Firestopping Submittal Package

Size: px
Start display at page:

Download "Firestopping Submittal Package"

Transcription

1 Firestopping Submittal Package Project: Architect: General Contractor: Installation Contractor: Distributor (and Contact): Commercial Plumbing Contractors (PVC & PEX Thru Gyp Board) Manufacturer's Representative: Rectorseal - Technical Services Ph (713) * (800)

2 Table of Contents Product Approvals... 1 Certificate of Compliance... 2 Metacaulk 1000 SDS... 8 Metacaulk MC 150+ SDS Metacaulk Wrap Strip SDS Metacaulk Pipe Collars SDS Metacaulk Intumescent Sleeve SDS Metacaulk 1000 Datasheet Metacaulk MC 150+ Datasheet Metacaulk Wrap Strip Datasheet Metacaulk Pipe Collars Datasheet Metacaulk Intumescent Sleeve Datasheet W-L W-L W-L W-L W-L W-L W-L W-L W-L W-L W-L W-L W-L W-L W-L W-L

3 APPROVALS FOR METACAULK PRODUCTS Below is a list of Model Building Codes requiring the use of firestop products in various types of constructions and occupancies. Most local codes are derived from one or more of these model codes. Metacaulk products and systems meet the through-penetration firestopping requirements of all of these codes. ICC International Code Council; International Building Code ICBO International Code of Building Officials; Uniform Building Code SBCCI..... Southern Building Code Congress International; Standard Building Code BOCA..... Building Official and Code Administrators International; National Building Code CABO..... Council of American Building Officials (coordinating agency between ICBO, SBCCI and BOCA) NBCC..... National Building Code of Canada NFPA National Fire Protection Association Life Safety Code IRC International Residence Code March 2011 Certain cities, counties and states have written their own code requirements which may supersede or supplement model building codes, check with these authorities for approvals. Metacaulk Products are UL Classified and conform to the codes and test requirements shown below. UL Fire Tests of Through-Penetration Firestops UL Tests for Fire Resistance of Building Joint Systems ASTM E Standard Test Method for Fire Resistive Joint Systems ASTM E Methods for Fire Tests of Through-Penetration Fire Stops NFPA National Fire Protection Association Life Safety Code ASTM E 84 (UL 723).. Test Method for Surface Burning Characteristics of Building Materials ASTM E 119 (UL 263).. Method for Fire Tests of Building Construction and Materials ULC CAN4-S115M.... Standard Method of Fire Tests of Firestop Systems B.S. 476/ pr EN European/ British Standards AS Part 4: Fire Resistance Tests of Elements of Building Construction AS Part 1: Service Penetration and Control Joint For Questions or Additional Information call Technical Service Fax Page 1

4 Page 2

5 Page 3

6 To Whom It May Concern: RectorSeal s Warranty statement for firestop is contingent upon actual storage conditions and proper installation. If RectorSeal firestop products are correctly installed in accordance with our stated Manufacturers instructions and according to the UL tested systems, our products comply with UL 1479 "Fire Tests for Through-Penetration Firestop" and UL 2079 Test for Fire Resistance of Building Joint System standard requirements for Environmental Exposure Tests. This test relates to the performance of firestop products as originally installed, and compares to the performance testing after exposure to extreme temperatures and high humidity for an extended period of time. If properly stored, our products have a minimum shelf life of two years, subject to inspection with the exception of our silicone product which has a one year shelf life. The RectorSeal Corporation, manufacturer of Metacaulk, Bio Firesheild and Flamesafe firestop products, has always been concerned about the long-term performance of our products. We implemented a testing program prior to the UL s requirement for Fire Tests for Through- Penetration Firestop and UL 2079 Test for Fire Resistance of Building Joint System. We burned materials in our UL sanctioned fire test facility to measure the performance of RectorSeal products after extended periods of time as in accordance with current standards. Some of the tested materials exceed 15 years in age. Assuming that the substrate area surrounding the actual penetration or construction joint has not been damaged, we warrant that Metacaulk, Bio Firesheild and Flamesafe products will perform satisfactorily for the sustainable life of the building. Sincerely, RECTORSEAL Larry Kaiser Larry Kaiser Vice President of Sales Page 4

7 March 3, 2016 To Whom It May Concern: RectorSeal s Warranty Statement for our Smoke and Acoustical sealant is contingent upon actual storage conditions and proper installation. If properly stored, our RectorSeal Smoke and Acoustic Sealant has a minimum shelf life of two years, subject to inspection. Assuming that the substrate area surrounding the actual penetration/joint has not been damaged, we warrant that the RectorSeal Smoke and Acoustic Sealant product, when fully cured will perform satisfactorily for the sustainable life of the building. If there are any additional questions, do not hesitate to call our office at Respectfully, RECTORSEAL Terry Gossett Terry Gossett Technical Services Page 5

