1 Stable Renewable Plant Voltage and Reactive Power Control NERC ERSTF June 11-12, 2014 Sebastian Achilles Nicholas Miller Einar Larsen Jason MacDowell GE Energy Consulting 1 /

2 Topics Features of modern wind turbine generators and wind plants Voltage vs. power factor control in wind plants Weak system control stability with PE sources Response coordination of multiple wind plants Summary 2 /

3 What makes a Wind Plant Grid Friendly? Not trip during Faults and other System Disturbances ride through capability Regulate Plant Voltage and Reactive Power Limits the Rate of Change of Power from Variations in Wind Speed Ramp Rate Control React to Changes in Grid Frequency Frequency Droop Provide reactive power all the time Provide inertial response to large under-frequency events: WindINERTIA TM Reliable operation with series compensated lines Reliable operation with low system strength 3 /

4 Wind Turbines and Reactive Power Control 4 /

5 WTG Reactive Power Capability Reactive Power for Voltage Support Steady-state PF range under-excited/0.90 over-excited Dynamic range meets or exceeds steady-state range WTG reactive capability often sufficient to satisfy PF requirements at POI VAR capability reduced at low power due to units cycling off-line GE offers reactive power capability with no wind Terminal Bus P gen WTG Q gen Reactive Capability all the time is valuable! 5 /

6 WindCONTROL Plant Level Control System Substation HV Bus Coordinated turbine and plant supervisory control structure Fast WTG controls Slower plant controls Voltage, VAR, & PF control Q L Q C Q WP P WP LTC Point of Interconnection (POI) Reactive Power Controller LV Bus Active Power control PF requirements primarily met by WTG reactive capability, but augmented by mechanically switched shunt devices if necessary Reactive Compensation (if required) Integrated with substation SCADA 6 / Q WTG

7 Voltage & Reactive Power Controls Regulates Grid Voltage at Point of Interconnection Minimizes Grid Voltage Fluctuations Even Under Varying Wind Conditions Actual measurements from a 162MW wind plant Wind Plant Voltage Voltage at POI Regulates Total Wind Plant Reactive Power through Control of Individual Turbines Average Wind Speed Wind Plant Power Output Voltage and Reactive Power Regulation Like A Conventional Power Plant 7 /

8 Network Stability: Voltage or Power Factor Control? 8 /

9 Steady State considerations Strong grid Weak grid PF Control Voltage Control Insufficient margin and challenging operation in PF control Plant level voltage control improves network voltage stability performance in constrained transmission systems 9 /

10 Control Stability of Power Electronic Sources in Weak Grids 10 /

11 Conventional and Power-Electronic sources Relevant electrical characteristics of Power-Electronic (PE) sources Performance aspect Conventional generation Power-Electronic Sources Short circuit contribution (system strength) Current sharing/distribution Around 3 pu Inherent to design characteristics. Sharing depends on size and impedances of the machines Small/none Fast current controls force current sharing All current-controlled PE sources require grid strength to operate reliably and stably Grid strength is high when electrically close to conventional generation 11 /

12 Conventional and Power-Electronic sources Long transmission corridors (low system strength) typically have power transfer limited below thermal limits due to stability challenges Conventional generation Transient Stability Dynamic stability Voltage stability Power-Electronic Sources Voltage stability Fast control stability Fast control stability refers to interactions between transmission system and PE sources (Wind Turbine Generators, SVCs, STATCOMs, etc.) 12 /

13 Wind turbine generators and system strength Modern WTGs are PE sources Some applications may need mitigations to achieve desired system performance under very low system strength conditions: Transmission upgrades» New lines» Updated Topology (meshed vs. radial)» Series compensation» Synchronous condensers (System strength, dyn VARs)» SVC, STATCOM (dyn VARs, control challenges) Special protection schemes (such as transfer trips) GE offers control features to improve performance in low SCR conditions More than one mitigation mechanism may be used and system coordination of multiple mechanisms is highly desirable and very effective (e.g. Wind Plant + Condenser) 13 /

14 SCR applied to Wind Plants In the case of Wind Plants, the characterization of system strength has to take into account all electrically close converters (Multi-infeed) Composite SCR (CSCR) considers the grid strength as seen by all electrically close converters and is used for wind plants. Converter locations WP1 WP 2 WP 3 14 /

15 Composite SCR Composite short circuit level: 3Ph short circuit at 34.5 KV buses - all interconnected Low load conditions (low/realistic commitment of conventional generation) Contingency conditions also considered No contribution from converters WP1 WP 2 WP 3 15 /

16 Composite SCR: Recommended Practice CSCR Composite SC MVA converter MW rating Composite SCR is useful to characterize grid strength and screen for system stability risks Understanding of the grid parameters, system operation and future wind projects is required to meaningfully estimate CSCR Grid entities should estimate this parameter for normal and contingency operation and communicate to developers. For very low CSCR applications, dedicated detailed analysis is recommended 16 /

17 Coordinated response of electrically close wind plant level controllers 17 /

18 Plant Level Control Interactions Substation HV Bus QWP Point of Interconnection (POI) MV Bus QWP1 Plant Level Control Wind CONTROL VWP Plant Level Wind CONTROL Control QWP2 time QWP1 QWP2 VWP time 18 / Q May WTG 10, 2008

19 Plant Level Control Interactions Substation HV Bus QWP Point of Interconnection (POI) MV Bus QWP1 QWP2 time Plant Level Control Wind CONTROL VWP Plant Level Wind CONTROL Control Circulating Q VWP time 19 / Q May WTG 10, 2008

