The energy and exergy analysis of a novel cogeneration organic Rankine power and twostage compression refrigeration cycle

Size: px
Start display at page:

Download "The energy and exergy analysis of a novel cogeneration organic Rankine power and twostage compression refrigeration cycle"

Transcription

1 Energy Equip. Sys./ Vol. 5/No.3/September 2017/ Energy Equipment and Systems ttp://energyequipsys.ut.ac.ir Te energy and exergy analysis of a novel cogeneration organic Rankine power and twostage compression refrigeration cycle Autors Hamed Mortazavi Beni a Afsin Amadi Nadoosan a* Morteza Bayare a a Department of Mecanical Engineering, Sarekord University, Sarekord,Iran Article istory: Received : 13 February 2017 Accepted : 24 April 2017 ABSTRACT Te energy crisis in recent years as led to te use of termodynamic cycles tat work based on renewable energies. Lowtemperature cycles suc as organic cycles are suitable strategies for te application of renewable energies. Te present study proposes a novel cycle troug te integration of a two-stage compression refrigeration cycle wit a combined Rankine power and ejector refrigeration cycle by using te cascade condenser metod. Te fundamental idea of tis cycle is to obtain refrigeration production at lower temperatures, and to acieve iger termal and exergy efficiencies. Te results sowed tat te new cycle recorded an percent improvement in termal efficiency and a percent improvement in exergy efficiency compared to te basic cycle. Even toug te network output of te cycle is reduced, a significant increase in te refrigeration capacity of te cycle is observed. Keywords: Cogeneration Cycle, Exergy, Solar Energy, Ejector, Cascade Condenser. 1. Introduction In tis researc, te new cogeneration organic Rankine power and two-stage compression refrigeration cycle as been analyzed from te viewpoint of energy and exergy. In tis cycle, solar energy is used as te eat source. Nowadays, solar energy is considered more frequently because it is a clean and renewable energy. Wile te use of solar collectors and setting up te cycles wit solar energy as te eat source as iger initial costs, te current cycle cost is muc lower due to te lack of environmental costs and as fossil fuels are not required. Tis issue is also significant wit regard to te lack of environmental pollution in te solar cycles. Low-temperature cycles suc as cycles tat use organic fluids *Corresponding autor: Afsin Amadi Nadoosan Address: Department of Mecanical Engineering, Sarekord University, Sarekord,Iran address: amadi@eng.sku.ac.ir as refrigerants are te proper approac for using sustainable, clean, and renewable energies suc as geotermal and solar energy. Zang et al. [1] evaluated te performance of te double-compression flas intercooling refrigeration cycle in comparison wit te double-compression external intercooling cycle. Te results sowed tat te doublecompression flas intercooling refrigeration cycle and te double-compression external intercooling cycle yield te maximum coefficient of performance improvement of 23.18% and 11.03% over te basic cycle, respectively. Tere are numerous metods for improving te performance of te vaporcompression refrigeration cycle. One of tese metods involves te use of an ejector as an expander device. Using an ejector is preferred due to te ig efficiency and te lack of mecanical rotary components, wic reduces depreciation. Nowadays, te ejector

2 300 Hamed Mortazavi Beni et al./ Energy Equip. Sys. / Vol. 5/No.3/Sep is used in many mecanical cycles suc as power plants and compression refrigeration cycles. So far, many researc studies ave focused on ejector expansion compression refrigeration cycles [2 6]. In tis researc, te ejector is used as an expander device in te compression refrigeration cycle instead of using an expansion valve in order to avoid te work and energy losses in te expansion valve. In anoter study, Xing et al. [7] proposed an ejector subcooled vaporcompression refrigeration cycle. Te results sowed tat te performance of te ejector subcooled cycle is better tan tat of te conventional cycle. Wang et al. [8] compared te use of te ejector expander in te vaporcompression refrigeration cycles for applications in domestic refrigerator freezers and presented a novel modified ejector expansion vapor-compression refrigeration cycle. Zu and Jiang [9] developed a refrigeration system by combining te basic vapor-compression refrigeration cycle wit an ejector cooling cycle. In tis system, te ejector-cooling cycle is driven by te waste eat from te condenser in te vaporcompression refrigeration cycle. Te results sow tat te coefficient of performance is improved by 9.1% in te ybrid refrigeration system. Te ejector application domain is not limited to te vapor-compression refrigeration cycle. It is used in many cases, suc as in te petroleum and petrocemical industries for te purification and separation of crude oil, and also as a vacuum pump in devices suc as condensers. Te ejector is also used in te ejector refrigeration cycle. So far, many researces on ejector refrigeration cycles, as well as on combined Rankine power and ejector refrigeration cycles, ave been carried out. Cen et al. [10] studied te interactions and relationsips of various ejector parameters in te ejector refrigeration system to gain access to an optimum generator temperature tat obtains te maximum Carnot efficiency. Sorouradin et al. [11] investigated te performance of an ejector refrigeration cycle teoretically and experimentally. Te results indicate a decrease in te coefficient of performance wit increasing generator temperature and an increase in te second law of efficiency wit increasing evaporator temperature and decreasing generator temperature. Adrian et al. [12] optimized an ejector refrigeration system wit different working fluids tat operates on waste eat provided by te exausted gas of an internal combustion engine by energy and exergy analysis. Lontsi et al. [13] proposed a multitemperature compression ejection refrigeration cycle by combining a compression refrigeration cycle and an ejector refrigeration cycle. Tey suggested using tis multi-temperature refrigeration cycle instead of te conventional two-stage vaporcompression refrigeration system. By adding a steam turbine before te ejector in ejector refrigeration, te new cycle can be based on combined power generation and ejector refrigeration. Many researc studies ave focused on suc cycles [14 18]. In tese researces, te researcers investigated te factors affecting te cycle, suc as te input and output temperature, te pressure of te turbine, te evaporator temperature, and te entrainment ratio of te ejector to analyze and optimize te combined Rankine power and ejector refrigeration cycle. In oter researces, Yang et al. [19 20] analyzed te combined power and refrigeration cycle by using a zeotropic refrigerant wit different mixture compositions. Te result sowed tat using a 50/50 composition of isobutane/pentane as te maximum exergy efficiency of 7.83%. In anoter study, Yang et al. [21] proposed a novel combined power and ejectorrefrigeration cycle by using te two-stage condensation of a zeotropic mixture. Also, a zeotropic mixture is divided into te power cycle and te ejector refrigeration cycle in different compositions. Te result revealed tat te cycle exergy efficiency acieves a maximum value of 10.29% wit te use of a 40/60 percent composition of isobutane/pentane, and te termal efficiency yields a maximum value of 10.77% wit te use of a 70/30 percent composition of an isobutane/pentane zeotropic mixture. In te current study, te novel cycle is proposed by te integration of a two-stage compression refrigeration cycle wit a combined Rankine power and ejector refrigeration cycle by using te cascade condenser metod. Since te ejector refrigeration cycle cannot produce refrigeration at very low temperatures, te fundamental idea of tis cycle is based on furter refrigeration production at lower temperatures by using te solar energy results in iger termal and exergy efficiencies. Nomenclature mass flow rate (kgs -1 ) entalpy (kjkg -1 )

3 Hamed Mortazavi Beni et al./ Energy Equip. Sys. / Vol. 5/No.3/Sep u P Greek Symbols work rate (kw) flow exergy rate (kw) eat transfer rate (kw) exergy destruction (kw) temperature (ᵒC) velocity (m/s) entropy (kjkg -1 K -1 ) pressure (kpa) exergy efficiency termal efficiency isentropic efficiency µ entrainment ratio Subscripts ambient conditions inlet e outlet out s surface des exergy destruction L cooled environment evap evaporator comp compressor cond condenser expan expansion valve Cas.Cond cascade condenser Se separator is isentropic T turbine B boiler P pump C1 Compressor 1 C2 Compressor 2 n primary nozzle m mixing camber d diffuser w water 2. Cycle description Te proposed cogeneration Rankine power and two-stage compression refrigeration cycle consists of a combined Rankine power and ejector refrigeration cycle and te two-stage compression refrigeration cycle. First, te refrigerant fluid, by taking eat in te steam generator troug te solar collector, and by increasing in temperature and pressure, canges into supereated steam. Usually from water or industrial oils used as primary fluid troug te solar collector absorber. In tis study, primary fluid from te industrial oil Terminol 66 is used in te absorbent collector. Terminol 66 is te world s most popular ig-temperature, liquid-pase eattransfer fluid. Terminol 66 is pumpable at low temperatures and offers termal stability at ig temperatures. Tis oil is used in a wide variety of systems, suc as te production of plastics and polymers, refining, syntetic fiber manufacturing, cemical processing, water purification, solar collectors, and organic Rankine cycle applications. Since tis oil as good stability even at te igest recommended temperature for oil in continuous use in te system, it also as considerable resistance against fouling. Fouling tends to reduce system efficiency and increase costs. Hence, tis oil is suggested for use in solar cycles. Using Terminol 66 as te primary fluid in te solar collectors can easily provide supereated vapor in te generator from te working fluid of te organic Rankine cycle even at temperatures up to 300 C. Te supereated vapor expands troug te turbine to produce power. Te turbine output tat is still supereated vapor is used as te primary flow in te ejector. Te inlet igpressure primary fluid of te ejector passes troug te converging diverging nozzle. Ten, by a vertical sock wave, te pressure energy of te fluid is converted to kinetic energy and te fluid velocity becomes supersonic. Te result of tis process creates a low-pressure area and produces te igvacuum area at te inlet of te ejector secondary fluid tat entrains te secondary fluid into te mixing camber of te ejector. So, te suction of te secondary fluid creates te required pressure drop in te evaporator to evaporate te refrigerant and produce a refrigeration effect. After mixing te primary and secondary flow in te mixing camber troug te constant diameter troat of te ejector, te fluid undergoes anoter sock wave; finally, te pressure of te fluid increases troug te divergent diffuser of te ejector. Te ejector outlet pressure is between te pressure of te primary and secondary flows. In te following step, te refrigerant fluid condensates troug te first condenser. Ten, to complete te processing part, te fluid is pumped into te vapor generator, and te rest of te refrigerant fluid passes troug te expansion valve and is driven to te

