1 COOLING LOADS AND OCCUPANT COMFORT IN HIGHLY GLAZED BUILDINGS AND THE EFFECTIVE EVALUATION OF WINDOW RETROFITS S. Armstrong ABSTRACT Urban centres contain thousands of mid to late 20th century commercial, institutional, and multi-unit residential buildings. In order to improve the efficiency of these buildings and reduce an ever-increasing infrastructure demand, our modern cities must face the retrofit imperative. Of course, it s not as simple as just installing insulation, window films, or extra sealant there are many challenges when evaluating building envelope retrofits. These challenges include obtaining reliable performance improvement information and determining realistic savings. This cannot be stressed enough: determining realistic savings is essential. We are often asked to evaluate various envelope upgrade measures, either as a standalone project or as part of a more holistic existing building commissioning (or re-commissioning) project. It doesn t take long to realize that finding accurate information on which improvements provide the best value is tough but accurate information is critical to the project s success. Equally critical is the need to understand the impetus for the upgrades: are occupants to hot? too cold? is there air leakage? water infiltration? The reason alters the approach and solution considerably. A recent example which highlights some of the challenges of evaluating envelope retrofits involved assessing the anticipated cooling load reduction with a post-applied solar heat gain control system for an office building in downtown Toronto. The project included an analysis of building energy use, in-situ monitoring of preand post-retrofit temperatures, in-situ heat gain monitoring, and energy cost savings calculations. The motivating factors: occupant comfort and energy savings. OBJECTIVE To determine an effective means for improving occupant comfort and achieving energy savings through post-applied solar control measures using in-situ monitoring of temperatures and solar energy gains and performing energy savings calculations. BACKGROUND One recent example where we encountered some of the challenges of evaluating envelope retrofits involved determining whether a reasonable retrofit solution existed for reducing solar load on an existing office building in downtown Toronto. The motivating factors: occupant comfort and energy savings. Our evaluation initially comprised a high-level analysis of possible retrofit options for controlling solar loads. The options considered included: active and passive exterior and interior shades and interior and exterior-applied window films. Our evaluation did not include solar heat gain through non-vision areas and did not consider the thermal resistance of vision or non-vision elements. 341

2 Existing Glazing Configuration The solar control for the existing vision lites comprises heat absorbing green-tinted float glass (heat strengthened) on the outer lite and a low-emissivity coating on the outer surface of the inner lite (surface #3). Based on the building s age, the low-e coating on the existing vision lites likely is a pyrolitic (hard coat) treatment, which has relatively low performance compared to modern sputter (soft coat) low-e treatments. For example, pyrolitic coatings have higher solar heat gain and u-values than sputter coatings. Pyrolitic coatings also have lower light-to-solar gain (LSG) values than sputter coatings, which means that for a given visible light transmittance a pyrolitic coating has a higher solar heat gain. While some buildings may benefit from higher solar heat gain, highly-glazed commercial office buildings rarely are in this category. The building has also had several units replaced over its service life, which comprise a green-tinted outer lite and sputter-coat low-e treatment similar in appearance to the original vision lite (i.e. green-tinted outer lite with high visible light transmittance and low outward reflectivity) but with a higher performance. The replacement units also comprise two lites of heat strengthened glass for improved durability. We calculated the solar heat gain co-efficient (SHGC) for the existing and replacement units by constructing the glazing unit in Optic5 (simulation software). Based on this simulation, we estimate the SHGC for the original glazing units to be approximately 0.70 and the SHGC for the replacement units to be approximately We estimate that approximately 10% of the original windows have been replaced as part of ongoing life-cycle replacement requirements. We calculated the vision-to-spandrel area for the building on each elevation and determined that the vision area (glass) comprises approximately 75-80% of the total wall area on occupied floors. The glazing is also quite clear in its appearance: the green tinted outer lite and low-e coatings on the inner lite do not greatly reduce the clarity of the glass or increase its reflectivity. This combination of a high ratio of vision to opaque (spandrel) area and visually clear glass results in high levels of daylighting and solar heat gain while providing views into the building from the exterior. Good daylighting of tenant spaces and clear views in and out of buildings are desirable characteristics in commercial office buildings; however, excess daylighting and solar heat gain can be the source of tenant discomfort. In the subject building, the owner had received numerous complaints of overheating (or undercooling) at the perimeter spaces over a prolonged period of time. These complaints were the impetus for the investigative program discussed herein. Based on the parameters of maintaining clear views, retaining good daylighting, and reducing solar heat gain, we investigated several retrofit strategies: exterior shades, interior shades, and retrofit window film. Exterior shades The most effective means of controlling solar heat gain is by blocking it before it strikes the façade. This can be achieved with exterior-applied shading systems designed to completely block incident solar radiation or designed to block a significant portion of incident solar radiation while maintaining desirable daylighting and views. Exterior shade systems can be simple, fixed blade elements or complex, fully integrated, solar tracking mechanisms that optimize shading effectiveness based on climatic conditions. All buildings must be evaluated on an individual basis and, for some, exterior-mounted shades may be part of a larger re-visioning or re-branding strategy; for others, they may be seen as detrimental to the aesthetic merits of an existing building. The architectural prominence of the subject property eliminated the possibility of deploying an exterior shading solution and, as such, we did not conduct an analysis of the performance 342

3 of this measure. However, the data presented in this paper still provides valuable insight into the possible savings from such systems. Interior shades The subject property has varying existing shade systems. At a minimum, the building is outfitted with horizontal mini blinds on all windows; additionally, some spaces have light-reducing fabric shades. Retrofitting the existing system to include automatic blind control devices and optional links to photosensitive lighting systems would provide the most significant improvement over the current strategy. Automatic blind and lighting control systems can react quickly and efficiently to the amount of incoming sunlight and these systems have the potential to reduce the energy consumption for lighting in office buildings by up to 30-80% (Galasiu, A. D., 2003). By casual observation, one can identify how manual shades provide sub-optimal performance: occupants may not be present in the room or may react too late to the high solar gain, resulting in sub-optimal performance; sun angle, temporary cloud cover, and time of day make the manual adjustment of shading to the ideal position difficult, and; solar heat gain is permitted to entering the occupied zone and is trapped near the glass. Look at any mid- or high-rise building in your neighbourhood no two shades are adjusted alike and many buildings look like a patchwork quilt. Upgrading the existing building and installing an integrated system to benefit from daylight harvesting would have required replacing all of the existing blinds and upgrading the lighting system to include dimmable ballasts, which would be very costly. Thus, further evaluation of this approach was abandoned. Window Films Window films can reduce solar heat gain by a significant amount, which, in highly glazed buildings, can improve occupant comfort by reducing the amount of direct gain experienced by occupants in perimeter zones. For example, ¼ clear glazing with a window film featuring ceramic technology can have a SHGC in the range of 0.41 to 0.53, compared to an original SHGC of 0.86 (Source: 3M, Ceramic Product Family Literature). Unfortunately, the effect of this solar heat gain reduction on cooling load is not as straightforward cooling loads in buildings with deep floor plates typically are driven by high internal loads (occupants, computers, equipment, etc.) and less by perimeter solar heat gain loads whereas cooling loads in buildings with shallow floor plates tend to be influenced more by solar heat gain. Without understanding how much solar heat gain impacts a building s cooling loads, the potential savings can be overstated. With approximately 80% glazing, a significant Architectural presence, and existing interior shades, the subject building seemed an ideal candidate for window film. Films can be visually clear or provide a range of options for modifying the reflective or tint qualities of glass. Thus, a window film retrofit was analysed in detail and is the subject of this paper. PROGRAM To determine the effectiveness of window film for addressing occupant comfort and reducing cooling costs, we conducted space temperature and thermal energy (BTU) transmission monitoring in two locations for a total of 16 days. The monitoring was performed during September 20 through October 5. The ambient outdoor temperature during this time ranged from daytime highs of 10.2 to 24.7 deg C and overnight lows of 5 to 18.4 deg C (Source: Environment Canada). Space temperature data was collected for 10 days prior to the film installation to develop a baseline and for 6 days after the film installation. Two simultaneous 343

