TRICOR Series TCM Coriolis Mass Flow Meters

Size: px
Start display at page:

Download "TRICOR Series TCM Coriolis Mass Flow Meters"

Transcription

1 TRICOR Series Coriolis Mass Flow Meters Technical Datasheet Original KEM Document _E68_D_EN_16050_E001

2 TRICOR - Coriolis Mass Flow Meters Description The TRICOR Coriolis Mass Flow Meters from TASI Flow are absolutely reliable and robust sensors in a variety of processes, performing multiple measurements simultaneously with customizable process parameters and multiple communication languages. The TRICOR production team mechanically balances every meter, assuring the dual tubes are dynamically aligned and in perfect balance before flow begins. The unique design and cutting edge manufacturing procedures ensure a meter with the highest resistance to external influences. Features All-in-one instrument: direct measurement of mass flow, density and temperature, calculated measurement of volumetric flow No moving parts: low maintenance, no need for recalibration Easy to install: no straight run of pipe required and multiple mounting options available Mechanically balanced tubes and superior mechanical design for best-in-class density measurement Exceptional mechanical design resists external interference API gravity reading in software Exceptional ease of use and fast setup time: we will pre-program your process parameters Frequency output up to 10,000 Hz resolution Superior meter calibration: DAkkS-Accreditation as per DIN EN ISO/IEC 1705:005 Easily accessible, integrated meter diagnostics to verify meter health & performance Hazardous area certifications: ATEX, IECEx, ccsaus, EAC (TR-CU) Customized process connections available Principle of operation Coriolis Mass Flow Meters () operate with two tubes with coils that cause them to oscillate at their resonance frequency. Should a measurement flow enter the measuring tube, Coriolis forces are the result. Coriolis forces appear in oscillating systems when a mass moves towards or away from a rotational axis. These forces act on the inlet and outlet side in the opposite direction and minimally deform the measuring tubes. The deflection of the measurement tubes is captured by sensors on the inflow and outflow side. These two sensors measure a phase shift that is proportional to the mass flow. The resonance frequency of the tubes varies depending on the density of the medium to be measured. This effect is used to measure the density of the medium. Since the elastic properties of the flow tubes depend on the temperature, a temperature measurement is carried out for compensation. The primary characteristics such as mass flow rate, density and temperature are measured with a single flow meter. The volume flow can be determined based on the mass flow rate and density. Additional Options Net Oil software High pressure designs available up to 345 bar/5000 PSI Special calibrations for an oil viscosity up to 100 mm /s Integrated pressure compensation Customizable installation length Extended warranty

3 Coriolis Mass Flow Meters - TRICOR Product Overview Compact version Exd housing: Wall mounted (remote version) Version with TCE 6000 (including options) Housing: Panel mounted (remote version) 3

4 TRICOR - Coriolis Mass Flow Meters Transducer - Technical Data for Liquids Max. Flow Rate (kg/h) Max. Flow Rate (lb/min) Basic Accuracy (% o.r.) ±0.1 Zero Stability (% f.s.) ±0.01 Repeatability (% o.r.) ± K 065K 30K Density Measuring Range kg/m³,.5 g/cm 3 (higher ranges on request) Density Accuracy ±1.0 kg/m 3, ±0.001 g/cm 3 (special calibration on request) Density Repeatability ±0.5 kg/m 3, ± g/cm 3 Temperature Accuracy Temperature Repeatability ±1 C ±0.5 % of reading (±1.8 F ±0.5 % of reading) ±0. C (±0.36 F) Process and Ambient Process Connections Max. Pressure Standard (Option) Pressure Drop at Max. Flow female thread 1/ adaptors for flanges, dairy and tri-clamp 00 bar/900 PSI (345 bar/5000 PSI) flanges EN109, ANSI B16.5, DIN51, threaded tri-clamp 100 b ar/1450 PSI for detail information please contact us -40 C C (-40 F F) (standard) Process Temperature (non Ex) -40 C C (-40 F F) (optional) -60 C C (-76 F F) (optional) meter mount -40 C C (-40 F F) (T4) n/a Process Temperature (Ex) remote version -40 C C (-40 F F) (T4) -40 C C (-40 F F) (T3) -60 C C (-76 F F) (T) Ambient Temperature -40 C C (-40 F F) Storage Temperature -40 C C (-40 F F) Electr. Connections Remote screw type terminals Electr. Connections Meter Mount none (internally connected to the electronics) Ingress Protection IP65 (IP66/IP67 on request) General Tube Arrangement serial serial Tube Inner Diameter 4 mm 4 mm 8 mm 8 mm 7 mm 9 mm 16 mm 8 mm 43 mm Tube Material /AISI 316L Housing Material Dimensions /AISI 316L see drawings /AISI 304 optional: /AISI 316L Calibration for Liquids and Gases: The TRICOR flowmeters are always factory calibrated with water. Calibration Conditions: Water : 0 C... 5 C (68 F F), ambient temperature : 0 C... 5 C (68 F F) All specifications are based on above mentioned calibration reference conditions, a flow calibration protocol is attached to each instrument. Stated accuracy combines the effects of repeatability, linearity and hysteresis. Typical flow dynamics based on max. flow rate is 100: / AISI 316L 4

