1 UA2 Introduction to UA2 I Purpose of Enclosure Enclosures are used to protect personnel against accidental contact with enclosed electrical devices or connections and to protect the enclosed devices or connections against specified external conditions. They also serve as intermediate pulling and splicing points in a conduit system. II Design of Enclosures Enclosures are offered in different designs and construction to permit their use in various locations and areas. These are as follows: Non-hazardous Locations: Weatherproof boxes are so constructed as to be suitable for use outdoors under normal conditions. If it is necessary to prevent the entry of water under extreme conditions of weather, boxes listed as watertight or raintight are recommended. 2 Raintight boxes are so constructed as to exclude a beating rain. All boxes in this catalog which are designated as raintight have been so listed by Underwriters Laboratories, Inc. Watertight boxes (NEMA Type 4) are constructed to meet the requirements listed under "NEMA DATA" on Page UA. 4 Submersible Boxes are so constructed that they will exclude water when submerged under specified conditions of pressure and time. Dust-Tight Boxes are so constructed to meet the requirements listed on Page UA under "NEMA DATA". Hazardous Locations: Consult Section V for our complete line of Hazardous Location Enclosures. III Advantages of Cast Enclosures Cast metal enclosures have the advantage over formed (fabricated) sheet metal enclosures for the following reasons: A They are of one piece construction and do not have the disadvantages of spot welded seams usually found in formed sheet metal boxes. B They have greater mechanical strength, have thicker walls and are suitable for drilling and tapping at the factory or in the field. C They are corrosion resistant and can withstand more mechanical abuse. IV Comparison of Enclosures in Various Cast Metals CAST IRON BOXES will provide long life, are inherently corrosion resistant and have the lowest initial cost. CAST ALUMINUM BOXES are lightweight, non-rusting, non-sparking, and non-magnetic. They are subject to corrosion under certain alkalis conditions such as encasement in concrete unless provided with a suitable coating. CAST BRONZE BOXES (optional) will provide long life under adverse atmospheric conditions, are non-rusting, non-sparking and non-magnetic. V Finishes on Cast Enclosures CAST IRON - The hot-dip galvanized finish which is applied to all our cast iron boxes will conform to ASTM Designation A-, Class A and NEMA requirements for rustresistance. Other protective finishes such as various types of paints or plastic coatings can be supplied. CAST ALUMINUM - supplemental finishes are not normally required on cast aluminum enclosures. Special finishes such as epoxy coating, anodizing or plastic coating to meet specific environmental conditions can be applied. CAST BRONZE is inherently corrosion resistant. Supplemental finishes are usually not required on cast bronze. VI Hardware Used on Cast Enclosures CAST IRON BOXES are furnished with Stainless Steel screws. Silicon bronze screws are available on most enclosures. CAST ALUMINUM BOXES are furnished with stainless steel screws. CAST BRONZE BOXES are furnished with either brass or silicon bronze screws. VII Specification of Extras on Cast Enclosures The type of holes to be provided for the entrance of conduit into the enclosure are defined under "Instructions for Ordering Boxes" on Page UA4. VIII Specification of Extras on Cast Enclosures The "Standard Construction" of each type of enclosure is shown on each listing. The extras which are available and must be specified are shown under "Additional Cost Items" on Pages UA6, UA. IX Delivery Schedules Cast enclosures are normally produced to order. However, faster deliveries can be provided for some of the more commonly specified styles and sizes. Contact your Local Representative for delivery information and assistance to expedite shipments of the material required on your order.

2 UA UA Cast & Cast Aluminum Boxes NEMA Data Our cast junction boxes are designed, constructed and tested to comply with NEMA standards. The following chart has been prepared to provide a quick reference for selecting enclosures to meet specific NEMA requirements. A brief description of the more common types of enclosures used by the electrical industry relating to their environmental capabilities follows. Please refer to the appropriate sections of NEMA Standards Publication No Enclosures for Electrical Equipment (000 Volts Maximum) for complete information regarding applications, features and design tests. Definitions Pertaining to Non-hazardous Locations Type enclosures are intended for use primarily to provide a degree of protection against contact with the enclosed equipment. Type 2 enclosures are intended for indoor use primarily to provide a degree of protection against limited amounts of falling water. Type Enclosures constructed for either indoor or outdoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment; to provide a degree of protection against falling dirt, rain, sleet, snow and windblown dust; and that will be undamaged by the external formation of ice on the enclosure. Type R enclosures are intended for outdoor use primarily to provide a degree of protection against falling rain, sleet, and external ice formation. Type S enclosures are intended for outdoor use primarily to provide a degree of protection against windblown dust, rain, sleet, and provide for operation of external mechanisms when ice laden. Type 4 enclosures are intended for indoor or outdoor use primarily to provide a degree of protection against windblown dust and rain, splashing water, and hose-directed water. *Type 4X enclosures are intended for indoor or outdoor use primarily to provide a degree of protection against corrosion, windblown dust and rain, splashing water, and hose-directed water. Type enclosures are intended for indoor use primarily to provide a degree of protection against dust and falling dirt. Type 6 enclosures are intended for indoor or outdoor use primarily to provide a degree of protection against the entry of water during occasional temporary submersion at a limited depth. (0 6 ft.) Type 6P enclosures are intended for indoor or outdoor use primarily to provide a degree of protection against the entry of water during prolonged submersion at a limited depth. (24 6ft.) Type 2 enclosures are intended for indoor use primarily to provide a degree of protection against dust, falling dirt, and dripping non-corrosive liquids. Type Type 2 Type of Type Type R Type2K Enclosure Type Type 2 Type S Type 4 Type 4X Type 6 Type YS & YS-A * YL & YL-A * YF YF-A * YW & YW-A * YU YR YT YC Type 2K enclosures with knockouts are intended for indoor use primarily to provide a degree of protection against dust, falling dirt, and dripping non-corrosive liquids other than at knockouts. Type enclosures are intended for indoor use primarily to provide a degree of protection against dust, spraying of water, oil, and non-corrosive coolant. Definitions Pertaining to Hazardous (Classified) Locations Type enclosures are for use indoors in locations classified as Class I, Groups A, B, C, or D, as defined in the National Electrical Code. See Section V. Type enclosures are for use in indoor locations classified in Class II, Groups E, F, or G, as defined in the National Electrical Code. See Section V. YW-T & YW-T-A * YCW & YCW-A * YPW & YPW-A * YBW & YBW-A * * Aluminum enclosures with stainless steel hardware may be ordered with optional spray applied epoxy powder coating to meet Type 4X corrosion protection. Use suffix -NX as listed in the price index. Contact your local representative for price and availability.

