Corrosion behavior of fastenings made with Hilti HIT-HY 150 and Hilti HIT-RE 500 injection systems

Size: px
Start display at page:

Download "Corrosion behavior of fastenings made with Hilti HIT-HY 150 and Hilti HIT-RE 500 injection systems"

Transcription

1 Technoparkstr Zurich Tel Fax Schweizerische Gesellschaft für corrosionsschutz Swiss Association for protection against corrosion Report no a Dated September 17, 2002 Subject: Corrosion behavior of fastenings made with Hilti HIT-HY 150 and Hilti HIT-RE 500 injection systems This report consists of 16 pages. Order from: Hilti Corporation, FL-9494 Schaan Order dated Testing between June 27, 2001 and January 7, 2002 Contents Summary 2 1. Background information 3 2. Experiments 4 3. Test results Behavior of steel specimens in Hilti HIT-HY Behavior of steel specimens in Hilti HIT-RE Frequent questions: Sealing of Hilti HIT-RE 500 system Influence of chlorides Defects in coating of Hilti HIT-RE Reference literature 16 Zurich, October 07, 2002 for SGK:

2 - 2 / 16 - Summary The Schweizerische Gesellschaft für Korrosionsschutz (SGK) (Swiss Association for protection against corrosion) was given the assignment of evaluating the corrosion behavior of anchor fastenings post-installed in concrete using the Hilti HIT-HY 150 and Hilti HIT-RE 500 injection systems. HIT-HY 150 is a hybrid injectable adhesive mortar which is based on a fast-curing, organic binder (methacrylate) and cement. Its characteristics are comparable to those of concrete it is alkaline and porous. HIT-RE 500 is an injectable adhesive mortar which is based on a slow-curing epoxy resin with a polyamine hardener. As regards its characteristics, it is alkaline and dense. Corrosion tests were carried out. The behavior of the two systems had to be evaluated as regards their use in field practice and compared with the behavior of anchors cast in concrete (reference). The SGK can look back on extensive experience in this field, especially on expertise in the field of repair and maintenance work on bridges in the Swiss alps. To model the corrosion tests, the worst case with respect to corrosion, namely fastenings used during bridge repair for anchoring concrete cover to old concrete. The overall evaluation was made on the basis of the tests conducted, while including SGK s practical experience, theoretical considerations and reports from field practice found in the pertaining reference literature. The result can be summarized as follows: Hilti HIT-HY 150 The Hilti HIT-HY 150 system in combination with reinforcing bars (hereinafter referred to as rebars) can be regarded as being resistant to corrosion when it is used in sound, alkaline concrete. The alkalinity of the adhesive mortar safeguards the initial passivation of the steel and, owing to the porosity of the adhesive mortar, an exchange takes place with the alkaline pore solution of the concrete. If rebars are bonded in chloride-free concrete using this system, in the event of later chloride exposure, the rates of corrosion are about half those of rebars that are either cast in or bonded with cement mortar. In concrete containing chlorides, the corrosion behavior of the system corresponds to that of cast-in or cemented-in rebars. Consequently, the use of unprotected steel in concrete exposed to chlorides in the past or possibly in the future is not recommended because corrosion must be expected after only short exposure times.

3 - 3 / 16 - Hilti HIT-RE 500 If the Hilti HIT-RE 500 system is used in corrosive surroundings, a sufficiently thick coat of adhesive significantly increases the time before corrosion starts to attack the bonded-in steel. The HIT-RE 500 system may be described as resistant to corrosion, if a coat thickness of at least 1 mm can be ensured, even in concrete that is carbonated and contains chlorides. In this case, the unprotected steel in a concrete joint and in the new concrete is decisive. If the coat thickness is not ensured, the HIT-RE 500 system may be used only in sound concrete. A rebar may then also lie against the wall of the drilled hole. At these points, the steel behaves as though it has a thin coating of epoxy resin. In none of the cases investigated did previously rusted steel (without chlorides) show signs of an attack by corrosion, even in concrete containing chlorides. Neither during this study was an acceleration of corrosion found at defective points in the adhesive mortar bond nor was there any reference to this in literature. Even if a macro-element forms, the high resistance to it spreading inhibits a locally increased rate of corrosion. Information in reference data corresponds with the results of this study. 1. Background information The situation investigated is depicted schematically in fig. 1. There are the following possible risks of corrosion: The existing structural concrete might be carbonated. This could impair the passivity of the steel specimens. The existing structural concrete might have been impaired by chlorides. The chlorides could reach the surface of the concrete as a result of the anchor fastening and then initiate corrosion there. Chlorides can permeate into concrete and lead to corrosion on the surface of the steel. The main permeation route is through the joint between the existing structural concrete and the new concrete (fig. 1: Permeation route 1). Progressing from a joint, chlorides can advance into the new concrete and into the existing concrete (permeation routes 3 and 4).

4 - 4 / 16 - On the other hand, chlorides can also get into a structure quickly through cracks appearing in new concrete due to constrained shrinkage (permeation route 2) and then proceed to the steel specimens through the joints. Basically, chlorides can also permeate through the new concrete (permeation route 5), but this permeation takes place much slower than through permeation routes 1 and reinforcement new concrete steel specimens adhesive old concrete permeation routes Fig. 1: Schematic situation with a concrete extension containing bonded-in steel specimens and showing possible chloride permeation routes 2. Experiments In order to simulate the possible corrosion risk for the anchoring system experimentally, concrete test specimens were made which would be able to reproduce the various risk mechanisms in question. The set-up for the experiments is shown in fig. 2. First, concrete test specimens were made, these having a water-cement factor of 0.6. For this simulation of the various corrosion hazards, these test specimens were given different treatments. Series I: The old concrete was exposed in advance by letting it soak up a 2 M NaCl solution with chlorides. After the pretreatment, the chloride concentration reached a value of approximately 1 percent by mass in relation to the cement content (m%/c). Series II: The old concrete was carbonated by rapid carbonation at a relative air humidity of 60%. The carbonation depth after the pretreatment was 20 mm. Series III: The old concrete was not pretreated.

5 - 5 / 16 - reading of potential U I reading of macro-element current cathode 10 mm dia. 40cm old concrete concrete block 5 cm 5 cm 8 cm 16 mm 30 mm 17cm 10 cm 1cm solution (tap water/tap water + 1M NaCl) reference electrode anchor 12 mm dia. SCE adhesive mortar new concrete coating chloride sensor interface of new / old concrete Fig. 2: Schematic test set-up and measuring equipment As pretreatment of the concrete would have immediately led to corrosion of the cast-in reference steel specimens in series I and II, the reference specimens were installed using cement mortar after pretreatment of the concrete (coat thickness 6 mm). Only in the case of series III was it possible for the reference specimens to be cast-in when making the old concrete. After pretreating the concrete specimens, the steel specimens were installed in the old concrete using the two HIT injectable adhesive mortars (coat thickness 2 mm). As a rule, normal, untreated reinforcing steel with a diameter of 12 mm was used for the steel specimens. Several specimens were installed with intentional defects in the enveloping HIT-RE 500 adhesive mortar and previously rusted reinforcing steel was used for several specimens. After carrying out these preparations, the new concrete with a water-cement factor of 0.5 was applied. Permeation routes 1 and 2 were the main corrosion risks for the steel specimens. Consequently, the new concrete was coated with epoxy resin to seal off permeation route 5 and to make the joint the primary route for the water. In series I, the test pieces were submerged in tap water and, in series II and III, in 1 M NaCl solutions. To analyse the corrosion behavior, the potential and the corrosion current were recorded. Fig. 3 is a typical plot of the results. The activation of a specimen was determined on the basis of the drop in potential and an increase in the macro-element current. The rate of corrosion was ascertained from the current and the corroding area. By determining the area of corrosion after the test, it was possible to calculate and plot the rate of corrosion in millimeters per year from the corrosion current.

6 - 6 / 16 - Potential [V SCE] rate potential Time[h] Rate of corrosion [mm/year] Fig. 3: Typical plot of potential and rate of corrosion 3. Test results 3.1 Behavior of steel specimens in Hilti HIT-HY 150 Bonding in a steel bar with HY 150, gives the steel protection which is comparable to that of steel cast in concrete. Despite the prior carbonation of the old concrete, the HIT-HY 150 adhesive mortar was able to passivate the steel. Nonetheless, the system is unsuitable for use in concrete containing chlorides. Chlorides in salinized concrete quickly find their way to the surface of the steel through pores in the HIT-HY 150 where they cause an attack of corrosion. In this case though, the HIT-HY 150 system performs at least as well as concrete. All the same, differences do exist, depending on the corrosive testing conditions. These are discussed in the following. Series I: In the concrete containing large amounts of chlorides, steel specimens bondedin with HIT-HY 150 initiated corrosion of the reference specimens and the steel specimens in HIT-HY 150 within a short time. The 6 mm thick cement mortar coat in which the reference bars were embedded showed a behavior similar to that of the HIT-HY 150 system (with a coat 2 mm thick). Series II: After the bar had been put in place, the HIT-HY 150 passivated the steel by reason of its alkalinity, even though the surrounding concrete was carbonated. The infiltration of chlorides along the joint then soon caused the steel to corrode. In this case, a considerably better behavior of the reference specimens was observed. Most probably, this could be attributed to the steel being embedded in a very high-quality 6 mm thick cement mortar layer.

