Technical Specifications: Measurable Metarial. Supply Signal Output

Size: px
Start display at page:

Download "Technical Specifications: Measurable Metarial. Supply Signal Output"

Transcription

1 ECAPm level transmitter is a capacitive level sensor for level measurement of conductive liquid, nonconductive liquid, granulated materials with solid particles, adhesive and acid/basic liquids. When a material comes between electrode rod and tank wall, a capacitance change occurs and when this change exceed adjustment threshold, contact output is delivered. Full-empty calibration can be performed easily and safely. Different designs and different solution related to industrial level measurement are offered especially for machinery manufacturers. Application Areas iquid tanks, food machines, cooling liquid tanks, shipping, glycol tanks, brine, waste water tanks. Oil tanks, CO2 liquid tanks, high temperature tanks, non-conductive liquids. Grain stores, cement, sand feed, flour, milk powder, organic and plastic granule. ticky hot and high viscosity liquid, acid and chemical liquids. ECAPm CAPACITIVE EVE TRANMITTER ECAPm 101 ECAPm 203 ECAPm 305 ECAPm 408B, 408T, 408Tm There are no moving parts. High pressure and temperature resistant design. Modular structure with easy assembly. Not affected by foam, liquid splashes. Not affected by vibration, has robust mechanical structure. Zero span adjustment is easy. Measurement along whole sensor. Operability with reverse assembly. Technical pecifications: Measurable Metarial upply ignal Output Accuracy inearity Capacity Range Min. Di-Electric Constant Connection Metarial Isolation Material Housing Material Working Pressure Working Temperature Ambient Temperature Display Power Consumption Electrical Connection Protection Class(EN60529) Test Max.Tensile Force Weight Conductive liquids ow conductive liquids olids particulate materials Adhesive and acid/basic liquids VDC 4-20mA two wire td. 0-20mA mA, 0-10 V three wire Opt. % 0,5, % 0,8, % %0,5 1pF...3nF 1,6 e r Opt.316 td.opt. PTFE Aluminium Max.150 bar (Depending on the model) (-) 30 / (+) 150 º C ((Depending on the model) 200 º C with cooling apparatus (-)20 / (+) 60 o C With ED-Power and Contact ED Max. 50mW Treminal IP 65 EMC, ow voltage Max. 40 NM 1000 g. for ECAPm mm ECAP

2 Working Principle : Capacitance definition, assuming two parallel conductive plates are used; C= e o. e r. d Ýzolasyon C: Capacity, Farad : urface Area, m2 d: Distance, m d C R Metal Tank However, there are scarcely any sensor type which this definition can be pratically utilized. Above Formula can no longer bi reliable especially when residual areas increase due to large distance (d) (which is usually the case). Thus, measuring impedance for distance measurements give more accurate results than capacitance measurement. Capacity Impedance Excitation applied between 10KHz 250KHz based on length for all our models. ( =2xpxf) inearity error that may be caused by conductivity component (R) effect is prevented by electronic circuit design and mechanical design. Reduced to a level lower than e 1ppm, acceptable as zero. Distance Distance P proses (bar) Process Pressure / Temperature Chart With Cooling Apparatus Tproses ( C) T ortam ( C) 80 Ambiance Pressure / Temperature Chart With Cooling Apparatus Tproses ( C) 2 ECAP

3 Application Examples : Hooter R mA / V / 1-5V /.. R1 / R2 / R3 / R4 %100 %0 Conductive iquid ow Conductive iquid olids Particulate Material Adhesive and Acid / Basic iquid % 100 % 100 Measure Range Can be etting Measure Range Can be etting * Measuring range can be set 1/10 during probe. *Can be mounted upside. Zero Point Can be etting Zero Point Can be etting % 0 % 0 3 ECAP