3 UA4 Instructions for Ordering Boxes UA4 The following information should be given on all box orders: and (L x W x D) should be specified. Sketch showing size and location of conduit entrances should be furnished similar to Drilling Template, Fig. 2, page UA. Tables on page UA give recommended spacing between conduits and minimum distance from corner and back of box. When spacings are not specified, they will be located at our discretion. Type of Conduit Entrances (see Fig., below) should be specified as follows: Slip-Hole (SH) - conduit clearance hole. 2 Drilled and Tapped hole (DT). Bossed, Drilled and Tapped hole to provide greater thread engagement (BDT). 4 Boss only (BWH) - for Drilling and Tapping in field. Specify conduit size. Mounting Lugs (See Fig. below) are provided on all surface mounted boxes over 00 cubic inches of internal volume to meet NEC Section 4.2(E). Boxes 00 cubic inches or less may be supported by 2 or more conduits threaded into the enclosure, or by optional mounting lugs. Boxes up to 2" x 6" have 2 mounting lugs. Larger boxes have 4 mounting lugs. All mounting lugs will be located on the long sides of the box, unless otherwise specified. Refer to page UA0 for dimensional data. Mounting Buttons (see Fig. below) for mounting equipment off the back of the box can be furnished located on standard centers and blind D & T for 4" - 20 screws. If special mounting button arrangement is required furnish a sketch showing layout including the size of the mounting screws. Please use the drilling template provided on page UA. Covers other than standard, must be specified if required. Gaskets other than standard must be specified if required. Conduit Entrances: Slip Holes: These are clearance holes for conduit. No threads are provided. Conduits are usually fastened in slip holes by means of locknuts and bushings. STANDARD LOCKNUT SPACINGS MUST BE ALLOWED BETWEEN THE CONDUITS. See Table on Page UA. Drilled & Tapped Holes are threaded holes provided in the enclosure wall into which the conduit is screwed. To meet UL requirements, they must conform to the following: * Enclosures for use in Non-hazardous Locations must have a wall thickness of not less than 4" at the tapped holes for the conduit and there shall be not less than 2 threads in the metal. * Compare the wall thickness shown in the catalog page for these enclosures with the chart below to determine the number of threads which the box wall will provide for the various conduit sizes. If more threads are required, please specify a Bossed, Drilled and Tapped hole, type BDT. Thickness Required - Inches of Conduit Threads / 2 Size per inch Threads Threads " " to 4" 4 4 " to 2" " to 6" 8 6 4" minimum wall thickness must be provided Bossed, Drilled & Tapped Holes are holes threaded thru the box wall and a boss (or pad) which has been added at the location of the conduit entrance to provide added wall thickness for threads of engagement. BOSSED, DRILLED AND TAPPED HOLE (BDT) SLIP HOLE (SH) DRILLED AND TAPPED HOLE (DT) MOUNTING BUTTONS (MBT) Fig. MOUNTING LUGS (ML)

4 UA Instructions For Ordering Boxes Drilling Template View looking into box - sides laid down. (2) 2 D & T with Boss Width W 2 /4 Top () /2 D & T with Boss UA Dimensions are always understood to be Inside Measurements unless otherwise specified. /4 /8 2 See page UA for a blank Drilling Template, for copier reproduction or computer scanning. Length L 8 8 /2 4 Back /2 (4) Mounting Buttons Tapped Blind For /4 20 UNC - 2B Left Side Right Side Depth D 6 (2) 2 Slip Holes /4 /8 Bottom /4 Fig. 2 Recommended Spacing and Location of Conduits (Allows for bushing and locknut clearance) All boxes of the Type YS, YL, YC, YW, and YT have a post in each corner and allowance must be made for them, when conduit entrances are to be located close to a corner. Dimension "A" in the table below is the minimum distance allowable from the sidewall of these boxes to the centerline of the conduit entrance, which provides the proper clearance between a locknut and the post. The "B" dimension will provide the proper clearance between a locknut or bushing and the sidewall of all other types of boxes and between a locknut or bushing and the backs of all boxes, including Types YS, YL, YC, YW, and YT. * If Conduit Fittings are used additional spacing between conduits will be required. Determine spacings based on fittings being used. Size of Conduit Minimum Space Between Centers of Conduits * (inches) Minimum Spacing of Conduit From Sides and Back Conduit Size 2" 4" " 4" 2" 2" 2 2" " 2" 4" " 6" Dimension - A 4" " " " 2" 2 " 2 " " 4" " 4 4" 4 " Dimension - B " " " " 2" 4" 2 " 2 2" 2 " " 4" 4 " B A B B Types YF, YU, YR Types YS, YL, YW, YC, YT