4 302 Hamed Mortazavi Beni et al./ Energy Equip. Sys. / Vol. 5/No.3/Sep evaporator. Te cogeneration Rankine power and two-stage compression refrigeration cycle in tis study is started up and operated by solar energy. Figure 1 sows a scematic diagram of te discussed cycle. Te process from te evaporator of te combined power and te ejector refrigeration cycle used as te cascade condenser to te primary condensing of te vapor refrigerant in te two-stage compression refrigeration cycle is sown in Fig. 3. Here, te refrigerant of te two-stage vapor-compression refrigeration cycle passes troug Compressor 1 and increases te pressure driven to te cascade condenser were te primary condensate lies. Te cascade condenser output tat is still in te two-pase mixture of te refrigerant is entered into te vapor liquid separator. Ten, te cascade condenser output mixed wit Flow 16 in te separation and te final composition is te two-pase mixture of te refrigerant. Te saturated vapor refrigerant moves to Compressor 2 for ig-pressure compression. Ten, te secondary condensate in Condenser 2 transforms to te saturated liquid state and after passing troug te expansion valve returns again to te separator. Also, te saturated liquid part of te refrigerant mixture in te separator moves into Expansion Valve 3. It is ten driven to te evaporator for refrigeration production and completion of te cycle. Te use of te two-stage compression tecnique not only elps to reduce te power consumption of te compressors but also, because of te twostage condensation and expansion processes, allows te cycle to produce more refrigeration at lower temperatures. Te following assumptions are made for te simulation of te cycle: 1) All cycle processes are steady-state, steady-flow processes, and te effects of kinetic and potential energy are neglected. Te pressure drop and eat losses in te pipes and system components are negligible. 2) Te condensers and te evaporator outlet state are te intended saturated liquid and saturated vapor, respectively. Te condenser-saturated temperature is considered to be 20 C; according to te source [14], te ambient temperature and pressure are assumed to be 15 C and kpa, respectively. 3) Te condensers eat excangers are considered water cooling and te evaporator eat excanger is considered air cooling. 4) Te flow across te expansion valves is isentalpic. 5) Te ejector flow is steady-state and onedimensional. Te velocity of streams at te inlet and outlet of te ejector is negligible. 6) For simplicity, te effects of te stream losses in te frictional and mixing processes in te nozzle, mixing, and diffuser sections are considered to be te isentropic efficiency of te nozzle, te mixing camber, and te diffuser. Also, te ejector processes are assumed to be adiabatic and do not excange eat wit te environment. 7) Since in comparing te primary flow velocity, te secondary flow velocity is negligible, it is assumed tat te suction process is ideal and witout a pressure drop. Terefore, te mixing process in te mixing camber of te ejector occurs at te suction pressure. It complies wit te laws of conservation of energy and momentum. 3.Simulation Te equations governing on te cycle are conservation of te mass, energy and exergy. In discussed cycle we are dealing wit flow exergy and steady state steady flow processes. Te conservation of mass, energy and exergy are expressed as follows: (1) (2) ( ) (3) In tese equations, denotes entalpy, is te eat transfer rate, is work, and is irreversibility or exergy destruction. In te conservation of exergy, ( ) refers to te eat transfer exergy. Te eat transfer of te control surface is te maximum obtainable work from te transferred termal energy at temperature. Tis term of te exergy balance equation will apply only on devices tat involve eat transfer wit te environment (eat excanger), suc as in an air-cooled evaporator. In te adiabatic

5 Hamed Mortazavi Beni et al./ Energy Equip. Sys. / Vol. 5/No.3/Sep Parabolic Solar Dis Collector Energy Storage Tank 3 way plug valves Oil out Oil in Generator 6 Pump 1 2 Turbine Cooling Water Ejector Condenser 1 Expansion Valve Separator Cascade Condenser Expansion Compressor 1 Valve 2 Compressor Evaporator 18 Expansion Valve 3 Condenser 2 14 Cilled Air Cooling Water Fig 1. Scematic diagram of cogeneration rankine power and two stage compression refrigeration cycle processes, were te eat transfer rate is considered to be zero, suc as in compressors, tis term of te exergy balance equation will be removed. By taking te control volume for every single component of te termal cycle and applying te conservation of mass, energy, and exergy for te various components of te cycle, te equations for te exergy and energy analysis, and te calculation of te exergy destruction of te cycle components can be acieved. According to Fig. 1, tese equations are defined in Table 1 by using Eqs. (1) to (3). is te termo- pysical exergy flow rates of streams, given as: (4) Te isentropic efficiency of te compressors can be defined as a function of te compressor pressure ratio [23]. Te isentropic efficiency of te compressors can be expressed as: (5) were Pi and Po are te compressor suction and discarge pressures, respectively.

6 304 Hamed Mortazavi Beni et al./ Energy Equip. Sys. / Vol. 5/No.3/Sep Table 1. Energy and exergy destruction equations for te various components of te combined cycle Components Boiler Turbine Pump Ejector Condenser 1 Condenser 2 Energy balance,, m oil oil i oil o m W. m T T, s 2 2 3,s W P m 6 1, s Ps, m m m Q m cond Q m cond B Exergy destruction.... I Ex Ex Ex Ex oil, i 1 oil, o 2.. IT Ex 2 Ex 3 WT I Ex Ex W P Ej 6 1 I Ex Ex Ex P I Ex Ex Ex Ex cond 1 4 w, i, c1 5 w, o, c1 I Ex Ex Ex Ex cond 2 14 w,i,c 2 15 w,o,c 2 Cascade condenser Evaporator Separator Expansion valve 1 Expansion valve 2 Expansion valve 3 Compressor 1 Compressor m m Q m evap m m m m W W m C 1 10 m C , s 10 C1, s 14, s 13 C 2, s I Ex Ex Ex Ex CaCo I Ex Ex Q 0 evap evap( 1 ) T L I Ex Ex Ex Ex Se T I expan1 Ex 7 Ex 8 I expan 2 Ex 15 Ex 16 I expan3 Ex 17 Ex 18 I Ex W Ex C1 10 C1 11 I Ex W Ex C2 13 C2 14 Te termal efficiency of te cogeneration Rankine power and two-stage compression refrigeration cycle is expressed as: (6) Here,,, and denote te termal energy rate entered into te cycle, te refrigeration rate produced in te evaporator, and te net work output of te cycle, respectively. Te net work is calculated by subtracting te total power generated in te turbine from te power consumption by te pump and compressors. Te exergy efficiency of te cycle can be expressed as: ( ) (7) Here, is te total exergy input to te cycle. Tis is calculated by summation of te total exergy input into te cycle by te vapor generator and te total exergy entered into te cycle by te pump and te compressors. In fact, te difference between te first and second laws of termodynamics is tat te first law of termodynamic components, suc as pumps and compressors in te termal cycles, are considered as energy consumers, wile from te viewpoint of te second law of termodynamics, tese components are te entry points of te exergy into te cycle. So, te exergy efficiency of te cogeneration Rankine power and two-stage compression refrigeration cycle is calculated by te following equation: (8)

7 Hamed Mortazavi Beni et al./ Energy Equip. Sys. / Vol. 5/No.3/Sep Here, refers to te sum of exergy destruction of te cycle components tat is obtained using te equations given in Table 1. 4.Ejector simulation Te ejector is te key component in te cogeneration Rankine power and two-stage compression refrigeration cycles. So far, different models ave been provided to simulate te ejector. In tis study, te constant-pressure mixing model is used for simulating te ejector performance due to te better and more accurate prediction of tis model. Te basic principle of tis model was presented by Keenan et al. [24] based on gas dynamics. Ten te researc of Huang et al. [23] developed and generalized tis principle [14]. Te ejector simulation algoritm presented in tis study is inspired by te Sarkar algoritm [26]. According to Fig. 2, for te given primary and secondary termodynamic properties of te ejector and by applying te conservation of energy and momentum equations for different processes in te ejector, te output termodynamic properties of te ejector can be calculated. Considering te isentropic efficiency of te nozzle and applying te energy conservation to te ejector s primary nozzle, te entalpy and velocity of te flow can be calculated. (9) (10) Based on Assumption (7), te velocity of te secondary flow after te suction is negligible. Terefore, te entalpy of te secondary flow before and after te suction is equal, and te mixing process is done on te suction pressure, wic means te ejector pressure is equal to te suction pressure. So, te conservation of momentum for te mixing process can be expressed as follows: (11) Te mixing efficiency is: (12) By knowing te velocity of te flow after te mixing process, te energy-conservation equation for te mixing section can be written as: ( ) ( ) (13) Finally, at te diffuser outlet, it can be expressed as: (14) (15) One of te key parameters for te design and simulation of te ejector is te entrainment ratio. Te ejector entrainment ratio is defined as te mass flow ratio of te secondary flow to te primary flow and is given by: (16) Tus, according to te definition of te ejector entrainment ratio, Eq.(11), by using te isentropic efficiency of te mixing process, and Eq. (13) are rewritten as follows: (17) Fig 2. Scematic of te structure and processes in te ejector

