DVPEC. Multi-Position, Variable-Speed air handler. Comfortnet Compatible ECM-based Internal EEV, Inverter-tuned 2 to 5 Tons

Size: px
Start display at page:

Download "DVPEC. Multi-Position, Variable-Speed air handler. Comfortnet Compatible ECM-based Internal EEV, Inverter-tuned 2 to 5 Tons"

Transcription

1 DVPEC Multi-Position, Variable-Speed air handler Comfortnet Compatible ECM-based Internal EEV, Inverter-tuned 2 to 5 Tons Contents Nomenclature... 2 Product Specifications... 3 Dimensions... 4 Airflow Data... 5 Heat Kit Data... 6 Wiring Diagram... 8 Product Features Electronic Expansion Valve (EEV) for cooling and heat pump applications. Variable-speed ECM blower motor ComfortNet Communicating System compatible Provides constant CFM over a wide range of static pressure conditions independent of duct system CFM indicator Thermostat provides adjustable low CFM for efficient fan-only operation All-aluminum evaporator coil Fault recall of six most recent faults Improved humidity and comfort control AHRI certified; ETL listed Cabinet air leakage less than 2.0% at 1.0 inch H₂O when tested in accordance with ASHRAE standard 193 Cabinet air leakage less than 1.4% at 0.5 inch H₂O when tested in accordance with ASHRAE standard kw 25 kw electric heater kits Horizontal or vertical configuration capabilities 21" depth for easier attic access DecaBDE-free thermoplastic drain pan with secondary drain connections Screw-less sides and back helps to reduce condensation when installed in humid locations Foil-faced insulation covers the internal casing to reduce cabinet condensation Galvanized, leather grain-embossed finish Glue-less cabinet insulation retention Tool-less filter access * Complete warranty details available from your local dealer or at To receive the 12-Year Parts Limited Warranty, online registration must be completed within 60 days of installation. Additional requirements for annual maintenance are required for the Unit Replacement Limited Warranty. Online registration and some of the additional requirements are not required in California or Quebec. SS-DVPEC 7/17 Supersedes 4/17

2 Nomenclature D V 24 P E C 1 2 3, C 1 4 AA ,12 Brand Engineering * D - Daikin Single- Piece Major/ Minor Revisions Air Handler *Not used for inventory management Unit Application Refrigerant Compatability V - Multi- Position 4 = R- 410A Variable- Speed Motor Electrical Nominal Capacity Range 1-208/240 V, 1 Phase, 60 Hz 25-2 Tons 59-4 Tons 37-3 Tons 61-5 Tons Cabinet Width B = 17½" C = 21" Cabinet Finish D = 24½" P - Painted Communications Expansion Device C - ComfortNet Compatible E - Electronic Expansion Valve HKS X 03 X A AA ,7 Unit Type Revisions HKS Heat Kit for Engineering Revisions Air Handlers Phase Circuit Breaker A Single Phase 208 V E Three Phase 240 V X No circuit breaker B Single Phase 240 V F Three Phase 208/240 V C Circuit Breaker C Single Phase 208/240 V G Three Phase 460 V D Three Phase 208 V Heating 240 Volts kw kw Cabinet Size (MAX) kw kw wth 150F limit C C Cabinet kw kw with 170F limit D D Cabinet kw kw X All Cabinet Sizes kw 2 SS-DVPEC

3 Product Specifications DV25PEC B14A* DV37PEC C14A* DV59PEC D14A* DV61PEC D14A* Nominal Ratings Cooling (BTU/h) 24,000 36,000 48,000 60,000 Blower Diameter 10⅝" 10⅝" 11⅝" 11⅝" Width 6 10⅝" 10⅝" 10⅝" Coil Connections Liquid ⅜" ⅜" ⅜" ⅜" Suction ¾ ⅞" ⅞" ⅞" Coil Drain Connection (FPT) ¾" ¾ ¾ ¾ Electrical Data Voltage 208/ / / /240 Min Circuit Ampacity 4.9/ / / /8.6 Max. Overcurrent Device (Amps) 15/15 15/15 15/15 15/15 Minimum VAC Maximum VAC Blower Motor Full Load Amps (FLA) Horsepower (HP) ½ ¾ 1 1 Ship Weight (Lbs.) Note: Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOP) for blower without supplemental heat installed. Refer to unit nameplate and/or Heat Kit Data for specification with approved accessory heaters installed. SS-DVPEC 3