4 temperature collection points were recorded using a HOBO U temperature relative humidity data logger with a single exterior temperature probe: one sensor was placed approximately 1 from the interior surface of the glass (perimeter zone) and one sensor was placed approximately 10 from the interior surface of the glass (interior zone). The sensor in the perimeter zone was approximately 8 above the floor and the sensor in the interior zone was approximately 5 above the floor (PHOTO 1). The sensors were placed at the south west corner of the building and both the horizontal mini blinds and the fabric shades were left in an open position for the duration of the test. The thermal energy transmission monitoring was conducted over a three day period using TES 1333R Solar Power Meter data loggers. Three data loggers were used simultaneously: one placed directly behind an untreated glazing unit and one placed behind each of the two film mock-up areas within the study area. In all cases, the thermal energy loggers were placed facing south and angled approximately 10 degrees above horizontal. The thermal energy monitoring was performed during the final three (3) days of the 16-day temperature monitoring period and after the retrofit film was installed. The monitored days coincided with high solar heat gain days (i.e. clear, sunny sky conditions), which may slightly overestimate the energy savings from reduced solar heat gain since cloudy days were not included in the test period. PHOTO 1: VIEW OF SPACE TEMPERATURE AND THERMAL ENERGY TRANSMISSION MONITORING SET-UP. Window Films We selected two window films for the study: 3M CM40 and CM50. These films were chosen based on their high solar energy rejection, visual clarity, and minimal interior reflection. The CM40 has a slightly lower visible light transmittance (VLT) compared to the CM50, which was selected as one of the options to help reduce glare. In addition to tenant concerns regarding overheating, glare was identified by the owner as an ongoing concern. While interior-applied windows films reject heat from the occupied space, this heat is absorbed both by the inner lite and the air space. Thus, it is important to consider glazing size and durability when selecting an interior-applied window film. Too aggressive a film (i.e. too much heat rejection) could result in breakage if the units are a certain size or if they comprise regular float glass. Solar Condition We developed a solar condition index (FIGURE 1) to identify whether a correlation exists between weather, sky condition, and solar heat gain. The solar condition index was developed using Environment Canada daily weather data and assigning a graduated scale to various sky conditions as follows: 344

5 We found a strong correlation between the solar condition index and space temperature data. For example, when the solar condition rating was 5 (or high), the interior space temperature at the glass and was high. Conversely, when the solar condition rating was lower, the interior space temperature at the glass (perimeter zone) was lower. This correlation helps support our understanding of solar heat gain on space temperatures in the perimeter zone. FIGURE 1: SOLAR CONDITION INDEX INDICATING THE RANGE OF ANTICIPATED SOLAR RADIATION BASED ON SKY CONDITION FOR THE DURATION OF THE STUDY. 345

6 Limitations The methodology was developed to obtain data which would assist in developing a meaningful conclusion pertaining to the impact of solar control film on space conditions. The study was restricted to three windows in a single area of an occupied open office area at the south west corner of the building on the 8 th floor. We were unable to measure directly the amount of cooling demand for the mock-up areas. The HVAC system and BAS were also incapable of measuring the amount of air delivered to the specific mock-up areas. It is our opinion that this type of direct monitoring of space cooling demand may provide additional data indicating whether a reduction in space cooling demand resulted in the mock-up areas. RESULTS Space Temperature Monitoring The space temperature monitoring data developed demonstrates that the temperature differential between the perimeter and interior zones decreased by between 0.8 (CM40) and 1 deg C (CM50) after the film was installed (FIGURE 2). This narrowing of space temperature differential occurred despite similar solar conditions (high solar heat gain) before and after the film installation. This narrowing of the space temperature differential between perimeter and interior zones could result in improved occupant comfort since cooling is delivered in response to interior zone space temperatures (i.e. the perimeter zone will be closer in temperature to the interior zone). 346

7 Thermal Energy Transmission The thermal energy transmission data indicates a reduction in energy transmission ranging between 38% and 45% depending on the film deployed (FIGURE 3). The fluctuations in thermal energy transmission correlated well with the fluctuations in temperature data and the solar condition index. 347

8 FIGURE 3: BTU ENERGY MONITORING SHOWING A COMPARISON BETWEEN THE EXISTING GLAZING AND TWO SAMPLES WITH RETROFIT WINDOW FILM INSTALLED. Energy Analysis The determination of potential savings as a result of installing solar control film is based on the above data collection and analysis as well as the conclusions resulting from an energy audit and existing building commissioning exercise conducted by our firm at the same building. Based on this energy audit, we obtained the following pertinent information: 1. The building is operating on a district energy cooling system, which means that approximately 50% of the total cooling costs are fixed and unrelated to actual consumption due to weather. 2. The consumption-related cooling costs are approximately $113,000 per year; the fixed cooling costs (unrelated to consumption) are approximately $95,000 per year; 3. Approximately 20% of the building s cooling load is attributable to weather, or $22,000 per year (based on consumption-related cooling costs of $113,000 per year) with the remaining load attributable to internal sources (people, lighting, computers, etc.); 4. The cooling costs are not significantly impacted by peak cooling demand, and; 5. Electrical consumption generally is unaffected by weather. A separate analysis was conducted of the district energy system billing method; however, that has been excluded for simplicity. Based on our research, solar heat gain is responsible for approximately 16% of typical large commercial office building cooling loads (Huang, J. 1999, pg 39) for buildings in climate zones similar to the subject building. The buildings included in the cited study had vision glazing in the range of 40-50% compared to 348

