PERFORMANCE EVALUATION OF TWO AIR DISTRIBUTION SYSTEMS. T Karimipanah 1 and H B Awbi 2

Size: px
Start display at page:

Download "PERFORMANCE EVALUATION OF TWO AIR DISTRIBUTION SYSTEMS. T Karimipanah 1 and H B Awbi 2"

Transcription

1 PERFORMANCE EVALUATION OF TWO AIR DISTRIBUTION SYSTEMS T Karimipanah 1 and H B Awbi 2 1 Air Innovation AB, Sweden 2 University of Reading, UK ABSTRACT This paper focuses on evaluating the performance of a wall displacement ventilation system and a new impinging jet ventilation system. Ventilation efficiency, local mean age of air and other characteristic parameters were experimentally and numerically obtained for a mock-up classroom. The internal heat load of 25 person-simulators were set to represent a crowded classroom in order to investigate any indoor climate problems caused by increased cooling loads. Four ventilation strategies were compared in a previous paper [1] but here we have chosen only the two systems mentioned. In addition to a large number of costly experiments we used CFD simulations to study certain parameters in more detail and explore the results for other situations such as industrial ventilation. The results presented here are part of a larger search programme to develop alternative and efficient systems for new challenging situations of room airflow distribution. Keywords: Displacement, Impinging jet ventilation, classroom, industrial ventilation, measurements, CFD INTRODUCTION Although the traditional mixing systems show poor ventilation efficiency and less energy efficient but they still occupy a large portion of the market. When displacement ventilation was first introduced almost three decades ago, it seemed at the time to be a promising ventilation concept due to its high ventilation efficiency and stratification principle. To create an effective ventilation system in the occupied zone, there should be a balance between the momentum and thermal (buoyancy) forces. In this low momentum displacement flow, the buoyancy forces created by heat sources have a tendency to take over and thus often causing poor ventilation efficiency in some zones of the room [2]. Another disadvantage of a displacement system is that it can only be used for cooling and is not suitable for winter heating. To overcome this problem new systems like ceiling mounted textile bag supply and down-to-floor impinging supply have been developed, see reference [1]. A new method of air distribution known as the Air Queen (AQ) has been developed in Sweden, which is based on the impinging jet principle [3]. This method has the advantages of both the mixing and displacement ventilation systems without known disadvantages. Impinging jet ventilation (IJV) has lower momentum than mixing and higher momentum than wall displacement ventilation (WDV). Although higher momentum than WDV, IJV produces a similar flow field and has, therefore, promising applications [1, 4]. Ventilation parameters To assess the effectiveness of a ventilation system in measurement or CFD simulation, some well-known parameters are used [5]:

2 Ventilation Effectiveness for Heat Distribution or Removal (ε t )- This is similar to a heat exchanger effectiveness and is defined by: To Ti ε t = (1) T T i Ventilation Effectiveness for Contaminant Removal (ε c )- This is a measure of how effective the ventilation system is in removing internally produced contamination. It is defined by: Co Ci ε c = (2) C Ci In equations (1) and (2), T is temperature ( o C), C is the contaminant concentration in parts per million (ppm), the subscripts i and o refer to inlet and outlet respectively and ( ) represents the mean value for the occupied zone (to a height of 1.8 m). The values of εt and ε c is dependent on the method of room air distribution, room characteristics, heat and contaminant sources, etc. In addition, expressions for the predicted percentage of dissatisfied (PPD) and predicted mean vote (PMV) that are used here are defined by Fanger [6]. EXPERIMENTS The size of the mock-up was 8.4x7.2x3 m and 25 person-simulators were placed in the room representing a teacher and 24 students. A climate chamber attached to the room was used to simulate extreme winter and summer conditions, see Figure 1. The heat output from personsimulators were 2375 W and 525 W was considered for lighting giving a total load of 2 9 W (48 W/m 2 ). In all tests the air flow rate was 1 l/s per person and the inlet air temperature was kept constant at +15 C. The outdoor temperature was kept at 21 C to simulate winter conditions and at + 25 C to simulate summer conditions. The devices were tested by measuring the air temperature, air velocity and air quality (local mean age of air) in the occupied zone. The room area was divided into 12 zones and a stand placed in the middle of each zone was used to measure the required quantities at different heights. The local mean age of air was measured by using the tracer gas decay technique at 1.2 m above floor. Further details can be found in references [1 and 4]. CFD CALCULATIONS The CFD program VORTEX [7] has been used to predict the airflow properties in the classroom. This program has been developed for the simulation of airflow, heat transfer, mean age of air distribution, PPD and PMV in enclosures. The code uses the standard κ-ε turbulence model and has been developed for ventilation research, which may be more suitable to ventilation simulations than the more general-purpose codes. In the simulations, the measured mean surface temperatures of all six room surfaces have been used as boundary conditions. The number of nodes used were 49 x 39x 37 giving a resolution of.17 m in the horizontal plane and.81 m in the vertical direction. The distance from the floor of the impinging jet outlet was.9 m in both the measurements and the CFD simulations.

3 Figure 1. Plan view of the classroom with supply positions. All dimensions in meters. RESULTS Figure 2 (a,b) shows the air flow patterns from the CFD results for the two supply methods at a height of 4 mm from the floor. Although the air supply velocity of 1.56 ms -1 in the case of IJV was much higher than in the displacement case the velocity close to the floor decays very rapidly and it is only large at a short distance from the jet impinging point on the floor. The spread of the impinging jet over the floor produces a velocity near the floor which is similar in magnitude to that of the displacement ventilation system. However, the floor layer in this case is much thinner than that in the case of the WDV. (a) wall displacement ventilation (b) impinging jet ventilation Fig. 2 Velocity vectors in a horizontal plane 9 cm from floor and age of air contours in a vertical plane

4 The temperature gradients for the two cases are shown in Fig. 3. The agreement between the measurements and CFD simulations are good. The recommended temperature gradient of 3K or less is fulfilled. The mean velocity gradients are shown in Figure 4. Except for heights up to 15 cm above the floor the velocities are much lower than.15 m/s for both cases, indicating a comfortable environment. The velocity distribution over a horizontal plane 1 cm above the floor (see Fig.1) is plotted in Figure 5. Only the wall displacement system shows a tendency for a velocity higher than the recommended maximum of.15 cm/s closed to the walls. 22, ,5 21 Temprature [ o C] 2,5 2 19, ,5 18,1,9,42,74,89 1,19 1,5 2,7 2,38 2,46 2,61 2,85 Height [m] Fig. 3 Mean temperature profiles for two ventilation systems,3,25 Mean velocity [m/s],2,15,1,5,1,9,42,74,89 1,19 1,5 2,7 2,38 2,46 2,61 2,85 Height [m] Fig. 4 Mean Velocity gradients for two ventilation systems

