The ISO received comments on PRR-1067 of the Business Practice Manual Change Management process from the following:

Size: px
Start display at page:

Download "The ISO received comments on PRR-1067 of the Business Practice Manual Change Management process from the following:"

Transcription

1 The ISO received comments on PRR-1067 of the process from the following: 1. Cities of Anaheim, Azusa, Banning, Colton, Pasadena, and Riverside, California (Six Cities) 2. Southern California Edison (SCE) Copies of the comments submitted are located on the page at: The following are the ISO s responses to the comments. Page 1 of 7

2 1. Cities of Anaheim, Azusa, Banning, Colton, Pasadena, and Riverside, California a Municipal Transmission (Six Cities) Submitted by: Margaret McNaul and Rebecca Shelton 1a (1) The CAISO has not identified a specific reliability need for modeling data The ISO is aware that Category 2 generators are not directly connected from Category 2 generating resources. Section of the TPP BPM to BES, and are thus not part of the scope of NERC Reliability defines Category 2 generators as Participating generators connected to Standards. Nevertheless, the Category 2 generators have an impact on facilities 60 kv and above, and not covered in category 1. Thus, Category the BES in terms of power flow and stability studies. As a result, the 2 generators are not connected to the Bulk Electric System ( BES ), but the CAISO believes it is necessary to ensure data and model quality for CAISO nevertheless is proposing that these generators submit test reports Category 2 generators. The data requirements including test reports and modeling data. (See Section ) Because these generators are are based on the NERC reliability standards for BES connected not connected to the BES, it is not clear for what reason the CAISO would generators (MOD-025, MOD-026 and MOD-027) and WECC need such extensive information. Further, the CAISO s request for test generating facility data, testing and model validation requirements. reports and modeling data from Category 2 generators appears to go Where WECC requirements are more stringent than the NERC beyond the scope of information required from these resources by NERC reliability standards, requirements are set based on the NERC reliability Reliability Standards. standard. For example, WECC policy requires generators being tested every five years while NERC MOD-026 and MOD-027 require the test every ten years. The CAISO proposes 10 year periodicity for dynamic 1b (2) Given that Category 2 generators are not connected to the BES, in the event that the TPP BPM is modified to require from Category 2 Participating Generators modeling and testing data that meets WECC requirements, the CAISO should accept the most recent WECC model data test results for modeling purposes. The generator would only have to be retested pursuant to any equipment modifications since the last test. This would provide the CAISO with the requisite modeling data without placing an undue burden on generator operators. model testing. See response above for 1a. It is necessary to test the facilities periodically even if there has been no major modifications to the facilities to ensure that the models reflect the actual performance and settings of the generator. 1c (3) The penalty provisions pursuant to Section 10 of the TPP BPM are unreasonable. A $500/day sanction for late submission or inadvertent submission of inaccurate information is unreasonably high. Additionally, the CAISO proposes to penalize not the Participating Generator, who is responsible for supplying the requested modeling data under the proposed procedures, but the Scheduling Coordinator. (See Section 10, Overview; and Section ). The Scheduling Coordinator could be a third party and may have no control over whether the Participating Generator submits accurate information or any information at all. Any penalties the CAISO Page 2 of 7 Under Section of the CAISO Tariff, the ISO is enforcing the $500/day penalty on late submissions. Please note that the ISO is allowing a 15 calendar day cure period if the submission is considered deficient prior to penalty being applied, as identified in section of the BPM Section 37 of the CAISO Tariff makes clear that the scheduling coordinator is the proper entity against which to levy penalties in the first instance. Where the scheduling coordinator can demonstrate that

3 assesses for failure to comply should focus on the entity responsible for providing the test reports and model data, rather than the Scheduling Coordinator. 1d (4) With regard to the Generator Data Templates posted by the CAISO, Section 10.3 of the proposed TPP BPM provides that the CAISO will provide Participating Generators with request letters for each unit, accompanied by completed Generator Data Templates reflecting the information that the CAISO and the relevant Participating TO currently have on file for the unit(s). The Six Cities urge the CAISO to provide this information to Participating Generators as promptly as possible. Without knowledge of the scope of information that the CAISO will supply versus the amount of information the Participating Generator is required to supply, it is difficult to assess the magnitude of the burden imposed by the requirement to provide a populated Generator Data Template. it played no part in the generator s failure to provide the required documentation, the scheduling coordinator potentially may avoid the impact of any such penalties. Section 37.8 contemplates that in some cases the ISO investigation must involve outreach to the market participant in addition to, or instead of, the scheduling coordinator. Under the circumstances covered by this BPM change, that means that where a participating generator does not submit the required information, any investigation the ISO conducts prior to assessing penalties may involve outreach to both the generator and its scheduling coordinator. Section 37.9, however, is specific that any Section 37 penalties first be assessed against the scheduling coordinator. Section , however, goes on to state that if a party other than the scheduling coordinator is responsible for the conduct giving rise to a penalty reflected on a Settlement Statement, and where the Scheduling Coordinator bears no responsibility for the conduct, such other party or parties ultimately shall be liable for the penalty. This Tariff section provides further detail on the procedures to follow where a scheduling coordinator looks to invoke this option. The ISO will be providing the data request letters and generator data templates reflecting the information on record, 6-7 months prior to submission deadline, which seems to be sufficient time for the generator owner to validate and update the data. The ISO believes that it already has clearly identified the requirements for each category through its BPM PRR and posted generator data templates, which allows generator owners to begin the required work now. Generator owners are encouraged to commence long lead items like generator testing as soon as possible, since the requirements are already clarified in the posted generator data templates. 1e (5) Section 10 does not specify the frequency of which it will require test reports and modeling data. The Overview section states that CAISO Tariff Section requires Participating Generators [to] provide the CAISO on an annual or periodic basis in accordance with the schedule, procedures and in the form required by the Business Practice Manual any information Page 3 of 7 The ISO notes this comment and will add additional clarification in the PRR revision addressing this concern. Due to the long lifecycle of the initial request, the ISO s intention is to propose the schedule for the next lifecycle of this process at a future time, based on data responses