8 306 Hamed Mortazavi Beni et al./ Energy Equip. Sys. / Vol. 5/No.3/Sep (18) Start 5.Simulation algoritm and validation A calculating program is written in EES. Te simulation procedure for te energy and exergy analysis of te cycle is as follows: First, Eqs. 5 to 8 are solved, followed by te equations in Table 1. Te termodynamic analysis of te cycle is performed in te EES code format. Te input information required in te simulation of te cycle is suc tat te equations are solved explicitly witout te need for trial and error. But in te ejector modeling, te simulation procedures will be sligtly different. Due to te equations given in te ejector simulation section, tere are two approaces to simulating te ejector. Te first approac is wen te entrainment ratio is given. Here, te equations are solved explicitly. Te second approac is wen te goal is to reac a given pressure in te output of te ejector. In tis case, te equations are solved by trial and error wit an initial value guess for te entrainment ratio to reac te required outlet pressure. Since te saturation temperature of te condenser is constant based on Assumption (2), te pressure of te ejector outlet stream must be equal to te saturation pressure corresponding to te saturation temperature of te condenser, so tat te evaporator back flow does not occur. Terefore, in tis study, te second approac is used. Fig. 3 sows te calculation flowcart used to solve te simulation algoritm proposed for te cogeneration cycle. To ensure te integrity of te software code written in EES and te accuracy of te calculation results obtained from te simulation outlet by EES, first a basic code is written to simulate te Rankine power and ejector refrigeration cycle. Next, te results of te simulation of tis cycle are validated by comparing tis wit te results of Dai et al. [14]. Te comparison results for te turbine power, refrigeration output, and exergy efficiency are sown in Fig. 4. Te results of te simulation matc te results of Dai et al. not only qualitatively [14] but also in numerical terms. Te minor differences in te results can be due to rounding-off errors in te computing process software. Tere may also be sligt differences in te resources and database used to calculate te properties of te refrigerants in te different software programs. No Select Refrigerant & input data: T 2,P 2,P 3,T c,t e,η n,η m,η d,etc. Evaluating flow and equipment properties using equations 1 to 5 & Table 1 Assume μ Solve ejector model equations 9 to 18 Output ejector properties T 4 & P 4 Is P 5-P 4 <ε? Yes Output result η T & η ex equations 6 & 8 Stop Fig 3. A simulation flowcart of te cycle analysis 6.Results and discussion Table 3 sows te results of te energy and exergy analysis of te cogeneration organic Rankine power and two-stage compression refrigeration cycle. In te simulation for a better analysis and understanding of te cycle performance, te input data and main assumptions of te cycle are taken to be te same as in te reference [14]. Tis allows comparing te results of te cogeneration Rankine power and two-stage compression refrigeration cycle wit te results of te conventional combined power and ejector refrigeration cycle. Some assumptions of te parameters are made as listed in Table 2. In te power section and two-stage compression refrigeration section of te cycle refrigerant, R123 and R134a are used respectively.

9 Hamed Mortazavi Beni et al./ Energy Equip. Sys. / Vol. 5/No.3/Sep Turbine power Refrigeration Exergy efficiency Present study Dai et al. [14] Qutput (kw) ex (%) T cond ( C) Fig 4. Validation te results of te turbine power, refrigeration output and exergy efficiency versus condenser temperature Table 2 Main assumptions for te combined cycle Parameter Heat source initial temperature (ºC) Cascade condenser temperature (ºC) Evaporator temperature (ºC) Turbine inlet pressure (kpa) Turbine inlet temperature (ºC) Turbine back pressure (kpa) Turbine isentropic efficiency (%) Pump isentropic efficiency (%) Nozzle efficiency of ejector (%) Mixing efficiency of ejector (%) Diffuser efficiency of ejector (%) Turbine mas flow rate (kg/s) Evaporator mas flow rate(kg/s) Value Table 3 Te results of energy and exergy analysis of te combined cycle Result Turbine work (kw) Pump work (kw) Compressor 1 work (kw) Compressor 2 work (kw) Refrigeration output (kw) Net power output (kw) Net power and refrigeration output (kw) Termal efficiency (%) Exergy efficiency (%) Present study Dai et al. [14]

10 308 Hamed Mortazavi Beni et al./ Energy Equip. Sys. / Vol. 5/No.3/Sep As sown in Table 2, te net work output of te Rankine power and two-stage compression refrigeration cycle is less tan te conventional combined power and ejector refrigeration cycle due to te lack of a compressor in te conventional cycle. Large increases are seen in te refrigeration capacity of te novel cycle, and a significant increase is observed in te termal efficiency and exergy efficiency compared to te conventional cycle. Since te increased refrigeration capacity is muc iger tan te decreased net power output, te termal efficiency as increased. Te increase in te exergy efficiency is due to increases in te net refrigeration exergy output of te cycle and reduction of te exergy destruction by te generator due to lack of a cimney in te generator owing to te use of solar energy. As a key component of te cycle, it is essential to investigate te effect of te ejector entrainment ratio on te termal and exergy efficiency. To do tis, by canging te temperature of te ejector s secondary flow, te ejector entrainment ratio can be canged. By increasing te temperature of te secondary flow, wic is in fact te temperature of te cascade condenser, te secondary flow rate will increase; tus, wit an increase in te secondary flow pressure, te entrainment ratio increases. Figs. 5 and 6 illustrate te effect of te variations of te entrainment ratio on te termal and exergy efficiency at various turbine inlet pressures. Te variation of te secondary flow temperature of te ejector is between 15 C to 5 C By increasing te turbine inlet pressure, te entalpy of te fluid increases and terefore te turbine power output increases. Tis causes an increase in te termal efficiency of te cycle. But by increasing te entrainment ratio in all te turbine inlet pressures, a reduction in te termal efficiency can be seen. Te reason for te decrease of te termal efficiency is tat it increases te Compressor 1 work and te cycle refrigeration capacity decreases as µ increases. Figure 6 sows tat te exergy efficiency increases as te turbine inlet pressure decreases. Tis beavior can be explained wit arguments similar to tose presented for termal efficiency. Also, it can be seen tat te exergy efficiency increases first to a maximum value and ten decreases as te entrainment ratio increases. By increasing te entrainment ratio, te ejector secondary mass flow rate increases. Increasing te secondary mass flow rate will increase te capacity of te cascade condenser, wic causes a reduction of te power consumption and te exergy destruction of te ig-pressure compressor. Terefore, at first, te exergy efficiency increases. But, on te oter side, increasing te secondary mass flow rate increases te exergy destruction by te cascade condenser. Also, by increasing te operating temperature of te cascade condenser, te power consumption and te exergy destruction of te ig-pressure compressor gradually increases. It is suc tat after a specific entrainment ratio, increasing te total exergy destruction as a predominant P Turbine =800 (kpa) P Turbine =810 (kpa) P Turbine =820 (kpa) P Turbine =830 (kpa) t (%) m Fig 5. Effect of te entrainment ratio on te termal efficiency at various turbine inlet pressure

11 Hamed Mortazavi Beni et al./ Energy Equip. Sys. / Vol. 5/No.3/Sep P Turbine =800 (kpa) P Turbine =810 (kpa) P Turbine =820 (kpa) P Turbine =830 (kpa) 39.4 ex (%) m Fig 6. Effect of te entrainment ratio on te exergy efficiency at various turbine inlet pressure effect on reducing te total exergy destruction since ten te exergy efficiency decreases. Figures 7 and 8 sow te effect of variations of te evaporator temperature on te termal and exergy efficiency at various entrainment ratios. Since in practical applications, te ejector refrigeration cycle cannot be used to produce refrigeration at very low temperatures, te ejector secondary flow temperature variations correspond to te considered entrainment ratio canges between 2 C to 5 C. As seen in Fig. 6, for an entrainment ratio more tan 0.1, wic approximately equates to a 5 C temperature for te ejector secondary flow, te exergy efficiency reduces as µ increases. Also, in Fig. 5, it is observed tat by increasing te entrainment ratio te termal efficiency decreases. Tis trend is also evident in Figs. 7 and 8. As sown in Figs. 7 and 8, generally by increasing te entrainment ratio, te termal and exergy efficiency decreases. But wit te increase of te evaporator temperature due to te reduction in te pressure ratio of Compressor 1, te power consumption of tis compressor reduces significantly. In addition, by increasing te evaporator temperature, te refrigeration capacity increases. So, in general, te termal efficiency of te cycle increases as te evaporator temperature increases. In te cogeneration organic Rankine power and two-stage compression refrigeration cycle, te evaporator temperature as a more important effect on te exergy efficiency. Wile te evaporator temperature increases, te low-pressure compressor power consumption and exergy destruction decrease.but tis decline in te power consumption of te low-pressure compressor decreases te net exergy input into te cycle. Also, increasing of te evaporator temperature despite be increased te refrigeration capacity, te quality of refrigeration output of te cycle yields because of te increasing te refrigeration temperature and approacing to te ambient temperature. However, as sown in Fig. 8, at te beginning of increasing te evaporator temperature, te reduction in te exergy destruction by te low-pressure compressor as a dominant influence in te exergy efficiency; so, at first, te exergy efficiency increases. But gradually wit a furter increase in te evaporator temperature, te effect of decreases in te net exergy input into te cycle and te yield of te quality of refrigeration ave a dominant effect on te exergy efficiency. Since ten, tere appears to be a decline in te exergy efficiency. Figure 9 illustrates te effect of te evaporator temperature on te exergy efficiency in comparison wit te termal efficiency at various eat source initial temperatures. Te exergy efficiency beavior can be explained qualitatively wit arguments similar to tose presented for Fig. 8. As sown in Fig. 9, te termal efficiency does not cange wit a variation of te eat source s initial temperature and only one