20 Plant Level Control Interactions: Voltage Droop QWP Uncoordinated Without Voltage Droop Effect of voltage setpoint differences or PT errors QWP1 QWP Coordinated With Droop Effect of system event time QWP1 QWP2 time QWP2 VWP VWP time time Faster control details neglected for this discussion Dynamic response coordination also assumed 20 /

21 Summary 21 /

22 Summary Coordinated plant level voltage control improves voltage stability performance in weak grid applications Fast terminal voltage control significantly improves the system performance during contingencies in weak grid applications Providing Reactive power all the time is valuable for system stability Understanding and potential remediation of very low grid strength wind plant operation is critical to maintain stability This requires collaboration between system operator, planners, developers and OEMs. CSCR estimation is an initial step in such collaboration Electrically close plant level controls require coordination to avoid negative interactions of reactive power These issues are resolvable if known and included in the planning/development process 22 /

23 Thank you! Questions? 23 /

24 Back-up 24 /

25 Fast or Slow Voltage Control? 25 /

26 Conventional Generation Fast acting Automatic Voltage Regulator (AVR) Quick an effective system support to improve stability Limits voltage variations at equipment Slower acting joint control Optimizes steady state operation Does not interfere with inner control loops Reduced risk of instabilities due to communication delays FAST Loop FAST Loop SLOW Loop FAST Loop A reasonable and valuable concept 26 /

27 Contingency operation of Wind Plants Contingency operation requires higher reactive power for stable operation with same power level N-0 Steady state Joint control is typically slower than WTG active power recovery Fast WTG terminal voltage control keeps system stable for wider range of operating conditions N-1 before joint control reaction Joint control further optimizes operating condition in steady state 27 /

28 How strong are grid conditions? The industry has used the Short Circuit Ratio (SCR) to assess the system strength for the connection of power electronic converters SCR varies with system conditions There are few different SCR calculation methods proposed in the industry SCR short circuitmvaof AC System converter MW rating HVDC rectifier 28 / March 2012

Coordination of Multiple Voltage Controllers of Adjacent Wind Plants Connected to João Câmara II with Droop Function

Coordination of Multiple Voltage Controllers of Adjacent Wind Plants Connected to João Câmara II with Droop Function Coordination of Multiple Voltage Controllers of Adjacent Wind Plants Connected to João Câmara II with Droop Function Mariana B. Pereira 1, Sebastian A. Achilles 2, Nath Venkit 2 Energy Consulting General

More information

Wind Farm Performance on the Grid: Perception and Reality

Wind Farm Performance on the Grid: Perception and Reality Wind Farm Performance on the Grid: Perception and Reality WindVAR and LVRT Data and Graphs provided by Nicholas W. Miller GE Energy, Energy Consulting 1 GE Energy Wind Energy Grid Performance: A Perception

More information

Low SCR Wind Identification and Mitigation. Will Lovelace MIPSYCON 2015 November 11 th, 2015

Low SCR Wind Identification and Mitigation. Will Lovelace MIPSYCON 2015 November 11 th, 2015 Low SCR Wind Identification and Mitigation Will Lovelace MIPSYCON 2015 November 11 th, 2015 System Background - Diagram System Background - Diagram System Background - Description 199.5 MW wind farm on

More information

Daniel Feltes Phone: Fax:

Daniel Feltes Phone: Fax: Coordination of Controls of Renewable Power Plants to Meet Steady State and Dynamic Response Requirements for Voltage Control and Reactive Power Supply Dinemayer Silva Phone: 518-395-5169 Fax: 518-346-2777

More information

Generator Interconnection Affected System Impact Study. Plains & Eastern Clean Line Final Report

Generator Interconnection Affected System Impact Study. Plains & Eastern Clean Line Final Report Generator Interconnection Affected System Impact Study Plains & Eastern Clean Line Final Report May 19, 2015 MISO 2985 Ames Crossing Eagan Minnesota - 55121 http://www.misoenergy.org Midcontinent Independent

More information

SYNOPSIS OF THE THESIS. Enhanced Power Quality Management of Grid Connected Wind Farm

SYNOPSIS OF THE THESIS. Enhanced Power Quality Management of Grid Connected Wind Farm SYNOPSIS OF THE THESIS Enhanced Power Quality Management of Grid Connected Wind Farm INTRODUCTION OF THE THESIS Faster depletion of fossil fuels and environmental damage has resulted into increased use

More information

Fault Current Contributions from Wind Plants Dean Miller PacifiCorp July 25, 2012

Fault Current Contributions from Wind Plants Dean Miller PacifiCorp July 25, 2012 Fault Current Contributions from Wind Plants Dean Miller PacifiCorp July 25, 2012 1 Presentation Overview Joint Working Group The Issue Structure of the Report Wind Plant Configuration Wind Turbine Generators

More information

2009 AEE TECHWINDGRID 09, April, 2009 Madrid 1

2009 AEE TECHWINDGRID 09, April, 2009 Madrid 1 2009 AEE TECHWINDGRID 09, 20-21 April, 2009 Madrid 1 GE Wind Plant Dynamic Performance for Grid and Wind Events Nicholas W. Miller*, Kara Clark, Mark E. Cardinal, Robert W. Delmerico GE Energy, Schenectady,

More information

TRANSMISSION PLANNING ASSESSMENT METHODOLOGY AND CRITERIA

TRANSMISSION PLANNING ASSESSMENT METHODOLOGY AND CRITERIA TRANSMISSION PLANNING ASSESSMENT METHODOLOGY AND CRITERIA For Compliance with NERC Reliability Standard: TPL-001-4 1/10/2017 Version: 4.2 Table of Contents 1 Revision and Approval History... 2 1.1 Revision

More information

BPA Wind Voltage Control Requirements

BPA Wind Voltage Control Requirements BPA Wind Voltage Control Requirements PJM Conference Dmitry Kosterev Bonneville Power Administration Many of BPA Paths are Stability-Limited Cross-Cascades North Montana - Northwest Cross-Cascades South

More information

8 th Annual Electric Power Industry Conference

8 th Annual Electric Power Industry Conference 8 th Annual Electric Power Industry Conference STATCOM Application to Address Grid Stability and Reliability: Part I November 11 th, 2013 Authors: Donald Shoup, P.E. and Dr. Gregory Reed Support: Nick

More information

Connection Study Requirements

Connection Study Requirements Document Release Released: September 20, 2010 The Customer shall comply with all the applicable requirements in this document when performing connection studies to produce the engineering study report.