5 UA6 Cast Boxes & Cast Aluminum Boxes Additional Cost Items The table below shows the additional cost items available on the different types of enclosures shown in this catalog. These cost items are shown in the tables on the adjacent page and when not furnished as standard equipment the cost must be added to the base price of the box. Special Equipment Consult Factory for Prices and Availability Complete data regarding quantities and specifications will be required for quotation of special boxes. Please refer your requirements to our local representative. Special Covers of plain or checkered aluminum, plain brass plate and plain or checkered bronze can be furnished as well as steel checkered plate covers for pedestrian or vehicular traffic. UA6 Special Coatings such as various types of epoxy paints or plastic coatings can be applied. Information regarding type of coating, thickness and color required must be specified. Lettering on Covers can be furnished. These are usually raised cast-on letters or engraved letters and can be applied to the cover of any type box. Box Assemblies: Our manufacturing and engineering facilities are available to help solve your special problems involving combinations of boxes and other equipment such as barriers, receptacles, cable seals, indicating lights, transformers, fuses, relays, terminal blocks, etc. Boxes incorporating variations of standard construction, special sizes and boxes of cast bronze can also be furnished. Special Gaskets to meet specific environmental or temperature requirements can be furnished. Some of the materials frequently specified are: Hypalon, Vellumoid, Nitrile and Silicon Rubber. Special Hardware such as tamper proof screws, silicon bronze screws or hex head screws are available. Submersibility Tests can be made on our Types YF within the limitations shown on Pages UA4 listing these enclosures. Certifications can be furnished if specific requirements are provided at time of order. ITEM TYPE OF ENCLOSURE Designation YS YL YF YW YU YR YT Y8E YC YNY YW-T 0 YCW YPW YBW Slip Holes (SH) NA NA NA NA NA NA D & T Holes (DT) NA NA NA NA NA Bosses Only (BWH) NA NA NA NA NA D & T/Boss (BDT) NA NA S S S Mtg. Lugs (ML) S S S S NA NA S S NA NA NA Mtg. Buttons (MBT) NA NA NA NA NA NA NA Mtg. Plates (YM) NA NA NA NA NA NA NA Hinges (HNG) NA NA NA S NA NA NA S NA S NA NA NA NA Drain & Breather (DB) NA NA NA NA NA Hasp (HSP) NA NA NA NA NA NA NA NA NA NA NA NA - Available as required - at additional charge. S - Furnished as standard equipment - at no additional charge (mounting lugs are standard only on surface mounted boxes over 00 cubic inches internal volume) NA - Not permitted on this type of enclosure by NEMA and Underwriters Laboratories, Inc. standards and specifications, or basic construction of box will not allow or require this item. Hinges can be added to most box types for an additional fee. Please contact your local representative for special pricing.

6 UA Cast Boxes & Cast Aluminum Boxes Additional Cost Items UA Drilling & Tapping Applies to: Types YS, YL, YF, YW-T, YT, YC, YU, YR Conduit Size Slip Hole Drilling Only Hinges for YU Boxes Drilling & Tapping No Boss 2 Threads Min. Boss Drilling & Tapping Threads Max. Boss Only Without Hole for Threads SH-8 DT-8 BDT-8 BWH-8 2 SH-0 DT-0 BDT-0 BWH-0 4 SH- DT- BDT- BWH- SH-00 DT-00 BDT-00 BWH-00 4 SH-2 DT-2 BDT-2 BWH-2 2 SH-0 DT-0 BDT-0 BWH-0 2 SH-200 DT-200 BDT-200 BWH SH-20 DT-20 BDT-20 BWH-20 SH-00 DT-00 BDT-00 BWH-00 2 SH-0 DT-0 BDT-0 BWH-0 4 SH-400 DT-400 BDT-400 BWH SH-40 DT-40 BDT-40 BWH-40 SH-00 DT-00 BDT-00 BWH-00 6 SH-600 DT-600 BDT-600 BWH-600 of Hinges Type Box Size Per Set Stainless Steel Up to 2" x 2" HNG-22S 2 Butt Type Up to 8" x 8" HNG-2SS 2 For YU Boxes Larger than 8" x 8" HNG-SS Hinges can be added to most box types for an additional fee. Please contact your local representative for special pricing. Optional Mounting Lugs with Bolt Holes Combination Drain & Breather Fittings D&T and installation included Size Max. Box Size No. of Lugs Sizes up to 2 2-ML "L x 4"W 4 4-ML-0604 Sizes 6"L x 6"W 2 2-ML-204 Up to 2"L x 4"W 4 4-ML-204 Sizes 2"L x 6"W 2 2-ML-86 Up to 8"L x 6"W 4 4-ML-86 Sizes 8"L x 8"W 4 4-ML-66 and larger Mounting lugs are standard equipment on surface mounted boxes over 00 cubic inches of internal volume at no additional charge. " MDB-8 2" MDB-0 Interior Mounting Buttons Standard tapped blind for 4" - 20 thread Quantity Per Box -MBT 2 2-MBT -MBT 4 4-MBT Grounding Kits Wire Capacity Al-Cu Tinned Copper Specify if other than 4"-20 thread required. Letters Engraved or Raised on Box Covers Description Hasps Hot dip galvanized steel (lock not Included) Box Size Up to 2" x 2" HSP-SG Larger than 2" x 2" HSP-SG GK-04 GK-0 GK-2 #4-4 AWG 8-/0 AWG 6 AWG-20kcmil Up to 0 letters, one line ENGRAVE- Up to 20 letters, two lines ENGRAVE-2 Up to 0 letters, one line RAISED- Up to 20 letters, two lines RAISED-2 XXXX CAST-IN OR ENGRAVED LETTERS SLIP HOLE (SH) BOSSED, DRILLED AND TAPPED HOLE (BDT) DRILLED AND TAPPED HOLE (DT) MOUNTING BUTTONS (MBT) MOUNTING LUGS (ML)