4 Parts : crew Caps Cap eal Electronic Card Cable Gland Housing Extension Pipe Connection Fully Insulated Probe Electrical Connection : 4-20mA Two Wire 4-20mA / 0-20mA Three Wire 0-10V Three Wire 4mA 20mA 4 ma 0 ma 20mA 20mA 0 V 10 V Z Z Z 12-36VDC oad 12-36VDC 12-36VDC 4-20mA 4-20mA 0-20mA 0-10V Calibration : Z: Measuring starting point - 4mA (zero) : Measuring peak point - 20mA (span) Zero adjustment (z): 4mA adjustment is performed at factory exit, assuming tank is completely empty. If adjustment is needed again, 4mA output adjustment can be performed by Z trimmer after the tank is filled until initial level. Measurement field (span) adjustment: 20mA is adjusted at factory exit, assuming tank is filled up to length of electrode. If adjustment is needed again, 20mA output adjustment can be performed by trimmer after filling the tank up to a desired level. 4 ECAP

5 B035 Housing : TYPE MATERIA PROTECTION CA TEMPERATURE ( o C) IZE a x b x c (mm) B035 Aluminum IP 65 With eal x 36 Mechanical Connection : (IO228-1) Thread Hex Dimension B Hex [mm] crew enght b [mm] b B 1/2 BP 3/4 BP 1 BP 1 1/4 BP 1 1/2 BP 2 BP Electronic Unit with Cable: Electronic unit and sensor component can be separated by a cable protected against exterior conditions for easy calibration on site. Cable provides easy assembly for user by its property not affecting capacitive measurement. ample Model : Cooling : For Max.200 C Hex 1/2 BP 5 ECAP

6 ample Models : CONDUCTIVE IQUID ECAPm 101 Fully Insulated Probe Conductive Tank OW CONDUCTIVE IQUID ECAPm 203 Coaxial Probe Conductive / Insulating Tank OID PARTICE IQUID ECAPm 305 Partly Insulated Probe Conductive Tank Max.80 mm 27 Hex Max.80 mm 27 Hex Max.80 mm 41 Hex 1/2 BP 1/2 BP 1 BP PTFE Ø12 =Max. 1m bar Max.150 C YADHEIVE AND ACID / BAIC IQUID =Max. 1m bar Max.+150 C YADHEIVE AND ACID / BAIC IQUID =Max. 1m bar Max.+150 C ECAPm 408B Double Probe - Without Partly Insulated Conductive / Insulating Tank ECAPm 408Tm / 408T Double Probe - Without Partly Insulated Conductive / Insulating Tank Max.50 mm Delrin 46 Hex 1 BP Max.50 mm PVDF/PBT 46 Hex 1 BP Ø4 Ø4 =Max. 1m bar Max.80 C =Max. 1m./150 C bar Max.120 C 6 ECAP

7 Order Form : Please consider sample models when coding. MODE ECAPm Conductive iquids...1 ow Conductive iquids...2 olids Particulate Materials...3 Adhesive and Acid/Basic iquids CERTIFICATE No PROBE TYPE ingle Probe - Insulated (Max.1000mm)...1 Coaxial Probe (Max 1000mm)...Ø13 or 21mm...3 ingle Probe - Partly Insulated (Max.1000mm)... 5 Double Probe - Without Partly Insulated (Max.1000mm)...8B Double Probe - Double Insulated (Max.1000mm)...8T Double Probe - Double Fully Insulated (Max.1000mm)...8Tm pecial...x 4 TEM ENGHT...mm PROCE TEMPERATURE 150 C tandard C with Cooling Apparatus...1 CONNECTION Theread (IO 228-1) 1/2 BP /4 BP BP /4 BP /2 BP C For Plastic (Delrin) Model C For Plastic (PVDF) Model C For Plastic (PBT) Model BP /2 NPT /4 NPT NPT OUTPUT 4-20mA Two Wire mA Three Wire V Three Wire mA Three Wire ohm ohm ohm...25 pecial...x Aluminium...B035 pecial...x 8 HOUING 9 INUATION MATERIA 10 PTFE...10 PEEK...11 Ceramic...12 Polyamide...13 PBT...14 CONNECTION MATERIA 316 tainless teel...02 Brass...03 Delrin...09 PTFE OPTIONA...17 Rubber...18 FKM...19 pecial...x PBT...14 PVDF...15 Polypropylene...16 pecial...x No.../ 0 By - Pass Tube.../ T eperable Electronic Unit.../ Wall Apparatus.../ W AMPE ECAPm mm B / 0 For Cond. iquid, =300mm, 1 BP, 0-10V, Aluminium Housing