DEVELOPMENT OF A GAS-FIRED DOMESTIC HEAT PUMP

Size: px
Start display at page:

Download "DEVELOPMENT OF A GAS-FIRED DOMESTIC HEAT PUMP"

Transcription

1 DEVELOPMENT OF A GAS-FIRED DOMESTIC HEAT PUMP Robert E. Critoph Steven J. Metcalf School of Engineering University of Warwick Coventry CV4 7AL, UK R.E.Critoph@warwick.ac.uk ABSTRACT An air source gas-fired heat pump system intended to replace conventional condensing boilers is under development. The adsorption cycle uses ammonia refrigerant and activated carbon sorbent in four reactors with heat and mass recovery and has a nominal heat output of 7kW. Predicted annual average COP based on gross calorific value is 1.35 in a UK application with low temperature radiators. If this new technology were takenup across the UK it would result in an 8% reduction in UK carbon emissions. The system is described together with the simulation model, the test facilities and procedures. Initial test results are approximately 10% below predicted values but improved valves are expected to yield the target COP levels when system tests resume in April Desorption phase Adsorption phase 1. INTRODUCTION The technology being developed is that of adsorption cycle heat pumps. Adsorption cycles may be used as the basis of heat driven refrigerators, air conditioners or heat pumps. The high temperature heat used to power the machines can be from waste heat, solar thermal heat or, as in this application, combustion of a fossil fuel. They rely upon the periodic heating and cooling of adsorbent within reactors referred to as sorption generators. In its simplest form (Fig. 1) an adsorption heat pump consists of two linked vessels, one of which contains adsorbent (in our case active carbon) and both of which contain refrigerant (in our case, ammonia). Initially the system is at low pressure and temperature, the adsorbent has a high concentration of refrigerant within it Fig. 1: Basic adsorption cycle heat pump and the other vessel contains refrigerant gas. The adsorbent vessel (generator) is heated, driving out refrigerant and raising the system pressure. The desorbed refrigerant condenses as a liquid in the second vessel, producing useful heat output. Finally the generator is cooled back to ambient temperature, simultaneously readsorbing the refrigerant, reducing the pressure and 1

2 producing useful heat output. The low pressure in the second vessel causes refrigerant to boil, taking in low temperature heat from the environment. In the drive to develop products and systems that will result in major energy end use reductions the development of domestic sorption heat pumps has a long history and many variations have been tried. One of the earliest attempts was by Shelton and the Wave-Air company (1). More recently products are being developed by Vaillant, Viessmann and Robur (2). The work described here has been carried out by the University of Warwick as part of a project called CALEBRE (Consumer Appealing Low Energy Technology for Building Retrofit) funded by EPSRC and EoN and is the subject of further development by Sorption Energy Ltd. The concept is an affordable air source sorption heat pump that can replace a conventional gas-fired boiler and reduce gas consumption by over one third Choice of Cycle The refrigerant chosen is ammonia, because of its ability to operate well below 0ºC and its high working pressure being an advantage in compact equipment due to the implied low pressure drops. The sorbent is active carbon, although many other solid or liquid sorbents might be used. There are a large number of possible cycles, ranging from Shelton s original thermal wave, through variations proposed by Critoph (3,4,5), Critoph and Thorpe (6) to isothermal beds with heat recovery Meunier (7). Metcalf (8) carried out modelling to determine the advantages of various cycle types in an objective way. Specifically, he compared a 2-bed cycle with heat and mass transfer between beds, a 4-bed cycle with 3 stages of regenerative heating/cooling between beds and a modular thermal wave cycle from (5). These results are shown in Fig. 2. Each line for a system shows the best combination of COP and Specific Heating Power (SHP in Watts per unit mass of adsorbent) that can be obtained when using the optimum cycle time. The conditions used were 200 C input from the gas heat exchanger, 40 C condensing and adsorber inlet water, 5 C evaporating temperature. It can be seen that whilst the thermal wave can deliver very high heating COP s it has a correspondingly very low SHP which would imply a very large and costly machine (per unit of heating power). At the other extreme a simple two bed system with heat recovery and mass recovery between beds has much higher SHP s although lower COP s. This lead to consideration of a four bed cycle. The four bed performance envelope is superior to that of the thermal wave for COP s less than 1.66 (SHP about 750 W/kg) and gives way to the two bed system for COP s less than 1.4 (SHP about 3200 W/kg). It was decided not to Figure 2 Cycle comparison in a heat pump application look at even larger numbers of beds since the mechanical complexity of valves and pumps would be excessive. Similar comparisons can be made for different operating conditions but the conclusion made was that a four bed cycle was most suitable for a domestic heat pump system. It requires complex valves and extra pumps but in the range of interest the COP is about 25% higher than that of a two bed design Description of four bed cycle The operation of a four bed system is described in more detail in Fig. 3. (a) (b) (c) (d) (e) (f) Figure 3 Processes in a four bed cycle. The six parts of the figure show progress through half the cycle. In the first part (a) Bed 1 has reached the maximum temperature. Mass recovery is carried out by opening a valve to Bed 4, resulting in further desorption from 1 and adsorption in 4. In (b) to (c) high temperature heat recovery is carried out between 1 and 2 and low temperature heat recovery between 3 and 4. From (c) to (d) high temperature (driving) heat goes to Bed 2, heat is rejected from Bed 3 and medium temperature heat 2