12 310 Hamed Mortazavi Beni et al./ Energy Equip. Sys. / Vol. 5/No.3/Sep grap is proposed for it. Te reason for tis beavior is because of te termal efficiency only Influenced by te eat flux input to te cycle and production of te net power and refrigeration. So, as long as te inlet eat flux input to te cycle troug te generator is fixed, te termal efficiency remains constant. Tis beavior sows te weakness of te first law of termodynamics in dealing wit te termal cycle. Te exergy efficiency decreases as te eat source s initial temperature increases. An increase in te inlet temperature of Terminol 66 in te generator wile te outlet temperature is fixed causes an increase in te generator temperature difference; terefore, te exergy destruction of te generator increases and te exergy efficiency decreases m=0.157 m=0.191 m=0.257 m=0.312 t (%) T evap ( C) Fig 7. Effect of te evaporator temperature on te termal efficiency at various entrainment ratio m=0.157 m=0.191 m=0.257 m=0.312 ex (%) T evap ( C) Fig 8. Effect of te evaporator temperature on te exergy efficiency at various entrainment ratio

13 Hamed Mortazavi Beni et al./ Energy Equip. Sys. / Vol. 5/No.3/Sep T B =150 ( C) T B =160 ( C) T B =170 ( C) ex (%) t (%) Termal efficiency T evap ( C) Fig 9. Effect of te evaporator temperature on te exergy efficiency in comparison wit te termal efficiency at various eat source initial temperature 7.Conclusion Te energy and exergy analysis of a novel cogeneration organic Rankine power and twostage compression refrigeration cycle was conducted by using EES software. Te results sowed tat te new cycle in te basic operation mode as percent improvement in te termal efficiency and percent improvement in te exergy efficiency compared to te conventional combined power and ejector refrigeration cycle. As observed in te results, because of te existence many components in te cycle, te exergy efficiency is more influenced by te variations of some parameters, suc as te eat source s initial temperature and te turbine inlet pressure, and less influenced by te variations of some oter parameters, suc as te evaporator temperature and te cascade condenser temperature. Even toug te net work output of te cycle is reduced, a significant increase occurs in te refrigeration capacity of te cycle. Te advantages of using tis new cogeneration organic Rankine power and two-stage compression refrigeration cycle includes te iger termal efficiency, te iger exergy efficiency, and increased access to more refrigeration capacity at te lower temperature compared to te conventional combined power and ejector refrigeration cycle. In te conventional ejector refrigeration cycle, refrigeration cannot be acieved at very low cooling temperatures. Te main idea of presenting tis new cycle is based on iger refrigeration production at lower temperatures. Since tis cycle as substantially improved te termal and exergy efficiency, it is recommended to use tis instead of te conventional combined power and ejector refrigeration cycle. References [1] Zang Z., Wang H., Tian L., Huang C., Termodynamic Analysis of Double- Compression Flas Intercooling Transcritical CO2 Refrigeration Cycle, Te Journal of Supercritical Fluids (2016)109: [2] Li H., Cao F., Bu X., Wang L., Wang X., Performance Caracteristics of R1234yf Ejector-Expansion Refrigeration Cycle, Applied Energy (2014)121: [3] Wang F., Li D.Y., Zou Y., Analysis for te Ejector Used as Expansion Valve in Vapor Compression Refrigeration Cycle, Applied Termal Engineering (2016) 96: [4] Lawrence N., Elbel S., Teoretical and Practical Comparison of Two-Pase Ejector Refrigeration Cycles Including First and Second Law analysis, International Journal of Refrigeration (2013)36: [5] Zang Z., Tong L., Cang L., Cen Y., Wang X., Energetic and Exergetic Analysis of an Ejector-Expansion Refrigeration Cycle Using te Working Fluid R32, Entropy (2015) 17: [6] Elgendy E., Parametric Study of a Vapor Compression Refrigeration Cycle Using a

14 312 Hamed Mortazavi Beni et al./ Energy Equip. Sys. / Vol. 5/No.3/Sep Two-Pase Constant Area Ejector, International Journal of Mecanical, Aerospace, Industrial, Mecatronic and Manufacturing Engineering (2013) 7. [7] Xing M., Yan G., Yu J., Performance Evaluation of an Ejector Subcooled Vapor-Compression Refrigeration Cycle, Energy Conversion and Management, (2015)92: [8] Wang X., Yu J., Zou M., Lv X., Comparative Studies of Ejector- Expansion Vapor Compression Refrigeration Cycles for Applications in Domestic Refrigerator-Freezers, Energy, (2014)70: [9] Zu Y., Jiang P., Hybrid Vapor Compression Refrigeration System wit an Integrated Ejector Cooling Cycle, Applied Energy (2012) 35: [10] Cen J., Havtun H., Palm B., Parametric Analysis of Ejector Working Caracteristics in te Refrigeration System, Applied Termal Engineering (2014)69: [11] Sorouradin A., Saberi A., Mamoudi S.M., Development of New Model to Prediction te Performance of Ejector Refrigeration Cycle, Modares Mecanical Engineering (2012)12: [12] Adrian G., Dobrovicescu A., Grosu L., Cerna E., Energy and Exergy Analysis of an Ejector Refrigeration System, U.P.B. Sci. Bull (2013)75. [13] Lontsi F., Hamandjoda O., Mayi O.T., Kemajou A., Development and Performance Analysis of a Multi- Temperature Combined Compression/Ejection Refrigeration Cycle Using Environment Friendly Refrigerants, International Journal of Refrigeration (2016)69: [14] Dai Y., Wang J., Gao L., Exergy Analysis, Parametric Analysis and Optimization for a Novel Combined Power and Ejector Refrigeration Cycle, Applied Termal Engineering (2005) 29: ,. [15] Zeng B., Weng Y.W., A Combined Power and Ejector Refrigeration Cycle for Low Temperature Heat Source, Solar Energy (2010) 84: [16] Habibzade A., Rasidi M.M., Galanis N., Analysis of a Combined Power and Ejector Refrigeration Cycle Using Low Temperature Heat, Energy Conversion and Management (2013) 65: [17] Wang J., Dai Y., Sun Z., A Teoretical Study on a Novel Combined Power and Ejector Refrigeration Cycle, International Journal of Refrigeration (2009)32: [18] Kim, K., Han C., Kim S., Ko H., Performance Analysis of a Combined Power and Ejector Refrigeration Cycle for Different Working Fluids ", International Journal of Mining, Metallurgy & Mecanical Engineering (2013) 1. [19] Yang X., Zao L., Li H., Yu Z., Teoretical Analysis of a Combined Power and Ejector Refrigeration Cycle Using Zeotropic Mixture, Applied Energy (2015) 160: [20] Yang X., Zao L., Termodynamic Analysis of a Combined Power and Ejector Refrigeration Cycle Using Zeotropic Mixtures, Energy Procedia (2015) 75: [21] Yang X., Zeng N., Zao L., Deng S., Li H., Yu Z., Analysis of a Novel Combined Power and Ejector- Refrigeration Cycle, Energy Conversion and Management (2016) 108: [22] Dincer I., Rosen M. A., Exergy, Energy, Environment and Sustainable Development, Elsevier (2007). [23] Brunin O., Feidt M., Hivet B., Comparison of te Working Domains of Some Compression Heat Pumps and a Compression-Absorption Heat Pump, International Journal of Refrigeration (1997)20: [24] Keenan H., Neumann E.P., Lustwerk F., An Investigation of Ejector Design by Analysis and Experiment, Journal of Applied Mecanics Transactions of te ASME (1950)72: [25] Huang B.J., Cang J.M., Wang C.P., Petrenko V.A., A 1-D Analysis of Ejector Performance, International Journal of Refrigeration (1999) 22: [26] Sarkar J., Performance Caracteristics of Natural-Refrigerants Based Ejector Expansion Refrigeration Cycles, Journal of Power and Energy (2009)223:

( h) ( ) Effect of Boiler Pressure (Using Molliar Diagram i.e., h-s diagram) We have, but W P << W T. = = h h h h

( h) ( ) Effect of Boiler Pressure (Using Molliar Diagram i.e., h-s diagram) We have, but W P << W T. = = h h h h Effect of Boiler Pressure (Using Molliar Diagram i.e., -s diagram) We ave, ( 3 ) ( 4 ) η t but W P P > P for te fixed

More information

Chapter 11 Power and Refrigeration Systems

Chapter 11 Power and Refrigeration Systems Capter 11 Power and Refrigeration Systems Cycle : working fluid undergoes a series of processes and finally ly returns to te initial state (ex. Steam power plant,cf)internal-combustion combustion engine)

More information

A 1-D analysis of ejector performance. Analyse unidimensionnelle de la performance d un éjecteur

A 1-D analysis of ejector performance. Analyse unidimensionnelle de la performance d un éjecteur International Journal of Refrigeration (1999) 354 364 A 1-D analysis of ejector performance B.J. Huang*, J.M. Cang, C.P. Wang, V.A. Petrenko Department of Mecanical Engineering, National Taiwan University,

More information

COMPARATIVE ANALYSES OF TWO IMPROVED CO 2 COMBINED COOLING, HEATING, AND POWER SYSTEMS DRIVEN BY SOLAR ENERGY

COMPARATIVE ANALYSES OF TWO IMPROVED CO 2 COMBINED COOLING, HEATING, AND POWER SYSTEMS DRIVEN BY SOLAR ENERGY S93 Introduction COMPARATIVE ANALYSES OF TWO IMPROVED CO 2 COMBINED COOLING, HEATING, AND POWER SYSTEMS DRIVEN BY SOLAR ENERGY by Wanjin BAI a* and Xiaoxiao XU b a School of Mechanical and Vehicle Engineering,

More information

Enhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis

Enhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2006 Enhancement of CO2 Refrigeration Cycle Using an Ejector: 1D Analysis Elias

