Surge arrester 3EQ3. contents to others without expressed authorization is prohibited. Offenders will be held liable

Size: px
Start display at page:

Download "Surge arrester 3EQ3. contents to others without expressed authorization is prohibited. Offenders will be held liable"

Transcription

1 Surge arrester 3EQ3 Operating instructions Order-No.: a The copying, distribution and utilization of this document as well as the communication of its contents to others without expressed authorization is prohibited. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility model or ornamental design registration. Siemens Aktiengesellschaft All rights reserved. Siemens AG 03/2003

2 Contents Contents 2 Technical data 4 Description 6 Design 6 Mode of operation 7 Transportation and storage 7 Screwed joints 8 Montage 9 Place of installation 9 Installing of the arrester 9 standing installation 10 suspended installation 11 Earthing 12 Terminal 12 Exploded view 14 Maintenance 16 Disposal arrester and arrester accessories 16 2 Siemens AG 03/2003

3 The manufacturer of this surge arrester Siemens AG Power Transmission and Distribution Group High Voltage Division has introduced and applies a quality system in accordance with DIN ISO 9001 / EN Quality systems: Model for quality assurance This system was first demonstrated in 1989 to the DQS (German Association for the Certification of Quality Systems). The electrical testing laboratories and the materials technology laboratories of the manufacturer have been certified since 1992 by the German Accreditation Body in accordance with DIN EN If you require further copies of the operating instructions, please order them from the appropriate Siemens office, indicating the title and order number shown on the title page. Published by: In case of request: Siemens AG Telephone exchange +49 / 30 / PTD H 4 Sales department: +49 / 30 / D Berlin Fax: +49 / 30 / mailto:arrester@siemens.de Subject to change. Note The equipment covered by these instructions should be installed and serviced only by competent personnel familiar with good safety practices. This instruction is written for such personnel and is not intended as a substitute for adequate training an experience in safe procedures. This information is intended for the correct installation of this product. Siemens has no control over the condition of the network, which can be greatly affected by the installation of a product. It is the responsibility of the user to chose the appropriate method of installation. Under no circumstance is Siemens liable for any direct or indirect damage caused by the use or misuse of this product. Siemens AG 03/2003 3

4 The 3EQ3 surge arrester serves to protect the insulation of a system (or of one of its components) from undue stresses resulting from overvoltages. Technical data The surge arrester 3EQ3 can be used in AC networks with Um up to 800 kv (162/ Hz) and in DC applications up to a maximum of 550 kv; this arrester type is made up of one or more modules. a b c a) for AC and DC systems b) for AC-systems c) for DC-systems Fig. 1 Example for arresters consisting of 1 and 2 modular units, standing installation It is suitable for both standing [Fig. 1] or suspended [Fig. 2] installation. 4 Siemens AG 03/2003

5 a b c a) for AC and DC systems b) for AC-systems c) for DC-systems Fig. 2 Examples for arresters consisting of 1 and 2 modular units, suspended installation The surge arrester meets the following standards as for as applicable: Standard IEC , Ed. 1.2, ANSI C Classification 20 ka Station Document CIGRE 33/14-86 (WG-05) The rating plate [Fig. 3] will be found on the lowest flange (in some cases this has a special design in accordance with customer requirements). Siemens AG 03/2003 5

6 1 Order number 6 Pressure relief class 2 Rated voltage 7 Year of manufacture 3 Continuous voltage 8 Works serial no. 4 Rated discharge current 9 Module no. of arrester and additional information 5 Line discharge class Fig. 3 Rating plate In the case of arresters in several sections, each module will also be provided with a module plate [Fig. 4]: 1 Order number 3 Year of manufacture 2 Rated voltage 4 Module no. Fig. 4 Module plate Description Design The active components of the arrester are metal oxide resistors. They are arranged in one or more parallel columns and accommodated in a hermetically sealed composite plastic housing 1 (tube made of glass-fibre-reinforced plastic with silicon sheds). The housing basically consists of two components: A glass-fibre-reinforced plastic tube means that high mechanical loads can be absorbed not only in normal operation but also in the case of seismic stresses, for example. In the event of overloading of an arrester no shattering will occur. The screening made of silicone rubber due to its hydrophobic properties keeps electrical discharges on the surface of the housing to a low level and thereby ensures particularly satisfactory operating properties even when the housing is dirty or contaminated. The flanges with an integrated pressure relief device are made of a light metal alloy suitable for outdoor use and are bonded to the composite plastic housing. An effective seal is assured thanks to ultraviolet and ozone-resistant seals and non-corroding metal diaphragms. Each module is equipped at both ends with pressure relief diaphragms and gas diversion nozzles. In the case of an overload these pressure relief diaphragms will already open at a pressure which is a fraction of the pressure resistance of the composite plastic housing. The shape of the gas diversion nozzles causes the gas streams then escaping to be directed towards each other, thus allowing the arc to continue burning outside the porcelain housing until the time when the line is switched out. The arresters are, where necessary, equipped with control fittings and / or shields. 6 Siemens AG 03/2003

7 Mode of operation Metal oxide resistors are markedly non-linear - in other words, they have a strongly curved currentvoltage characteristic, which means that with the continuous voltage obtaining under normal circumstances only the so-called leakage current of just a few milliamps will be flowing. In the case of overvoltages due to lightning or to switching operations, the resistors become conductive (ohm range) thereby allowing a discharge current to flow to ground and the overvoltage to be reduced to the value of the voltage drop at the arrester ( discharge voltage ). Here the discharge currents may range up to 2 ka in the case of switching surges and ka in the case of lightning surges. 1 Insulator 2 Flange with gas diverter 3 Seal 4 Pressure-relief diaphragm 5 Compression spring 6 Non-linear metal-oxide resistors Fig. 5 Cross section of a unit with multi-column MO resistor insert Transportation and storage The modules of the surge arrester are packed in boxes or crates in the factory in accordance not only with the stresses and climatic conditions they will encounter during shipping. but also with the requirements of the customer. The packaging will have the appropriate transportation and storage labelling as well as instructions on proper handling. The consignment should be inspected immediately after receipt for signs of damage. If damage is found the carrier should be informed without delay. Loose parts packed with the consignment should be checked against the dispatch note to make sure none is missing. This means that all shipping containers will need to be opened. If the items are to be stored for extended periods, we recommend you leave the modules and accessories in their shipping containers. All of the screws, terminals and supplementary equipment (tell-tale spark gap, surge counter) required for assembly and installation are supplied in an accessory pack. Siemens AG 03/2003 7