8 2601 Spenwick Dr Houston, TX ph: fax: May 26, 2011 RE: RectorSeal Smoke and Acoustic Sealant LEED Product Information TO: Whom It May Concern This letter will detail the contribution of RectorSeal Smoke and Acoustic Sealant materials to the LEED Green Building Rating System in accordance with LEED-NC, CS, CI and School Rating Systems. MR Credit 2.1: Construction Waste Management, Divert 50% form Disposal MR Credit 2.2: Construction Waste Management, Divert 75% from Disposal In areas where facilities exist, the following RectorSeal Smoke and Acoustic Sealant materials are recyclable and can contribute to earning Materials and Resources Credit 2.1 or Credit 2.2. Carton Cardboard 2 lbs / carton 20.2 oz foil pack Mylar 5 g. / pack 5 gallon pail HDPE 934 g. / pail Wooden pallet wood 45 lbs. / pallet MR Credit 5.1: Regional Materials, 10% Extracted, Processed & Manufactured Regionally MR Credit 5.2: Regional Materials, 20% Extracted, Processed & Manufactured Regionally RectorSeal Smoke and Acoustic Sealant materials are manufactured in one location Houston, Texas. If these locations fall within a 500-mile radius of the project site and the location the raw materials used to make the finished product are extracted, recovered or harvested within a 500-mile radius of the project, then these materials or a portion of the materials can contribute to earning Materials and Resources Credit 5.1 and Credit 5.2. The following are the locations of the RectorSeal Smoke and Acoustic Sealant materials manufacturing plants: RectorSeal Product Smoke and Acoustic Sealant Location Houston, Texas Page 6

9 Please contact your local RectorSeal Representative to request a project specific letter pertaining to Credit 5.1 and Credit 5.2. The letter will provide the location where the raw materials are extracted, recovered or harvested in relation to the location of the project. EQ Credit 4.1: Low Emitting Materials, Adhesives & Sealants EQ Credit 4.2: Low Emitting Materials, Paints & Coatings The volatile organic content (VOC) of RectorSeal Smoke and Acoustic Sealant materials is listed below for those products that are lower than the minimum LEED requirements for low-emitting materials. These materials can help contribute to earning Indoor Environmental Quality EQ Credit 4.1 and 4.2. RectorSeal Product EQ Credit VOC Content (g/l) RectorSeal Smoke and Acoustic Sealant 4.1 <10 (Caulk Grade) RectorSeal Smoke and Acoustic Sealant 4.2 <10 (Spray Grade) Please feel free to contact me with any additional questions or information. Sincerely, Terry Gossett Technical Service Page 7

10 SDS 0169 SAFETY DATA SHEET Section 1 -- PRODUCT AND COMPANY IDENTIFICATION HMIS CODES PRODUCT NAME Health 1 Metacaulk 1000 Flammability 0 Reactivity 0 PRODUCT CODES PPI B 66640, 66242, 66302, 66303, 66305, 66307, 66309, CHEMICAL FAMILY Organic/Inorganic USE Firestopping Sealant MANUFACTURER'S NAME EMERGENCY TELEPHONE NO. The RectorSeal Corporation Chemtrec 24 Hours 2601 Spenwick Drive (800) USA Houston, Texas USA (703) International DATE OF VALIDATION TECHNICAL SERVICE TELEPHONE NO. January 23, 2015 (800) or (713) DATE OF PREPARATION May 22, 2012 Section 2 -- HAZARDS IDENTIFICATION GHS CLASSIFICATION PHYSICAL HAZARDS: None HEALTH HAZARDS Acute Toxicity: Oral: Not Classified Dermal: Not Classified Inhalation: Not Classified Skin Corrosion/Irritation: Not Classified Serious Eye Damage/Eye Irritation: Not Classified Respiratory or Skin Sensitization: Not Classified Germ Cell Mutagenicity: Not Classified Carcinogenicity: Not Classified Reproductive Toxicology: Not Classified Target Organ Systemic Toxicity - Single Exposure: Not Classified Target Organ Systemic Toxicity - Repeated Exposure: Not Classified Aspiration Toxicity: Not Classified ENVIRONMENTAL HAZARDS Hazardous to the Aquatic Environment: Not Classified Acute aquatic toxicity: Not Classified Chronic aquatic toxicity: Not Classified Bioaccumulation potential: Not Classified Rapid degradability: Not Classified GHS Label elements, including precautionary statements Pictogram: None Signal Word: None Hazard Statements: None Precautionary Statements: P102 - Keep out of reach of children. P264 - Wash hands thoroughly after handling. Classification according to EU Directives 67/548/EEC or 1999/45/EC LABELING SYMBOLS: None RISK R-PHRASES: NOne SAFETY S-PHRASES: S2 : Keep out of the reach of children. SUMMARY OF ACUTE HAZARDS May cause skin irritation. ROUTE OF EXPOSURE, SIGNS AND SYMPTOMS INHALATION Not a respiratory irritant. EYE CONTACT Contact may cause eye irritation. Page 8