7 UA8 UA8 Mounting Plates For Cast & Cast Aluminum Boxes Mounting plates are used for mounting equipment up off the back of an enclosure. Steel Plates are all /8" thick hot dip galvanized material. Aluminum plates are /8" thick material up to and including 2" x 2" size. All larger sizes are constructed of /6" thick aluminum plate. Select mounting plates based on inside length and width of box. Order as a separate line item immediately following the of the box as follows: Example: YS YM For mounting plates in smaller boxes than listed, use similar catalog number logic. Example: A steel mounting plate for a YF box would be "YM " Pricing will be based upon a YM price. THE CATALOG NUMBER SHOWN IN THE TABLE BELOW INCLUDES THE MOUNTING BUTTONS AND THE COST OF MOUNTING THE PLATE IN THE BOX. A Style L B W /6 Dia. Holes Inside Length & Width of Junction Box in Inches - Steel Plates - Aluminum Plates Dimension in Inches For use in YT, YF, YR, YE & YG Junction Boxes For use in YS, YL & YW Junction Boxes For use in YF, YR, YE & YG Junction Boxes For use in YS, YL & YW Junction Boxes Style L W A B 8 x 8 YM YM-0808-A YM YM A x 8 YM-008- YM-008-A YM YM-008-2A x 0 YM-00- YM-00-A YM-00-2 YM-00-2A x 8 YM-208- YM-208-A YM YM-208-2A x 0 YM-20- YM20-A YM-20-2 YM20-2A x 2 YM-22- YM-22-A YM-22-2 YM-22-2A x 8 YM-408- YM-408-A YM YM-408-2A x 4 YM-44- YM-44-A YM-44-2 YM-44-2A x 8 YM-608- YM-608-A YM YM-608-2A x 2 YM-62- YM-62-A YM-62-2 YM-62-2A x 6 YM-66- YM-66-A YM-66-2 YM-66-2A x 8 YM-808- YM-808-A YM YM-808-2A x 0 YM-80- YM-80-A YM-80-2 YM-88-2A x 2 YM-82- YM-82-A YM-82-2 YM-82-2A x 4 YM-84- YM-84-A YM-84-2 YM-84-2A x YM-86-2 YM-86-2A x 8 YM-88- YM-88-A YM-88-2 YM-88-2A x 0 YM-200- YM-200-A YM YM A Smaller size mounting plates available. If required, please contact your area representative for details. Refer to Section V for YE and YG Junction Boxes.

8 UA Mounting Plates UA For Cast & Cast Aluminum Boxes Mounting plates are used for mounting equipment up off the back of an enclosure. Steel Plates are all /8" thick hot dip galvanized material. Aluminum plates are /8" thick material up to and including 2" x 2" size. All larger sizes are constructed of /6" thick aluminum plate. Style 2 B W Select mounting plates based on inside length and width of box. Order as a separate item immediately following the of the box as follows: Example: YS YM A L /6 Dia. Holes W THE CATALOG NUMBER SHOWN IN THE TABLE BELOW INCLUDES THE MOUNTING BUTTONS AND THE COST OF MOUNTING THE PLATE IN THE BOX. Style B A L /6 Dia. Holes Inside Length & Width of Junction Box in Inches - Steel Plates - Aluminum Plates Dimension in Inches For use in YT, YF, YR, YE & YG Junction Boxes For use in YS, YL & YW Junction Boxes For use in YF, YR, YE & YG Junction Boxes For use in YS, YL & YW Junction Boxes See page UA8 for smaller mounting plates. 4 x 4 and 4 x 6 are available as specials. Please contact your local representative for special pricing. Refer to Section V for YE and YG Junction Boxes. Style L W A B 24 x 2 YM-242- YM-242- YM-242-A YM-242-A x 8 YM-248- YM-248- YM-248-A YM-248-A x 24 YM YM YM-2424-A YM-2424-A x 2 YM-282- YM-282- YM-282-A YM-282-A x 2 YM-02- YM-02- YM-02-A YM-02-A x 8 YM-08- YM-08- YM-08-A YM-08-A x 24 YM-024- YM-024- YM-024-A YM-024-A x 2 YM-62- YM-62- YM-62-A YM-62-A x 8 YM-68- YM-68- YM-68-A YM-68-A x 24 YM-624- YM-624- YM-624-A YM-624-A x 0 YM-60- YM-60- YM-60-A YM-60-A x 6 YM-66- YM-66- YM-66-A YM-66-A 4 4

