Hourly Analysis Program v.4.1 Page 1 of 1

Size: px
Start display at page:

Download "Hourly Analysis Program v.4.1 Page 1 of 1"

Transcription

1 Air System Design Load Summary for Zona 9 DESIGN COOLING DESIGN HEATING COOLING DATA AT Jan 1400 HEATING DATA AT DES HTG COOLING OA DB / WB 34.5 C / 23.7 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible Latent Sensible Latent ZONE LOADS Details (W) (W) Details (W) (W) Window & Skylight Solar Loads 20 m² m² - - Wall Transmission 28 m² m² Roof Transmission 36 m² m² Window Transmission 20 m² m² Skylight Transmission 0 m² 0-0 m² 0 - Door Loads 0 m² 0-0 m² 0 - Floor Transmission 36 m² 0-36 m² 0 - Partitions 48 m² 0-48 m² 0 - Ceiling 0 m² 0-0 m² 0 - Overhead Lighting 778 W Task Lighting 0 W Electric Equipment 800 W People Infiltration Miscellaneous Safety Factor 5% / 5% % >> Total Zone Loads Zone Conditioning Plenum Wall Load 0% Plenum Roof Load 0% Plenum Lighting Load 0% Return Fan Load 601 L/s L/s 0 - Ventilation Load 42 L/s L/s Supply Fan Load 608 L/s L/s Space Fan Coil Fans Duct Heat Gain / Loss 5% 327-5% >> Total System Loads Central Cooling Coil Central Heating Coil >> Total Conditioning Key: Positive values are clg loads Positive values are htg loads Negative values are htg loads Negative values are clg loads

2 Psychrometric Analysis for Zona 9 Location: Buenos Aires, Argentina Altitude: 19.8 m. Data for: January DESIGN COOLING DAY, Outdoor Air Mixed Air 3. Central Cooling Coil Outlet 4. Supply Fan Outlet 5. Duct Heat 6. Room Air 7. Return Duct Outlet Specific Humidity ( kg/kg ) Temperature ( C )

3 System Psychrometrics for Zona 9 January DESIGN COOLING DAY, 1400 TABLE 1: SYSTEM DATA Dry-Bulb Specific Sensible Latent Temp Humidity Airflow Heat Heat Component Location ( C) (kg/kg) (L/s) (W) (W) Ventilation Air Inlet Vent - Return Mixing Outlet Central Cooling Coil Outlet Central Heating Coil Outlet Supply Fan Outlet Cold Supply Duct Outlet Zone Air Zone Direct Exhaust Outlet Return Plenum Outlet Duct Leakage Air Outlet Return Duct Outlet Return Fan Outlet Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = W/(L/s-K) Air Density x Heat of Vaporization x Conversion Factor: At sea level = ; At site altitude = W/(L/s) Site Altitude = 19.8 m TABLE 2: ZONE DATA Zone Terminal Zone Sensible Zone Zone Zone Heating Heating Load T-stat Cond Temp Airflow Coil Unit Zone Name (W) Mode (W) ( C) (L/s) (W) (W) Zone Cooling

4 System Psychrometrics for Zona 9 WINTER DESIGN HEATING TABLE 1: SYSTEM DATA Dry-Bulb Specific Sensible Latent Temp Humidity Airflow Heat Heat Component Location ( C) (kg/kg) (L/s) (W) (W) Ventilation Air Inlet Vent - Return Mixing Outlet Central Cooling Coil Outlet Central Heating Coil Outlet Supply Fan Outlet Cold Supply Duct Outlet Zone Air Zone Direct Exhaust Outlet Return Plenum Outlet Duct Leakage Air Outlet Return Duct Outlet Return Fan Outlet Air Density x Heat Capacity x Conversion Factor: At sea level = 1.207; At site altitude = W/(L/s-K) Air Density x Heat of Vaporization x Conversion Factor: At sea level = ; At site altitude = W/(L/s) Site Altitude = 19.8 m TABLE 2: ZONE DATA Zone Terminal Zone Sensible Zone Zone Zone Heating Heating Load T-stat Cond Temp Airflow Coil Unit Zone Name (W) Mode (W) ( C) (L/s) (W) (W) Zone Heating Hourly Analysis Program v.4.1 Page 2 of 2

5 Air System Sizing Summary for Zona 9 Project Name: Av. cabildo 3067, 4 piso 02/13/2011 Air System Information Air System Name... Zona 9 Equipment Class... SPLT AHU Air System Type... SZCAV Number of zones... 1 Floor Area m² Sizing Calculation Information Zone and Space Sizing Method: Zone L/s... Sum of space airflow rates Space L/s... Individual peak space loads Calculation Months... Jan to Dec Sizing Data... Calculated Central Cooling Coil Sizing Data Total coil load kw Sensible coil load kw Coil L/s at Jan L/s Max block L/s L/s Sum of peak zone L/s L/s Sensible heat ratio m²/kw W/m² Water 5.6 K rise N/A Load occurs at... Jan 1400 OA DB / WB / 23.7 C Entering DB / WB / 18.9 C Leaving DB / WB / 15.2 C Coil ADP C Bypass Factor Resulting RH % Design supply temp C Zone T-stat Check... 1 of 1 OK Max zone temperature deviation K Central Heating Coil Sizing Data Max coil load kw Coil L/s at Des Htg L/s Max coil L/s L/s Water 11.1 K drop N/A Load occurs at... Des Htg W/m² Ent. DB / Lvg DB / 26.3 C Supply Fan Sizing Data Actual max L/s L/s Standard L/s L/s Actual max L/(s-m²) L/(s-m²) Outdoor Ventilation Air Data Design airflow L/s L/s L/(s-m²) L/(s-m²) Fan motor BHP BHP Fan motor kw kw Fan static Pa l/s/person l/s/person

6 Zone Design Load Summary for Zona 9 Project Name: Av. cabildo 3067, 4 piso 02/13/2011 Zone 9 DESIGN COOLING DESIGN HEATING COOLING DATA AT Jan 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 34.9 C / 23.8 C HEATING OA DB / WB -0.6 C / -3.2 C OCCUPIED T-STAT 23.9 C OCCUPIED T-STAT 21.1 C Sensible Latent Sensible Latent ZONE LOADS Details (W) (W) Details (W) (W) Window & Skylight Solar Loads 20 m² m² - - Wall Transmission 28 m² m² Roof Transmission 36 m² m² Window Transmission 20 m² m² Skylight Transmission 0 m² 0-0 m² 0 - Door Loads 0 m² 0-0 m² 0 - Floor Transmission 36 m² 0-36 m² 0 - Partitions 48 m² 0-48 m² 0 - Ceiling 0 m² 0-0 m² 0 - Overhead Lighting 778 W Task Lighting 0 W Electric Equipment 800 W People Infiltration Miscellaneous Safety Factor 5% / 5% % >> Total Zone Loads