ADE-5F, ADE-6F. Type Size. Cable type. Clamping. Service Temperature. -30 C to +95 CC Sealant IP rating: NEMA NEMA-4X

Size: px
Start display at page:

Download "ADE-5F, ADE-6F. Type Size. Cable type. Clamping. Service Temperature. -30 C to +95 CC Sealant IP rating: NEMA NEMA-4X"

Transcription

1

2

3

4 ADE-1F2 (not for Mining application) a n 3 to n 17 for cable external diameter from 2,75 to 104mm sizes M10 to M1100 or NPT1/8 to NPT4 inclusive UL thread size M20 to M110 or NPT1/2 to NPT4 inclusive Unarmored cable and Marine Shipboard cable. By sealing ring (25%), the user shall provide additional clamping of the cable. Alternative material Stainless-steel, Bronze or Aluminum. From -30 to +80 C with Neoprene sealing ring From -60 to +140 C with Silicone S sealing ringg NPT according to ANSI/ASME B Lubricant / STL2 (2oz) or STL8 (8oz) ; range -20 F to +200 F -30 C to +95 CC HTL4 (4oz) ; e range -70 F to F -60 C to : g - On equipment with blankk hole (not for d use), fixed with Capri qualified locknut, all the threads must be engaged: * IP66 depending to the flatness and the roughness of the contact surface of the enclosure:. Without added gasket for Ra 0.4 µmm maxi. * IP68 tested 30m/7days with Capri qualified Fiber-Gasket for f Ra 1.6 µm maxi roughness of the contact surface. - The length of the threaded entry permit to meet the applicable thread engage, also with the add of gasket between thee cable and the enclosuree (gasket thickness 1,5 or 2mm). on equipment withh threaded hole: IP66 or IP68 tested 30m/7days, with STL or HTL sealant. INERIS: INERIS120032X 6 II2GD / Ex db IIC/ Ex eb IIC / Ex tb IIIC IP66 II3G Ex nrc IIC Zones 1 & 2 ; Groups IIA, IIB and IIC ; for usee "d", "e", "ia", "ib",, "ic", "ma", "mb", "mc", "na", "nc", "nr, "o", pv, "px", "py", "pz" & "q". Zones 21 & 22 ; Groups IIIA, IIIB and IIIC ; for use "tb", "tc", "ia", "ib", "ma", "mb", "mc"" & "p". IEC :2011, IEC :2007, :2010, IEC :2008 Ex db IIC / Ex eb IIC / Ex nrc n IIC / Ex tb IIIC IP66 Other Ex (Inmetro): X Certificates Approval certificate N 11/00072 culus: E UL 514B, UL 2225 and C22.2 No 1 with respect to the US National Electrical Codee (NEC) and Canadian Electrical Code (CEC). For use in Class I, Zone 2, AEx e II, Ex e II Hazardous Areas, with unarmored ITC, MV, PLTC & TC cable. Allow installation in all gass atmospheres Article 505 of the NEC and section 18 of CEC. culus: E UL 514B, UL 2225 and C22.2 No 1 with respect to the US National Electrical Codee (NEC) and Canadian Electrical Code (CEC). For use in Class I, Zone 2, AEx e II, Ex e II Hazardous Areas, with unarmored marine shipboard cable. Allow installation in all gass atmospheres Article 505 of the NEC and section 18 of CEC. N SRD / Certificates / ABS ADE Model Description Capri docxx /page 1/8

5 ADE-1F2 anchorage n 3 to n 17 for cable external diameter fromm 2,75 to 104mm sizes M10 to M110 or NPT1/8 to NPT4 inclusive UL thread size M20 to M110 or NPT1/2 too NPT4 inclusive Unarmored cable and Marine Shipboard cable. By sealing rings and external clamping device. Alternative material Stainless-steel, Bronze or Aluminum (Aluminum not for Mining application). From -30 to +80 C with Neoprene N sealing ring From -60 to +140 C with Silicone sealing ring Lubricant / STL2 (2oz) or STL8 (8oz)) ; range -20 F to +200 F -30 C to +95 C HTL4 (4oz) ; e range -70 F to F -60 C to on equipment with threaded hole: IP66 or IP68 tested 30m/7days, with STL or HTL sealant. INERIS: INERIS120032X IM2 Ex db I / Ex eb I ( for Mining application) Zones 1 & 2 ; Groups I, IIA, IIB, IIC ; for usee "d", "e", "ia", "ib", "ic"," "ma", "mb", "mc", "na", "nc", "nr, "o", pv, "px", "py", "pz" & "q". Ex db IIC / Ex eb IIC / Ex nrc IIC / Ex tb IIICC IP66 Ex db I / Ex eb I (for Mining application) (Inmetro): L X Approval certificate N 11/00072 culus: E For use in Class I, Zone 2, 2 AEx e II, Ex e II Hazardous Areas, with unarmored ITC, MV, PLTC & TCC cable. culus: E For use in Class I, Zone 2, 2 AEx e II, Ex e II Hazardous Areas, with unarmored marine shipboard cable. N SRD / Certificates / ABS ADE Model Description Capri docxx /page 2/8

