Using Annual Building Energy Analysis for the Sizing of Cooling Tower for Optimal Chiller-Cooling Tower Energy Performance
|
|
- Scarlett McBride
- 6 years ago
- Views:
Transcription
1 Proceedings: ISHVAC 007 Using Annual Building Energy Analysis for the Sizing of Cooling Tower for Optimal Chiller-Cooling Tower Energy Performance Chia-Wei Liu, Yew-Khoy Chuah Institute of Mechanical and Electrical Engineering, National Taipei University of Technology, Taipei 10608, Taiwan China ABSTRACT Lower condenser water temperature is an important factor for water chiller energy performance. In contrary to the usual consideration of trade off between cooling tower fan power and chiller power consumption, this study investigated the effects of oversized cooling tower on the total chiller-cooling tower energy performance. A dynamic building energy method was used in this study to compare the annual energy performance with this strategy using an office building under typical climatic conditions of tropical and subtropical regions. It has been found that oversizing cooling tower would result in ever decreasing total annual energy consumption for chillers and cooling towers as a whole. These results were obtained with different control methods used for the cooling tower fans. Moreover, this rate of decrease in total energy consumption is steepest at 10% oversize of cooling tower at standard conditions. Discussion is presented on the analysis for understanding the principles behind the results thus obtained. KEYWORDS Cooling tower, Chiller energy consumption, Cooling tower energy consumption, Building energy INTRODUCTION Chillers constitute the largest power consumption item of all the air-conditioning equipment, usually take up 60% of the power demand. Therefore, increasing the operating efficiency of the chiller is very important for building energy saving. Most chiller manufacturers provide energy efficiency index for their chillers such as the coefficient of performance (COP) at full load conditions. However, a water chiller usually operates at part load, and usually with condenser water temperature different from standard test conditions. Therefore, evaluation of the actual energy use should consider the cooling tower performance due to year round weather conditions. Liu and Chuah (006) analyzed for three cities in Taiwan, the effects of condenser water temperature control on annual energy saving with different tower fan control methods. Stout and Leach (00) presented a model for simplified analysis on the design and control of cooling tower and condensing water systems to save energy. The control of the condenser water temperature is important to increase the chiller energy efficiency in operation (Crowther and Furlong 004). It has been known that lower condenser water temperature could be achieved at the expense of higher cooling tower energy. This study analyzed the effects on the lower condenser water supply temperature by the oversizing of cooling tower. This study was done with different cooling water temperature control methods. The advantages and energy saving potential of these methods are presented and discussed. SIMULATION This study used the VisualDOE (Eley Associates 001) dynamic building energy program for hourly building energy analysis in one year duration. Annual hourly weather conditions at three different cities were considered in the analysis. Then, the annual total energy consumption by the chillers and the cooling tower fans were analyzed for various cases and are discussed in terms of energy saving. Electric chiller component model The VisualDOE dynamic building energy program is based on DOE-.1E. It can be used for simulating the hourly power consumption of water chillers and cooling tower fans (Winkelmann et al. 1993). Chiller and cooling tower power consumption can be modeled for operation under different conditions (Hydeman et al 00). In DOE-.1E, three regression curves are used to represent the performance of a chiller at part-load and off-design conditions as follows: CAPFT: A curve that represents the available capacity as a function of evaporator and condenser temperatures. EIRFT: A curve that represents the full-load efficiency as a function of evaporator and condenser temperatures. EIRFPLR: A curve that represents the efficiency as a function of part-load ratio
2 Proceedings: ISHVAC 007 The chilled water and the condenser water fluid temperatures are used as indicators of refrigerant pressures respectively in the evaporator and the condenser in CAPFT and EIRFT as shown below in Eqs. (1)-(4). CAPFT a b t d t EIRFT a b t d t EIRFPLR c t e t c t e t f t f t t t (1) () a b PLR c PLR (3) Q PLR (4) Q CAPFT rated By solving Eqs. (1)-(4), the power consumption of the water chiller can be determined at various chiller operating conditions using Eq (5). P Prated CAPFT EIRFT EIRFPLR Cooling tower component model (5) Two regression curves are used to represent the cooling tower performance at part-load and offdesign conditions : GPMRA: A curve that represents the capacity variable as a function of range and approach. GPMWB: A curve that represents the capacity variable as a function of GPMRA and outdoor wetbulb temperature. These two regression curves are combined to obtain the capacity as a function of three variables, and shown below in equations (6) to (11). t A t R tcwr t (6) t A t towb (7) a b tr c tr d GPMRA (8) e GPMRA f tr GPMRA GPMRA d f t R ( d f t ) d t owb R e e t 4 e ( a b t GPMWB a b GPMRA c GPMRA owb R t ) (9) f GPMRA t (10) tr q available qrated GPMWB (11) 10 This study used three types of cooling tower fan modulations, i.e., one-speed fan (on-off), two-speed fan for 1/ capacity (100%-50%-off) and variable A owb speed fan (ASHRAE 1999 and 001). Figure 1 shows the performance of the three fan modulation methods at different fan flows. Fan power (%) (on-off) (100%-50%-off) Variable-speed fan (VFD) Fan flow (%) Figure 1: Cooling tower fan modulations. The coefficients of the chiller and the cooling tower regression curves used are shown in Table 1. Table 1: Chiller and cooling tower curve coefficients a b c CAPFT EIRFT EIRFPLR GPMRA GPMWB d e f CAPFT EIRFT GPMRA GPMWB E Building energy simulation An office building with 10 floors was used as the building cooling case in this study. Table shows the chiller and cooling tower system parameters at design conditions. Figure shows the building configuration and load planing parameters. Typical weather types in this study are represented by cities located in tropical and subtropical regions, namely, Taipei, Hongkong and Singapore. Figure 3 shows the annual wet-bulb temperature profiles of these three cities