4 and data reasonably required by the CAISO to perform the Transmission Planning Process..., but it does not go further in explaining whether the information is required annually or based on some other time period. received in this cycle and additional new generators becoming operational. 1f 1g 1h 1i (6) The proposed deadlines, particularly for Category 2 resources, may be inadequate. The Six Cities understand that Participating Generators may need to engage outside vendors in order to perform the model verification and testing required under the proposed TPP BPM provisions, and there are a limited number of vendors with the necessary capabilities and equipment. If the CAISO proceeds with the testing and verification requirements as proposed, it is possible that a large number of resources classified under Category 2 will need to have this testing and verification completed in advance of the 2021 deadlines. It may not be feasible for all Category 2 Participating Generators to schedule testing with a finite pool of vendors in the limited time allotted. (7) The CAISO s proposed testing and validation requirements do not account for the cost to perform the testing and validation. The Six Cities understand that the cost to complete the activities specified in the proposed TPP BPM provision may exceed $8,000-$10,000 per unit, separate and apart from any costs associated with removal of the unit(s) from service. Given the limited discussion of the need for this information from Category 2 resources, it is not clear that these costs are justified. (8) The CAISO and SCE have previously developed a Joint Transmission Planning Base Case Preparation Process pursuant to NERC Reliability Standard MOD How will this document interrelate with the proposed requirements of the TPP BPM? (9) The proposed revisions to the TPP BPM are far more specific and detailed than the Tariff provisions that the CAISO cites as authority for imposing Section 10 s requirements. Because the proposed changes to the TPP BPM arguably go beyond the scope of the current Tariff, the CAISO s Page 4 of 7 The ISO is allowing up to 3 years for Category 2 generators to schedule and complete their testing, which it considers to be sufficient lead time to complete this process. The ISO is not proposing any changes to the schedule at this time. Please note response to comment 1a, in terms of reliability need for this request. The ISO notes the comment on costs for generator testing. As per NERC MOD-032-1, the ISO, as a Planning Coordinator (PC), can request modelling data from its Generator Owners (GOs). The current initiative, PRR 1067 is in line with MOD The ISO will be updating all the different ISO-Transmission Planner (TP) Joint Transmission Planning Base Case Preparation Process documents to reference this BPM change in the generator data section, once the BPM is approved. Section of the CAISO Tariff provides the ISO with authority and discretion to require any information and data reasonably required by the CAISO to perform the Transmission Planning Process.... The ISO has determined that each data element required under the BPM

5 proposal to require Participating Generators to submit test reports and modeling data should remain an issue for discussion in the ongoing stakeholder initiative on 2018 Interconnection Process Enhancements. This initiative, which was the catalyst for the proposed revisions in PRR 1067, provides a broader forum for addressing the CAISO s proposed requirements. revision is reasonably related to the transmission planning process. As the nature of the transmission planning process changes over time, the ISO may adjust the information requirements, either by expanding or reducing the scope of information it requires under its section authority. The CAISO Tariff Section , defers to the BPM for requirements, schedule and process. The ISO has leveraged this authority in development of the proposed section 10 of the BPM for Transmission Planning Process, in order to provide greater detail and clarity to generator owners to respond to its request. Consequently, the ISO believes this issue is not required to be addressed in the ongoing 2018 Interconnection Process Enhancements. Page 5 of 7

6 Page 6 of 7 2. Southern California Edison (SCE) Submitted by: Aditya Chauhan 2a The CAISO has incorrectly identified the scheduling coordinator as responsible for compliance The technical data requested by the CAISO is relevant to physical design attributes of the generator and are known only to the generator owner (GO). The GO is not always the scheduling coordinator (SC). In such a case, the SC has not control over the GO s compliance with the result that the SC will simply be penalized without any change in data submission compliance. As the CAISO already has a participating generator agreement (PGA) with the GO, the CAISO should directly assign the penalty to the GO. The SC is not party to the PGA and inclusion of the SC in this process is unnecessary. Excluding any impact to the SC will not only guarantee the GO s compliance with data submission but will also maintain consistency with the CAISO policy of keeping contractual dealings independent from uninvolved parties in this case keeping the SC independent of PGA enforcement between the CAISO and the GO. Thus, SCE proposes the following language: Section 10 The failure of a participating generator to make a timely submission of the required information will subject the participating generator s scheduling coordinator to sanctions under CAISO Tariff Section Section Failure to make an initial submission by the deadline or failure to resubmit requested data during the 15-day cure period will subject the generating unit s scheduling coordinator owner to a $500/day penalty, as per CAISO Tariff section In the alternative, the CAISO should, at minimum, clearly delineate that the GO is responsible for the non-compliance penalty. In this case, SCE proposes the following language: Section 10 The failure of a participating generator to make a timely submission of the required information will subject the participating generator s Under Section of the CAISO Tariff, the ISO is enforcing the $500/day penalty on late submissions. Please note that the ISO is allowing a 15 day cure period if the submission is considered deficient before the penalty is applied, as identified in section of the BPM Section 37 of the CAISO Tariff makes clear that the scheduling coordinator is the proper entity against which to levy penalties in the first instance. Where the scheduling coordinator can demonstrate that it played no part in the generator s failure to provide the required documentation, the scheduling coordinator potentially may avoid the impact of any such penalties. Section 37.8 contemplates that in some cases the ISO investigation must involve outreach to the market participant in addition to, or instead of, the scheduling coordinator. Under the circumstances covered by this BPM change, this means that where a participating generator does not submit the required information any investigation the ISO conducts prior to assessing penalties may involve outreach to both the generator and its scheduling coordinator. Section 37.9, however, is specific that any Section 37 penalties first be assessed against the scheduling coordinator. Section , however, goes on to state that if a party other than the scheduling coordinator is responsible for the conduct giving rise to a penalty reflected on a Settlement Statement, and where the Scheduling Coordinator bears no responsibility for the conduct, such other party or parties ultimately shall be liable for the penalty. This Tariff section provides further detail on the procedures to follow where a scheduling coordinator looks to invoke this option.

