolaos Taousanidis 1* and Elisavet Amanatidou 2 Nikolaos Taousanidis 1* and Elisavet Amanatidou 2 1 Department of Mechanical Engineering and Industrial Design, Technological Education Institution of Western Macedonia, Kozani 50100, Greece, E-mail address:

More information

Design guidelines for direct ground cooling systems in different climates

Design guidelines for direct ground cooling systems in different climates Design guidelines for direct ground cooling systems in different climates Adriana Angelotti and Giulio Solaini Dipartimento BEST, Politecnico di Milano, Milano, Italy ABSTRACT: Direct ground cooling systems

More information

IEA HPP Annex 40 International collaboration Outline and national contributions

IEA HPP Annex 40 International collaboration Outline and national contributions IEA HPP Annex 40 Heat pump concepts for Nearly Zero Energy Buildings (nzeb) IEA HPP Annex 40 International collaboration Outline and national contributions Carsten Wemhoener, University of Applied Sciences

More information

SolarCoolingOpt Austrian R&D project

SolarCoolingOpt Austrian R&D project SolarCoolingOpt Austrian R&D project 2010-2013 Bettina Nocke AEE Institut für Nachhaltige Technologien (AEE INTEC) A-8200 Gleisdorf, Feldgasse 19 AUSTRIA Funding authority and partners Funding Authority:

More information

Reference System, Austria Solar combisystem system, single-family house

Reference System, Austria Solar combisystem system, single-family house Description: Definition of the reference solar system for domestic hot water preparation and space heating (combi) for single family house (SFH), Austria Date: 30.11.2016, revised 07.11.2017 Authors: Download

More information

Energy savings certificates in France Selection of calculation sheets. IEA-DSM Task XXI: Standardisation of Energy Savings Calculation

Energy savings certificates in France Selection of calculation sheets. IEA-DSM Task XXI: Standardisation of Energy Savings Calculation Energy savings certificates in France Selection of calculation sheets IEA-DSM Task XXI: Standardisation of Energy Savings Calculation March 2010 Household sector Insulation building envelope Internal wall

More information

Solar Home Design and Thermal Mass

Solar Home Design and Thermal Mass Solar Home Design and Thermal Mass Solar Home Design And Simulation of Thermal Mass Stefan Fortuin fortland@gmail.com Papers Renewable Energy System Design Renenwable En Conversion Devices Energy Policy

More information

Passive house optimization for Southern Italy based on the New Passivhaus Standard

Passive house optimization for Southern Italy based on the New Passivhaus Standard Passive house optimization for Southern Italy based on the New Passivhaus Standard Paolo Zangheri end-use Effi ciency Research Group, Dipartimento di Energia Politecnico di Milano, Italy paolo.zangheri@polimi.it

More information

Influence Of Building Zoning On Annual Energy Demand

Influence Of Building Zoning On Annual Energy Demand Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Influence Of Building Zoning On Annual Energy Demand Lisa Rivalin Mines ParisTech,

More information

EVALUATION OF STANDARD SOLAR COMBI PLUS SYSTEMS FOR SMALL SCALE APPLICATIONS

EVALUATION OF STANDARD SOLAR COMBI PLUS SYSTEMS FOR SMALL SCALE APPLICATIONS EVALUATION OF STANDARD SOLAR COMBI PLUS SYSTEMS FOR SMALL SCALE APPLICATIONS R. Fedrizzi 1, G. Franchini 2, D. Mugnier 3, P. N. Melograno 1, M. Theofilidi 4, A. Thuer 5, B. Nienborg 6, L. Koch 6, R. Fernandez

More information

Barriers and opportunities for achieving compliance and enforcement: application to transmission aspects Peter Wouters

Barriers and opportunities for achieving compliance and enforcement: application to transmission aspects Peter Wouters Barriers and opportunities for achieving compliance and enforcement: application to transmission aspects Peter Wouters INIVE EEIG Robust Details Update after 900,000 homes Not able t Not possible to have