More information

Wind Farms in Weak Grids Compensated with STATCOM

Wind Farms in Weak Grids Compensated with STATCOM Nordic PhD course on Wind Power (June 5-11, 2005) Final Examination Report Ph.D. Candidate: Akarin Suwannarat Supervisors: Birgitte Bak-Jensen Institute of Energy Technology, Aalborg University Pontoppidantstraede

More information

California Independent System Operator Renewable Integration Study

California Independent System Operator Renewable Integration Study California Independent System Operator Renewable Integration Study Clyde Loutan Proposed Transmission Plan for Integration of Renewables Transmission System Analysis - Overview Joint Study between the

More information

Standard Development Timeline

Standard Development Timeline Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard is adopted by the NERC Board of Trustees (Board).

More information

Grid Interconnection Issues for Wind Generation

Grid Interconnection Issues for Wind Generation Grid Interconnection Issues for Wind Generation NRECA APPA - DOE Teleconference December 8, 2005 By Thomas A. Wind, PE Wind Utility Consulting Jefferson, Iowa Topics I Will Cover What are the key technical

More information

CENTRE FOR WIND ENERGY TECHNOLOGY CHENNAI INDIAN WIND GRID CODE

CENTRE FOR WIND ENERGY TECHNOLOGY CHENNAI INDIAN WIND GRID CODE CHENNAI INDIAN WIND GRID CODE Rajesh Katyal Unit Chief, R&D Centre for Wind Energy Technology OVERVIEW NEED FOR INDIAN WIND GRID CODE Wind energy constitutes 6% of the installed capacity in the power scenario

More information

April 26, PJM Mr. Mark J. Kuras Senior Lead Engineer NERC and Regional Coordination 2750 Monroe Blvd. Audubon, PA 19403

April 26, PJM Mr. Mark J. Kuras Senior Lead Engineer NERC and Regional Coordination 2750 Monroe Blvd. Audubon, PA 19403 AMERICAN ELECFRIC POWER BOUNDLESS F.1'ERGY" American Electric Power 8500 Smiths Mill Road New Albany, OH 43054 www.aep.com April 26, 2017 PJM Mr. Mark J. Kuras Senior Lead Engineer NERC and Regional Coordination

More information

Standard Development Timeline

Standard Development Timeline Standard TPL-001-4 Transmission System Planning Performance Requirements Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be

More information

ISSN Vol.07,Issue.16, November-2015, Pages:

ISSN Vol.07,Issue.16, November-2015, Pages: ISSN 2348 2370 Vol.07,Issue.16, November-2015, Pages:3181-3185 www.ijatir.org Improvement of Power Quality in A Grid Connected Induction Generator Based Wind Farm using Static Compensator K. YOSHMA 1,

More information

NERC PLANNING STANDARDS

NERC PLANNING STANDARDS NERC PLANNING STANDARDS North American Electric Reliability Council April 2004 Version of All Planning Standards Terms and Their Definitions As Used in the Analysis (Study) an examination or simulation

More information

Standard MH-TPL Transmission System Planning Performance Requirements

Standard MH-TPL Transmission System Planning Performance Requirements A. Introduction 1. Title: Transmission System Planning Performance Requirements 2. Number: MH-TPL-001-4 3. Purpose: Establish Transmission system planning performance requirements within the planning horizon

More information

Standard Development Timeline

Standard Development Timeline Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard is adopted by the NERC Board of Trustees (Board).

More information

Utility Tools and Design Modifications to Mitigate the Impact of PV on the Distribution System

Utility Tools and Design Modifications to Mitigate the Impact of PV on the Distribution System Utility Tools and Design Modifications to Mitigate the Impact of PV on the Distribution System? IEA-Task 14/SEPA High Penetration PV Workshop Dec. 1, 2010 Overview Service Territory & PV Activity PV System

More information

Standard TPL Transmission System Planning Performance Requirements

Standard TPL Transmission System Planning Performance Requirements A. Introduction 1. Title: Transmission System Planning Performance Requirements 2. Number: TPL-001-4 3. Purpose: Establish Transmission system planning performance requirements within the planning horizon

More information

Lesson Learned Loss of Wind Turbines due to Transient Voltage Disturbances on the Bulk Transmission System

Lesson Learned Loss of Wind Turbines due to Transient Voltage Disturbances on the Bulk Transmission System Lesson Learned Loss of Wind Turbines due to Transient Voltage Disturbances on the Bulk Transmission System Primary Interest Groups Balancing Authorities (BAs) Transmission Operators (TOPs) Generator Operators

More information

Hydro-Quebec s experience with HYPERSIM Real-time Power System Simulator

Hydro-Quebec s experience with HYPERSIM Real-time Power System Simulator Hydro-Quebec s experience with HYPERSIM Real-time Power System Simulator Christian Larose, Power System Simulation, Hydro-Québec (CANADA) June 26, 2013 Presentation overview > Application of Hypersim at

More information

Standards de planification du NERC

Standards de planification du NERC Demande R-3498-2002 Standards de planification du NERC PREUVE EN CHEF DE TRANSÉNERGIE Original : 2002-11-27 HQT-4, Document 2 (en liasse) NERC PLANNING STANDARDS North American Electric Reliability Council