5 Figure 6 shows the predicted percentage of dissatisfied (PPD. One can see from the figure that in a large portion of the room PPD is below 1% for both systems and this is acceptable for such large heat loads. The normalised mean age of air (i.e. the local age divided by that at the exhaust) is shown in Figure 7 for all the measuring points at a height of 1.2 m above the floor (breathing zone level). There is some agreement between the WDV and the IJV results at some of the points but not at others. This may be due to the difference between the momentum in the two systems and its interaction with the local buoyancy forces. The CFD results show similar trends to measurements.,25,2 Mean velocity [m/s].,15,1,5, 1,5 3,15 5,25 7,35 8, Distance from window, x[m] Fig. 5 Predicted and measured mean velocity distribution in a horizontal plane 1 cm above the floor for two ventilation systems PPD [%] ,1,9,42,74,89 1,19 1,5 2,7 2,38 2,46 2,61 2,85 Height [m] Fig. 6 Predicted PPD profiles for two ventilation systems

6 The temperature and velocity profiles at all measuring points 1.2 m above the floor (breathing zone) are shown in Figures 8 and 9. Both systems show good temperature distributions but the WDV gives a higher values. Considering the velocity field for both cases one can see that the velocities are very low and there is little tendency to draught risk. An overall look to the all parameters studied show that both systems can handle the extreme situation they exposed for with some small differences in behaviours. 1,8 1,6 Normalised mean age εi [-] 1,4 1,2 1,8,6,4, Measuring point number Fig. 7 Predicted and measured normalised local mean age of air profiles at the breathing zone (1.2 m above floor) for two ventilation systems Temprature [ o C] Measuring point number Fig. 8 Predicted and measured local mean temperature profiles at the breathing zone (1.2 m above the floor) for two ventilation systems The predicted contaminant removal effectiveness (ε), was 14% for WDV and 13% for IJV indicating the ability of both systems to remove the contaminants in an effective way. The

7 predicted mean votes (PMV) were.63 and.61, which are still less than.5 that is suggested by Fanger [6] to be acceptable.,16 Mean velocity [m/s],14,12,1,8,6,4, Measuring point number Fig. 9 Predicted and measured local mean velocity profiles in breathing zone (1.2 m above the floor) for two ventilation systems Figure 1 shows four sequences of smoke visualisation for an impinging jet supply device. One can see that when the jet reaches the heat source (sitting person) a plume forms and due to sufficient momentum the jet continues along the floor. This is the advantage of impinging jet ventilation compared to a displacement system, in which case the flow sometimes has insufficient momentum to continue passed a heat source and its totally consumed by the plume. Two industrial application of impinging jet ventilation in Sweden are shown in Figure 11a & b. Figure 11a shows an installation of impinging jet supply in System 3R International, which was installed to replace displacement devices in a building where precision instruments/tools are manufactured. When displacement ventilation was used there were many complains from the workers and after their replacement with impinging jet systems no compliment was reported. Figure 11b shows the IJV installed in a factory for heavy metal industry. Another advantage of impinging jet ventilation is that the duct itself has a sound damping effect, which reduces aerodynamic noise at the supply terminal. CONCLUSIONS The results obtained here have shown that the floor level air distribution can handle a full room heat load in an acceptable manner. Although both the WDV and the IJV systems show similar tendencies, some small differences were observed in their performance. Because of better balance between buoyancy and momentum forces the IJV system show slightly better age and velocity distributions. Furthermore, the latter can also be used for both heating and cooling purposes. According to references [1 and 4] the impinging height has a significant

8 effect on the IJV performance but this is not considered here. Therefore, this new system may need further studies by ventilation researchers and designer to fully understand its performance at different conditions. Fig. 1. Smoke visualisation of impinging jet ventilation (a) System 3R International Factory (b) Heavy Metal Industries in Fagersta in Stockholm Fig. 11 Two industrial applications of impinging jet ventilation. Acknowledgements

9 The authors gratefully acknowledge Prof. Mats Sandberg, Leif Claesson (in BMG, Gävle), Mr Bengt Svensson and Lars Berthilson (VVESS Consulting AB, Gävle), Per-Johan Ohlsson, Johan Kostakis and Örjan Josefsson for their valuable contribution to this work. REFRENCES [1] Karimipanah, T, Sandberg, M and Awbi, HB (2), A comparative study of different air distribution systems in a classroom, Air Distribution in Rooms: Ventilation for Health and Sustainable Environment, Proc. ROOMVENT 2, HB Awbi (ed.), Vol. 2, pp , Elsevier, Oxford. [2] Etheridge D. and Sandberg M (1996), John Wiley & Sons Ltd., UK. Building Ventilation: Theory and Measurement, [3] Karimipanah, T (1996), Turbulent jets in confined spaces, PhD thesis, Royal Institute of Technology, Sweden. [4] Kostakis J and Josefsson, Ö (1999), Thermal Comfort and Air Quality in a classroom, University college of Gävle, B.Sc Thesis (In Swedish). [5] Awbi, H.B. (1998), Energy efficient room air distribution, Renewable Energy, Vol. 15, pp [6] Fanger, P.O. (1972). Thermal Comfort, McGraw-Hill, New York. [7] Gan, G and Awbi, HB (1994), Numerical simulation of the indoor environment, Building and Environment, Vol 29, No 4, pp

Postprint.

Postprint. http://www.diva-portal.org Postprint This is the accepted version of a paper presented at 13th International Conference on Indoor Air Quality and Climate, July 7-12, 2014, Hong Kong. Citation for the original

More information

LOCAL VENTILATION SYSTEMS: SOME INVESTIGATIONS ABOUT COMFORT LEVELS AND ENERGY DEMANDS

LOCAL VENTILATION SYSTEMS: SOME INVESTIGATIONS ABOUT COMFORT LEVELS AND ENERGY DEMANDS LOCAL VENTILATION SYSTEMS: SOME INVESTIGATIONS ABOUT COMFORT LEVELS AND ENERGY DEMANDS Elena Buchberger - ebuch@iuav.it Luca Porciani, porciani@iuav.it Fabio Peron, fperon@iuav.it Universita IUAV di Venezia,

More information

IDENTIFICATION OF VENTILATION PROBLEMS IN AN UNDERGROUND BUS TERMINAL IN KOREA

IDENTIFICATION OF VENTILATION PROBLEMS IN AN UNDERGROUND BUS TERMINAL IN KOREA IDENTIFICATION OF VENTILATION PROBLEMS IN AN UNDERGROUND BUS TERMINAL IN KOREA H Han 1* and Y-I Kwon 2 1 Dept. Of Mechanical Engineering, Kookmin University, Korea 2 Dept. Of Building Mechanical Engineering,

More information

Energy and Thermal Comfort Management in a Kindergarten School Building in the South of Portugal in Winter Conditions

Energy and Thermal Comfort Management in a Kindergarten School Building in the South of Portugal in Winter Conditions 4th IASME/WSEAS International Conference on ENERGY, ENVIRONMENT, ECOSYSTEMS and SUSTAINABLE DEVELOPMENT (EEESD'8) Algarve, Portugal, June 11-13, 8 Energy and Thermal Comfort Management in a Kindergarten

