Attaining Thermal Comfort in. Buildings with Predominantly. Glazed Facades. presented to: ANSYS Boston Regional Conference
|
|
- Marion Cunningham
- 6 years ago
- Views:
Transcription
1 Attaining Thermal Comfort in Buildings with Predominantly Glazed Facades presented to: ANSYS Boston Regional Conference September 14, 2011
2 Case Study Background High floor to ceiling windows Large skylight area Automatic Shading Devices External Shades Chilled Beam HVAC design The space evaluated is the most dangerous area for thermal discomfort
3 Designing for Comfort vs. Energy Reduction Why is this good practice? Allows the space to keep an active chilled beam HVAC design rather than switching to a Variable Air Volume system Reacts to peak cooling issues with low static pressure fan coil units rather than a medium pressure VAV system So why increase energy for comfort? Ignoring comfort only increases energy in operation Operators will adjust the system until occupants are satisfied These adjustments are a big reason for buildings not living up to their modeled performance By acknowledging thermal comfort and providing an approach that is operationally realistic, the design building can achieve the modeled energy target
4 Chilled Beam Design Unit use induction from primary air supply to create flow Allows for less primary supply air while maintaining lower static pressure than a standard VAV system
5 Chilled Beam Approximation and Boundary Conditions Actual flow leaving the chilled beam is not directly measured 2D simulation used to approximate chilled beam slot leaving velocity Chilled beam slot width was varied to match value from Reference point VH1 from vendor s calculator
6 Physical Conditions Rng k-e turbulence model Ideal incompressible gas Radiation DO August 10 th, 10 AM (Fair Weather Conditions) Peak Solar Time August 10 th 10 AM (determined from zone peak in energy model) Design outdoor temperature 90 F Direct Normal Solar Irradiation 853 W/m2 Solar Flux East Wall 71 Btu/hr-sf South Wall 10 Btu/hr-sf Perimeter Skylight 100 Btu/hr-sf Core Skylight 95 Btu/hr-sf Only ~10 Btu/hr-sf on the floor This results in a relatively cool floor but hot walls and ceiling 54.7 kw of Solar load into the space
7 Boundary Conditions Core Skylight Triple Glazed ( U-value of 0.21 Btu/hr-sf ) 5.22% trans, 53.25% reflect, 41.53% abs Perimeter Glass Wall Triple Glazed ( U-value of 0.19 Btu/hr-sf ) 23 % trans, 32% reflect, 45% abs Automatic Shades ( activated by glare and light levels ) 3% trans, 72% reflect, 25 % abs Adjusted Perimeter Glass Wall to include shades Transmissivity = 23 % * 3% = 0.69% Reflectivity = 23% % + 32 % = 54.31% Absorptivity = % % = 45% 8 Occupants (450 Btu/person) 8 Computers (400 W each, recirculation inlets/outlets)
8 Computational Summary Cut Cell Mesh due to the orthogonal nature of the space 2.8 million elements Minimum Orthogonal quality 0.23 (0.975 Avg,.0527 std) Simulation progression Initialized and iterated in Steady State Continued until oscillation due to unsteady nature of thermal plumes in the space Continued in Transient for at least 1 air change and 1% energy and mass convergence
9 Chilled Beam Only Breathing Plane Temperature
10 Chilled Beam Only Breathing Plane Velocity
11 Chilled Beam Only Airflow
12 Chilled Beam Only Airflow
13 Chilled Beam Only Comfort Analysis Temperature is at a reasonable level, but is it really comfortable? Refer to ASHRAE (Thermal Comfort) to check Use Predicted Mean Vote Calculation to analyze comfort Inputs are Air Temp, Mean Radiant Temp, Relative Humidity, Air Velocity, Clothing Level, Activity Level, and External Work Output is a number between 2 and 2 to describe how people experience the environment
14 The Problem We can extract the Peak values from the CFD simulation and energy model to analyze the comfort in the space Design Level F Air Temperature 76 F Radiant Temp 95.0 % Rel Hum 50 ft/min Air Velocity 40 Clo Clothing Level 0.97 Met Activity 1 Met External Work 0 Atm Pressure 0 PMV 1.38 PPD We find that the space is actually uncomfortable due to the high radiant temperature in the space
15 Fan Assisted CB Breathing Plane Temperature
16 Fan Assisted CB Breathing Plane Velocity
17 Fan Assisted CB Airflow
18 Fan Assisted CB Airflow
19 The Design Results Extracting the peak values again, we can see comfort is vastly improved Design Level F Air Temperature 69 F Radiant Temp 95.0 % Rel Hum 50 ft/min Air Velocity 60 Clo Clothing Level 0.97 Met Activity 1 Met External Work 0 Atm Pressure 0 PMV 0.40 PPD 8.34 The space is now comfortable at peak times
20 Operation What about part load? Theoretical models are great at sizing systems, but how can they be controlled in the real world? Using EnergyPlus to analyze the cooling season we can see how the space will react With some custom code that controls the building s BMS system, GenOpt (LBNL) can optimize the operative temperature (weighted average between mean air and mean radiant temperature) to find the ratio that results in the most comfortable cooling season Recalling the PMV calculation, some inputs are easy to monitor (Air temp, Relative Humidity), some can be adjusted by the operator (Clothing level, Activity level, work level), and some will require further analysis to control (Mean radiant temperature, velocity) Using this data, we can plot the glazed façade s temperature against the mean radiant temperature In design, thermostats can measure the temperature of the glazing and report back the data to the BMS system