7 scheduling coordinator to sanctions under CAISO Tariff Section 37.6, through notifications sent to the scheduling coordinator. Section Failure to make an initial submission by the deadline or failure to resubmit requested data during the 15-day cure period will subject the generating unit s scheduling coordinator owner to a $500/day penalty, as per CAISO Tariff section , through notifications sent to the scheduling coordinator. 2b SCE requests additional time for Category 3 generators SCE requests that the schedule proposed in Section be extended for Category 3 to SCE s Category 3 units are numerous, small, low capacity units of advanced age. These have been modified or retrofitted over the past several decades. Manufacturer data may be not be relevant for these units, and SCE is requesting additional time so it may perform tests on the units where manufacturer data may no longer apply. The ISO notes this comment but does not have a proposal for extending the submission deadline for Category 3 generators, at this time. Page 7 of 7

BUSINESS PRACTICE MANUAL CHANGE MANAGEMENT CAISO RESPONSE TO APPEALS

BUSINESS PRACTICE MANUAL CHANGE MANAGEMENT CAISO RESPONSE TO APPEALS BUSINESS PRACTICE MANUAL CHANGE MANAGEMENT CAISO RESPONSE TO APPEALS I. Introduction The CAISO followed its business practice manual change management process 1 and submitted proposed revision request

More information

Business Practice Manual for The Transmission Planning Process

Business Practice Manual for The Transmission Planning Process Business Practice Manual for The Transmission Planning Process Posted: June 2, 2015 Intentionally left blank TABLE OF CONTENTS 1. Introduction... 9 1.1. Purpose of California ISO Business Practice Manuals...

More information

Stakeholder Comments Template. Excess Behind the Meter Production: Draft Final Proposal

Stakeholder Comments Template. Excess Behind the Meter Production: Draft Final Proposal Stakeholder Comments Template : Draft Final Proposal This template has been created for submission of stakeholder comments on the Excess Behind the Meter Production: Draft Final Proposal that was published

More information

Business Practice Manual for the Transmission Planning Process

Business Practice Manual for the Transmission Planning Process Business Practice Manual for the Transmission Planning Process Order 890 Compliance Version 76.0 September 15,February 11, 2010 TABLE OF CONTENTS Order 890 Compliance... i 1. Introduction... 6 1.1 Purpose

More information

Business Practice Manual for Reliability Requirements. Version 34

Business Practice Manual for Reliability Requirements. Version 34 Business Practice Manual for Reliability Requirements Version 34 Last Revised: January 1, 2009July 28, 2010 Approval History Approval Date: 3/27/09 Effective Date: 3/31/09 BPM Owner: Chetty Mamandur BPM

More information

165 FERC 61,050 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION ORDER ACCEPTING PROPOSED TARIFF REVISIONS. (Issued October 29, 2018)

165 FERC 61,050 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION ORDER ACCEPTING PROPOSED TARIFF REVISIONS. (Issued October 29, 2018) 165 FERC 61,050 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION Before Commissioners: Neil Chatterjee, Chairman; Cheryl A. LaFleur and Richard Glick. California Independent System Operator

More information

NERC Compliance Public Bulletin # Guidance for Entities that Delegate Reliability Tasks to a Third Party Entity

NERC Compliance Public Bulletin # Guidance for Entities that Delegate Reliability Tasks to a Third Party Entity NERC Compliance Public Bulletin #2010-004 Guidance for Entities that Delegate Reliability Tasks to a Third Party Entity Version 2.0 July 16, 2015 Public Process Announcement I. Introduction This guidance

More information

Reliability Services Initiative Phase 2: Revised Draft Final Proposal

Reliability Services Initiative Phase 2: Revised Draft Final Proposal Reliability Services Initiative Phase 2: Revised Draft Final Proposal July 7, 2016 CAISO/M&IP/IP/EKim/KMeeusen 1 Table of Contents 1. Executive summary... 3 2. Changes to proposal and stakeholder comments...

More information

Revised Transmission Planning Process. Complete Final Proposal

Revised Transmission Planning Process. Complete Final Proposal Revised Transmission Planning Process Complete Final Proposal May 7, 2010 Complete Final Proposal 1. Introduction and Summary In this document the ISO provides a complete description of its revised transmission

More information

Individual Hamid Zakery Calpine Corp Yes

Individual Hamid Zakery Calpine Corp Yes Individual or group. (11 Responses) Name (4 Responses) Organization (4 Responses) Name (7 Responses) Lead Contact (7 Responses) Question 1 (9 Responses) Question 1 Comments (11 Responses) Question 2 (9

More information

Business Practice Manual for Metering. Version 56

Business Practice Manual for Metering. Version 56 Business Practice Manual for Metering Version 56 Last Revised: September 09, 2011 May 7, 2012 Approval History Approval Date: March 13, 2009 Effective Date: March 31, 2009 BPM Owner: Nancy TraweekBenik

More information

Business Practice Energy Imbalance Market (EIM BP) Revision Number: Revision Date: November 30July 29, 2015

Business Practice Energy Imbalance Market (EIM BP) Revision Number: Revision Date: November 30July 29, 2015 Revision Number: 3.02.1 Revision Date: November 30July 29, 2015 Revision Log 0.0 3/31/15 Pre-market initial draft 1.0 5/15/15 Email and phone contacts, Sections 3, 7, 8, 9, 11 and Appendix A for participating

More information

Reliability Coordinator Services. Rate Design, Terms and Conditions Straw Proposal COMMENTS TEMPLATE

Reliability Coordinator Services. Rate Design, Terms and Conditions Straw Proposal COMMENTS TEMPLATE Reliability Coordinator Services Rate Design, Terms and Conditions Straw Proposal COMMENTS TEMPLATE Company Contact Person Date Submitted Public Utility District #1, Chelan County, WA Chad Bowman 509 661

More information

Roles and Responsibilities: Standards Drafting Team Activities (Approved by Standards Committee June 2018)

Roles and Responsibilities: Standards Drafting Team Activities (Approved by Standards Committee June 2018) Roles and Responsibilities: Standards Drafting Team Activities (Approved by Standards Committee June 2018) Standards are developed by industry stakeholders, facilitated by NERC staff, following the process

More information

Standards for Imports of Regulation

Standards for Imports of Regulation Standards for Imports of Regulation Page 1 of 12 REVISION HISTORY VERSION NO. DATE REVISED BY DESCRIPTION 3.0 11/1/12 C. Sibley R. Kott S. Adigun Document review. Update of document template to current

More information

California Independent System Operator Corporation Fifth Replacement Electronic Tariff

California Independent System Operator Corporation Fifth Replacement Electronic Tariff Table of Contents California Independent System Operator Corporation 8. Ancillary Services... 3 8.1 Scope... 3 8.2 Ancillary Services Standards... 4 8.2.1 Determination Of Ancillary Service Standards...