More information

These systems are offered an alternative to overhead, mixing ventilation (MV), systems. Due to their potential advantages which are [1]:

These systems are offered an alternative to overhead, mixing ventilation (MV), systems. Due to their potential advantages which are [1]: Prediction of thermal comfort, IAQ, and Energy consumption in a dense occupancy environment with the under floor air distribution system Ghassem Heidarinejad 1, Mohammad Hassan Fathollahzadeh 2, Hadi Pasdarshahri

More information

DISPLACEMENT VENTILATION

DISPLACEMENT VENTILATION DISPLACEMENT VENTILATION D3 OVERVIEW The fundamental approach to displacement ventilation utilizes the natural buoyancy forces created by the convective flows from heat sources in the space. As supply

More information

DEMAND CONTROLLED VENTILATION (DCV) SYSTEMS

DEMAND CONTROLLED VENTILATION (DCV) SYSTEMS DEMAND CONTROLLED VENTILATION (DCV) SYSTEMS Mari-Liis Maripuu, PhD CIT Energy mari-liis.maripuu@cit.chalmers.se Swegon Air Academy, Portugal, 27 May 211 Outline Introduction Concept of a DCV system Adapting

More information

COMPARISON OF THE STANDARDIZED REQUIREMENTS FOR INDOOR CLIMATE IN OFFICE BUILDINGS

COMPARISON OF THE STANDARDIZED REQUIREMENTS FOR INDOOR CLIMATE IN OFFICE BUILDINGS Kazderko Mikhail COMPARISON OF THE STANDARDIZED REQUIREMENTS FOR INDOOR CLIMATE IN OFFICE BUILDINGS Bachelor s Thesis Building Services Engineering December 2012 DESCRIPTION Date of the bachelor's thesis

More information

FLOOR-SUPPLY DISPLACEMENT VENTILATION FOR WORKSHOPS. Josephine Lau and Qingyan Chen*

FLOOR-SUPPLY DISPLACEMENT VENTILATION FOR WORKSHOPS. Josephine Lau and Qingyan Chen* Lau, J. and Chen, Q. 27. "Floor-supply displacement ventilation for workshops," Building and Environment, 42(4), 78-73. FLOOR-SUPPLY DISPLACEMENT VENTILATION FOR WORKSHOPS Josephine Lau and Qingyan Chen*

More information

Designing Air-Distribution Systems To Maximize Comfort

Designing Air-Distribution Systems To Maximize Comfort Designing Air-Distribution Systems To Maximize Comfort By David A. John, P.E., Member ASHRAE An air-distribution system that provides occupant thermal comfort can be a complicated system to predict and

More information

An experimental investigation of a passive chilled beam system in subtropical

An experimental investigation of a passive chilled beam system in subtropical An experimental inestigation of a passie chilled beam system in subtropical conditions Alex Hole 1, Risto Kosonen 2 1 Arup, Sydney - Australia 2 Halton, Kausala - Finland Corresponding email: alex.hole@arup.com.au

More information

Effect of Rotation Speed of a Rotary Thermal Wheel on Ventilation Supply Rates of Wind Tower System

Effect of Rotation Speed of a Rotary Thermal Wheel on Ventilation Supply Rates of Wind Tower System Available online at www.sciencedirect.com ScienceDirect Energy Procedia 75 (2015 ) 1705 1710 The 7 th International Conference on Applied Energy ICAE2015 Effect of Rotation Speed of a Rotary Thermal Wheel

More information

Published in: Proceedings of the 7th International Conference on Healthy Buildings 2003, Singapore, December 2003, Vol. 2

Published in: Proceedings of the 7th International Conference on Healthy Buildings 2003, Singapore, December 2003, Vol. 2 Aalborg Universitet Design Methods for Air Distribution Systems and Comparison Between Mixing Ventilation and Displacement Ventilation Nielsen, Peter Vilhelm; Larsen, Tine Steen; Topp, Claus Published

More information

A STUDY OF CROSS CONTAMINATION OF IN-SUITE VENTILATION SYSTEMS USED IN MULTI-UNIT RESIDENTIAL BUILDINGS

A STUDY OF CROSS CONTAMINATION OF IN-SUITE VENTILATION SYSTEMS USED IN MULTI-UNIT RESIDENTIAL BUILDINGS A STUDY OF CROSS CONTAMINATION OF IN-SUITE VENTILATION SYSTEMS USED IN MULTI-UNIT RESIDENTIAL BUILDINGS C.A. Parker, K.D. Pressnail, M.F. Touchie, D. DeRose, and S. Dedesko ABSTRACT Complaints of cross

More information

ARCHIVES OF CIVIL ENGINEERING, LX, 1, 2014 NUMERICAL INVESTIGATIONS OF EFFECT OF INDOOR AIR QUALITY ON THERMAL COMFORT IN RESIDENTIAL BUILDINGS

ARCHIVES OF CIVIL ENGINEERING, LX, 1, 2014 NUMERICAL INVESTIGATIONS OF EFFECT OF INDOOR AIR QUALITY ON THERMAL COMFORT IN RESIDENTIAL BUILDINGS DOI: 10.2478/ace-2014-0005 ARCHIVES OF CIVIL ENGINEERING, LX, 1, 2014 NUMERICAL INVESTIGATIONS OF EFFECT OF INDOOR AIR QUALITY ON THERMAL COMFORT IN RESIDENTIAL BUILDINGS M. KRZACZEK 1, J. TEJCHMAN 2 The

More information

ENERGY AND THERMAL COMFORT EVALUATION FOR DIFFERENT PASSIVE SOLUTIONS IN A KINDERGARTEN IN SUMMER CONDITIONS.

ENERGY AND THERMAL COMFORT EVALUATION FOR DIFFERENT PASSIVE SOLUTIONS IN A KINDERGARTEN IN SUMMER CONDITIONS. Eleventh International IBPSA Conference Glasgow, Scotland July -, 2009 ENERGY AND THERMAL COMFORT EVALUATION FOR DIFFERENT PASSIVE SOLUTIONS IN A KINDERGARTEN IN SUMMER CONDITIONS Eusébio. Z. E. Conceição

More information

ASSESSMENT OF AIR CHANGE RATE AND CONTRIBUTION RATIO IN IDEALIZED URBAN CANOPY LAYERS BY TRACER GAS SIMULATIONS

ASSESSMENT OF AIR CHANGE RATE AND CONTRIBUTION RATIO IN IDEALIZED URBAN CANOPY LAYERS BY TRACER GAS SIMULATIONS Topic B4: Ventilation ASSESSMENT OF AIR CHANGE RATE AND CONTRIBUTION RATIO IN IDEALIZED URBAN CANOPY LAYERS BY TRACER GAS SIMULATIONS Qun WANG 1, Mats SANDBERG 2, Jian HANG 1* 1 Department of Atmospheric

More information

Centre for Sustainability of the Built Environment

Centre for Sustainability of the Built Environment Case Study Report Indoor air quality of a demandcontrolled air-conditioning system Mayfield House Lecture Theatre, Falmer Campus, University of Brighton European Regional Development Fund Executive summary

More information

P. Rohdin 1, M. Johansson 2, J. Löfberg 3, M. Ottosson 4. Abstract

P. Rohdin 1, M. Johansson 2, J. Löfberg 3, M. Ottosson 4. Abstract ENERGY EFFICIENT PROCESS VENTILATION IN PAINT SHOPS IN THE CAR INDUSTRY EXPERIENCES AND AN EVALUATION OF A FULL SCALE IMPLEMENTATION AT SAAB AUTOMOBILE IN SWEDEN P. Rohdin 1, M. Johansson 2, J. Löfberg

More information

Thermal comfort and indoor air quality analysis of a low-energy cooling windcatcher.