21 GenOpt Output
22 Operation Approximating MRT and airflow The CFD simulation results can allow us to set a simple function that will return the air velocity at the breathing plane based on the part load of the fan coil motors (can be adjusted during balancing) 40 ft/min 60 ft/min Range The mean radiant temperature will require more analysis due to the fact that it is more difficult to measure Client will not install MRT sensor, now what? Using this data, we can plot the glazed façade s temperature against the mean radiant temperature In operation, thermostats can measure the temperature of the glazed wall and report back the data to the BMS system
23 South Zone Controls South Zone MRT Graph Mean Radiant Temp y = x R 2 = South Wall Temperature
24 East Zone Controls East Zone MRT Graph Mean Radiant Temp y = x R 2 = Skylight Temperature
25 The Predicted Operational Results What do we Gain? The seasonal PMV with the modified control system is far superior to the standard setpoint control Predicted Mean Vote Over Cooling Season (South) Base Avg PMV Base Min PMV Base Max PMV Design Avg PMV Design Min PMV Design Max PMV PMV Hour
26 The Predicted Operational Results What do we Gain? The seasonal PMV with the modified control system is far superior to the standard setpoint control 1.5 Predicted Mean Vote Over Cooling Season (East) Base Avg PMV Base Min PMV Base Max PMV Design Avg PMV Design Min PMV Design Max PMV 1 PMV Hour
27 Summary Active chilled beams save energy when compared to a traditional VAV system Special controls are required for high load spaces By analyzing comfort criteria in design phase, we can establish an energy efficient response to the environment without having the operator make costly adjustments The space now not only benefits from an energy efficient design but also has a smart control system that reacts to comfort rather than simply dry bulb temperature This use of ANSYS FLUENT and energy modeling software is one method to ensure a zone will be well designed and able to maintain an appropriate comfort level for the occupants
BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY. Dr Mirek Piechowski 1, Adrian Rowe 1
BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY Dr Mirek Piechowski 1, Adrian Rowe 1 Meinhardt Building Science Group, Meinhardt Australia 1 Level 12, 501
More informationOptimizing Indoor Environments for Occupant Satisfaction. Presented by: Kelli Goldstone April 2016
Optimizing Indoor Environments for Occupant Satisfaction Presented by: Kelli Goldstone April 2016 Outline Function of HVAC Thermal Comfort Air Distribution Radiant Heating / Cooling Case Study Function
More informationFEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF
FEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF Oliver Baumann 1, and Claudius Reiser 1/2 1 Ebert & Baumann Consulting Engineers, Washington, D.C. 2 Ebert-Ingenieure GmbH &Co. KG, Munich,
More information125BEPM - Building energy performance modeling. Lecture handouts
125BEPM - Building energy performance modeling Lecture handouts 2 - Introduction to building energy performance modeling and simulation prof. Karel Kabele - Page 1/13 - CONTENT 1 INTRODUCTION TO BUILDING
More informationDEVELOPMENT AND CONSTRUCTION OF BIOCLIMATIC DOUBLE SKIN ACTIVE FACADE FOR HOT AND HUMID CLIMATE OF UAE
DEVELOPMENT AND CONSTRUCTION OF BIOCLIMATIC DOUBLE SKIN ACTIVE FACADE FOR HOT AND HUMID CLIMATE OF UAE Eng. Ray Karbor MSc. Director Engenius Green Technology FZE RAK, UAE & Ex-Sustainability Manager Reem
More informationP. Rohdin 1, M. Johansson 2, J. Löfberg 3, M. Ottosson 4. Abstract
ENERGY EFFICIENT PROCESS VENTILATION IN PAINT SHOPS IN THE CAR INDUSTRY EXPERIENCES AND AN EVALUATION OF A FULL SCALE IMPLEMENTATION AT SAAB AUTOMOBILE IN SWEDEN P. Rohdin 1, M. Johansson 2, J. Löfberg
More informationMilwaukee, WI. Darron Rempel
Application of Hydronic Radiant and Beam Systems ASHRAE Region IV Conference Milwaukee, WI May 14, 2010 Darron Rempel darronr@price hvac hvac.comcom Introduction Topics covered: o Theory of using water
More informationCost Benefits of SunGuard SN 54
Cost Benefits of SunGuard SN 54 Guardian Industries recently introduced SunGuard SN 54 low-e glass. This new low-e glass is clear in appearance and has optimal energy performance for commercial building
More informationOptimisation of an HVAC system for energy saving and thermal comfort in a university classroom
Optimisation of an HVAC system for energy saving and thermal comfort in a university classroom Giovanni Semprini DIN / CIRI, University of Bologna, Bologna, Italy Cosimo Marinosci DIN / CIRI, University
More informationThermal Delight in Architecture
THERMAL COMFORT DESIGN CRITERIA Ball State Architecture ENVIRONMENTAL SYSTEMS 1 Grondzik 1 Thermal Delight in Architecture This work began with the hypothesis that the thermal function of a building could
More informationUC Berkeley Indoor Environmental Quality (IEQ)
UC Berkeley Indoor Environmental Quality (IEQ) Title Energy savings from extended air temperature setpoints and reductions in room air mixing Permalink https://escholarship.org/uc/item/28x9d7xj Authors
More informationThe effect of shading design and control on building cooling demand
International Conference Passive and Low Energy Cooling 953 for the Built Environment, May 25, Santorini, Greece The effect of shading design and control on building cooling demand A. Tzempelikos and A.K.