5 Coriolis Mass Flow Meters - TRICOR Accuracy for Liquids Flow Rate of full Scale Accuracy Zero Point Basic Accuracy * 100 ± Basic Accuracy < Zero Point Basic Accuracy * 100 ± Zero Point Measured Value * 100 Example for a 035: 35 kg/h * ZeroPoint (0.01 %) = kg/h 1 lb/min * 0.01 % = lb/min 35 kg/h * Basic Accuracy (0.1 %) = 0.35 kg/h 1 lb/min * 0.5 % = 0.01 lb/min Result: (0.035 / 0.35) * 100 = 10 % (3.5 kg/h) (0.001 / 0.01) * 100 = 10 % (1. lb/min) All flow rates 10 % or 3.5 kg/h (1. lb/min): Measured error = Basic Accuracy All flow rates < 10 % or 3.5 kg/h (1. lb/min): Measured error = (Zero Point / Measured Value) * 100 5

6 TRICOR - Coriolis Mass Flow Meters Transducer - Technical Data for Gases Nom. Flow Rate (kg/h) 1) 3) Nom. Flow Rate (lb/min) 1) 3) Nom. Flow Rate (Nm 3 /h) 1) ) Nom. Flow Rate (SCFM) 1) ) Basic Accuracy (% o.r.) ±0.5 Zero Stability in kg/h (lb/min) (0.001) (0.004) (0.0057) 0.31 (0.0114) 0.55 (0.00) Repeatability (% o.r.) ± (0.09) 08K.8 (0.103) 065K 6.5 (0.39) 30K 3 (0.845) Density Measuring Range see comment 3) Density Accuracy ±.0 kg/m 3, ±0.00 g/cm 3 (special calibration on request) Density Repeatability ±1 kg/m 3, ±0.001 g/cm 3 Temperature Accuracy Temperature Repeatability ±1 C ±0.5 % of reading (±1.8 F ±0.5 % of reading) ±0. C (±0.36 F) Process and Ambient Process Connections Max. Pressure Standard (Option) Pressure Drop at Max. Flow female thread 1/ adaptors for flanges, dairy and tri-clamp 00 bar/900 PSI (345 bar/5000 PSI) flanges EN109, ANSI B16.5, DIN51, threaded tri-clamp 100 b ar/1450 PSI for detail information please contact us -40 C C (-40 F F) (standard) Process Temperature (non Ex) -40 C C (-40 F F) (optional) -60 C C (-76 F F) (optional) meter mount -40 C C (-40 F F) (T4) n/a Process Temperature (Ex) remote version -40 C C (-40 F F) (T4) -40 C C (-40 F F) (T3) -60 C C (-76 F F) (T) Ambient Temperature -40 C C (-40 F F) Storage Temperature -40 C C (-40 F F) Electr. Connections Remote screw type terminals Electr. Connections Meter Mount none (internally connected to the electronics) Ingress Protection IP65 (IP66/IP67 on request) General Tube Arrangement serial serial Tube Inner Diameter 4 mm 4 mm 8 mm 8 mm 7 mm 9 mm 16 mm 8 mm 43 mm Tube Material /AISI 316L Housing Material /AISI 316L /AISI 304 optional: /AISI 316L / AISI 316L Dimensions see drawings Max. allowed flow velocity (Ma 0.5) For gas applications, flow rate and pressure drop for individual sensor sizes are dependent on operating temperature, pressure and fluid composition. Therefore, when selecting a sensor for any particular gas application, please use the the TSP (TRICOR Sizing Program) or contact us. 1) Nominal flow rates that produce approximately 3 bar (43 psi) pressure drop for natural gas at 50 bar (75 psi) operational pressure. ) Normal reference conditions (Nm 3 /h) are bar und 0 C. Standard (SCFM) reference conditions are 14.7 psi und 60 F. 3) Flow rate and density range depend on the gas density and the pressure range. 6