7 - 7 / 16 - Series III: Tendentially, the time required for the HIT-HY 150 system to trigger corrosion is longer than in series II. Immediately after the tests were started, the cast-in reference specimens were attacked by corrosion. Hilti HIT-HY 150 Reference Hilti HIT-HY 150 Reference Series I Series I Series II Series II Series III Series III Time [h] Fig. 4: Time to initiate corrosion Rate of removal [mm/year] Fig. 5: Max. rate of corrosion From the test readings, it could be seen that, on average, the rate of corrosion with the HIT-HY 150 system was slower than with the reference specimens. Among the reference specimens, no positive effect of the cement mortar on the rate of corrosion compared with the bonded-in with HIT-HY 150 specimens could be observed. 3.2 Behavior of steel specimens in Hilti HIT-RE 500 HIT-RE 500 significantly extended the time until corrosion began. Based on the available data, it could be assumed that corrosion could take place only on unprotected steel in the joint or in the new concrete, if they had been exposed to chlorides. After a test duration of 2,400 hours, steel used with the HIT-RE 500 system showed no significant signs of corrosive attack. In view of this, the testing conditions were made more stringent through exposure to an increased temperature. The test pieces were kept at 50 C for 7 days and then left at room temperature for approximately 21 days afterwards. This cycle was repeated three times. How these cycles affected the corrosion behavior was depicted fig. 6. Series I: The concrete containing chlorides was unable to cause the steel specimens in HIT-RE 500 to corrode. The contrary was the case with the reference specimens in cement mortar and the steel specimens in HIT-HY 150. If HIT-RE 500 enveloped the steel specimens, it prevented chloride access to the steel and inhibited an attack of corrosion in this way. Even the defects provided artificially in the HIT-RE 500 opened up no routes for the damaging substances to permeate to the specimen surfaces.

8 - 8 / 16-0 cycle: Fig. 6: Potential [V SCE] rate potential Time [h] Activation of specimen (example) during first temperature cycle Rate of corrosion [mm/year] Series II: At the start of the test, the HIT-RE 500 system displayed a clearly passive behavior in the carbonated concrete. Infiltrating chlorides were unable to initiate corrosion after the first temperature cycles. It was then found that the artificially provided defects had no negative effects. Only in the unprotected new concrete did both specimens with defect and specimens without defect corrode, and this during the same period. After stopping the tests, furthermore, several specimens were still not corroded. The previously rusted specimens installed with HIT-RE 500 showed no attack by corrosion throughout the entire test duration. The infiltrating chlorides were only able to initiate corrosion on the reference specimens bonded in with cement after a relatively long test duration. This good resistance could be attributed to the surrounding 6 mm thick, highly alkaline, cement mortar layer and the water-filled pores. Series III: By using HIT-RE 500, it was also possible to efficiently delay the start of corrosion in series III. Only when there was high chloride contents of up to 4 M%/C and, in some cases, only after additional exposure to heat were the specimens activated. After removal of the specimens, it was apparent that corrosion had been initiated primarily in the cast-in specimen section of the concrete cover. Consequently, the activation can be attributed to the high chloride content of the new concrete. The different activation times for the unprotected steel thus permitted the times to be deduced until the critical chloride content in the concrete cover was reached. None of the previously rusted specimens embedded in HIT-RE 500 showed signs of corrosion. The characteristic russet-brown coloration of the rust prior to installation changed to a black oxide layer under the HIT-RE 500 and a largely plain steel surface in the concrete cover.

9 - 9 / 16 - The activation times ascertained on the basis of the potential and rate of corrosion are depicted in 7. Reference RE 500 rusty Reference RE 500 rusty RE 500 RE 500 with defect RE 500 RE 500 with defect Series I Series I Series II Series II Series III Series III time [h] Fig. 7: Activation times rate [mm/year] Fig. 8: Max. rate of corrosion removal The rate of corrosion removal was calculated with the aid of corrosion current readings and measured sizes of the active zones. The results for die max. rate of corrosion were plotted in fig. 8. The graph shows that the rate of corrosion of the HIT-RE 500 system is less on average than that of the reference specimens. In no case, however, was a higher rate of corrosion observed than with the reference specimens. It was also seen that the rate of corrosion of specimens which corroded in the defective adhesive mortar in addition to corroding in new concrete was not higher. A visual examination of the installed bars, after the experiments had been stopped, indicated that corrosion of the reference specimens occurred primarily in the joint or in the old concrete. This means that the test arrangement led to the anticipated permeation of chlorides. In contrast to this, an attack of corrosion was observed on all HIT-RE 500 systems in the new concrete. In odd cases, corrosion also occurred at the defects. 4. Frequent questions about "sealing" of the HIT-RE 500 system 4.1 Effect of chlorides In the case of all systems installed with HIT-RE 500 which proved to initiate corrosion, corrosion always also occurred in the new concrete. This corrosion in the new concrete could be attributed to the penetration of chlorides. The results of the chloride analysis after stopping the tests were depicted in fig. 9. It was clearly shown that the critical chloride content of 0.4 percentage by mass in relation to the cement content (M%/C) had been

10 - 10 / 16 - exceeded in series II and III in the new concrete. As a result, corrosion had to be expected in the new concrete. By contrast, the chloride content in the new concrete in series I was below the critical value, as the chlorides could only diffuse from the old concrete to the new concrete. No attack of corrosion was observed in this case either. This means that the attacks of corrosion on the unprotected steel surfaces were primarily the result of chloride penetration into the new concrete. New concrete Old concrete Content of chloride [M%/Z] Series I Series II Series III depth [mm] Fig. 9: Chloride content in relation to cement at various depths in test pieces; the critical chloride content of 0.4 M%/C is indicated by the dotted line. 4.2 Defects in coat of HIT-RE 500 The excellent protection against corrosion of HIT-RE 500 cames from almost complete separation of the steel from the concrete (sealing), as it is achieved by the propper application of the system HIT.RE 500. As a result, corrosive substances can not access the surface of the steel and electro-chemical reactions can not take place. By reflecting on analogies with other applications with sealing systems as protection against corrosion, it became possible to put forward the following arguments against this protective principle: 1. The access of corrosive substances through defects in the coating is possible and corrosion could thus take place locally, e.g. (a) air voids, (b) cracks, (c) immediately on rebars in contact with the concrete and, possibly, (d) in connection with rebars previously exposed to chlorides. 2. Electro-chemical reactions are largely rendered impossible underneath the coating. Consequently, there is also no passivation of the surface, e.g. (d) for not cleaned, rusted rebars.

11 - 11 / When cracks are present, the solution in concrete pores (possibly, not alkaline or containing chlorides) could permeate to the steel surface, e.g. (a) air voids, (b) cracks. 4. The attack of corrosion is strongly localized in the defects. If the corrosion current is the same, there could bee rapid reductions in cross-sectional area, e.g. (a) air voids, (b) cracks and (c) rebars lying against the concrete. 5. If a bond is poor and the surface pretreatment inadequate, there could be corrosion beneath coats of paint applied as protection against corrosion and a rapid loss of the protective sealing effect, e.g. (c) rebars lying on the concrete, perhaps in combination with (d) non-cleaned or even chloride-contaminated rebars. In the following, the listed scenarios are discussed with respect to their potential risk. (a) Air voids Basically, it had to be expected that pores existed in the HIT-RE 500 coating. With this in mind, specific defects were made artificially in the adhesive mortar during the tests carried out. After removal of the specimens, natural air voids were actually found on one specimen which were comparable to the man-made defects. In view of this, it could be concluded that it was realistic to provide the defects in the way they were. During the experiments, it was found that it took around the same time for corrosion to begin on specimens with defects as on specimens without defects. Consequently, the conclusion was that pores had no pronounced negative effect on the corrosion behavior. On removing the specimens, the pores proved to be empty. This effect can be explained by the large diameter of the pores and the resulting lack of capillary action. (The same effect is used to achieve the resistance of concrete to freezing and thawing: Large pores do not fill with water because there is no capillary action. Only as a result of evaporation and condensation due to temperature fluctuations can an electrolytic solution get into these pores. Corrosion, which would be initiated by this process, cannot be analyzed by measuring potential and current because the origin of the corrosion has no electrolytic link with the concrete. Consequently, a macro-element cannot form either. The rate of corrosion thus remains extremely low, particularly as only internal corrosion can take place. Basically, the risk of corrosion from pores can be rated as very small, and this was also confirmed by the results of the experiments.) (b) Cracks in HIT-RE 500 In principle, defects are also conceivable which have a capillary action. First and foremost, they would be cracks which have a narrow opening and pass through both the concrete and the HIT-RE 500. If the crack opening is sufficiently narrow, the solution in the