3 Proceedings: ISHVAC 007 Table : Building chiller and cooling tower system parameters. Building Type Office Floor Area ft (18000 m ) Floor Height 13.1 ft (4 m) Number of Floor 10 Schedule 9:00 am to 6:00 pm Summer Design 78 (5.6 ) Winter Design 64.4 (18 ) Number and Cooling Tower Fan Performance 1 at bhp/rt Cooling Tower Range 10 (5.6 ) Cooling Tower Approach 7 (3.9 ) Cooling Tower Rating WB 78 (6.6 ) Number and Chiller Performance 1 at kw/rt Chiller Water Temperature 44 (6.7 ) Condenser Water Temperature 85 (9.4 ) Location Taipei Hongkong Singapore Chiller Capacity (Calculated) 57 RT 593 RT 664 RT Cooling Tower Capacity (Calculated) 68 RT 70 RT 786 RT Construction: Exterior wall: 3.94 W/m K Interior floor: 3.37 W/m K Roof: 0.75 W/m K Partition:.84 W/m K Occupancy: 10 m /person Light: 0 W/m Equipment: 0 W/m OA requirement: 8.5 L/s*person Opening: Fenestration 30% Glazing: 3 W/m K SC: 0.96 Figure : Building configuration and load planing parameters. Wet-bulb (C o ) Month Taipei HongKong Singapore Figure 3: Annual wet-bulb profiles. RESULTS AND DISCUSSION Cooling tower and chiller energy performance Cooling towers of various sizes were first used in the analysis of the variation of fan power with condenser water supply. Figure 4 shows for July in Taipei (at wet-bulb temperature of 78 (5.6 )) the variation of fan power ratio at different condenser water temperature for different sizes of cooling tower. It is shown in Figure 4 that the use of larger cooling towers could result in lower fan power ratio. The fan power ratio is compared with cooling tower fan power at 100% load at design conditions. For the range of condenser water supply temperature analyzed, larger cooling towers have lower fan power ratio at the same supply temperature, thus lower energy consumption. It is observed in Figure 4 that larger cooling tower can reach smaller approach temperature when fans operating at full load, but relatively have higher power consumption. Figure 5 shows the results of chiller power ratio obtained with different condenser water temperature for different sizing of cooling tower. Chiller power ratio is compared to chiller operating at full load at standard conditions. It can be seen that lower condenser water temperature obtained is the result of smaller approach with larger cooling tower. It also clearly shows that the chiller power decreases with larger sizes of cooling tower, hence higher efficiency can be obtained with larger sizes of cooling tower
4 Proceedings: ISHVAC 007 Fan power ratio Chiller power ratio Approach 10% Design Condenser water supply (C o ) Figure 4: Cooling tower fan performance for the month of July, one-speed fan, Taipei % Desigh Approach = 5.1 o F 140% Desigh Approach = 3.6 o F Condenser water supply (C o ) 100% Desigh Approach = 5.8 o F 10% Desigh Approach = 4.5 o F 130% Desigh Approach = 4 o F 150% Desigh Approach = 3. o F 160% Desigh Approach =.9 o F Figure 5: Chiller performance for the month of July, fan speed at full load, Taipei. Annual energy consumption Three different control methods of condenser water temperature were compared in this study. First is the fixed temperature control at 85 (9.4 ) which is the condenser water temperature for full load operation of chiller. Second is the wet-bulb reset method that reset the condenser water temperature hourly according to the variation of ambient wetbulb temperature. Lastly, the control of condenser water temperature at lowest temperature allowed for the chiller, eg, 66 (18.9 ). In this method, the cooling tower will operate at its capacity to achieve or approach this low temperature. Table 3 to Table 5 are the results the annual energy consumption of chiller and cooling tower due to the different control methods, for the three cities. The case of fixed temperature at 85 (9.4 ) with one speed fan is used as the base case. The one speed fan allows for on/off control. Even using the variable speed control could save no more than 1% of total chiller cooling tower annual energy for the three cities. However, the wet-bulb reset and the low fixed temperature controls result in significant energy saving. Although higher tower fan energy is required, it is more than offset by the decrease in chiller energy consumption. It is noticed that the low temperature setting has the best energy saving. Also for this case, the control method of fan speed matters less. It is also noticed that for Singapore that located in tropical climatic region, energy saving is less significant for the control methods due to the yearly round higher ambient wet bulb temperature. Figure 6 and Figure 7 use Taipei as an example, to analyze the energy consumption of cooling tower and chiller respectively with sizing of cooling tower. It can be seen in Figure 6 that when using fixed temperature 85 (9.4 ) and wet-bulb reset control methods, larger cooling tower results in lower fan energy consumption. This result was obtained as the fan of larger cooling tower operates at partial load in longer duration. However, when the condenser water temperature was set at low temperature 66 (18.9 ), the cooling tower fan would operate at larger or full load for longer duration, thus consumed more energy hencewith. But it can be seen in Figure 7 that when the control of condenser water temperature at low temperature 66 (18.9 ) was used, larger cooling tower would result in lowest condenser water temperature in operation. Therefore, largest saving in chiller energy was obtained. It is thus shown that the control of condenser water temperature is important to the energy saving in chilller. Table 3: Simulation results of chiller-tower performance, Taipei. Chiller Location: Taipei Tower Total Energy Savings Fixed Temp. 85 (9.4 ) One-speed Baseline Two-speed % VFD % Wet-bulb Reset One-speed % Two-speed % VFD % Fixed Temp. 66 (18.9 ) One-speed % Two-speed % VFD %