More information

Effect of Suction Nozzle Pressure Drop on the Performance of an Ejector-Expansion Transcritical CO 2 Refrigeration Cycle

Effect of Suction Nozzle Pressure Drop on the Performance of an Ejector-Expansion Transcritical CO 2 Refrigeration Cycle Entropy 2014, 16, 4309-4321; doi:10.3390/e16084309 Article OPEN ACCESS entropy ISSN 1099-4300 www.mdpi.com/journal/entropy Effect of Suction Nozzle Pressure Drop on the Performance of an Ejector-Expansion

More information

Optimized geothermal binary power cycles

Optimized geothermal binary power cycles Optimized geotermal binary power cycles Kontoleontos E., Mendrinos D., Karytsas C. Centre for Renewable Energy Sources, 9t km Maratonos ave., 9009 Pikermi Attikis, Greece ABSTRACT Tis study as been carried

More information

Thermodynamic Modeling and Exergy Analysis of a Heat Recovery System in Meshkinshahr Geothermal Power Plant, Iran

Thermodynamic Modeling and Exergy Analysis of a Heat Recovery System in Meshkinshahr Geothermal Power Plant, Iran Proceedings orld Geotermal Congress 2010 Bali, Indonesia, 25-29 April 2010 Termodynamic Modeling and xergy Analysis of a Heat Recovery System in Meskinsar Geotermal Power Plant, Iran Benam Radmer 1, Sajjad

More information

Recap: Greenhouse Effect

Recap: Greenhouse Effect Recap: Greenouse Effect Relies on fact tat glass (or plastic) is transparent to visible radiation but opaque to infra-red (IR) radiation. E,g. Car window closed visible radiation only transmitted. Car

More information

Conventional Paper I Determine time required in minutes for a 50mm diameter steel sphere

Conventional Paper I Determine time required in minutes for a 50mm diameter steel sphere Conventional aper I-04. (a) Give reasons wy te Carnot cycle cannot be considered as te teoretical cycle for steam power plants even toug its efficiency is te igest for te given eat source and sink temperatures.

More information

ANALYSIS OF ALTERNATIVES FOR GAS TURBINES INLET AIR COOLING

ANALYSIS OF ALTERNATIVES FOR GAS TURBINES INLET AIR COOLING ANALYSIS OF ALTERNATIVES FOR GAS TURBINES INLET AIR COOLING Waldir Guirardi, Maua Institute of Tecnology Praça Mauá 01, 09580-900 S. Caetano do Sul, SP, Brasil Pone: +55 11 4239-3401 Fax: +55 11 4239-3041

More information

A Thermal Analysis and Optimization of a Combined Cycle by Several Technologies

A Thermal Analysis and Optimization of a Combined Cycle by Several Technologies American Journal of Energy Researc, 2014, Vol. 2, No. 2, 5-41 Available online at ttp://pubs.sciepub.com/ajer/2/2/ Science and Education Publising DOI:10.12691/ajer-2-2- A ermal Analysis and Optimization

More information

- 2 - SME Q1. (a) Briefly explain how the following methods used in a gas-turbine power plant increase the thermal efficiency:

- 2 - SME Q1. (a) Briefly explain how the following methods used in a gas-turbine power plant increase the thermal efficiency: - 2 - Q1. (a) Briefly explain how the following methods used in a gas-turbine power plant increase the thermal efficiency: i) regenerator ii) intercooling between compressors (6 marks) (b) Air enters a

More information

ANALYSIS OF REFRIGERATION CYCLE PERFORMANCE WITH AN EJECTOR

ANALYSIS OF REFRIGERATION CYCLE PERFORMANCE WITH AN EJECTOR 000 (06) DOI:.5/ matecconf/067000 ICMER 05 ANALYSIS OF REFRIGERATION CYCLE PERFORMANCE WITH AN EJECTOR Wani J. R., Aklilu T. Baheta,a, Abraham D. Woldeyohannes, and Suhaimi Hassan Department of Mechanical

More information

Development of Lithium Bromide-Water Absorption Heat Pump System for Simultaneous Production of Heated-up Air and Steam From Waste Heat

Development of Lithium Bromide-Water Absorption Heat Pump System for Simultaneous Production of Heated-up Air and Steam From Waste Heat HEFT214 1 t International Conference on Heat Transfer, Fluid Mecanics and Termodynamics 14 16 July 214 Orlando, Florida Development of Litium Bromide-Water bsorption Heat Pump System for Simultaneous Production

More information

Design Optimization of a Hybrid Solar-Geothermal Power Plant

Design Optimization of a Hybrid Solar-Geothermal Power Plant Design Optimization of a Hybrid Solar- Power Plant Hybrid Solar Power plant Rafika Maali 1 *,Taar Kir 2, Ammar Ben Braim 1 1 Researc Unit Applied Termodynamic UR11ES8, Cemical Engeerg Processes /National

More information

Geothermal Energy For Residential Co-Generation

Geothermal Energy For Residential Co-Generation Geotermal Energy For Residential Co-Generation COROIU Miaela PD student Electrical Engineering Faculty, Tecnical University of Cluj-Napoca, Romania Energy Efficiency Director Energobit S.A. Cluj-Napoca,

More information

Second Law Analysis of a Carbon Dioxide Transcritical Power System in Low-grade Heat Source Recovery

Second Law Analysis of a Carbon Dioxide Transcritical Power System in Low-grade Heat Source Recovery Second Law Analysis of a Carbon Dioxide Transcritical Power System in Low-grade Heat Source Recovery Y. Chen, Almaz Bitew Workie, Per Lundqvist Div. of Applied Thermodynamics and Refrigeration, Department

More information

Parametric Study of a Vapor Compression Refrigeration Cycle Using a Two-Phase Constant Area Ejector

Parametric Study of a Vapor Compression Refrigeration Cycle Using a Two-Phase Constant Area Ejector Vol:7, No:, 01 Parametric Study of a Vapor Compression Refrigeration Cycle Using a Two-Phase Constant Area Ejector E. Elgendy International Science Index, Mechanical and Mechatronics Engineering Vol:7,

More information

MODELING THERMODYNAMIC ANALYSIS AND SIMULATION OF ORGANIC RANKINE CYCLE USING GEOTHERMAL ENERGY AS HEAT SOURCE

MODELING THERMODYNAMIC ANALYSIS AND SIMULATION OF ORGANIC RANKINE CYCLE USING GEOTHERMAL ENERGY AS HEAT SOURCE MODELING THERMODYNAMIC ANALYSIS AND SIMULATION OF ORGANIC RANKINE CYCLE USING GEOTHERMAL ENERGY AS HEAT SOURCE Colak L.* and Bahadir T. *Author for correspondence Department of Mechanical Engineering,

More information

The effect of operating temperature on the performance of Molten Carbonate Fuel Cell systems

The effect of operating temperature on the performance of Molten Carbonate Fuel Cell systems Te effect of operating temperature on te performance of Molten Carbonate Fuel Cell systems A. Musa, H.J. Steeman, M. De aepe (Department of Flow, Heat and Combustion Mecanics, Gent University- UGent, Sint-ietersnieuwstraat

More information

Supersonic Nozzle Flow in the Two-Phase Ejector as Water Refrigeration System by Using Waste Heat

Supersonic Nozzle Flow in the Two-Phase Ejector as Water Refrigeration System by Using Waste Heat HEFAT2012 9 th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics 16 18 July 2012 Malta Supersonic Nozzle Flow in the Two-Phase Ejector as Water Refrigeration System by Using

More information

HPC 2017 Performance simulation and exergy analysis on multi-stage compression high temperature heat pumps with R1234ze(Z) refrigerant

HPC 2017 Performance simulation and exergy analysis on multi-stage compression high temperature heat pumps with R1234ze(Z) refrigerant Performance simulation and exergy analysis on multi-stage compression high temperature heat pumps with R1234ze(Z) refrigerant Bin Hu, Di Wu, R.Z. Wang Institute of Refrigeration and Cryogenics Shanghai

More information

K.S. Rawat 1, H. Khulve 2, A.K. Pratihar 3 1,3 Department of Mechanical Engineering, GBPUAT, Pantnagar , India

K.S. Rawat 1, H. Khulve 2, A.K. Pratihar 3 1,3 Department of Mechanical Engineering, GBPUAT, Pantnagar , India Thermodynamic Analysis of Combined ORC-VCR System Using Low Grade Thermal Energy K.S. Rawat 1, H. Khulve 2, A.K. Pratihar 3 1,3 Department of Mechanical Engineering, GBPUAT, Pantnagar-263145, India 2 Department

More information

Copyright 2012 Neal D. Lawrence

Copyright 2012 Neal D. Lawrence Copyright 2012 Neal D. Lawrence ANALYTICAL AND EXPERIMENTAL INVESTIGATION OF TWO-PHASE EJECTOR CYCLES USING LOW-PRESSURE REFRIGERANTS BY NEAL D. LAWRENCE THESIS Submitted in partial fulfillment of the

More information

Effect of Generator, Condenser and Evaporator Temperature on the Performance of Ejector Refrigeration System (ERS)

Effect of Generator, Condenser and Evaporator Temperature on the Performance of Ejector Refrigeration System (ERS) Journal of Basic and Applied Engineering Research pp. 4-9 Krishi Sanskriti Publications http://www.krishisanskriti.org/jbaer.html Effect of Generator, Condenser and Evaporator Temperature on the Performance

More information

Study on Ejector - Vapor Compression Hybrid Air Conditioning System Using Solar Energy

Study on Ejector - Vapor Compression Hybrid Air Conditioning System Using Solar Energy Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 202 Study on Ejector - Vapor Compression Hybrid Air Conditioning System Using