9 the approximately 80% vision glazing in the subject building. Due to the high percentage of glazing on the subject building, we conservatively estimate that solar heat gain contributes to approximately 40% of the total weather-related cooling loads, as summarized in TABLE 1. TABLE 1: SOLAR HEAT GAIN RELATED COOLING ENERGY CALCULATION. Based on the above assumptions, we prepared an estimate of the savings to be obtained by installing the solar control film using three methods. Note that calculations are based on the assumption that uniform savings or load reductions can be anticipated across all solar exposures. In reality, the effect will be more pronounced on areas with the highest solar exposure, which suggest that a targeted retrofit program may be most economical. Method 1: SHGC improvement The solar heat gain coefficient (SHGC) of the existing window units was compared to the SHGC of the improved windows with the solar control film installed. In order to determine the SHGC for the existing windows, we assumed that 10% of the glazing units have been replaced with newer units. To determine a baseline SHGC for the existing windows, we created a weighted average between the original and replacement units, resulting in a baseline SHGC of This baseline was compared against the improved windows with a SHGC of to calculate the potential savings (TABLE 2). TABLE 2: ESTIMATED COOLING ENERGY SAVINGS ($) AS A FUNCTION OF SOLAR HEAT GAIN MITIGATION. Method 2: BTU energy reduction The BTU energy transmission reduction obtained from the on-site monitoring was used to estimate the potential energy cost savings. The BTU reduction is measured using the most effective of the three films tested (TABLE 3). TABLE 3: ESTIMATED COOLING ENERGY SAVINGS ($) AS A FUNCTION OF BTU REDUCTION. 349

10 Method 3: Building Energy Modeling We created a representative building energy model based on the geometry of the subject building using EE-4 to identify potential cooling energy savings and heating energy cost increases. The window-to-wall ratio of the subject building was used as was building orientation and floor area. Based on this simulation, the peak cooling load decrease was insignificant and the total cooling load was offset completely by the heating consumption increase due to reduced winter free-heating. The following is a summary of the modeling results: Peak cooling reduction: 1 kw Cooling consumption reduction: 2,980 kwh/floor or $298/floor based on current building energy costs Heating consumption increase: 1,060 m3 of natural gas/floor or $371/floor based on current building energy costs Net energy savings: -$72/floor/year (i.e. net energy cost increase) Based on our assessment, the window film installation could not be justified on a simple payback resulting from cooling energy savings. The simple payback for a whole-building window film retrofit is in excess of 65 years based on the most optimistic energy savings. CONCLUSION Based on research, observations, data collection, and analysis, it appears that occupant comfort will be positively affected by installing a solar control window film on the interior surface of the glazing even if significant cooling energy savings aren t realized. The temperature differential between the interior and perimeter zone was reduced by installing the film in both test areas. The moderating of space temperature at the building perimeter should result in more consistent temperature control across the floor, leading to greater occupant comfort. The solar control film also reduced total solar heat entering the building, which would reduce the same radiant heat gain experienced by occupants sitting close to the exterior walls. The window film provides these benefits regardless of how occupants adjust their existing blinds or install additional interior shade systems. The window film also has minimal impact on the building s aesthetics, unlike the installation of an exterior shade structure. Although glare was not identified as a primary concern by occupants, glare was visibly reduced after installing the solar control film, particularly with the CM40. This observation was supported by anecdotal feedback from tenants in the immediate area of the test installation. It is conceivable that the solar control film and resultant solar heat gain and glare reduction will result in occupants keeping the base building and tenant shade systems in an open position during a greater portion of the day. At present, the lighting system is not capable of dimming in response to effective daylighting; however, effective glare control can facilitate this type of upgrade at a later date when the lighting system is due for a major upgrade. Based on our assessment of the potential energy savings from the window film installation, it was apparent that the film installation cannot be justified on a simple payback (in excess of 65 years) based on the most optimistic energy savings. Lastly, as with all solar heat gain reduction strategies, there will be a corresponding increase in heating energy consumption to account for the lost solar heat gain. In cooling-dominated buildings, the heating energy consumption increase typically is lower than the cooling energy consumption decrease, resulting in overall lower energy costs. 350

11 Based on the lessons learned during this study, we recommended that the decision to install a solar control film should be justified by its ability to improve occupant comfort resulting from reduced heat gain and glare. There will be some energy savings; however, this will is not the driving factor. Of course, all buildings are unique and those with shallower floor plates, less internal heat load, or higher solar heat gain may present a different scenario. REFERENCES Galasiu, A. D. Energy performance of daylight-linked automatic lighting control systems in large atrium spaces: report on two field-monitored case studies. Energy and Buildings, vol 35, M. Ceramic Product Family < evtsessssss &fn=ceramic%20family%20card_ > Environment Canada. Daily Data Report for 2011 < &dlyrange= &Year=2011&Month=9&cmdB1=Go#> Huang, Joe and Francioni, Ellen Commercial Heating and Cooling Loads Component Analysis. Lawrence Berkeley National Laboratory,

Assessing the energy performance of modern glass facade systems

Assessing the energy performance of modern glass facade systems Assessing the energy performance of modern glass facade systems Abdelsalam Aldawoud * Architectural Engineering Department, University of Sharjah Sharjah, United Arab Emirates Abstract. The design and

More information

COMPARATIVE EVALUATION OF SIDE-DAYLIGHTING STRATEGIES

COMPARATIVE EVALUATION OF SIDE-DAYLIGHTING STRATEGIES COMPARATIVE EVALUATION OF SIDE-DAYLIGHTING STRATEGIES Michael J. Holtz, FAIA LightLouver LLC 685 S. Arthur Avenue Louisville, Colorado 80027 mholtz@lightlouver.com Zack Rogers, PE, IESNA LightLouver LLC

More information

IMPROVING THE HUMAN EXPERIENCE IN THE BUILT ENVIRONMENT

IMPROVING THE HUMAN EXPERIENCE IN THE BUILT ENVIRONMENT IMPROVING THE HUMAN EXPERIENCE IN THE BUILT ENVIRONMENT SageGlass tints automatically to control daylight and solar heat, making it easier for architects to design sustainable, visually compelling buildings

More information

Effect of Building Orientation and Window Glazing on the Energy Consumption of HVAC System of an Office Building for Different Climate Zones

Effect of Building Orientation and Window Glazing on the Energy Consumption of HVAC System of an Office Building for Different Climate Zones Effect of Building Orientation and Window Glazing on the Energy Consumption of HVAC System of an Office Building for Different Climate Zones Maya Yeshwanth Pai Dept. of Electrical & Electronics Engineering

More information

Glazing Alternatives

Glazing Alternatives Glazing Alternatives Background / Goals When initially investigating the current glazing system used in the building, it became apparent that for sustainability purposes, the most efficient glazing type

More information

Selecting Energy Efficient New Windows in Illinois

Selecting Energy Efficient New Windows in Illinois Selecting Energy Efficient New Windows in Illinois www.efficientwindows.org January 016 ENERGY STAR Zones 1. Meet the Energy Code & Look for the ENERGY STAR Windows must comply with your local energy code.