More information

Rochelle Municipal Utilities TRANSMISSION PLANNING CRITERIA. March 21, 2017

Rochelle Municipal Utilities TRANSMISSION PLANNING CRITERIA. March 21, 2017 Rochelle Municipal Utilities TRANSMISSION PLANNING CRITERIA March 21, 2017 Contents 1 Background...3 2 National and Regional Criteria and Guides...4 2.1 2.1 NERC Transmission Planning Standards...4 2.2

More information

Transfer Capability Methodology. for the Near-Term. Transmission Planning Horizon

Transfer Capability Methodology. for the Near-Term. Transmission Planning Horizon Transfer Capability Methodology for the Near-Term Transmission Planning FAC-013-2 Version 2.2 June 30, 2018 Table of Contents 1 PURPOSE... 3 2 DEFINITION... 3 3 APPLICABILITY... 3 4 TRANSFER CAPABILITY

More information

Mapping Document for FAC-010-3

Mapping Document for FAC-010-3 Mapping Document for FAC-010-3 The Project 2015 09 standard drafting team (SDT) is proposing the retirement of the NERC FAC 010 3 Reliability Standard. The SDT further proposes a new paradigm regarding

More information

Standard 600 Determine Facility Ratings, System Operating Limits, and Transfer Capabilities

Standard 600 Determine Facility Ratings, System Operating Limits, and Transfer Capabilities These definitions will be posted and balloted along with the standard, but will not be restated in the standard. Instead, they will be included in a separate Definitions section containing definitions

More information

Dynamic Reactive Power issue in Wind Integrated Power Systems and LVRT Compliance of WPPs

Dynamic Reactive Power issue in Wind Integrated Power Systems and LVRT Compliance of WPPs Dynamic Reactive Power issue in Wind Integrated Power Systems and LVRT Compliance of WPPs RE integration workshop, Chennai January 23, 2018 Zakir H Rather, IIT Bombay Email: zakir.rather@iitb.ac.in Wind

More information

WWSIS - 3: Western Frequency Response and Transient Stability Study

WWSIS - 3: Western Frequency Response and Transient Stability Study WWSIS - 3: Western Frequency Response and Transient Stability Study GE Energy Nicholas W. Miller (PM) Miaolei Shao Slobodan Pajic Rob D Aquila NREL Kara Clark (PM) NERC ERSTF Briefing Atlanta December

More information

Standard PRC-002-NPCC-01 Disturbance Monitoring

Standard PRC-002-NPCC-01 Disturbance Monitoring A. Introduction 1. Title: Disturbance Monitoring 2. Number: PRC-002-NPCC-01 3. Purpose: Ensure that adequate disturbance data is available to facilitate Bulk Electric System event analyses. All references

More information

ASSOCIATED NERC STANDARD(S): TPL (referred to as TPL-001 in this document) IMPLEMENTATION: In effect when approved.

ASSOCIATED NERC STANDARD(S): TPL (referred to as TPL-001 in this document) IMPLEMENTATION: In effect when approved. ASSOCIATED NERC STANDARD(S): TPL-001-4 (referred to as TPL-001 in this document) IMPLEMENTATION: In effect when approved. Phase in of individual TPL-001 requirements will be based on the effective dates

More information

Criteria. C~/v~ ~ ~ ~ G! " A1A "~"" T"""g"'~10N COr'P""''~ P LG -C R-0001-V T~c~e: Transmission System Planning Criteria

Criteria. C~/v~ ~ ~ ~ G!  A1A ~ Tg'~10N COr'P''~ P LG -C R-0001-V T~c~e: Transmission System Planning Criteria A1A "~"" T"""g"'~10N COr'P""''~ Criteria Department: Document No: System Planning and Strategic Projects P LG -C R-0001-V 19.2 T~c~e: Transmission System Planning Criteria issue gate: Previous Date: February

More information

Investigation of Impacts of Solar PV on Transmission System Voltage Stability Considering Load Characteristics and Protection

Investigation of Impacts of Solar PV on Transmission System Voltage Stability Considering Load Characteristics and Protection 7th Solar Integration Workshop, 24-25 October 2017, Berlin, Germany Investigation of Impacts of Solar PV on Transmission System Voltage Stability Considering Load Characteristics and Protection Baheej

More information

Table of Contents. To provide a methodology for determining the System Operating Limits (SOL) for the Planning Horizon at the California ISO.

Table of Contents. To provide a methodology for determining the System Operating Limits (SOL) for the Planning Horizon at the California ISO. Table of Contents Purpose... 1 Applicable Reliability Standard(s)... 1 Applicability to California ISO... 1 SOLs and IROLs... 1 Study Methodology... 2 Supporting Information... 6 Responsibilities... 6

More information

COLUMBIAGRID 2018 SYSTEM ASSESSMENT DRAFT STUDY PLAN

COLUMBIAGRID 2018 SYSTEM ASSESSMENT DRAFT STUDY PLAN COLUMBIAGRID 2018 SYSTEM ASSESSMENT DRAFT STUDY PLAN January 11, 2018 ColumbiaGrid 8338 NE Alderwood Road, Suite 140 Portland, OR 97220 www.columbiagrid.org (503) 943-4940 8338 NE Alderwood Road, Suite

More information

Mitigation of Voltage Fluctuations in Power System Using STATCOM

Mitigation of Voltage Fluctuations in Power System Using STATCOM RESEARCH ARTICLE OPEN ACCESS Mitigation of Voltage Fluctuations in Power System Using STATCOM M. Venkatesh & Ramakrishna Raghutu Assistant Professors, Dept. of Electrical & Electronics Engineering, GMRIT,