3 recovery occurs between Beds 1 and 4. In (d) mass recovery is carried out between 2 and 3. In (e) to (f) high temperature heat recovery is carried out between 2 and 4 and low temperature heat recovery between 1 and 3. Finally in (f) high temperature (driving) heat goes to Bed 4, heat is rejected from Bed 1 and medium temperature heat recovery occurs between Beds 2 and 3. This is half the cycle in which Bed 1 has gone from maximum to minimum temperature and Bed 4 has gone from minimum to maximum temperature. The second half continues in similar fashion to complete the cycle. Such an arrangement demands five pumps: one each for the source and sink and three for heat recovery. Obviously their electricity consumption must be minimised but in principle the pumping power can be very low. 2. MODELLING AND DESIGN 2.1. Modelling A simulation model of a four bed system has been validated by Metcalf (9) and used to generate the predicted performance data of Fig. 4. The machine was designed around a specification for a typical UK house that had been retrofitted with good insulation to the point that the heat pump needed to deliver 7kW of heat. Assuming the UK climate and heat delivery at 50 C to low temperature radiators the calculated mean annual COP based on the higher calorific value of gas burnt would be Carbon packed between 1.2 mm tubes Fig. 5 Generator core. Water flow Fig. 6 Complete generator. Figure 4 Predicted COP (HCV) v. delivery temperature and ambient air temperature 2.2. Component design Previous sorption generators [10] have used plate shim designs but theoretical modelling suggests that a shell and micro-tube construction could have less thermal mass and equivalent heat transfer. The core of such a heat exchanger is shown in Fig. 5 and fully assembled in Fig. 6. The four generators form a sub-assembly as shown in the drawing of Fig. 7. The module consists of the generators, ammonia check valves that connect to the evaporator and condenser and the mass recovery solenoid valves. Fig. 7 Generator module in Solidworks. Fig. 8 shows the complete unit as originally built but without insulation. It is designed as a single unit to be installed outside the house with water, gas and electrical connections being made through the wall. 3