7 Coriolis Mass Flow Meters - TRICOR Accuracy for Gases Flow Rate of full Scale Accuracy Zero Point Basic Accuracy * 100 ± Basic Accuracy < Zero Point Basic Accuracy * 100 ± Zero Point Measured Value * 100 Analogous to calculation for liquids. Only the basic accuracy value (% o. r.) is deviant from the calculation for liquids. Example for a 035: 35 kg/h * ZeroPoint (0.01 %)= kg/h 1 lb/min * 0.01 % = lb/min 35 kg/h * Basic Accuracy (0.5 %) = kg/h 1 lb/min * 0.5 % = 0.06 lb/min Result: (0.035 / 1.635) * 100 = % (6.5 kg/h) (0.001 / 0.06) * 100 = % (0.4 lb/min) All flow rates % or 6.5 kg/h (0.4 lb/min): Measured error = Basic Accuracy All flow rates < % or 6.5 kg/h (0.4 lb/min): Measured error = (Zero Point / Measured Value) * 100 Ex Certifications ATEX (Ex) ATEX (Exn) IECEx (Ex) ccsaus (Ex1) 4) ATEX + IECEx + ccsaus Zone 4) 5) triple approval (Ex3) EAC (TR-CU) Zone 1: Group IIC or IIB, T...T4 Zone : II 3G Ex na IIC T...T4 Gc Zone 1: Group IIC or IIB, T...T4 Class 1, Division 1: Group A, B, C, D or C, D, T T4 1: Group IIC or IIB, T...T4 and Class 1, Division 1: Group A, B, C, D or C, D, T T4 Group IIC or IIB, T T4 4) For ccsaus and triple Ex-approval the Ex-approvals for remote electronics in /316L is pending. 5) Only with remote electronics 7

8 TRICOR - Coriolis Mass Flow Meters Technical Data - TCE 8000/8100 Transmitter General Display Supply Voltage Programming Interface graphic, 13 x 3 dot 4 V DC, ±0 % or V (version dependent) via front keyboard or Windows-based TRICOR configurator program (MODBUS) RS 485 (MODBUS-RTU), Option HART, other options on request EMC according to EN and Power Consumption ExD Housing: Wall-mounted Dimensions Electrical Connections Cable Glands max. 6 W see drawing cage clamp terminals for 7-13 mm cables Housing Material aluminium diecast (option: /AISI 316L) Protection Class Weight Temperature Housing: Panel-mounted (only TCE 8000) Dimensions Electrical Connections Housing Material Protection Class Weight Temperature Analog Output Current Outputs (x) Resolution Linearity Temperature Drift Load Output Value Pulse Output Frequency Range Output Signal Status In- and Output Status Output Control Input Analog Input (option) Input Type Resolution Linearity Temperature Drift Supply Voltage IP65 (IP66/IP67 on request) with Aluminium diecast housing: 3.8 kg/8.3 lb with 3 m cable with /AISI 316L housing: 6.15 kg/13.56 lb ambient: -40 C C (-40 F F) storage and transport: -40 C C (-40 F F) see drawing cage clamp terminals Noryl front: IP50, rear: IP kg/0.88 lb ambient: 0 C C (3 F... + F) storage and transport: -0 C C (-4 F F) ma passive, two-wire, isolated 14 bit ±0.05 % of full scale 0.05 % per 10 K < 60 Ω (at 4 V supply) programmable: flow, total, density, temperature Hz active push pull output for flow rate push pull programmable (in TOTAL mode: Hz; in FREQUENCY mode: Hz) programmable 4-0 ma active for two-wire passive pressure sensor 1 bit ±0.05 % of full scale 0.05 % per 10 K > 0 V (at 0 ma sensor current) 8