More information

Designated Entity Design Standards Task Force (DEDSTF) Minimum Design Requirements for FERC Order 1000 Projects. System Protection Subgroup

Designated Entity Design Standards Task Force (DEDSTF) Minimum Design Requirements for FERC Order 1000 Projects. System Protection Subgroup Designated Entity Design Standards Task Force (DEDSTF) Minimum Design Requirements for FERC Order 1000 Projects System Protection Subgroup For any substation facility included in the scope of a transmission

More information

Power Plant Model Verification using PMUs

Power Plant Model Verification using PMUs Power Plant Model Verification using PMUs Ryan D. Quint, PhD, PE NASPI Work Group Meeting March 2016 Importance of Accurate Models 2 Verifying Power Plant Component Models 3 MOD-026-1 & MOD-027-1: Verification

More information

WIND TURBINE PLANT CAPABILITIES REPORT

WIND TURBINE PLANT CAPABILITIES REPORT WIND TURBINE PLANT CAPABILITIES REPORT 2013 Wind Integration Studies Published by AEMO Australian Energy Market Operator ABN 94 072 010 327 Copyright 2013 AEMO AEMO 2013 WIND TURBINE PLANT CAPABILITIES

More information

Stakeholder Communication. Inputs, Assumptions, and Preliminary Assessment. Base Model. Needs, Solutions, Sensitivity: Yr 5

Stakeholder Communication. Inputs, Assumptions, and Preliminary Assessment. Base Model. Needs, Solutions, Sensitivity: Yr 5 Methodology and Assumptions 1.1 Overview These sections describe the process we used to perform a network assessment of the ATC transmission system. The description includes study assumptions, methods

More information

Standard Development Timeline

Standard Development Timeline Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard is adopted by the NERC Board of Trustees (Board).

More information

Regulation and Frequency Response Service Capability of Modern Wind Power Plants

Regulation and Frequency Response Service Capability of Modern Wind Power Plants 1 Regulation and Frequency Response Service Capability of Modern Wind Power Plants Germán Claudio Tarnowski, Philip Carne Kjær, Søren Dalsgaard, Anders Nyborg Technology R&D, Vestas Wind Systems A/S, Denmark

More information

Recent US Wind Interconnection Experience

Recent US Wind Interconnection Experience Wind Energy and Grid Integration Recent US Wind Interconnection Experience J. Charles Smith Nexgen Energy LLC Utility Wind Integration Group January 24-25, 2006 Madrid, Spain Outline of Topics Background

More information

Platte River Power Authority. Ten-Year Transmission Plan ( )

Platte River Power Authority. Ten-Year Transmission Plan ( ) Platte River Power Authority Ten-Year Transmission Plan (2015-2024) Prepared by PRPA System Planning December 31, 2014 Table of Contents I. Executive Summary II. III. IV. Scope Assumptions Criteria V.

More information

WIND TURBINES IN WEAK GRIDS CONSTRAINTS AND SOLUTIONS. J O G Tande and K Uhlen. SINTEF Energy Research, Norway SUMMARY

WIND TURBINES IN WEAK GRIDS CONSTRAINTS AND SOLUTIONS. J O G Tande and K Uhlen. SINTEF Energy Research, Norway SUMMARY WIND TURBINES IN WEAK GRIDS CONSTRAINTS AND SOLUTIONS J O G Tande and K Uhlen SINTEF Energy Research, Norway SUMMARY Cost efficient utilisation of the wind energy resource requires wind farms to be located

More information

SSR STUDY REPORT FINAL

SSR STUDY REPORT FINAL System Support Resource Study Escanaba 1 & 2: 25 MW Coal 36 Month Suspension 6/15/2012 6/15/2015 SSR STUDY REPORT FINAL June 21, 2012 Redacted version for January 3, 2013 filing EXECUTIVE SUMMARY An Attachment

More information

Standard TPL (i) System Performance Under Normal Conditions

Standard TPL (i) System Performance Under Normal Conditions Standard TPL-001-0.1(i) System Performance Under rmal Conditions A. Introduction 1. Title: System Performance Under rmal ( Contingency) Conditions (Category A) 2. Number: TPL-001-0.1(i) 3. Purpose: System

More information

Research Co-design Activity

Research Co-design Activity Research Co-design Activity A. Purpose of Co-design: The ultimate goals of this co-design activity are to: Directly involve all members of a group to make decisions together that would affect their daily

More information

ReliabilityFirst Regional Criteria 1. Verification and Data Reporting of Generator Gross and Net Reactive Power Capability

ReliabilityFirst Regional Criteria 1. Verification and Data Reporting of Generator Gross and Net Reactive Power Capability ReliabilityFirst Regional Criteria 1 Verification and Data Reporting of Generator Gross and Net Reactive Power Capability 1 A ReliabilityFirst Board of Directors approved good utility practice document

More information

Analysis of System Stability in Developing and Emerging Countries

Analysis of System Stability in Developing and Emerging Countries Analysis of System Stability in Developing and Emerging Countries Impact of Variable Renewable Energies on Power System Reliability and System Security Table of Contents 1 Background... 4 2 Reliability

More information

Harnessing Renewables in Power System Restoration

Harnessing Renewables in Power System Restoration Harnessing Renewables in Power System Restoration Dr. Wei Sun, and Amir Golshani Assistant Professor, EECS Dept. University of Central Florida (South Dakota State University) Panel: Cascading Failures:

More information

Interconnection of Distributed Generators and Their Influences on Power System

Interconnection of Distributed Generators and Their Influences on Power System International Energy Journal: Vol. 6, No. 1, Part 3, June 2005 3-127 Interconnection of Distributed Generators and Their Influences on Power System www.serd.ait.ac.th/reric Vu Van Thong, Johan Driesen,

More information

POWER SYSTEM AND ASSET MODELS

POWER SYSTEM AND ASSET MODELS POWER SYSTEM AND ASSET MODELS OPAL-RT SEMINAR MODEL-BASED DESIGN FOR SMART GRID APPLICATIONS 16/03/2017 DR. FLORIN IOV Content Distribution Grids Models Balance of Plants Wind Power Transmission System

More information

SECURITY ASPECTS OF MULTI AREA ECONOMIC DISPATCH WITH RENEWABLE ENERGY AND HVDC TIE LINES.