5 Proceedings: ISHVAC 007 Table 4: Simulation results of chiller-tower performance, Hongkong. Table 5: Simulation results of chiller-tower performance, Singapore. Chiller Location: Singapore Tower Total Energy Savings Fixed Temp. 85 (9.4 ) One-speed Baseline Two-speed % VFD % Wet-bulb Reset One-speed % Two-speed % VFD % Fixed Temp. 66 (18.9 ) One-speed % Two-speed % VFD % Cooling tower fans energy consumption Chiller Location: Hong Kong Tower Total Cooling tower capacity (%) Fixed Temp. 66 o F(18.9 o C) Wet-bulb Reset Fixed Temp. 85 o F(9.4 o C) Energy Savings Fixed Temp. 85 (9.4 ) One-speed Baseline Two-speed % VFD % Wet-bulb Reset One-speed % Two-speed % VFD % Fixed Temp. 66 (18.9 ) One-speed % Two-speed % VFD % Figure 6: Cooling tower energy consumption for oversizing cooling tower, Taipei. Chillers energy consumption Cooling tower capacity (%) Fixed Temp. 66 o F(18.9 o C) Wet-bulb Reset Fixed Temp. 85 o F(9.4 o C) Figure 7: Chiller energy consumption for oversizing cooling tower, Taipei. Figure 8 to Figure 10 show the comparison of energy saving of chiller and cooling tower for the three cities. It can be seen that variable speed fan control has the largest energy saving potential followed by two speed fan control. It is also noticed that 110% of design value has the largest increase in energy saving. The benefits of larger cooling tower become more marginal thereon. It has been noticed that larger cooling tower can result in smaller approach. As the decrease in the approach will become more marginal, the increase in cooling tower performance will becoming smaller, as can be seen in Figure 5. In effects, the condenser water temperature can be lowered very little when the size of the cooling tower is already relatively large. Therefore, the benefits of increasing chiller efficiency become marginal. It can also be seen in the comparison between the three cities in Figure 8 to Figure 10 that Singapore has less energy saving potential for chiller-tower. It was shown in Figure 3 that the ambient wet-bulb in Singapore is relatively high year round. In comparisin Taipei has lower year average ambient wet bulb temperature. This seasonal change in ambient wet-bulb temperature allows for effective condenser water temperature control. It is observed in Figure 10 that for condenser water temperature control set at 18.9, the magnitude of increase in energy efficiency is greatest when cooling tower increase to 110%. However, it is seen in Figure 10 that energy consumption for cooling tower will increase beyond the energy saving of chiller when the size of the cooling tower increase to 140%. This trend is more obvious for Singapore with higher wet-bulb temperature year round
6 Proceedings: ISHVAC 007 Energy savings (%) Fixed Temp. 85 o F(9.4 o C) 10% Design Taipei Hongkong Singapore Baseline Figure 8: Chiller-tower energy saving for different sizing of cooling tower, fixed temp. 85 (9. 4 ) control method. Energy savings (%) Fixed Temp. 66 o F(18.9 o C) % Design Taipei Hongkong Singapore Figure 10: Chiller-tower energy saving for different sizing of cooling tower, fixed temp. 66 (18.9 ) control method. 3 Energy savings (%) Wet-bulb Reset % Design Taipei Hongkong Singapore Figure 9: Chiller-tower energy saving for different sizing of cooling tower, wet-bulb reset control method. CONCLUSION Standard test conditions are often used for selection of cooling tower, and the condenser water supply temperature of 85 (9.4 ) is usually taken as the control temperature. The benefits of lower condenser water temperature often do not attract sufficient attention. This study has found that oversizing of cooling tower can achieve lower energy concumption for chiller and cooling tower as a whole. Moreover, 10% oversizing has the greatest rate of increase in the total energy efficiency of chiller and cooling tower. This increase in energy efficiency is resulted from the higher fan power being offset by the energy saving of chiller power. As the cooling tower over sizing about 40%, the benefits of energy saving becomes marginal as the cooling tower approach is meeting the limit. For the the cases studied for the three cities in Asia, Singapore seemed to have less potential for energy saving by the control methods analyzed here. It is due to the higher ambient wet-bulb temperature year round. It has been found that 6% to 7% of energy saving is possible with proper design and control of cooling tower. ACKNOWLEDGMENT It is acknowledged herewith this study is supported by the National Science Council of Taiwan
7 Proceedings: ISHVAC 007 REFERENCES [1]ASHRAE Handbook of HVAC Applications. pp.40.9~ []ASHRAE ANSI/ASHRAE/IESNA Standard 90.1, User s Manual. pp.6-71~6-7. [3]Crowther, H. and J. Furlong, 004. Optimizing Chillers & Towers. ASHRAE Journal Vol. 46 Iss. 7 p. 34. [4]Eley Associates VisualDOE 3.0 Program Documentation. 14 Minna St., SF, California. [5]Hydeman, M. and K.L. Gillespie. 00. Tools and Techniques to Calibrate Electric Chiller Component Models. ASHRAE Transactions Vol pp.733~741. [6]Hydeman, M., S.T. Taylor and D. Winiarski. 00. Application of Component Models for Standards Development. ASHRAE Transactions Vol pp.74~750. [7]Liu C.W. and Y.K. Chuah The Effects of Weather Conditions on the Cooling Tower Performance and the Energy Consumption of Water Chillers in Taiwan. ACRA006 Conference V ol.. pp.589~593. [8]Stout Jr, M.R. and J.W. Leach. 00. Cooling Tower Fan Control for Energy Efficiency. Energy Engineering Vol. 99. NO. 1. pp.9~31. [9]Winkelmann, F.C., B.E. Birdsall, W.F. Buhl, K.L. Ellington, A.E. Erden DOE- Supplement version.1e. Lawrence Berkeley Laboratory, Berkeley, California. q rated : Heat rejection capacity from cooling tower at rated condition (MBtu/hr) NOMENCLATURE a,b,c,d,e,f: Regression coefficients t : Condenser water supply temperature ( ) t : Chilled water supply temperature ( ) Q: Capacity of chiller (tons) Q ref : Capacity of chiller at rated condition (tons) PLR: Operating part-load ratio of chiller P: Present power consumption of chiller (kw) P ref : Power consumption of chiller at rated condition (kw) t R : Range ( ) t A : Approach ( ) t cwr : Condenser water return temperature ( ) t : Condenser water supply temperature ( ) t owb : Outdoor wet-bulb temperature ( ) q available : Available heat rejection capacity from cooling tower (MBtu/hr)
Assessment of Building Energy Performance for EEMs A Case Study in Mumbai
Assessment of Building Energy Performance for EEMs A Case Study in Mumbai Mr. Tej Singh Chouhan #1, Dr. (Prof.) Ashish Dutt Sharma *2 # Research Scholar in Mechanical Engineering JJT University, Vidyanagari,
More informationApplication of Near-Optimal Tower Control and Free Cooling on the Condenser Water Side for Optimization of Central Cooling Systems
Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2014 Application of Near-Optimal Tower Control and Free Cooling on the Condenser Water
More informationEvaluation of Energy Savings of the New Chinese Commercial Building Energy Standard