6 ADE-4F n 4 to n 17 for cable external diameter fromm 4,5 to 104mm sizes M10 to M110 or NPT1/8 to NPT4 inclusive UL thread size M20 to M110 or NPT1/2 too NPT4 inclusive Armored or Braided & Jacketed cable (STA,, SWA or SWB) and Marine Shipboard cable. By sealing rings Alternative material Stainless-steel, Bronze or Aluminum (Aluminum not for Mining application). From -30 to +80 C with Neoprene N sealing ring From -60 to +140 C with Silicone sealing ring Lubricant / STL2 (2oz) or STL8 (8oz)) ; range -20 F to +200 F -30 C to +95 C HTL4 (4oz) ; e range -70 F to F -60 C to on equipment with threaded hole: IP66 or IP68 tested 30m/7days, with STL or HTL sealant. INERIS: INERIS120032X IM2 Ex db I / Ex eb I (for Mining application) Zones 1 & 2 ; Groups I, IIA, IIB, IIC ; for usee "d", "e", "ia", "ib", "ic"," "ma", "mb", "mc", "na", "nc", "nr, "o", pv, "px", "py", "pz" & "q". Ex db IIC / Ex eb IIC / Ex nrc IIC / Ex tb IIICC IP66 Ex db I / Ex eb I (for Mining application) (Inmetro): L X Approval certificate N 11/00072 culus: E For use in Class I, Zone 2, 2 AEx e II, Ex e II Hazardous Areas, with ITC, MV, PLTCC and TC armored cable. culus: E For use in Class I, Zone 1, 1 AEx e II, Ex e II Hazardous Areas, with armored marine shipboard cable. N SRD / Certificates / ABS ADE Model Description Capri docxx /page 3/8

7 ADE-5F n 4 to n 17 for cable external diameter fromm 4,5 to 104mm sizes M10 to M110 or NPT1/8 to NPT4 inclusive UL thread size M20 to M110 or NPT1/2 too NPT4 inclusive Armored or Braided & Jacketed cable (STA,, SWA or SWB) and Marine Shipboard cable. By sealing rings Alternative material Stainless-steel, Bronze or Aluminum (Aluminum not for Mining application). From -30 to +80 C with Neoprene N sealing ring From -60 to +140 C with Silicone sealing ring Lubricant / STL2 (2oz) or STL8 (8oz)) ; range -20 F to +200 F -30 C to +95 C HTL4 (4oz) ; e range -70 F to F -60 C to on equipment with threaded hole: IP66 or IP68 tested 30m/7days, with STL or HTL sealant. INERIS: INERIS120032X IM2 Ex db I / Ex eb I (for Mining application) Zones 1 & 2 ; Groups I, IIA, IIB, IIC ; for usee "d", "e", "ia", "ib", "ic"," "ma", "mb", "mc", "na", "nc", "nr, "o", pv, "px", "py", "pz" & "q". Ex db IIC / Ex eb IIC / Ex nrc IIC / Ex tb IIICC IP66 Ex db I / Ex eb I (for Mining application) (Inmetro): L X Approval certificate N 11/00072 N SRD / Certificates / ABS ADE Model Description Capri docxx /page 4/8

8 ADE-6F (not for Mining application) n 5 to n 11 for cable external diameter fromm 6 to 48mm sizes M16 to M633 or NPT3/8 to NPT2 inclusive UL thread size M20 to M63 or NPT1/2 to NPT2 inclusive Armored or Braided & Jacketed cable (STA,, SWA or SWB) and Marine Shipboard cable. By Armor clamping device and sealing ring. Alternative material Stainless-steel, Bronze or Aluminum From -30 to +80 C always with Internal Silicone sealing ring (diaphragm) Lubricant / STL2 (2oz) or STL8 (8oz)) ; range -20 F to +200 F -30 C to +95 C HTL4 (4oz) ; e range -70 F to F -60 C to on equipment with threaded hole: IP66 or IP68 tested 30m/7days, with STL or HTL sealant. INERIS: INERIS120032X Zones 1 & 2 ; Groups IIA, IIB, IIC ; for use "d", "e", "ia", "ib", "ic", "ma", "mb", "mc", "na", "nc", "nr, "o", pv, "px", "py",, "pz" & "q". Ex db IIC / Ex eb IIC / Ex nrc IIC / Ex tb IIICC IP66 (Inmetro): L X Approval certificate N 11/00072 culus: E For use in Class I, Zone 2, 2 AEx e II, Ex e II Hazardous Areas, with ITC, MV, PLTCC and TC armored cable. culus: E For use in Class I, Zone 1, 1 AEx e II, Ex e II Hazardous Areas, with armored marine shipboard cable. N SRD / Certificates / ABS ADE Model Description Capri docxx /page 5/8