More information

Selecting Energy Efficient New Windows in Tennessee

Selecting Energy Efficient New Windows in Tennessee Selecting Energy Efficient New Windows in Tennessee www.efficientwindows.org January 06 STAR Zones. Meet the Energy Code & Look for the STAR Windows must comply with your local energy code. Windows that

More information

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates

Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates Modelling Analysis of Thermal Performance of Internal Shading Devices for a Commercial Atrium Building in Tropical Climates Kittitach Pichatwatana, and Fan Wang Abstract This paper examines the TAS computer

More information

Selecting Energy Efficient Replacement Windows in Arizona

Selecting Energy Efficient Replacement Windows in Arizona Selecting Energy Efficient Replacement Windows in Arizona www.efficientwindows.org January 016 ENERGY STAR Zones 1. Meet the Energy Code & Look for the ENERGY STAR Windows must comply with your local energy

More information

Selecting Energy Efficient New Windows in Nevada

Selecting Energy Efficient New Windows in Nevada Selecting Energy Efficient New Windows in Nevada www.efficientwindows.org January 06 STAR Zones. Meet the Energy Code & Look for the STAR Windows must comply with your local energy code. Windows that are

More information

Modeling Energy Consumption Effects of Glazing

Modeling Energy Consumption Effects of Glazing Modeling Energy Consumption Effects of Glazing Daniel Lu 12/7/2012 Table of Contents Introduction... 3 Design Options... 5 Option 1... 5 Option 2... 5 Preliminary Energy Simulation... 7 Objectives... 7

More information

Table Type U-factor SHGC Single pane clear single pane tint double pane clear double pane tint

Table Type U-factor SHGC Single pane clear single pane tint double pane clear double pane tint Construction Management Breadth Florida codes for maximum U-values and Solar Heat Gain Characteristics of different types of glass are located in Table 13-601.1 of the Florida Building Code: Table 13-601.1

More information

Daylight Harvesting in Tropic

Daylight Harvesting in Tropic Daylight Harvesting in Tropic Daylight space when done right is much nicer environment than electrically lit spaces. Efficacy lm/watt Daylight is Cool & Free 280 Luminous Efficacy 280 230 180 130 80 30

More information

Introduction to basics of energy efficient building design

Introduction to basics of energy efficient building design Introduction to basics of energy efficient building design Pierre Jaboyedoff Seminar on Energy Efficient & Thermally Comfortable Buildings in Amravati For CRDA, Andhra Pradesh May 2 nd 2017 Indo-Swiss

More information

An Experimental Study for the Evaluation of the Environmental Performance by the Application of the Automated Venetian Blind

An Experimental Study for the Evaluation of the Environmental Performance by the Application of the Automated Venetian Blind An Experimental Study for the Evaluation of the Environmental Performance by the Application of the Automated Venetian Blind Ji-Hyun Kim 1, Kyoung-Wn Yang 1, Young-Joon Park 1, Kyung-Hee Lee 2, Myoung-Souk

More information

ADVANCED FAÇADES AND HVAC SYSTEMS: PRELIMINARY RESULTS OF FULL-SCALE MONITORING

ADVANCED FAÇADES AND HVAC SYSTEMS: PRELIMINARY RESULTS OF FULL-SCALE MONITORING ADVANCED FAÇADES AND HVAC SYSTEMS: PRELIMINARY RESULTS OF FULL-SCALE MONITORING M. Kragh, M. Colombari and M. Zobec Permasteelisa Group, Research & Engineering, 31020 San Vendemiano (TV), Italy www.permasteelisa.com,

More information

SageGlass. SageGlass Product Guide. Dynamic glass for a changing world

SageGlass. SageGlass Product Guide. Dynamic glass for a changing world SageGlass Dynamic glass for a changing world SageGlass Product Guide Ultra-efficient SageGlass provides unmatched performance and proven reliability in commercial, institutional and residential buildings

More information

European Timber Windows & Doors

European Timber Windows & Doors European Timber Windows & Doors Providers of Passivhaus building performance solutions Passive House Pty Ltd 7-9 Raglan St North Melbourne VIC p 03 9329 3693 e info@passivehouse.com.au Building Thermal

More information

Energy loss through glazing (windows) is the largest and most variable loss in buildings and has major implications on energy consumption and peak

Energy loss through glazing (windows) is the largest and most variable loss in buildings and has major implications on energy consumption and peak Energy loss through glazing (windows) is the largest and most variable loss in buildings and has major implications on energy consumption and peak heating and cooling loads 2009 Buildings Industry Data

More information

Inflector Solar Shades Radiant Heat Barrier

Inflector Solar Shades Radiant Heat Barrier Inflector Solar Shades Radiant Heat Barrier www.inflectoraustralia.com.au Inflector Solar Shades Developed from NASA technology WHAT ARE INFLECTOR SOLAR SHADES? Inflector Solar Shades are a unique, energy

More information

Designing for thermal comfort near a glazed exterior wall. * School of Engineering, Auckland University of Technology, Auckland, New Zealand

Designing for thermal comfort near a glazed exterior wall. * School of Engineering, Auckland University of Technology, Auckland, New Zealand Designing for thermal comfort near a glazed exterior wall T.N. Anderson ǂ *, M.B. Luther ** * School of Engineering, Auckland University of Technology, Auckland, New Zealand ** School of Architecture and

More information

Iv. Absolute Towers, Ontario, Canada Architect: Yansong Ma

Iv. Absolute Towers, Ontario, Canada Architect: Yansong Ma Iv. BRANDS and products 2. Glazing Architectural 2.0 Introduction 130 2.1 Low-emissivity Glass 133 2.1.1 Hard-Coat 134 energy Select 73 134 2.1.2 Soft-Coat 136 energy Select 63 137 energy Select R42 139

More information

Selecting Energy Efficient Replacement Windows in Florida

Selecting Energy Efficient Replacement Windows in Florida Selecting Energy Efficient Replacement Windows in Florida www.efficientwindows.org January 06 Zones. Meet the Energy Code & Look for the Windows must comply with your local energy code. Windows that are

More information

The Lehigh Valley Heritage Center Allentown, Pennsylvania

The Lehigh Valley Heritage Center Allentown, Pennsylvania Research on Smart Window Technology Building lighting loads in buildings account for a large percentage of electricity consumption and heat generation. Being able to utilize natural daylight to illuminate

More information

The energy benefits of View Dynamic Glass

The energy benefits of View Dynamic Glass Workplace demonstration Energy monitoring over a period of 12 months resulted in the commercial office room installed with View Dynamic Glass saving 39 percent of the total energy consumed compared to

More information

LoE LoE LoE-i89 Clear & Grey. Glassworks performance range

LoE LoE LoE-i89 Clear & Grey. Glassworks performance range LoE 3-366 LoE 3-340 LoE-i89 Clear & Grey Glassworks performance range At the forefront of performance driven glass to enhance sustainability, Glassworks are proud to have a range of the most advanced energy