More information

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION North American Electric Reliability Corporation Docket No. RR06-1-000 REQUEST FOR REHEARING OR CLARIFICATION OF THE TRANSMISSION

More information

Acceptance Criteria of a Reliability Standard Quality Objectives

Acceptance Criteria of a Reliability Standard Quality Objectives Acceptance Criteria of a Reliability Standard Quality Objectives Note: The Federal Energy Regulatory Commission (FERC or the Commission) established criteria in Order No. 672 that are used to assess Reliability

More information

California Independent System Operator Corporation Fifth Replacement Electronic Tariff

California Independent System Operator Corporation Fifth Replacement Electronic Tariff Table of Contents 8. Ancillary Services... 3 8.1 Scope... 3 8.2 Ancillary Services Standards... 4 8.2.1 Determination of Ancillary Service Standards... 4 8.2.2 Time-Frame for Revising Ancillary Service

More information

Consideration of Issues and Directives Project Connecting New Facilities to the Grid

Consideration of Issues and Directives Project Connecting New Facilities to the Grid Project 2010-02 Connecting New Facilities to the Grid Project 2010-02 Connecting New Facilities to the Grid is implementing the recommendations that the FAC Five-Year Review Team (FYRT) made with respect

More information

WECC Criterion INT-004-WECC-CRT-2.1

WECC Criterion INT-004-WECC-CRT-2.1 WECC Criterion INT-004-WECC-CRT-2.1 A. Introduction 1. Title: Reliability Curtailments and Reload 2. Number: INT-004-WECC-CRT-2.1 3. Purpose: To define treatment and approval of reliability curtailment

More information

Stakeholder Comments Template

Stakeholder Comments Template Stakeholder Comments Template Submitted by Company Date Submitted Margaret E. McNaul mmcnaul@thompsoncoburn.com 202.585.6940 Bonnie S. Blair bblair@thompsoncoburn.com 202.585.6905 Cities of Anaheim, Azusa,

More information

Six Cities Comments Generator Interconnection Driven Network Upgrade Cost Recovery Initiative. Revised Straw Proposal

Six Cities Comments Generator Interconnection Driven Network Upgrade Cost Recovery Initiative. Revised Straw Proposal Six Cities Comments Generator Interconnection Driven Network Upgrade Cost Recovery Initiative Submitted by Company Date Submitted Meg McNaul mmcnaul@thompsoncoburn.com 202-585-6940 Bonnie Blair bblair@thompsoncoburn.com

More information

UNITED STATES OF AMERICA 81 ferc 61, 320 FEDERAL ENERGY REGULATORY COMMISSION

UNITED STATES OF AMERICA 81 ferc 61, 320 FEDERAL ENERGY REGULATORY COMMISSION UNITED STATES OF AMERICA 81 ferc 61, 320 FEDERAL ENERGY REGULATORY COMMISSION Before Commissioners: James J. Hoecker, Chairman; Vicky A. Bailey, William L. Massey, Linda Breathitt, and Curt Hebert, Jr.

More information

Functional Mapping. Michael Dalebout Manager of Business Services

Functional Mapping. Michael Dalebout Manager of Business Services Michael Dalebout Manager of Business Services 2 Defined Why is WECC doing it now Importance of Current Situation New Reporting Capabilities Next Steps Questions 3 4 5 Importance of 6 Rules of Procedure

More information

Open Access Transmission Tariff ATTACHMENT K

Open Access Transmission Tariff ATTACHMENT K ATTACHMENT K PART I Introduction The Transmission Provider s (herein referred to as Tacoma Power) local transmission planning process will include open planning meetings that Tacoma Power will conduct

More information

Periodic Review Recommendation FAC System Operating Limits Methodology for the Planning Horizon

Periodic Review Recommendation FAC System Operating Limits Methodology for the Planning Horizon Periodic Review Recommendation FAC-010-3 - System Operating Limits Methodology for the Planning Horizon Introduction NERC is required to conduct a periodic review of each NERC Reliability Standard at least

More information

April 28, Filing of CAISO Rate Schedule No. 90 Docket No. ER

April 28, Filing of CAISO Rate Schedule No. 90 Docket No. ER California Independent System Operator Corporation The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426 April 28, 2017 Re: California

More information

California Independent System Operator Corporation. California ISO. Invoicing WECC NERC/ERO Costs. March 29, Prepared by: Michael Epstein

California Independent System Operator Corporation. California ISO. Invoicing WECC NERC/ERO Costs. March 29, Prepared by: Michael Epstein California Independent System Operator Corporation California ISO Invoicing WECC NERC/ERO Costs March 29, 2007 Prepared by: Michael Epstein Table of Contents 1. Executive Summary 2. Background 3. Overview

More information

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION California Independent System ) Docket No. ER10-1401-000 Operator Corporation ) ANSWER OF THE CALIFORNIA INDEPENDENT SYSTEM OPERATOR

More information

Issue Paper. Direct Participation of Demand Response Resources in CAISO Electricity Markets. December 22, CAISO JEP / BDC/ JDG 12/22/08, page 1

Issue Paper. Direct Participation of Demand Response Resources in CAISO Electricity Markets. December 22, CAISO JEP / BDC/ JDG 12/22/08, page 1 Issue Paper Direct Participation of Demand Response Resources in CAISO Electricity Markets December 22, 2008 CAISO JEP / BDC/ JDG 12/22/08, page 1 Direct Participation of DR Resources Table of Contents

More information

Dynamic Transfers Final Proposal

Dynamic Transfers Final Proposal Dynamic Transfers Final Proposal Provided in Support of 2009-2011 Stakeholder Process to Consider Expansion of Dynamic Transfer Services in ISO Tariff May 2, 2011 CAISO/M&ID/Dynamic Transfer Team May 2,