8 Note: To avoid damaging the insulators, do not remove the assembly and shipping protector until assembly and installation has been completed. Screwed joints For mounting the arrester use only the bolts supplied. Grease the bolt threads with Molykote Longterm 2 plus. Attention Unchecked tightening can result in damage to or loosing of bolt joints Use torque wrench for assembly. Necessary torque for screwed joints: M 8: 18 ± 2 Nm 13 ± 1.5 ft lb M 10: 35 ± 5 Nm 25 ± 4 ft lb M 12: 60 ± 5 Nm 43 ± 4 ft lb M 16: 90 ± 10 Nm 65 ± 7 ft lb M 20: 105 ± 10 Nm 75 ± 7 ft lb 8 Siemens AG 03/2003

9 Montage Important note: Note the following before installing Warning Before any work starts: switch off and isolate secure against reclosing verify that equipment is dead earth and short circuit the equipment cover or fence off nearby live parts Death, severe injury and considerable damage to property and environmental damage may result if the safety instructions are not followed. Confirm that these safety measures have been carried out. Place of installation The range of protection offered by the arresters is restricted, which is why the surge arrester should be installed as close as possible to that part of the system being protected. The distance between grounded or live components and adjacent arresters or their control components should be selected on the basis of the relevant regulations. Important If at all possible, the expulsion aperture should not point towards any other part of the installation, in order to prevent damage caused by hot gases blowing out. The arresters must be installed or suspended vertically. If they need to be installed in a non-vertical position, you should first contact the manufacturer. Installing of the arrester Attention Danger of damage to the interior of the arrester The arrows on the top flange of the arrester must always point upwards. Do not lean a ladder against the surge arrester. The contact faces of the flanges of the arresters must be cleaned with a steel brush, if necessary. With arresters consisting of several units the units must be placed one on top of the other in the sequence of their numbers [Fig. 6]. The unit with the highest number is at the top. Siemens AG 03/2003 9

10 1 lower unit 2 upper unit 3 Rating plate for unit 4 Plate (2x) Fig. 6 Surge arrester units Attention Danger of damage to the interior of the arrester The plates [Fig. 6/4] must not be removed during installation. standing installation The bottom arrester unit can be mounted with 4 lag bolts on a concrete foundation or on a steel construction [Fig. 7] [Exploded view] with 4 M20 bolts. If requested by the customer and approved by the manufacturer, the arrester can also be fastened by means of M16 bolts. The necessary adapter (reducer) bushes are then included in the scope of supply. In both cases do not remove the insulating tube from the bolt [2/Fig. 7]. Before fitting the bolt, ensure that the insulating tube is in perfect condition. Likewise if requested by the customer the arrester can be supplied with an adapter plate [7/Fig. 7] with mounting dimensions of 310 mm x 310 mm. In this case, only the adapter plate with the factory-fitted lower arrester module need be fitted with four M20 bolts to the point provided. The bottom arrester unit must be horizontal (check with a spirit level). If necessary use shims for adjustment. Note Shim plates between the individual arrester units are not allowed. 10 Siemens AG 03/2003

11 1 Bolt M20 x 140 (if requested: M16 with adapter (reducer) bushes) 2 Insulating tube 3 bottom arrester unit 4 Cover plate 5 Insulating tube 6 Earthing terminal 7 Adapter plate 310 x 310 (Possibility) x Shim plates (if necessary) Fig. 7 Erecting of the bottom arrester unit The upper arrester units must be placed on the bottom units by means of appropriate lifting gear (crane, tackle) comprising slings and lifting lugs. Put the comprising slings around the flanges [Fig. 8]. Attention Danger of damage to the interior of the arrester The comprising slings must not put around the silicon coatings. 1 High voltage terminal 2 Flange a Transport packing Fig. 8 Lifting gear Before the top unit is located in place, it is advisable to fit the outer grading ring struts and the terminal plate to the upper flange. suspended installation The cover plate [4/Fig. 7] and the earthing terminal [6/Fig. 7] may have to be exchanged together with their associated bolts and insulating parts to make it into a hanging version [Fig. 1] [Fig. 2] [Exploded view]. In other respects, the arrester must be installed at site in accordance with local contitions. Siemens AG 03/

12 Earthing To ensure safe, reliable function of the arrester and optimal protection, earthing must be effective. So as not to reduce the protection level of the arrester, the earthing connection should be as short and straight as possible (no more than 2 m long). Take account of the minimum cross-section of the conductor. If operation of the surge arrester is checked by means of a telltale spark gap (3EX6040) and/or a surge counter (3EX5...) or another device, the connection between the arrester and the earthing terminal of the checking device should not exceed 2 m. If this distance is any longer, a separate sensing device and counter must be used. The connection must be made to the earthing terminal [6/Fig. 7]. Terminal Attention High-voltage connections with tube conductors should be flexible in order to prevent exertion of any inadmissible mechanical forces on the surge arrester. The high-voltage terminal is made at the top flange. Fig. 9 Bolt terminal Fig. 10 DIN Flat terminal 12 Siemens AG 03/2003

13 Fig. 11 NEMA-Flat terminal Pay attention to the electro-chemical compatibility of the materials utilized. Finally remove the protective packing for installation/transport. Siemens AG 03/

14 Exploded view Item Qty. Designation 1 4 Screw M16 x 90 1a 4 Screw M16 x Washer 17 4 Reducing socketn 4 Nut M Terminal plate 2a 0-1 Bolt terminal 2b 0-1 Flat terminal Strut Grading ring Screw M10 x Washer 10,5 0-8 Nut M Polymeric composite housing Screw M16 x Reducing socket 0-8 Washer Nut M Flange Metal plate 10 4 Screw M20 x Washer 21 4 Insulating tube 8 Insulating socket 4 Nut M20 10a 4 Screw M20 x Washer 21 4 Insulating tube 8 Insulating socket 11 1 Platte 12 1 Adapter plate 13 1 Earthing terminal 1 Screw M12 x 30 2 Washer 17 1 Nut M Rating plate Rating plate for arrester unit Corona ring 14 Siemens AG 03/2003