More informationAvailable online at ScienceDirect. Procedia Engineering 145 (2016 ) 18 25
Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 145 (2016 ) 18 25 International Conference on Sustainable Design, Engineering and Construction Applicability of Radiant Heating-Cooling
More informationHourly Analysis Program v.4.1 Page 1 of 1
Air System Design Load Summary for Zona 11 DESIGN COOLING DESIGN HEATING COOLING DATA AT Dec 1700 HEATING DATA AT DES HTG COOLING OA DB / WB 33.1 C / 23.5 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible
More informationThe Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort
The Effects of Set-Points and Dead-Bands of the HVAC System on the Energy Consumption and Occupant Thermal Comfort Ongun Berk Kazanci, Bjarne W. Olesen 1 1 International Center for Indoor Environment and
More informationMartin Ratcliffe Visiting Research Fellow, Centre for Energy Studies at LSBU Head of Roger Preston Environmental
REAPING THE BENEFITS AVOIDING THE PITFALLS Martin Ratcliffe Visiting Research Fellow, Centre for Energy Studies at LSBU Head of Roger Preston CIBSE/ASHRAE Meeting LSBU May 12th 2004 1 Show that glazing
More informationCOMMERCIAL LOAD ESTIMATING. Load Estimating Level 3: Block and Zone Loads. Technical Development Program
COMMERCIAL LOAD ESTIMATING Load Estimating Level 3: Block and Zone Loads Technical Development Program Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design,
More informationChilled Beams. The new system of choice?
Chilled Beams The new system of choice? Presented By: Kevin M. Pope P.E. Jason Leffingwell Hammel Green And Abrahamson, Inc. and Ken Bauer, P.E., LEED AP Butters-Fetting Co., Inc. History of Chilled Beams
More informationDesigning Air-Distribution Systems To Maximize Comfort
Designing Air-Distribution Systems To Maximize Comfort By David A. John, P.E., Member ASHRAE An air-distribution system that provides occupant thermal comfort can be a complicated system to predict and
More informationEnergy Performance And Long-Term Evaluation Of Internal Thermal Comfort Of An Office Building With Different Kinds Of Glazing Systems And Window Sizes
Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering Energy Performance And Long-Term Evaluation Of Internal Thermal Comfort Of An Office
More informationThermal Delight in Architecture
THERMAL COMFORT OPR Ball State Architecture ENVIRONMENTAL SYSTEMS 1 Grondzik 1 Thermal Delight in Architecture This work began with the hypothesis that the thermal function of a building could be used
More informationVentilative Cooling potential tool
Ventilative Cooling potential tool User guide Version 1.0 IEA EBC Programme Annex 62 Ventilative Cooling AUTHORS: ANNAMARIA BELLERI EURAC RESEARCH Institute for renewable energy Druso 1 39100 Bolzano Italy
More informationDemonstration of modeling of radiant cooling system in design builder. Prashant Bhanware & Bharath Reddy
Demonstration of modeling of radiant cooling system in design builder Prashant Bhanware & Bharath Reddy CONTENTS Introduction to Design Builder Building Energy Simulation Modeling procedure Making a model
More informationHourly Analysis Program v.4.1 Page 1 of 1
Air System Design Load Summary for Zona 8 DESIGN COOLING DESIGN HEATING COOLING DATA AT Dec 1700 HEATING DATA AT DES HTG COOLING OA DB / WB 33.1 C / 23.5 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible Latent
More informationSelecting Energy Efficient New Windows in Tennessee
Selecting Energy Efficient New Windows in Tennessee www.efficientwindows.org January 06 STAR Zones. Meet the Energy Code & Look for the STAR Windows must comply with your local energy code. Windows that
More informationPOST OCCUPANCY DESIGN INERVENTION TO IMPROVE COMFORT AND ENERGY PERFORMANCE IN A DESERT HOUSE
POST OCCUPANCY DESIGN INERVENTION TO IMPROVE COMFORT AND ENERGY PERFORMANCE IN A DESERT HOUSE Vidar Lerum Arizona State University P O Box 871605, Tempe, AZ, 85287-1605, USA vidar.lerum@asu.edu Venkata
More informationSelecting Energy Efficient New Windows in Nevada
Selecting Energy Efficient New Windows in Nevada www.efficientwindows.org January 06 STAR Zones. Meet the Energy Code & Look for the STAR Windows must comply with your local energy code. Windows that are
More informationSTEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS
STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS 1. ABSTRACT In modern architecture the buildings are often designed with large glass facades or windows. Due to these
More informationSelecting Energy Efficient New Windows in Illinois
Selecting Energy Efficient New Windows in Illinois www.efficientwindows.org January 016 ENERGY STAR Zones 1. Meet the Energy Code & Look for the ENERGY STAR Windows must comply with your local energy code.