9 UA0 Mounting Lug Data For Cast & Cast Aluminum Boxes Types YS, YL, YW, YU, YW-T Refer to Fig. Bolt Box Size Hole Dia. in Inches Dimension in Inches in Inches L x W A B D Types YS, YL, YW, YU, YW-T Refer to Fig. Bolt Box Size Hole Dia. in Inches Dimension in Inches in Inches L x W A B D Types YF, YR Refer to Fig. UA0 Bolt Box Size Hole Dia. in Inches Dimension in Inches in Inches L x W A B D 4 x 4 6 x x x 6 4 x x 4 8 x 6 8 x 8 4 x x 4 0 x 6 0 x x x x x x x x x x x x x x 2 6 x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x 4 6 x x x x x 6 8 x 8 0 x 6 0 x x 0 2 x x x x x x x x x x x x x x x x x x x x x The dimensions listed in these tables are approximate and may vary as much as 4" in any direction. If closer tolerances are required or if other locations of the mounting lugs are desired, specify on the order or drawing. Fig.

10 UA Drilling Template for Junction Boxes UA For copier reproduction or computer scanning. Please send to your local representative for quotation or order confirmation. FOR COPIER REPRODUCTION OR COMPUTER SCANNING. PLEASE SEND TO YOUR LOCAL REPRESENTATIVE FOR QUOTATION OR ORDER CONFIRMATION. Distributor End User Req. No. P.O. No. Date Mark Box Looking Into Box - Sides Laid Down All dimensions are from inside of box. Width NEW Electronic Drilling Template! Depth Top To layout your boxes electronically, visit our website and use our electronic drilling templete. Left Side Right Side Length Back Cover All dimensions are from inside of box. Bottom (Outside View) Gasket Standard (Neoprene) Other Drilling Data NOTE: If location of openings are not definitely dimensioned, they will be located at our discretion. Slip-hole Only Drilled and Tapped Req d Drilled and Tapped with Boss Boss Only No. Quantity Material: Cast - H.D.G Cast Aluminum Mounting Lugs NOTE: Mounting Lugs are provided on all surfacemount boxes over 00 cubic inches internal volume. See Page UA4 and box catalog page. Not Req d Standard Spacing - See Page UA0 Special Spacing - Location on Template Additional Specifications: Dwg. No. Company/Location Signature Print Name

11 UA2 UA2 Unflanged Junction or Pull Boxes Cast Box For Surface Mounting - NEMA 4 Type YS Raintight - Watertight - Dust Tight Use: These boxes are general purpose enclosures listed by Underwriters Laboratories, Inc. as Type 4. They are suitable for use indoors or outdoors, or where they would be subjected to rain, dripping or splashing of water, and hose directed water. Standard Construction: Cast iron box and cover Hot dip galvanized finish Neoprene gasket Stainless steel cover screws Cast mounting lugs (see notes) Options Available in aluminum. Add suffix -A to catalog number. Third Party Certification: UL Listed: Type 4 Raintight E-80 and E Applicable Third Party Standards: UL Standard: 4A, 0 NEMA 20- Type 4 Notes: Mounting Lugs are standard on boxes over 00 cubic inches internal volume, and optional on boxes 00 cubic inches or less. See Pages UA4 and UA for additional information and ordering instructions. Type YS boxes have a post in each corner and allowances must be made for them when conduit entrances are to be located close to a corner. See "Recommended Location and Spacing of Conduits" on Page UA. The listing of all Type YS boxes larger than 8" x 8" are now included with the Type YL boxes shown on Pages UA and UA. See Page UA for additional NEMA data. See Pages UA4-UA for ordering instructions and additional cost items. See Page UA0 for mounting lug dimensions, if applicable. See Page UA for blank Drilling Template, to lay out conduit entries and optional features. YS x 4 x 4 YS x 4 x 4 YS YS YS YS YS YS YS YS YS YS YS YS x 6 x x 6 x x 4 x x 6 x x 6 x x 8 x x 8 x x 8 x x 6 x x 6 x x 8 x x 0 x 4 YS-0006 YS YS YS YS-2206 YS-2208 YS-222 YS-6208 YS YS-8206 YS-820 YS-8806 YS-8808 YS x 0 x x 8 x x 8 x x 8 x x 2 x x 2 x 8 2 x 2 x x 2 x x 8 x x 2 x 6 8 x 2 x x 8 x x 8 x x 8 x 2 * Measured 2" up from back of box. Mounting Lugs are optional.