15 Siemens AG 03/

16 Maintenance Warning Before any work starts: switch off and isolate secure against reclosing verify that equipment is dead earth and short circuit the equipment cover or fence off nearby live parts Death, severe injury and considerable damage to property and environmental damage may result if the safety instructions are not followed. Confirm that these safety measures have been carried out. For technical reasons the silicone sheds do not need cleaning. Should they nonetheless be cleaned, only use clear or soapy water and a soft cloth or sponge. Important Do not use solvents or abrasive or scratching materials. Regular maintenance of the arresters is not necessary. The only monitoring required is to: Read the operations counter Check the tell-tale spark gap Check the arrester for any overloads (blackening or traces of burning at the blow-out aperture of the flange). In such a case you will need to replace the arrester Disposal arrester and arrester accessories Surge arresters and the accessories are an environmentally compatible product. In disposal, priority must be given to reuse of the materials. Environmentally acceptable disposal of the surge arresters and the accessories is possible in line with current legislation. The following materials have been used to make up the device: Steel, copper, aluminium, PTFE, cast resin or cast-resin-impregnated fabric, glass-fibre-reinforced plastics, polyurethane, rubbers for sealing, ceramics, electronic components and silicon rubber (VMQ), ceramics (porcelain, metal oxide). The device can be recycled as mixed scrap, or, if it is dismantled as far as possible, in a more environmentally acceptable way as sorted scrap with a mixed-scrap residual portion. The arrester resistors of metal oxide (MO) should be disposed of as industrial waste similar to domestic garbage (not as building rubble). In as-supplied-by-siemens state, the device incorporates no hazardous substances in the sense of the pertinent regulations in Germany. If the device is to be operated outside Germany, the locally applicable laws and regulations must be followed. Local customer support offices will be able to answer any questions concerning disposal. 16 Siemens AG 03/2003

Surge arrester 3EB4. with polymeric composite housing for operating aboard traction units

Surge arrester 3EB4. with polymeric composite housing for operating aboard traction units Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders

More information

Surge arrester 3EB1. with polymeric composite housing for operating aboard traction units

Surge arrester 3EB1. with polymeric composite housing for operating aboard traction units Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders

More information

Design features - Polymer-housed arresters, PEXLIM

Design features - Polymer-housed arresters, PEXLIM features - Polymer-housed arresters, PEXLIM PEXLIM arresters, using the same ZnO blocks as the EXLIM arresters, match their electrical performance. Silicone as outer insulation material has been used for

More information

ENGINEERING SPECIFICATION EE SPEC

ENGINEERING SPECIFICATION EE SPEC /. Company Directive ENGINEERING SPECIFICATION EE SPEC : 84/1 Relating to Surge Arresters EE SPEC : 84/1 20 December 2013-1 of 7 - IMPLEMENTATION PLAN Introduction This document defines the surge arresters

More information

Manufacturing and Application of Cage Design High Voltage Metal Oxide Surge Arresters

Manufacturing and Application of Cage Design High Voltage Metal Oxide Surge Arresters Manufacturing and Application of Cage Design High Voltage Metal Oxide Surge Arresters K. Steinfeld, B. Kruska and W. Welsch Siemens Surge Arresters and Limiters, Berlin, Germany Abstract: Metal oxide surge

More information

660 Volts 630 & 800AMP

660 Volts 630 & 800AMP Ergon Energy Corporation Limited Technical Specification for Switch- Disconnectors and Fuse-Switch- Disconnectors 660 Volts 630 & 800AMP ETS-06-02-01 Check this is the latest Process Zone version before

More information

Operating Instructions

Operating Instructions Operating Instructions A-2600 SERIES AWWA SWING CHECK VALVE 500 West Eldorado Street Decatur, Illinois 62522 www.muellercompany.com! WARNING! 1. Read and follow all pertinent instructions carefully. Proper

More information

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH SPECIFICATIONS FOR LOAD BREAK SWITCH This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE CODES

More information

Technical Specification for LV ABC Fuse Switch Disconnectors

Technical Specification for LV ABC Fuse Switch Disconnectors Ergon Energy Corporation Limited Technical Specification for LV ABC Fuse ETS-06-02-02 Check this is the latest Process Zone version before use. Specification ETS 06-02-02 Ver 3 Contents 1. Purpose and

More information

TABLE OF CONTENTS. FOREWORD... Error! Bookmark not defined. INTRODUCTION SCOPE NORMATIVE REFERENCES DRAWING...4

TABLE OF CONTENTS. FOREWORD... Error! Bookmark not defined. INTRODUCTION SCOPE NORMATIVE REFERENCES DRAWING...4 TITLE SPECIFICATION FOR FREE- STANDING 11 DATE: AUGUST 2006 PAGE: 1 OF 15 TABLE OF CONTENTS Page FOREWORD... Error! Bookmark not defined. INTRODUCTION...3 1 SCOPE...3 2 NORMATIVE S...3 3 DRAWING...4 4

More information

KEEP FOR FUTURE REFERENCE MRT FORKLIFT ADAPTER READ ALL INSTRUCTIONS AND WARNINGS BEFORE USING THIS PRODUCT

KEEP FOR FUTURE REFERENCE MRT FORKLIFT ADAPTER READ ALL INSTRUCTIONS AND WARNINGS BEFORE USING THIS PRODUCT KEEP FOR FUTURE REFERENCE P.O. Box 368 908 West Main Laurel, MT USA 59044 phone 800-548-7341 phone 406-628-8231 fax 406-628-8354 INSTRUCTIONS International Version STOCK NUMBER: 95722 MRT FORKLIFT ADAPTER

More information

Ground Fault Protection. Medium Voltage Artificial Neutrals

Ground Fault Protection. Medium Voltage Artificial Neutrals Ground Fault Protection Medium Voltage Artificial Neutrals Installation and Maintenance Instruction Manual 7615 Kimbel Street, Mississauga, Ontario Canada L5S 1A8 Tel: (905)673-1553 Fax: (905)673-8472

More information

SECTION VIBRATION CONTROLS FOR PLUMBING PIPING AND EQUIPMENT

SECTION VIBRATION CONTROLS FOR PLUMBING PIPING AND EQUIPMENT Page 220548-1 SECTION 220548 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS SECTION 260548 - VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section includes: 1. Isolation pads. 2. Spring isolators. 3. Restrained spring isolators. 4. Channel