More informationItalcementi Center for Research and Innovation
Italcementi Center for Research and Innovation Bergamo, Italy LEED-NC v2.1 EAc1 A. Project Narrative (Viridian) analyzed the energy use of the proposed Italcementi Center for Research and Innovation located
More informationANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS
ANSI/ASHRAE STANDARD 200-2015, METHODS OF TESTING CHILLED BEAMS NEMIC 2017 Agenda 1. Foreword 2. Purpose & Scope 3. Definitions 4. Instrumentation & Facilities 5. Test Methods 6. Reporting 7. Normative
More informationSelecting Energy Efficient Replacement Windows in Arizona
Selecting Energy Efficient Replacement Windows in Arizona www.efficientwindows.org January 016 ENERGY STAR Zones 1. Meet the Energy Code & Look for the ENERGY STAR Windows must comply with your local energy
More informationDESIGN OF A GREEN DEMO BUILDING IN A HOT AND HUMID CITY IN CHINA. Ana Bacall Sebesta Blomberg & Associates Woburn, MA
DESIGN OF A GREEN DEMO BUILDING IN A HOT AND HUMID CITY IN CHINA Yi Jiang Sebesta Blomberg & Associates Woburn, MA William Hammer HKT Architects Somerville, MA Ana Bacall Sebesta Blomberg & Associates
More informationCanada Published online: 28 Feb 2011.
This article was downloaded by: [Bibliothèque ÉTS] On: 21 July 2015, At: 04:30 Publisher: Taylor & Francis Informa Ltd Registered in England and Wales Registered Number: 1072954 Registered office: 5 Howick
More informationARCHIVES OF CIVIL ENGINEERING, LX, 1, 2014 NUMERICAL INVESTIGATIONS OF EFFECT OF INDOOR AIR QUALITY ON THERMAL COMFORT IN RESIDENTIAL BUILDINGS
DOI: 10.2478/ace-2014-0005 ARCHIVES OF CIVIL ENGINEERING, LX, 1, 2014 NUMERICAL INVESTIGATIONS OF EFFECT OF INDOOR AIR QUALITY ON THERMAL COMFORT IN RESIDENTIAL BUILDINGS M. KRZACZEK 1, J. TEJCHMAN 2 The
More informationTHERMAL ANALYSIS OF A FACADE-MOUNTED PV ARRAY
SESCI 23 CONFERENCE Queen's University Kingston, Ontario, Canada August 18 to 2, 23 THERMAL ANALYSIS OF A FACADE-MOUNTED PV ARRAY S. J. Harrison 1, A. Driesse 2, Q. Lin 1 1 Queen's University, Solar Calorimetry
More informationIntegrated BIPV performance assessment for tropical regions: a case study for Bangalore
Integrated BIPV performance assessment for tropical regions: a case study for Bangalore Gayathri Aaditya Indian Institute of Science, Bangalore, India Rohitkumar Pillai Indian Institute of Science, Bangalore,
More informationThe pros and cons of chilled beams
The pros and cons of chilled beams Peter Clackett, Technical Director Skanska Rashleigh Weatherfoil William Booth, Operations Manager BSRIA Agenda 09.30 Registration 10.00 Welcome & Introduction - Jo Harris,
More informationExperimental investigation of zero energy office under natural and forced ventilation
Experimental investigation of zero energy office under natural and forced ventilation Hussain H. Al-Kayiem 1, Syed I. U. Gilani 1, * and Mahmoud S. Abdalfatah 2 1 Mech. Eng. Dept., Universiti Teknologi
More informationBusting the Myth: Passive Houses Only Work in Cold Climates. (The Comfort Proposition)
Busting the Myth: Passive Houses Only Work in Cold Climates (The Comfort Proposition) Alison Kwok, Ph.D., AIA, LEED AP, CPHC Alison G. Kwok Ph.D., AIA, LEED AP University of Oregon Walter T. Grondzik P.E.,
More informationModelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates
Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates Kittitach Pichatwatana, and Fan Wang Abstract This paper examines the TAS computer
More informationDISPLACEMENT VENTILATION
DISPLACEMENT VENTILATION D3 OVERVIEW The fundamental approach to displacement ventilation utilizes the natural buoyancy forces created by the convective flows from heat sources in the space. As supply
More informationThermal Comfort Evaluation of HDB flats
Thermal Comfort Evaluation of HDB flats Objective Measurements For this study, empirical data on the thermal comfort parameters (i.e. room space temperature, velocity and relative humidity) was collected
More informationProceedings of BS2013: 13th Conference of International Building Performance Simulation Association, Chambéry, France, August 26-28