More information

Earth, Wind & Fire Natural Airconditioning [1] Research objectives and Methods

Earth, Wind & Fire Natural Airconditioning [1] Research objectives and Methods Earth, Wind & Fire Natural Airconditioning [1] Research objectives and Methods Ben Bronsema Department of Architectural Engineering, Faculty of Architecture, Delft University of Technology, The Netherlands

More information

INFO Sheet A06. Reference System, Austria Solar Domestic Hot Water system, multi-family house. Introduction. Hydraulic Scheme of the System

INFO Sheet A06. Reference System, Austria Solar Domestic Hot Water system, multi-family house. Introduction. Hydraulic Scheme of the System Description: Definition of the reference solar domestic hot water (SDHW) system for multifamily house (MFH), Austria Date: 30.11.2016, last revision: 12.11.2017 Authors: Download possible at: Thomas Ramschak,

More information

THE MODELLING OF PHOTOVOLTAIC, SOLAR THERMAL, AND PHOTOVOLTAIC/THERMAL DOMESTIC HOT WATER SYSTEMS

THE MODELLING OF PHOTOVOLTAIC, SOLAR THERMAL, AND PHOTOVOLTAIC/THERMAL DOMESTIC HOT WATER SYSTEMS THE MODELLING OF PHOTOVOLTAIC, SOLAR THERMAL, AND PHOTOVOLTAIC/THERMAL DOMESTIC HOT WATER SYSTEMS By Jonathan Berger A thesis submitted to the Department of Mechanical and Materials Engineering in conformity

More information

SIMULATION OF SOLAR INTENSITY IN PERFORMANCE OF FLAT PLATE COLLECTOR

SIMULATION OF SOLAR INTENSITY IN PERFORMANCE OF FLAT PLATE COLLECTOR SIMULATION OF SOLAR INTENSITY IN PERFORMANCE OF FLAT PLATE COLLECTOR A.Ponshanmugakumar 1, A. Aldrich Vincent 2 Abstract Solar collectors behave differently at different radiations and temperatures. The

More information

Life Cycle Assessment of a Positive Energy House in France. THIERS Stéphane, PEUPORTIER Bruno

Life Cycle Assessment of a Positive Energy House in France. THIERS Stéphane, PEUPORTIER Bruno Life Cycle Assessment of a Positive Energy House in France THIERS Stéphane, PEUPORTIER Bruno LIFE CYCLE ASSESSMENT OF A POSITIVE ENERGY HOUSE IN FRANCE S. THIERS 1 ; B. PEUPORTIER 1 1: Centre for Energy

More information

nzeb Germany - Strategy to improve energy efficiency in the German building sector and the leading role of public buildings Dr.-Ing.

nzeb Germany - Strategy to improve energy efficiency in the German building sector and the leading role of public buildings Dr.-Ing. BBR Bonn 2011 nzeb Germany - Strategy to improve energy efficiency in the German building sector and the leading role of public buildings Dr.-Ing. Olaf Böttcher - Commissioner for Energy in Federal Buildings

More information

2000 Antwerp, terraced house

2000 Antwerp, terraced house 2000 Antwerp, terraced house 1. INTRODUCTION PROJECT SUMMARY - First phase energy renovation: 1999 - Second phase energy renovation: 2007 SPECIAL FEATURES - Two phased energy renovation - The owners stayed

More information

How to Design Zero Emission Buildings

How to Design Zero Emission Buildings Federico Butera, Politecnico di Milano Energy end uses Europe 2004 (Source: Eurostat Yearbook 2006-2007) EU Targets: Reduction of greenhouse gas emissions by 20% and ensure 20% of renewable energy sources