4 Dimensions 7 3/16" (18.26 cm) 6 1/8" (15.56 cm) 4 1/2" (11.43 cm) K C 5/8" (1.59 cm) B 5/8" (1.59 cm) J 4 5/16" (4.31 cm) 2 1/8" (5.40 cm) 9 1/4" (23.50 cm) 7 1/2" (19.05 cm) 5 1/8" (13.02 cm) 3 1/8" (7.94 cm) 1 3/8" (3.49 cm) 21" (55.88 cm) 11 5/16" (28.73 cm) 1/2" (1.27 cm) 1 5/8" (4.13 cm) 1 5/16" (3.33 cm) 1 3/4" (4.45 cm) HORIZONTAL DRAIN PORT DETAIL 2 11/16" (6.83 cm) 1 3/4" (4.45 cm) 3 1/16" (7.78 cm) A G SEE HORIZONTAL DRAIN PORT DETAIL SUCTION TUBE LIQUID LINE INLET TUBE 2 15/16" (7.46 cm) 3 3/4" (9.53 cm) 1 5/8" (4.13 cm) 10 3/16" (25.88 cm) E D VERTICAL DRAIN PORT DETAIL SEE VERTICAL DRAIN PORT DETAIL H 1 13/16" (4.60 cm) F INLET (FRONT VIEW) 1 13/16" (4.60 cm) 1 " (2.54 cm) 19.5" (49.53 cm) 9/16 (1.43 cm) INLET (RIGHT SIDE VIEW) Model A B C D E F G H DV25PECB14 53⁷ ₁₆ 16⅜ 17½ 20 21½ 14⅛ 9⅛ 7⅝ DV37PECC14 53⁷ ₁₆ 19⅞ 21 21¹³ ₁₆ 18⅝ 17¹¹ ₁₆ 10¹³ ₁₆ 6¹³ ₁₆ DV59PECD14 53⁷ ₁₆ 23⁵ ₁₆ 24½ 21½ 18⁵ ₁₆ 21³ ₁₆ 12⅝ 6⅞ DV61PECD ⁵ ₁₆ 24½ 26⅛ 22⅞ 21³ ₁₆ 12⁵ ₁₆ 25⅛ 4 SS-DVPEC

5 Airflow Data Model Rated Air flow CFM DV25PECB14A* DV37PECC14A* DV59PECD14A* DV61PECD14A* Model Maximum Air flow CFM DV25PECB14A* DV37PECC14A* DV59PECD14A* DV61PECD14A* Note: The chart is for information only. For satisfactory operation, external static pressure must not exceed value shown on rating plate. Use the CFM adjustment factors of.98 for horizontal left,.95 for horizontal right &.96 for downflow orientations. Airflow data indicated is at 230V without air filter in place. SS-DVPEC 5

6 Heat Kit Data Models Circuit 1 Circuit 2 Single-Point Kit Amps MCA¹ MOP² Amps MCA¹ MOP² MCA¹ MOP² DV25PECB14AC 0.0/ /4.9 15/ HKSX03XC V HKSX05XC V HKSX06XC V No Breaker HKSX08XC V HKSX10XC V HKSC05XC V HKSC08XC V Breaker HKSC10XC V HKSX03XC V HKSX05XC V HKSX06XC V No Breaker HKSX08XC V HKSX10XC V HKSC05XC V HKSC08XC V Breaker HKSC10XC V DV37PECC14AC 0.0/ /6.5 15/ HKSX03XC V HKSX05XC V HKSX06XC V No Breaker HKSX08XC V HKSX10XC V HKSC05XC V HKSC08XC V HKSC10XC V HKSC15XA V Breaker HKSC19CA V HKSC15XF V ^ HKSC20XF V ^ HKSX03XC V HKSX05XC V HKSX06XC V No Breaker HKSX08XC V HKSX10XC V HKSC05XC V HKSC08XC V HKSC10XC V HKSC15XB V Breaker HKSC19CB V HKSC15XF V ^ HKSC20XF V ^ DV59PECD14AC 0.0/ /8.6 15/ HKSX03XC V HKSX05XC V HKSX06XC V No Breaker HKSX08XC V HKSX10XC V HKSC05XC V HKSC08XC V Breaker HKSC10XC V SS-DVPEC

7 Models Circuit 1 Circuit 2 Single-Point Kit Amps MCA¹ MOP² Amps MCA¹ MOP² MCA¹ MOP² HKSC15XB V Breaker HKSC20DH V HKSX03XC V HKSX05XC V HKSX06XC V No Breaker HKSX08XC V HKSX10XC V HKSC05XC V HKSC08XC V HKSC10XC V Breaker HKSC15XB V HKSC20DB V DV61PECD14AC 0.0/ /8.6 15/ HKSX03XC V HKSX05XC V HKSX06XC V No Breaker HKSX08XC V HKSX10XC V HKSC05XC V HKSC08XC V HKSC10XC V Breaker HKSC15XB V HKSC20DH V HKSC25DA V HKSX03XC V HKSX05XC V HKSX06XC V No Breaker HKSX08XC V HKSX10XC V HKSC05XC V HKSC08XC V HKSC10XC V Breaker HKSC15XB V HKSC20DB V HKSC25DB V ¹ Minimum Circuit Ampacity (Heater Amps + Motor Amps) X 1.25 ² Maximum Overcurrent Protection = 2.25 X Motor Amps + Heater Amps 3 Notation is correct as XB because technically the 240V heater kit application can be used here without any issues. ^ Circuit 1: Single-phase for Air Handlers Circuit 2: Three-phase for HKR3 Heater Kits --- indicates Not Required Heating kw Correction Factor Supply Voltage Correction Factor Multiply the 240-volt heating capacity by correction factors. SS-DVPEC 7