Thermal comfort and indoor air quality analysis of a low-energy cooling windcatcher. Thermal comfort and indoor air quality analysis of a low-energy cooling windcatcher. Item type Authors Citation DOI Publisher Journal Article Calautit, John Kaiser; Aquino, Angelo I.; Shahzad, Sally; Nasir,

More information

Articles. Figure 2. Typical set-up of personalized ventilation system.

Articles. Figure 2. Typical set-up of personalized ventilation system. Revision of 15251: ndoor Environmental Criteria Abstract: 15251 specifies indoor environmental input parameters for design and assessment of energy performance of buildings addressing indoor air quality,

More information

For all those with the ability to influence the design, layout or indoor air quality of buildings

For all those with the ability to influence the design, layout or indoor air quality of buildings Natural Selection For all those with the ability to influence the design, layout or indoor air quality of buildings By the end of this presentation you will:- Understand what Natural Ventilation is. Know

More information

Computational and field test analysis of thermal comfort performance of user-controlled thermal chair in an open plan office

Computational and field test analysis of thermal comfort performance of user-controlled thermal chair in an open plan office Available online at www.sciencedirect.com ScienceDirect Energy Procedia 105 (2017 ) 2635 2640 The 8 th International Conference on Applied Energy ICAE2016 Computational and field test analysis of thermal

More information

BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY. Dr Mirek Piechowski 1, Adrian Rowe 1

BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY. Dr Mirek Piechowski 1, Adrian Rowe 1 BUILDING DESIGN FOR HOT AND HUMID CLIMATES IMPLICATIONS ON THERMAL COMFORT AND ENERGY EFFICIENCY Dr Mirek Piechowski 1, Adrian Rowe 1 Meinhardt Building Science Group, Meinhardt Australia 1 Level 12, 501

More information

Modelling Approaches for Displacement Ventilation in Offices

Modelling Approaches for Displacement Ventilation in Offices Modelling Approaches for Displacement Ventilation in Offices J L M Hensen *,MJHHamelinck % and M G L C Loomans # * University of Strathclyde % Physibel c.v. # Eindhoven University of Technology Energy

More information

Sustainable Chilled Beam Design

Sustainable Chilled Beam Design MAIJA VIRTA HARRI ITKONEN PANU MUSTAKALLIO MIKA RUPONEN RISTO KOSONEN 1 - Halton Oy ABSTRACT Chilled beam technology is seen as a very sustainable technology providing both excellent indoor conditions

More information

Numerical Modelling of Air Distribution in the Natatorium Supported by the Experiment

Numerical Modelling of Air Distribution in the Natatorium Supported by the Experiment Proceedings of the World Congress on Mechanical, Chemical, and Material Engineering (MCM 2015) Barcelona, Spain July 20-21, 2015 Paper No. 277 Numerical Modelling of Air Distribution in the Natatorium

More information

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Available online at  ScienceDirect. Procedia Engineering 121 (2015 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 121 (2015 ) 1689 1696 9th International Symposium on Heating, Ventilation and Air Conditioning (ISHVAC) and the 3rd International

More information

Optimizing Indoor Environments for Occupant Satisfaction. Presented by: Kelli Goldstone April 2016

Optimizing Indoor Environments for Occupant Satisfaction. Presented by: Kelli Goldstone April 2016 Optimizing Indoor Environments for Occupant Satisfaction Presented by: Kelli Goldstone April 2016 Outline Function of HVAC Thermal Comfort Air Distribution Radiant Heating / Cooling Case Study Function

More information

Numerical Investigation of the Integration of Heat Transfer Devices into Wind Towers

Numerical Investigation of the Integration of Heat Transfer Devices into Wind Towers A publication of CHEMICAL ENGINEERING TRANSACTIONS VOL. 34, 2013 Guest Editors: Neven Duić, Petar Sabev Varbanov Copyright 2013, AIDIC Servizi S.r.l., ISBN 978-88-95608-25-9; ISSN 1974-9791 The Italian

More information

The Design and Simulation of Natural Personalised Ventilation (NPV) System for Multi-Bed Hospital Wards

The Design and Simulation of Natural Personalised Ventilation (NPV) System for Multi-Bed Hospital Wards Buildings 2015, 5, 381-404; doi:10.3390/buildings5020381 Article OPEN ACCESS buildings ISSN 2075-5309 www.mdpi.com/journal/buildings/ The Design and Simulation of Natural Personalised Ventilation (NPV)

More information

THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING. Gang Wang, Yafeng Hu, and Songtao Hu

THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING. Gang Wang, Yafeng Hu, and Songtao Hu THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING Gang Wang, Yafeng Hu, and Songtao Hu School of Environmental & Municipal Engineering, Qingdao Technological University, Qingdao

More information

Earth, Wind & Fire Natural Airconditioning [1] Research objectives and Methods

Earth, Wind & Fire Natural Airconditioning [1] Research objectives and Methods Earth, Wind & Fire Natural Airconditioning [1] Research objectives and Methods Ben Bronsema Department of Architectural Engineering, Faculty of Architecture, Delft University of Technology, The Netherlands

More information

Ventilation standards EN15251 and ANSI/ASHRAE 62.1 Professor Bjarne W. Olesen, Ph.D.