9 ADE-1FC n 4 to n 16 for cable external diameter fromm 4 to 93mm sizes M16 to M110 or NPT3/8 to NPT4 inclusive UL thread size M20 to M110 or NPT1/2 too NPT4 inclusive Unarmored cable and Marine Shipboard cable. By TSC filling compound and sealing ring Alternative material Stainless-steel, Bronze or Aluminum (Aluminum not for Mining application). From -60 to +80 C with A & certification From -20 to +40 C with UL U Marine for Division certification below Lubricant / STL2 (2oz) or STL8 (8oz)) ; range -20 F to +200 F -30 C to +95 C HTL4 (4oz) ; e range -70 F to F -60 C to on equipment with threaded hole: IP66 or IP68 tested 30m/7days, with STL or HTL sealant. INERIS: INERIS120032X IM2 Ex db I / Ex eb I (for Mining application) Zones 1 & 2 Groups I, IIA, IIB, IIC for use "d", "e", "ia", "ib", "ic", "ma", "mb", "mc", "na", "nc", "nr, "o", pv, "px", "py", "pz" & "q". Ex db IIC / Ex eb IIC / Ex nrc IIC / Ex tb IIICC IP66 Ex db I / Ex eb I (for Mining application) (Inmetro): L X Approval certificate N 11/00072 culus: E For use in Class I, Zone 2, 2 AEx de II, Ex de II Hazardous Areas with unarmored ITC, MV, PLTC, TCC cable and TSC compound. UL: E For use in Class I, Division 2, Groups A, B, C, D Hazardous Locations, with unarmored marine shipboard cable and TSC compound. Allow installation in all gas atmospheres allowed by Subpart of the United States Coast Guard Electrical Engineering Regulations, Subchapter J (Title 46 of Federal Regulations, Parts 110 to 113 inclusive) Ships Electrical, TPP 127E, Section 26, Subsections 7(a) 7 and 7(b). N SRD / Certificates / ABS ADE Model Description Capri docxx /page 6/8

10 ADE-6FC n 5 to n 17 for cable external diameter fromm 6 to 104mm sizes M16 to M110 or NPT3/8 to NPT4 inclusive UL thread size M20 to M110 or NPT1/2 too NPT4 inclusive Armored or Braided & Jacketed cable (STA,, SWA or SWB) and Marine Shipboard cable. by TSC filling compound and sealing ring Alternative material Stainless-steel, Bronze or Aluminum (Aluminum not for Mining application). From -60 to +80 C with A & certification From -20 to +40 C with certification c UL Marine for Div. below Lubricant / STL2 (2oz) or STL8 (8oz)) ; range -20 F to +200 F -30 C to +95 C HTL4 (4oz) ; e range -70 F to F -60 C to on equipment with threaded hole: IP66 or IP68 tested 30m/7days, with STL or HTL sealant. INERIS: INERIS120032X IM2 Ex db I / Ex eb I (for Mining application) Zones1&2 Groups I, IIA, IIB and IIC for use "d", "e", "ia", "ib", " ic", "ma", "mb", "mc", "na", "nc", "nr,, "o", pv, "px", "py", "pz" & "q". Ex db IIC / Ex eb IIC / Ex nrc IIC ; Ex tb IIICC IP66 ; Ex db I / Ex eb I (for Mining application) XX Approval certificate N 11/00072 culus: E For use in Class I, Zone 2, 2 AEx de II, Ex de II Hazardous Areas, with armored ITC, MV, PLTC, TC cable and TSC compound. UL: E For use in Class I, Division 1, Groups A, B, C, D Hazardous Locations, with armored marine shipboard cable and TSCC compound. Allow installation in all gas atmospheres allowed by Subpart of the United States Coast Guard Electrical Engineering Regulations, Subchapter J (Title 46 of Federal Regulations, Parts 110 to 113 inclusive) Ships Electrical, TPP 127E, Section 26, Subsections 7(a) 7 and 7(b). N SRD / Certificates / ABS ADE Model Description Capri docxx /page 7/8

11 Approval documentation: Test Reports/Certificates: Ex Test Report reference n FR/INE/ExTR /01 According to EC Examination certification c Technical file: Cooper Capri n SRD/Certificates/INERIS/Files/ADE Rev-I-1 N SRD / Certificates / ABS ADE Model Description Capri docxx /page 8/8