Evaluation of Energy Savings of the New Chinese Commercial Building Energy Standard Wei Feng, Ke Huang, Mark Levine and Nan Zhou, Lawrence Berkeley National Laboratory Shicong Zhang, Lawrence Berkeley
More informationCALIBRATION OF AN ENERGYPLUS CENTRAL COOLING PLANT MODEL WITH MEASUREMENTS AND INTER-PROGRAM COMPARISON
CALIBRATION OF AN ENERGYPLUS CENTRAL COOLING PLANT MODEL WITH MEASUREMENTS AND INTER-PROGRAM COMPARISON Danielle Monfet 1 and Radu Zmeureanu 2 1 Department of Construction Engineering, École de technologie
More informationChapter 4. Analysis of Building Energy Performance
Chapter 4 Analysis of Building Energy Performance 128 4.1 Introduction This chapter deals with energy modeling and simulation of the baseline models for the buildings to assess energy performance of the
More informationA Comparison of Methods to Verify Energy-Saving Benefits for Chillers
Open Journal of Applied Sciences, 2013, 3, 44-49 doi:10.4236/ojapps.2013.31007 Published Online March 2013 (http://www.scirp.org/journal/ojapps) A Comparison of Methods to Verify Energy-Saving Benefits
More informationA USER-FRIENDLY TOOL FOR THE INTEGRATED SIMULATION OF BUILDING HVAC CONTROL PERFORMANCE
A USER-FRIENDLY TOOL FOR THE INTEGRATED SIMULATION OF BUILDING HVAC CONTROL PERFORMANCE E.H. Mathews and E. van Heerden Department of Mechanical Engineering University of Pretoria South Africa Consultants
More informationCOOLING EFFECTIVENESS OF MIST PRECOOLER FOR IMPROVING ENERGY PERFORMANCE OF AIR-COOLED CHILLER
Yu, F. W., et al.: Cooling Effectiveness of Mist Precooler for THERMAL SCIENCE: Year 2018, Vol. 22, No. 1A, pp. 193-204 193 COOLING EFFECTIVENESS OF MIST PRECOOLER FOR IMPROVING ENERGY PERFORMANCE OF AIR-COOLED
More informationEnergy Efficiency in Building Active Design Part II
Energy Efficiency in Building Active Design Part II Presented by: CK Tang BSEEP Component 4 Manager Veritas Enviornment Sdn Bhd ck.tang@veritas.com.my Air Conditioning System System Sizing 1 Current Industry
More informationIn typical commercial buildings, water-cooled chilled water plants use a signifi cant amount of energy.
The following article was published in ASHRAE Journal, June 2007. Copyright 2007 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes
More informationMechanical Redesign. Existing System: The following schematic was devised below.
Mechanical Redesign Existing System: The mechanical system explained in the existing conditions was simulated on an energy modeling system call equest. This program was used because of its strong detailed
More informationAnalysis and System Design of a Large Chiller Plant for Korea, with or without Thermal Storage
Analysis and System Design of a Large Chiller Plant for Korea, with or without Thermal Storage Christine Levin HVAC Designer Flack + Kurtz Consulting Engineers, LLP New York, New York Peter Simmonds Director
More informationDEVELOPMENT OF A HIGH-PERFORMANCE OFFICE BUILDING SIMULATION MODEL FOR A HOT AND HUMID CLIMATE
Eleventh International IBPSA Conference Glasgow, Scotland July 27-3, 29 DEVELOPMENT OF A HIGH-PERFORMANCE OFFICE BUILDING SIMULATION MODEL FOR A AND HUMID CLIMATE Soolyeon Cho 1 and Jeff S. Haberl 2 1
More informationVerification of Chiller Performance Promotion and Energy Saving
Engineering, 2013, 5, 141-145 http://dx.doi.org/10.4236/eng.2013.51a020 Published Online January 2013 (http://www.scirp.org/journal/eng) Verification of Chiller Performance Promotion and Energy Saving
More informationRetro-commissioning and on-going commissioning 23 November 2016
Retro-commissioning and on-going commissioning 23 November 2016 1 CONTENTS 1. Needs for Retro-Commissioning (RCx) 2. Retro-Commissioning (RCx) Definition and Scope 3. Briefing of RCx Process 4. Alternative
More informationCONDENSING TEMPERATURE CONTROL THROUGH ENERGY MANAGEMENT SYSTEM SIMULATON FOR A LARGE OFFICE BUILDING
CONDENSING TEMPERATURE CONTROL THROUGH ENERGY MANAGEMENT SYSTEM SIMULATON FOR A LARGE OFFICE BUILDING Young-Hoon Kwak 1, Dong-Seok Kong 1, Se-Hwan Cheon 1, Ro-Yeul Kwak 2, and Jung-Ho Huh 3 1 Department
More informationProceedings of BS2013: 13th Conference of International Building Performance Simulation Association, Chambéry, France, August 26-28
HVAC CONTROL SIMULATION STUDY FOR AUSTRALIAN OFFICE BUILDINGS Hongsen Zhang and Paul Bannister Exergy Australia Pty Ltd, Canberra, Australia hongsen@xgl.com.au; paul@xgl.com.au ABSTRACT This paper presents
More informationEnergy Consumption Analysis and Energy Conservation Evaluation of a. Commercial Building in Shanghai
Energy Consumption Analysis and Energy Conservation Evaluation of a Commercial Building in Shanghai Chen Chen Yiqun Pan ZhizhongHuang Gang Wu Master Ph.D. Assistant Engineer Associate Professor Senior
More informationEnergyPlus Testing with HVAC Equipment Component Tests
EnergyPlus Testing with HVAC Equipment Component Tests EnergyPlus Version 4.0.0.024 October 2009 Prepared for: U.S. Department of Energy Energy Efficiency and Renewable Energy Office of Building Technologies
More informationHVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya
HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya (vahid.vakiloroaya@engineer.com) ABSTRACT: The overall attainable reduction in energy consumption and enhancement of
More informationItalcementi Center for Research and Innovation
Italcementi Center for Research and Innovation Bergamo, Italy LEED-NC v2.1 EAc1 A. Project Narrative (Viridian) analyzed the energy use of the proposed Italcementi Center for Research and Innovation located
More informationSURNA Grow Facility: Systems Comparison - IEA
SURNA Grow Facility: Systems Comparison - IEA May 2016 SURNA Grow Facility This analysis provides the projected energy and associated cost comparison between the Surna proposed facility in comparison to
More informationIMPLEMENTATION OF ANALYTICAL MODELS FOR PASSIVE DOWN-DRAFT EVAPORATIVE COOLING (PDEC) TOWER WITH SPRAY SYSTEMS
IMPLEMENTATION OF ANALYTICAL MODELS FOR PASSIVE DOWN-DRAFT EVAPORATIVE COOLING (PDEC) TOWER WITH SPRAY SYSTEMS Daeho Kang 1, Richard K. Strand 2 1 Department of Environmental Control Technology, New York
More informationHVAC Simulation Guidebook Volume. VolumeIII
Advanced HVAC Simulation Guidebook Volume VolumeIII Second Edition The High Performance July 2012Process Building Table of Contents Part 1: Underfloor Air Distribution and Thermal Displacement Ventilation
More informationSimulation Studies on Performance of Solar Cooling System in UAE Conditions