Ventilation standards EN15251 and ANSI/ASHRAE 62.1 Professor Bjarne W. Olesen, Ph.D. Ventilation standards EN15251 and ANSI/ASHRAE 62.1 Professor Bjarne W. Olesen, Ph.D. Technical University of Denmark Energy consumption for ventilation Exhaust Ventilation air Up to 30% of the total energy

More information

BEYOND ARROWS: ENERGY PERFORMANCE OF A NEW, NATURALLY VENTILATED DOUBLE-SKIN FACADE CONFIGURATION FOR A HIGH-RISE OFFICE BUILDING IN CHICAGO

BEYOND ARROWS: ENERGY PERFORMANCE OF A NEW, NATURALLY VENTILATED DOUBLE-SKIN FACADE CONFIGURATION FOR A HIGH-RISE OFFICE BUILDING IN CHICAGO BEYOND ARROWS: ENERGY PERFORMANCE OF A NEW, NATURALLY VENTILATED DOUBLE-SKIN FACADE CONFIGURATION FOR A HIGH-RISE OFFICE BUILDING IN CHICAGO BY MONA AZARBAYJANI DISSERTATION Submitted in partial fulfillment

More information

INDOOR AIR QUALITY MEASUREMENTSS AND CFD SIMULATIONS IAQ POMIARY I SYMULACJE CFD

INDOOR AIR QUALITY MEASUREMENTSS AND CFD SIMULATIONS IAQ POMIARY I SYMULACJE CFD RICHRD NGY, INGRID ŠENITKOVÁ INDOOR IR QULITY MESUENTSS ND CFD SIMULTIONS IQ POMIRY I SYMULCJE CFD Odpowiedzialność za poprawność językową ponoszą autorzy b s t r a c t This paper presents an experimental

More information

CFD INVESTIGATION OF AIRFLOW AROUND CONIC TENSILE MEMBRANE STRUCTURES

CFD INVESTIGATION OF AIRFLOW AROUND CONIC TENSILE MEMBRANE STRUCTURES CFD INVESTIGATION OF AIRFLOW AROUND CONIC TENSILE MEMBRANE STRUCTURES A. M. ElNokaly 1, J. C. Chilton 2 and R. Wilson 1 1 School of the Built Environment, University of Nottingham, Nottingham, NG7 2RD,

More information

FEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF

FEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF FEDERATION TOWER MOSCOW DIFFERENT ROOM CLIMATES UNDER ONE ROOF Oliver Baumann 1, and Claudius Reiser 1/2 1 Ebert & Baumann Consulting Engineers, Washington, D.C. 2 Ebert-Ingenieure GmbH &Co. KG, Munich,

More information

Underf loor For Schools

Underf loor For Schools The following article was published in ASHRAE Journal, May 2008. Copyright 2008 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes

More information

PERFORMANCE BASED EVALUATION OF FIRE SCENARIOS USING FLUENT

PERFORMANCE BASED EVALUATION OF FIRE SCENARIOS USING FLUENT PERFORMANCE BASED EVALUATION OF FIRE SCENARIOS USING FLUENT Shyam Dayanandan, Dan Chong Computational Engineering Solutions LLP E-mail: shyam@ce-sol.com Website: www.ce-sol.com ABSTRACT The Fire and Engineering

More information

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models L. Pagliano et al, I: Optimization of air tightness and night ventilation for Passive houses in Italian climates... 1 Optimization of air tightness and night ventilation for Passive houses in Italian climates

More information

Protected zone ventilation reduces personal exposure to indoor pollution

Protected zone ventilation reduces personal exposure to indoor pollution The full length version of this article is available at www.rehva.eu > Publications & Resources > HVAC Journal Protected zone ventilation reduces personal exposure to indoor pollution Guangyu Cao VTT Technical

More information

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS

OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS OPERATION AND CONTROL OF THERMALLY ACTIVATED SLAB HEATING AND COOLING SYSTEMS Bjarne W. Olesen Ph. D, International Centre for Indoor Environment and Energy, Department of Mechanical Engineering, Technical

More information

Performance Analysis for Natural Draught Cooling Tower & Chimney through Numerical Simulation

Performance Analysis for Natural Draught Cooling Tower & Chimney through Numerical Simulation Performance Analysis for Natural Draught Cooling Tower & Chimney through Numerical Simulation Kanteyya A 1, Kiran Kumar Rokhade 2 Assistant Professor, Department of Mechanical Engineering, HKESSLN College

More information

Practical Guide Comfort level measurement in the workplace :32. PMV PPD measurement protocol Default Point Graphic Date/Time

Practical Guide Comfort level measurement in the workplace :32. PMV PPD measurement protocol Default Point Graphic Date/Time 05.05.2015 16:32 PMV PPD measurement protocol Default Point Graphic Date/Time 04.05.2015 10:51 Practical Guide Comfort level measurement in the workplace 1 Introduction. Several hundred million people

More information

Proceedings of BS2013: 13th Conference of International Building Performance Simulation Association, Chambéry, France, August 26-28

Proceedings of BS2013: 13th Conference of International Building Performance Simulation Association, Chambéry, France, August 26-28 CLIMATIC BASED CONSIDERATION OF DOUBLE SKIN FAÇADE SYSTEM: NATURAL VENTILATION PERFORMANCE OF A CASE STUDY WITH DOUBLE SKIN FAÇADE IN MEDITERRANEAN CLIMATE ABSTRACT There is an unexploited opportunity

More information

The pros and cons of chilled beams

The pros and cons of chilled beams The pros and cons of chilled beams Peter Clackett, Technical Director Skanska Rashleigh Weatherfoil William Booth, Operations Manager BSRIA Agenda 09.30 Registration 10.00 Welcome & Introduction - Jo Harris,

More information

Transport of gaseous pollutants around a human body in quiescent indoor environment

Transport of gaseous pollutants around a human body in quiescent indoor environment Downloaded from orbit.dtu.dk on: May 01, 2018 Transport of gaseous pollutants around a human body in quiescent indoor environment Licina, Dusan; Melikov, Arsen Krikor; Mioduszewski, Pawel ; Sekhar, Chandra;

More information

Live Transportation Research and Improvement Initiatives

Live Transportation Research and Improvement Initiatives Live Transportation Research and Improvement Initiatives MLF Transport Working Committee As a major chicken processor in Canada, MLF recognizes the critical need to identify improved live bird transportation

More information

Thermal performance of a closed wet cooling tower for chilled ceilings: measurement and CFD simulation

Thermal performance of a closed wet cooling tower for chilled ceilings: measurement and CFD simulation INTERNATIONAL JOURNAL OF ENERGY RESEARCH Int. J. Energy Res. 2000; 24:1171}1179 Thermal performance of a closed wet cooling tower for chilled ceilings: measurement and CFD simulation Sa!a Ri!at*, Armando

More information

Optimization of a Dual-Fuel Low-NOx Combustion System for a Tangentially-Fired Utility Boiler Operating at a High Elevation.