CLIMATIC BASED CONSIDERATION OF DOUBLE SKIN FAÇADE SYSTEM: NATURAL VENTILATION PERFORMANCE OF A CASE STUDY WITH DOUBLE SKIN FAÇADE IN MEDITERRANEAN CLIMATE ABSTRACT There is an unexploited opportunity
More informationIntroduction to basics of energy efficient building design
Introduction to basics of energy efficient building design Pierre Jaboyedoff Seminar on Energy Efficient & Thermally Comfortable Buildings in Amravati For CRDA, Andhra Pradesh May 2 nd 2017 Indo-Swiss
More informationENERGY AND THERMAL COMFORT EVALUATION FOR DIFFERENT PASSIVE SOLUTIONS IN A KINDERGARTEN IN SUMMER CONDITIONS.
Eleventh International IBPSA Conference Glasgow, Scotland July -, 2009 ENERGY AND THERMAL COMFORT EVALUATION FOR DIFFERENT PASSIVE SOLUTIONS IN A KINDERGARTEN IN SUMMER CONDITIONS Eusébio. Z. E. Conceição
More informationNearly Zero Energy Building in Lecco Modern technological building compared to an ancient Villa
Nearly Zero Energy Building in Lecco Modern technological building compared to an ancient Villa Matteo BRASCA *, Oscar Luigi PAGANI **, Kanza RAUF*** * partner - AIACE S.r.l. società di ingegneria, contract
More informationEvaluation of natural ventilation systems in a landscaped office.
Plea24 - The 21 th Conference on Passive and Low Energy Architecture. Eindhoven, The Netherlands, 19-22 September 24 Page 1 of 6 Evaluation of natural ventilation systems in a landscaped office. Hilde
More informationDevelopment of New Self-Comparison Test Suites for EnergyPlus
Development of New Self-Comparison Test Suites for EnergyPlus Michael J. Witte Robert H. Henninger GARD Analytics, Inc., Arlington Hts., IL Drury B. Crawley U.S. Department of Energy, Washington, DC IBPSA-USA
More informationRadiant Slab Cooling for Retail
This article was published in ASHRAE Journal, December 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Reprinted here by permission from ASHRAE at www.newportventures.net.
More informationA field study of the performance of the Dutch Adaptive Temperature Limits guideline
Proceedings of Clima 07 WellBeing Indoors A field study of the performance of the Dutch Adaptive Temperature Limits guideline Stanley Kurvers 1, Kees van der Linden 1, Marco van Beek 2 1 Delft University
More informationCeiling Radiant Cooling Panels
2006, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc (wwwashraeorg) Published in ASHE Journal Vol 48, Oct 2006 For personal use only Additional reproduction, distribution,
More informationUnderf loor For Schools
The following article was published in ASHRAE Journal, May 2008. Copyright 2008 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes
More informationSageGlass. SageGlass Product Guide. Dynamic glass for a changing world
SageGlass Dynamic glass for a changing world SageGlass Product Guide Ultra-efficient SageGlass provides unmatched performance and proven reliability in commercial, institutional and residential buildings
More informationModeling the Brillhart House
Modeling the Brillhart House Located in a neighborhood like this 1 In a climate like this: Where almost every day has hours in the adaptive comfort zone. And the most effective passive strategies are:
More informationScienceDirect. Influence of the balcony glazing construction on thermal comfort of apartments in retrofitted large panel buildings
Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 108 (2015 ) 481 487 7th Scientific-Technical Conference Material Problems in Civil Engineering (MATBUD 2015) Influence of the
More informationThermal Characteristics and Energy Performance of Double Skin. Façade System in the Hot Summer and Cold Winter Zone
Thermal Characteristics and Energy Performance of Double Skin Façade System in the Hot Summer and Cold Winter Zone L.F. Shu 1, G.Q. He 1,*, S.M. Zhang 1 and Q.A. Bai 2 1 College of Civil Engineering and
More informationComputational and field test analysis of thermal comfort performance of user-controlled thermal chair in an open plan office
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 105 (2017 ) 2635 2640 The 8 th International Conference on Applied Energy ICAE2016 Computational and field test analysis of thermal
More informationSustainable Chilled Beam Design
