Declaration of Performance

Size: px
Start display at page:

Download "Declaration of Performance"

Transcription

1 Product Unique identification code of the product type FK-EU Intended use Fire damper Manufacturer TROX GmbH Phone +49 (0) Fax +49 (0) Heinrich-Trox-Platz Neukirchen-Vluyn, Internet Germany TROX HESCO Schweiz AG Phone +41 (0) Fax +41 (0) Walderstrasse Rüti ZH Internet Switzerland System of assessment and verification of constancy of System 1 Harmonised standard Notified body/ies EN 15650:2010 The notified body IBS - carried out the initial inspection of the manufacturing plants and of the factory production control as well as the continuous surveillance, assessment and evaluation of factory production control according to System 1 of the Products Regulation and issued the certificate of constancy of : 1322-CPR-74135/ CPR-61977/01 Declared s Solid wall (partially with mineral wool) Installation kit E1/E2 Installation kit WA on the face of the wall Installation kit WV adjacent to the wall Page 1/7

2 Installation kit WE remote from the wall Solid wall Flexible ceiling joint Installation kit GM With and without reinforcing strips made of calcium silicate or mineral wool 20 mm Distance between casings 100 mm (and kit) d 80 mm EI 60 (v e i o) S d 75 mm Page 2/7

3 with sheet steel, used as a compartment wall, safety or to provide radiation protection with sheet steel, used as a compartment wall, safety or to provide radiation protection d 75 mm d 75 mm Flexible ceiling joint Installation kit GL Distance to load-bearing structural elements = 40 mm Page 3/7

4 (also timber panel s and timber frames) d 105 mm (also timber panel s and timber frames) d 105 mm (also timber panel s and timber frames) d 105 mm Half-timbered d 140 mm Half-timbered d 140 mm Half-timbered d 140 mm Page 4/7

5 Solid wood wall/clt wall d 95 mm Solid wood wall/clt wall d 95 mm Solid wood wall/clt wall d 95 mm Shaft wall (also steel support structure and facings) Cladding on one side d 90 mm 2 x 20 mm gypsum bonded or cement bonded panel materials, fibre-reinforced gypsum or fire-rated calcium silicate boards (also steel support structure and facings) Cladding on one side d 90 mm 2 x 12.5 mm with reinforcing board Gypsum bonded or cement bonded panel materials, fibre- reinforced gypsum or fire-rated calcium silicate boards (also steel support structure and facings) Cladding on one side d 90 mm 2 x 20 mm gypsum bonded or cement bonded panel materials Fibre-reinforced gypsum or fire-rated calcium silicate boards Shaft wall without metal support structure d 40 mm 2 x 20 mm gypsum bonded or cement bonded panel materials, fibre-reinforced gypsum or fire-rated calcium silicate boards Shaft wall without metal support structure d 40 mm 2 x 20 mm gypsum bonded or cement bonded panel materials, fibre-reinforced gypsum or fire-rated calcium silicate boards Solid ceiling slab Page 5/7

6 Solid ceiling slab EI120S (ho i o) S d 150 mm Hensomastik fire batt system EI 180 (h o i o) S Below the ceiling, with horizontal duct Installation kit WE remote from the ceiling Combined with wooden beam ceilings (glued laminated timber also) Combined with suspended ceiling systems (Cadolto system) Combined with solid wood ceilings Page 6/7

7 Declared s Essential characteristics Technical specification Nominal activation conditions/sensitivity Sensing element load-bearing capacity ISO :2001 Sensing element response temperature 72 C, 95 C Response delay/response time EN :2015 Closure time Operational reliability EN 15650:2010 Open and closing cycle, 50 cycles EN :2015 Durability of response delay ISO :2001 Sensing element response to temperature and load-bearing capacity Durability of operational reliability Testing of the open and closing cycle, 10,000 cycles BLF 230-T(N)-(ST) TR BLF 24-T(N)-(ST) TR BF230-T(N)-(ST) TR BF24-T(N)-(ST) TR BF24TL-T(N)-ST(-2) TR BFN 230-T(N)-(ST) TR BFN 24-T(N)-(ST) TR BFL 230-T(N)-(ST) TR EN 15650:2010 BFL 24-T(N)-(ST) TR ExMax-15-BF TR RedMax-15-BF TR GGA126.1E/T../GGA326.1E/T GRA126.1E/T../GRA326.1E/T GNA126.1E/T../GNA326.1E/T SFR 1.90 T SLC SFR 1.90 T SFR 2.90 T Protection against corrosion EN 15650:2010 Damper blade leakage EN 1751:2014 At least class 2 Damper casing leakage EN 1751:2014 At least class B The classification of the fire damper must not be higher than the classification of the wall or ceiling slab it is installed in. In this case the class of of the wall or ceiling slab applies also to the fire damper. The of the product identified above is in conformity with the set of declared s. This declaration of is issued, in accordance with regulation (EU) no. 305/2011, under the sole responsibility of the manufacturer identified above. Signed for and on behalf of TROX GmbH: Neukirchen-Vluyn, Jan Heymann Authorised Representative CE-marked products Page 7/7