More information

Design and retrofitting of a hybrid building in Athens

Design and retrofitting of a hybrid building in Athens International Conference Passive and Low Energy Cooling 597 Design and retrofitting of a hybrid building in Athens A. Gavalas Gavalas Architects, Athens ABSTRACT This paper s aim is to present a building

More information

Highly Transparent & Energy Saving Glass for Green Buildings

Highly Transparent & Energy Saving Glass for Green Buildings Highly Transparent & Energy Saving Glass for Green Buildings State of the Art Windows & Facades Float Glass Plant Sun Management Glass system SAVING SAVING ENERGY SAVING MONEY Solar Energy Flow Through

More information

WINDOW ENLIGHTENMENT

WINDOW ENLIGHTENMENT WINDOW ENLIGHTENMENT WINDOW ENLIGHTENMENT A New Vision for Energy Savings Today s buildings are dynamic living and working environments, expected to meet ever increasing demands for comfort, as well as

More information

As curtain wall and window systems. The Perfect (Retro)Fit: Overcoming Challenges with Curtain Wall Retrofits. FEATURE n n n

As curtain wall and window systems. The Perfect (Retro)Fit: Overcoming Challenges with Curtain Wall Retrofits. FEATURE n n n The Perfect (Retro)Fit: Overcoming Challenges with Curtain Wall Retrofits By Rob Wood, P.Eng., President, C3 Polymeric As curtain wall and window systems age, leakage and thermal problems escalate. Maintenance

More information

THE IMPACT OF GLAZING SELECTION ON DAYLIGHTING AND ENERGY PERFORMANCE FOR AN OFFICE BUILDING IN CANBERRA

THE IMPACT OF GLAZING SELECTION ON DAYLIGHTING AND ENERGY PERFORMANCE FOR AN OFFICE BUILDING IN CANBERRA THE IMPACT OF GLAZING SELECTION ON DAYLIGHTING AND ENERGY PERFORMANCE FOR AN OFFICE BUILDING IN CANBERRA Peter Taylor, Hélène Duponchel, and Paul Bannister Exergy Australia Pty Ltd PO Box 546 Belconnen

More information

Glassworks Pty Ltd in Melbourne, Australia. Self-Tinting Interlayer for Dynamic Windows. In Alliance with

Glassworks Pty Ltd in Melbourne, Australia. Self-Tinting Interlayer for Dynamic Windows. In Alliance with by Glassworks Pty Ltd in Melbourne, Australia Self-Tinting Interlayer for Dynamic Windows In Alliance with SUNTUITIVE INTERLAYER What s happening above: All of the windows above have the same exterior

More information

Energy Saving Benefits of Daylighting Combined with Horizontal Exterior Overhangs in Hot-and-Humid Regions

Energy Saving Benefits of Daylighting Combined with Horizontal Exterior Overhangs in Hot-and-Humid Regions Energy Saving Benefits of Daylighting Combined with Horizontal Exterior Overhangs in Hot-and-Humid Regions Speakers: Huang, Kuo-Tsang 1 ; Fu, Chun 2 1 Department of Bioenvironmental Systems Engineering,

More information

Assessment of thermal comfort near a glazed exterior wall

Assessment of thermal comfort near a glazed exterior wall Assessment of thermal comfort near a glazed exterior wall Timothy Anderson 1, Mark Luther 2 and Tim Brain 3 1 School of Engineering, Auckland University of Technology, Auckland 1142, New Zealand 2 School

More information

Comparative Analysis of Retrofit Window Film to Replacement with High Performance Windows

Comparative Analysis of Retrofit Window Film to Replacement with High Performance Windows Comparative Analysis of Retrofit Window Film to Replacement with High Performance Windows By Steve DeBusk, CEM, CMVP Global Energy Solutions Manager CPFilms, a Subsidiary of Solutia Inc. Abstract Energy

More information

Curtainwalls. Brussels Window. Objectives. Windows & Curtainwalls. Curtainwalls. 1 R2 R3. High tech? Low tech?

Curtainwalls. Brussels Window. Objectives. Windows & Curtainwalls. Curtainwalls.  1 R2 R3. High tech? Low tech? Curtainwalls Windows have long been important to buildings Brussels Window Objectives Windows & Curtainwalls This talk aims to Develop awareness of curtainwall performance appreciate impact of performance

More information

SKYLIGHT DESIGN PERFORMANCE EVALUATION METHOD DEVELOPMENT WITH THERMAL AND DAYLIGHT SIMULATION

SKYLIGHT DESIGN PERFORMANCE EVALUATION METHOD DEVELOPMENT WITH THERMAL AND DAYLIGHT SIMULATION SKYLIGHT DESIGN PERFORMANCE EVALUATION METHOD DEVELOPMENT WITH THERMAL AND DAYLIGHT SIMULATION Xianou Li, Frederick Wong, and Yihan Li Arup International Consultants (Shanghai) Co Ltd ABSTRACT This paper

More information

Products for Energy Applications

Products for Energy Applications Draft Document Products for Energy Applications GIB Draft 13 2018.10.01 For Task Group Development Use Only - Not Intended for Further Distribution Glass Informational Bulletin GANA (Doc. #)-XXXX Products

More information

ANALYSIS AND EXPERIMENTAL INVESTIGATION OF THE NTCH BUILDING ON ENERGY CONSERVATION DESIGNS

ANALYSIS AND EXPERIMENTAL INVESTIGATION OF THE NTCH BUILDING ON ENERGY CONSERVATION DESIGNS , Volume 2, Number 1, p.7-14, 2001 ANALYSIS AND EXPERIMENTAL INVESTIGATION OF THE NTCH BUILDING ON ENERGY CONSERVATION DESIGNS K.H. Yang and J.N. Lee Mechanical Engineering Department, National Sun Yat-Sen

More information

Irvine CA MAE ROW ROW ROW. Office Lighting Plan. Page 93

Irvine CA MAE ROW ROW ROW. Office Lighting Plan. Page 93 MAE DEPTH DAYLIGH TING STUDY To complete the MAE additional depth requirement for thesis, a daylighting analysis for the third floor open office space has been performed. Three northern windows provide

More information

Green your Condo Optimize Glass Coatings for Energy Savings

Green your Condo Optimize Glass Coatings for Energy Savings Green your Condo Optimize Glass Coatings for Energy Savings BY MATT CHARBONNEAU Matt Charbonneau, M.A.Sc., P.Eng. Project Manager, Shareholder mcharbonneau@edisonengineers.ca 289-983-5721 Considering Window

More information

STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS

STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS STEADY STATE AND DYNAMIC THERMOPHYSICAL PARAMETERS OF TRANSPARENT BUILDING COMPONENTS 1. ABSTRACT In modern architecture the buildings are often designed with large glass facades or windows. Due to these

More information

Comparison of Energy and Visual Comfort Performance of Independent and Integrated Lighting and Daylight Controls Strategies

Comparison of Energy and Visual Comfort Performance of Independent and Integrated Lighting and Daylight Controls Strategies Comparison of Energy and Visual Comfort Performance of Independent and Integrated Lighting and Daylight Controls Strategies Eric Shen and Maulin Patel, Philips Research North America Jia Hu, University