More information

Preparation and Installation of the FA, FAV, and FAS Type Rupture Discs in Forward Acting Insert, Full Bolted, and Union Type Holders

Preparation and Installation of the FA, FAV, and FAS Type Rupture Discs in Forward Acting Insert, Full Bolted, and Union Type Holders GEP-6050 Rev. F 23777 Ref. I.D.: 8681 Preparation and Installation of the FA, FAV, and FAS Type Rupture Discs in Forward Acting Insert, Full Bolted, and Union Type Holders WARNING USER SHOULD READ AND

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 22 0548 - PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SPECIFICATIONS - DETAILED PROVISIONS Section Stainless Steel Sluice Gates C O N T E N T S

SPECIFICATIONS - DETAILED PROVISIONS Section Stainless Steel Sluice Gates C O N T E N T S SPECIFICATIONS - DETAILED PROVISIONS Section 11294 - Stainless Steel Sluice Gates C O N T E N T S PART 1 - GENERAL... 1 1.01 SUMMARY... 1 1.02 REFERENCES... 1 1.03 DEFINITIONS... 1 1.04 DESIGN REQUIREMENTS...

More information

Conergy SolarFamulus II

Conergy SolarFamulus II Conergy SolarFamulus II Installation manual www.conergy.com Table of Contents Table of Contents SolarFamulus II for universal use on flat roofs 1 Introduction 1 1.1 Short description 1 1.2 Intended use

More information

SECTION ENCLOSED BUS ASSEMBLIES

SECTION ENCLOSED BUS ASSEMBLIES SECTION 262500 ENCLOSED BUS ASSEMBLIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Technical Specification for Helical Fittings for Overhead Power Lines

Technical Specification for Helical Fittings for Overhead Power Lines Ergon Energy Corporation Limited Technical Specification for Helical Fittings for Overhead Power Lines ETS01-09-03 Specification ETS01-09-03 Ver 3 Contents 1. Purpose and Scope... 4 2. References... 4

More information

NPS/001/008 Technical Specification for Gapless Metal Oxide Surge Arresters

NPS/001/008 Technical Specification for Gapless Metal Oxide Surge Arresters Version:- 5.0 Date of Issue:- October 2017 Page 1 of 18 NPS/001/008 Technical Specification for Gapless Metal Oxide Surge Arresters 1. Purpose The purpose of this document is to detail the technical requirements

More information

9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA

9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA 9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA Technical specification for 9KV/18KV 5KA Metal oxide Lightning Arrestors without Gap. ----------------------------------------------------------------------------------------------------------------

More information

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008 Revisions Notes Changed note Date 1 (A) Changed template 09 / 07 / 2008 2 Changed template. Clause 12.5.4.1 hot-rolled steel added. Clause 12.5.4.2, 12.5.2.4, 12.5.3.4, 12.5.4.4, 12.5.5.4, 12.5.6.4, 12.5.7.4

More information

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

Student Services & Classroom Addition SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS

Student Services & Classroom Addition SECTION VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS SECTION 26 05 48 - VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section includes: 1. Isolation pads. 2. Spring isolators. 3. Restrained spring isolators. 4. Channel

More information

KEEP FOR FUTURE REFERENCE FORKLIFT ADAPTER FOR MRTA6 AND MRTA8 LIFTERS READ ALL INSTRUCTIONS AND WARNINGS BEFORE USING THIS PRODUCT

KEEP FOR FUTURE REFERENCE FORKLIFT ADAPTER FOR MRTA6 AND MRTA8 LIFTERS READ ALL INSTRUCTIONS AND WARNINGS BEFORE USING THIS PRODUCT KEEP FOR FUTURE REFERENCE P.O. Box 368 908 West Main Laurel, MT USA 59044 phone 800-548-7341 phone 406-628-8231 fax 406-628-8354 INSTRUCTIONS International Version STOCK NUMBER: 95457 FORKLIFT ADAPTER

More information

Z5054 Ci60/Ci90 Flying adapter Mounting instructions

Z5054 Ci60/Ci90 Flying adapter Mounting instructions Z5054 Ci60/Ci90 Flying adapter Mounting instructions Z5054 Ci60/Ci90 Flying adapter References in the manual CAUTION! IMPORTANT! Symbols on the equipment This refers to a potentially dangerous situation

More information

INSTRUCTIONS FOR ASSEMBLING NEBS FLOODED RACKS

INSTRUCTIONS FOR ASSEMBLING NEBS FLOODED RACKS INSTRUCTIONS FOR ASSEMBLING NEBS FLOODED RACKS Publication No. US-NEBS-IM-003 September 2013 INSTRUCTIONS for ASSEMBLING NEBS FLOODED RACKS Read all instructions carefully and observe all warnings before

More information

Z5028 E3/Ci80 Horizontal bracket Mounting instructions

Z5028 E3/Ci80 Horizontal bracket Mounting instructions Z5028 E3/Ci80 Horizontal bracket Mounting instructions Z5028 E3/Ci80 Horizontal bracket References in the manual CAUTION! IMPORTANT! Symbols on the equipment This refers to a potentially dangerous situation

More information

1 29SEP03 ALL General update with miscellaneous changes in entire document.

1 29SEP03 ALL General update with miscellaneous changes in entire document. REVISION RECORD SECTION 16461 Dry-Type Transformers (600 V and Less) REV DATE PAGE PARA NO. DESCRIPTION APPROVED BY 28SEP01 ALL Initial issue. 1 29SEP03 ALL General update with miscellaneous changes in

More information

2016 V1 SERAPHIM ECLIPSE PHOTOVOLTAIC MODULE JIANGSU SERAPHIM PHOTOVOLTAIC SYSTEM CO. LTD. ADDRESS: JIANGSU CITY OF CHANGZHOU PROVINCE WANG ZHEN HENG

2016 V1 SERAPHIM ECLIPSE PHOTOVOLTAIC MODULE JIANGSU SERAPHIM PHOTOVOLTAIC SYSTEM CO. LTD. ADDRESS: JIANGSU CITY OF CHANGZHOU PROVINCE WANG ZHEN HENG 016 V1 SERAPHIM ECLIPSE JIANGSU SERAPHIM PHOTOVOLTAIC SYSTEM CO. LTD. ADDRESS: JIANGSU CITY OF CHANGZHOU PROVINCE WANG ZHEN HENG ROAD NO. 1-. TELEPHONE: +86-519-8877608 FAX: +86-519-88786181 MAILBOX: info@seraphim-energy.com

More information

What to Look for in a Good Quality Arrester

What to Look for in a Good Quality Arrester All good quality arresters have much in common. This first in a series of articles, sponsored by NEMA Surge Arrester Section members, covers what to look for in that quality arrester. Introduction We've

More information

This guide can be used to prepare a specification for incorporating wall bracket jib cranes into a competitively bid construction project.

