ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 02/07/2013 BUILDING SURVEY DATE

Size: px
Start display at page:

Download "ORIGINAL YEAR OF CONSTRUCTION NUMBER OF BUILDING STORIES 02/07/2013 BUILDING SURVEY DATE"

Transcription

1 SOUTH GOODWIN AVENUE URBANA, ILLINOIS SYSTEM CONDITION INDEX.860 PRIMARY BUILDING USE BUILDING SURVEY TEAM BUILDING SYSTEM REPLACEMENT COST $ 14,711,600 LABORATORY BUILDING GROSS SQUARE FEET 123,151 NUMBER OF BUILDING STORIES 4 BUILDING SURVEY DATE CANNON DESIGN: Tim Morriss (M), Amanda Buchheit (E) ORIGINAL YEAR OF CONSTRUCTION /07/2013 B U I L D I N G D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y TRADE E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR ($) GOOD ($) (5-10 YEARS) (10-20 YEARS) POOR ($) (1-5 YEARS) EXCELLENT ($) (20+ YEARS) TOTAL ($) $/GSF PERCENT OF BUILDING TOTAL (%) MECHANICAL 8,826,100 8,826, PLUMBING 2,636, , ,300 3,038, FIRE PROTECTION 49, , , ELECTRICAL 1,049, , ,600 2,015, COMMUNICATIONS 93, , , TOTAL % OF TOTAL 12,654, , ,400 1,028,900 14,711, NO CRITICAL ITEMS IDENTIFIED FOR THIS BUILDING NOTE: Cost Estimates are Construction Costs are in 2013 dollars to Replace in Kind unless otherwise noted PAGE 1

2 PAGE 2

3 Text106 M E C H A N I C A L D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y CHILLED WATER SYSTEM STEAM AND CONDENSTATE SYSTEM HEATING HOT WATER SYSTEM HEAT EXCHANGER SUPPLY AIR SYSTEM AIR HANDLER TOILET EXHAUST SYSTEM LABORATORY EXHAUST SYSTEM NATURAL GAS SYSTEM SYSTEM/COMPONENT Chilled Water Piping Steam and Condensate piping Heating Hot Water Heat Exchanger for bridge/link Supply Air Ductwork 63.AHU1 63.AHU11 63.AHU2 63.AHU3 63.AHU4 63.AHU5 63.AHU6 63.AHU7 63.AHU8 Toilet Exhaust Laboratory Exhaust Natural Gas POOR (1-5 YEARS) E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR GOOD (5-10 YEARS) (10-20 YEARS) EXCELLENT (20+ YEARS) TOTAL 261, ,700 1,490,400 1,490,400 23,000 23,000 17,500 17,500 3,189,600 3,189, , ,900 55,800 55, , , , , , , , , , ,500 58,900 58,900 77,500 77,500 6,200 6, , ,300 5,000 5, PAGE 3

4 Text106 M E C H A N I C A L D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y HVAC CONTROLS SYSTEM SYSTEM/COMPONENT HVAC Controls MECHANICAL TOTAL % OF TOTAL POOR (1-5 YEARS) E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR GOOD (5-10 YEARS) (10-20 YEARS) EXCELLENT (20+ YEARS) TOTAL 32,400 32,400 8,826,100 8,826, PAGE 4

5 Text6 C H I L L E D W A T E R P I P I N G A S S E S S M E N T D A T A Item ID The building is served by a 12 chilled water supply and return line from the campus chilled water loop. These pipes enter the building on the east side of the basement Mechanical Room 30. This piping serves the chilled water cooling coils in the air handlers (located in the penthouse). There are no chilled water pumps. From the basement mechanical room there is also a 6 chilled water supply and return branch line routed to the Superconductivity Center to serve that building. The branch pipes exit the building at the northwest corner of basement Mechanical Room 30. Overall Condition Date Installed 1/1/1966 Material Comments The piping from the campus chilled water loop was installed around This newer piping ties into the existing piping. Most of the chilled water piping in the building is 1964 original. The branch piping to the Superconductivity Center was installed around The chilled water is metered. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Steel pipe Replacement Cost $261,700 The older canvas-style insulation on the 1964 original piping may possibly contain asbestos PAGE 5

6 Text6 C H I L L E D W A T E R P I P I N G S U R V E Y P H O T O G R A P H S Chilled water piping entrance (black insulation) in basement Mechanical Room 30. Reworked chilled water piping (black insulation) ties to the 1964 original chilled water piping (grey insulation) in basement Mechanical Room 30. Branch chilled water piping to Superconductivity Center and taps for the since-removed absorption chillers in basement Mechanical Room 30. Some of the taps are also remnants of the phased plan to convert this building and adjoining buildings to the campus chilled water system PAGE 6

7 Text6 S T E A M A N D C O N D E N S A T E P I P I N G A S S E S S M E N T D A T A Item ID The building is served by the campus steam system. The steam system provides heating to the building via the perimeter heating system and the steam heating coils in the air handling units (in the penthouse). There is no heating hot water, except for the bridge link between this building and the Loomis Physics lab (the bridge was constructed as part of the Materials Research Lab building and is served from the building). The steam system also provides domestic hot water to the building, via a steam-to-hot water heat exchanger assembly in the basement. The steam system at one time did serve absorption chillers in the basement, but in approximately 2002 the building was added to the campus chilled water system. The labs do not appear to use steam for any process purposes. The supply air distribution system uses a dual-duct system, so there does not appear to be any zone heating coils. Overall Condition Date Installed 1/1/1966 Material Comments The building appears to be served by a 16 medium pressure steam line. This line would have been sized to accommodate the absorption chillers in the basement. The building is also served by a 4 pumped condensate and a 4 vacuum condensate line. These lines all enter the building at the northeast corner of basement Mechanical Room 30. The vacuum and pumped condensate receivers (both duplex) are also in this area of Rm. 30. The incoming 4 vacuum condensate line appears to be tied to the inlet side of the vacuum condensate receiver, which presumably pumps into the pumped condensate receiver. The vacuum condensate receiver also appears to serve the perimeter radiation (fin tube and convectors). The overall condensate return is metered. Most of the steam and condensate piping and equipment in the building appear to be 1964 original construction. Steam traps appear to be well maintained in the building and the system is not blowing steam. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Size/Capacity Steel piping Replacement Cost $1,490, medium pressure steam supply, 4 vacuum condensate return, 4 pumped condensate return The older canvas style insulation seen on the steam and condensate return piping may possibly contain asbestos PAGE 7

8 Text6 S T E A M A N D C O N D E N S A T E P I P I N G S U R V E Y P H O T O G R A P H S Pumped condensate receiver, with duplex pumps. Vacuum condensate receiver, with duplex pumps (4 pumps total). 4 vacuum condensate line (at far right, with white insulation), 4 pumped condensate line, and 16 steam supply where they enter the building at the northeast corner of basement Mechanical Room 30. Steam fin tube in one of the stairways PAGE 8

9 Text6 H E A T I N G H O T W A T E R A S S E S S M E N T D A T A Item ID There is a small steam-to-hot water heat exchanger system located in the Penthouse. This heat exchanger produces hot water for heating the bridge link between the Materials Research Lab and the Loomis Physics Lab. The bridge link has hot water fin tube heating and a radiant floor in the portion of the 1st floor that is exposed above Boneyard Creek. This radiant floor is abandoned. There is a base-mounted simplex pump (P-7) that serves the fin tube. The separate pump (P-8) for the radiant floor is abandoned. The bridge link supply air system appears to use a dual duct system, so there does not appear to be hot water reheat coils in use. Overall Condition Poor Date Installed 1/1/1966 Remaining Useful Life Exceeded Nominal Useful Life: 30 Years HP/kW P-7: 1 HP Voltage P-7: 208V / 3 phase Replacement Cost $23,000 Comments The canvas-type insulation on the original hot water piping may possibly contain asbestos PAGE 9