12 UA UA Overlapping Cover Boxes Cast Box & Cover - NEMA 4 Type YL Watertight - Raintight - Dust Tight Use: These overlapping cover boxes are listed by Underwriters Laboratories, Inc. as Type 4. They are suitable for use indoors or outdoors, or where they would be subjected to rain, dripping or splashing of water, and hose directed water. Standard Construction: Cast iron box and cover Hot dip galvanized finish Neoprene gasket Stainless steel cover screws Cast mounting lugs (see notes) Options Available in aluminum. Add suffix -A to catalog number. Third Party Certification: UL Listed: Type 4 Raintight E-80 and E (inches) (inches) Applicable Third Party Standards: UL Standard: 4A, 0 NEMA 20- Type 4 YL x 4 x 4 YL x 4 x 4 YL x 6 x 4 YL-2206 YL-2208 YL x 2 x x 2 x 8 2 x 2 x 2 Notes: Mounting Lugs are standard on boxes over 00 cubic inches internal volume, and optional on boxes 00 cubic inches or less. See Pages UA4 and UA for additional information and ordering instructions. Type YL boxes have a post in each corner and allowances must be made for them when conduit entrances are to be located close to a corner. See "Recommended Location and Spacing of Conduits" on Page UA. See Page UA for additional NEMA data. See Pages UA4-UA for ordering instructions and additional cost items. See Page UA0 for mounting lug dimensions, if applicable. See Page UA for blank Drilling Template, to lay out conduit entries and optional features. YL YL YL YL YL YL YL YL YL YL YL-0004 YL-0006 YL YL YL x 6 x x 4 x x 6 x x 6 x x 8 x x 8 x x 8 x x 6 x x 6 x x 8 x x 0 x x 0 x x 8 x x 8 x x 8 x 8 YL-6208 YL YL-8206 YL-820 YL-8806 YL-8808 YL-882 YL YL-2482 YL YL YL-622 YL-6242 YL x 2 x x 8 x x 2 x 6 8 x 2 x x 8 x x 8 x x 8 x x 2 x x 8 x x 24 x 2 28 x 2 x x 2 x x 24 x x 6 x 2 * Measured 2" up from back of box. Mounting Lugs are optional.

13 UA4 Flat Flanged Boxes UA4 Cast Box For Surface Mounting - NEMA 4, 6, 6P Type YF - Submersible Watertight - Raintight - Dust Tight Use: These boxes have been listed by Underwriters Laboratories, Inc. as a Type 4 enclosure. They are also suitable for use indoors or outdoors where they would be subjected to splashing water, seepage of water, falling or hose directed water and severe external condensation. These boxes will withstand occasional submersion under a 6 foot head of water for 0 minutes (NEMA 6 requirements). Standard Construction: Cast iron box and cover Hot dip galvanized finish Neoprene gasket Stainless steel cover screws Box flange ground before galvanizing Screw on cast mounting lugs (see notes) YF x 4 x 4 The ridge on the underside of the cover assures a good seal. YF x 8 x 8 Options Available in aluminum. Add suffix -A to catalog number. YF x 4 x 4 YF x 6 x 4 YF x 6 x 6 YF-2206 YF-2208 YF x 2 x x 2 x x 2 x 2 Third Party Certification: UL Listed: Type 4 Watertight E-80 and E YF x 4 x YF x 4 x 4 YF x 6 x 6 YF-6208 YF YF x 2 x x 8 x x 2 x 6 Applicable Third Party Standards: UL Standard: 4A, 0 NEMA 20- Type 4, 6, 6P Submersible Applications These boxes can be tested to withstand occasional submersion under a 6 foot head of water for 0 minutes (NEMA 6 requirements). Add suffix -SUB6 to catalog number These boxes can be tested to withstand Prolonged submersion under a 6 foot head of water for 24 hours (NEMA 6P requirements). Add suffix -SUB6P to catalog number. These boxes can be tested to withstand submersion up to a 20-foot head of water. Add suffix -SUB to catalog number, filling in the blank space with the number of feet from up to 20, followed by P if Prolonged submersion is required. * Measured 2" up from back of box. Mounting Lugs are optional. YF YF YF YF YF YF-0004 YF-0006 YF YF All YF-SUB enclosures are subject to a price addition on application and must have:. Mounting Lugs 2. Bossed, drilled, and tapped conduit entrances (BDT series).. NEMA Type Required. 2 8 x 8 x x 8 x x 8 x x 6 x x 8 x x 0 x x 0 x x 8 x x 8 x 6 YF-820 YF-8806 YF-882 YF YF-2482 YF YF YF-682 YF x 2 x x 8 x x 8 x x 2 x x 8 x 2 24 x 24 x 2 28 x 2 x 8 6 x 8 x x 6 x 2 Notes: Mounting Lugs are standard on boxes over 00 cubic inches internal volume, and optional on boxes 00 cubic inches or less. See Pages UA4 and UA for additional information and ordering instructions. See Page UA for additional NEMA data. See Pages UA4-UA for ordering instructions and additional cost items. See Page UA0 for mounting lug dimensions, if applicable. See Page UA for blank Drilling Template, to lay out conduit entries and optional features.

