2 Revisions Revisions Dae Drawn by Checked by Approved by - Aug. /8 /2008 S.Higuchi New Descripion Fuji Elecric Sysems Co., Ld. Dwg.No SI /7

3 1. Special Specificaions 1.1. Addiional Funcion Codes Table 1-1. Addiional Funcion codes Code Name Daa seing range Incremen Uni Change when running Daa copying Defaul seing Saus Signal Assignmen E20 o [Y1] (Transisor signal) Add 44 (1044): (PID-STP) Moor sopping due o slow 0 Saus Signal Assignmen flowrae under PID conrol E21 E27 o [Y2] (Transisor signal) Saus Signal Assignmen o [30A/B/C] (Relay conac signal) Add 87 (1087): (FARFDT) Logical of (FAR) and (FDT) - - N Y 7 99 PID Conrol J15 (Sop frequency for slow flowrae) 0: Disable 1 o Hz Y Y 0 J16 (Slow flowrae level sop laency) 0 o 60 1 s Y Y 30 J17 (Saring frequency) 0: Disable 1 o Hz Y Y 0 J23 J24 (Saring feedback deviaion level from he slow flowrae sop) (Saring laency from he flow flowrae sop) 0 o % Y Y 0 0 o 60 1 s Y Y 0 Fuji Elecric Sysems Co., Ld. Dwg.No SI /7

4 1.2. Saus Signal: FARFDT This oupu signal comes ON when boh FAR and FDT urn ON, and i goes OFF if any FAR or FDT is OFF (logical ): FARFDT = FDT FAR. Frequency command FAR allowable error zone (E30 : 2.5 Hz) Oupu frequency E31: FDT deecion level E32: FDT Hyseresis level (FDT) ON ON (FAR) ON ON ON (FARFDT) ON ON Figure 1-1. FARFDT signal oupu overview Table 1-2. Seing Funcion code Code Name Seing E20, E21, E27 Saus Signal Assignmen o: [Y1][Y2][30A/B/C] 87(1087) : (FARFDT) Fuji Elecric Sysems Co., Ld. Dwg.No SI /7

5 1.3. Slow Flowrae Sop (equiv.frenic-eco) These funcion codes specify he daa for he slow flowrae sop in pump conrol, a feaure ha sops he inverer when he discharge pressure rises, causing he volume of waer o decrease. Slow flowrae sop feaure When he discharge pressure has increased, decreasing he reference frequency (oupu of he PID processor) below he sop frequency for slow flowrae level (J15) for more han he elapsed sopping ime on slow flowrae level sop laency (J16), he inverer deceleraes o sop, while PID conrol iself coninues o operae. When he discharge pressure decreases, increasing he reference frequency (oupu of he PID processor) above he saring frequency (J17), he inverer resumes operaion. If you wish o have a signal indicaing he sae in which he inverer is sopped due o he slow flowrae sop feaure, you need o assign (PID-STP) (Inverer sopping due o slow flowrae under PID conrol) o one of he general-purpose oupu erminal (funcion code daa = 44). PID Conrol (Sop frequency for slow flowrae) (J15) Specifies he frequency which riggers slow flowrae sop of inverer. PID Conrol (Slow flowrae level sop laency) (J16) Specifies he elapsed ime from when he inverer sops operaion due o slow flowrae level condiion. PID Conrol (Saring frequency) (J17) Specifies he saring frequency. Selec a frequency higher han he slow flowrae level sop frequency. If he specified saring frequency is lower han he slow flowrae level sop frequency, he laer sop frequency is ignored; he slow flowrae level sop is riggered when he oupu of he PID processor drops below he specified saring frequency. Figure 1-2. Saring inverer by PID process overview Fuji Elecric Sysems Co., Ld. Dwg.No SI /7

6 Run command ON ON Oupu frequency F23 Pump sar Pump sar again PID oupu (MV) J16 J17 J15 MV >= J17 MV >= J17 Feedback value (PV) Command (SV) MV sars increasing. Pressure sars decreasing when he fauce is opened. J24 Pressure sars decreasing slighly by leaks, ec. SV - PV >= J23 J23: Saring From he Slow Flowrae Sop (Feedback deviaion level) Sar laency imer couns Laency imer couns >= J24 J24: Saring From he Slow Flowrae Sop (Sar laency) Sar couns Clear couns (RUN) Inverer running Inverer running (PID-STP) Slow Flowrae Sop Figure 1-3. Saring inverer by PID process overview (when i sopped by slow flowrae) Fuji Elecric Sysems Co., Ld. Dwg.No SI /7

7 Table 1-3. Saring inverer condiions Condiions Previous process Upgraded process Pump sars Pump sars again from Slow flowrae sop [A] Coun laency imer [B] Clear laency imer couns PID oupu (MV) J17 No Implemened PID oupu (MV) J17 SV - PV J23 SV > PV (Normal operaion) SV < PV (Inverse operaion) Laency imer couns J24 PID oupu (MV) J17 SV-PV J23 SV > PV (Normal operaion) SV < PV (Inverse operaion) Disablemen pump conrol OR [A] OR NOT [B] 1.4. Jogging Operaion The jogging operaion can be acivaed hrough communicaions (link funcions). When he operaion command of link is effecive, he jogging operaion urns on he Run command (FWD or REV) and he Ready for jogging (JOG) wih S Updae Funcions a) The PID conrol awake, in case of H63=1, when he inverer is rese afer a Trip. b) In posiioning conrol, he posiion daa deviaion does no occurs when Z is acive. Fuji Elecric Sysems Co., Ld. Dwg.No SI /7