10 Text6 H E A T I N G H O T W A T E R S U R V E Y P H O T O G R A P H S Heat exchanger in Penthouse. Pump P-7, serving fin tube in bridge link. The motor for pump P-8 is disconnected from the pump. Fin tube in the 1st floor of the bridge link PAGE 10

11 Text6 H E A T E X C H A N G E R F O R B R I D G E / L I N K A S S E S S M E N T D A T A Overall Condition Item ID Date Installed 1/1/1966 Comments There is a small steam-to-hot water heat exchanger system located in the Penthouse. This heat exchanger produces hot water for heating the bridge link between the Materials Research Lab and the Loomis Physics Lab. Poor Remaining Useful Life Exceeded Nominal Useful Life: 35 Years Replacement Cost $17,500 The heat exchanger appears to be covered with an insulation that may possibly contain asbestos. Text6 H E A T E X C H A N G E R F O R B R I D G E / L I N K S U R V E Y P H O T O G R A P H S Heat exchanger in Penthouse PAGE 11

12 Text6 S U P P L Y A I R D U C T W O R K A S S E S S M E N T D A T A Item ID There has been no major renovation of the building supply and return air ductwork system since the building was constructed in There have been piecemeal renovations when labs have been reconfigured, but generally the ductwork in this building is 1964 original construction. Overall Condition Date Installed 1/1/1966 Material Comments The supply air system is a dual-duct system, tied to zone damper boxes that mix the warm and cold airstreams to achieve occupant comfort. The supply air system is constant volume (not VAV), even though there are zone-level damper systems. Supply air and return air is routed from the air handlers in the Penthouse down to the occupied floors through four different building shafts. Supply ductwork is round or rectangular, and return air ductwork is typically rectangular. The rectangular supply and return air ductwork is said to be lined. Given the age of this lining it has deteriorated and the fibers will flake off into the supply airstream and can possibly contaminate the lab spaces. Some of the supply air distribution ducts to labs that require a clean airflow have added HEPA filters with booster fans. In other labs the supply air diffusers have been covered with a filter batt. The entire building appears to be air conditioned. There are no window AC units in this building. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Replacement Cost $3,189,600 Galvanized steel sheet metal Given the age of the dual-duct boxes, spare parts are apparently no longer available for these boxes. The original canvas-type insulation seen on the ductwork may possibly contain asbestos PAGE 12

13 Text6 S U P P L Y A I R D U C T W O R K S U R V E Y P H O T O G R A P H S Supply air ductwork (gray insulation), return air ductwork (white insulation) and exhaust air ducts (bare metal) in the penthouse, where they enter one of the four main building shafts. Return air grille in corridor. Supply air ductwork and diffuser in a lab. The lack of insulation on this ductwork indicates that it is probably lined. Ductwork above a corridor ceiling PAGE 13

14 Text A H U 1 A S S E S S M E N T D A T A Item ID AHU1 is a built-up air handler located in the Penthouse. This AHU has a steam heating coil and a chilled water cooling coil. The supply air fan and return/exhaust fan are floor-mounted utility-set type fans. Most components of this air handler appear to be 1964 original construction. Overall Condition Date Installed 1/1/1966 Equipment Tag HP/kW This AHU feeds a dual-duct system, so the airflow is split immediately downstream of the AHU. The chilled water coil is located at the main air handler, but the steam heating coil is located downstream of the ductwork split. The chilled water coil has been replaced since The original chilled water coil was located downstream of the ductwork split, opposite of the steam heating coil. This abandoned coil is still located in the ductwork. The newer chilled water coil is at the main air handler. Both the supply and return air fans are on variable-frequency drives (VFDs) for fan balancing and possible night setback. The AHU is otherwise constant volume. This AHU serves the northeast portions of all four floors plus the basement. Like the connected ductwork, this AHU appears to have an acoustic lining on the inside. This lining has deteriorated and is flaking off into the airstream, creating air quality problems in the laboratories. Additionally the exterior of this AHU is insulated with a canvas-type insulation that may possibly contain asbestos. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Size/Capacity Voltage S1 and E1 37,746 cfm Replacement Cost $555,900 Supply fan: 40hp, Return fan: 10 HP 208V / 3 phase PAGE 14

15 Text A H U 1 S U R V E Y P H O T O G R A P H S 63.AHU-1 supply air fan. VFD for supply fan. 63.AHU-1 return air fan. Chilled water cooling coil connections at 63.AHU PAGE 15

16 Text A H U 1 1 A S S E S S M E N T D A T A Item ID AHU11 is a small horizontal air handler (not built-up) located in the Penthouse. This AHU has a steam heating coil and a chilled water cooling coil. The supply fan is integral to the unit, but E11 is a separate base-mounted utility-set type fan. Most components of this air handler appear to be 1964 original construction. This AHU does not appear to use variable-frequency drives (VFDs). The AHU is constant volume. Overall Condition Date Installed 1/1/1966 Equipment Tag HP/kW Comments This AHU serves rooms 452 and 448 on the fourth floor. Like the connected ductwork, this AHU appears to have an acoustic lining on the inside. This lining has deteriorated and is flaking off into the airstream, creating air quality problems in the laboratories. Additionally the exterior of this AHU is insulated with a canvas-type insulation that may possibly contain asbestos. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Size/Capacity Voltage S11 and E cfm Replacement Cost $55,800 Supply fan: 2 HP, Return fan: 1/2 HP 208V / 3 phase 63.AHU9 and 63AHU10 are no longer in use and are abandoned PAGE 16

17 Text A H U 1 1 S U R V E Y P H O T O G R A P H S 63.AHU11. Coil connections for 63.AHU AHU-11 return air fan E11 (directly behind the piping and pumps in the foreground). Disconnect for supply fan S PAGE 17

18 Text A H U 2 A S S E S S M E N T D A T A Item ID AHU2 is a built-up air handler located in the Penthouse. This AHU has a steam heating coil and a chilled water cooling coil. The supply air fan and return/exhaust fan are floor-mounted utility-set type fans. Most components of this air handler appear to be 1964 original construction. Overall Condition Date Installed 1/1/1966 Equipment Tag HP/kW This AHU feeds a dual-duct system, so the airflow is split immediately downstream of the AHU. The chilled water coil is located at the main air handler, but the steam heating coil is located downstream of the ductwork split. The chilled water coil has been replaced since The original chilled water coil was located downstream of the ductwork split, opposite of the steam heating coil. This abandoned coil is still located in the ductwork. The newer chilled water coil is at the main air handler. Both the supply and return air fans are on variable-frequency drives (VFDs) for fan balancing and possible night setback. The AHU is otherwise constant volume. This AHU serves the southeast portions of all four floors plus the basement. Like the connected ductwork, this AHU appears to have an acoustic lining on the inside. This lining has deteriorated and is flaking off into the airstream, creating air quality problems in the laboratories. Additionally the exterior of this AHU is insulated with a canvas-type insulation that may possibly contain asbestos. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Size/Capacity Voltage S2 and E2 34,249cfm Replacement Cost $503,500 Supply fan: 30hp, Return fan: 7.5 HP 208V / 3 phase PAGE 18

19 Text A H U 2 S U R V E Y P H O T O G R A P H S Steam heating coil for 63.AHU-2. VFD for supply fan. The VFD for the return fan is below. 63.AHU-2. Supply air fan for 63.AHU PAGE 19