SECURITY ASPECTS OF MULTI AREA ECONOMIC DISPATCH WITH RENEWABLE ENERGY AND HVDC TIE LINES. SECURITY ASPECTS OF MULTI AREA ECONOMIC DISPATCH WITH RENEWABLE ENERGY AND HVDC TIE LINES. PROJECT INDEX: 134. PRESENTED BY KIPKOECH C. JOHN. SUPERVISOR: MR. PETER MOSES MUSAU. EXAMINER: DR. CYRUS WEKESA.

More information

Operating High Variable, Renewable Generation Power Systems Lessons Learned from Ireland and Northern Ireland

Operating High Variable, Renewable Generation Power Systems Lessons Learned from Ireland and Northern Ireland Operating High Variable, Renewable Generation Power Systems Lessons Learned from Ireland and Northern Ireland 16 th September 2015 Overview 2 EirGrid s Role EirGrid is the Transmission System Operator

More information

Technical considerations for integration of distributed renewables on the grid

Technical considerations for integration of distributed renewables on the grid Technical considerations for integration of distributed renewables on the grid A paper by Dr Charlotte Higgins, Dr Bunmi Adefajo & Kumbuyani Chisoro Kumbuyani Chisoro Manager Southern Africa TNEI Services

More information

MAY 1, Variable Generation Integration Costs

MAY 1, Variable Generation Integration Costs MAY 1, 2014 Variable Generation Integration Costs Executive Summary The addition of variable generation (wind and solar) to the electrical system introduces additional costs associated with unit dispatch

More information

Standard MOD Verification of Models and Data for Generator Excitation Control Sys tem or Plant Volt/Var Control Functions

Standard MOD Verification of Models and Data for Generator Excitation Control Sys tem or Plant Volt/Var Control Functions Standard MOD-026-1 Verification of Models and Data for Generator Excitation Control Sys tem or Plant Volt/Var Control Functions Standard Development Roadmap This section is maintained by the drafting team

More information

SPP RTO Compliance Forum TPL Jason Terhune

SPP RTO Compliance Forum TPL Jason Terhune SPP RTO Compliance Forum TPL-001-4 Jason Terhune 501-688-8261 jterhune@spp.org 1 TPL Standards have been Consolidated TPL-001-0.1 TPL-002-0b TPL-003-0b TPL-004-0a TPL-001-4 R1 R2 R3 R4 R5 R6 R7 R8 2 Overview

More information

Transmission System Security and Planning Standards

Transmission System Security and Planning Standards ver. 1.4 page 1 from 13 Transmission System Security and Planning Standards April 2014 ver. 1.4 page 2 from 13 TABLE OF CONTENTS 1 Introduction... 4 2 Definitions... 4 2.1 Transmission System... 4 2.2

More information

UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION COMMENTS OF NATIONAL HYDROPOWER ASSOCIATION

UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION COMMENTS OF NATIONAL HYDROPOWER ASSOCIATION UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION Electric Storage Participation in Regions ) with Wholesale Electric Markets ) Docket No. AD16-20-000 COMMENTS OF NATIONAL HYDROPOWER ASSOCIATION

More information

I Department: System Planning and Strategic Projects. Methodology

I Department: System Planning and Strategic Projects. Methodology ~, I Department: System Planning and Strategic Projects AMENICAN TIIANSMISSION CONPANY~~ Methodology Document No: P LG -M ETH'OOO?'V7 T~cie: Transmission Planning Assessment Practices issue gate: January

More information

Standard Development Roadmap

Standard Development Roadmap Standard Development Roadmap This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed:

More information

SYSTEM OPERATING LIMITS IN THE PLANNING HORIZON FAC-010 COMPLIANCE

SYSTEM OPERATING LIMITS IN THE PLANNING HORIZON FAC-010 COMPLIANCE SYSTEM OPERATING LIMITS IN THE PLANNING HORIZON FAC-010 COMPLIANCE System Operating Limits (SOLs) in the planning horizon are required to be identified by FAC-010. This guideline describes how Duke Energy

More information

Page 1 of 5 Version 1

Page 1 of 5 Version 1 GREATER BAY AREA BLACKSTART TECHNICAL VARIABLES and CRITERIA Geographic Area of Consideration Upon the loss of AC to the Greater Bay Area (GBA), the potential blackstart resource must support the restoration

More information

Power Quality and Voltage Stability of Power Systems with a large share of Distributed Energy Resources

Power Quality and Voltage Stability of Power Systems with a large share of Distributed Energy Resources University of Texas at Tyler Scholar Works at UT Tyler Electrical Engineering Theses Electrical Engineering Spring 4-30-2012 Power Quality and Voltage Stability of Power Systems with a large share of Distributed

More information

Grid Connection and Power Quality Optimization of Wind Power Plants

Grid Connection and Power Quality Optimization of Wind Power Plants Grid Connection and Power Quality Optimization of Wind Power Plants Fikri Baris UZUNLAR 1, Onder GULER 2, Ozcan KALENDERLI 3 1, 2 Istanbul Technical University, Energy Institute, Istanbul, Turkey barisuzunlar@hotmail.com,