Available online at www.sciencedirect.com Energy Procedia 00 (2014) 000 000 www.elsevier.com/locate/procedia SHC 2013, International Conference on Solar Heating and Cooling for Buildings and Industry September
More informationCAE 331/513 Building Science Fall 2017
CAE 331/513 Building Science Fall 2017 November 28, 2017 Energy estimation and design for efficiency Advancing energy, environmental, and sustainability research within the built environment www.built-envi.com
More informationTWO DOE-2 FUNCTIONS. Tianzhen Hong, Charles Eley, and Erik Kolderup Architectural Energy Corporation 142 Minna Street, San Francisco, CA 94105, USA
Ninth International IBPSA Conference Montréal, Canada August 15-18, 2005 TWO DOE-2 FUNCTIONS Tianzhen Hong, Charles Eley, and Erik Kolderup Architectural Energy Corporation 142 Minna Street, San Francisco,
More informationThis article does not examine economic payback; a detailed energy. analysis is the best method of comparing system options and their respective
This article was published in ASHRAE Journal, November 29. Copyright 29 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not be
More informationSimulation of Source Energy Utilization and Emissions for HVAC Systems. A report ASHRAE TC 6.9 in response to the 991-TRP workstatement.
Simulation of Energy Utilization and Emissions for HVAC Systems A report ASHRAE TC 6.9 in response to the 991-TRP workstatement submitted by Douglas T. Reindl, Ph. D, P.E. Director of Research University
More informationProceedings of BS2015: 14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 2015.
OPTIMISATION OF SUPPLY AIR TEMPERATURE CONTROLS FOR VAV SYSTEMS IN TEMPERATE AUSTRALIA Paul Bannister, Hongsen Zhang Energy Action (Australia) Pty Ltd, Canberra, Australia Paul.Bannister@energyaction.com.au;
More informationTHERMODYNAMIC MODELING OF HVAC PLANT COOLING EQUIPMENT FOR QUANTIFICATION OF ENERGY SAVINGS THROUGH CONTINUOUS COMMISSIONING MEASURES.
THERMODYNAMIC MODELING OF HVAC PLANT COOLING EQUIPMENT FOR QUANTIFICATION OF ENERGY SAVINGS THROUGH CONTINUOUS COMMISSIONING MEASURES A Thesis by STEVEN JAMES RIVERA Submitted to the Office of Graduate
More informationChiller plant optimization
Chiller plant optimization CLEANROOM Terrence Morris & Steve Blaine PE, CH2M HILL, Oregon, USA ABSTRACT Outside of the process tools themselves, the chilled water plant is typically the single largest
More informationChilled Water System Optimization
Advanced HVAC Diagnostics and Control Strategies Chilled Water System Optimization Brian Leduc Carrier Corporation August 16, 2017 Contents of this presentation 2017 Carrier Corporation Tampa Convention
More informationENERY COST AND CONSUMPTION IN A LARGE ACUTE HOSPITAL
, Volume 5, Number 1, p.11-19, 24 ENERY COST AND CONSUMPTION IN A LARGE ACUTE HOSPITAL S.C. Hu, J.D. Chen and Y.K. Chuah Department of Air-Conditioning and Refrigeration Engineering, National Taipei University
More informationhow to read an energy model
how to read an energy model Kohler Ronan, LLC is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported
More informationMechanical Depth. Redesign and Analysis
Depth Redesign and Analysis 14 Analysis Scope The scope of my mechanical redesign will include the 2 nd and 3 rd floors of the SW hospital wing which includes Semi-Private, Private and Isolations rooms.
More informationYear-round Energy Saving Potential for a Stratum Ventilated Subtropical Office. C.K. Lee Zhang Lin K.F. Fong
Year-round Energy Saving Potential for a Stratum Ventilated Subtropical Office C.K. Lee Zhang Lin K.F. Fong Building Energy & Environmental Technology Research Unit, School of Energy and Environment &
More informationResearch paper titled. Analysis and Evaluation of Energy Conservation Potential in an Indian Commercial Building A Case Study in Jaipur
Annexure: D Research paper titled Analysis and Evaluation of Energy Conservation Potential in an Indian Commercial Building A Case Study in Jaipur Published in Referred International Journal International
More informationThe Impact of VISIONWALL High Performance Windows on the Northern Telecom Building in Ottawa, Ontario
The Impact of VISIONWALL High Performance Windows on the Northern Telecom Building in Ottawa, Ontario Visionwall Technologies Inc. 14904-123 Avenue Edmonton, Alberta, Canada T5V 1B4 Tel: 403 451 4000 Fax:
More informationCost Benefits of SunGuard SN 54
Cost Benefits of SunGuard SN 54 Guardian Industries recently introduced SunGuard SN 54 low-e glass. This new low-e glass is clear in appearance and has optimal energy performance for commercial building
More informationOnline Optimal Control of The Central Chilling System in a Super High-Rise Commercial Building
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Online Optimal Control of The Central Chilling System in a Super High-Rise
More informationTechnical Report 2. Bellevue Ambulatory Care Pavilion New York, NY. Building and Plant Energy Analysis
Technical Report 2 Building and Plant Energy Analysis Bellevue Ambulatory Care Pavilion New York, NY Prepared for: Dr. Jelena Srebric, PhD Department of Architectural Engineering The Pennsylvania State
More informationCooling coil optimisation in hot and humid climates for IAQ and energy considerations
Cooling coil optimisation in hot and humid climates for IAQ and energy considerations Chandra Sekhar 1, Uma Maheswaran 2 1 Department of Building, National University of Singapore 2 Jurong Consultants
More informationOPTIMIZATION OF ICE THERMAL STORAGE SYSTEM DESIGN FOR HVAC SYSTEMS
OPTIMIZATION OF ICE THERMAL STORAGE SYSTEM DESIGN FOR HVAC SYSTEMS Nabil Nassif, Ph.D. P.E. Christopher Hall Dante' Freeland Assistant professor Graduate Student Graduate Student Department of Civil, Architectural,
More informationBUILDING FOR THE FUTURE
BUILDING FOR THE FUTURE The following article was published in ASHRAE Journal, September 4. Copyright 4 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented
More informationPERFORMANCE CORRELATIONS FOR COUNTERFLOW COOLING TOWER
Jurnal Mekanikal June 2016, Vol 39, 15-26 PERFORMANCE CORRELATIONS FOR COUNTERFLOW COOLING TOWER Mohd Yusoff Senawi* Faculty of Mechanical Engineering Universiti Teknologi Malaysia 81310 UTM Johor Bahru
More informationAHU Models Using Whole Building Cooling and Heating Energy Consumption Data
Calibrating AHU Models Using Whole Building Cooling and Heating Energy Consumption Data Mingsheng Liu, Ph.D., P. E. ; Guanghua Wei; and D. E. Claridge, Ph.D., P. E. Energy Systems Laboratory Texas A&k?