20 Text A H U 3 A S S E S S M E N T D A T A Item ID AHU3 is a built-up air handler located in the Penthouse. This AHU has a steam heating coil and a chilled water cooling coil. The supply air fan and return/exhaust fan are floor-mounted utility-set type fans. Most components of this air handler appear to be 1964 original construction. Overall Condition Date Installed 1/1/1966 Equipment Tag HP/kW This AHU feeds a dual-duct system, so the airflow is split immediately downstream of the AHU. The chilled water coil is located at the main air handler, but the steam heating coil is located downstream of the ductwork split. The chilled water coil has been replaced since The original chilled water coil was located downstream of the ductwork split, opposite of the steam heating coil. This abandoned coil is still located in the ductwork. The newer chilled water coil is at the main air handler. Both the supply and return air fans are on variable-frequency drives (VFDs) for fan balancing and possible night setback. The AHU is otherwise constant volume. This AHU serves the southwest portions of all four floors plus the basement. Like the connected ductwork, this AHU appears to have an acoustic lining on the inside. This lining has deteriorated and is flaking off into the airstream, creating air quality problems in the laboratories. Additionally the exterior of this AHU is insulated with a canvas-type insulation that may possibly contain asbestos. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Size/Capacity Voltage S3 and E3 37,350 cfm Replacement Cost $559,000 Supply fan: 40hp, Return fan: 7.5 HP 208V / 3 phase PAGE 20

21 Text A H U 3 S U R V E Y P H O T O G R A P H S 63.AHU-3 supply air fan. VFD for supply fan. 63.AHU-3 return air fan. Chilled water cooling coil connections at 63.AHU PAGE 21

22 Text A H U 4 A S S E S S M E N T D A T A Item ID AHU4 is a built-up air handler located in the Penthouse. This AHU has a steam heating coil and a chilled water cooling coil. The supply air fan and return/exhaust fan are floor-mounted utility-set type fans. Most components of this air handler appear to be 1964 original construction. Overall Condition Date Installed 1/1/1966 Equipment Tag HP/kW This AHU feeds a dual-duct system, so the airflow is split immediately downstream of the AHU. The chilled water coil is located at the main air handler, but the steam heating coil is located downstream of the ductwork split. The chilled water coil has been replaced since The original chilled water coil was located downstream of the ductwork split, opposite of the steam heating coil. This abandoned coil is still located in the ductwork. The newer chilled water coil is at the main air handler. Both the supply and return air fans are on variable-frequency drives (VFDs) for fan balancing and possible night setback. The AHU is otherwise constant volume. This AHU serves the northwest portions of all four floors plus the basement. Like the connected ductwork, this AHU appears to have an acoustic lining on the inside. This lining has deteriorated and is flaking off into the airstream, creating air quality problems in the laboratories. Additionally the exterior of this AHU is insulated with a canvas-type insulation that may possibly contain asbestos. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Size/Capacity Voltage S4 and E4 36,963 cfm Replacement Cost $543,900 Supply fan: 40hp, Return fan: 10 HP 208V / 3 phase PAGE 22

23 Text A H U 4 S U R V E Y P H O T O G R A P H S 63.AHU-4 supply air fan. VFD for 63.AHU-4 supply fan, at right. 63.AHU-4 return air fan. Chilled water cooling coil connections at 63.AHU PAGE 23

24 Text A H U 5 A S S E S S M E N T D A T A Item ID AHU5 is a built-up air handler located in the Penthouse. This AHU has a steam heating coil and a chilled water cooling coil. The supply air fan and return/exhaust fan are floor-mounted utility-set type fans. Most components of this air handler appear to be 1964 original construction. Overall Condition Date Installed 1/1/1966 Equipment Tag HP/kW This AHU feeds a dual-duct system, so the airflow is split immediately downstream of the AHU. The chilled water coil is located at the main air handler, but the steam heating coil is located downstream of the ductwork split. The chilled water coil has been replaced since The original chilled water coil was located downstream of the ductwork split, opposite of the steam heating coil. This abandoned coil is still located in the ductwork. The newer chilled water coil is at the main air handler. Both the supply and return air fans are on variable-frequency drives (VFDs) for fan balancing and possible night setback. The AHU is otherwise constant volume. This AHU serves bridge/link between the Materials Research Lab and the Loomis Physics Lab. The bridge/link was constructed as part of the Materials Research Lab. Like the connected ductwork, this AHU appears to have an acoustic lining on the inside. This lining has deteriorated and is flaking off into the airstream, creating air quality problems in the laboratories. Additionally the exterior of this AHU is insulated with a canvas-type insulation that may possibly contain asbestos. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Size/Capacity Voltage S5 and E5 30,230 cfm Replacement Cost $441,000 Supply fan: 25hp, Return fan: 10 HP 208V / 3 phase PAGE 24

25 Text A H U 5 S U R V E Y P H O T O G R A P H S 63.AHU-5 supply air fan. VFD for 63.AHU-5 supply fan. 63.AHU-5 return air fan. Chilled water cooling coil connections at 63.AHU PAGE 25

26 Text A H U 6 A S S E S S M E N T D A T A Item ID AHU6 forms the top part of a triple-stacked built-up air handler located in the Penthouse, along with 63.AHU-7 and 63.AHU-8. This AHU has a steam heating preheat coil, a chilled water cooling coil, and a steam reheat coil. The supply air fan is a centrifugal utility-type fan that is suspended from the ceiling. The chilled water coil was added around 1986, but most other components of this air handler appear to be 1964 original construction. This AHU appears to provide 100% outside air and does not have return air capability. The exhaust fan is located separately from the AHU and discharges into the louvered penthouse chicken coop on the roof. The supply and return fans do not appear to be on variable-frequency drives (VFDs). The AHU is otherwise constant volume. Overall Condition Date Installed 1/1/1966 Equipment Tag HP/kW This AHU serves several basement clean rooms. Like the connected ductwork, this AHU appears to have an acoustic lining on the inside. This lining has deteriorated and is flaking off into the airstream, creating air quality problems in the laboratories. Additionally the exterior of this AHU is insulated with a canvas-type insulation that may possibly contain asbestos. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Size/Capacity Voltage S6 and E cfm Replacement Cost $102,500 Supply fan: 5 HP, Exhaust fan: 3/4 HP 208V / 3 phase PAGE 26

27 Text A H U 6 S U R V E Y P H O T O G R A P H S The triple-stacked AHU that comprises 63.AHU6, 63.AHU7, and 63.AHU8. 63.AHU6 is at the top. The exhaust fan for the 63.AHU6 system is at the far right. 63.AHU-6 supply air fan. 63.AHU6 preheat coil connections (top 2 connections) PAGE 27

28 Text A H U 7 A S S E S S M E N T D A T A Item ID AHU7 forms the middle part of a triple-stacked built-up air handler located in the Penthouse, along with 63.AHU-6 and 63.AHU-8. This AHU has a steam heating preheat coil, a chilled water cooling coil, and a steam reheat coil. The supply air fan is a centrifugal utility-type fan that is suspended from the ceiling. The chilled water coil was added around 1986, but most other components of this air handler appear to be 1964 original construction. This AHU appears to provide 100% outside air and does not have return air capability. The exhaust fan is located separately from the AHU and discharges into the louvered penthouse chicken coop on the roof. The supply and return fans do not appear to be on variable-frequency drives (VFDs). The AHU is constant volume. Overall Condition Date Installed 1/1/1966 Equipment Tag HP/kW This AHU serves several clean rooms on the third floor. Like the connected ductwork, this AHU appears to have an acoustic lining on the inside. This lining has deteriorated and is flaking off into the airstream, creating air quality problems in the laboratories. Additionally the exterior of this AHU is insulated with a canvas-type insulation that may possibly contain asbestos. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Size/Capacity Voltage S7 and E cfm Replacement Cost $58,900 Supply fan: 3 HP, Exhaust fan: 1/4 HP 208V / 3 phase PAGE 28

29 Text A H U 7 S U R V E Y P H O T O G R A P H S The triple-stacked AHU that comprises 63.AHU6, 63.AHU7, and 63.AHU8. 63.AHU7 is in the middle. The exhaust fan for the 63.AHU7 system is second from the right. 63.AHU-7 supply air fan (top). 63.AHU7 preheat coil connections (bottom 2 connections) PAGE 29