More information

CAISO EIM Straw Proposal Process

CAISO EIM Straw Proposal Process CAISO EIM Straw Proposal Process General Comments The Third Revised Straw Proposal shows progress toward a workable EIM. We appreciate the effort expended by the CAISO to address the issues raised by the

More information

Proposal for Elimination of CAISO Tariff Section Regarding Annual Operational Review

Proposal for Elimination of CAISO Tariff Section Regarding Annual Operational Review Proposal for Elimination of CAISO Tariff Section 22.1.2.2 Regarding Annual Operational Review August 22, 2014 I. Overview Section 22.1.2.2 of the CAISO tariff requires that each year an independent party

More information

Dynamic Transfers Revised Draft Final Proposal

Dynamic Transfers Revised Draft Final Proposal Dynamic Transfers Revised Draft Final Proposal Provided in Support of 2009-2011 Stakeholder Process to Consider Expansion of Dynamic Transfer Services in ISO Tariff Revised February 18, 2011 CAISO/M&ID/Dynamic

More information

ENERGY IMBALANCE MARKET BUSINESS PRACTICE ( EIM BP ) TABLE OF CONTENTS 1. Introduction 2. Communication with the PSEI EIM Entity 3.

ENERGY IMBALANCE MARKET BUSINESS PRACTICE ( EIM BP ) TABLE OF CONTENTS 1. Introduction 2. Communication with the PSEI EIM Entity 3. ENERGY IMBALANCE MARKET BUSINESS PRACTICE ( EIM BP ) TABLE OF CONTENTS 1. Introduction 2. Communication with the PSEI EIM Entity 3. PSEI EIM Participating Resource Application and Processing 3.1 Application

More information

Operating Procedure PURPOSE... 1

Operating Procedure PURPOSE... 1 No. 5320 Table of Contents PURPOSE... 1 1. RESPONSIBILITIES... 1 2. SCOPE/APPLICABILITY... 2 2.1. Background... 2 2.2. Scope/ Applicability... 2 3. PROCEDURE DETAIL... 3 3.1. Prerequisites... 3 3.2. Submit

More information

Business Requirements Specification

Business Requirements Specification Business Requirements Specification Flexible Resource Adequacy Criteria and Must- Offer Obligation Revision History Date Version Description 5/30/2013 1.0 Creation of Document 7/21/2013 1.1 Deletion of

More information

Storage as a Transmission Asset Stakeholder Comment Template

Storage as a Transmission Asset Stakeholder Comment Template Storage as a Transmission Asset Stakeholder Comment Template Submitted by Company Date Submitted Fernando E. Cornejo fernando.cornejo@sce.com Southern California Edison June 7, 2018 Please use this template

More information

Transmission Planning Process Phase 3 Competitive Solicitation

Transmission Planning Process Phase 3 Competitive Solicitation 2018 2019 Transmission Planning Process Phase 3 Competitive Solicitation Scott Vaughan Lead Grid Assets Engineer Chris Hillman Lead Grid Assets Engineer April 11, 2019 Transmission Planning Process Phase

More information

Revised Draft Final Proposal for Participation of Non-Generator Resources in California ISO Ancillary Services Markets

Revised Draft Final Proposal for Participation of Non-Generator Resources in California ISO Ancillary Services Markets Revised Draft Final Proposal for Participation of Non-Generator Resources in California ISO Ancillary Services Markets March 8, 2010 Revised Draft Final Proposal for Participation of Non- Generator Resources

More information

Comment Form for Functional Model Version 4 and Associated Technical Reference

Comment Form for Functional Model Version 4 and Associated Technical Reference Comment Form for Functional Model Version 4 and Associated Technical Reference Please use this form to submit comments on Version 4 of the Functional Model and its associated Technical Reference. must

More information

Six Cities Comments. Transmission Access Charge Options

Six Cities Comments. Transmission Access Charge Options Six Cities Comments Transmission Access Charge Options February 10, 2016 Straw Proposal & March 9 Benefits Assessment Methodology Workshop Submitted by Company Date Submitted Meg McNaul mmcnaul@thompsoncoburn.com

More information

Stakeholder Process: Commitment Cost Bidding Improvements. Summary of Submitted Comments

Stakeholder Process: Commitment Cost Bidding Improvements. Summary of Submitted Comments Stakeholder Process: Commitment Cost Bidding Improvements Attachment A Summary of Submitted Comments Two stakeholder initiatives are consolidated into one memo as both propose market improvements to ISO

More information

Commitment Cost Enhancements Phase 3 Action Plan

Commitment Cost Enhancements Phase 3 Action Plan Commitment Cost Enhancements Phase 3 Action Plan November 10, 2017 Table of Contents 1. Executive Summary... 3 2. Background... 3 3. Stakeholder Engagement... 6 4. Summary of Stakeholder Comments... 6

More information

RDRP Stakeholder Initiative

RDRP Stakeholder Initiative Reliability Demand Response Product RDRP Stakeholder Initiative Draft Final Proposal Review Stakeholder Conference Call September 13, 2010 Reliability Demand Response Product (RDRP) 1 2 3 We are here Project

More information

Addressing Affected System Impacts of Generator Interconnection: Processes and Principles

Addressing Affected System Impacts of Generator Interconnection: Processes and Principles Addressing Affected System Impacts of Generator Interconnection: Processes and Principles August 5, 2013 Table of Contents 1 Executive Summary... 2 2 Introduction... 2 3 Stakeholder Process and Schedule...