12 - 12 / 16 - concrete pores is drawn towards the steel surface by capillary action. As, however, the alkalinity of the concrete pore solution is high, the surface of the steel will be passivated. If the concentration of chlorides in the concrete pore solution happens to be above the critical value, there will be a local attack of corrosion. The speed of the corrosive attack will most likely be dominated by the crack, according to the general geometric conditions. With a narrow crack opening, only a thin and thus high-resistance electrolytic contact exists with the surrounding medium. The so-called spreading resistance enters the corrosion current circuit directly and reduces the corrosion current. In view of this, the rates of corrosion of even a small corroding area would probably not increase disproportionally. A calculation of the spreading resistance has shown that a locally increased rate of corrosion will occur only if the crack width is larger than the thickness of the epoxy coating. With narrow cracks, the drop in voltage in the crack dominates and, even if a macro-element exists, there would probably be no locally accelerated rate of corrosion. (c) Points of contact with concrete If the steel is lying directly on the concrete, there is no positive effect from the spreading resistance. This can be the case if a rebar is angulated or touching. In alkaline and chloride-free concrete, the point of contact can passivate the steel. If the concentration of chlorides is high, however, local corrosion begins. The case of steel rebars touching the concrete is also discussed under point (d). (d) Surface quality of steel It is known from the use of anti-corrosion coatings that the success of this protective measure depends to a great extent on the quality of the surface treatment of the steel and on the coating thickness. A correspondingly large amount of time, money and effort is required to manufacture durable coatings for protection against corrosion. Experience with epoxy resins is available from, e.g. when used for repair and restoration purposes in reinforced-concrete construction. In these cases, the carbonated or chloridecontaminated concrete was removed, the surface of the reinforcing steel coated with an epoxy resin and the concrete reprofiled again. In many cases, however, the steel was badly attacked again in a short time. During respective studies, the causes, among others, were given as inadequate surface cleaning before applying the coating and the high chloride contamination of the concrete [5]. The renewed, strong attacks of corrosion in a very short time resulted in the bad reputation of epoxy resins as protection against corrosion in reinforced-concrete construction. This experience contradicts the results of the study presented here. It was shown that previously rusted rebars have an excellent corrosion behavior even if their rusty surfaces were not cleaned at all prior to being set in HIT- RE 500. In fact, their corrosion behavior is even superior to that of bright steels. The cause for this difference in behavior must be seen in the different type of prior corrosion,

13 - 13 / 16 - on the one hand, and, on the other hand, the considerably thicker coating used during the corrosion tests presented here. Condition of steel surface when coating: If prior corrosion steel took place when chlorides were present in the concrete, the steel surface is attacked locally. This leads to the formation of FeCl 3. This is a hygroscopic salt with a high redox (oxidation reduction) potential. During concrete repair and restoration, it is possible only to a limited extent for the steel surface to be cleaned owing to construction site conditions and roughening of the surface by the corrosion. FeCl 3 residues are probably always left on the surface. Moisture finds its way to the steel surface through pores in the thin coating or through the matrix by diffusion and osmotic processes, where it finds ideal conditions for corrosion. If the amount of aggressive ions, e.g. chlorides, is below the critical concentration when there are products of atmospheric corrosion, the outset situation is decisively different and, even if other soluble, trivalent iron salts are produced, e.g. Fe 3 (SO 4 ) 3, these might act as passivators. A prime reason for the contradiction is thus the different chemical contamination of the surface. Influence of coating thickness: Once corrosion begins, voluminous products of corrosion are produced on the surface. They split open thin coatings, thus facilitating the further access of corrosive substances to the surface. As a result of the sequence of corrosion and splitting, centers of corrosion form which spread along the surface. This phenomenon is referred to as corrosion beneath a coating or under rusting. Oxygen diffusion through the thin synthetic material coating is a further decisive step which, due to a local increase in ph value, destroys the bonding force between steel and coating and speeds up the electro-chemical reaction. If, however, in the case of rebars set in HIT-RE 500, the coating has a thickness in the millimeter range, this is a difference of at least one order of magnitude. This thick coating of epoxy resin resists the resulting compressive stresses with higher forces than a thin coating, whose build-up has to rely on the supporting structure of the steel. Even if corrosion occurs at the joint, the coating the risk of spliting is significantly decreased due to the high thickness of the coating. This inhibits the spread of corrosion along the surface. Whether or not oxygen diffusion through the thin coatings in concrete plays an important role for the progress of the corrosion in the case of the previously mentioned repair and restoration work, is still not clear. Basically, it should be less significant than attacks of atmospheric corrosion because the structural member is completely enveloped in a conductive electrolyte. Furthermore, it is possible for macro-elements to form and the oxygen diffusion is greatly retarded by the thick coating. A detailed study of these processes is presented in the paper by Nguyen and Martin [6].

14 - 14 / 16 - Consequently, the excellent behavior of HIT-RE 500 on previously rusted steels stems primarily from the fact that, although the surfaces were somewhat corroded, they were not contaminated with chlorides, and the coating was very thick. If a steel surface is contaminated with chlorides when the steel is used in maritime surroundings, the formation of FeCl 3 must be expected. By applying a comparatively thick layer of several millimeters of epoxy resin, this coating largely inhibits the mass transfer between steel surface and enveloping concrete. In general, it is found that epoxy resin coatings more than 300 microns thick are sufficient to produce a complete separating barrier. Water and oxygen diffuse if coatings are thin. This will result in a loss of bonding, blistering due to osmotic pressure, splitting of thin coatings and opening up of the steel surface. If the concrete is alkaline and free of chlorides passivation of the steel surface will occur. In presence of chlorides, however, pitting corrosion is expected to occur. These processes can be inhibited by applying a sufficiently thick coating. In the case of HIT-RE 500, the mass transport is efficiently stopped. In this way, possible attacks at coating defects are restricted. The comparatively thick coating of HIT-RE 500 on the steel surface, furthermore, confronts forming products of corrosion with higher mechanical strength. As a result, the splitting and thus the spread of an attack of corrosion under the coating will most likely be avoided as well. This situation was not investigated in the case in question. Theoretically, however, good performance by HIT-RE 500 can be expected, even if a surface of steel has been contaminated with chlorides, as long as the concrete is free of chlorides and non carbonated as long as the coathing thickness is sufficient and the concrete is alkaline and free of chlorides. If the benefit of a thick coating of HIT-RE 500 is put to use, e.g. with the aid of spacers, when installing rebars or other anchoring devices in old concrete, attention must, nonetheless, be paid to the anticipated scenarios at the unprotected zones, namely the concrete joint and the new concrete. If these zones are also at risk from chloride contamination, those responsible must use precoated steel or corrosion-resistant steel selected to suit the given conditions. (e) Rebar connections without guaranteed coat thickness When structural connections are made using rebars without spacers, the rebars can be in contact with their hole wall over a large area or at many points where the ribs might be touching. In these case, the effectiveness of the HIT-RE 500 system is impaired where the resistance to chloride exposure is concerned. Right next to the points of contact, the adhesive mortar will not be very thick. As long as there is no carbonation and no chlorides reach the steel surface, no corrosion will take place in this situation. In other words, the use of rebar connections made with HIT-RE 500 can be considered only if the concrete is sound and a minimum coating thickness of, for example, 1 millimeter is ensured.

15 - 15 / 16 - (f) Comparison of test results with data in reference literature on epoxy resin coated rebars Reports in pertaining literature are first and foremost about good experience with epoxy resin coated steel. There is, however, also mention of some negative results in the south of the USA. These studies carried out in Florida [5] showed a heavy attack of corrosion and large-area separation of the coating after a few years of exposure to a maritime environment. The causes were combinations of several mistakes made during work execution, such as very heavy concrete salinization, cracks in the coating caused by bending rebars, much to thin a concrete cover which resulted in cover cracking and inadequate pretreatment of the steel surface. Products of corrosion containing chlorides were left on the steel surface when the rebars were coated and they set off, among other things, the processes described under points (d and e). Other investigations into causes in Virginia showed that the coating had separated over a considerable area [7 and 8], but that no attacks of corrosion had taken place. Problems can also arise from delamination of the coating. This reduction in bond strength can occur if a structure is permanently saturated throughout. It has also been observed that the loss of bonding strength is reversible. On the other hand, irreversible delamination takes place when an increase in ph value at the interface occurs due to oxygen reduction [10]. This negative experience conflicts with numerous positive results [9]. The examination of 82 structures in the USA and Canada showed the corrosion behavior to be clearly better than that of uncoated reinforcement. Even misgivings about a small size of defect leading to a locally accelerated rate of corrosion were not verified during experiments [4]. The comparatively high resistance to spreading prevents this process from taking place. The evaluation in reference literature throws a positive light overall on the corrosion behavior of epoxy resin coated reinforcing bars. Prime requisites with these thin coatings are good surface pretreatment and, in particular, the absence of products of corrosion containing chlorides. The problems with epoxy resin coated steels referred to in reference literature are only vaguely relevant to the HIT-RE 500 system. For example, no cracks in the coating can be produced by bending. When rebars are bonded in with HIT-RE 500, the clearly thicker coating prevents oxygen and water from reaching the steel surface, and thus the bond is not lost. During the presented tests, it was observed with all specimens bonded in with HIT-RE 500 which had begun to corrode that there was always corrosion in the new concrete too. The occurrence of corrosion in the new concrete can be attributed to chloride penetration. In it, they can initiate corrosion on a bare steel surface.