MAIJA VIRTA HARRI ITKONEN PANU MUSTAKALLIO MIKA RUPONEN RISTO KOSONEN 1 - Halton Oy ABSTRACT Chilled beam technology is seen as a very sustainable technology providing both excellent indoor conditions
More informationIECC Commercial Significant Changes Summary Tier I
2009-2015 IECC Commercial Significant Changes Summary Tier I The first change is in the layout of the book. Instead of having Chapters 1-3 that applied to all projects and then having Chapter 4 Residential
More informationTHE USE OF SOLAR DESIGN DAYS IN A PASSIVE SOLAR HOUSE CONCEPTUAL DESIGN TOOL
Fredericton, N.B., Aug. -, THE USE OF SOLAR DESIGN DAYS IN A PASSIVE SOLAR HOUSE CONCEPTUAL DESIGN TOOL William O Brien 1, Ted Kesik, Andreas Athienitis 1 1 Department of Building, Civil and Environmental
More informationIMPLICATIONS OF CLIMATE CHANGE AND OCCUPANT BEHAVIOUR ON FUTURE ENERGY DEMAND IN A ZERO CARBON HOUSE
IMPLICATIONS OF CLIMATE CHANGE AND OCCUPANT BEHAVIOUR ON FUTURE ENERGY DEMAND IN A ZERO CARBON HOUSE Halla Huws and Ljubomir Jankovic Birmingham School of Architecture Birmingham Institute of Art and Design,
More informationPe r f o r m a n c e As s e s s m e n t of
June 2010 Page 1 of 1 Pe r f o r m a n c e As s e s s m e n t of Sa g e Gl a s s El e c t r o c h r o m i c Co a t i n g s and Control Scenarios Prepared For : SAGE Electrochromics, Inc. 1 Sage Way Faribault,
More informationAn experimental investigation of a passive chilled beam system in subtropical
An experimental inestigation of a passie chilled beam system in subtropical conditions Alex Hole 1, Risto Kosonen 2 1 Arup, Sydney - Australia 2 Halton, Kausala - Finland Corresponding email: alex.hole@arup.com.au
More informationA Case Study on the Daylighting and Thermal Effects of Fixed and Motorized Light Louvers
A Case Study on the Daylighting and Thermal Effects of Fixed and Motorized Light Louvers Yuxiang Chen 1, Samson Yip 1, Andreas Athienitis 1 1 Building, Civil and Environmental Engineering, Concordia University,
More informationExtended pilot study of an energy efficient glazed office building during pre-design and design. Åke Blomsterberg (WSP och LTH)
Extended pilot study of an energy efficient glazed office building during pre-design and design Åke Blomsterberg (WSP och LTH) 2 Project participants Client: Midroc projects Design: WSP at fixed price
More informationEnergy modeling in IDA ICE according to ASHRAE , app. G
Energy modeling in IDA ICE according to ASHRAE 90.1-2007, app. G About this document This document is a user s guide for a relatively experienced IDA ICE operator for using the 90.1 add-in and for performing
More informationENERGY CALCULATOR & MODELLING PROTOCOL
Green Star SA Retail Centre v1 ENERGY CALCULATOR & MODELLING PROTOCOL GUIDE VERSION 1.1 Last Update: 17 June 2010 1 Executive Summary The Green Star SA Retail Centre v1 rating tool has been developed to
More informationEnergy Consumption Measurement of Energy-saving Buildings and Analysis of Simulation Example
Sensors & Transducers 203 by IFSA http://www.sensorsportal.com Energy Consumption Measurement of Energy-saving Buildings and Analysis of Simulation Example Ying Li, 2 Tiegang Kang Zhejiang College of Construction,
More information1.1 Mechanical Systems Comfort Criteria Space Performance Conditions
1.1 Mechanical Systems Comfort Criteria The intention is to operate the building through a broader range of internal environmental conditions than is typical within current industry norms. The building
More informationIMPACT OF COLUMNS AND BEAMS ON THE THERMAL RESISTANCE OF THE BUILDING ENVELOPE
IMPACT OF COLUMNS AND BEAMS ON THE THERMAL RESISTANCE OF THE BUILDING ENVELOPE Dr. Essam Al-Sayed Omar Department Manager Kuwait Institute for Scientific Research Kuwait ABSTRACT This paper addresses the
More informationProceedings: Building Simulation 2007
MULTICRITERION EVALUATION OF AN INTEGRATED SUSTAINABLE HEATING/COOLING SYSTEM IN CLIMATE CONDITIONS OF CENTRAL EUROPE Karel Kabele and Pavla Dvořáková Czech Technical University in Prague, Faculty of Civil
More informationPrinciples of Ventilation and Air Conditioning Design & Installation