9 Coriolis Mass Flow Meters - TRICOR Technical Data - TCE 6000 Transmitter General Supply Voltage 4 V DC, ±0 % Programming via interface Interface RS485, USB (option) EMC according to EN and EN Power Consumption max. 4 W Connections connectors M1 Housing Material aluminium diecast Temperature ambient: -40 C C (-40 F F) storage: -40 C C (-40 F F) Protection Class IP65 Analog Output Current Output ma active Resolution 14 bit Linearity ±0.05 % Temperature Drift 0.05 % per 10 K Load < 800 Ω Output Value programmable: flow, total, density, temperature Pulse Output Frequency Range Output Signal Status In- and Output Status Output Control Input Hz active push pull output for flow rate, optional: insulated optical pulse output push pull programmable (option) (in TOTAL mode: Hz; in FREQUENCY mode: Hz) programmable (standard: 1 input/option: inputs), optional: insulated optical control input Technical Data - TRD 8001 Remote Display Display Supply Voltage Programming graphic, 13 x 3 dot via interface Interface to TCE RS 485 via front keyboard EMC according to EN and Dimensions 90 x 10 x 50 mm (h x w x d) Connections Housing Material Protection Class Weight Temperature Wall Mount connectors M1, B coded ABS- FR (plastic, flame retardant) IP kg/0.88 lb operation: 0 C C (3 F... + F) storage and transport: -0 C C (-4 F F) hidden screws 9

10 TRICOR - Coriolis Mass Flow Meters 035 to Sensor Type A C D E H L* G** 14 mm (8.43 in) 14 mm (8.43 in) 350 mm (13.78 in) 350 mm (13.78 in) 160 mm (6.30 in) 160 mm (6.30 in) 58 mm (10.16 in) 58 mm (10.16 in) M6 10 M6 10 M6 10 M mm (0.59 in) 15 mm (0.59 in) 18 mm (0.71 in) 18 mm (0.71 in) 18 mm (7.17 in) 18 mm (7.17 in) 80 mm (11.0 in) 80 mm (11.0 in) mm (4.33 in) mm (4.33 in) mm (5.51 in) mm (5.51 in) G ½ G ½ G ½ G ½ 5500 to 065K 5500, K 065K Sensor Type B C H L 6) I.D. Connection 7) 61 mm (.40 in) 80 mm (3.15 in) 151 mm (5.94 in) 04 mm (8.03 in) 53 mm (9.96 in) 387 mm (15.4 in) 60 mm (10.4 in) 315 mm (1.40 in) 480 mm (18.90 in) mm (18.11 in) mm (4.61 in) mm (3.68 in) Ø 13 mm (Ø 0.51 in) Ø 3 mm (Ø 0.91 in) Ø 40 mm (Ø 1.57 in) on request on request on request 10 6) further lengths on request 7) other connections on request

11 Coriolis Mass Flow Meters - TRICOR 30K Meter-Mount Electronics TCE 8000/

12 TRICOR - Coriolis Mass Flow Meters Wall-Mount Electronics TCE 8000/8100 Panel-Mounted Housing Type A B TCE 80** - S TCE 80** - L 96 mm (3.78 in) 96 mm (3.78 in) 96 mm (3.78 in) 144 mm (5.67 in) 1