16 - 16 / Reference literature [1] H. Kaesche, Die Korrosion der Metalle, Springer-Verlag, Berlin, (1990). [2] W. Richartz, Die Bindung von Chloriden bei der Zementerhärtung, Zement-Kalk- Gips, 10 (1969) [3] Y. Schiegg, Dissertation, ETH Nr [4] B. Elsener, Einsatz epoxidbeschichteter Stähle in Korrosion und Korrosionsschutz, SIA Dokumentation D021 (1988) [5] J. A. Read, Need for correct specification and quality control, Concrete, 23 (1989) 23. [6] T. Nguyen and J. W. Martin, Durability of building materials and components, 7 Volume 1 (1996) 491 [7] R. E. Weyers, M. M. Sprinke, W.A. Pyc, J. Zemaijtis, Y. Liu, and D. Mokarem, VTRC 98-R4 (1997) [8] R. E. Weyers, D. W. Morakem, J. G. Dillard, Concrete International (2000) 57 [9] J. L. Smith, Y. P. Virmani, Performance of epoxy coated rebars [10] J. J. Ritter, J. Kruger, Studies of subcoating environment of coated iron using ellipsometric and electrochemical technique, In Corrosion control by Organic Coatings (Ed. H. Leiheiser) (1981) 28.

1. CORROSION OF REINFORCEMENT

1. CORROSION OF REINFORCEMENT MAB 1033 Structural Assessment and Repair 1. CORROSION OF REINFORCEMENT Professor Dr. Mohammad bin Ismail C09-313 Learning Outcome At the end of the course students should be able to understand Mechanism

More information

REFURBISHMENT Sika FerroGard -903 Plus THE UNIQUE MULTI-FUNCTIONAL SURFACE APPLIED CORROSION INHIBITOR FOR REINFORCED CONCRETE

REFURBISHMENT Sika FerroGard -903 Plus THE UNIQUE MULTI-FUNCTIONAL SURFACE APPLIED CORROSION INHIBITOR FOR REINFORCED CONCRETE THE UNIQUE MULTI-FUNCTIONAL SURFACE APPLIED CORROSION INHIBITOR FOR REINFORCED CONCRETE CORROSION IN REINFORCED CONCRETE STRUCTURES AGGRESSIVE INFLUENCES ON REINFORCED CONCRETE In reinforced concrete the

More information

Sika FerroGard Surface Applied Corrosion Inhibitor for Reinforced Concrete

Sika FerroGard Surface Applied Corrosion Inhibitor for Reinforced Concrete FerroGard -903 + Surface Applied Corrosion Inhibitor for Reinforced Concrete Corrosion in Reinforced Concrete Structures Corrosion Management with Ferrogard Technology Aggressive Influences on Reinforced

More information

REFURBISHMENT Sika FerroGard -903+

REFURBISHMENT Sika FerroGard -903+ REFURBISHMENT Sika FerroGard -903+ INCREASE THE SERVICE LIFE OF REINFORCED CONCRETE BY UP TO 100% CORROSION IN REINFORCED CONCRETE STRUCTURES AGGRESSIVE INFLUENCES ON REINFORCED CONCRETE In reinforced

More information

DURABILITY of CONCRETE STRUCTURES

DURABILITY of CONCRETE STRUCTURES DURABILITY of CONCRETE STRUCTURES Assist. Prof. Dr. Mert Yücel YARDIMCI This presentation covers the subjects in CEB Durable Concrete Structures Guideline and has been prepared by the graduate students

More information

Author: M Shaw, Sika Limited. Construction. A Guide to the Concrete Repair European Standards BS EN 1504 Series

Author: M Shaw, Sika Limited. Construction. A Guide to the Concrete Repair European Standards BS EN 1504 Series Author: M Shaw, Sika Limited A Guide to the Concrete Repair European Standards BS EN 1504 Series 1 Contents Section Heading Page Introduction 3 1.0 Overview of BS EN 1504 Documents 4 2.0 BS EN 1504 Principles

More information

Corrosion Resistance of Alternative Reinforcing Bars: An Accelerated Test

Corrosion Resistance of Alternative Reinforcing Bars: An Accelerated Test Corrosion Resistance of Alternative Reinforcing Bars: An Accelerated Test Final Report 24 July 2006 WJE No. 2006.0773 Prepared for: CRSI Prepared by: Wiss, Janney, Elstner Associates, Inc. CORROSION RESISTANCE

More information

6.4.1 Concrete mix design. The four concrete mixes were designed using the absolute volume method as shown below:

6.4.1 Concrete mix design. The four concrete mixes were designed using the absolute volume method as shown below: Chapter No. (6) Materials and Test Methods 6.4.1 Concrete mix design The four concrete mixes were designed using the absolute volume method as shown below: 6.4.1.1 Mix No. (1): f cu = 3MPa, w/c =.32 162

More information

Investigation of Chloride Ingress in Cracked Concrete Treated with Water Repellent Agents

Investigation of Chloride Ingress in Cracked Concrete Treated with Water Repellent Agents Hydrophobe V 5 th International Conference on Water Repellent Treatment of Building Materials Aedificatio Publishers, 299-310 (2008) Investigation of Chloride Ingress in Cracked Concrete Treated with Water

More information

Corrosion. Lab. of Energy Conversion & Storage Materials. Produced by K. B. Kim

Corrosion. Lab. of Energy Conversion & Storage Materials. Produced by K. B. Kim Corrosion 대기환경에의한금속소재 (organic film coated steel) 의퇴화현상평가연구 Lab. of Energy Conversion & Storage Materials Produced by K. B. Kim Introduction AC Impedance Spectroscopy Application of AC Impedance to Corrosion

More information

2. Wet Corrosion: Characteristics, Prevention and Corrosion Rate

2. Wet Corrosion: Characteristics, Prevention and Corrosion Rate 2. Wet Corrosion: Characteristics, Prevention and Corrosion Rate Mighty ships upon the ocean suffer from severe corrosion. Even those that stay at dockside are rapidly becoming oxide Alas, that piling

More information

Corrosion Mitigation Systems for Concrete Structures

Corrosion Mitigation Systems for Concrete Structures Corrosion Mitigation Systems for Concrete Structures By J. Christopher Ball and David W. Whitmore According to a recently completed study by the U.S. Federal Highway Administration, the annual direct cost

More information

EFFECT OF CHLORIDE CONCENTRATION IN SOIL ON REINFORCEMENT CORROSION

EFFECT OF CHLORIDE CONCENTRATION IN SOIL ON REINFORCEMENT CORROSION EFFECT OF CHLORIDE CONCENTRATION IN SOIL ON REINFORCEMENT CORROSION By M. Maslehuddin 1*, M. M. Al-Zahrani 1, M. Ibrahim 1, M. H. Al-Mehthel 2, and S. H. Al- Idi 2 ABSTRACT This paper presents results

More information

CTRE Center for Transportation Research and Education

CTRE Center for Transportation Research and Education IMPACT OF DECK CRACKING ON DURABILITY Sponsored by the Project Development Division of the Iowa Department of Transportation and the Iowa Highway Research Board Iowa DOT Project TR-405 CTRE Management

More information

Rusty Boicourt, P.G. NDE & Materials Specialist Materials Testing & Inspection

Rusty Boicourt, P.G. NDE & Materials Specialist Materials Testing & Inspection Corrosion Damaged Concrete Causes & Repair Presented by Rusty Boicourt, P.G. NDE & Materials Specialist Materials Testing & Inspection Examples of Corrosion Damage Examples of Corrosion Damage Examples

More information

European Standard En 1504

European Standard En 1504 BS EN 1504 Products and Systems for the protection and repair of concrete structures Definitions, requirements, quality control and evaluation of conformity John Drewett Concrete Repairs Ltd 25% of the

More information

Bridge Preservation Corrosion Mitigation Option in Concrete Repair Systems

Bridge Preservation Corrosion Mitigation Option in Concrete Repair Systems Bridge Preservation Corrosion Mitigation Option in Concrete Repair Systems September 29, 2010 Northeast Bridge Preservation Partnership Meeting TSP-2 TODAY WE WILL DISCUSS Corrosion of Bridge Decks Surface

More information

Impact of self-healing engineered materials on the corrosion of reinforced concrete

Impact of self-healing engineered materials on the corrosion of reinforced concrete Impact of self-healing engineered materials on the corrosion of reinforced concrete Hilke Verbruggen a,c & Bjorn Van Belleghem b,c Florian Hiemer d, Sylvia Keßler d, Christoph Gehlen d, Nele De Belie b,

More information

Application of Silane-based Compounds for the Production of Integral Water Repellent Concrete

Application of Silane-based Compounds for the Production of Integral Water Repellent Concrete Hydrophobe VI 6 th International Conference on Water Repellent Treatment of Building Materials Aedificatio Publishers, 137-144 (2011) Application of Silane-based Compounds for the Production of Integral