More information

MEEG 346 Thermal Laboratory

MEEG 346 Thermal Laboratory MEEG 346 Termal Laboratory Experiment #4: Te Four-Stroke Combustion Engine Introduction Small engines are used in many applications. Tey are used to power motorcycles, lawnmowers, go-carts, and even small

More information

Chapter 9: Vapor Power Systems

Chapter 9: Vapor Power Systems Chapter 9: Vapor Power Systems Table of Contents Introduction... 2 Analyzing the Rankine Cycle... 4 Rankine Cycle Performance Parameters... 5 Ideal Rankine Cycle... 6 Example... 7 Rankine Cycle Including

More information

A Review to Increase Productive Output of An Active Solar Distillation System

A Review to Increase Productive Output of An Active Solar Distillation System A Revi to Increase Productive Output of An Active Solar Distillation System UMANG R SONI 1, Dr. P.K.BRAHMBHATT 2, HEMANT B PATEL 1P.d Student, Department of Mecanical Engineering, PAHER, Udaipur, Rajastan,

More information

CHAPTER 1 BASIC CONCEPTS

CHAPTER 1 BASIC CONCEPTS GTU Paper Analysis CHAPTER 1 BASIC CONCEPTS Sr. No. Questions Jan 15 Jun 15 Dec 15 May 16 Jan 17 Jun 17 Nov 17 May 18 Differentiate between the followings; 1) Intensive properties and extensive properties,

More information

Revue des Energies Renouvelables Spécial ICT3-MENA Bou Ismail (2015) Numerical study of a single effect ejector-absorption cooling system

Revue des Energies Renouvelables Spécial ICT3-MENA Bou Ismail (2015) Numerical study of a single effect ejector-absorption cooling system Revue des Energies Renouvelables Spécial ICT3-MENA Bou Ismail (2015) 71-77 Numerical study of a single effect ejector-absorption cooling system D. Sioud 1*, M. Bourouis 2 et A. Bellagi 1 1 Unité de Recherche

More information

A NOVEL INTEGRATED ENERGY SYSTEM OF SOLAR POWER, HEAT PUMPS AND AI-EV (AIR-CONDITIONER ELECTRIC VEHICLE)

A NOVEL INTEGRATED ENERGY SYSTEM OF SOLAR POWER, HEAT PUMPS AND AI-EV (AIR-CONDITIONER ELECTRIC VEHICLE) t International Conference on Heat Transfer, Fluid Mecanics and Termodynamics HEFAT6 t International Conference on Heat Transfer, Fluid Mecanics and Termodynamics July 6 Malaga, Spain A NOVEL INTEGRATED

More information

Dual Source Solar Powered Combined-Cycle Multi-Temperature Refrigeration System for Cold Production in the Context of Off-Grid and Rural Energy Access

Dual Source Solar Powered Combined-Cycle Multi-Temperature Refrigeration System for Cold Production in the Context of Off-Grid and Rural Energy Access International Journal of Thermal Technologies E-ISSN 2277 4114 2017 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijtt/ Research Article Dual Source Solar Powered Combined-Cycle

More information

BOD 5 removal kinetics and wastewater flow pattern of stabilization pond system in Birjand

BOD 5 removal kinetics and wastewater flow pattern of stabilization pond system in Birjand vailable online at www.pelagiaresearclibrary.com European Journal of Experimental Biology, 2013, 3(2):430-436 ISSN: 2248 9215 CODEN (US): EJEBU BOD 5 removal kinetics and wastewater flow pattern of stabilization

More information

Experimentation on Pool Boiling With Sodium Dodecyl Sulfate

Experimentation on Pool Boiling With Sodium Dodecyl Sulfate International Journal of Engineering Researc and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 12, Issue 12 (December 2016), PP.45-53 Experimentation on Pool Boiling Wit Sodium

More information

ME ENGINEERING THERMODYNAMICS UNIT III QUESTION BANK SVCET

ME ENGINEERING THERMODYNAMICS UNIT III QUESTION BANK SVCET 1. A vessel of volume 0.04m 3 contains a mixture of saturated water and steam at a temperature of 250 0 C. The mass of the liquid present is 9 kg. Find the pressure, mass, specific volume, enthalpy, entropy

More information

During my career spanning over

During my career spanning over P (PSIA) METERING DEVICE SAT. LIQUID CONDENSER EVAPORATOR H (BTU / LB) SAT. VAPOR COMPRESSOR Some Misconcetions about te Refrigeration Cycle And ow use of te ressure/entaly diagram can el clear suc doubts

More information

R13. II B. Tech I Semester Regular/Supplementary Examinations, Oct/Nov THERMODYNAMICS (Com. to ME, AE, AME) Time: 3 hours Max.

R13. II B. Tech I Semester Regular/Supplementary Examinations, Oct/Nov THERMODYNAMICS (Com. to ME, AE, AME) Time: 3 hours Max. SET - 1 1. a) Discuss about PMM I and PMM II b) Explain about Quasi static process. c) Show that the COP of a heat pump is greater than the COP of a refrigerator by unity. d) What is steam quality? What

More information

Determining Dryness Fraction

Determining Dryness Fraction Determining Dryness Fraction SUPERHEATED EVAPORATION 100 C WATER LINE 0 C g Temperature/Entalpy Dryness Fraction Tis andout assumes te student is amiliar wit Steam Tables and te terms ound terein. I required,

More information

Open Access The Current Situation and Development of Fire Resistance Design for Steel Structures in China

Open Access The Current Situation and Development of Fire Resistance Design for Steel Structures in China Te Open Construction and Building Tecnology Journal, 010, 4, 55-63 55 Open Access Te Current Situation and Development of Fire Resistance Design for Steel Structures in Cina Jinceng Zao* and Xiuying Yang

More information

Introduction of Prediction Method of Welding Deformation by Using Laminated Beam Modeling Theory and Its Application to Railway Rolling Stock

Introduction of Prediction Method of Welding Deformation by Using Laminated Beam Modeling Theory and Its Application to Railway Rolling Stock IJR International Journal of Railway Vol., No. 4 / December 009, pp. 175-179 Introduction of Prediction Metod of Welding Deformation by Using Laminated Beam Modeling Teory and Its Application to Railway

More information

Energy and Buildings

Energy and Buildings Energy and Buildings 41 (009) 175 181 Contents lists available at ScienceDirect Energy and Buildings journal homepage: www.elsevier.com/locate/enbuild Modeling solar-driven ejector refrigeration system

More information

Eng Thermodynamics I: Sample Final Exam Questions 1

Eng Thermodynamics I: Sample Final Exam Questions 1 Eng3901 - Thermodynamics I: Sample Final Exam Questions 1 The final exam in Eng3901 - Thermodynamics I consists of four questions: (1) 1st Law analysis of a steam power cycle, or a vapour compression refrigeration

More information

Chapter 8. Vapor Power Systems

Chapter 8. Vapor Power Systems Chapter 8 Vapor Power Systems Introducing Power Generation To meet our national power needs there are challenges related to Declining economically recoverable supplies of nonrenewable energy resources.

More information

Problems in chapter 9 CB Thermodynamics

Problems in chapter 9 CB Thermodynamics Problems in chapter 9 CB Thermodynamics 9-82 Air is used as the working fluid in a simple ideal Brayton cycle that has a pressure ratio of 12, a compressor inlet temperature of 300 K, and a turbine inlet

More information

PARAMETRIC STUDY OF GAS TURBINE CYCLE COUPLED WITH VAPOR COMPRESSION REFRIGERATION CYCLE FOR INTAKE AIR COOLING

PARAMETRIC STUDY OF GAS TURBINE CYCLE COUPLED WITH VAPOR COMPRESSION REFRIGERATION CYCLE FOR INTAKE AIR COOLING International Journal of Mechanical Engineering and Technology (IJMET) Volume 9, Issue 9, September 2018, pp. 248 261, Article ID: IJMET_09_09_029 Available online at http://www.iaeme.com/ijmet/issues.asp?jtype=ijmet&vtype=9&itype=9

More information

Indirect Evaporative cooling systems: modelling and performance analysis

Indirect Evaporative cooling systems: modelling and performance analysis Available online at www.sciencedirect.com ScienceDirect Energy Procedia 140 (2017) 475 485 www.elsevier.com/locate/procedia AiCARR 50t International Congress; Beyond NZEB Buildings, 10-11 May 2017, Matera,

More information

AREN 2110: Thermodynamics Spring 2010 Homework 7: Due Friday, March 12, 6 PM

AREN 2110: Thermodynamics Spring 2010 Homework 7: Due Friday, March 12, 6 PM AREN 2110: Thermodynamics Spring 2010 Homework 7: Due Friday, March 12, 6 PM 1. Answer the following by circling the BEST answer. 1) The boundary work associated with a constant volume process is always

More information

Investigations of N 2 O Transcritical Refrigeration Cycle Using Dedicated Mechanical Subcooling. Sanjeev Kumar 1 and Dr. D.K.