Optimization of a Dual-Fuel Low-NOx Combustion System for a Tangentially-Fired Utility Boiler Operating at a High Elevation. Optimization of a Dual-Fuel Low-NOx Combustion System for a Tangentially-Fired Utility Boiler Operating at a High Elevation. by F. McKenty, N. Brais, M. Mifuji, L. Gravel, and Y. Sirois STAR Global Energy

More information

A Solar Wall System Utilized in Rural Houses of Northeast China

A Solar Wall System Utilized in Rural Houses of Northeast China A Solar Wall System Utilized in Rural Houses of Northeast China Tiantian Zhang and Yufei Tan in rural buildings, for instance, only 16.4% of the investigated houses employ solar energy to produce hot water

More information

A Field Study of the Thermal Environment in Residential Buildings in Harbin

A Field Study of the Thermal Environment in Residential Buildings in Harbin KC-03-13-4 (4664) A Field Study of the Thermal Environment in Residential Buildings in Harbin Zhao-Jun Wang, Ph.D. Gang Wang Le-Ming Lian ABSTRACT This paper presents the main findings of Project HIT.2000.25

More information

DEVELOPMENT AND CONSTRUCTION OF BIOCLIMATIC DOUBLE SKIN ACTIVE FACADE FOR HOT AND HUMID CLIMATE OF UAE

DEVELOPMENT AND CONSTRUCTION OF BIOCLIMATIC DOUBLE SKIN ACTIVE FACADE FOR HOT AND HUMID CLIMATE OF UAE DEVELOPMENT AND CONSTRUCTION OF BIOCLIMATIC DOUBLE SKIN ACTIVE FACADE FOR HOT AND HUMID CLIMATE OF UAE Eng. Ray Karbor MSc. Director Engenius Green Technology FZE RAK, UAE & Ex-Sustainability Manager Reem

More information

FINE CONTROL AND NATURAL VENTILATION. WindowMaster Solutions for Natural Ventilation 1

FINE CONTROL AND NATURAL VENTILATION. WindowMaster Solutions for Natural Ventilation 1 FINE CONTROL AND NATURAL VENTILATION WindowMaster Solutions for Natural Ventilation 1 VKR Group Structure WindowMaster Solutions for Natural Ventilation 2 Why are we here? WindowMaster, through research

More information

Evaluation of Underfloor Air Distribution

Evaluation of Underfloor Air Distribution McCarran International Airport Terminal 3 L as Vegas, NV Evaluation of Underfloor Air Distribution and Displacement Ventilation Systems The Pennsylvania State University AESenior ThesisPresentation, Spring

More information

CFD modeling of airflows and contaminant transport in an aircraft cabin

CFD modeling of airflows and contaminant transport in an aircraft cabin 20th International Congress on Modelling and Simulation, Adelaide, Australia, 1 6 December 2013 www.mssanz.org.au/modsim2013 CFD modeling of airflows and contaminant transport in an aircraft cabin Jiuzhou

More information

Evaluation of natural ventilation systems in a landscaped office.

Evaluation of natural ventilation systems in a landscaped office. Plea24 - The 21 th Conference on Passive and Low Energy Architecture. Eindhoven, The Netherlands, 19-22 September 24 Page 1 of 6 Evaluation of natural ventilation systems in a landscaped office. Hilde

More information

LIFE CYCLE COST OF DISPLACEMENT VENTILATION IN AN OFFICE BUILDING WITH A HOT AND HUMID CLIMATE

LIFE CYCLE COST OF DISPLACEMENT VENTILATION IN AN OFFICE BUILDING WITH A HOT AND HUMID CLIMATE LIFE CYCLE COST OF DISPLACEMENT VENTILATION IN AN OFFICE BUILDING WITH A HOT AND HUMID CLIMATE By LANE W. BURT A THESIS PRESENTED TO THE GRADUATE SCHOOL OF THE UNIVERSITY OF FLORIDA IN PARTIAL FULFILLMENT

More information

Study on Emporium cooling load distribution and Airflow Optimization indoor

Study on Emporium cooling load distribution and Airflow Optimization indoor , pp.50-54 http://dx.doi.org/10.14257/astl.2014.75.13 Study on Emporium cooling load distribution and Airflow Optimization indoor LV Ziqiang 1,2, Liu Yingjie 1 1 University of Science and Technology of

More information

Indoor Climate and Ventilation in Finnish Schools Air Distribution and Temperature Control in Classrooms

Indoor Climate and Ventilation in Finnish Schools Air Distribution and Temperature Control in Classrooms Indoor Climate and Ventilation in Finnish Schools Air Distribution and Temperature Control in Classrooms Abstract Finland is a country without a debate on natural ventilation. In such a cold climate, it

More information

Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France

Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France Sylvain Boulet 1, Stéphanie Armand-Decker 2, FCBA Technological Institute I2M-TREFLE laboratory -

More information

VENTILATION REQUIREMENTS TO PREVENT PIT AIR UP-DRAFTING IN

VENTILATION REQUIREMENTS TO PREVENT PIT AIR UP-DRAFTING IN This is not a peer-reviewed article. Pp. 05-030 in Swine Housings II Proceedings of the -5 October 003 Conference (Research Triangle Park, North Carolina USA), Publication Date October 003. ASAE Publication

More information

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Available online at  ScienceDirect. Procedia Engineering 121 (2015 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 121 (2015 ) 1449 1453 9th International Symposium on Heating, Ventilation and Air Conditioning (ISHVAC) and the 3rd International

More information

Canada Published online: 28 Feb 2011.

Canada Published online: 28 Feb 2011. This article was downloaded by: [Bibliothèque ÉTS] On: 21 July 2015, At: 04:30 Publisher: Taylor & Francis Informa Ltd Registered in England and Wales Registered Number: 1072954 Registered office: 5 Howick

More information

AN APPLICATION OF BUILDING SIMULATION TECHNIQUES TO THE ASSESSMENT OF NATURAL VENTILATION IN OFFICE WITH DOUBLE SKIN FACADE

AN APPLICATION OF BUILDING SIMULATION TECHNIQUES TO THE ASSESSMENT OF NATURAL VENTILATION IN OFFICE WITH DOUBLE SKIN FACADE Third German-Austrian IBPSA Conference AN APPLICATION OF BUILDING SIMULATION TECHNIQUES TO THE ASSESSMENT OF NATURAL VENTILATION IN OFFICE WITH DOUBLE SKIN FACADE Milan Janak, Katarina Moravcikova Slovak

More information

125BEPM - Building energy performance modeling. Lecture handouts

125BEPM - Building energy performance modeling. Lecture handouts 125BEPM - Building energy performance modeling Lecture handouts 2 - Introduction to building energy performance modeling and simulation prof. Karel Kabele - Page 1/13 - CONTENT 1 INTRODUCTION TO BUILDING

More information

NOTE: Some guidance on a performance approach to natural ventilation systems design is provided in the Supplement to this Standard.