30 Text A H U 8 A S S E S S M E N T D A T A Item ID AHU8 forms the bottom part of a triple-stacked built-up air handler located in the Penthouse, along with 63.AHU-6 and 63.AHU-7. This AHU has a steam heating preheat coil, a chilled water cooling coil, and a steam reheat coil. The supply air fan is a centrifugal utility-type fan that is suspended from the ceiling. The chilled water coil was added around 1986, but most other components of this air handler appear to be 1964 original construction. This AHU appears to provide 100% outside air and does not have return air capability. The exhaust fan is located separately from the AHU and discharges into the louvered penthouse chicken coop on the roof. The supply and return fans do not appear to be on variable-frequency drives (VFDs). The AHU is constant volume. Existing drawings are unclear on the exact location of E8, but it appears to be a small base-mounted utility-set type fan that exhausts to the louvered penthouse chicken coop on the roof. Overall Condition Date Installed 1/1/1966 Equipment Tag HP/kW This AHU serves several clean rooms on the third floor. Like the connected ductwork, this AHU appears to have an acoustic lining on the inside. This lining has deteriorated and is flaking off into the airstream, creating air quality problems in the laboratories. Additionally the exterior of this AHU is insulated with a canvas-type insulation that may possibly contain asbestos. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Size/Capacity Voltage S8 and E cfm Replacement Cost $77,500 Supply fan: 2 HP, Exhaust fan: 1/6 HP 208V / 3 phase PAGE 30

31 Text A H U 8 S U R V E Y P H O T O G R A P H S The triple-stacked AHU that comprises 63.AHU6, 63.AHU7, and 63.AHU8. 63.AHU8 is at the bottom. Disconnect for S8 supply air fan. 63.AHU-8 supply air fan. 63.AHU8 preheat coil connections (bottom 2 connections) PAGE 31

32 Text6 T O I L E T E X H A U S T A S S E S S M E N T D A T A Item ID The main toilet exhaust fan appears to be original 1964 construction (with a newer motor). The exhaust fan is a belt-driven inline fan, located at the vertical duct riser in the penthouse. Per existing drawings this is the only toilet exhaust fan in the building. The fan and its flex connections appear to have been reasonably well maintained. Overall Condition Date Installed 1/1/1966 Equipment Tag Fan E-20 HP/kW 1 Comments This exhaust fan discharges through the louvered penthouse (known as the chicken coop ) on the roof. Nearly all lab exhaust fans also discharge through this louvered penthouse. This louvered penthouse, due to its low elevation above the roof, reportedly does not allow the exhaust air discharges to disperse thoroughly enough into the prevailing winds. The result is that this building has some issues with exhaust air discharge being sucked back in through the outside air intake louvers at the sides of the penthouse. Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Voltage Replacement Cost $6, V / 3 phase The need to rework the lab exhaust to prevent contamination of the ventilation air intake was also listed as one of the biggest priorities for this building by the director for this facility PAGE 32

33 Text6 T O I L E T E X H A U S T S U R V E Y P H O T O G R A P H S Toilet exhaust fan E-20 is the bigger exhaust fan seen in the center of this photo. The motor for exhaust fan E-20 is seen in the lower left foreground. The louvered exhaust penthouse chicken coop on the roof of the building. The toilet exhaust fan and most lab exhaust fans discharge through this louvered penthouse PAGE 33

34 Text6 L A B O R A T O R Y E X H A U S T A S S E S S M E N T D A T A Item ID This lab building contains many fume hoods (approx. 50 to 60) and many exhaust fans serving these fume hoods. There appears to be a fan for each individual hood. These fans appear to operate as constant volume. There is no provision for heat recovery from any lab exhaust system. The lab exhaust fans are generally inline fans located in the penthouse, although there are four roof-mounted fans. Some inline fans in the penthouse are located in the vertical rises as they come out of the building shafts, and some are located in horizontal duct runs. Most of the penthouse fans appear to be 1964 original construction, but have been maintained reasonably well. Overall Condition Date Installed 1/1/1966 Comments The exhaust fans in the penthouse discharge through the louvered penthouse assembly (known as the chicken coop ) on the roof. This louvered penthouse assembly, due to its low elevation above the roof, reportedly does not allow the exhaust air discharges to disperse thoroughly enough into the prevailing winds. The result is that this building has some issues with exhaust air discharge being sucked back into the building through the outside air intake louvers at the sides of the building penthouse. Possibly the exhaust fans on the roof (which are dilution-type with extended-height discharge) are serving hoods with especially hazardous or odorous fumes. One of the newer roof-mounted exhaust fans on the roof makes use of one of the 12 condenser water pipes that runs from the lower floors up to the penthouse roof area. This condenser water pipe serves as part of the exhaust ductwork system for a fume hood in a renovated lab. These condenser water pipes were otherwise abandoned when the building was added to the campus chilled water system around Poor Remaining Useful Life Exceeded Nominal Useful Life: 30 Years Replacement Cost $902,300 The need for a heat recovery system for the lab exhaust was listed as one of the biggest priorities for this building by the director for this facility. The need to rework the lab exhaust to prevent contamination of the ventilation air intake was also listed as one of the biggest priorities for this building by the director for this facility PAGE 34

35 Text6 L A B O R A T O R Y E X H A U S T S U R V E Y P H O T O G R A P H S Vertical inline exhaust fans in penthouse. Overhead exhaust fans in penthouse. The louvered penthouse assembly chicken coop on the roof of the building penthouse. The exhaust fans located in the penthouse discharge exhaust air through this assembly, which apparently creates an issue where the exhaust discharge can be sucked back into the building through the outside air intake louvers (at the sides of the penthouse level) for the building air handlers. View looking up at the underside of the louvered penthouse assembly PAGE 35

36 Text6 N A T U R A L G A S A S S E S S M E N T D A T A Item ID A natural gas service enters the building, but it is reportedly no longer used. Overall Condition Poor Date Installed 1/1/1966 Remaining Useful Life Exceeded Nominal Useful Life: 40 Years Material Black iron pipe Replacement Cost $5,000 Text6 N A T U R A L G A S S U R V E Y P H O T O G R A P H S Gas piping at north end of basement Mechanical Room PAGE 36

37 Text6 H V A C C O N T R O L S A S S E S S M E N T D A T A Item ID HVAC controls in the building are almost entirely pneumatic. Many components of this system are 1964 original. Most of the perimeter fin tube does appear to have a pneumatically-operated control valve that is tied to a thermostat. Some thermostats may no longer be functioning due to leaks in the piping. Overall Condition Date Installed 1/1/1966 Manufacturer The air compressor for the HVAC control system is located in basement Mechanical Room 30. This duplex air compressor is a newer installation and is in good condition. The lab compressed air piping systems for both the Superconductivity Center and the Materials Research Lab are also tied into the compressed air system for the HVAC controls. So essentially there are four separate air compressors that back up the HVAC control system. This is because the pneumatic thermostats of the HVAC controls system will fail high, where a failure of the HVAC controls compressed air system will cause the building(s) to overheat, ultimately tripping the heat detectors of the fire alarm system and bringing the fire department to the building. The air handlers in the Penthouse all appear to have variable-frequency drives for their supply and return fans. These VFDs appear to be tied into a limited BAS system. Poor Remaining Useful Life Exceeded Nominal Useful Life: 18 Years Replacement Cost $32,400 Johnson and Siemens PAGE 37

38 Text6 H V A C C O N T R O L S S U R V E Y P H O T O G R A P H S Duplex air compressor for temperature controls, in basement Mechanical Room 30. VFDs and control panels in Penthouse, serving the air handlers. Typical pneumatic thermostat. VFDs serving air handlers in the Penthouse. The larger VFDs are for the supply fans and the smaller VFDs are for the return fans PAGE 38