This guide can be used to prepare a specification for incorporating wall bracket jib cranes into a competitively bid construction project. SECTION 14654 WALL BRACKET JIB CRANE ***** Gorbel, Inc. manufacturers a broad range of material handling cranes including monorail, bridge, gantry, and jib cranes. Numerous work station and industrial

More information

SECTION VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND EQUIPMENT

SECTION VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND EQUIPMENT SECTION 230548 - VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

Industrial flue gas probes. Instruction manual

Industrial flue gas probes. Instruction manual Industrial flue gas probes Instruction manual 2 1 Contents 1 Contents 1 Contents... 3 2 Safety and the environment... 4 2.1. About this document... 4 2.2. Ensure safety... 4 2.3. Protecting the environment...

More information

POLYMER HOUSED SURGE ARRESTORS

POLYMER HOUSED SURGE ARRESTORS POLYMER HOUSED SURGE ARRESTORS March 2015 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091.

More information

SPECIFICATIONS FOR Gas-to-Cable termination

SPECIFICATIONS FOR Gas-to-Cable termination Product GSM-145 1.0 APPLICATION: Gas-to-cable termination is a part of high voltage gas insulated indoor switchgear equipment. The component is intended for a high voltage system of 132 kv (AC), 50 Hz.

More information

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466

BUSWAY LOW VOLTAGE (POW-R-WAY III) SECTION SECTION 16466 BUSWAY LOW VOLTAGE (POW-R-WAY III) PART 1 GENERAL 1.01 1.02 SCOPE The Contractor shall furnish and install the busway system including all necessary fittings, hangers and accessories as specified herein

More information

KRIWAN Wind Sensors. Operating Instructions Accessories and Application Information

KRIWAN Wind Sensors. Operating Instructions Accessories and Application Information KRIWAN Wind Sensors Operating Instructions Accessories and Application Information Contents Contents General information... 4 Manufacturer...4 Storage information...4 Supplementary documents...4 List of

More information

ON-ROOF ATTACHMENT FLAT COLLECTOR HELIOSTAR

ON-ROOF ATTACHMENT FLAT COLLECTOR HELIOSTAR ON-ROOF ATTACHMENT FLAT COLLECTOR HELIOSTAR INSTALLATION INSTRUCTIONS ENERGY AND SANITARY SYSTEMS Installation requirements Generel requirements The on-roof attachment set is capable for installation of

More information

SECTION to 5000 AMPERE PLUG-IN AND FEEDER BUSWAYS - SPECTRA. A. Low-Voltage Plug-in Busway to 5000 ampere, 600 VAC

SECTION to 5000 AMPERE PLUG-IN AND FEEDER BUSWAYS - SPECTRA. A. Low-Voltage Plug-in Busway to 5000 ampere, 600 VAC PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Low-Voltage Plug-in Busway - 225 to 5000 ampere, 600 VAC 1.02 RELATED

More information

Electrical containment penetrations 3 ROUTINE TESTING (PRODUCTION TESTING)

Electrical containment penetrations 3 ROUTINE TESTING (PRODUCTION TESTING) Page 1 (6) EXAMINATION PROCEDURE Electrical containment penetrations Document Issue Date KBE EP-146 3 (E) 2011-06-15 Supersedes KBE EP-146 Issue 2 (E) 1 SCOPE This Examination Procedure is applicable to

More information

A. Section includes busway and fittings including plug-in units.

A. Section includes busway and fittings including plug-in units. SECTION 26 25 00 ENCLOSED BUS ASSEMBLIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes busway and fittings including plug-in units. 1.2 REFERENCES A. Institute of Electrical and Electronics Engineers:

More information

Z5010 (Version 2) TV spigot with fixing plate Mounting instructions

Z5010 (Version 2) TV spigot with fixing plate Mounting instructions Z5010 (Version 2) TV spigot with fixing plate Mounting instructions Z5010 (Version 2) TV spigot with fixing plate References in the manual CAUTION! IMPORTANT! Symbols on the equipment This refers to a

More information

SECTION VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT

SECTION VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT Page 230548-1 SECTION 230548 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

PMA 31-G. English. Printed: Doc-Nr: PUB / / 000 / 00

PMA 31-G. English. Printed: Doc-Nr: PUB / / 000 / 00 PMA 31-G English 1 Information about the documentation 1.1 About this documentation Read this documentation before initial operation or use. This is a prerequisite for safe, trouble-free handling and

More information

SECTION COLD-FORMED METAL TRUSSES

SECTION COLD-FORMED METAL TRUSSES SECTION 054400 COLD-FORMED METAL TRUSSES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Subject: Guidance on Corrosion Assessment of Ex Equipment

Subject: Guidance on Corrosion Assessment of Ex Equipment 1. Introduction Maintaining the integrity of Ex certified electrical equipment is a key barrier against Major Accident Hazards in the oil and gas industry. The integrity must be maintained to ensure that

More information

New designed XLPE-insulated cables substituting paper-insulated pipe type cables

New designed XLPE-insulated cables substituting paper-insulated pipe type cables MODERN CABLE SYSTEMS IN STEEL PIPES New designed XLPE-insulated cables substituting paper-insulated pipe type cables Volker AUE, Nexans Deutschland Industries, Germany, Volker.Aue@nexans.com Wilfried ROSEBROCK,

More information

A. This Section includes the following types of dry-type transformers rated 600 V and less, with capacities up to 1000 kva:

A. This Section includes the following types of dry-type transformers rated 600 V and less, with capacities up to 1000 kva: SECTION 16461 - LOW-VOLTAGE TRANSFORMERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Design of MO Surge Arresters with Polymeric Housings

Design of MO Surge Arresters with Polymeric Housings Design of MO Surge Arresters with Polymeric Housings Kai Steinfeld (Director R&D Surge Arresters) High Voltage Surge Arrester s Voltages in Electric Power Systems Voltage Limiting Effect of Surge Arresters