More information

Business Practice Manual for Metering. Version 1415

Business Practice Manual for Metering. Version 1415 Business Practice Manual for Metering Version 1415 Revised: May 25August 1October 1, 2016 Approval History Approval Date : March 13, 2009 Effective Date : March 13, 2009 BPM Owner BPM Owner s Title : Benik

More information

Storage as a Transmission Asset Stakeholder Comment Template

Storage as a Transmission Asset Stakeholder Comment Template Storage as a Transmission Asset Stakeholder Comment Template Submitted by Company Date Submitted Fernando E. Cornejo fernando.cornejo@sce.com Southern California Edison November 6, 2018 Please use this

More information

156 FERC 61,152 FEDERAL ENERGY REGULATORY COMMISSION WASHINGTON, DC September 1, 2016

156 FERC 61,152 FEDERAL ENERGY REGULATORY COMMISSION WASHINGTON, DC September 1, 2016 156 FERC 61,152 FEDERAL ENERGY REGULATORY COMMISSION WASHINGTON, DC 20426 September 1, 2016 California Independent System Operator Corporation Attn: Roger E. Collanton 250 Outcropping Way Folsom, CA 95630

More information

Five-Year Review Template Updated February 26, 2012

Five-Year Review Template Updated February 26, 2012 Five-Year Review Template Updated February 26, 2012 Introduction NERC has an obligation to conduct a five-year review of each Reliability Standard developed through NERC s American National Standards Institute-accredited

More information

Five-Year Review Template Updated February 26, 2012

Five-Year Review Template Updated February 26, 2012 Five-Year Review Template Updated February 26, 2012 Introduction NERC has an obligation to conduct a five-year review of each Reliability Standard developed through NERC s American National Standards Institute-accredited

More information

Comments of Pacific Gas and Electric Company on Draft Tariff Language Regulatory Must-Take Generation

Comments of Pacific Gas and Electric Company on Draft Tariff Language Regulatory Must-Take Generation Comments of Pacific Gas and Electric Company on Draft Tariff Language Regulatory Must-Take Generation Submitted by Company Date Submitted Hugh Merriam, 415-973-1269 Jeannette Woo, 415-973-5097 Pacific

More information

Reliability Coordinator Services Rate Design, Terms and Conditions Straw Proposal Comments of the Salt River Project

Reliability Coordinator Services Rate Design, Terms and Conditions Straw Proposal Comments of the Salt River Project Reliability Coordinator Services Rate Design, Terms and Conditions Straw Proposal Comments of the Salt River Project Company Contact Person Date Submitted Salt River Project (SRP) Steven Cobb, Director

More information

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION. NEW HARQUAHALA ) Docket No. RC GENERATING COMPANY, LLC )

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION. NEW HARQUAHALA ) Docket No. RC GENERATING COMPANY, LLC ) UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION NEW HARQUAHALA ) Docket No. RC08-4-002 GENERATING COMPANY, LLC ) COMPLIANCE FILING OF THE NORTH AMERICAN ELECTRIC RELIABILITY CORPORATION

More information

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION MANDATORY RELIABILITY STANDARDS ) FOR THE CALCULATION OF AVAILABLE ) Docket Nos. RM08-19-000 TRANSFER CAPABILITY, CAPACITY ) RM08-19-001

More information

Reliability Services Initiative Phase 2: Draft Final Proposal

Reliability Services Initiative Phase 2: Draft Final Proposal Reliability Services Initiative Phase 2: Draft Final Proposal January 26, 2016 CAISO/M&IP/IP/KMeeusen 1 Table of Contents 1. Executive summary... 4 2. Changes to proposal and stakeholder comments... 5

More information

Black Start and System Restoration Phase 2. Draft Final Proposal

Black Start and System Restoration Phase 2. Draft Final Proposal Black Start and System Restoration Phase 2 Draft Final Proposal March 14, 2017 Table of Contents 1 Introduction and Background... 3 2 Stakeholder process... 3 3 FERC Cost Allocation Principles... 4 4 Draft

More information

PJM Manual 14A: New Services Request Process Revision: 20 Effective Date: October 1, Prepared by Interconnection Planning Department

PJM Manual 14A: New Services Request Process Revision: 20 Effective Date: October 1, Prepared by Interconnection Planning Department PJM Manual 14A: New Services Request Process Revision: 20 Effective Date: October 1, 2017 Prepared by Interconnection Planning Department PJM 2017 Table of Contents Table of Contents Table of Exhibits...7

More information

Operating Procedure PURPOSE... 1

Operating Procedure PURPOSE... 1 No. 5360 Table of Contents PURPOSE... 1 1. RESPONSIBILITIES... 1 2. SCOPE/APPLICABILITY... 3 2.1. Background... 3 2.2. Scope/ Applicability... 3 3. PROCEDURE DETAIL... 3 3.1. Test Criteria... 3 3.2. Submit

More information

Acceptance Criteria of a Reliability Standard Quality Objectives

Acceptance Criteria of a Reliability Standard Quality Objectives Acceptance Criteria of a Reliability Standard Quality Objectives Note: The Federal Energy Regulatory Commission (FERC) has established in Order No. 672 criteria that will be used to assess reliability

More information

Storage as a Transmission Asset Stakeholder Comment Template

Storage as a Transmission Asset Stakeholder Comment Template Storage as a Transmission Asset Stakeholder Comment Template Submitted by Company Date Submitted Brian McDonald One Post Street, Suite 2550 San Francisco, CA 94104 925.989.7908 NextEra Energy Resources,

More information

March 12, 2014 VIA ELECTRONIC FILING. Veronique Dubois Régie de l'énergie Tour de la Bourse 800, Place Victoria Bureau 255 Montréal, Québec H4Z 1A2

March 12, 2014 VIA ELECTRONIC FILING. Veronique Dubois Régie de l'énergie Tour de la Bourse 800, Place Victoria Bureau 255 Montréal, Québec H4Z 1A2 March 12, 2014 VIA ELECTRONIC FILING Veronique Dubois Régie de l'énergie Tour de la Bourse 800, Place Victoria Bureau 255 Montréal, Québec H4Z 1A2 Re: North American Electric Reliability Corporation Dear

More information

155 FERC 61,229 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION ORDER ACCEPTING PROPOSED TARIFF REVISIONS SUBJECT TO CONDITION

155 FERC 61,229 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION ORDER ACCEPTING PROPOSED TARIFF REVISIONS SUBJECT TO CONDITION 155 FERC 61,229 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION Before Commissioners: Norman C. Bay, Chairman; Cheryl A. LaFleur, Tony Clark, and Colette D. Honorable. California Independent

More information

Approved by Standing Committees Approved by Board of Trustees

Approved by Standing Committees Approved by Board of Trustees Reliability Functional Model Function Definitions and Responsible Entities Prepared by the Functional Model Working Group Version 4 Approved by Standing Committees Approved by Board of Trustees August