More information

EVALUATING MITIGATION METHODS FOR CHLORIDE INDUCED CORROSION OF REINFORCED CONCRETE STRUCTURES

EVALUATING MITIGATION METHODS FOR CHLORIDE INDUCED CORROSION OF REINFORCED CONCRETE STRUCTURES EVALUATING MITIGATION METHODS FOR CHLORIDE INDUCED CORROSION OF REINFORCED CONCRETE STRUCTURES B.H.J. Pushpakumara Research Student Department of Civil and Environmental Engineering, Faculty of Engineering,

More information

VITCON 9001 RCI Bipolar Roving / Migratory Corrosion Inhibitor Admixture For Reinforced Concrete

VITCON 9001 RCI Bipolar Roving / Migratory Corrosion Inhibitor Admixture For Reinforced Concrete VITCON 9001 RCI Bipolar Roving / Migratory Corrosion Inhibitor Admixture For Reinforced Concrete Corrosion in Reinforced Concrete Structures Aggressive Influences on Reinforced Concrete In reinforced concrete

More information

Behaviour of Post-Installed GFRP Adhesive Anchors in Concrete

Behaviour of Post-Installed GFRP Adhesive Anchors in Concrete NSERC Industrial Research Chair in Innovative FRP Composites for Infrastructures Behaviour of Post-Installed GFRP Adhesive Anchors in Concrete Prepared by: Ehab A. Ahmed, Ehab El-Salakawy, and Brahim Benmokrane

More information

Introduction of a Japan Concrete Institute Guideline: Practical Guideline for Investigation, Repair and Strengthening of Cracked Concrete Structures

Introduction of a Japan Concrete Institute Guideline: Practical Guideline for Investigation, Repair and Strengthening of Cracked Concrete Structures Journal of Civil Engineering and Architecture 9 (2015) 213-224 doi: 10.17265/1934-7359/2015.02.010 D DAVID PUBLISHING Introduction of a Japan Concrete Institute Guideline: Practical Guideline for Investigation,

More information

Schweizerische Gesellschaft für Korrosionsschutz Société Suisse de Protection contre la Corrosion Korrosionskommission / Commission de Corrosion

Schweizerische Gesellschaft für Korrosionsschutz Société Suisse de Protection contre la Corrosion Korrosionskommission / Commission de Corrosion Schweizerische Gesellschaft für Korrosionsschutz Société Suisse de Protection contre la Corrosion Korrosionskommission / Commission de Corrosion Bericht Nr. Rapport No. 04 017 Technoparkstr. 1 8005 Zürich

More information

REFURBISHMENT Sika FerroGard GALVANIC AND HYBRID ANODE TECHNOLOGIES

REFURBISHMENT Sika FerroGard GALVANIC AND HYBRID ANODE TECHNOLOGIES Sika FerroGard GALVANIC AND HYBRID ANODE TECHNOLOGIES CONCRETE CORROSION CONTROLLED FOR UP TO 50 YEARS REDUCING MAINTENANCE COSTS AND EXTENDING THE LIFE OF REINFORCED CONCRETE REINFORCED CONCRETE IS A

More information

C. Gianocca, C. Haldemann, IM Maggia Engineering SA, Locarno / Switzerland

C. Gianocca, C. Haldemann, IM Maggia Engineering SA, Locarno / Switzerland Thermal Sprayed Zinc as Sacrificial Anode for Cathodic Corrosion Protection in a Covered Car Park Suffering from Chloride Corrosion- An Optimized, Durable and Time Effective Repair Method C. Gianocca,

More information

Relationship between corrosion and element severity score for reinforced concrete beams

Relationship between corrosion and element severity score for reinforced concrete beams Relationship between corrosion and element severity score for reinforced concrete beams O'FLAHERTY, Fin , BROWNE, Elena, MANGAT, Pal

More information

Cathodic Protection of Steel in Concrete

Cathodic Protection of Steel in Concrete Cathodic Protection of Steel in Concrete For many years industrial companies have fought to protect steel reinforced concrete from corrosion. The prime causes of corrosion in concrete include salt, chloride

More information

Fundamental study on the effectiveness of nitrite for polymer-cement mortar

Fundamental study on the effectiveness of nitrite for polymer-cement mortar Fundamental study on the effectiveness of nitrite for polymer-cement mortar Hirotaka Hazehara 1*, Masashi Soeda 2, Ryo Matsumoto 3 and Shinichiro Hashimoto 1 1 Assistant professor, Fukuoka University,

More information

SURVEY ON ENVIRONMENTAL IMPACT OF CARBONATION PROGRESS AND REBAR CORROSION IN ACTUAL CONCRETE STRUCTURE

SURVEY ON ENVIRONMENTAL IMPACT OF CARBONATION PROGRESS AND REBAR CORROSION IN ACTUAL CONCRETE STRUCTURE SURVEY ON ENVIRONMENTAL IMPACT OF CARBONATION PROGRESS AND REBAR CORROSION IN ACTUAL CONCRETE STRUCTURE Takeshi IYODA 1 and Satoshi Maehara 2 1 Department of Civil Engineering, Shibaura Institute of Technology,

More information

Advantages of the Simultaneous Use of Corrosion Inhibitors and Inorganic Coatings

Advantages of the Simultaneous Use of Corrosion Inhibitors and Inorganic Coatings Cement and Concrete Technology in the 2000 s Second International Symposium, 6-10 September 2000. Istanbul, Turkey Advantages of the Simultaneous Use of Corrosion Inhibitors and Inorganic Coatings George

More information

Determination of the suitability of technical textiles for cathodic corrosion protection

Determination of the suitability of technical textiles for cathodic corrosion protection 1 Determination of the suitability of technical textiles for cathodic corrosion protection Amir Asgharzadeh Institute of Building Materials Research RWTH-Aachen University, Germany Michael Raupach Institute

More information

Iron is found in an oxidized state and is mined from the ground as an iron ore.

Iron is found in an oxidized state and is mined from the ground as an iron ore. Iron is found in an oxidized state and is mined from the ground as an iron ore. Energy is used to convert this iron oxide into steel. Ore is loaded into a blast furnace where heat energy removes the oxygen

More information

INITIAL EVALUATION OF CORROSION PERFORMANCE AND ALKALI REACTIVITY OF CERAMIC-COATED REINFORCING BARS

INITIAL EVALUATION OF CORROSION PERFORMANCE AND ALKALI REACTIVITY OF CERAMIC-COATED REINFORCING BARS INITIAL EVALUATION OF CORROSION PERFORMANCE AND ALKALI REACTIVITY OF CERAMIC-COATED REINFORCING BARS By Matthew O Reilly David Darwin JoAnn Browning A Report on Research Sponsored by CMC Steel Fabricators

More information

Cathodic Protection as a Corrosion Control Alternative

Cathodic Protection as a Corrosion Control Alternative Cathodic Protection as a Corrosion Control Alternative By William T. Scannell and Ali Sohanghpurwala Corrosion of reinforcing steel in concrete is a widespread and enormously costly problem in all parts

More information

SPECIAL SPECIFICATION 4703 Repair Of Impact Damaged Prestressed Concrete Bridge Beams

SPECIAL SPECIFICATION 4703 Repair Of Impact Damaged Prestressed Concrete Bridge Beams 1993 Specifications CSJ 0162-01-080, etc. SPECIAL SPECIFICATION 4703 Repair Of Impact Damaged Prestressed Concrete Bridge Beams 1. Description. This Item shall govern for the repair of impact damaged prestressed

More information

Significance and influence of the ambient temperature as a rate factor of steel reinforcement corrosion

Significance and influence of the ambient temperature as a rate factor of steel reinforcement corrosion Bull. Mater. Sci., Vol. 25, No. 5, October 2002, pp. 375 379. Indian Academy of Sciences. Significance and influence of the ambient temperature as a rate factor of steel reinforcement corrosion V Z V IVICA

More information

Sealing Concrete Bridge Decks: Overview of Current Technologies. Lorella Angelini Angelini Consulting Services

Sealing Concrete Bridge Decks: Overview of Current Technologies. Lorella Angelini Angelini Consulting Services Sealing Concrete Bridge Decks: Overview of Current Technologies Lorella Angelini Angelini Consulting Services Concrete Non-Film Forming Sealers Overview of most recent and commonly used non-film forming

More information

Prepared by M. Donadio, Market Development Manager, TM Refurbishment, Sika Services AG, Switzerland

Prepared by M. Donadio, Market Development Manager, TM Refurbishment, Sika Services AG, Switzerland Sika Services AG, Switzerland Sewage treatment plant protective coating long term investigation Dated: April 2013 Version : n 003.2013 Sewage treatment plant protective coating long term investigation