13 Coriolis Mass Flow Meters - TRICOR Standard Connection Head (A) High Temperature Connection Head (H) 13

14 TRICOR - Coriolis Mass Flow Meters Meter-Mount Electronics TCE 6000 (F) 64mm,5in 57mm,5in 98mm 3,86in 38mm 1,50in Remote Display TRD

15 Coriolis Mass Flow Meters - TRICOR Ordering Information Meter (Series TRICOR) XXXX - X X - X X X X - X X X X - Ex - X X Process connections 8) see page 17 ff XX Mechanical options Medium Temperature range -40 C +100 C (-40 F +1 F) S -40 C +150 C (-40 F +30 F) Ex max : 135 C (75 F) H -40 C +70 C (-40 F +158 F) Ex, compact E -60 C C (-76 F F) T Pressure range With rupture disc max. 5 BAR (7.5 PSI) G Mechanical Design Standard S Face to face length Standard (other length on request) S Electronics options Electronics type Junction box Alu (only for replacements) A Z Z S Junction box /316L H Z Z S Meter mount electronics TCE 8000 (NPT) 9) C Meter mount electronics TCE 8000 (M0 x 1.5) 9) K Meter mount electronics TCE 8100 (NPT) 9) M Meter mount electronics TCE 8100 (M0 x 1.5) 9) O Meter mount electronics TCE ) F Interface 11) RS485 (Modbus RTU) S RS485 (Modbus RTU) and HART A RS485 (Modbus RTU) + FF (not with Ex) B FF (Foundation Fieldbus ) D RS485 (Modbus RTU) + USB (only TCE 6000) F Not used Z Supply voltage 4 V DC D V AC M Not used Z Options Pressure compensation, 4 0 ma input A 8 pin I/O connector (TCE 6000 only) B Optical I/O (TCE 6000 only) C No option S EX-protection ATEX + IECEx Zone1: Group IIC or IIB, T T4 ATEX Zone : II 3G Ex na IIC, T T4 Gc ccsaus: Class 1, Division 1: Group A, B, C, D or C, D, T T4 ATEX+IECEx: Zone 1: Group IIC or IIB, T T4 and ccsaus: Class 1, Division 1: Group A, B, C, D or C, D, T T4 1) EAC (TR-CU): Group IIC or IIB, T T4 ExR Special Options NOC (Net Oil Computer) 01 8) For connections not indicated with installation length, please contact manufacturer 9) For compact version with Ex-protection temperature class T4 only 10) Ex-protection only available in the option Exn 11) Other interfaces on request 1) Only with remote electronics Ex Exn Ex1 Ex3 15

16 TRICOR - Coriolis Mass Flow Meters Ordering Information TCE Transmitter (Series 8XXX) TCE 8 X X X - X - X X X X - X X - XX 035 to 7900 (Alu) K to 065K (Alu) K (Alu) to 7900 (1.4404/316L) K to 065K (1.4404/316L) K (1.4404/316L) Housing Wall mount (NPT) Wall mount (M0 x 1.5) Panel mount 13) Panel mount, wide for "Ex", "associated equipment" 13) Options Interface 14) RS485 (MODBUS RTU) RS485 (MODBUS RTU) + HART Supply Voltage 4 V DC V AC (only housing S+L) B 4 V DC D V AC (only housing W, I) M Electronic Options Standard Pressure compensation, 4 0 ma input Cable length 3 Meters/ 10 ft., Standard (high temperature) S (H) 6 Meters/ 0 ft., (high temperature) B (I) 10 Meters/ 33 ft., (high temperature) C (J) 15 Meters/ 49 ft., (high temperature) D(O) 0 Meters/ 65 ft., (high temperature) E (P) D-SUB Connector, (housing L+S) seperate cable required EX-Protection ATEX + IECEx Zone1: Group IIC, T T4 ATEX Zone : II3G Ex na IIC, T T4 Gc ccsaus: Class 1, Division 1: Group A, B, C, D or C, D, T T4 ATEX+IECEx, Zone 1: Group IIC or IIB, T T4 and ccsaus: Class 1, Div. 1: Group A, B, C, D or C, D, T T4 EAC (TR-CU): Group IIC or IIB, T T4 Special Options NOC (Net Oil Computer) 01 13) Only for TCE 80XX 14) Other interfaces on request W I S L S A S A N Ex Exn Ex1 Ex3 ExR 16