14 UA Hinged Cover Boxes UA Cast Box For Surface Mounting - NEMA 4 Type YW Watertight - Raintight - Dust Tight Use: These Hinged Cover Boxes make ideal enclosures where equipment within the box has to be inspected frequently and easy access is required. The hinges are adjusted at the factory for proper gasket pressure, but can be readjusted in the field as required. Standard Construction: Cast iron box and cover Neoprene gasket Stainless steel cover screws Screw on mounting lugs (see notes) Features: Hinges are always located on the long side of the box and unless otherwise specified on the right side. YW x 4 x 4 YW YW YW YW YW YW x 6 x x 6 x x 4 x x 6 x x 6 x x 8 x 4 YW YW YW-2422 YW YW YW YW x 2 x x 2 x x 2 x x 6 x x 6 x x 8 x x 8 x 8 Options Available in aluminum. Add suffix -A to catalog number. Third Party Certification: UL Listed: Type 4 Raintight E-80 and E YW YW YW YW-0060 YW YW x 8 x x 8 x x 6 x x 6 x 2 0 x 6 x x 8 x 6 YW-2480 YW-2482 YW YW YW YW x 8 x x 8 x x 24 x x 24 x 8 24 x 24 x x 24 x 2 Applicable Third Party Standards: UL Standard: 4A, 0 NEMA 20- Type 4 Notes: Mounting Lugs are standard on boxes over 00 cubic inches internal volume, and optional on boxes 00 cubic inches or less. See Pages UA4 and UA for additional information and ordering instructions. Type YW Boxes have a post in each corner and allowances must be made for them when conduit entrances are to be located close to a corner. See "Recommended Location and Spacing of Conduits" on page UA. See Page UA for additional NEMA data. See Pages UA4-UA for ordering instructions and additional cost items. See Page UA0 for mounting lug dimensions, if applicable. See Page UA for blank Drilling Template, to lay out conduit entries and optional features. YW-0004 YW-0006 YW YW YW YW-2206 YW-2208 YW-222 YW-6208 YW YW-8206 YW-820 YW-8806 YW-8808 YW-880 YW-882 YW YW YW YW YW x 0 x x 0 x x 8 x x 8 x x 8 x x 2 x x 2 x 8 2 x 2 x x 2 x x 8 x x 2 x 6 8 x 2 x x 8 x x 8 x 8 8 x 8 x x 8 x x 0 x x 0 x x 20 x x 8 x x 8 x 8 YW YW YW YW-2822 YW YW YW-0808 YW-082 YW-084 YW YW YW-0242 YW YW-6208 YW-622 YW-6808 YW YW-6242 YW-6608 YW x 24 x x 2 x 6 28 x 2 x x 2 x x 8 x x 8 x x 8 x x 8 x x 8 x x 24 x 6 0 x 24 x x 24 x x 6 x x 2 x x 2 x x 8 x x 24 x x 24 x 2 6 x 6 x x 6 x 2 * Measured 2" up from back of box. Mounting Lugs are optional.

15 UA6 UA6 Outside Flanged Recessed Cover Boxes Cast Box For Flush Mounting - NEMA 4 Type YR Watertight - Raintight - Dust Tight Use: These recessed cover boxes are listed by Underwriters' Laboratories, Inc. as Type 4. They are suitable for use outdoors where they would be subjected to rain or dripping or splashing of water. This type of box is designed especially for flush mounting in walls or floors as shown or can be used for surface mounting using optional mounting lugs. They are furnished with a plain cover as shown but can be supplied with steel checkered plate covers suitable for foot traffic (add Suffix "CS"). Steel checkered covers suitable for vehicular traffic (H-2 loading) can also be furnished at a price addition (add Suffix "CSV"). Standard Construction: Cast iron box and plain cover Hot dip galvanized finish Neoprene gasket Stainless steel cover screws Installation in Masonry Third Party Certification: UL Listed Type 4 E-80 and E Applicable Third Party Standards: UL Standard: 4A, 0 NEMA 20- Type 4 Notes: These boxes can be furnished in Cast Aluminum however they are not recommended for installation in concrete. For aluminum add suffix -A. Contact your local representative for price and availability. See Page UA for additional NEMA data. See Pages UA4-UA for ordering instructions and additional cost items. See Page UA0 for mounting lug dimensions, if applicable. See Page UA for blank Drilling Template, to lay out conduit entries and optional features. YR YR YR YR YR YR YR YR YR YR YR YR-0004 YR x 4 x x 4 x x 6 x x 6 x x 4 x x 6 x x 8 x x 8 x x 8 x x 6 x x 8 x x 0 x x 0 x 6 YR-2206 YR-2208 YR-222 YR-228 YR YR-6208 YR YR-8206 YR-820 YR-8806 YR-882 YR YR x 2 x x 2 x x 2 x 2 2 x 2 x x 8 x x 2 x x 8 x x 2 x x 2 x x 8 x x 8 x x 2 x x 8 x 2 YR x 8 x 4 YR x 24 x 2 YR x 8 x 6 YR x 8 x 2 YR x 8 x 8 YR x 6 x 2 YR x 0 x 0 * Measured 2" up from back of box.

16 UA UA Inside Flanged Recessed Cover Boxes Cast Box For Flush Mounting - NEMA R Type YU Dust Tight - Raintight Use: These recessed cover boxes are designed for flush mounting in masonry. They are furnished with a plain cover as shown but can be supplied with steel checkered plate covers suitable for foot traffic, if specified, at a price addition. Add suffix "CS" to catalog number. Standard Construction: Cast iron box and plain cover Hot dip galvanized finish Neoprene gasket Stainless steel cover screws Third Party Certification: UL Listed E-80 and E Applicable Third Party Standards: UL Standard: 4A, 0 NEMA 20- Type R Notes: These boxes can be furnished in Cast Aluminum however they are not recommended for installation in concrete. For aluminum add suffix -A. Contact your local representative for price and availability. See Page UA for additional NEMA data. See Pages UA4-UA for ordering instructions and additional cost items. See Page UA0 for mounting lug dimensions, if applicable. See Page UA for blank Drilling Template, to lay out conduit entries and optional features. YU YU YU YU x 4 x x 6 x x 6 x x 8 x 4 YU YU YU-6208 YU-820 Installation in Masonry 4 8 x 8 x x 8 x x 2 x x 2 x 0 * Measured 2" up from back of box.