More information

January 27, The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426

January 27, The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426 California Independent System Operator Corporation The Honorable Kimberly D. Bose Secretary Federal Energy Regulatory Commission 888 First Street, NE Washington, DC 20426 January 27, 2017 Re: California

More information

Reliability Coordinator Services. Rate Design, Terms and Conditions Straw Proposal COMMENTS TEMPLATE

Reliability Coordinator Services. Rate Design, Terms and Conditions Straw Proposal COMMENTS TEMPLATE Reliability Coordinator Services Rate Design, Terms and Conditions Straw Proposal COMMENTS TEMPLATE Company Contact Person Date Submitted Balancing Authority of Northern California and the Sacramento Municipal

More information

Review TAC Structure Revised Straw Proposal Stakeholder Meeting

Review TAC Structure Revised Straw Proposal Stakeholder Meeting Review TAC Structure Revised Straw Proposal Stakeholder Meeting April 11, 2018 Chris Devon, Market and Infrastructure Policy Agenda Time (PDT) Topic Presenter 10:00 10:10 am Welcome and introduction James

More information

Five-Year Review Template Updated February 26, 2012

Five-Year Review Template Updated February 26, 2012 Five-Year Review Template Updated February 26, 2012 Introduction NERC has an obligation to conduct a five-year review of each Reliability Standard developed through NERC s American National Standards Institute-accredited

More information

WESTERN ELECTRICITY COORDINATING COUNCIL GENERATING UNIT MODEL VALIDATION POLICY

WESTERN ELECTRICITY COORDINATING COUNCIL GENERATING UNIT MODEL VALIDATION POLICY WESTERN ELECTRICITY COORDINATING COUNCIL GENERATING UNIT MODEL VALIDATION POLICY A. Introduction A.1. Title: Generating Unit Model Validation Policy A.2. Purpose: Accurate models of generators and associated

More information

November 14, 2016 VIA ELECTRONIC FILING

November 14, 2016 VIA ELECTRONIC FILING November 14, 2016 VIA ELECTRONIC FILING David Erickson President and Chief Executive Officer Alberta Electric System Operator 2500, 330-5 Avenue SW Calgary, Alberta T2P 0L4 RE: North American Electric

More information

Response Deadline: October 30, 2017

Response Deadline: October 30, 2017 SOUTHERN CALIFORNIA PUBLIC POWER AUTHORITY Request for Proposals for Energy Scheduling and Trading, Credit, Risk Management, Contract Management, Settlements, and Related Services Request for Proposal

More information

California Independent System Operator Corporation Comments on Draft Resolution E-4909

California Independent System Operator Corporation Comments on Draft Resolution E-4909 California Independent System Operator Corporation Via U.S. Mail and Electronic Mail Energy Division Attn: Tariff Unit California Public Utilities Commission 505 Van Ness Avenue San Francisco, CA 94102

More information

Northeast Power Coordinating Council, Inc. Regional Reliability Standards Development Procedure

Northeast Power Coordinating Council, Inc. Regional Reliability Standards Development Procedure Northeast Power Coordinating Council, Inc. Regional Reliability Standards Development Procedure Approved by NPCC Board of Directors September 19, 2007 Approved by NERC BOT October 23, 2007 Adopted by FERC

More information

Reliability Demand Response Product

Reliability Demand Response Product Reliability Demand Response Product CAISO Response to Stakeholder Comments on the RDRP Straw Proposal Prepared for The Reliability Demand Response Product Stakeholder Initiative September 1, 2010 Comments

More information

Black Start and System Restoration Phase 2. Issue Paper

Black Start and System Restoration Phase 2. Issue Paper Black Start and System Restoration Phase 2 Issue Paper January 17, 2016 California ISO Straw Proposal Table of Contents 1 Introduction and Background... 3 2 Additional Procurement and Cost Allocation...

More information

Technical Justification Resource Document Project Generator Requirements at the Transmission Interface Updated July 16, 2012

Technical Justification Resource Document Project Generator Requirements at the Transmission Interface Updated July 16, 2012 Technical Justification Resource Document Project 2010-07 Generator Requirements at the Transmission Interface Updated July 16, 2012 I. Background As part of its work on Project 2010-07 Generator Requirements

More information

Review of Data Change Management Processes for RTCA and Planning Models (Recommendation 16) March, 2017

Review of Data Change Management Processes for RTCA and Planning Models (Recommendation 16) March, 2017 Review of Data Change Management Processes for RTCA and Planning Models (Recommendation 16) March, 2017 Background In April 2012, the Federal Energy Regulatory Commission (FERC) and the North American

More information

Project : Generator Requirements at the Transmission Interface Background Resource Document

Project : Generator Requirements at the Transmission Interface Background Resource Document Project 2010-07: Generator Requirements at the Transmission Interface Background Resource Document Introduction The integrated grid consists of many parts such as power plants, Transmission, and Facilities

More information

Reliability Standards Development Plan:

Reliability Standards Development Plan: Reliability Standards Development Plan: 2010 2012 Volume I Overview October 7, 2009 Reliability Standards Development Plan: 2010 2012 Acknowledgement The NERC Reliability Standards Program would like to

More information

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION ) )

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION ) ) UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION North American Electric Reliability Corporation ) ) Docket No. PETITION OF THE NORTH AMERICAN ELECTRIC RELIABILITY CORPORATION FOR

More information

Stakeholder Comments Template. Generator Interconnection Procedures Phase 3 ( GIP 3 ) Issue Paper, posted March 1, 2012

Stakeholder Comments Template. Generator Interconnection Procedures Phase 3 ( GIP 3 ) Issue Paper, posted March 1, 2012 Stakeholder Comments Template Generator Interconnection Procedures Phase 3 ( GIP 3 ) Issue Paper, posted March 1, 2012 Please submit comments (in MS Word) to GIP3@caiso.com no later than the close of business

More information

California Independent System Operator Corporation Fifth Replacement Electronic Tariff

California Independent System Operator Corporation Fifth Replacement Electronic Tariff Table of Contents 40. Resource Adequacy Demonstration for all SCs in the CAISO BAA... 3 40.1 Applicability... 3 40.1.1 [Not Used]... 3 40.2 Information Requirements for Resource Adequacy Programs... 3