17 Coriolis Mass Flow Meters - TRICOR Slip on, process connection dim. + facing acc. ANSI B16.5 Installation length in mm (inch) Process connection 15) Code ½ ANSI flange class 150 AA ½ ANSI flange class 300 AB ½ ANSI flange class 600 AC ½ ANSI flange class 900 AD ½ ANSI flange class 1500 BV ½ ANSI flange class 500 BE K 065K 30K ¾ ANSI flange class 150 BA ¾ ANSI flange class 300 BB ¾ ANSI flange class 600 BC ¾ ANSI flange class 900 BD ¾ ANSI flange class 1500 AI 1 ANSI flange class 150 AE 1 ANSI flange class 300 AF 1 ANSI flange class 600 AG 1 ANSI flange class 900 AH 1 ANSI flange class 1500 AQ 1 ANSI flange class 500 BN 1½ ANSI flange class 150 AJ 1½ ANSI flange class 300 AK 1½ ANSI flange class 600 AL 1½ ANSI flange class 900 AM 1½ ANSI flange class 1500 BI 15) Connections without installation length are not possible or need manufacturer release. Please contact the manufacturer. 17

18 TRICOR - Coriolis Mass Flow Meters Slip on, process connection dim. + facing acc. ANSI B16.5 Installation length in mm (inch) Process connection 15) Code ANSI flange class 150 AN ANSI flange class 300 AO ANSI flange class 600 AP ANSI flange class 900 AR ANSI flange class 1500 BU K 065K 30K ½ ANSI flange class 150 BT ½ ANSI flange class 300 BY ½ ANSI flange class 600 BQ ½ ANSI flange class 900 BW 3 ANSI flange class 150 AS 3 ANSI flange class 300 AT 3 ANSI flange class 600 AU 3 ANSI flange class 900 AV 4 ANSI flange class 150 AW 4 ANSI flange class 300 AX 4 ANSI flange class 600 AY 4 ANSI flange class 900 AZ 5 ANSI flange class 150 BF 5 ANSI flange class 300 BG 5 ANSI flange class 600 BH 5 ANSI flange class 900 BJ 6 ANSI flange class 150 BM 6 ANSI flange class 600 BX 15) Connections without installation length are not possible or need manufacturer release. Please contact the manufacturer. 18

19 Coriolis Mass Flow Meters - TRICOR Slip on, process connection dim. + facing acc. EN Form B Installation length in mm (inch) Process connection 15) DN 10, EN flange PN 16 DN 10, EN flange PN 40 DN 10, EN flange PN 63 DN 10, EN flange PN 100 DN 10, EN flange PN 160 DN 10, EN flange PN 50 DN 10, EN flange PN 400 Code DY DS DZ EA EB EC ED K 065K 30K DN 15, EN flange PN 16 DN 15, EN flange PN 40 DN 15, EN flange PN 63 DN 15, EN flange PN 100 DN 15, EN flange PN 160 DN 15, EN flange PN 50 DN 15, EN flange PN 400 EE DA EF DB EG EH EI DN 0, EN flange PN 40 DT DN 5, EN flange PN 16 DN 5, EN flange PN 40 DN 5, EN flange PN 63 DN 5, EN flange PN 100 DN 5, EN flange PN 160 DN 5, EN flange PN 160 Mat.:. DN 5, EN flange PN 50 DN 5, EN flange PN 400 EZ DC EJ DD DW DW DP DV 15) Connections without installation length are not possible or need manufacturer release. Please contact the manufacturer. 19