More information

EXPERIMENTATION AND MODELLING OF A SMALL-SCALE ADSORPTION COOLING SYSTEM IN TEMPERATE CLIMATE. July 22, 2013

EXPERIMENTATION AND MODELLING OF A SMALL-SCALE ADSORPTION COOLING SYSTEM IN TEMPERATE CLIMATE. July 22, 2013 EXPERIMENTATION AND MODELLING OF A SMALL-SCALE ADSORPTION COOLING SYSTEM IN TEMPERATE CLIMATE Sébastien Thomas 1, Samuel Hennaut 1, Stefan Maas 2 and Philippe André 1 1 University of Liège, Arlon, Belgium

More information

Passive Houses in South West Europe

Passive Houses in South West Europe Dr. Wolfgang Feist Passivhaus Institut Rheinstraße 44/46 D-64283 Darmstadt www.passiv.de Passive Houses in South West Europe A quantitative investigation of some passive and active space conditioning techniques

More information

NZEB: The new challenge of HVAC Manufacturers. ASTRO Tower (Archi Urbain)

NZEB: The new challenge of HVAC Manufacturers. ASTRO Tower (Archi Urbain) NZEB: The new challenge of HVAC Manufacturers ASTRO Tower (Archi Urbain) Who are we? 35 production sites units compressors refrigerants chillers Who are we? Daughter company (100%) of Daikin Europe Specialised

More information

CombiSol project. Solar Combisystems Promotion and Standardisation

CombiSol project. Solar Combisystems Promotion and Standardisation CombiSol project Solar Combisystems Promotion and Standardisation D3.1 : Comparison of test methods Draft December 21rd 2010 B. Mette 1), J. Ullmann 1), H. Drück 1) M. Albaric 2), A. Leconte 2), Philippe

More information

Effect of Distance between Double Glazing on the Performance of a Solar Thermal Collector Control

Effect of Distance between Double Glazing on the Performance of a Solar Thermal Collector Control Journal of Mechanics Engineering and Automation 5 (215) 161-166 doi: 117265/2159-5275/21534 D DAVID PUBLISHING Effect of Distance between Double Glazing on the Performance of a Solar Thermal Collector

More information

Solar Flat Plate Thermal Collector

Solar Flat Plate Thermal Collector Solar Flat Plate Thermal Collector 1 OBJECTIVE: Performance Study of Solar Flat Plate Thermal Collector Operation with Variation in Mass Flow Rate and Level of Radiation INTRODUCTION: Solar water heater

More information

EVASOLK. Evaluation of Solar Cooling in Comparison to Reference Technologies

EVASOLK. Evaluation of Solar Cooling in Comparison to Reference Technologies EVASOLK Evaluation of Solar Cooling in Comparison to Reference Technologies Björn Nienborg Edo Wiemken Anna Raquel Petry Elias Fraunhofer Institute for Solar Energy Systems ISE Partners: ILK Dresden, ZAE

More information

Energy Efficient Buildings in Germany An Introduction

Energy Efficient Buildings in Germany An Introduction Energy Efficient Buildings in Germany An Introduction Contents Introduction Statutory provisions and targets From research and demonstration projects to marketable buildings Designing of energy efficient

More information

Retrofit of an historical building toward NZEB

Retrofit of an historical building toward NZEB Available online at www.sciencedirect.com ScienceDirect Energy Procedia 00 (2015) 000 000 www.elsevier.com/locate/procedia 6th International Building Physics Conference, IBPC 2015 Retrofit of an historical

More information

DESIGN AND USE OF RADIANT BARRIERS AS THERMAL INSULATION FOR HIGH INERTIA HOUSES IN TROPICAL CONDITIONS A CASE STUDY

DESIGN AND USE OF RADIANT BARRIERS AS THERMAL INSULATION FOR HIGH INERTIA HOUSES IN TROPICAL CONDITIONS A CASE STUDY HEFAT2007 5 th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number: MF2 DESIGN AND USE OF RADIANT BARRIERS AS THERMAL INSULATION FOR HIGH INERTIA

More information

Research on Ground Source Heat Pump Design

Research on Ground Source Heat Pump Design Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Research on Ground Source Heat Pump Design Amanda Jo Pertzborn University

More information