More information

Effect of a Window Shade on Home Energy Use

Effect of a Window Shade on Home Energy Use University of Nebraska - Lincoln DigitalCommons@University of Nebraska - Lincoln Environmental Studies Undergraduate Student Theses Environmental Studies Program Fall 2015 Effect of a Window Shade on Home

More information

GLASS SELECTION GUIDE

GLASS SELECTION GUIDE GLASS SELECTION GUIDE www.metrotech.co.nz GLASS SELECTION The Glass Selection Flow Chart should be used in conjunction with the Selection Sheets and Section 11.1.2 of the Catalogue and Reference Guide

More information

Spandrel Glass Types and Recommendations

Spandrel Glass Types and Recommendations Introduction Vitro (formerly PPG Industries) has long offered recommendations regarding alternatives for glass spandrel applications. Over the years these recommendations were included in various publications

More information

The lotus flower: biomimicry solutions in the built environment

The lotus flower: biomimicry solutions in the built environment Sustainable Development and Planning VII 1085 The lotus flower: biomimicry solutions in the built environment Y. Nanaa & H. Taleb Sustainable Design of the Built Environment, British University in Dubai,

More information

ADAPTIVE LOW-E DOUBLE GLAZING WINDOW

ADAPTIVE LOW-E DOUBLE GLAZING WINDOW ADAPTIVE LOW-E DOUBLE GLAZING WINDOW Hussein Abaza 1 and Ihab Sa ad 2 ABSTRACT This paper investigates the thermal performance of a new adaptive window which is seasonally reversible. The new window is

More information

Smart. Easy. Profitable.

Smart. Easy. Profitable. Smart. Easy. Profitable. SageGlass dynamic glass for commercial, industrial and residential buildings Generate larger and more profitable contracts, differentiate yourself from competitors, and stay ahead

More information

Solar Control. Pilkington Solar Control range

Solar Control. Pilkington Solar Control range Solar Control Pilkington Solar Control range Contents Energy efficiency in buildings Solar Control How it works Low-emissivity How it works Introduction to the Pilkington Solar Control range Coated Glass

More information

Chapter 5 Glazing Properties

Chapter 5 Glazing Properties Chapter 5 Glazing Properties Building Energy Efficiency Technical Guideline for Passive Design (Draft 1) CK Tang Foreword This document is produced as part of Component 4, Building Sector Energy Efficiency

More information

NRC CONSTRUCTION TECHNOLOGY UPDATE

NRC CONSTRUCTION TECHNOLOGY UPDATE NRC CONSTRUCTION TECHNOLOGY UPDATE No. 82, June 2014 Performance of Tubular Daylighting Devices By A. Laouadi and H.H. Saber Tubular daylighting devices (TDDs) can economically admit natural light into

More information

Facade Design for Super High- Rise Building in Subtropic Region in China

Facade Design for Super High- Rise Building in Subtropic Region in China Facade Design for Super High- Rise Building in Subtropic Region in China Super high-rise building will always be iconic elements at any location. Accompanied by the growth of building technology and urbanization,

More information

DAYLIGHTING. 5.1 Introduction{ TC "5.1 Introduction" \l 2 } { TC "'CHAPTER FIVE: DAYLIGHTING'" \l 1 }CHAPTER FIVE

DAYLIGHTING. 5.1 Introduction{ TC 5.1 Introduction \l 2 } { TC 'CHAPTER FIVE: DAYLIGHTING' \l 1 }CHAPTER FIVE 1 { TC "'CHAPTER FIVE: DAYLIGHTING'" \l 1 }CHAPTER FIVE 5.1 Introduction{ TC "5.1 Introduction" \l 2 } DAYLIGHTING This chapter presents the method and results of an analysis of daylighting for the retail

More information

Energy Analysis for Window Films Applications in Florida Offices

Energy Analysis for Window Films Applications in Florida Offices Energy & Environmental Solutions Energy Analysis for Window Films PREPARED FOR: INTERNATIONAL WINDOW FILM ASSOCIATION P.O. BOX 3871 MARTINSVILLE, VA 24115-3871 PREPARED BY: CONSOL 5757 PACIFIC AVENUE,

More information

White Paper. Central Catholic High School, Portland, OR

White Paper. Central Catholic High School, Portland, OR White Paper Using Infrared Thermography of Existing Masonry Walls to Target Retrofit Efforts and Lessons for Future Additions Central Catholic High School, Portland, OR Corey Griffin, Assistant Professor,

More information

Available online at ScienceDirect. Energy Procedia 78 (2015 ) th International Building Physics Conference, IBPC 2015

Available online at  ScienceDirect. Energy Procedia 78 (2015 ) th International Building Physics Conference, IBPC 2015 Available online at www.sciencedirect.com ScienceDirect Energy Procedia 78 (2015 ) 340 345 6th International Building Physics Conference, IBPC 2015 The influence of solar control films on energy and daylighting

More information

A new blast-mitigation solution for building facade protection with a laminated polycarbonate based system

A new blast-mitigation solution for building facade protection with a laminated polycarbonate based system Safety and Security Engineering V 353 A new blast-mitigation solution for building facade protection with a laminated polycarbonate based system V. Benz 1, J. Lorenzo 2, R. Pyles 2, R. Rumer 2 & K. Wiecking

More information

optimize daylighting Opportunities

optimize daylighting Opportunities optimize daylighting Opportunities DESIGN STRATEGIES DESIGN STRATEGIES NATURAL LIGHTING FOR ENERGY EFFICIENCY DAYLIGHTING Using indirect natural light to illuminate indoor spaces as an alternative to electric

More information

Window Options. Keeping cool in summer, warm in winter, comfortable all the time,... and saving energy too

Window Options. Keeping cool in summer, warm in winter, comfortable all the time,... and saving energy too Window Options Keeping cool in summer, warm in winter, comfortable all the time,... and saving energy too Ross McCluney, Ph.D., Prinicipal Research Scientist Florida Solar Energy Center! Many factors affect

More information

Poor distribution & glare

Poor distribution & glare Light transmission The benefits of the use of natural daylight in buildings in respect of health & well-being, safety, productivity and energy savings are well documented. LIGHT TRANSMISSION Light that

More information

The Technical Merit of Double Facades for Office Buildings in Cool Humid Climates

The Technical Merit of Double Facades for Office Buildings in Cool Humid Climates The Technical Merit of Double Facades for Office Buildings in Cool Humid Climates By: John F Straube and Randy van Straaten University of Waterloo So-called double facades (DF) or ventilated facades, environmental

More information

The effect of shading design and control on building cooling demand

The effect of shading design and control on building cooling demand International Conference Passive and Low Energy Cooling 953 for the Built Environment, May 25, Santorini, Greece The effect of shading design and control on building cooling demand A. Tzempelikos and A.K.