Investigations of N 2 O Transcritical Refrigeration Cycle Using Dedicated Mechanical Subcooling. Sanjeev Kumar 1 and Dr. D.K. e t International Journal on Emerging Technologies (Special Issue NCETST-2017) 8(1): 340-344(2017) (Published by Research Trend, Website: www.researchtrend.net) ISSN No. (Print) : 0975-8364 ISSN No. (Online)

More information

Solar Absorption Refrigeration System Using New Working Fluid Pairs

Solar Absorption Refrigeration System Using New Working Fluid Pairs INERNAIONAL JOURNAL OF ENERGY, Issue, Vol., Solar Absorption Refrigeration Syste Using New Working Fluid Pairs Jasi M. Abdulateef, Kaaruzzaan Sopian, M. A. Algoul, Mod Yusof Sulaian, Azai Zaari and Ibrai

More information

The Exergy Analysis Of Gas Cooler In CO 2 Heat Pump System

The Exergy Analysis Of Gas Cooler In CO 2 Heat Pump System Available onle at www.sciencedirect.com Procedia Environmental Sciences 11 (211 1555 156 e Exergy Analysis Of Gas Cooler In CO 2 Heat Pump System Ygbai Xie a, Zicao Wang b, Kuikui Cui c, Xuedong Zang d

More information

The Manufacture and Test of (110) Orientated Silicon Based Micro Heat Exchanger

The Manufacture and Test of (110) Orientated Silicon Based Micro Heat Exchanger Tamkang Journal of Science and Engineering, Vol. 5, No. 3, pp. 129-136 (2002) 129 Te Manufacture and Test of (110) Orientated Silicon Based Micro Heat Excanger Sung-Wen Kang, Yu-Tang Cen and Guang-Sang

More information

Using Matrix to Solving the Probabilistic Inventory Models (Demand Model)

Using Matrix to Solving the Probabilistic Inventory Models (Demand Model) IAAST ONLINE ISSN 77-1565 PRINT ISSN 0976-488 CODEN: IAASCA International Arcive of Applied Sciences and Tecnology IAAST; Vol 4 [3] September 013: 09-15 01 Society of Education, India [ISO9001: 008 Certified

More information

Chapter 10 POWER CYCLES. Department of Mechanical Engineering

Chapter 10 POWER CYCLES. Department of Mechanical Engineering Chapter 10 VAPOR AND COMBINED POWER CYCLES Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University it 2 Objectives Analyze vapor power cycles in which h the working fluid is alternately

More information

Analysis of a Two Phase Flow Ejector for the Transcritical CO 2 Cycle

Analysis of a Two Phase Flow Ejector for the Transcritical CO 2 Cycle 3, Page Analysis of a Two Phase Flow Ejector for the Transcritical CO Cycle Fang LIU *, Eckhard A. GROLL Purdue University, School of Mechanical Engineering, West Lafayette, IN, USA Tel: 765-494-03, Fax:

More information

Nonconventional Technologies Review no. 3/2009

Nonconventional Technologies Review no. 3/2009 Nonconventional Tecnologies Review no. /2009 CONSTRUCTIVE AND FUNCTIONAL UPGRADING OPPORTUNITIES FOR THE HEAT SECTION FROM UNIVERSITY OF ORADEA Cercetător ştiințific III Cristian VANCEA, Centrul de cercetări

More information

Improvement of distillation column efficiency by integration with organic Rankine power generation cycle. Introduction

Improvement of distillation column efficiency by integration with organic Rankine power generation cycle. Introduction Improvement of distillation column efficiency by integration with organic Rankine power generation cycle Dmitriy A. Sladkovskiy, St.Petersburg State Institute of Technology (technical university), Saint-

More information

Energy analysis and performance evaluation of a novel multi-evaporator ejector refrigeration cycle (ERC)

Energy analysis and performance evaluation of a novel multi-evaporator ejector refrigeration cycle (ERC) Research Article Journal of Energy Management and Technology (JEMT) Vol. 1, Issue 2 38 Energy analysis and performance evaluation of a novel multi-evaporator ejector refrigeration cycle (ERC) MOHAMMAD

More information

Parametric Study of a Double Effect Absorption Refrigeration System

Parametric Study of a Double Effect Absorption Refrigeration System Parametric Study of a Double Effect Absorption Refrigeration System 1 Abbas Alpaslan KOCER, 2 Murat OZTURK 1 Uluborlu Selahattin Karasoy Vocational School, Suleyman Demirel University, 32260, Isparta Turkey,

More information

Chapter 10 VAPOR AND COMBINED POWER CYCLES

Chapter 10 VAPOR AND COMBINED POWER CYCLES Thermodynamics: An Engineering Approach, 6 th Edition Yunus A. Cengel, Michael A. Boles McGraw-Hill, 2008 Chapter 10 VAPOR AND COMBINED POWER CYCLES Copyright The McGraw-Hill Companies, Inc. Permission

More information

Energy and Exergy Analysis of Combined Ejector-Absorption Refrigeration System

Energy and Exergy Analysis of Combined Ejector-Absorption Refrigeration System Energy and Exergy Analysis of Combined Ejector- Seyed Reza Fakheri 1, Hadi Kargar Sharif Abad 2, Hossein Sakhaii Nia 3 1 M.A Student, Azad University of Science and Research of Semnan, Mechanics College,

More information

Compound ejectors with improved off-design performance

Compound ejectors with improved off-design performance Compound ejectors with improved off-design performance Dr M. Dennis 1, Dr K. Garzoli 2 1,2 Centre for Sustainable Energy Systems School of Engineering The Australian National University Canberra, ACT 0200

More information

EXTRA CREDIT OPPORTUNITY: Due end of day, Thursday, Dec. 14

EXTRA CREDIT OPPORTUNITY: Due end of day, Thursday, Dec. 14 EXRA CREDI OPPORUNIY: Due end of day, hursday, Dec. 4 his extra credit set of questions is an opportunity to improve your test scores (including an insurance policy for your final exam grade). here are

More information

Faculty of Engineering 2 nd year 2016 Mechanical Engineering Dep. Final-exam (code: M 1222)

Faculty of Engineering 2 nd year 2016 Mechanical Engineering Dep. Final-exam (code: M 1222) Benha University Thermodynamics II Faculty of Engineering 2 nd year 2016 Mechanical Engineering Dep. Final-exam (code: M 1222) Time: Three Hours (attempt all questions) (assume any missing data) Question1

More information

Chapter 10. In Chap. 9 we discussed gas power cycles for which the VAPOR AND COMBINED POWER CYCLES. Objectives

Chapter 10. In Chap. 9 we discussed gas power cycles for which the VAPOR AND COMBINED POWER CYCLES. Objectives Chapter 0 VAPOR AND COMBINED POWER CYCLES In Chap. 9 we discussed gas power cycles for which the working fluid remains a gas throughout the entire cycle. In this chapter, we consider vapor power cycles

More information

Chapter 10. In Chap. 9 we discussed gas power cycles for which the VAPOR AND COMBINED POWER CYCLES. Objectives

Chapter 10. In Chap. 9 we discussed gas power cycles for which the VAPOR AND COMBINED POWER CYCLES. Objectives Chapter 0 VAPOR AND COMBINED POWER CYCLES In Chap. 9 we discussed gas power cycles for which the working fluid remains a gas throughout the entire cycle. In this chapter, we consider vapor power cycles

More information

Modeling of the Seawater Greenhouse Systems

Modeling of the Seawater Greenhouse Systems Modeling of te Seawater Greenouse Systems M. Amidpour Associate Professor Head of epartment of Energy System Engineering K.N.oosi University of ecnology, eran, Iran amidpour@gmail.com G.R. Salei P.. Student

More information

A Study on Pendulum Seismic Isolators for High-Rise Buildings

A Study on Pendulum Seismic Isolators for High-Rise Buildings ctbu.org/papers Title: Autors: Subjects: Keywords: A Study on Pendulum Seismic Isolators for Hig-Rise Buildings Ikuo Tatemici, Maeda Corp. Mamoru Kawaguci, Kawaguci & Engineers Masaru Abe, Hosei University

More information

COEFFICIENT OF PERFORMANCE OF TWO PHASE CONDENSING EJECTOR REFRIGERATION SYSTEM WITH R-22

COEFFICIENT OF PERFORMANCE OF TWO PHASE CONDENSING EJECTOR REFRIGERATION SYSTEM WITH R-22 INTERNATIONAL JOURNAL OF RESEARCH IN COMPUTER APPLICATIONS AND ROBOTICS ISSN 2320-7345 COEFFICIENT OF PERFORMANCE OF TWO PHASE CONDENSING EJECTOR REFRIGERATION SYSTEM WITH R-22 Kuldip Kumar 1, Anjani Kumar

More information

W t. Strategy: We need to step through the equipments and figure out the inlets and outlets to allow us to calculate the work and heat terms.

W t. Strategy: We need to step through the equipments and figure out the inlets and outlets to allow us to calculate the work and heat terms. Problem et G 10.1 olution pring 00 YT ) A schematic of the Rankine cycle and representation on a T- diagram: 1 Boiler P 0 W p pump 0 P 0 Condenser turbine 0 4 C 475 o C Depends on your last name. The information

More information

a. The power required to drive the compressor; b. The inlet and output pipe cross-sectional area. [Ans: kw, m 2 ] [3.34, R. K.

a. The power required to drive the compressor; b. The inlet and output pipe cross-sectional area. [Ans: kw, m 2 ] [3.34, R. K. CHAPTER 2 - FIRST LAW OF THERMODYNAMICS 1. At the inlet to a certain nozzle the enthalpy of fluid passing is 2800 kj/kg, and the velocity is 50 m/s. At the discharge end the enthalpy is 2600 kj/kg. The

More information

UNIVERSITY OF TORONTO FACULTY OF APPLIED SCIENCE AND ENGINEERING FINAL EXAMINATION, DECEMBER 2008 MIE 411H1 F - THERMAL ENERGY CONVERSION

UNIVERSITY OF TORONTO FACULTY OF APPLIED SCIENCE AND ENGINEERING FINAL EXAMINATION, DECEMBER 2008 MIE 411H1 F - THERMAL ENERGY CONVERSION UNIVERSITY OF TORONTO FACULTY OF APPLIED SCIENCE AND ENGINEERING FINAL EXAMINATION, DECEMBER 2008 MIE 411H1 F - THERMAL ENERGY CONVERSION Exam Type: X Examiner: J.S. Wallace You may use your copy of the