More information

IN SITU MONITORING OF REINFORCEMENT CORROSION BY MEANS OF ELECTROCHEMICAL METHODS

IN SITU MONITORING OF REINFORCEMENT CORROSION BY MEANS OF ELECTROCHEMICAL METHODS ABSTRACT IN SITU MONITORING OF REINFORCEMENT CORROSION BY MEANS OF ELECTROCHEMICAL METHODS Oskar Klinghoffer, M.Sc. FORCE Institute, Park Allé 345, DK-2605 Brøndby, Denmark The well-known and usually adapted

More information

Threshold Chloride Concentration of Stainless Steels in Simulated Concrete Pore Solution

Threshold Chloride Concentration of Stainless Steels in Simulated Concrete Pore Solution 5th International Conference on Durability of Concrete Structures Jun 30 Jul 1, 2016 Shenzhen University, Shenzhen, Guangdong Province, P.R.China Threshold Chloride Concentration of Stainless Steels in

More information

AASHTO/NTPEP Rapid Set Concrete Patching Materials

AASHTO/NTPEP Rapid Set Concrete Patching Materials AASHTO/NTPEP Rapid Set Concrete Patching Materials User Guide 2015 Introduction: The National Transportation Product Evaluation Program (NTPEP) was established to minimize the amount of duplicative testing

More information

Technical data No. 17/0002 of 22/05/2017

Technical data No. 17/0002 of 22/05/2017 Hilti Corporation Feldkircherstrasse 100 FL-9494 Schaan Principality of Liechtenstein www.hilti.group Technical data No. 17/0002 of 22/05/2017 General Part Trade name Injection system Hilti HIT-RE 500

More information

SIKA FERROGARD CORROSION INHIBITORS DONADIO MICHEL SIKA SERVICES AG / TM REFURBISHMENT

SIKA FERROGARD CORROSION INHIBITORS DONADIO MICHEL SIKA SERVICES AG / TM REFURBISHMENT SIKA FERROGARD CORROSION INHIBITORS DONADIO MICHEL SIKA SERVICES AG / TM REFURBISHMENT MOTHER NATURE S RULES Dig up Iron ore (various oxides) 2 MOTHER NATURE S RULES Spend 1000 kw s of energy to produce

More information

Sika Injection Systems for Concrete Structures. Concrete Structures

Sika Injection Systems for Concrete Structures. Concrete Structures Sika Injection Systems for Concrete Structures Sika is a globally active company in the speciality and construction chemicals business. It has subsidiary manufacturing, sales and technical support facilities

More information

Corrosion Mechanisms, Monitoring, and Service Life Enhancement of Reinforced Concrete Structures

Corrosion Mechanisms, Monitoring, and Service Life Enhancement of Reinforced Concrete Structures Corrosion Mechanisms, Monitoring, and Service Life Enhancement of Reinforced Concrete Structures Radhakrishna G. Pillai Concrete Materials Research Group (Building Technology & Construction Management

More information

Effects of Corrosion on Reinforced Concrete Beams with Silica Fume and Polypropylene Fibre

Effects of Corrosion on Reinforced Concrete Beams with Silica Fume and Polypropylene Fibre Effects of Corrosion on Reinforced Concrete Beams with Silica Fume and Polypropylene Fibre S.Shanmugam, V.G. Srisanthi, and S.Ramachandran Abstract Reinforced concrete has good durability and excellent

More information

EFFECT OF CHLORIDE IONS SOURCE ON CORROSION OF REINFORCED NORMAL AND HIGH PERFORMANCE CONCRETE

EFFECT OF CHLORIDE IONS SOURCE ON CORROSION OF REINFORCED NORMAL AND HIGH PERFORMANCE CONCRETE EFFECT OF CHLORIDE IONS SOURCE ON CORROSION OF REINFORCED CONCRETE EFFECT OF CHLORIDE IONS SOURCE ON CORROSION OF REINFORCED NORMAL AND HIGH PERFORMANCE CONCRETE PhD, Assist. Prof. Tareq Salih AL-ATTAR

More information

Diffusion of moisture and chloride ions in repaired concrete subjected to complex deterioration factors

Diffusion of moisture and chloride ions in repaired concrete subjected to complex deterioration factors Journal of Asian Concrete Federation Vol. 3, No. 1, pp. -26, June 17 ISSN 246-7964 / eissn 246-7972 http://dx.doi.org/.1872/acf.17.6.3.1. Technical Paper Diffusion of moisture and chloride ions in repaired

More information

Development of Simulation Model of Chloride Ion Transportation in Cracked Concrete

Development of Simulation Model of Chloride Ion Transportation in Cracked Concrete Journal of Advanced Concrete Technology Vol., No., 85-9, February 5 / Copyright 5 Japan Concrete Institute 85 Scientific paper Development of Simulation Model of Chloride Ion Transportation in Cracked

More information

Re-alkalisation technology applied to corrosion damaged concrete

Re-alkalisation technology applied to corrosion damaged concrete Concrete Repair, Rehabilitation and Retrofitting II Alexander et al (eds) 2009 Taylor & Francis Group, London, ISBN 978-0-415-46850-3 Re-alkalisation technology applied to corrosion damaged concrete G.K.

More information

CORROSION PREVENTION OF CONCRETE REINFORCE MENT BY EPOXY COATING SYNOPSIS. One of the methods of preventing concrete reinforcement corrosion

CORROSION PREVENTION OF CONCRETE REINFORCE MENT BY EPOXY COATING SYNOPSIS. One of the methods of preventing concrete reinforcement corrosion 25 CORROSION PREVENTION OF CONCRETE REINFORCE MENT BY EPOXY COATING Liisa Salparanta Technical Research Centre of Finland Concrete and Silicate Laboratory MScTech, Research Scientist SYNOPSIS In this study

More information

Product Data Sheet Product Description tio Uses tru n Characteristics / Advantages

Product Data Sheet Product Description tio Uses tru  n Characteristics / Advantages Product Data Sheet Edition 11/12/2014 Identification no: 02 03 03 04 001 0 000001 Sika FerroGard -903+ Corrosion inhibiting impregnation Product Description Sika FerroGard -903+ is a surface applied mixed

More information

EFFECT OF SACRIFICIAL ZINC ANODES ON CURRENT DENSITY FOR EFFECTIVE CATHODIC PROTECTION OF RCC

EFFECT OF SACRIFICIAL ZINC ANODES ON CURRENT DENSITY FOR EFFECTIVE CATHODIC PROTECTION OF RCC EFFECT OF SACRIFICIAL ZINC ANODES ON CURRENT DENSITY FOR EFFECTIVE CATHODIC PROTECTION OF RCC Krishna Shinde 1, R. K. Shrivastava 2 and R. D. Angal 3 1 Department of Mechanical Engineering, Govt. College

More information

Thermal Spray Coating

Thermal Spray Coating Thermal Spray Coating for Corrosion Protection Presented by: John Crowe, PCS What You Need To Know PRESENTATION TOPICS Corrosion Basics Thermal Spray Coating-What It Is & What It Does Advantages & Disadvantages

More information

MANAGEMENT OF CATHODIC PROTECTION SYSTEMS IN MARINE ENVIRONMENTS

MANAGEMENT OF CATHODIC PROTECTION SYSTEMS IN MARINE ENVIRONMENTS MANAGEMENT OF CATHODIC PROTECTION SYSTEMS IN MARINE ENVIRONMENTS A. Cheaitani Remedial Technology Pty Ltd, Sydney, Australia SUMMARY: Impressed current cathodic protection (ICCP) for reinforced concrete

More information

AN OVERVIEW OF THE USE OF GALVANIZED REINFORCEMENT IN CONCRETE CONSTRUCTION

AN OVERVIEW OF THE USE OF GALVANIZED REINFORCEMENT IN CONCRETE CONSTRUCTION 1 AN OVERVIEW OF THE USE OF GALVANIZED REINFORCEMENT IN CONCRETE CONSTRUCTION Professor Stephen R Yeomans School of Civil Engineering University of New South Wales, Canberra Introduction The loss of durability

More information

Building Condition Survey and Diagnosis

Building Condition Survey and Diagnosis APC Revision Course 1 8 July 2013 Building Condition Survey and Diagnosis APC Revision Course 2 8 July 2013 Condition Survey Common Practice in Hong Kong Fixed fee for a report and hourly rate for presentation

More information

PRESENTED AT NATIONAL BRIDGE PRESERVATION PARTNERSHIP CONFERENCE ORLANDO, FLORIDA 2014 AUTHORS ROBERT WALDE, SURTREAT HOLDING, LLC PRESENTER RICH

PRESENTED AT NATIONAL BRIDGE PRESERVATION PARTNERSHIP CONFERENCE ORLANDO, FLORIDA 2014 AUTHORS ROBERT WALDE, SURTREAT HOLDING, LLC PRESENTER RICH PRESENTED AT NATIONAL BRIDGE PRESERVATION PARTNERSHIP CONFERENCE ORLANDO, FLORIDA 2014 AUTHORS ROBERT WALDE, SURTREAT HOLDING, LLC PRESENTER RICH LAMPO, U.S. ARMY CORPS OF ENGINEERS RESEARCH LABORATORY

More information

Strength in unity. Quelle/Publication: European Coatings Journal. Seite/Page:

Strength in unity. Quelle/Publication: European Coatings Journal. Seite/Page: 1 Strength in unity A waterborne hybrid protective coating system has been developed which provides very high salt spray resistance with very low VOC levels Careful selection of the binder system was required

More information

PREMATURE FAILURE OF REPAINTED EPOXY ON THE BOTTOM PLATE OF A MAIN FUEL OIL TANK - A CASE STUDY 1

PREMATURE FAILURE OF REPAINTED EPOXY ON THE BOTTOM PLATE OF A MAIN FUEL OIL TANK - A CASE STUDY 1 PREMATURE FAILURE OF REPAINTED EPOXY ON THE BOTTOM PLATE OF A MAIN FUEL OIL TANK - A CASE STUDY 1 M. Mobin and A.U. Malik Saline Water Desalination Research Institute Saline Water Conversion Corporation

More information

Solutions. for Severe Corrosion

Solutions. for Severe Corrosion Solutions for Severe Corrosion Linas Mazeika, President, 3L&T Inc., USA, reveals how to prevent equipment corrosion caused by hot combustion gases in a cement plant. Summary The serious economic consequences

More information

SikaInjectionSystemsfor ConcreteStructures

SikaInjectionSystemsfor ConcreteStructures SikaInjectionSystemsfor ConcreteStructures Sika Injection Systems for Concrete Structures Typical Problems in Concrete Structures Waterproofing of Construction Joints Surface Sealing of leaking Concrete

More information

Zinc Silicate (Inorganic)

Zinc Silicate (Inorganic) Product code: 477-041: part A 477-042: part B General description: Two-component, zinc-ethyl silicate-. Forms a continuous coat of metallic zinc that provides cathodic protection to metal (as in hot galvanization).

More information

NON-CLEANING AND OPTIMIZED FOR CORROSIVE ENVIRONMENTS. Hilti HIT-Z-F and HIT-HY 200 ultimate performance chemical anchor system

NON-CLEANING AND OPTIMIZED FOR CORROSIVE ENVIRONMENTS. Hilti HIT-Z-F and HIT-HY 200 ultimate performance chemical anchor system NON-CLEANING AND OPTIMIZED FOR CORROSIVE ENVIRONMENTS Hilti HIT-Z-F and HIT-HY 200 ultimate performance chemical anchor system ULTIMATE PERFORMANCE THAT LASTS Hilti HIT-Z-F corrosion-resistant anchor rod

More information

Experimental Investigation on Diffusion Coefficient of Carbon Dioxide for Sustainable Construction Materials

Experimental Investigation on Diffusion Coefficient of Carbon Dioxide for Sustainable Construction Materials Experimental Investigation on Diffusion Coefficient of Carbon Dioxide for Sustainable Construction Materials Sang Hwa Jung 1, Myung Kue Lee 2, Seong Lo Lee 3, and Byung Hwan Oh 4 1 Korea Institute of Construction

More information

DUAL EXPANSION. facilitate casting and ensure the total filling of voids even in tight or complex spaces and when working on large surfaces.

DUAL EXPANSION. facilitate casting and ensure the total filling of voids even in tight or complex spaces and when working on large surfaces. Fluid expansive mortar for precision anchoring of machinery and structural elements LAYER THICKNESS FROM 1 TO 10 CM REFURBISHMENT and PROTECTION Line Expansive cement-based mortar for anchoring and grouting

More information

PROCON I N T E R N A T I O N A L, L L C. CONSULTING ARCHITECTS & ENGINEERS CONSTRUCTION TECHNOLOGY

PROCON I N T E R N A T I O N A L, L L C. CONSULTING ARCHITECTS & ENGINEERS CONSTRUCTION TECHNOLOGY PROCON P R O F E S S I O N A L C O N S U L T A N T S I N T E R N A T I O N A L, L L C CONSULTING ARCHITECTS & ENGINEERS CONSTRUCTION TECHNOLOGY www.proconweb.com Assessing the Performance of Metal Trim

More information

MasterEmaco S 488 TIX

MasterEmaco S 488 TIX DESCRIPTION is an expansive mortar that, for its specific performances, is ideal for concrete repair for thickness from 1 to 5 cm in a single layer on vertical walls or/and on the ceiling of horizontal

More information

TECHNICAL BULLETIN. Dissimilar Metal Corrosion in Roofing Installations

TECHNICAL BULLETIN. Dissimilar Metal Corrosion in Roofing Installations TECHNICAL BULLETIN Dissimilar Metal Corrosion in Roofing Installations This Technical Bulletin provides guidance when working with different metals used in roofing installations. Most metals used for construction

More information

New Materials and Systems for Prestressed Concrete Structures" COST Materials Action 534

New Materials and Systems for Prestressed Concrete Structures COST Materials Action 534 New Materials and Systems for Prestressed Concrete Structures" COST Materials Action 534 WG5-P2 LONG TERM DURABILITY AND SERVICE LIFE OF POSTENSIONED STRUCTURES Toulouse-November 2007 Carmen. Andrade_IETcc,

More information

Fundamentals of Concrete

Fundamentals of Concrete Components Cement Water Fine Aggregate Coarse Aggregate Fundamentals of Range in Proportions Advantages of Reducing Water Content: Increased strength Lower permeability Fundamentals of Increased resistance

More information

ONLINE MONITORING OF UNDERCOATING CORROSIONS UTILIZING COUPLED MULTIELECTRODE SENSORS. Xiaodong Sun Corr Instruments, LLC San Antonio TX, USA ABSTRACT

ONLINE MONITORING OF UNDERCOATING CORROSIONS UTILIZING COUPLED MULTIELECTRODE SENSORS. Xiaodong Sun Corr Instruments, LLC San Antonio TX, USA ABSTRACT ONLINE MONITORING OF UNDERCOATING CORROSIONS UTILIZING COUPLED MULTIELECTRODE SENSORS Xiaodong Sun Corr Instruments, LLC San Antonio TX, USA ABSTRACT Online monitoring of carbon steel corrosion under different

More information

Corrosion Protection Effect with Sacrificial Anode for Corroded Steel Members using Al-Zn Casting Alloy and Fiber Sheet

Corrosion Protection Effect with Sacrificial Anode for Corroded Steel Members using Al-Zn Casting Alloy and Fiber Sheet Corrosion Protection Effect with Sacrificial Anode for Corroded Steel Members using Al-Zn Casting Alloy and Fiber Sheet *Yohei Tsuchihashi 1), Shigenobu Kainuma 2), Young-Soo Jeong 3), Shuji Ishihara,

More information

Bond between Reinforcement and Concrete Influence of Steel Corrosion

Bond between Reinforcement and Concrete Influence of Steel Corrosion Bond between Reinforcement and Concrete Influence of Steel Corrosion Mohammed Sonebi 1 Richard Davidson 2 David Cleland 3 ABSTRACT The investigation into the deterioration of the bond between concrete

More information

Effect of Corrosion Inhibitor in Mild Steel Bar

Effect of Corrosion Inhibitor in Mild Steel Bar Effect of Corrosion Inhibitor in Mild Steel Bar K. Kavya 1, V. Kavyadharshini 2, M. Keerthana 3, S. Karthika 4, S. Suresh 5 U.G. Student, Department of Civil Engineering, Sona College of Technology, Salem,

More information

Modeling the Performance of Protective Coatings in Marine Service. J. Peter Ault and James A. Ellor Elzly Technology Company

Modeling the Performance of Protective Coatings in Marine Service. J. Peter Ault and James A. Ellor Elzly Technology Company Modeling the Performance of Protective Coatings in Marine Service J. Peter Ault and James A. Ellor Elzly Technology Company Abstract Despite improvement in organic coating technology, accurate prediction

More information

Durability of Marine Concrete with Mineral Admixture and Marine Aquatic Organism Layer

Durability of Marine Concrete with Mineral Admixture and Marine Aquatic Organism Layer Durability of Marine Concrete with Mineral Admixture and Marine Aquatic Organism Layer Amry Dasar 1, Hidenori HAMADA 1, Yasutaka SAGAWA 1 and Takanori IKEDA 2 1 Kyushu University, Japan 2 Maeda Corporation,

More information

SPECIAL COMPOUND FOR RHEOPLASTIC AND ANTI-CORROSION SUPERCONCRETE WITH VERY HIGH DURABILITY

SPECIAL COMPOUND FOR RHEOPLASTIC AND ANTI-CORROSION SUPERCONCRETE WITH VERY HIGH DURABILITY BS 40 M6 MuCis mono SPECIAL COMPOUND FOR RHEOPLASTIC AND ANTI-CORROSION SUPERCONCRETE WITH VERY HIGH DURABILITY LE CE LE type: "expansive binder which allows the production of extremely fluid concrete

More information

Durability of Seawater Mixed Concrete with Different Replacement Ratio of BFS (Blast Furnace Slag) and FA (Fly Ash)

Durability of Seawater Mixed Concrete with Different Replacement Ratio of BFS (Blast Furnace Slag) and FA (Fly Ash) Journal of Civil Engineering and Architecture 10 (2016) 568-580 doi: 10.17265/1934-7359/2016.05.006 D DAVID PUBLISHING Durability of Seawater Mixed Concrete with Different Replacement Ratio of BFS (Blast