More information

Passive Solar Systems

Passive Solar Systems Passive Solar Systems Content Passive Solar Systems Passive Solar Heating Passive Solar Cooling Night Sky Radiation Time Lag Cooling Thermal Mass Earth Cooling Daylighting Passive Solar Systems Passive

More information

THERMAL ANALYSIS OF A FACADE-MOUNTED PV ARRAY

THERMAL ANALYSIS OF A FACADE-MOUNTED PV ARRAY SESCI 23 CONFERENCE Queen's University Kingston, Ontario, Canada August 18 to 2, 23 THERMAL ANALYSIS OF A FACADE-MOUNTED PV ARRAY S. J. Harrison 1, A. Driesse 2, Q. Lin 1 1 Queen's University, Solar Calorimetry

More information

CONTROLITE. Intelligent Daylighting System FACADE SKYLIGHT

CONTROLITE. Intelligent Daylighting System FACADE SKYLIGHT CONTROLITE Intelligent Daylighting System FACADE SKYLIGHT INTELLIGENT DAYLIGHTING SYSTEM CONTROLITE FEATURES A TRANSLUCENT GLAZING PANEL WITH INTEGRATED, ROTATING LOUVRES THAT ADJUST THEIR POSITION THROUGHOUT

More information

TREES Training for Renovated Energy Efficient Social housing. Section 1 Techniques 1.2 Replacement of glazing

TREES Training for Renovated Energy Efficient Social housing. Section 1 Techniques 1.2 Replacement of glazing TREES Training for Renovated Energy Efficient Social housing Intelligent Energy -Europe programme, contract n EIE/05/110/SI2.420021 Section 1 Techniques 1.2 Replacement of glazing Bruno PEUPORTIER ARMINES

More information

State Of The Art Office Building & Campus For Maharashtra Energy Development Agency(MEDA) At AUNDH, PUNE

State Of The Art Office Building & Campus For Maharashtra Energy Development Agency(MEDA) At AUNDH, PUNE State Of The Art Office Building & Campus For Maharashtra Energy Development Agency(MEDA) At AUNDH, PUNE Architectural Design Basis: 2 o The sole motive and mission of MEDA is to Promote Energy Conservation,

More information

The Impact of VISIONWALL High Performance Windows on the Northern Telecom Building in Ottawa, Ontario

The Impact of VISIONWALL High Performance Windows on the Northern Telecom Building in Ottawa, Ontario The Impact of VISIONWALL High Performance Windows on the Northern Telecom Building in Ottawa, Ontario Visionwall Technologies Inc. 14904-123 Avenue Edmonton, Alberta, Canada T5V 1B4 Tel: 403 451 4000 Fax:

More information

COST EFFECTIVENESS FOR SOLAR CONTROL FILM FOR RESIDENTIAL APPLICATIONS H. Al-Taqi G.P. Maheshwari R. Alasseri Senior Research Associate

COST EFFECTIVENESS FOR SOLAR CONTROL FILM FOR RESIDENTIAL APPLICATIONS H. Al-Taqi G.P. Maheshwari R. Alasseri Senior Research Associate COST EFFECTIVENESS FOR SOLAR CONTROL FILM FOR RESIDENTIAL APPLICATIONS H. Al-Taqi G.P. Maheshwari R. Alasseri Senior Research Associate Senior Research Specialist Department of Building and Energy Technologies

More information

DYNAMIC FACADE. BUILDING ENERGY EFFICIENCY REHABILITATION.

DYNAMIC FACADE. BUILDING ENERGY EFFICIENCY REHABILITATION. Albert López. Architect (SOMFY Spain) albert.lopez@somfy.com DYNAMIC FACADE. BUILDING ENERGY EFFICIENCY REHABILITATION. 1. Energy in the the running costs of buildings. 2. The energy consumption of a building.

More information

Thermal Control in Buildings by John Straube (updated )

Thermal Control in Buildings by John Straube (updated ) building science.com 2006 Building Science Press All rights of reproduction in any form reserved. Building Science Digest 011 Thermal Control in Buildings 2006-11-02 by John Straube (updated 2011-12-12)

More information

Be Aggressive About the Passive Solutions

Be Aggressive About the Passive Solutions Be Aggressive About the Passive Solutions Integrating Building Envelope Design in Whole Building Energy Goals Daniel Luddy, PE BEMP CPHC LEEP AP Senior Energy Engineer 2015 Building Envelope Forum AIA

More information

SECTION SPECIALTY FILMS FOR GLASS ENHANCEMENT (DECORATIVE) RED SR HPR

SECTION SPECIALTY FILMS FOR GLASS ENHANCEMENT (DECORATIVE) RED SR HPR SECTION 088723 SPECIALTY FILMS FOR GLASS ENHANCEMENT (DECORATIVE) RED SR HPR PART 1 - GENERAL 1.01 SUMMARY A. Section includes film products applied to glass surfaces to impart aesthetic characteristics.

More information

ANALYSIS AND MITIGATION OF THERMAL EFFECTS ON A LARGE FACADE-MOUNTED PV ARRAY

ANALYSIS AND MITIGATION OF THERMAL EFFECTS ON A LARGE FACADE-MOUNTED PV ARRAY ANALYSIS AND MITIGATION OF THERMAL EFFECTS ON A LARGE FACADE-MOUNTED PV ARRAY A. Driesse 1, S. J. Harrison 2, Q. Lin 2 1 Queen's University, Integrated Learning Center, Kingston, ON, Canada; 2 Queen's

More information

The Elithis Tower is an experimental and demonstration. Elithis Tower in Dijon, France. nzeb case studies

The Elithis Tower is an experimental and demonstration. Elithis Tower in Dijon, France. nzeb case studies COM Elithis Tower in Dijon, France Elithis Tower, located in Dijon, France, provides strong evidence that net zero energy office buildings are achievable in near future. The building, which was designed

More information

Lead Organizations. Kerry Haglund Center for Sustainable Building Research University of Minnesota

Lead Organizations. Kerry Haglund Center for Sustainable Building Research University of Minnesota Efficient Windows Collaborative Design and Simulation Tools for Window System Energy Performance The Efficient Windows Collaborative is a coalition of window, door, skylight, and component manufacturers,

More information

A Study on the Variation of Heating & Cooling Load by the Various Shading and Performance of Window in Office Buildings Seok-Hyun Kim 1, Kyung-ju Shin

A Study on the Variation of Heating & Cooling Load by the Various Shading and Performance of Window in Office Buildings Seok-Hyun Kim 1, Kyung-ju Shin A Study on the Variation of Heating & Cooling Load by the Various Shading and Performance of Window in Office Buildings Seok-Hyun Kim 1, Kyung-ju Shin 1, Bo-eun Choi 1, Jae-Hun Jo 2, Young-Hum Cho 3, Soo

More information

Design of Green Building

Design of Green Building Sumit Kumar, Abhinav Singh Abstract The 4th Assessment Report from the Intergovernmental Panel on Climate Change (IPCC) has shown that buildings have the highest potential to reduce carbon emissions. This