39 Text106 P L U M B I N G D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y DOMESTIC COLD WATER SYSTEM DOMESTIC HOT WATER SYSTEM HEATER PLUMBING FIXTURES SYSTEM SANITARY WASTE AND VENT SYSTEM STORM DRAINAGE SYSTEM SUB-SOIL DRAINAGE SYSTEM VACUUM NITROGEN SYSTEM OTHER PIPED GAS SYSTEM/COMPONENT Domestic Cold Water Domestic Hot Water Domestic Hot Water Heater Plumbing Fixtures Compressed Air (for labs) Sanitary, Waste, and Vent Storm Drainage Subsoil Drainage Vacuum Nitrogen Helium Recovery Piping PLUMBING TOTAL % OF TOTAL POOR (1-5 YEARS) E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR GOOD (5-10 YEARS) (10-20 YEARS) EXCELLENT (20+ YEARS) TOTAL 368, , , ,100 79,100 79, , , , , , , , ,200 76,900 76, , ,300 28,500 28, , ,600 2,636, , ,300 3,038, PAGE 39

40 Text6 D O M E S T I C C O L D W A T E R A S S E S S M E N T D A T A Overall Condition Item ID Date Installed 1/1/1966 Material Comments A 4 domestic cold water line (ductile iron) enters the north side of the basement Mechanical Room 30 and a 6 domestic cold water line (ductile iron) enters the south side of the building and is routed (suspended at basement ceiling) to basement Mechanical Room 30. These two services tie together in this room to feed the fire protection (standpipe) system and the domestic cold water system. There has been no major renovation of the domestic cold water piping since its 1964 original installation. Sections have been replaced on an as-needed basis due to leaks. Due to the age of this piping it is considered to be in poor condition. There is no booster pump. No major issues with this system have been reported. This system apparently supplies water to the labs in the building. There is no separate non-potable water system for lab use. Emergency shower stations in the building appear to use cold water only, not tempered. Poor Remaining Useful Life 1 Year Nominal Useful Life: 50 Years Size/Capacity Replacement Cost $368,100 Combined 6 and 4 water service, serving domestic cold water and fire protection (probably) galvanized steel with some newer copper Some domestic cold water is used in a once through arrangement to provide heat rejection for lab process cooling. The piping insulation may contain asbestos PAGE 40

41 Text6 D O M E S T I C C O L D W A T E R S U R V E Y P H O T O G R A P H S 4 domestic cold water service entering the north end of mechanical room 30. Domestic cold water valve train in basement Mechanical Room 30. The 6 and 4 cold water services tie together near the top of the picture. Piping at lab sink. Lab process cooling equipment uses domestic water in a once-through arrangement for heat rejection. The water is discharged to the sanitary drain at right PAGE 41

42 Text6 D O M E S T I C H O T W A T E R A S S E S S M E N T D A T A Overall Condition Item ID Date Installed 1/1/1966 Material Comments Domestic hot water is supplied to the building from two steam-to-hot water heat exchangers and one storage tank. There are two hot water recirculation pumps. There is a 2-1/2 hot water supply to the building and a 1-1/2 recirculation line. There has been no major renovation of the domestic hot water piping since its 1964 original installation. Sections have been replaced on an as-needed basis due to leaks. Due to the age of this piping it is considered to be in poor condition. No other major issues with this system have been reported. This system apparently supplies hot water to the labs in the building. There is no separate nonpotable hot water system for lab use. Emergency showers in the building appear to use cold water only, not tempered water. Poor Remaining Useful Life 1 Year Nominal Useful Life: 50 Years Size/Capacity Replacement Cost $357, /2 HWS and 1-1/2 HWR (probably) galvanized steel with some newer copper The piping insulation may contain asbestos PAGE 42

43 Text6 D O M E S T I C H O T W A T E R S U R V E Y P H O T O G R A P H S Piping at lab sink. Domestic hot water heater in basement mechanical room PAGE 43

44 Text6 D O M E S T I C H O T W A T E R H E A T E R A S S E S S M E N T D A T A Overall Condition Item ID Date Installed 1/1/1966 HP/kW The basement Mechanical Room 30 contains a domestic hot water heater that uses two steam-to-hot water heat exchangers to create hot water. This water heater is a packaged unit, with the two heat exchangers located below a large storage tank. There are two hot water recirculation pumps, and the building has a hot water recirculation piping system. The pumps and the steam control valves have been replaced, but the tank and heat exchangers are possibly 1964 originals. Based on the age of this equipment it is considered to be in poor condition. Poor Remaining Useful Life Exceeded Nominal Useful Life: 25 Years Size/Capacity Voltage Replacement Cost $79,100 Tank: 1500 gallons, Pumps: 28 gpm each Pumps: 3/4 HP each. Pumps: 208V / 3 phase PAGE 44

45 Text6 D O M E S T I C H O T W A T E R H E A T E R S U R V E Y P H O T O G R A P H S Hot water heater in basement Mechanical Room 30. The two heat exchangers are located below the large storage tank. Hot water recirculation pumps. Hot water heater in basement Mechanical Room 30. The two heat exchangers are located below the large storage tank. Heat exchangers and associated valves and piping at water heater PAGE 45

46 Text6 P L U M B I N G F I X T U R E S A S S E S S M E N T D A T A Overall Condition Item ID Date Installed 1/1/1966 Most plumbing fixtures appear to be 1964 original installation. Toilets and urinals appear to use flush valves, but these are not sensor-type (touchless). Existing drawings do not show any ADA renovation projects for the restrooms. Emergency showers in the building appear to use cold water only. They are not tempered. Plus the emergency shower stations are not equipped with a floor drain. Poor Remaining Useful Life 1 Year Nominal Useful Life: 50 Years Replacement Cost $392, PAGE 46

47 Text6 P L U M B I N G F I X T U R E S S U R V E Y P H O T O G R A P H S Typical Mens restroom. Typical restroom. Water fountain. Mop sink in Janitor s Closet PAGE 47

48 Text6 C O M P R E S S E D A I R ( F O R L A B S ) A S S E S S M E N T D A T A Overall Condition Item ID Date Installed 1/1/1966 Material Most labs in the building have compressed air service. The air compressor in this building is in the basement Mechanical Room 30. The lab air compressor is a newer simplex model. This compressor has no tank of its own but uses the tank from the older and otherwise abandoned lab air compressor located nearby. This newer lab air compressor essentially serves as a backup to the air compressor in the Superconductivity Center. The lab compressed air piping systems in Superconductivity Center and the Materials Research Lab are tied together, and the newer air compressor in the Superconductivity Center is set at a higher discharge pressure and is the primary air compressor for the system. This compressed air system is also tied to the pneumatic control system for HVAC controls (by use of pressure regulators) and serves as a backup to that system. The pneumatic thermostats of the HVAC controls system will fail high, where a failure of the HVAC controls compressed air system will cause the building(s) to overheat, ultimately tripping the heat detectors of the fire alarm system and bringing the fire department to the building. Poor Remaining Useful Life 1 Year Nominal Useful Life: 50 Years Replacement Cost $187,700 Copper and iron pipe PAGE 48

49 Text6 C O M P R E S S E D A I R ( F O R L A B S ) S U R V E Y P H O T O G R A P H S Simplex air compressor (for lab air) in basement Mechanical Room 30. Older duplex air compressor in basement Mechanical Room 30. The newer simplex air compressor uses the tank from this older (and otherwise abandoned) air compressor. Compressed air piping (at right) in a renovated lab space PAGE 49