More information

S Pene- Krete (Spray- Applied)

S Pene- Krete (Spray- Applied) S- 1300 Pene- Krete (Spray- Applied) S- 1400 Pene- Krete Additive S- 1300 Pene- Krete Spray Applied S- 1300 Pene- Krete is a topically- applied densifier that is sprayed on to the surface. It provides

More information

A SIMPLIFIED METHOD TO ESTIMATE CORROSION RATES A NEW APPROACH BASED ON INVESTIGATIONS OF MACROCELLS Method to estimate corrosion rates

A SIMPLIFIED METHOD TO ESTIMATE CORROSION RATES A NEW APPROACH BASED ON INVESTIGATIONS OF MACROCELLS Method to estimate corrosion rates A SIMPLIFIED METHOD TO ESTIMATE CORROSION RATES A NEW APPROACH BASED ON INVESTIGATIONS OF MACROCELLS Method to estimate corrosion rates M. RAUPACH, Schiessl & Raupach, Consulting & Engineering, Aachen,

More information

Migrating Corrosion Inhibitors to Protect Reinforced Concrete Structures

Migrating Corrosion Inhibitors to Protect Reinforced Concrete Structures Paper No. 11011 Migrating Corrosion Inhibitors to Protect Reinforced Concrete Structures Behzad Bavarian, Akinbosede Oluwaseye, Lisa Reiner College of Engineering and Computer Science California State

More information

An Experimental Study on Corrosion Protection Performance of HPFRCCs with Fine Cracks

An Experimental Study on Corrosion Protection Performance of HPFRCCs with Fine Cracks An Experimental Study on Corrosion Protection Performance of HPFRCCs with Fine Cracks Le Anh Dung 1, Koichi Kobayashi 2, Keitetsu Rokugo 3 123 Department of Civil Engineering, Gifu University, Yanagido

More information

Florida Atlantic University, U.S.A, D = diffusion coefficient ( m / s ) eff

Florida Atlantic University, U.S.A, D = diffusion coefficient ( m / s ) eff Correlation of Chloride Diffusivity and Electrical Resistivity for Cracked Concrete D.V. Reddy, Ph.D., P.E., P.Eng, C. Eng (U.K.) 1, Stanley W. Merantus, B.S., and Khaled Sobhan, Ph.D. 1 1 Florida Atlantic

More information

Assessment of reinforcement corrosion in concrete façades

Assessment of reinforcement corrosion in concrete façades Assessment of reinforcement corrosion in concrete façades J. Lahdensivu & S. Varjonen Tampere University of Technology, Tampere, Finland ABSTRACT: Outdoor concrete structures are damaged by several different

More information

Reinforcing Wire in Solutions with Chloride and Cement

Reinforcing Wire in Solutions with Chloride and Cement Reinforcing Wire in Solutions with Chloride and Cement Protection of reinforcing steel from corrosion is usually attributed, in the first instance, to a protective layer which forms at the high ph provided

More information

TECHNOLOGY AND CONCEPTS TOTAL CORROSION MANAGEMENT SYSTEMS

TECHNOLOGY AND CONCEPTS TOTAL CORROSION MANAGEMENT SYSTEMS TOTAL CORROSION MANAGEMENT SYSTEMS CONTENT 2 Introduction 4 Sectors 5 in Reinforced Concrete Structures 6 Multi-functional Inhibitors 7 Vapour Phase Inhibitors 8 Embedded Galvanic and Impressed Current

More information

DIFFUSION OF Cl - IONS IN PARTIALLY DRY AND SATURATED CRACKED REINFORCED CONCRETE MEMBERS

DIFFUSION OF Cl - IONS IN PARTIALLY DRY AND SATURATED CRACKED REINFORCED CONCRETE MEMBERS - Technical paper - DIFFUSION OF Cl - IONS IN PARTIALLY DRY AND SATURATED CRACKED REINFORCED CONCRETE MEMBERS Pa Pa WIN* 1, Atsuhiko MACHIDA*, Daisuke MORI* 3 and Hansu PARK* ABSTRACT: Both of the ingression

More information

A NEW CORROSION TREATMENT FOR PRESTRESSED REBARS: THE DIRECT INJECTION OF A CORROSION INHIBITOR BY AN ULTRASONIC PUMP

A NEW CORROSION TREATMENT FOR PRESTRESSED REBARS: THE DIRECT INJECTION OF A CORROSION INHIBITOR BY AN ULTRASONIC PUMP A NEW CORROSION TREATMENT FOR PRESTRESSED REBARS: THE DIRECT INJECTION OF A CORROSION INHIBITOR BY AN ULTRASONIC PUMP E. Cailleux & V. Pollet CSTC-WTCB-BBRI Avenue Pierre Holoffe 21 B-1342 Limelette Belgium

More information

A REVIEW ON CORROSION: CAUSES AND PREVENTION

A REVIEW ON CORROSION: CAUSES AND PREVENTION A REVIEW ON CORROSION: CAUSES AND PREVENTION A Review on Corrosion: Causes and Prevention, Rajindervir Singh Sandhu, Dr. Jaspal Singh, Dr. Rajindervir Singh Sandhu 1, Dr. Jaspal Singh 2, Dr. Gurpreet Singh

More information

HILTI HY 150 REBAR DESIGN GUIDE

HILTI HY 150 REBAR DESIGN GUIDE HILTI HY 150 REBAR DESIGN GUIDE HILTI HY 150 REBAR DESIGN GUIDE 1 HY150 Rebar Dowelling using Limit States Concrete Design ( A23.3-94) The design method presented here was originally based on Eurocode

More information

INFLUENCE OF REBAR CORROSION BY CHLORIDE AND CARBONATION OF MORTAR SURFACE STRAIN

INFLUENCE OF REBAR CORROSION BY CHLORIDE AND CARBONATION OF MORTAR SURFACE STRAIN The 7th International Conference of Asian Concrete Federation SUSTAINABLE CONCRETE FOR NOW AND THE FUTURE 3 Oct 2 Nov, 216, Hanoi, Vietnam www.acf216.vn INFLUENCE OF REBAR CORROSION BY CHLORIDE AND CARBONATION

More information

FINAL REPORT. Gerardo G. Clemeña, Ph.D. Research Scientist

FINAL REPORT. Gerardo G. Clemeña, Ph.D. Research Scientist FINAL REPORT TESTING OF SELECTED METALLIC REINFORCING BARS FOR EXTENDING THE SERVICE LIFE OF FUTURE CONCRETE BRIDGES: SUMMARY OF CONCLUSIONS AND RECOMMENDATIONS Gerardo G. Clemeña, Ph.D. Research Scientist

More information

Ductile Iron Piles Corrosion Resistance

Ductile Iron Piles Corrosion Resistance Ductile Iron Piles Corrosion Resistance Ductile Iron Piles are often a preferred, cost-effective foundation support solution for a variety of projects particularly in urban settings. Similar to other types

More information

DURABILITY of CONCRETE STRUCTURES. 3 PART Prof. Dr. Halit YAZICI

DURABILITY of CONCRETE STRUCTURES. 3 PART Prof. Dr. Halit YAZICI DURABILITY of CONCRETE STRUCTURES 3 PART Prof. Dr. Halit YAZICI 1 CARBONATION & CORROSION 2 PROTECTION of STEEL FROM CORROSION BY CONCRETE PHYSICAL PROTECTION PREVENTION of PENETRATION of WATER & HARMFUL

More information

Corrosion of reinforcing steel in reinforced and prestressed concrete bridges

Corrosion of reinforcing steel in reinforced and prestressed concrete bridges Simulation of Electrochemical Processes II 287 Corrosion of reinforcing steel in reinforced and prestressed concrete bridges A.-K. M. Hussain & A. M. Rifai Civil Engineering Department, Engineering College,

More information

Injection Systems for Concrete Structures. Causes, Remedies and Repairs

Injection Systems for Concrete Structures. Causes, Remedies and Repairs Injection Systems for Concrete Structures Causes, Remedies and Repairs Overview - General introduction - Reason for cracks - Different types of cracks - Crack characteristics - Crack investigation and

More information

SECTION MAINTENANCE OF STONE ASSEMBLIES

SECTION MAINTENANCE OF STONE ASSEMBLIES SECTION 04 01 40 - MAINTENANCE OF STONE ASSEMBLIES PART 1 GENERAL 1.1 SUMMARY OF WORK A. Submit the following items in time to prevent delay of the work and to allow adequate time for review, do not order

More information

RAPID MACROCELL TESTS OF ASTM A775, A615, and A1035 REINFORCING BARS

RAPID MACROCELL TESTS OF ASTM A775, A615, and A1035 REINFORCING BARS RAPID MACROCELL TESTS OF ASTM A775, A615, and A1035 REINFORCING BARS By W. Joseph Sturgeon Matthew O Reilly David Darwin JoAnn Browning A Report on Research Sponsored by the EPOXY INTEREST GROUP OF THE

More information