8 Wiring Diagram BR (SEE NOTE 4) GROUND LUG WH THERMOSTAT PL1 (SEE NOTE 7) GY PL2 AC24V COM VAC COM VAC VAC VAC TR2 TR1 (SEE NOTE 1) (SEE NOTE 1) 24VAC 24VAC CONNECTION DISAED INSTALLING GR AUX ALARM (ALARM) (SEE NOTE 9) ~ TR2 TB3 COM TH1 TR1 TB7 TB1 TB2 O Y2 Y1 W2 W1 G C R 2 1 TB4 TH2 DEHUM TB10 F1U X8A ~ TB5 TB4 X12A X13A TB5 F2U RX LED RELAY IN (SEE NOTE 6) (ACC-IN) TB6 X7A ~ RELAY OUT (ACC-OUT) HEATER KIT OUTPUT TB8 TB9 K1R K2R NOTES: 1. PLACE RED WIRES ON 208 V TERMINAL OF 2-TRANSFORMER (TR1/TR2) FOR 208 VAC OPERATION. 2. MANUFACTURER'S SPECIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING. 3. IF ANY OF THE ORIGINAL WIRES AS SUPPLIED WITH THIS UNIT MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105 C. USE COPPER CONDUCTORS ONLY. 4. UNIT MUST BE PERMANENTLY GROUNDED AND CONFORM TO N.E.C ANDLOCAL CODES. 5. TO RECALL THE LAST 6 FAULTS, MOST RECENT TO LEAST RECENT, DEPRESS FAULT RECALL BUTTON FOR MORE THAN 2 SECONDS WHILE IN STANDBY (NO THERMOSTAT INPUTS) 6. RED STATUS LED PROVIDES NETWORK STATUS. GREEN RX LED INDICATES NETWORK TRAFFIC. USE LEARN BUTTON TO RESET NETWORK. 7. DISCA CONNECTOR PL1 WHEN INSTALLING OPTIONAL HEAT KIT. X1A K3R X3A EEV OR YL M EEV COIL 8. THE POSITION OF SELECTOR SWITCHES (DS1 - DS6) INDICATE FACTORY SETTING. X2A SHARE DATA PS SEG2 SEG1 DS6 THERMISTOR PRESSURE SENSOR (HEAT EXCHANGER 1,2) INTEGRATION TYPE S21 S22 S23 S24 FLASH WRITER CPU LED RAM MONITOR (SEE NOTE 5) FAULT RECALL BS2 DS1 DS2 DS3 BS1 (SEE NOTE 6) LEARN STATUS LED (SEE NOTE 6) INTEGRATED CONTROL: LOW VOLTAGE LOW VOLTAGE FIELD HIGH VOLTAGE HIGH VOLTAGE FIELD JUNCTION TERMINAL INTERNAL TO RESISTOR OVERCURRENT PROT. DEVICE PLUG CONNECTION EQUIPMENT GND FIELD GROUND MPU S1 S2 S3 S4 ON OFF S5 S6 S7 S8 DS5 DS4 S9 S10 S11 S12 S13 S14 S15 S16 S17 S18 S19 S20 EARTH INDOOR AIR CIRCULATIOR WR GY GR 24V THERMOSTAT CONNECTIONS COLOR CODES: - UE - RED YL - YELLOW OR - ORANGE - ACK GY - GREY BR - BROWN GR - GREEN R W1 W2 Y1 Y2 O DEHUM C DISCONNECT L1 FUSE 3 A TO MICRO L1 TH PL1, PL2 W1 (1) W2 (2) CAS (1) CAS (2) DS1 - DS6 TL TR F1U, F2U VDC (1) RX (2) TX (3) GRND (4) TR INDOOR AIR CIRCULATOR WR COMPONENT CODES: GRND 208/230 VAC 24 VAC COM INTEGRATED CONTROL MODULE POWER/HEATER CONNECTOR SELECTOR SWITCH THERMAL LIMIT TRANSFORMER FUSE LINK L2 GRND L2 40 VA TRANSFORMER HEAT 1 COIL/R1 HEAT 2 COIL/ R2 CONDENSATE SWITCH INDOOR AIR CIRCULATOR WR GRND 9. REMOVE SHORT RED CIRCUITING WIRE AND PUT AUX ALARM SWITCH WHEN INSTALLING AUX ALARM SWITCH. USE N.E.C CLASS 2 WIRE. 0140A00322-A Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. Warning High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death. Our continuing commitment to quality products may mean a change in specifications without notice Houston, Texas Printed in the USA 8 SS-DVPEC