17 UA8 Checkered Cover Sidewalk Boxes Cast Box For Flush Mounting Type YT UA8 Use: These boxes are specially designed to be mounted in sidewalks and other flat concrete surfaces. Their checkered covers are made to withstand pedestrian traffic. The flanges and covers are interchangeable to permit replacement without disturbing the box or conduit system. Steel checkered covers suitable for vehicular traffic (H-2 loading) can also be furnished at a price addition (add Suffix "CSV"). Features: Flanges and covers are interchangeable to permit replacement without disturbing box or conduit system. Standard Construction: Cast iron box, flange and cover Cross-ribbed checkered cover with pry bar slots Hot dip galvanized finish Neoprene gasket Stainless steel cover screws Notes: Type YT boxes have a post in each corner and allowances must be made for them, when conduit entrances are to be located close to a corner. See "Recommended Location and Spacing of Conduits", on Page UA. These boxes can be furnished in Cast Aluminum however they are not recommended for installation in concrete. For aluminum add suffix -A. Contact your local representative for price and availability. See Page UA for additional NEMA data. See Pages UA4-UA for ordering instructions and additional cost items. See Page UA0 for mounting lug dimensions, if applicable. See Page UA for blank Drilling Template, to lay out conduit entries and optional features. YT YT YT YT YT Thickness 4 6 x 6 x x 6 x x 8 x x 8 x x 8 x 8 YT YT-2206 YT-2208 YT-222 YT-80 Thickness 6 2 x 8 x x 2 x 6 2 x 2 x 8 2 x 2 x 2 8 x 0 x * Measured 2" up from back of box.

18 UA Hinged Door & Trim Cabinet Cast Box With Keyed Lock For Flush Mounting in s Type YC UA Use: These boxes have ornamental trim for flush mounting in concrete or stone structures. They are used in bridge construction, underpasses and approaches. They may house time switches, relays or other types of equipment. Standard Construction: Cast iron box, hot dip galvanized Trim and door - cast iron, hot dip galvanized, or cast bronze - specify correct from table. Neoprene gasket and one-piece lead gasket Non-removable brass hinges Brass cylinder lock with two keys Lettering cast on cover per specification at price option Keys can be made to match upon request Keyed Lock Hinges Notes: Type YC boxes have a post in each corner and allowances must be made for them, when conduit entrances are to be located close to a corner. See "Recommended Location and Spacing of Conduits" on Page UA. See Page UA for additional NEMA data. See Pages UA4-UA for ordering instructions and additional cost items. See Page UA0 for mounting lug dimensions, if applicable. See Page UA for blank Drilling Template, to lay out conduit entries and optional features. Installation in YC YC YC-2206 YC x 6 x x 8 x x 2 x 6 2 x 2 x 8 * Measured 2" up from back of box.

19 UA20 Cast Box For Flush Mounting - Open Bottom Type Y8E Checkered Cover Sidewalk Topping Box UA20 Use: These open-bottom boxes are designed to top off an underlying concrete pull box. The construction details of the cover and flange are the same as those of the Type YT shown on Page UA8. Standard Construction: Cast iron box, flange and cover Cross-ribbed checkered cover with pry bar slots Hot dip galvanized finish Neoprene gasket Stainless steel cover screws Options: Engraved Lettering on Cover per specification Notes: See Page UA for additional NEMA data. See Pages UA4-UA for ordering instructions and additional cost items. See Page UA0 for mounting lug dimensions, if applicable. See Page UA for blank Drilling Template, to lay out conduit entries and optional features. Installation in Concrete Y8E-22 2 x 2 x Y8E-08 0 x 8 x Y8E-82 8 x 2 x Y8E-68 6 x 8 x Y8E x 2 x Y8E x 24 x Y8E x 8 x Y8E-66 6 x 6 x Y8E x 24 x Y8E x 24 x

20 UA2 Checkered Cover Roadway Topping Box Cast Box For Flush Mounting - Open Bottom Type YNY UA2 Use: These open-bottom boxes are designed to top off concrete pull boxes. Design of these boxes is similar to the Type Y8E on Page UA20 except box and flange are one piece and cover is of cast steel or ductile iron. Units designed to withstand vehicular traffic, H-20 loading. Standard Construction: Cast iron box and cast steel or ductile iron cover Cross-ribbed checkered cover with pry bar slots Hot dip galvanized finish Neoprene gasket Stainless steel cover screws Options: Engraved Lettering on Cover per specification Notes: See Page UA for additional NEMA data. See Pages UA4-UA for ordering instructions and additional cost items. See Page UA0 for mounting lug dimensions, if applicable. See Page UA for blank Drilling Template, to lay out conduit entries and optional features. Installation in Concrete YNY-82-DIV YNY-248-DIV YNY-08-DIV YNY-68-DIV YNY-624-DIV YNY-4824-DIV 8 x 2 x -/2 24 x 8 x -/2 0 x 8 x -/2 6 x 8 x -/2 6 x 24 x -/2 48 x 24 x -/2 *Measured 2" up from back of box.