More information

SECTION MANUAL FOUR FOLD DOORS MODEL 38 DECORATIVE PANEL DESIGN

SECTION MANUAL FOUR FOLD DOORS MODEL 38 DECORATIVE PANEL DESIGN SECTION 08350 MANUAL FOUR FOLD DOORS MODEL 38 DECORATIVE PANEL DESIGN PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

East Central College HANSEN HALL LEVEL 300/400 RENOVATIONS CONSTRUCTION PACKAGE

East Central College HANSEN HALL LEVEL 300/400 RENOVATIONS CONSTRUCTION PACKAGE SECTION 220529 - HANGERS AND SUPPORTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Documentation. Transient voltage suppressor - AX2090- TS Version: Date:

Documentation. Transient voltage suppressor - AX2090- TS Version: Date: Documentation Version: Date: 1.0 12.01.2017 Table of content Table of content 1 Foreword... 4 1.1 Notes on the documentation... 4 1.2 Documentation issue status... 5 1.3 Appropriate use... 5 2 Safety...

More information

Operating Instructions

Operating Instructions Operating Instructions Series B37000 Hose Reels BB37118 L CB37118 L EB37118 L12D BB37122 L CB37122 L EB37122 L12D BB37128 L CB37128 L EB37128 L12D Dimensional Data C A B D Part # A B C D BB/CB37118 L 31

More information

INSTALLATION GUIDE. 4-Post Lift. Model United States. United Arab Emirates. Egypt.

INSTALLATION GUIDE. 4-Post Lift. Model United States. United Arab Emirates. Egypt. 4-Post Lift INSTALLATION GUIDE United States 17779 Main Street Suite C Irvine, CA 92614 USA Tel: +1(949) 333-3800 Fax: +1(949) 333-3804 United Arab Emirates Model 46614 P.O. Box 121971 Saif Zone A2-032

More information

MATERIAL SPECIFICATION FOR LUMINAIRE RAISING AND LOWERING EQUIPMENT

MATERIAL SPECIFICATION FOR LUMINAIRE RAISING AND LOWERING EQUIPMENT ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 2476 JANUARY 1990 MATERIAL SPECIFICATION FOR LUMINAIRE RAISING AND LOWERING EQUIPMENT 2476.01 SCOPE 2476.02 REFERENCES 2476.05 MATERIALS TABLE OF CONTENTS

More information

SECTION VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT

SECTION VIBRATION CONTROLS FOR HVAC PIPING AND EQUIPMENT SECTION 230548 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Elastomeric Isolation pads. 2. Elastomeric Isolation mounts. 3. [Freestanding] [Restrained] [Freestanding and restrained]

More information

POWER PINNER BENCH HAND WELDER 7250 OPERATOR S MANUAL

POWER PINNER BENCH HAND WELDER 7250 OPERATOR S MANUAL POWER PINNER BENCH HAND WELDER 7250 OPERATOR S MANUAL Copyright: November 20, 2018 Revised: Serial No. Gripnail Corporation An Employee Owned Company 97 Dexter Road East Providence, Rhode Island 02914-2045

More information

PRY-MOULD. High Voltage Accessories for Extruded Cables

PRY-MOULD. High Voltage Accessories for Extruded Cables PRY-MOULD High Voltage Accessories for Extruded Cables Linking the future As the worldwide leader in the cable industry, Prysmian Group believes in the effective, efficient and sustainable supply of energy

More information

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT SECTION 220529 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

15~35KV Termination Kit

15~35KV Termination Kit 15~35KV Termination Kit Luyon Corporation 21221 Western Ave., #210 Torrance, CA 90501, U.S.A. Advantages of Silicone Rubber Power Cable Accessories Feature of silicone rubber: Silicone rubber is a unique

More information

SPECIFICATION FOR FIBERGLASS REINFORCED PLASTIC CHEMICAL STORAGE TANKS

SPECIFICATION FOR FIBERGLASS REINFORCED PLASTIC CHEMICAL STORAGE TANKS The following specification for FRP Chemical Storage Tanks has been developed to assist the specifier and the buyer in detailing their own specification for equipment that meets the minimum design parameters

More information

SECTION ENCLOSED BUS ASSEMBLIES

SECTION ENCLOSED BUS ASSEMBLIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

ANSI/ ASME HST Performance Standard For Overhead Electric Wire Rope Hoists

ANSI/ ASME HST Performance Standard For Overhead Electric Wire Rope Hoists SECTION 412213- BRIDGE CRANES Part 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION HANGERS AND SUPPORTS PART 1 - GENERAL. A. Drawings and Division 1 Specification Sections, apply to this Section.

SECTION HANGERS AND SUPPORTS PART 1 - GENERAL. A. Drawings and Division 1 Specification Sections, apply to this Section. 1.01 RELATED DOCUMENTS SECTION 15060 HANGERS AND SUPPORTS PART 1 - GENERAL A. Drawings and Division 1 Specification Sections, apply to this Section. 1.02 SUMMARY A. This Section includes hangers and supports

More information

1. Telecommunications mounting elements. 2. Backboards. 3. Telecommunications equipment racks and cabinets. 4. Grounding.

1. Telecommunications mounting elements. 2. Backboards. 3. Telecommunications equipment racks and cabinets. 4. Grounding. ALLIANT ENERGY CENTER PAVILIONS Project No. 2013 027 SECTION 27 11 00 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

More about Fabric Expansion Joints (Functioning/Operating Principle) FUNCTION

More about Fabric Expansion Joints (Functioning/Operating Principle) FUNCTION More about Fabric Expansion Joints (Functioning/Operating Principle) FUNCTION Non-metallic Expansion Joints are flexible joints designed to provide stress relief in ducting systems by absorbing movement

More information

MASTERSPEC - SHORT FORM. B. See Division 5 Section "Metal Stairs" for steel tube railings associated with metal stairs.