4 The COP (based on LCV) is plotted for three output temperatures. It was not possible to operate the burner at low enough power at 170ºC and the mean output temperature was 146ºC. The COP s are adjusted to take out the measured heat losses from the valve array and then compared with the simulation shown in the upper line (170º) and the line below which is the simulation at 146ºC. Although after adjustment the simulation and actual results were in reasonable agreement, the decision was taken to develop a water valve closer to a production version to improve the performance. The new design is a ceramic disc valve in which modular disc pairs constitute a five port valve. The valve bodies are machined from an engineering polymer to reduce both internal and external heat leakage. The overall size of each of the two valves is 100mm diameter and 150mm long. Fig. 8 Prototype heat pump. The gas burner and heat exchanger were developed especially for this project and can modulate from 3 to 11 kw heat output of pressurized water at 170 C with a gross efficiency exceeding 80%. The unit was tested outside the heat pump and performed well. It delivers the pressurised water supplied to any of the four beds via the water valve assemblies. The water valve assemblies were very complex. Each is the equivalent of a 4-pole 5-way switch. They have 8 positions during a complete cycle and individual poppet valves are actuated by push rods driven by a cam shaft. This was intended to be a comparatively risk free design but not suitable for production. In mid-march 2012 the new valves are complete and the prototype is being re-commissioned. FUTURE DEVELOPMENT In order to make a major impact on carbon emissions a complete gas heat pump package must be applicable in as wide a range of applications as possible. In European markets this demands a system with minimal volume. Discussions with potential manufacturing partners and consumer studies imply that a split system is required, consisting of an external air source evaporator and an internal package that is no larger than a conventional gas boiler. This is technically feasible and a mock-up is shown in Fig PROGRESS TO MARCH 2012 Initial running in May 2011 successfully produced output water at 60 C. The machine functioned as per design but excessive heat losses and internal leakage from the valve assemblies lead us to a re-design before further tests. We first tried an array [2 x 5 x 4] of pneumatically operated valves. They were commissioned in September 2011 and testing begun. No internal leakage occurred but thermal mass and heat loss from the large assembly were still an issue. Results are given in Fig. 9. Fig. 10 Future concept, Indoor Unit In applications where a failed boiler is being replaced (there are at least 900,000 such in the UK each year), payback times should be less than three years and fuel savings of at least 30% are possible. Fig. 9 Experimental and simulated COP (LCV) ACKNOWLEDGEMENTS The project has been funded by EPSRC / EoN project 4

5 EP/G00387/1 and by the EPSRC Follow on Fund project EP/G00387/1. Instrumentation and test chambers are made available by the AWM / ERDF Birmingham Science City project. REFERENCES 1. Shelton S.V., 1986, United States patent No. 4,610,148, Solid adsorbent heat pump system. 2. Albus R., Nitschke-Kowsky, P., Wessing, W., 2009, Gas heat pumps A chance for the heat energy market in Germany, proc. Heat Powered Cycles 2009, 7th-9th September 2009, Berlin. ISBN Critoph R.E., 1999, Forced convection adsorption cycle with packed bed heat regeneration, International Journal of Refrigeration-Revue Internationale du Froid, 22(1), pp.38-46, ISSN: Critoph R.E., Thorpe R., 1999, Experimental results from a forced convection adsorption heat pump / air conditioner, Int. Sorption Heat Pump Conf., Munich, Critoph R.E., 2001, Simulation of a continuous multiplebed regenerative adsorption cycle, International Journal of Refrigeration-Revue Internationale du Froid, 24(5), pp , ISSN: Critoph R.E., 2005, Modular regenerative adsorption cycles with fixed beds applied to trigeneration", J. Process Mech. Eng, 219 Part E, pp , ISSN: Meunier F., 1985, Second law analysis of a solid adsorption heat pump operating on reversible cascaded cycles: application to the zeolite water pair. Heat recovery systems and CHP; 5; Chua, H. T., Ng, K. C., Malek, A. et al., 2001, Multi-bed regenerative adsorption chiller improving the utilization of waste heat and reducing the chilled water outlet temperature fluctuation. Int. J. Refrig., 24, Metcalf S.J., 2009, Compact, Efficient Carbon-Ammonia Adsorption Heat Pump, PhD thesis, University of Warwick. 10. Critoph R.E., Tamainot-Telto Z., Metcalf S.J., 2009, Novel compact sorption generators for car air conditioning Int. J. Refrigeration, 32 ( 4)