More information

California Independent System Operator Corporation Fifth Replacement Tariff

California Independent System Operator Corporation Fifth Replacement Tariff Table of Contents Method to Assess Available Transfer Capability... 2 L.1 Description of Terms... 2 L.1.1 Available Transfer Capability (ATC)... 2 L.1.2 Total Transfer Capability (TTC)... 2 L.1.3 Existing

More information

California Independent System Operator Corporation Fifth Replacement Tariff

California Independent System Operator Corporation Fifth Replacement Tariff Table of Contents Method to Assess Available Transfer Capability... 2 L.1 Description of Terms... 2 L.1.1 Available Transfer Capability (ATC)... 2 L.1.2 Total Transfer Capability (TTC)... 2 L.1.3 Existing

More information

Generation Interconnection System Impact Study Report. For. PJM Generation Interconnection Request Queue Position AA1-038

Generation Interconnection System Impact Study Report. For. PJM Generation Interconnection Request Queue Position AA1-038 Generation Interconnection System Impact Study Report For PJM Generation Interconnection Request Queue Position AA1-038 Lexington Low Moor 230kV 10.1MW Capacity / 78.2MW Energy September / 2015 Introduction

More information

WESTERN ELECTRICITY COORDINATING COUNCIL GENERATING UNIT MODEL VALIDATION POLICY

WESTERN ELECTRICITY COORDINATING COUNCIL GENERATING UNIT MODEL VALIDATION POLICY WESTERN ELECTRICITY COORDINATING COUNCIL GENERATING UNIT MODEL VALIDATION POLICY A. Introduction A.1. Title: Generating Unit Model Validation Policy A.2. Purpose: Accurate models of generators and associated

More information

State of the Ar t. May Utility Wind Integration Group. American Public Power Association. Edison Electric Institute

State of the Ar t. May Utility Wind Integration Group. American Public Power Association. Edison Electric Institute Utility Wind Integration State of the Ar t Prepared By: Utility Wind Integration Group in cooperation with American Public Power Association Edison Electric Institute National Rural Electric Cooperative

More information

~2~ ~ i. Methodology """ '~"" T"""S""~' " ~ " """~ P LG -METH V7.2

~2~ ~ i. Methodology  '~ TS~'  ~  ~ P LG -METH V7.2 """ '~"" T"""S""~' " ~ " """~ Methodology Department: Document No: System Planning and Strategic Projects P LG -METH -0002-V7.2 T~t~e: Transmission Planning Assessment Practices issue gate: February 6,

More information

TSOs, taking into account the following: Whereas

TSOs, taking into account the following: Whereas All TSOs proposal for a common grid model methodology in accordance with Articles 67(1) and 70(1) of Commission Regulation (EU) 2017/1485 of 02 August 2017 establishing a guideline on electricity transmission

More information

Collaborative Approach for Wind Power Plant Model Data and Validation

Collaborative Approach for Wind Power Plant Model Data and Validation Collaborative Approach for Wind Power Plant Model Data and Validation Dmitry Kosterev, Steve Yang and Gordon Kawaley, BPA WECC MVWG October 5, 2017 1 Regulatory Landscape NERC MOD-032 Data for Power System

More information

DRAFT STUDY PLAN FOR 2018

DRAFT STUDY PLAN FOR 2018 DRAFT STUDY PLAN FOR 2018 Introduction The Ten-year transmission planning process is intended to facilitate a timely, coordinated and transparent process that fosters the development of electric infrastructure

More information

2012 Grid of the Future Symposium. Modeling and Simulation of Advanced Reactive Compensation Systems in Renewable Energy Applications

2012 Grid of the Future Symposium. Modeling and Simulation of Advanced Reactive Compensation Systems in Renewable Energy Applications , rue d Artois, F78 PARIS CIGRE US National Committee http : //www.cigre.org Grid of the Future Symposium Modeling and Simulation of Advanced Reactive Compensation Systems in Renewable Energy Applications

More information

AESO TRANSMISSION PLANNING CRITERIA BASIS AND ASSUMPTIONS

AESO TRANSMISSION PLANNING CRITERIA BASIS AND ASSUMPTIONS APPENDIX G AESO TRANSMISSION PLANNING CRITERIA BASIS AND ASSUMPTIONS Transmission Planning Criteria - Basis and Assumptions Version 1.0 1. Introduction This document presents the reliability standards,

More information

Methodological Application to Integrate Renewable Energy Resource into Kuwait s Electrical Grid

Methodological Application to Integrate Renewable Energy Resource into Kuwait s Electrical Grid Methodological Application to Integrate Renewable Energy Resource into Kuwait s Electrical Grid Adel Qabazard Energy and Building Research Center Kuwait Institute for Scientific Research P. O. Box 24885,

More information

Large-scale Integration of Distributed Energy Resources within Electric Power Systems. Danish Cell Controller Project Brief

Large-scale Integration of Distributed Energy Resources within Electric Power Systems. Danish Cell Controller Project Brief Large-scale Integration of Distributed Energy Resources within Electric Power Systems Danish Cell Controller Project Brief Project Introduction Energinet.dk Owns/Operates High Voltage Electric Power System

More information

Impacts of the Decentralized Wind Energy Resources on the Grid

Impacts of the Decentralized Wind Energy Resources on the Grid 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2013 Grid of the Future Symposium Impacts of the Decentralized Wind Energy Resources on the Grid Babak Enayati, PhD, Senior

More information

Comparative Analysis between IG and DFIG for Wind Energy Conversion Systems using STATCOM