MASTERSPEC - SHORT FORM. B. See Division 5 Section Metal Stairs for steel tube railings associated with metal stairs. SECTION 05721 - ORNAMENTAL RAILINGS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Glass supported railings. B. See Division 5 Section "Metal Stairs" for steel tube railings associated

More information

Vibranivo Mononivo. Series VN 4000 MN Series. Instruction manual

Vibranivo Mononivo. Series VN 4000 MN Series. Instruction manual Vibranivo Mononivo Series Series VN 4000 MN 4000 Instruction manual 010516 1 UWT GmbH Westendstraße 5 Tel.: +49 (0)831 57123-0 Internet:www.uwt.de D-87488 Betzigau Fax: +49 (0)831 76879 E-Mail: info@uwt.de

More information

Installation Instruction for DMEGC Photovoltaic Module

Installation Instruction for DMEGC Photovoltaic Module Content 1. PURPOSE... 1 1.1 GENERAL TERM... 1 2. SAFETY PRECAUTIONS FOR SOLAR PV SYSTEM INSTALLATION... 3 3. INSTALLATION CONDITION... 4 3.1 INSTALLATION LOCATION AND WORKING CONDITIONS... 4 3.2 SELECTION

More information

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS SECTION 26 05 29 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.1 DESCRIPTION A. Scope: 1. CONTRACTOR shall provide all labor, materials, equipment, and incidentals as shown, specified, and

More information

Transmission Silicone Insulators Line Post 69 kv to 230 kv

Transmission Silicone Insulators Line Post 69 kv to 230 kv K-LINE INSULATORS LIMITED Catalogue T-LP Transmission Silicone Insulators Line Post 69 kv to 230 kv ISO9001 SAI GLOBAL FILE No. 000117 Transmission Silicone Insulators Line Post Today transmission lines

More information

VAREC 3600B/3650B SERIES PRESSURE OR VACUUM RELIEF VALVES INSTRUCTION, OPERATION AND MAINTENANCE MANUAL

VAREC 3600B/3650B SERIES PRESSURE OR VACUUM RELIEF VALVES INSTRUCTION, OPERATION AND MAINTENANCE MANUAL Before installation these instructions must be fully read and understood 3600B 3650B DISCLAIMER OF WARRANTIES The contract between Varec Vapor Control Inc. and our customer states Varec Vapor Control Inc.

More information

Operating Instructions in compliance with Pressure Equipment Directive 2014/68/EU. FAS Welding and Solder Flange

Operating Instructions in compliance with Pressure Equipment Directive 2014/68/EU. FAS Welding and Solder Flange Operating Instructions in compliance with Pressure Equipment Directive 2014/68/EU FAS Welding and Solder Flange Please read these operating instructions carefully to ensure a safe operation and keep the

More information

37-SDMS-01 REV. 03 SPECIFICATIONS FOR

37-SDMS-01 REV. 03 SPECIFICATIONS FOR 37-SDMS-01 REV. 03 SPECIFICATIONS FOR LOW VOLTAGE MOLDED CASE CIRCUIT BREAKERS FOR SERVICE CONNECTIONS This specification is property of SEC and subject to change or modification without any notice CLAUSE

More information

INSTALLATION INSTRUCTIONS AS 2.1 CORRUGATED ETERNIT ROOF

INSTALLATION INSTRUCTIONS AS 2.1 CORRUGATED ETERNIT ROOF INSTALLATION INSTRUCTIONS AS 2.1 CORRUGATED ETERNIT ROOF ALUMERO GROUP YOUR BIG ADVANTAGE! + in-house consulting and design office + competent and reliable staff + aluminium mounting profiles and custom-drawn

More information

1.2 ACTION AND INFORMATIONAL SUBMITTALS.1 Provide submittals in accordance with Section Submittal Procedures.

1.2 ACTION AND INFORMATIONAL SUBMITTALS.1 Provide submittals in accordance with Section Submittal Procedures. BID OPPORTUNITY NO. 253-2011 PAGE 1 OF 7 PART 1 GENERAL 1.1 REFERENCES.1 American Society of Mechanical Engineers (ASME).1 ASME B31.1, Power Piping, B31.3 Process Piping, B31.9 Building Services Piping..2

More information

Fig. 1 - Standard Clevis Hanger

Fig. 1 - Standard Clevis Hanger Revision 10/24/2007 Fig. 1 - Standard Clevis Hanger Component of State of California OSHPD Approved Seismic Restraints System Size Range Size 1/2" thru 36" pipe. Function Recommended for the suspension

More information

Cutlass Fasteners, Inc. 83 Vermont Ave., Unit 6, Warwick, RI Tel: (401) Fax: (401) cutlass-studwelding.com

Cutlass Fasteners, Inc. 83 Vermont Ave., Unit 6, Warwick, RI Tel: (401) Fax: (401) cutlass-studwelding.com MODEL : A-58 ARC WELD GUN PART NO. : 602-378A SERIAL NO. : PLEASE READ THIS OPERATION AND MAINTENANCE MANUAL CAREFULLY BEFORE USING YOUR NEW CUTLASS STUD WELDER. COPYRIGHT CFI 2009 email: sales@ PAGE -

More information

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

SECTION HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT SECTION 220529 - HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The General Conditions, Special Conditions and Division 1 through Division 22 as set forth in

More information

ASSEMBLY INSTRUCTIONS for DATASAFE TM HX and HX FRONT TERMINAL UBC BATTERY RACKS

ASSEMBLY INSTRUCTIONS for DATASAFE TM HX and HX FRONT TERMINAL UBC BATTERY RACKS US-HXRACK-IM-002 ASSEMBLY INSTRUCTIONS for DATASAFE TM HX and HX FRONT TERMINAL UBC BATTERY RACKS Read all instructions carefully and observe all warnings before installation. See Installation, Operation

More information

Type II Environmental Declaration according ISO 14021:2001/A1:2011

Type II Environmental Declaration according ISO 14021:2001/A1:2011 Type II Environmental Declaration according ISO 14021:2001/A1:2011 Product: Hunter Douglas Panels Module 200-600mm Product code: 26005 Module 601-900mm Product code: 26025 Module 901-1200mm Product code:

More information

.1 ANSI/ASME B31.1, Power Piping, (SI Edition)..2 American Society for Testing and Materials (ASTM)

.1 ANSI/ASME B31.1, Power Piping, (SI Edition)..2 American Society for Testing and Materials (ASTM) Fitness Facility Addition Page 1 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 03300 - Cast-in-Place Concrete.2 Section 05121 - Structural Steel for Buildings.3 Section 05500 - Metal Fabrications 1.2 REFERENCES.1

More information

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY

SECTION GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 05 26 GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY SPEC WRITER NOTE: Delete // // if not applicable to project. Also delete any other item or paragraph