More informationENERGY AS SERVICES COMPANY ESCO. Jamal E. Alostaz. Projects Engineer Al-Salem Johnson Controls
ENERGY AS SERVICES COMPANY ESCO Jamal E. Alostaz Projects Engineer Al-Salem Johnson Controls AGENDA About Johnson Controls Introduction to ESCO Case Study: Empire State Building, USA Project Information
More informationOpportunities and Limitations of Building Precooling
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 1994 Opportunities and Limitations of Building Precooling K. R. Keeney Purdue
More informationEVALUATION OF BUILDING ENERGY CONSUMPTION BASED ON FUZZY LOGIC AND NEURAL NETWORKS APPLICATIONS
P P (1) EVALUATION OF BUILDING ENERGY CONSUMPTION BASED ON FUZZY LOGIC AND NEURAL NETWORKS APPLICATIONS Kajl, SP (1) P., Roberge, M-AP (1) P., Lamarche, LP (1) P., Malinowski, PP PEcole de technologie
More informationGLOBAL OPTIMISATION OF CHILLER SEQUENCING AND LOAD BALANCING USING SHUFFLED COMPLEX EVOLUTION
GLOBAL OPTIMISATION OF CHILLER SEQUENCING AND LOAD BALANCING USING SHUFFLED COMPLEX EVOLUTION IAIN STEWART, MEng Renewable Energy and Energy Efficiency Group Department of Infrastructure Engineering The
More informationLEED Energy Performance Summary Report
Section 1.1 - General Information Simulation Program: Principle Source: Energy Code Used: Weather File: Climate Zone: New Construction Percent: Existing Renovation Percent: Quantity of Floors: Proposed:
More informationAN INNOVATIVE DEDICATED OUTDOOR AIR APPLICATION FOR A GOVERNMENT OFFICE TOWER. MICHAEL HALLENBECK, PE, CEM Southland Industries
AN INNOVATIVE DEDICATED OUTDOOR AIR APPLICATION FOR A GOVERNMENT OFFICE TOWER MICHAEL HALLENBECK, PE, CEM Southland Industries BRAC 133 OVERVIEW PROJECT OVERVIEW FAN POWERED INDUCTION UNIT CENTRAL UTILITY
More informationGround-Coupled Heat Pump And Energy Storage
Ground-Coupled Heat Pump And Energy Storage By Ed Lohrenz, Member ASHRAE; and Sergio Almeida, P.Eng., Member ASHRAE Ground-coupled heat pump (GCHP) systems consume less purchased energy than an HVAC system
More informationAvailable online at ScienceDirect. Procedia Engineering 121 (2015 )
Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 121 (2015 ) 881 890 9th International Symposium on Heating, Ventilation and Air Conditioning (ISHVAC) and the 3rd International
More informationOptimized System for Your Bottom Line. Trane Training Class 1 Dec, 2017
Optimized System for Your Bottom Line Trane Training Class 1 Dec, 2017 Total Cost of Ownership Setting your system for great payback Where is money spent over a 30 year lifetime? First Cost 4.9% Service
More informationChilled Water Plant Redesign
17 Chilled Water Plant Redesign OVERVIEW The chilled water plant redesign includes the addition of a thermal energy storage system. This allows for economic and operational benefits for the facility by
More informationCeiling Radiant Cooling Panels
Copyright 2006, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc This posting is by permission from ASHE Journal This article may not be copied nor distributed in either paper
More informationField Performance Measurements of VRF System with Subcooling Heat Exchanger
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 01 Field Performance Measurements of VRF System with Subcooling Heat Exchanger
More informationLoad Estimation. Ir. Dr. Sam C. M. Hui Faculty of Science and Technology
SPD4121 HVAC Technology for Plumbing Engineers http://ibse.hk/spd4121/ Load Estimation Ir. Dr. Sam C. M. Hui Faculty of Science and Technology E-mail: cmhui@vtc.edu.hk Jul 2016 Contents Basic Concepts
More informationA NEW METHOD FOR THE OPTIMAL CHILLER SEQUENCING CONTROL
A NEW METHOD FOR THE OPTIMAL CHILLER SEQUENCING CONTROL Sen Huang 1, Wangda Zuo 1*, Michael D. Sohn 2 1 Department of Civil, Architectural and Environmental Engineering, University of Miami, Coral Gable,
More informationEnergy Saving Report. Frigi-Tech Oil Additive. Application. In HKU Central Plant. Chiller No. 3
Energy Saving Report Of Frigi-Tech Oil Additive Application In HKU Central Plant Chiller No. 3 Prepared By: Evaluated and Endorsed By: December 2003 Eric P L Leung Sales Manager Electrical and Mechanical
More informationMeeting the Variable Needs of Energy- Efficient Mechanical Ventilation When and Where You Need It
Meeting the Variable Needs of Energy- Efficient Mechanical Ventilation When and Where You Need It Charles Withers Jr. 1 Introduction Effectively providing mechanical ventilation in commercial buildings
More informationLarge University Central Chiller Plant Design Considerations
Carrier Engineering Newsletter Volume 5, Issue 3 Large University Central Chiller Plant Design Considerations Large campus chilled water plants have unique constraints and need careful evaluation for successful
More informationFree Cooling Technology
Free Technology Utilise low ambient temperatures to save energy and reduce your cooling costs by up to 70% Free for industrial process and air conditioning How Free can save you money Free is a fast and
More informationGregory W. Stevens and Ronald K. Ishii, Alternative Energy Systems Consulting, Inc.