More information

Lecture No.1. Vapour Power Cycles

Lecture No.1. Vapour Power Cycles Lecture No.1 1.1 INTRODUCTION Thermodynamic cycles can be primarily classified based on their utility such as for power generation, refrigeration etc. Based on this thermodynamic cycles can be categorized

More information

Solar Cooling Using Variable Geometry Ejectors

Solar Cooling Using Variable Geometry Ejectors Solar Cooling Using Variable Geometry Ejectors M. Dennis Centre for Sustainable Energy Systems Department of Engineering The Australian National University Canberra, ACT 2 AUSTRALIA E-mail:Mike.Dennis@anu.edu.au

More information

S.E. (Mechanical) (First Semester) EXAMINATION, 2012 APPLIED THERMODYNAMICS (2008 PATTERN) Time : Three Hours Maximum Marks : 100

S.E. (Mechanical) (First Semester) EXAMINATION, 2012 APPLIED THERMODYNAMICS (2008 PATTERN) Time : Three Hours Maximum Marks : 100 Total No. of Questions 12] [Total No. of Printed Pages 8 Seat No. [4162]-111 S.E. (Mechanical) (First Semester) EXAMINATION, 2012 APPLIED THERMODYNAMICS (2008 PATTERN) Time : Three Hours Maximum Marks

More information

MCE535 Thermal Power and Propulsive Systems. Lecture 04: 04/10/2017

MCE535 Thermal Power and Propulsive Systems. Lecture 04: 04/10/2017 MCE535 Thermal Power and Propulsive Systems Lecture 04: 04/10/2017 Dr. Ayokunle O. Balogun (A212) balogun.ayokunle@lmu.edu.ng Class: Thursday (3 5 pm) Etiquettes and MOP Attendance is a requirement. There

More information

COMPARISON OF FINNED TUBE AND PLATE-FINNED HEAT EXCHANGERS IN WASTE HEAT RECOVERY

COMPARISON OF FINNED TUBE AND PLATE-FINNED HEAT EXCHANGERS IN WASTE HEAT RECOVERY Mario olik Marija Živić Zdravko Virag Antun Barac ttps://doi.org/10.178/tof.4si101 ISSN 1333-114 eissn 1849-1391 OMPARISON OF FINNED TUBE AND PLATE-FINNED EAT EXANGERS IN WASTE EAT REOVERY Summary Te use

More information

Chapter 1 STEAM CYCLES

Chapter 1 STEAM CYCLES Chapter 1 STEAM CYCLES Assoc. Prof. Dr. Mazlan Abdul Wahid Faculty of Mechanical Engineering Universiti Teknologi Malaysia www.fkm.utm.my/~mazlan 1 Chapter 1 STEAM CYCLES 1 Chapter Objectives To carry

More information

Optimization of New 25A-size Metal Gasket Design Based on Contact Width Considering Forming and Contact Stress Effect

Optimization of New 25A-size Metal Gasket Design Based on Contact Width Considering Forming and Contact Stress Effect World Academy of Science, Engineering and Tecnology International Journal of Mecanical, Aerospace, Industrial, Mecatronic and Manufacturing Engineering Vol:6, No:3, 2012 Optimization of New 25A-size Metal

More information

CHAPTER 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES

CHAPTER 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES Thermodynamics: An Engineering Approach 8th Edition in SI Units Yunus A. Ç engel, Michael A. Boles McGraw-Hill, 2015 CHAPTER 5 MASS AND ENERGY ANALYSIS OF CONTROL VOLUMES Objectives Develop the conservation

More information

A Review on Performance of Air Conditioning System using Two Phase Ejector

A Review on Performance of Air Conditioning System using Two Phase Ejector International Journal of Current Engineering and Technology E-ISSN 2277 4106, P-ISSN 2347 5161 2016 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article A Review

More information

Exergy analysis of a flat plate solar collector

Exergy analysis of a flat plate solar collector Exergy analysis of a flat plate solar collector Sunil Chamoli GRDIMT Dehradun, Uttarakhand, India Abstract In this study, exergetic performance analysis of flat plate solar collector has been carried out

More information

Numerical study on the electrical performance of photovoltaic panel with passive cooling of natural ventilation

Numerical study on the electrical performance of photovoltaic panel with passive cooling of natural ventilation International Journal o Smart Grid and Clean Energy Numerical study on te electrical perormance o potovoltaic panel wit passive cooling o natural ventilation Hongbing Cen *, Xilin Cen, Sizuo Li, Hanwan

More information

Effect Weibull Distribution Parameters Calculating Methods on Energy Output of a Wind Turbine: A Study Case

Effect Weibull Distribution Parameters Calculating Methods on Energy Output of a Wind Turbine: A Study Case Int. J. of Termal & Environmental Engineering Volume 14, No. 2 (2017) 163-173 Effect Weibull Distribution Parameters Calculating Metods on Energy Output of a Wind Turbine: Study Case beer Qawasmi, Suil

More information

Prime mover sizing for base-loaded combined heating and power systems

Prime mover sizing for base-loaded combined heating and power systems 17 Prime mover sizing for base-loaded combined eating and power systems P J Mago* and R Luck Department of Mecanical Engineering, Mississippi State University, Mississippi, USA Te manuscript was received

More information

Thermodynamic Analysis of Organic Rankine Cycle using Different Working Fluids

Thermodynamic Analysis of Organic Rankine Cycle using Different Working Fluids Thermodynamic Analysis of Organic Rankine Cycle using Different Working Fluids Jayaram Bhat 1, G.L. Arunkumar 2 Deapartment of mechanical engineering, NMIT Bangalore Abstract ORC (Organic Rankine Cycle)

More information

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 03 Issue: 08 Aug p-issn:

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 03 Issue: 08 Aug p-issn: Thermodynamic analysis and comparison of various organic fluids for ORC in Gas turbine-organic Rankine combined cycle plant with solar reheating and regeneration of ORC fluid Dr. R.S. Mishra 1, Dharmendra

More information

Thermodynamic Analysis of District Heating System Assisted by Geothermal Sourced Heat Pump

Thermodynamic Analysis of District Heating System Assisted by Geothermal Sourced Heat Pump Thermodynamic Analysis of District Heating System Assisted by Geothermal Sourced Heat Pump Halit ARAT*, Merve SENTURK ACAR** and Oguz ARSLAN* * Mechanical Engineering Department ** Electricity and Energy

More information

Practice Final Exam (A) Six problems. (Open-book, HW solutions, and notes) (Plus /minus 10 % error acceptable for all numerical answers)

Practice Final Exam (A) Six problems. (Open-book, HW solutions, and notes) (Plus /minus 10 % error acceptable for all numerical answers) ME 3610 Practice Final Exam (A) Six problems. (Open-book, HW solutions, and notes) (Plus /minus 10 % error acceptable for all numerical answers) (18 points) 1. A gasoline engine operating on the ideal

More information

Melt Pool Size Control in Thin-Walled and Bulky Parts via Process Maps

Melt Pool Size Control in Thin-Walled and Bulky Parts via Process Maps Melt Pool Size Control in Tin-Walled and Bulky Parts via Process Maps Aditad Vasinonta, Jack L. Beut and Raymond Ong Department of Mecanical Engineering Carnegie Mellon University Pittsburg, PA 15213 Abstract

More information

Performance Analysis of a Combined Power and Ejector Refrigeration Cycle for Different Working Fluids

Performance Analysis of a Combined Power and Ejector Refrigeration Cycle for Different Working Fluids International Journal of Mining, Metallurgy & Mechanical Engineering (IJMMME) Volume 1, Issue (13) ISSN 23-42; EISSN 23-46 Performance Analysis of a Combined Power and Ejector Refrigeration Cycle for Different

More information

Application of Viper Energy Recovery Expansion Device in Transcritical Carbon Dioxide Refrigeration Cycle

Application of Viper Energy Recovery Expansion Device in Transcritical Carbon Dioxide Refrigeration Cycle Abstract Application of Viper Energy Recovery Expansion Device in Transcritical Carbon Dioxide Refrigeration Cycle Riley B. Barta a *, Eckhard A. Groll b a Purdue University, School of Mechanical Engineering,

More information

FEE, CTU in Prague Power Engineering 2 (BE5B15EN2) Exercise 3

FEE, CTU in Prague Power Engineering 2 (BE5B15EN2) Exercise 3 Example 1: How is the applied heat for 1 kg of water steam at constant pressure p = 1.47 MPa, if the dryness of wet water is increased from x 1 = 0.8 to x 2 = 0.96? Dryness of wet steam the ratio of steam

More information

Modelling and Simulation of Solar-Biomass Hybrid Trigeneration using ORC-VCC

Modelling and Simulation of Solar-Biomass Hybrid Trigeneration using ORC-VCC Modelling and Simulation of Solar-Biomass Hybrid Trigeneration using ORC-VCC Dr. Kamal Kishore Khatri 1, M. Sai Praneeth 2 1 Associate Professor and Head, 2 Undergraduate student, Mechanical Engineering

More information

Mitigating autogenous shrinkage of hardening concrete

Mitigating autogenous shrinkage of hardening concrete Mitigating autogenous srinkage of ardening concrete H.W.M. van der Ham, E.A.B. Koenders & K. van Breugel Delft University of Tecnology, Delft, Neterlands ABSTRACT: Te probability of early age cracking

More information

Exergetic Sensitivity Analysis of ORC Geothermal Power Plant Considering Ambient Temperature

Exergetic Sensitivity Analysis of ORC Geothermal Power Plant Considering Ambient Temperature GRC Transactions, Vol. 40, 2016 Exergetic Sensitivity Analysis of ORC Geothermal Power Plant Considering Ambient Temperature Saeid Mohammadzadeh Bina, Saeid Jalilinasrabady, and Hikari Fujii Graduate School

More information