Comparative Analysis between IG and DFIG for Wind Energy Conversion Systems using STATCOM International Journal of Energy and Power Engineering 2014; 3(6-2): 21-26 Published online November 27, 2014 (http://www.sciencepublishinggroup.com/j/ijepe) doi: 10.11648/j.ijepe.s.2014030602.14 ISSN:

More information

Regional Impact of Renewables: ERCOT

Regional Impact of Renewables: ERCOT Regional Impact of Renewables: ERCOT Kenan Ögelman VP, Commercial Operations, ERCOT February 1, 2018 The ERCOT Region The interconnected electrical system serving most of Texas, with limited external connections

More information

Emerging ancillary service products in large-scale renewable energy integrated system

Emerging ancillary service products in large-scale renewable energy integrated system Emerging ancillary service products in large-scale renewable energy integrated system Zakir H Rather Dept. of Energy Science and Engineering, IIT Bombay, India 1 st international conference on Large-Scale

More information

Inverter-Based Resources During a Cascading Failure: Present State and Future State

Inverter-Based Resources During a Cascading Failure: Present State and Future State 1 Inverter-Based Resources During a Cascading Failure: Present State and Future State IEEE PES GM 2018 - CFWG Panel 08/08/2018, Portland, OR Ryan Quint, NERC (ryan.quint@nerc.net) Andrew Groom, AEMO (andrew.groom@aemo.com.au)

More information

SESSION 3: Grid Integration Studies for Planning Secure and Reliable System Operations with Expected Shares of Variable Renewables

SESSION 3: Grid Integration Studies for Planning Secure and Reliable System Operations with Expected Shares of Variable Renewables SESSION 3: Grid Integration Studies for Planning Secure and Reliable System Operations with Expected Shares of Variable Renewables Presenter: Eduard Muljadi National Renewable Energy Laboratory 15013 Denver

More information

POWER QUALITY ASPECTS IN A WIND POWER PLANT IMAMHUSEN M PATIL. MASTER OF TECHNOLOGY IN ELECTRICAL ENGINEERING (Computer Controlled Industrial Power)

POWER QUALITY ASPECTS IN A WIND POWER PLANT IMAMHUSEN M PATIL. MASTER OF TECHNOLOGY IN ELECTRICAL ENGINEERING (Computer Controlled Industrial Power) POWER QUALITY ASPECTS IN A WIND POWER PLANT A THESIS Submitted by IMAMHUSEN M PATIL In partial fulfillment for the award of the Degree of MASTER OF TECHNOLOGY IN ELECTRICAL ENGINEERING (Computer Controlled

More information

POTOMAC ELECTRIC POWER COMPANY

POTOMAC ELECTRIC POWER COMPANY POTOMAC ELECTRIC POWER COMPANY FERC Form 715 (Part 4) - Transmission Planning Study Guidelines Transmission Reliability Guidelines 1. General Overview The reliability guidelines used to plan the transmission

More information

Dynamic Response of Large Wind Power Plant Affected by Diverse Conditions at Individual Turbines

Dynamic Response of Large Wind Power Plant Affected by Diverse Conditions at Individual Turbines Dynamic Response of Large Wind Power Plant Affected by Diverse Conditions at Individual Turbines Marcelo A. Elizondo Pacific Northwest National Laboratory Seattle, Washington USA Marcelo.Elizondo@pnnl.gov

More information

Dynamic Compensation of Reactive Power for Integration of Wind Power in a Weak Distribution Network

Dynamic Compensation of Reactive Power for Integration of Wind Power in a Weak Distribution Network INTERNTIONL ONFERENE ON ONTROL, UTOMTION, OMMUNITION ND ENERGY ONSERVTION -2009, 4th-6 th June 2009 Dynamic ompensation of Reactive Power for Integration of Wind Power in a Weak Distribution Network 1

More information

TABLE OF CONTENTS. UNCONTROLLED WHEN PRINTED 2 USA Operations

TABLE OF CONTENTS. UNCONTROLLED WHEN PRINTED 2 USA Operations National Grid 2010 TGP28 Issue 3 22 November TABLE OF CONTENTS 1.0 Change Control...3 2.0 Introduction...4 3.0 System Studies...6 4.0 Design Criteria...15 5.0 Interconnection Design Requirements...21 6.0

More information

500 MW Wind Farm Technical System Impact Study

500 MW Wind Farm Technical System Impact Study FINAL REPORT Report to: El Paso Electric for 500 MW Wind Farm Technical System Impact Study Prepared by: Goran Drobnjak Sang Lee Emad Ahmed Reigh Walling Einar Larsen February 19, 2008 EPE_TechSIS_Final.doc

More information

Planning Coordinator and/or Transmission Planner TRANSMISSION SYSTEM PLANNING GUIDELINES

Planning Coordinator and/or Transmission Planner TRANSMISSION SYSTEM PLANNING GUIDELINES Planning Coordinator and/or Transmission Planner TRANSMISSION SYSTEM PLANNING GUIDELINES Effective Date: September 11, 2017 Revision History Date Version Description June 6, 1998 0.0 Initial LGEE document

More information

PID 276 Feasibility Study Report 4.4MW Distribution Inter-Connection Mermentau Substation

PID 276 Feasibility Study Report 4.4MW Distribution Inter-Connection Mermentau Substation PID 276 Feasibility Study Report 4.4MW Distribution Inter-Connection Mermentau Substation Prepared by: Entergy Services, Inc. T & D Planning 639 Loyola Avenue New Orleans, LA 70113 Rev Issue Date Description

More information

Preferential Subjects for the 2010 Session

Preferential Subjects for the 2010 Session Preferential Subjects for the 2010 Session Study Committee A1 PS1: Developments in Electrical Machine Design and Experience in Service New trends in design, materials, insulation, cooling and bearings

More information