More information

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION ) )

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION ) ) UNITED STATES OF AMERICA BEFE THE FEDERAL ENERGY REGULATY COMMISSION North American Electric Reliability Corporation ) ) Docket No. JOINT PETITION OF THE NTH AMERICAN ELECTRIC RELIABILITY CPATION AND RELIABILITYFIRST

More information

MOD Steady-State and Dynamic System Model Validation

MOD Steady-State and Dynamic System Model Validation MOD-033-1 Steady-State and Dynamic System Model Validation A. Introduction 1. Title: Steady-State and Dynamic System Model Validation 2. Number: MOD-033-1 3. Purpose: To establish consistent validation

More information

Pay for Performance Stakeholder Comments Issue Paper and Straw Proposal

Pay for Performance Stakeholder Comments Issue Paper and Straw Proposal Pay for Performance Stakeholder Comments Issue Paper and Straw Proposal California Department of Water Resources State Water Project... 1 Summary... 1 Comments... 1 California Energy Storage Alliance...

More information

133 FERC 61,074 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION. 18 C.F.R. Part 40. Docket No. RM

133 FERC 61,074 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION. 18 C.F.R. Part 40. Docket No. RM 133 FERC 61,074 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION 18 C.F.R. Part 40 Docket No. RM09-19-000 Western Electric Coordinating Council Qualified Transfer Path Unscheduled Flow Relief

More information

166 FERC 61,138 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION. California Independent System Operator Corporation

166 FERC 61,138 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION. California Independent System Operator Corporation 166 FERC 61,138 UNITED STATES OF AMERICA FEDERAL ENERGY REGULATORY COMMISSION Before Commissioners: Neil Chatterjee, Chairman; Cheryl A. LaFleur, Richard Glick, and Bernard L. McNamee. California Independent

More information

Pursuant to the California Independent System Operator s ( CAISO s ) February 7, 2013

Pursuant to the California Independent System Operator s ( CAISO s ) February 7, 2013 Pathfinder Renewable Wind Energy, LLC and Zephyr Power Comments on the CAISO Draft 2013/2014 Transmission Planning Process Unified Planning Assumptions and Study Plan Pursuant to the California Independent

More information

Guidance for Handling Policy Initiatives within the Decisional Authority or Advisory Role of the EIM Governing Body

Guidance for Handling Policy Initiatives within the Decisional Authority or Advisory Role of the EIM Governing Body Policy Adopted Policy Adopted I. Introduction Relying on recommendations from the EIM Transitional Committee comprised of stakeholders from throughout the region, the ISO Board of Governors established

More information

Reforms to Improve Gas-Electric Coordination Mark R. Haskell, Floyd L. Norton, IV, Brett A. Snyder April 29, 2014

Reforms to Improve Gas-Electric Coordination Mark R. Haskell, Floyd L. Norton, IV, Brett A. Snyder April 29, 2014 Reforms to Improve Gas-Electric Coordination Mark R. Haskell, Floyd L. Norton, IV, Brett A. Snyder April 29, 2014 www.morganlewis.com Presentation Overview Revisions to the operating and scheduling processes

More information

Mapping of Revised TOP and IRO Reliability Standards to Address 2011 Southwest Outage Report Recommendations

Mapping of Revised TOP and IRO Reliability Standards to Address 2011 Southwest Outage Report Recommendations Mapping of Revised TOP and IRO Reliability Standards to Address 2011 Southwest Outage Report Recommendations The following table provides a mapping of the recommendations applicable to the Reliability

More information

Transmission Competitive Solicitation Questions Log Question / Answer Matrix Delaney to Colorado River 2014

Transmission Competitive Solicitation Questions Log Question / Answer Matrix Delaney to Colorado River 2014 No. Comment Submitted ISO Response Date Q&A Posted 1 Can the CAISO provide a line rating methodology (similar to a NERC FAC-008 standard) or include a requirement of using any The ISO does not provide

More information

Storage as a Transmission Asset Stakeholder Comment Template

Storage as a Transmission Asset Stakeholder Comment Template Storage as a Transmission Asset Stakeholder Comment Template Submitted by Company Date Submitted Jan Strack San Diego Gas & Electric June 7, 2018 Please use this template to provide your comments on the

More information

Business Practice Manual for Metering

Business Practice Manual for Metering Business Practice Manual for Metering Version 187 Revised: October 27, 2017May 24 th, 2018 Formatted: Superscript Approval History Approval Date : March 13, 2009 Effective Date : March 13, 2009 BPM Owner

More information

PJM Manual 21: Rules and Procedures for Determination of Generating Capability Revision: 12 Effective Date: January 1, 2017

PJM Manual 21: Rules and Procedures for Determination of Generating Capability Revision: 12 Effective Date: January 1, 2017 PJM Manual 21: Rules and Procedures for Determination of Generating Capability Revision: 12 Effective Date: January 1, 2017 Prepared by System Planning Department PJM 2017 Table of Contents Table of Contents

More information

Five-Year Review Template Updated February 26, 2012

Five-Year Review Template Updated February 26, 2012 Five-Year Review Template Updated February 26, 2012 Introduction NERC has an obligation to conduct a five-year review of each Reliability Standard developed through NERC s American National Standards Institute-accredited

More information

Storage as a Transmission Asset:

Storage as a Transmission Asset: Storage as a Transmission Asset: Enabling transmission connected storage assets providing regulated cost-of-service-based transmission service to also access other market revenue streams March 30, 2018

More information

Business Requirements Specification

Business Requirements Specification Business Requirements Specification Energy Storage and Distributed Energy Resources Phase -2 Doc ID: GNFDMDEHU6BB-46-53 Page 1 of 18 Disclaimer All information contained in this draft Business Requirements

More information

MOD Data for Power System Modeling and Analysis

MOD Data for Power System Modeling and Analysis MOD-032-1 Data for Power System Modeling and Analysis A. Introduction 1. Title: Data for Power System Modeling and Analysis 2. Number: MOD-032-1 3. Purpose: To establish consistent modeling data requirements

More information