More information

Technical Specification for Live Line Tap Connectors

Technical Specification for Live Line Tap Connectors Ergon Energy Corporation Limited Technical Specification for Live Line Tap ETS-06-01-01 Check this is the latest Process Zone version before use. Specification ETS 06-01-01 Ver 1 Contents 1. Purpose and

More information

TOLCO Fire Protection Support Systems. Pipe Hangers Supports Seismic Bracing. UL Listed FM Approved for Fire Sprinkler Installations

TOLCO Fire Protection Support Systems. Pipe Hangers Supports Seismic Bracing. UL Listed FM Approved for Fire Sprinkler Installations TOLCO Fire Protection Support Systems Pipe Hangers Supports Seismic Bracing UL Listed FM Approved for Fire Sprinkler Installations Revision 12/06/2007 Catalog Forward This catalog has been created with

More information

2017 V1 SERAPHIM PHOTOVOLTAIC MODULE TUV VERSION B JIANGSU SERAPHIM PHOTOVOLTAIC SYSTEM CO. LTD.

2017 V1 SERAPHIM PHOTOVOLTAIC MODULE TUV VERSION B JIANGSU SERAPHIM PHOTOVOLTAIC SYSTEM CO. LTD. 017 V1 SERAPHIM PHOTOVOLTAIC MODULE TUV VERSION B JIANGSU SERAPHIM PHOTOVOLTAIC SYSTEM CO. LTD. ADDRESS: JIANGSU CITY OF CHANGZHOU PROVINCE WANG ZHEN HENG ROAD NO. 1-. TELEPHONE: +86-519-8877608 FAX: +86-519-88786181

More information

2019 V1 SERAPHIM DG PHOTOVOLTAIC MODULE JIANGSU SERAPHIM PHOTOVOLTAIC SYSTEM CO. LTD. ADDRESS: JIANGSU CITY OF CHANGZHOU PROVINCE WANG ZHEN HENG

2019 V1 SERAPHIM DG PHOTOVOLTAIC MODULE JIANGSU SERAPHIM PHOTOVOLTAIC SYSTEM CO. LTD. ADDRESS: JIANGSU CITY OF CHANGZHOU PROVINCE WANG ZHEN HENG 2019 V1 SERAPHIM DG PHOTOVOLTAIC MODULE JIANGSU SERAPHIM PHOTOVOLTAIC SYSTEM CO. LTD. ADDRESS: JIANGSU CITY OF CHANGZHOU PROVINCE WANG ZHEN HENG ROAD NO. 1-2. TELEPHONE: +86-519-88776028 FAX: +86-519-88786181

More information

SECTION OVERHEAD CONDUCTOR RAIL

SECTION OVERHEAD CONDUCTOR RAIL SECTION 34 23 06 OVERHEAD CONDUCTOR RAIL PART 1 - GENERAL 1.1 DESCRIPTION This Section describes and specifies the performance requirements to design, furnish, install, test, and place into satisfactory

More information

Stainless steel. 1.6 Stainless steel IP 69 K. Premium Panel, protection category IP 69K

Stainless steel. 1.6 Stainless steel IP 69 K. Premium Panel, protection category IP 69K T Premium Panel, protection category IP 69K IP 69 K.6 H H H Optionally with or without keyboard housing Resistant to high-pressure cleaning (protection category IP 69K). The seal lies between two surfaces

More information

Model: LoLander Series Truck Scale Model: LL FT Model: LL FT Installation, Set-Up and Operation Manual

Model: LoLander Series Truck Scale Model: LL FT Model: LL FT Installation, Set-Up and Operation Manual SCALE WORKS, INC. Model: LoLander Series Truck Scale Model: LL8035-10FT Model: LL8035-11FT Installation, Set-Up and Operation Manual Cambridge Scale Works, Inc. P.O. Box 670 Honey Brook, PA. 19344 (800)

More information

INSTALLATION MANUAL. All Types F Series Rev G

INSTALLATION MANUAL. All Types F Series Rev G INSTALLATION MANUAL All Types - 1570 F Series Page 1 of 16 TABLE OF CONTENTS DESCRIPTION PAGE GENERAL INFORMATION & ADVISORIES 2 PRODUCT INFORMATION 3 GET TO KNOW YOUR CBU 4 HARDWARE AND COMPONENTS 5 CONCRETE

More information

HELIOSTAR 252, 218 VERTICAL, FREE INSTALLATION

HELIOSTAR 252, 218 VERTICAL, FREE INSTALLATION HELIOSTAR 252, 218 VERTICAL, FREE INSTALLATION INSTRUCTION MANUAL ENERGY AND SANITARY SYSTEMS Installation requirements General requirements The free-standing installation set is to be used or installing

More information

Site Preparation... 2

Site Preparation... 2 TRUFIREWALLS INSTALLATION MANUAL This Installation Manual is intended to assist in the preparation and installation of TruFireWalls products manufactured by Oldcastle Enclosure Solutions. The TruFireWalls

More information

Aurora Genmounts Install LT Installation Manual

Aurora Genmounts Install LT Installation Manual Aurora Genmounts Install LT Installation Manual TABLE OF CONTENTS 1.0 INTRODUCTION 2.0 PRODUCT OVERVIEW 3.0 TECHNICAL SPECS 4.0 INSTALLER RESPONSIBILITY 5.0 SITE SELECTION 6.0 TOOLS REQUIRED 7.0 COMPONENT

More information

Cutlass Fasteners, Inc. 83 Vermont Ave., Unit 6, Warwick, RI Tel: (401) Fax: (401) cutlass-studwelding.com

Cutlass Fasteners, Inc. 83 Vermont Ave., Unit 6, Warwick, RI Tel: (401) Fax: (401) cutlass-studwelding.com MODEL : PHM-12 ARC WELD GUN PART NO. : PHM-12 (PHM-12-RS) SERIAL NO. : PLEASE READ THIS OPERATION AND MAINTENANCE MANUAL CAREFULLY BEFORE USING YOUR NEW CUTLASS STUD WELDER. COPYRIGHT CFI 2009 email: sales@

More information

SECTION ELECTRIC FOUR FOLD DOORS MODEL 46 FLAT SHEETED

SECTION ELECTRIC FOUR FOLD DOORS MODEL 46 FLAT SHEETED SECTION 08350 ELECTRIC FOUR FOLD DOORS MODEL 46 FLAT SHEETED PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information