More information

CHIANG MAI HEALTH CARE CENTER Energy Efficiency Study, Chiang Mai, January 19, 2017

CHIANG MAI HEALTH CARE CENTER Energy Efficiency Study, Chiang Mai, January 19, 2017 CHIANG MAI HEALTH CARE CENTER Energy Efficiency Study, Chiang Mai, January 19, 2017 Unexpected Co., Ltd. EGS-plan (Bangkok) Co.,Ltd. Project location, 18 45'47.2"N / 99 00'40.9 E Chiang Mai Old City Ban

More information

Q-Air unique selling propositions in detail

Q-Air unique selling propositions in detail Q-Air unique selling propositions in detail Afraid of sitting at the window in winter? Q-Air offers a U value so low that there can be no perceptible cold air movement at the panoramic window even in coldest

More information

The Assessment of Advanced Daylighting Systems in Multi-Story Office Buildings Using a Dynamic Method

The Assessment of Advanced Daylighting Systems in Multi-Story Office Buildings Using a Dynamic Method The Assessment of Advanced Daylighting Systems in Multi-Story Office Buildings Using a Dynamic Method Jianxin Hu 1,*, Jiangtao Du 2, Wayne Place 1 1 College of Design, School of Architecture, North Carolina

More information

Guidelines for Design and Construction of Energy Efficient County Facilities

Guidelines for Design and Construction of Energy Efficient County Facilities APPENDIX C - DAYLIGHTING The role of daylighting in the total energy balance and performance of a building is a significant one. The admission of useful daylight means that electrical lighting fixtures

More information

additional cooling energy consumption. Because the thermal resistance of windows has always been a weak point, even with vacuum glass or low-e glass,

additional cooling energy consumption. Because the thermal resistance of windows has always been a weak point, even with vacuum glass or low-e glass, Simulation Study of Automated Blinds Control Strategy for Minimizing Cooling and Lighting Energy Consumptions L. Xiao 1, F. Wang 2,*, Y. Gao 2, T. Gong 2, Y. Di 2, Y. Qian 2, and X. Luo 2 1 School of Mechanical

More information

Ultimate Performance Glass

Ultimate Performance Glass Ultimate Performance Glass CG ENGINEERING THE FUTURE OF COATED GLASS U L T I M A T E P E R F O R M A N C E G L A S S Introducing the new standard. Introducing Loå 3-366 (pronounced low E cubed-366), the

More information

EXTERNAL SHADING DEVICES

EXTERNAL SHADING DEVICES EXTERNAL SHADING DEVICES External shading devices, such as eaves, awnings, and verandahs, play a critical role in reducing unwanted solar heat gain, especially in cooling-dominant climates and during summer

More information

Window Labelling Program for India

Window Labelling Program for India Window Labelling Program for India Stakeholder consultation meeting : October 13, 2012, New Delhi Centre for Advanced Research in Building Science and Energy, CEPT University, Ahmedabad INDIA Rajan Rawal,

More information

The only constant aspect of Technology is,.change! Sustaining Technology! MATERIAL. Sustaining Technology in Glazing

The only constant aspect of Technology is,.change! Sustaining Technology! MATERIAL. Sustaining Technology in Glazing Sustaining Technology! The only constant aspect of Technology is,.change! -- Anonymous Sustaining Technology in Glazing Long way since 4000 BC, Today, Glass is no more a window element, but is an effective

More information

690: Form Follows the Sun: Hill County SEZ Office Complex

690: Form Follows the Sun: Hill County SEZ Office Complex 690: Form Follows the Sun: Hill County SEZ Office Complex Varun Kohli* Skidmore, Owings & Merrill LLP, New York, USA * varun.kohli@som.com Abstract The paper discusses a rigorous and methodical environmental

More information

Environmental Principles

Environmental Principles The Ownership group and lead consultants commitment to sustainability has been a driving force for its design. The project will achieve, per council policy for rezoning, an equivalency of LEED Gold (63

More information

The Top Five Ways an Architect Can Drive Sustainability. Early-stage design decisions that can have a significant impact on building performance

The Top Five Ways an Architect Can Drive Sustainability. Early-stage design decisions that can have a significant impact on building performance The Top Five Ways an Architect Can Drive Sustainability Early-stage design decisions that can have a significant impact on building performance Architects are responsible for a large number of fundamental

More information

NEED FOR A CORRECT GLASS DESCRIPTIVE CODE: ENERGY-CODING

NEED FOR A CORRECT GLASS DESCRIPTIVE CODE: ENERGY-CODING NEED FOR A CORRECT GLASS DESCRIPTIVE CODE: ENERGY-CODING Carl Axel Lorentzen BSc (Eng) Technical Advisory Service, Pilkington Danmark A/S, Oslo Plads 14, 2100 Copenhagen, Denmark Phone +45 35426600, Fax

More information

Cost Benefits of SunGuard SN 54

Cost Benefits of SunGuard SN 54 Cost Benefits of SunGuard SN 54 Guardian Industries recently introduced SunGuard SN 54 low-e glass. This new low-e glass is clear in appearance and has optimal energy performance for commercial building

More information

10 tips from your Architect

10 tips from your Architect 10 tips from your Architect Within the context of the national week of Energy Efficiency, in collaboration with the Energy Efficiency Management Office, the Mauritius Association of Architects offers you

More information

Analysis 2: Alternative Thermal Window Design

Analysis 2: Alternative Thermal Window Design Analysis 2: Alternative Thermal Window Design (8.1) Problem Statement: In the first analysis, the cost and environmental impacts of the addition of solar PV panels to the roof of GrandView was determined.

More information

Design of Sunshade Board with South External Window of Residential Building in Hangzhou Based on Software Simulation Analysis of Energy Saving

Design of Sunshade Board with South External Window of Residential Building in Hangzhou Based on Software Simulation Analysis of Energy Saving , pp. 157-166 http://dx.doi.org/10.14257/ijsh.2015.9.9.17 Design of Sunshade Board with South External Window of Residential Building in Hangzhou Based on Software Simulation Analysis of Energy Saving

More information

Energy Analysis of Using Thermal Mass in a Hot Humid climate

Energy Analysis of Using Thermal Mass in a Hot Humid climate Energy Analysis of Using Thermal in a Hot Humid climate SARA MOTAMEDI Architecture Department University of Texas at Austin 1 University Station B7500 Austin, Texas, U.S.A, 787us2-0222 s.motamedi@mail.utexas.edu

More information

The Bahen Centre for Information Technology. Glazing Studies of the Gallery. Introduction. University of Toronto ~ Toronto, Ontario, Canada

The Bahen Centre for Information Technology. Glazing Studies of the Gallery. Introduction. University of Toronto ~ Toronto, Ontario, Canada Glazing Studies of the Gallery Introduction The gallery in the Bahen Centre is a circulation space located in the northeast side of the building. One side of the corridor composed of the walls of an auditorium

More information