50 Text6 S A N I T A R Y, W A S T E, A N D V E N T A S S E S S M E N T D A T A Overall Condition Item ID Date Installed 1/1/1966 Material There has been no major renovation of the sanitary, waste, and vent piping since original 1964 construction. Sanitary waste exits on the north side of the building, through two 6 cast iron pipes and one 4 cast iron pipe. With the construction of the Superconductivity Center building around 1993, one of these 6 sanitary lines now ties into a sanitary line in the basement mechanical room of the Superconductivity Center. Sanitary risers appear to be grouped into soil stacks and lab waste stacks. The lab waste stacks and all downstream horizontal runs are Duriron, which is apparently in poor condition after many years of accepting lab waste. Any portions of lab waste piping that have been replaced (on an as-needed basis due to leaks) have been replaced with plastic acid-resistant piping. Soil stacks and any other non-lab waste (such as floor drains in the mechanical room) are served by cast iron piping. There is a duplex ejector pit in the northwest corner of the basement mechanical room 30. All basement sanitary waste appears to tie into this ejector pit. Emergency shower stations in the building do not have a floor drain. Poor Remaining Useful Life 1 Year Nominal Useful Life: 50 Years Replacement Cost $746,300 Mostly Duriron, with some cast iron, some PVC, and (probably) some plastic acid-resistant piping PAGE 50

51 Text6 S A N I T A R Y, W A S T E, A N D V E N T S U R V E Y P H O T O G R A P H S In the Superconductivity Center basement mechanical room, a 6 sanitary line (upper left) from the Seitz Materials Research Lab ties into a larger sanitary line. Duplex ejector pit at the northwest corner of basement mechanical room Duriron sanitary pipe (labeled sewer ) where it exits the building at the northwest corner of mechanical room 30. The PVC piping is the pumped discharge from the ejector pit, which ties to a 4 sanitary line that exits the building. The pipes with the black insulation are the chilled water supply and return piping to the Superconductivity Center. Sanitary vent on roof PAGE 51

52 Text6 S T O R M D R A I N A G E A S S E S S M E N T D A T A Overall Condition Item ID Date Installed 1/1/1966 Material The building has a flat roof and uses roof drains. These roof drains are piped within the building and tie together on the 1st floor (near the bridge to Loomis Physics Lab) into a 12 downspout main, which appears to drain into Boneyard Creek. The discharge from the sump pit in the basement mechanical room (which serves the subsoil drainage system) ties into the 1st floor downspout system. There are no secondary roof drains, but the building apparently has scuppers to serves as a backup to the roof drains. This system is considered to be in fair condition due to the age of the piping. Otherwise, with recent improvements to Boneyard Creek, storm drainage and potential flooding is not considered to be a major concern. Poor Remaining Useful Life 1 Year Nominal Useful Life: 50 Years Size/Capacity Cast iron Replacement Cost $400, downspout discharge to Boneyard Creek Text6 S T O R M D R A I N A G E S U R V E Y P H O T O G R A P H S Roof drain (center) on lower level (1st floor) roof. Roof drain on 4th floor roof. Sump pit in basement mechanical room PAGE 52

53 Text6 S U B S O I L D R A I N A G E A S S E S S M E N T D A T A Overall Condition Item ID Date Installed 1/1/1966 Material The building has a drain tile system that runs under the basement level of the building, including around the perimeter of the building. These drain tile lines tie together at a sump pit at the south end of basement mechanical room 30. There are approximately 15 rod-out basins (with an 18 dia. cover) for the drain tile systems. These basins are located around the basement level. The rod-out basins are not regularly opened for rod-out maintenance. There are also some cleanouts in the basement floor that serve the drain tile system. The duplex sump pit in basement mechanical room 30 ties into the downspout drain system on the 1st floor, which ultimately empties into Boneyard Creek. Flooding is not considered a major concern for this building, mostly due to the availability of nearby Boneyard Creek for stormwater drainage. Poor Remaining Useful Life 1 Year Nominal Useful Life: 50 Years Drain tile Replacement Cost $76, PAGE 53

54 Text6 S U B S O I L D R A I N A G E S U R V E Y P H O T O G R A P H S Sump pit in basement mechanical room 30. Rod-out basin for drain tile system, at the stair outside of basement mechanical room 30. Sump pit control panel in basement mechanical room. Rod-out basin in basement PAGE 54

55 Text6 V A C U U M A S S E S S M E N T D A T A Overall Condition Item ID Date Installed 1/1/2010 Material A newer vacuum piping system has been installed in phases in recent years to serve the labs. This system appears to be designed for the exhaust of vacuum pumps. The electrically-driven vacuum pumps used in the labs have exhaust air that may contain oil droplets. This vacuum system is designed to accept gases only. There are no provisions for separation of liquids or solids in the airstream. This system appears to be tied to the duplex vacuum pump system located in Loomis Physics Lab. Excellent Remaining Useful Life 27 Years Nominal Useful Life: 30 Years Replacement Cost $223,300 Copper and plastic piping Text6 V A C U U M S U R V E Y P H O T O G R A P H S Electrically-driven vacuum pump in a lab. The air discharge from this pump is connected to the lab vacuum piping. Vacuum piping in a lab that is being renovated. Vacuum piping in a lab that is being renovated PAGE 55

56 Text6 N I T R O G E N A S S E S S M E N T D A T A Item ID A piped nitrogen supply originates from the tanks at the Engineering Sciences Building (and not the Loomis Physics Lab, although the nitrogen supply from Loomis Physics Lab can be tied into the system from Engineering Sciences Building by operating a manual valve). This system is reported to have an unacceptably low supply pressure, possibly due to leaks in the piping. Nitrogen at higher pressure appears to be provide in some labs using gas cylinders. The installation date for this piping is unclear. It does not appear on the original 1964 construction drawings. Overall Condition Poor Date Installed 01/01/1985 Remaining Useful Life 2 Years Nominal Useful Life: 30 Years Material Copper Replacement Cost $28,500 Text6 N I T R O G E N S U R V E Y P H O T O G R A P H S Nitrogen piping to a 1st floor lab that is being renovated. 1st floor lab fume hood, with nitrogen available PAGE 56

57 Text6 H E L I U M R E C O V E R Y P I P I N G A S S E S S M E N T D A T A Item ID The labs in this building have a helium recovery system. This is a system of metered piping to allow helium (used for cooling lab experiments) to be reclaimed and recycled for future use. The helium reclamation system (and liquefying system) is located in the nearby Loomis Physics Lab (Bldg. 67). This system also serves labs in the adjacent Superconductivity Center and the Engineering Sciences Building. Piping from the Engineering Sciences Building extends through the Superconductivity Center and through the Materials Research Lab to reach the Loomis Physics Lab. Overall Condition Date Installed 1/1/1988 Material The piping system does not have a suction pump; rather it relies on the pressure of the helium gas that is discharged into the piping to transport the gas to the Loomis Physics Lab. There is also a system of inflatable gas bags connected to the piping that allows the system to store gaseous helium at times when the reclamation system (which compresses the gaseous helium for storage in high pressure tanks) can t keep up. There are meters that measure the amount of gaseous helium recovered. These meters are located high on the wall, typically in a storage room or a corridor, and look like natural gas meters. These meters keep track of how much helium is recovered, as projects/departments are charged for how much helium is used (not recovered). Helium supply is not piped. Liquid helium is transported into this building in dewars, from the Loomis Physics Lab, for use in experiments. Several different piping materials appear to be in use for this system: copper (sweat), PVC, and braided-jacket flex hoses. The exact installation date of this piping system is unclear. It does not appear on the 1964 original drawings. Good Remaining Useful Life 15 Years Nominal Useful Life: 40 Years Replacement Cost $178,600 Copper and possibly some PVC PAGE 57

58 Text6 H E L I U M R E C O V E R Y P I P I N G S U R V E Y P H O T O G R A P H S Helium recovery meter in 1st floor corridor. Helium recovery piping connections in a 1st floor corridor. Helium recovery piping connections in a 1st floor lab, with a gas storage bag in the overhead storage area. Liquid helium dewar (silver tank) connected to the helium recovery system, in a 1st floor lab PAGE 58