20 TRICOR - Coriolis Mass Flow Meters Slip on, process connection dim. + facing acc. EN Form B Installation length in mm (inch) Process connection 15) DN 3, EN flange PN 40 Code DR K 065K 30K DN 40, EN flange PN 16 DN 40, EN flange PN 40 DN 40, EN flange PN 63 DN 40, EN flange PN 100 DN 40, EN flange PN 160 DN 40, EN flange PN 50 DN 40, EN flange PN 400 DU DE EK DF EL EM EN DN 50, EN flange PN 16 DN 50, EN flange PN 40 DN 50, EN flange PN 63 DN 50, EN flange PN 100 EO DG EP DH DN 65, EN flange PN 16 DN 65, EN flange PN 40 DN 65, EN flange PN 63 DN 65, EN flange PN 100 EQ DQ ER ES DN 80, EN flange PN 16 DN 80, EN flange PN 40 DN 80, EN flange PN 63 DN 80, EN flange PN 100 ET DJ EU DK 15) Connections without installation length are not possible or need manufacturer release. Please contact the manufacturer. 0

21 Coriolis Mass Flow Meters - TRICOR Slip on, process connection dim. + facing acc. EN Form B Installation length in mm (inch) Process connection 15) DN 100, EN flange PN 16 DN 100, EN flange PN 40 DN 100, EN flange PN 63 DN 100, EN flange PN 100 Code EV DL EW DM K 065K 30K DN15, EN flange PN 16 DN15, EN flange PN 40 DN15, EN flange PN 63 DN15, EN flange PN 100 EX DN EY DO DN150, EN flange PN 16 DN150, EN flange PN 40 DI DX EN flange weld neck Installation length in mm (inch) Process connection 15) DN 3, PN40 DIN /316L Type C Face DN 3, PN64 DIN /316L Type E Face DN 3, PN100 DIN /316L Type E Face Code VO VP VQ K 065K 30K Triclamp Installation length in mm (inch) Process connection 15) Code ½ Triclamp TA (8.66) (8.66) (9.84) (9.84) K 065K 30K DN 5 Triclamp PN 16 DIN 3676 TL 10 (8.7) 10 (8.7) 40 (9.45) 40 (9.45) 15) Connections without installation length are not possible or need manufacturer release. Please contact the manufacturer. 1

22 TRICOR - Coriolis Mass Flow Meters Female thread Installation length in mm (inch) Process connection 15) Code ¼ NPT female thread FJ ¾ NPT female thread FL ½ NPT female thread FK NPT female thread FQ K 065K 880 (34.65) 30K ¼ G, female thread FB ⅜ G, female thread FR ¾ G, female thread FC ½ G, female thread FA 15) Connections without installation length are not possible or need manufacturer release. Please contact the manufacturer.

23 Coriolis Mass Flow Meters - TRICOR Connection Cable for TCE 8000-S or TCE 8000-L to Lenght TCC X X - X X 3 Meter (Standard) ( 10 ft.) Meter ( 0 ft.) Meter ( 33 ft.) Meter ( 49 ft.) Meter ( 66 ft.) 0 Additional Accessories IPS9-9 IPS9-14 Front cover IP65 for TCE 80**-S-* Front cover IP65 for TCE 80**-L-* TRD 8001 TRD-TCE-6- TRD-TCE-6-5 Add. Remote display for meter mount version Connection cable TRD-TCE 6000, meter Connection cable TRD-TCE 6000, 5 meter TCD 0 Gauge Volume Totalizer KAB-USB-TCE KAB-RS485-TCE CON.USB.RS 3.WKZ USB Cable, USB to mini USB M1, meter, for TCE 6000 Cable with plug connector (Type A) (RS 485) to USB (PC) for TCE 6000, 1.8 meter Adaptor cable USB to RS 485, 1.8 meter Inspection certificate 3.1 according to DIN /EN 1004 Oxygen cleaning 3

24 North and South America AW-Lake Company 8809 Industrial Drive Franksville, WI 5316 USA P: Singapore TASI Flow Southeast Asia Representative Office (RO) Singapore 1003 Bukit Merah Central #06-3, Singapore UEN: T15RF0080G P: China TASI Flow China Rm. 49 Jin Yuan Office Building, No. 36 CN - BeiYuan Road, Beijing P: Rest of the World KEM Küppers Elektromechanik GmbH Liebigstraße Karlsfeld, Germany P: +49 (0) Copyright KEM, Subject to change without notice