Unit 10: Unit code Principles of Ventilation and Air Conditioning Design & Installation D/615/1926 Unit level 4 Credit value 15 Introduction The demands of modern living as well as the potential impact
More informationUsing Radiant Cooled Floors to Condition Large Spaces and Maintain Comfort Conditions
DA-00-8-3 Using Radiant Cooled Floors to Condition Large Spaces and Maintain Comfort Conditions Peter Simmonds, Ph.D. Member ASHRAE Stefan Holst ABSTRACT Stephanie Reuss This paper describes the development
More informationPERFORMANCE EVALUATION OF PV VENTILATED GLAZING
Eleventh International IBPSA Conference Glasgow, Scotland July 27-30, 2009 PERFORMANCE EVALUATION OF PV VENTILATED GLAZING Tin-tai Chow 1,*, Zhongzhu Qiu 2, and Chunying Li 1 1 Building Energy and Environmental
More informationDEMAND CONTROLLED VENTILATION (DCV) SYSTEMS
DEMAND CONTROLLED VENTILATION (DCV) SYSTEMS Mari-Liis Maripuu, PhD CIT Energy mari-liis.maripuu@cit.chalmers.se Swegon Air Academy, Portugal, 27 May 211 Outline Introduction Concept of a DCV system Adapting
More informationEvaluation of Energy Savings of the New Chinese Commercial Building Energy Standard
Evaluation of Energy Savings of the New Chinese Commercial Building Energy Standard Wei Feng, Ke Huang, Mark Levine and Nan Zhou, Lawrence Berkeley National Laboratory Shicong Zhang, Lawrence Berkeley
More informationRetrofitting Adaptive Comfort Strategies into Conventionally Air Conditioned Commercial Buildings
Retrofitting Adaptive Comfort Strategies into Conventionally Air Conditioned Commercial Buildings Hisham Allam 1 The University Of Sydney SUMMARY Reducing the temperature difference between indoor HVAC
More informationAcutherm was spec d here. Building Automation Guide for Therma-Fuser Systems
Building Automation Guide for Therma-Fuser Systems Acutherm was spec d here BUILDING AUTOMATION OPTIONS FOR THERMA-FUSER SYSTEMS As energy costs continue to rise, the management of energy while balancing
More informationA STUDY OF DAYLIGHTING TECHNIQUES AND THEIR ENERGY IMPLICATIONS USING A DESIGNER FRIENDLY SIMULATION SOFTWARE
A STUDY OF DAYLIGHTING TECHNIQUES AND THEIR ENERGY IMPLICATIONS USING A DESIGNER FRIENDLY SIMULATION SOFTWARE Amarpreet Sethi College of Architecture and Environmental Design Arizona State University,
More informationModelling Approaches for Displacement Ventilation in Offices
Modelling Approaches for Displacement Ventilation in Offices J L M Hensen *,MJHHamelinck % and M G L C Loomans # * University of Strathclyde % Physibel c.v. # Eindhoven University of Technology Energy
More informationDTS & ENERGY MODELLING PROTOCOL GUIDE Version 1.0
DTS & ENERGY MODELLING PROTOCOL GUIDE Version 1.0 Green Star SA Multi Unit Residential v1 DTS & Energy Modelling Protocol Guide First Released: 27 th October 2011 Last Update: 27 th October 2011 Change
More informationARCH-MEDES (I) CONSULTANTS PVT. LTD. Green Park Delhi
Passive & Energy Efficient Design Assistance Report for Proposed Hospital Complex Manipal Health System at Pitampura, New Delhi ARCH-MEDES (I) CONSULTANTS PVT. LTD. Green Park Delhi Prepared By (Low Carbon
More informationAIC TECH 2015 Sustainability in Practice Turning Ideas into Reality Jan 16, 2015 FUTURE & NET ZERO BUILDINGS
AIC TECH 2015 Sustainability in Practice Turning Ideas into Reality Jan 16, 2015 FUTURE & NET ZERO BUILDINGS CONTENTS Introduction to Net Zero Can we get to Net Zero? Pathway to Net Zero Energy Buildings
More informationLIFE CYCLE COST OF DISPLACEMENT VENTILATION IN AN OFFICE BUILDING WITH A HOT AND HUMID CLIMATE
LIFE CYCLE COST OF DISPLACEMENT VENTILATION IN AN OFFICE BUILDING WITH A HOT AND HUMID CLIMATE By LANE W. BURT A THESIS PRESENTED TO THE GRADUATE SCHOOL OF THE UNIVERSITY OF FLORIDA IN PARTIAL FULFILLMENT
More informationTHERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE
S447 THERMAL MASS IMPACT ON ENERGY PERFORMANCE OF A LOW, MEDIUM, AND HEAVY MASS BUILDING IN BELGRADE by Bojan V. ANDJELKOVIĆ *,a, Branislav V. STOJANOVIĆ b, Mladen M. STOJILJKOVIĆ b, Jelena N. JANEVSKI
More informationCase Study for Fortune 500 Telecom: Retrofitting Pneumatic Controls for Energy Efficiency