NOTE: Some guidance on a performance approach to natural ventilation systems design is provided in the Supplement to this Standard. 19 SECTION 3 NATURAL VENTILATION 3.1 SCOPE OF SECTION This Section specifies the means of achieving the quantity of outdoor air required in a naturally ventilated enclosure. The provisions described include

More information

THERMAL ANALYSIS OF A FACADE-MOUNTED PV ARRAY

THERMAL ANALYSIS OF A FACADE-MOUNTED PV ARRAY SESCI 23 CONFERENCE Queen's University Kingston, Ontario, Canada August 18 to 2, 23 THERMAL ANALYSIS OF A FACADE-MOUNTED PV ARRAY S. J. Harrison 1, A. Driesse 2, Q. Lin 1 1 Queen's University, Solar Calorimetry

More information

Comparison Between PIV Measurements and CFD Simulation on a Model of GT Annular Burner

Comparison Between PIV Measurements and CFD Simulation on a Model of GT Annular Burner Comparison Between PIV Measurements and CFD Simulation on a Model of GT Annular Burner D. Giordano, S. Giammartini, M. Rufoloni, G. Calchetti, F. Manfredi, E. Giacomazzi ENEA - C. R. Casaccia Sec. ENE-IMP

More information

COUPLING STRATEGY OF HVAC SYSTEM SIMULATION AND CFD PART 2: STUDY ON MIXING ENERGY LOSS IN AN AIR-CONDITIONED ROOM

COUPLING STRATEGY OF HVAC SYSTEM SIMULATION AND CFD PART 2: STUDY ON MIXING ENERGY LOSS IN AN AIR-CONDITIONED ROOM 12th Conference of International Building Performance Simulation Association, Sdne, 14-16 November. COUPLING STRATEGY OF HVAC SYSTEM SIMULATION AND CFD PART 2: STUDY ON MIXING ENERGY LOSS IN AN AIR-CONDITIONED

More information

COMPUTATIONAL ASSESSMENT OF COOLING WITH LOW-TEMPERATURE HEATING SYSTEMS

COMPUTATIONAL ASSESSMENT OF COOLING WITH LOW-TEMPERATURE HEATING SYSTEMS Ninth International IBPSA Conference Montréal, Canada August 15-18, 2005 COMPUTATIONAL ASSESSMENT OF COOLING WITH LOW-TEMPERATURE HEATING SYSTEMS P. de Wilde 1, H. van Wolferen 2 and M. Loomans 1 1. TNO

More information

ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS

ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS ANSI/ASHRAE STANDARD 200-2015, METHODS OF TESTING CHILLED BEAMS NEMIC 2017 Agenda 1. Foreword 2. Purpose & Scope 3. Definitions 4. Instrumentation & Facilities 5. Test Methods 6. Reporting 7. Normative

More information

681: Environmentally Responsive Architecture; Passive Design for School in Southern India

681: Environmentally Responsive Architecture; Passive Design for School in Southern India 681: Environmentally Responsive Architecture; Passive Design for School in Southern India Varun Kohli* Architectural Association School of Architecture, London, UK * varun.kohli@som.com Abstract This paper

More information

IMPLICATIONS OF CLIMATE CHANGE AND OCCUPANT BEHAVIOUR ON FUTURE ENERGY DEMAND IN A ZERO CARBON HOUSE

IMPLICATIONS OF CLIMATE CHANGE AND OCCUPANT BEHAVIOUR ON FUTURE ENERGY DEMAND IN A ZERO CARBON HOUSE IMPLICATIONS OF CLIMATE CHANGE AND OCCUPANT BEHAVIOUR ON FUTURE ENERGY DEMAND IN A ZERO CARBON HOUSE Halla Huws and Ljubomir Jankovic Birmingham School of Architecture Birmingham Institute of Art and Design,

More information

Thermal Management of Densely-packed EV Battery Set

Thermal Management of Densely-packed EV Battery Set EVS28 KINTEX, Korea, May 3-6, 2015 Thermal Management of Densely-packed EV Battery Set Abstract Z. Lu 1, X.Z. Meng 1, W.Y. Hu 2, L.C. Wei 3, L.Y. Zhang 1, L.W. Jin 1* 1 Building Environment and Equipment

More information

Woodside Energy Ltd, Perth, AUSTRALIA.

Woodside Energy Ltd, Perth, AUSTRALIA. Comparing CFD and CORMIX for Buoyant Wastewater Near-Field Dispersion Modeling Simon Mortensen 1, Carl Jackson 2, Ole Petersen 3 and Geoff Wake 4 1 DHI Water & Environment, Gold Coast, AUSTRALIA, email:

More information

Optimisation of an HVAC system for energy saving and thermal comfort in a university classroom

Optimisation of an HVAC system for energy saving and thermal comfort in a university classroom Optimisation of an HVAC system for energy saving and thermal comfort in a university classroom Giovanni Semprini DIN / CIRI, University of Bologna, Bologna, Italy Cosimo Marinosci DIN / CIRI, University

More information

Verification and Validation of Preliminarily Result of CFD of Electrostatic Precipitator Mr.Dharmendra Dekate 1 Mr.K.M.Narkar 2

Verification and Validation of Preliminarily Result of CFD of Electrostatic Precipitator Mr.Dharmendra Dekate 1 Mr.K.M.Narkar 2 IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 01, 015 ISSN (online): 31-013 Verification and Validation of Preliminarily Result of CFD of Electrostatic Precipitator

More information

MODELLING BUOYANCY INDUCED FLOWS OF PASSIVE COOLING SYSTEMS Pedro Correia da Silva 1, Vítor Leal 1 and J. Correia da Silva 2

MODELLING BUOYANCY INDUCED FLOWS OF PASSIVE COOLING SYSTEMS Pedro Correia da Silva 1, Vítor Leal 1 and J. Correia da Silva 2 Eleventh International IBPSA Conference Glasgow, Scotland July 27-30, 2009 MODELLING BUOYANCY INDUCED FLOWS OF PASSIVE COOLING SYSTEMS Pedro Correia da Silva 1, Vítor Leal 1 and J. Correia da Silva 2 1

More information

CFD on Small Flow Injection of Advanced Accumulator in APWR

CFD on Small Flow Injection of Advanced Accumulator in APWR 54 CFD on Small Flow Injection of Advanced Accumulator in APWR TOMOSHIGE TAKATA TAKAFUMI OGINO TAKASHI ISHIBASHI TADASHI SHIRAISHI The advanced accumulator in the advanced pressurized-water reactor is

More information

Heat transfer modelling of slot jet impinging on an inclined plate

Heat transfer modelling of slot jet impinging on an inclined plate Heat transfer modelling of slot jet impinging on an inclined plate A. Ramezanpour 1, H. Shirvani 1 & I. Mirzaee 2 1 School of Design and Communication Systems, APU University, UK 2 CFD Research Centre,

More information

MODELLING THE URBAN MICROCLIMATE AND ITS INFLUENCE ON BUILDING ENERGY DEMANDS OF AN URBAN NEIGHBOURHOOD

MODELLING THE URBAN MICROCLIMATE AND ITS INFLUENCE ON BUILDING ENERGY DEMANDS OF AN URBAN NEIGHBOURHOOD MODELLING THE URBAN MICROCLIMATE AND ITS INFLUENCE ON BUILDING ENERGY DEMANDS OF AN URBAN NEIGHBOURHOOD J. Allegrini 1,2 ; J. Kämpf 3 ; V. Dorer 1 ; J. Carmeliet 1,2 1: Empa, Laboratory for Building Science