59 Text106 F I R E P R O T E C T I O N D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y FIRE ALARM SYSTEM STANDPIPE SYSTEM SYSTEM/COMPONENT Fire Alarm System Standpipes FIRE PROTECTION TOTAL % OF TOTAL POOR (1-5 YEARS) E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR GOOD (5-10 YEARS) (10-20 YEARS) EXCELLENT (20+ YEARS) TOTAL 240, ,400 49,300 49,300 49, , , PAGE 59

60 Text6 F I R E A L A R M S Y S T E M A S S E S S M E N T D A T A Overall Condition Date Installed 1/1/2000 Equipment Tag Manufacturer Model Number Item ID HP/kW Material The main fire alarm panel is located off the lower level corridor. Smoke detectors are installed throughout the building and in front of the elevators for elevator recall. Notification devices are installed in corridors, restrooms and labs, however, coverage is inadequate per current codes. Fair Remaining Useful Life 7 Years Nominal Useful Life: 20 Years Serial Number Size/Capacity Voltage Siemens MXL Replacement Cost $240, PAGE 60

61 Text6 F I R E A L A R M S Y S T E M S U R V E Y P H O T O G R A P H S FACP Pull Station Smoke Detector Horn Strobe PAGE 61

62 Text6 S T A N D P I P E S A S S E S S M E N T D A T A Overall Condition Item ID Date Installed 1/1/1966 Material The building does not have any sprinklers. The building has an older system of standpipes, with hose valve cabinets (without any hoses) that have 2-1/2 valves with 1-1/2 hose adapters attached. These hose valve cabinets are typically located in stairways. Due to the age of the piping this system is considered to be in fair condition. There is no fire pump. There is a 4 siamese fire dept. connection at the southwest corner of the building. The system is served by the same cold water piping that feeds the domestic cold water system. A 4 water service enters the basement mechanical room from the north side of the building, and a 6 water service enters the basement mechanical room at the south side of the building. These two services tie together in the basement mechanical room to feed the standpipe system and the domestic cold water valve assembly. Poor Remaining Useful Life 1 Year Nominal Useful Life: 50 Years Size/Capacity Replacement Cost $49, /2 hose valves. Steel piping and ductile iron PAGE 62

63 Text6 S T A N D P I P E S S U R V E Y P H O T O G R A P H S Standpipe in penthouse. Hose valve cabinet/standpipe in the south stairs. 6 and 4 water services tie together at this location in basement mechanical room 30 to serve the standpipe system and the domestic cold water system PAGE 63

64 Text106 E L E C T R I C A L D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y MEDIUM VOLTAGE SYSTEM SUBSTATION LOW VOLTAGE SYSTEM EMERGENCY POWER SYSTEM GENERATOR INTERIOR LIGHTING EMERGENCY LIGHTING SYSTEM EXIT LIGHTING SYSTEM LIGHTING CONTROL SYSTEM EXTERIOR LIGHTING SYSTEM SYSTEM/COMPONENT Medium Voltage System Medium Voltage System - Substation Low Voltage System Low Voltage System Emergency Power System Emergency Power System - Generator Interior Lighting System Emergency Lighting System Exit Lighting System Lighting Control System Exterior Lighting System ELECTRICAL TOTAL % OF TOTAL POOR (1-5 YEARS) E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR GOOD (5-10 YEARS) (10-20 YEARS) EXCELLENT (20+ YEARS) TOTAL 508, ,700 44,300 44, , , , , , ,400 51,900 51, , ,600 53,400 53,400 21,600 21, , ,300 26,000 26,000 1,049, , ,600 2,015, PAGE 64

65 Text6 M E D I U M V O L T A G E S Y S T E M A S S E S S M E N T D A T A Overall Condition Date Installed 1/1/1966 Equipment Tag Manufacturer Model Number Item ID HP/kW Material Two building services provide redundant electricity to the building. One service from the campus loop and one service from the Utility (Ameren). The double ended substation has a manual tie, where one end (feeder) is capable of supporting the entire building in the event of a loss of one power source. Poor Remaining Useful Life Exceeded Nominal Useful Life: 40 Years Serial Number Size/Capacity Not observed GE 600A Voltage 4,160V Replacement Cost $508, PAGE 65

66 Text6 M E D I U M V O L T A G E S Y S T E M S U R V E Y P H O T O G R A P H S Medium Voltage Substation Utility Transformer PAGE 66

67 Text6 M E D I U M V O L T A G E S Y S T E M - S U B S T A T I O N A S S E S S M E N T D A T A Overall Condition Date Installed 1/1/1966 Equipment Tag Manufacturer Model Number Item ID HP/kW Material A double ended substation provides power to the entire building. Two 1000 KVA transformers step the voltage down to 120/208V. The unit is freestanding and located in room 30. The substation is fed from LC 52-2, with 65KAIC ratings. Breakers are drawout style. Poor Remaining Useful Life Exceeded Nominal Useful Life: 40 Years Serial Number Size/Capacity Not observed GE 600A Voltage 4,160V Replacement Cost $44, PAGE 67

68 Text6 M E D I U M V O L T A G E S Y S T E M - S U B S T A T I O N S U R V E Y P H O T O G R A P H S Medium Voltage Substation PAGE 68

69 Text6 L O W V O L T A G E S Y S T E M A S S E S S M E N T D A T A Overall Condition Date Installed 1/1/1966 Equipment Tag Manufacturer Model Number Item ID HP/kW Material Comments From the 1600A, 208V/120V low voltage side of the substation, several bus ducts provide power to various GE 208/120V panelboards located throughout corridors on every level of the building. Some of the 100A panelboards are located immediately inside the research labs near the door. A 1600A distribution panel is connected to a 300KVA buck=boost transformer to provide two 150A feeders to the data center on the level above. This item was installed within the last few years. Motor Control Centers in the penthouse provide local starter/disconnects to mechanical equipment in the penthouse. Poor Remaining Useful Life Exceeded Nominal Useful Life: 40 Years Serial Number Size/Capacity GE Varies Voltage 208/120V Replacement Cost $161,000 Occupants noted there are balancing issues with some of the lab panelboards. These panels are monitored and circuitry is revised to assist in balancing of the load across the phases PAGE 69

70 Text6 L O W V O L T A G E S Y S T E M A S S E S S M E N T D A T A Overall Condition Date Installed 1/1/1966 Comments (2) 600A Distribution Panels per floor, provide power to panelboards located in laboratories or the elec closet. Distribution panels are fed from the Bus duct that rises vertically through each closet. Equipment Tag Power North 1, Power South 1 Manufacturer Model Number Item ID HP/kW Material Poor Remaining Useful Life Exceeded Nominal Useful Life: 40 Years Serial Number Size/Capacity GE 600A Voltage 208/120V Replacement Cost $112,700 Occupants noted there are balancing issues with some of the lab panelboards. These panels are monitored and circuitry is revised to assist in balancing of the load across the phases PAGE 70

71 Text6 L O W V O L T A G E S Y S T E M S U R V E Y P H O T O G R A P H S Bus Duct from Distribution Panel Distribution Panel (typical) PAGE 71

72 Text6 E M E R G E N C Y P O W E R S Y S T E M A S S E S S M E N T D A T A Overall Condition Date Installed 1/1/1994 Equipment Tag Manufacturer Model Number Item ID HP/kW Material Comments A 125KW Diesel generator provides emergency power to lighting for the entire building. The 400A, 208V open transition automatic switch supplies panel EM with normal load connection from the distribution panel in the main electrical room. Fair Remaining Useful Life 6 Years Nominal Useful Life: 25 Years Serial Number Size/Capacity Cummins 125KW Voltage 208/120V Replacement Cost $109,400 Exhaust stack was added to the generator recently due the generators location next to an area well. The exhaust fan for the electrical room pulls air in, including diesel fumes (when running), thus the stack was added to above the roof PAGE 72