Case Study for Fortune 500 Telecom: Retrofitting Pneumatic Controls for Energy Efficiency Summary Major Fortune 500 Telecom Company Estimated 40% the corporate building portfolio still use pneumatic thermostats
More informationAvailable online at ScienceDirect. Energy Procedia 78 (2015 ) th International Building Physics Conference, IBPC 2015
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 340 345 6th International Building Physics Conference, IBPC 2015 The influence of solar control films on energy and daylighting
More informationThe optimization of the mechanical night cooling system in the office building
The optimization of the mechanical night cooling system in the office building Milos Lain 1, Jan Hensen 2 1 Department of Environmental Engineering, Faculty of Mechanical Engineering, Czech Technical University
More informationThe Art of Thermal Mass Modeling for Energy Conservation in Buildings, Part 2
The Art of Thermal Mass Modeling for Energy Conservation in Buildings, Part 2 Linda Lam is a Project Engineer at Transsolar, Inc. She has a traditional mechanical engineering background with an energetic
More informationCOMPUTATIONAL ASSESSMENT OF COOLING WITH LOW-TEMPERATURE HEATING SYSTEMS
Ninth International IBPSA Conference Montréal, Canada August 15-18, 2005 COMPUTATIONAL ASSESSMENT OF COOLING WITH LOW-TEMPERATURE HEATING SYSTEMS P. de Wilde 1, H. van Wolferen 2 and M. Loomans 1 1. TNO
More informationUncertainties in Energy Consumption Introduced by Building Operations and Weather for a Medium-Size Office Building
Uncertainties in Energy Consumption Introduced by Building Operations and Weather for a Medium-Size Office Building Liping Wang, Paul Mathew, Xiufeng Pang Environmental Energy Technologies Division Lawrence
More informationAir Conditioning Inspections for Buildings Assessing Equipment Sizing
Air Conditioning Inspections for Buildings Assessing Equipment Sizing PRESENTED BY NIRAJ MISTRY aircon@stroma.com Size V s Load Regulation 22 of EPB Regulations The inspection report must include an assessment
More informationArticle Control of Thermally Activated Building System Considering Zone Load Characteristics
Article Control of Thermally Activated Building System Considering Zone Load Characteristics Woong June Chung 1, Sang Hoon Park 2, Myoung Souk Yeo 3 and Kwang Woo Kim 4, * 1 Department of Architecture
More informationWhite Paper ENVELOPE-FIRST APPROACH TO NET-ZERO ENERGY BUILDINGS
BOULDER CHICAGO NASHVILLE SALT LAKE CITY SAN FRANCISCO SPRINGFIELD, MO WASHINGTON, DC 2540 Frontier Avenue, Suite 100 Boulder, Colorado 80301 303.444.4149 White Paper ENVELOPE-FIRST APPROACH TO NET-ZERO
More informationNot Presented. Investigating thermal comfort and occupants position impacts on building sustainability using CFD and BIM. 1.
R.H. Crawford and A. Stephan (eds.), Living and Learning: Research for a Better Built Environment: 49 th International Conference of the Architectural Science Association 2015, pp.257 266. 2015, The Architectural
More informationAssessment of the energy demand in energy-saving office buildings from the viewpoint of variations of internal heat gains
Assessment of the energy demand in energy-saving office buildings from the viewpoint of variations of internal heat gains Andrzej Baranowski 1,2 and Joanna Ferdyn-Grygierek 1,2 1 Silesian University of
More informationPostprint.
http://www.diva-portal.org Postprint This is the accepted version of a paper presented at 13th International Conference on Indoor Air Quality and Climate, July 7-12, 2014, Hong Kong. Citation for the original
More informationOptimization for Passive Design of Large Scale Housing Projects for Energy and Thermal Comfort in a Hot and Humid Climate
Optimization for Passive Design of Large Scale Housing Projects for Energy and Thermal Comfort in a Hot and Humid Climate Tam Nguyen Van*, Damien Trigaux, Karen Allacker and Frank De Troyer Architectural
More informationOptimal Design of an Office Building for Low-Primary Energy Requirement and High-Indoor Thermal Comfort Level
Optimal Design of an Office Building for Low-Primary Energy Requirement and High-Indoor Thermal Comfort Level Kai Siren Professor Aalto University School of Science and Technology Finland kai.siren@tkk.fi
More information