More information

Numerical Investigation of the Flow Dynamics of a Supersonic Fluid Ejector

Numerical Investigation of the Flow Dynamics of a Supersonic Fluid Ejector Proceedings of the International Conference on Heat Transfer and Fluid Flow Prague, Czech Republic, August 11-12, 2014 Paper No. 171 Numerical Investigation of the Flow Dynamics of a Supersonic Fluid Ejector

More information

EFFECTIVE THRUST TRANSFORMATION INSIDE TUNNELS WITH JET FANS (BANANA JET)

EFFECTIVE THRUST TRANSFORMATION INSIDE TUNNELS WITH JET FANS (BANANA JET) - 74 - EFFECTIVE THRUST TRANSFORMATION INSIDE TUNNELS WITH JET FANS (BANANA JET) Witt K.C. 1, Schütze J. 1 1 Witt&Sohn AG, Pinneberg, Germany ABSTRACT Every few years an idea comes along, which in its

More information

PRODUCT BROCHURE. Fixed Helical Swirl Diffuser HSC-FD HSC-FD : smartemp.com

PRODUCT BROCHURE. Fixed Helical Swirl Diffuser HSC-FD HSC-FD : smartemp.com PRODUCT BROCHURE Fixed Helical Swirl Diffuser HSC-FD HSC-FD : 07 smartemp.com DESCRIPTION The SMARTEMP Fixed Helical Swirl Diffuser, type HSC-FD, produces highly inductive swirl discharge, diffusing the

More information

On-Site Experimental Validation of a Coupled Multizone and CFD Model for Building Contaminant Transport Simulations PROOF

On-Site Experimental Validation of a Coupled Multizone and CFD Model for Building Contaminant Transport Simulations PROOF Authors may request permission to reprint or post on their personal or company Web site once the final version of the article has been published. A reprint permission form may be found at www.ashrae.org.

More information

UNCERTAINTIES IN AIRFLOW NETWORK MODELLING TO SUPPORT NATURAL VENTILATION EARLY STAGE DESIGN

UNCERTAINTIES IN AIRFLOW NETWORK MODELLING TO SUPPORT NATURAL VENTILATION EARLY STAGE DESIGN UNCERTAINTIES IN AIRFLOW NETWORK MODELLING TO SUPPORT NATURAL VENTILATION EARLY STAGE DESIGN Annamaria Belleri* 1, 2, Roberto Lollini 1 1 EURAC research Druso, 1 39100 Bolzano, Italy *annamaria.belleri@eurac.edu

More information

Thermal Characteristics and Energy Performance of Double Skin. Façade System in the Hot Summer and Cold Winter Zone

Thermal Characteristics and Energy Performance of Double Skin. Façade System in the Hot Summer and Cold Winter Zone Thermal Characteristics and Energy Performance of Double Skin Façade System in the Hot Summer and Cold Winter Zone L.F. Shu 1, G.Q. He 1,*, S.M. Zhang 1 and Q.A. Bai 2 1 College of Civil Engineering and

More information

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates Kittitach Pichatwatana, and Fan Wang Abstract This paper examines the TAS computer

More information

INVESTIGATION OF HEAT TRANSFER BEHAVIOR OF A FINNED SOLAR AIR COLLECTOR USING FLUENT

INVESTIGATION OF HEAT TRANSFER BEHAVIOR OF A FINNED SOLAR AIR COLLECTOR USING FLUENT INVESTIGATION OF HEAT TRANSFER BEHAVIOR OF A FINNED SOLAR AIR COLLECTOR USING FLUENT A KHALID 1, H JUNAIDI 2 1 DEPARTMENT OF MECHANICAL ENGINEERING, NED UNIVERSITY OF ENGINEERING AND TECHNOLOGY, KARACHI

More information

Chapter 21 Numerical Analysis of Air Flow Around a Hot Water Radiator for Its Structure Improvement

Chapter 21 Numerical Analysis of Air Flow Around a Hot Water Radiator for Its Structure Improvement Chapter 21 Numerical Analysis of Air Flow Around a Hot Water Radiator for Its Structure Improvement Juan Wang, Zhanyong Li, Ruifang Wang, Qing Xu, Wei Tian and Miaomiao Li Abstract Hot water radiators

More information

Work Package 2: Performance of naturally ventilated buildings

Work Package 2: Performance of naturally ventilated buildings Work Package 2: Performance of naturally ventilated buildings Detailed Monitoring Report BRF-kredit Headquarters (DK2) Niels C. Bergsøe Danish Building Research Institute, SBI Energy and Indoor Climate

More information

Not Presented. Investigating thermal comfort and occupants position impacts on building sustainability using CFD and BIM. 1.

Not Presented. Investigating thermal comfort and occupants position impacts on building sustainability using CFD and BIM. 1. R.H. Crawford and A. Stephan (eds.), Living and Learning: Research for a Better Built Environment: 49 th International Conference of the Architectural Science Association 2015, pp.257 266. 2015, The Architectural

More information

Available online at ScienceDirect. Energy Procedia 112 (2017 )

Available online at  ScienceDirect. Energy Procedia 112 (2017 ) Available online at www.sciencedirect.com ScienceDirect Energy Procedia 112 (2017 ) 613 620 Sustainable Solutions for Energy and Environment, EENVIRO 2016, 26-28 October 2016, Bucharest, Romania Experimental

More information

Cooling Ceiling Panel

Cooling Ceiling Panel A Study on the Performance of Cooling Ceiling Panel Dr. Chirdpun Vitooraporn 1 and Aryut Wattanawanichakorn 2 1 Lecturer at Building Technology and Environment Laboratory, 2 Former graduate student Mechanical

More information

ESTIMATION OF THE GAS EXHAUST RATE REQUIRED ON AN ALUMINIUM REDUCTION CELL DURING START-UP USING TASCflow3D

ESTIMATION OF THE GAS EXHAUST RATE REQUIRED ON AN ALUMINIUM REDUCTION CELL DURING START-UP USING TASCflow3D ESTIMATION OF THE GAS EXHAUST RATE REQUIRED ON AN ALUMINIUM REDUCTION CELL DURING START-UP USING TASCflow3D Marc Dupuis (GéniSim Eng.) Edgar Dernedde (Kroll International) ABSTRACT During the start-up

More information

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1 Air System Design Load Summary for Zona 8 DESIGN COOLING DESIGN HEATING COOLING DATA AT Dec 1700 HEATING DATA AT DES HTG COOLING OA DB / WB 33.1 C / 23.5 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible Latent

More information

TABS, THERMAL ACTIVATED BUILDING SYSTEM, TO IMPROVE COMFORT IN SCHOOLS

TABS, THERMAL ACTIVATED BUILDING SYSTEM, TO IMPROVE COMFORT IN SCHOOLS TABS, THERMAL ACTIVATED BUILDING SYSTEM, TO IMPROVE COMFORT IN SCHOOLS Wim Zeiler, Robin Scholten, and Gert Boxem Technische Universiteit Eindhoven, TU/e, the Netherlands ABSTRACT Indoor air quality has

More information