73 Text6 E M E R G E N C Y P O W E R S Y S T E M S U R V E Y P H O T O G R A P H S Automatic transfer switch Generator PAGE 73

74 Text6 E M E R G E N C Y P O W E R S Y S T E M - G E N E R A T O R A S S E S S M E N T D A T A Item ID Overall Condition Date Installed 01/01/1994 Equipment Tag Manufacturer HP/kW Material A 125KW Diesel generator provides emergency power to lighting for the entire building. The 400A, 208V open transition automatic switch supplies panel EM with normal load connection from the distribution panel in the main electrical room. The generator contains a 300 gallon belly tank. Fair Remaining Useful Life 6 Years Nominal Useful Life: 25 Years Cummins Model Number OT 400 Serial Number Size/Capacity I KW Voltage 208/120V Replacement Cost $51, PAGE 74

75 Text6 E M E R G E N C Y P O W E R S Y S T E M - G E N E R A T O R S U R V E Y P H O T O G R A P H S Automatic transfer switch Generator PAGE 75

76 Text6 I N T E R I O R L I G H T I N G S Y S T E M A S S E S S M E N T D A T A Overall Condition Date Installed 4/17/2009 Equipment Tag Manufacturer Model Number Item ID HP/kW Material The interior lighting system consists of recessed 2x4 lensed troffers throughout the corridors on each floor. Labs are provided with direct pendant fluorescent fixtures. Lighting in the penthouse is via pendant fixtures with A21 lamps and light levels are minimal. Excellent Remaining Useful Life 20 Years Nominal Useful Life: 25 Years Serial Number Size/Capacity Voltage 208/120V Replacement Cost $730, PAGE 76

77 Text6 I N T E R I O R L I G H T I N G S Y S T E M S U R V E Y P H O T O G R A P H S Corridor Lighting Lab Lighting PAGE 77

78 Text6 E M E R G E N C Y L I G H T I N G S Y S T E M A S S E S S M E N T D A T A Overall Condition Date Installed 4/23/2009 Equipment Tag Manufacturer Model Number Item ID HP/kW Material The emergency generator provides emergency lighting circuits to select fixtures in the corridors. Emergency lighting units are supplemented in the stairwells for emergency illumination. Excellent Remaining Useful Life 20 Years Nominal Useful Life: 25 Years Serial Number Size/Capacity Voltage 208/120V Replacement Cost $53, PAGE 78

79 Text6 E M E R G E N C Y L I G H T I N G S Y S T E M S U R V E Y P H O T O G R A P H S Emergency Lighting Unit PAGE 79

80 Text6 E X I T L I G H T I N G S Y S T E M A S S E S S M E N T D A T A Item ID Exit lighting through the building is LED and located at all corridor ends and stairwells. Overall Condition Excellent Date Installed 4/17/2009 Remaining Useful Life 20 Years Nominal Useful Life: 25 Years Equipment Tag Manufacturer Model Number Serial Number Size/Capacity HP/kW Voltage 208/120V Material Replacement Cost $21, PAGE 80

81 Text6 E X I T L I G H T I N G S Y S T E M S U R V E Y P H O T O G R A P H S Exit Light Fixture PAGE 81

82 Text6 L I G H T I N G C O N T R O L S Y S T E M A S S E S S M E N T D A T A Overall Condition Date Installed 1/1/1966 Equipment Tag Manufacturer Model Number HP/kW Material Recommendation Item ID Lighting controls for the corridors, offices and restrooms are all manual on/off light switches. Poor Remaining Useful Life Exceeded Nominal Useful Life: 20 Years Serial Number Size/Capacity Voltage 208/120V Replacement Cost $196,300 Recommend adding local occupancy sensors to offices and restrooms. Recommend installing a central system to control common spaces (corridor, lobby, stairwells, labs) PAGE 82

83 PAGE 83

84 Text6 E X T E R I O R L I G H T I N G S Y S T E M A S S E S S M E N T D A T A Overall Condition Date Installed 1/1/1966 Equipment Tag Manufacturer Model Number HP/kW Material Recommendation Item ID Comments Exterior luminaires are minimal around the building. The canopy over the porch is lit with metal halide lamps which provide no emergency illumination. Along the sides of the building, incandescent lamps light a sidewalk to an exterior door with minimal lighting at the door. Poor Remaining Useful Life Exceeded Nominal Useful Life: 25 Years Serial Number Size/Capacity Voltage 208/120V Replacement Cost $26,000 Provide fixtures and/or lamps in exterior fixtures with battery back-up capable of providing required egress lighting in the event of a power outage. Lighting on rear of building was observed on during a sunny day. Recommend reviewing controls for these luminaires PAGE 84

85 Text6 E X T E R I O R L I G H T I N G S Y S T E M S U R V E Y P H O T O G R A P H S Exterior Canopy Lighting Exterior Sidewalk Lighting Rear Fixtures Seen on during sunny day PAGE 85

86 Text106 C O M M U N I C A T I O N S D I S C I P L I N E R E P L A C E M E N T C O S T S U M M A R Y DATA SYSTEM CCTV SYSTEM SYSTEM/COMPONENT Communication Infrastructure System Security CCTV System COMMUNICATIONS TOTAL % OF TOTAL POOR (1-5 YEARS) E X P E C T E D R E M A I N I N G S E R V I C E L I F E FAIR GOOD (5-10 YEARS) (10-20 YEARS) EXCELLENT (20+ YEARS) TOTAL 447, ,800 93,800 93,800 93, , , PAGE 86

87 Text6 C O M M U N I C A T I O N I N F R A S T R U C T U R E S Y S T E M A S S E S S M E N T D A T A Item ID The building is fed with 12 strands of single mode fiber and 700 copper pairs with each pair grounded and individually protected by a fuse/surge arrestor. Fiber and copper originate from Node #1. The building IDF is located in closet 79 on the basement level. Fiber distributes radially from the building IDF to hub rooms (telecommunication rooms) to within 100 meters of end-use equipment and lands at rack mounted fiber switches within the hub room. Overall Condition There are two hub rooms located within the building, both on the second floor - hub room 213 (hub A) feeds the west side of the building and hub room 259 (hub B) feeds the east side of the building. Each hub room is equipped with free standing racks (two in hub A and four in hub B), wire management, overhead ladder cable tray. Both hub rooms have smoke detection. Hub room B has a dedicated fan coil unit with a central chilled water connection; hub room A does not have a dedicated cooling system-it is conditioned by the base building HVAC system. Outlet standards typically have 1"C stubbed to cable management. Standard outlet consists of two network cables and two data jacks. Station cable consists of Cat 5, Cat 5e, Cat 6 and Cat 6e. The building is typically equipped with WIFI throughout (coverage not noted). Good Date Installed UIUC network upgrade complete (date range 2006 to 2012) Remaining Useful Life 20 Years Nominal Useful Life: 20 Years Replacement Cost $447, PAGE 87

88 Text6 C O M M U N I C A T I O N I N F R A S T R U C T U R E S Y S T E M S U R V E Y P H O T O G R A P H S Building 66 IDF Building 66 Hub Room A Building 66 Hub Room B Building 66 Hub Room B A/C Unit PAGE 88

89 Text6 S E C U R I T Y C C T V S Y S T E M A S S E S S M E N T D A T A Overall Condition Date Installed 1/1/1966 Equipment Tag Manufacturer Model Number Item ID HP/kW Material The security system for the building is outdated. The visibility of the picture captured by the cameras is very poor. The cameras record to a VCR and not a manned security console. Cameras are located at the building entries. Poor Remaining Useful Life Exceeded Nominal Useful Life: 20 Years Serial Number Size/Capacity Voltage Replacement Cost $93, PAGE 89

90 Text6 S E C U R I T Y C C T V S Y S T E M S U R V E Y P H O T O G R A P H S Security Camera at front entry PAGE 90