A Study of Optimizing the System Integration of Combined Heat and Power (CHP) with Absorption Cooling for Cold Storage Applications: Design Considerations, Modeling and Life Cycle Costing Gregory W. Stevens
More informationDemonstration of Load Shifting and Peak Load Reduction with Control of Building Thermal Mass
Demonstration of Load Shifting and Peak Load Reduction with Control of Building Thermal Mass J. E. Braun and T. M. Lawrence, Ray W. Herrick Laboratories, Purdue University C. J. Klaassen and John M. House,
More information7 Measurement and Verification for Generic Variable Loads
7 Measurement and Verification for Generic Variable Loads 7 Measurement and Verification for Generic Variable Loads 7.1 Overview Projects that improve the efficiency of end-uses that exhibit variable energy
More informationOptimizing Central Chilled Water Systems
Optimizing Central Chilled Water Systems OPTIMIZING CENTRAL CHILLED WATER SYSTEMS kent.peterson@p2seng.com 1 O P T I M I Z I N G C E N T R A L C H I L L E D W A T E R S Y S T E M S Kent W. Peterson, PE,
More informationPromoting Building Energy Efficiency through Performancebased Standards: Is it a Challenge? By Priyantha Bandara
Promoting Building Energy Efficiency through Performancebased Standards: Is it a Challenge? By Priyantha Bandara Senior Lecturer General Sir John Kotelawala Defence University, Sri Lanka & Rahula Attalage
More informationOPTION 1: PERFORMANCE RATING METHOD
OPTION 1: PERFORMANCE RATING METHOD I confirm that the energy simulation software used for this project has all capabilities described in EITHER section `G2 Simulation General Requirements' in Appendix
More informationChilled Water Loop Optimization. Kazimir Gasljevic Richard Dewey Sandro Sanchez
Chilled Water Loop Optimization Kazimir Gasljevic Richard Dewey Sandro Sanchez WHAT WE STARTED WITH: LOOP OUTLINE: WHAT WE STARTED WITH: LOOP OUTLINE: - Justification for the loop WHAT WE STARTED WITH:
More informationEvaluating Energy Performance and Improvement Potential of China Office Buildings in the Hot Humid Climate against US Reference Buildings
Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2010 Evaluating Energy Performance and Improvement Potential of China Office Buildings
More informationDemonstration of modeling of radiant cooling system in design builder. Prashant Bhanware & Bharath Reddy
Demonstration of modeling of radiant cooling system in design builder Prashant Bhanware & Bharath Reddy CONTENTS Introduction to Design Builder Building Energy Simulation Modeling procedure Making a model
More informationSolar cooling design: a case study
Eco-Architecture IV 399 Solar cooling design: a case study S. Grignaffini & M. Romagna Department of Astronautic, Electric and Energetic Engineering, Sapienza, University of Rome, Italy Abstract Throughout
More informationCeiling Radiant Cooling Panels
2006, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc (wwwashraeorg) Published in ASHE Journal Vol 48, Oct 2006 For personal use only Additional reproduction, distribution,
More informationFigure 26.5 Potential fan energy savings using fan speed limiting 16.
COMMISSIONING FOR ENERGY MANAGEMENT 685 Figure 26.5 Potential fan energy savings using fan speed limiting 16. 26.4.2.2. Set Minimum Outside Air Intake Correctly Outside air intake rates are often significantly
More informationAnalysis of Heat Gain in Computer Laboratory and Excellent Centre by using CLTD/CLF/SCL Method
Available online at www.sciencedirect.com Procedia Engineering 53 ( 2013 ) 655 664 Malaysian Technical Universities Conference on Engineering & Technology 2012, MUCET 2012 Part 2 Mechanical And Manufacturing
More informationCAE 331/513 Building Science Fall 2017
CAE 331/513 Building Science Fall 2017 November 14, 2017 Heating load calculations Advancing energy, environmental, and sustainability research within the built environment www.built-envi.com Twitter:
More informationUNDERFLOOR AIR DISTRIBUTION INTEGRATED WITH AN INDIRECT AND DIRECT EVAPORATIVE COOLING ASSISTED 100% OUTDOOR AIR SYSTEM
UNDERFLOOR AIR DISTRIBUTION INTEGRATED WITH AN INDIRECT AND DIRECT EVAPORATIVE COOLING ASSISTED 100% OUTDOOR AIR SYSTEM YJ Seok, HJ Cho, SK Han and JW Jeong Department of Architectural Engineering, Sejong
More informationDevelopment of New Self-Comparison Test Suites for EnergyPlus
Development of New Self-Comparison Test Suites for EnergyPlus Michael J. Witte Robert H. Henninger GARD Analytics, Inc., Arlington Hts., IL Drury B. Crawley U.S. Department of Energy, Washington, DC IBPSA-USA
More informationRETRO-COMMISSIONING OF A HEAT SOURCE SYSTEM IN A DISTRICT HEATING AND COOLING SYSTEM Eikichi Ono 1*, Harunori Yoshida 2, Fulin Wang 3 KEYWORDS
Eleventh International IBPSA Conference Glasgow, Scotland July 7-, 9 RETRO-COMMISSIONING OF A HEAT SOURCE SYSTEM IN A DISTRICT HEATING AND COOLING SYSTEM Eikichi Ono *, Harunori Yoshida, Fulin Wang KAJIMA
More informationOPTIMAL CONTROL OF CHILLER PLANTS USING BAYESIAN NETWORK
OPTIMAL CONTROL OF CHILLER PLANTS USING BAYESIAN NETWORK Ana Carolina Laurini Malara 1, Sen Huang 2, Wangda Zuo 2*, Michael D. Sohn 3, Nurcin Celik 4 1 Institute of Mathematics and Computer Science, University
More informationTHERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING. Gang Wang, Yafeng Hu, and Songtao Hu
THERMAL ENVIRONMENT OF OUTDOOR UNITS OF VRV SYSTEM IN HIGH- RISE BUILDING Gang Wang, Yafeng Hu, and Songtao Hu School of Environmental & Municipal Engineering, Qingdao Technological University, Qingdao
More informationIntelligent. Powerful. Proven. usa.siemens.com/demandflow
Demand Flow Chilled Water System Optimization Intelligent. Powerful. Proven. usa.siemens.com/demandflow Demand Flow CHW Building Technologies A powerful solution to reduce energy consumption and improve
More informationCOMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING
COMPARISON OF ENERGY USE INDICATORS OF A NON-RESIDENTIAL PASSIVE HOUSE WITH ASHRAE 90.1 BUDGET BUILDING ABSTRACT F. Bagheri 1, M. Fakoor 1, B. Young 1, C. Cranswick 1 1 BC Building Science Ltd. 611 Bent
More informationCentral Chiller Plants
Central Chiller Plants Institute for Facilities Management New Orleans, LA January 18,2016 Course 319 Presenter: John Vucci Associate Director HVAC Systems University of Maryland College Park, Maryland
More informationInfluence of the control strategy on the heat rejection potential and electricity consumption of air-to-water condensers for solar cooling systems
Influence of the control strategy on the heat rejection potential and electricity consumption of air-to-water condensers for solar cooling systems M. D'Antoni, R. Fedrizzi, D. Romeli EURAC Research, Viale
More informationThe Application Practice of Energy Performance Rating Method for Fab Energy Efficient Design
The Application Practice of Energy Performance Rating Method for Fab Energy Efficient Design Kuei-Peng Lee 1 Te-Ang Cheng 2 Hsiang-Lun Chen 2 1 Assistant Professor 2 Ph.D. Student Department of Energy
More informationBuilding Energy Efficiency Analysis for a High School
Building Energy Efficiency Analysis for a High School (LG Multi V Water II VRF System) School Building Air-Conditioning Engineering Study VRF-ES-BF-002-US 013A16 Contents Executive Summary...3 Introduction...4
More informationEnergy Efficiency Baselines for LABORATORIES. PG&E s Customized New Construction and Customized Retrofit Incentive Programs.
Energy Efficiency Baselines for LABORATORIES PG&E s Customized New Construction and Customized Retrofit Incentive Programs October 1, 2010 Funded By: Written By: 427 13 th Street Oakland, CA 94612 510.663.2070
More informationCOST EFFECTIVENESS FOR SOLAR CONTROL FILM FOR RESIDENTIAL APPLICATIONS H. Al-Taqi G.P. Maheshwari R. Alasseri Senior Research Associate
COST EFFECTIVENESS FOR SOLAR CONTROL FILM FOR RESIDENTIAL APPLICATIONS H. Al-Taqi G.P. Maheshwari R. Alasseri Senior Research Associate Senior Research Specialist Department of Building and Energy Technologies
More informationENERGY EFFICIENT DESIGN OF SIDE-WINDOW FOR DAYLIGHTING APPLICATION IN THAILAND. S. Chungloo, B. Limmeechokchai and S.
Seventh International IBPSA Conference Rio de Janeiro, Brazil August 13-15, 21 ENERGY EFFICIENT DESIGN OF SIDE-WINDOW FOR DAYLIGHTING APPLICATION IN THAILAND S. Chungloo, B. Limmeechokchai and S. Chungpaibulpatana
More informationNEW FEATURES IN THE CARRIER HOURLY ANALYSIS PROGRAM v4.40
NEW FEATURES IN THE CARRIER HOURLY ANALYSIS PROGRAM v4.40 By: Carrier Software Systems Carrier Corporation Syracuse, New York rev August 11, 2008 Copyright 2008 Carrier Corporation, All Rights Reserved
More informationA NEW POLYNOMIAL BASED MODEL FOR DETERMINING COOLING TOWER EVAPORATION WATER LOSS. Aaron Powers Johnson Controls, Inc.
ASHRAE and IBPSA-USA SimBuild 2016 Building Performance Modeling Conference Salt Lake City, UT August 8-12, 2016 A NEW POLYNOMIAL BASED MODEL FOR DETERMINING COOLING TOWER EVAPORATION WATER LOSS Aaron
More informationDetermining Energy Use Volatility for Commercial Mortgage Valuation
Determining Energy Use Volatility for Commercial Mortgage Valuation Paul Mathew, XiuFeng Pang, Liping Wang Building Technologies and Urban Systems Department Lawrence Berkeley National Laboratory June
More informationENERGYPLUS: A NEW-GENERATION BUILDING ENERGY SIMULATION PROGRAM
ENERGYPLUS: A NEW-GENERATION BUILDING ENERGY SIMULATION PROGRAM Drury B. Crawley U.S. Department of Energy 1000 Independence Avenue, SW Washington, DC 20585-0121 Linda K. Lawrie U.S. Army Engineer Research
More informationEnergy Efficiency Analysis for a Multi-Story Research Office Building (LG Multi V Water IV Heat Recovery VRF System)
Energy Efficiency Analysis for a Multi-Story Research Office Building (LG Multi V Water IV Heat VRF System) (* Source: http://kr.lgeaircon.com/) Commercial Air-Conditioning Engineering Study ES-MultiVWaterIV_EnergyAnalysis-08-14
More informationTEA Facility Data Survey
TEA Facility Data Survey Date: Facility Setup Printed Version 1. *Facility Name Click here type in name. Contact: Click here to enter text. 2. CRM Click here to enter CRM. Phone: Click here to enter text.
More informationModeling Energy Consumption Effects of Glazing
Modeling Energy Consumption Effects of Glazing Daniel Lu 12/7/2012 Table of Contents Introduction... 3 Design Options... 5 Option 1... 5 Option 2... 5 Preliminary Energy Simulation... 7 Objectives... 7
More information