11 SKIN CONTACT Contact may cause skin irritation. INGESTION Possible irritation to mucous membranes of the mouth, throat, and stomach. SUMMARY OF CHRONIC HAZARDS None known. MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE Persons with pre-existing skin conditions or chemical allergies may be more susceptible to contact effects of the cured elastomer. Section 3 -- COMPOSITION/INFORMATION ON INGREDIENTS % by WT CAS No. INGREDIENT UNITS None as defined by OSHA Hazard Communication Standard 29 CFR Section 4 -- FIRST AID MEASURES If INHALED: Not a respiratory irritant. If on SKIN: Wash with soap and water. If irritation occurs, seek medical attention. If in EYES: Immediately flush with large amounts of water. If If SWALLOWED: irritation occurs, seek medical attention. If swallowed, call a physician immediately. Only induce vomiting at the instruction of a physician. Never give anything by mouth to an unconscious person. Section 5 -- FIRE FIGHTING MEASURES EXTINGUSING MEDIA Foam, dry chemical, carbon dioxide or water fog. SPECIAL FIRE FIGHTING PROCEDURES: Wear self-contained breathing apparatus (SCBA) and other protective clothing. Hazardous decomposition products possible (see Section 10). UNUSUAL FIRE AND EXPLOSION HAZARDS: Heat may build up and rupture closed containers. Section 6 -- ACCIDENTAL RELEASE MEASURES STEPS TO BE TAKEN IN CASE MATERIAL IS RELEASED OR SPILLED: Wipe up spills to prevent footing hazard. Avoid flushing into sewers, drains, waterways and soil. Wear protective clothing during clean up. Section 7 -- HANDLING AND STORAGE PRECAUTIONS TO BE TAKEN IN HANDLING AND STORING: Keep container closed and upright when not in use. To prevent freezing and possible rupture of container, do not store below 35 F. OTHER PRECAUTIONS: Avoid prolonged or repeated contact with skin or clothing. Empty containers may contain residues and vapors; treat as if full and observe all product precautions. Do not reuse empty containers. KEEP OUT OF REACH OF CHILDREN. Section 8 -- EXPOSURE CONTROLS/PERSONAL PROTECTION RESPIRATORY PROTECTION (SPECIFY TYPE): None required. VENTILATION - LOCAL EXHAUST: N/A SPECIAL: N/A MECHANICAL (GENERAL): N/A OTHER: N/A PROTECTIVE GLOVES: None required. EYE PROTECTION: None required. OTHER PROTECTIVE CLOTHING OR EQUIPMENT: None required. WORK/HYGIENIC PRACTICES: Where use can result in skin contact, wash exposed areas thoroughly before eating, drinking, smoking, or leaving work area. Launder contaminated clothing before reuse. Section 9 -- PHYSICAL AND CHEMICAL PROPERTIES BOILING POINT: 212 F ( mm Hg SPECIFIC GRAVITY (H20 = 1): 1.25 VAPOR PRESSURE (mm Hg): 68 F (20 C) MELTING POINT: N/A VAPOR DENSITY (AIR = 1): N/A Page 9

12 EVAPORATION RATE (ETHYL ACETATE = 1): >1 APPEARANCE/ODOR: Red Paste/Mild Odor SOLUBILITY IN WATER: Soluble VOLATILE ORGANIC COMPOUNDS(VOC)Content (Theoretical Percentage By Weight): Page 10

13 SDS 0581 SAFETY DATA SHEET Section 1 -- PRODUCT AND COMPANY IDENTIFICATION HMIS CODES PRODUCT NAME Health 1 Metacaulk MC 150+ Flammability 0 Reactivity 0 PRODUCT CODES PPI B 66382, 66383, 66385, 66389, CHEMICAL FAMILY Organic/Inorganic USE Firestopping Sealant MANUFACTURER'S NAME EMERGENCY TELEPHONE NO. The RectorSeal Corporation Chemtrec 24 Hours 2601 Spenwick Drive (800) USA Houston, Texas USA (703) International DATE OF VALIDATION TECHNICAL SERVICE TELEPHONE NO. January 23, 2015 (800) or (713) DATE OF PREPARATION March 21, 2011 Section 2 -- HAZARDS IDENTIFICATION GHS CLASSIFICATION PHYSICAL HAZARDS: None HEALTH HAZARDS Acute Toxicity: Oral: Not Classified Dermal: Not Classified Inhalation: Not Classified Skin Corrosion/Irritation: Not Classified Serious Eye Damage/Eye Irritation: Not Classified Respiratory or Skin Sensitization: Not Classified Germ Cell Mutagenicity: Not Classified Carcinogenicity: Not Classified Reproductive Toxicology: Not Classified Target Organ Systemic Toxicity - Single Exposure: Not Classified Target Organ Systemic Toxicity - Repeated Exposure: Not Classified Aspiration Toxicity: Not Classified ENVIRONMENTAL HAZARDS Hazardous to the Aquatic Environment: Not Classified Acute aquatic toxicity: Not Classified Chronic aquatic toxicity: Not Classified Bioaccumulation potential: Not Classified Rapid degradability: Not Classified GHS Label elements, including precautionary statements Pictogram: None Signal Word: None Hazard Statements: None Precautionary Statements: P102 - Keep out of reach of children. P264 - Wash hands thoroughly after handling. Classification according to EU Directives 67/548/EEC or 1999/45/EC LABELING SYMBOLS: None RISK R-PHRASES: NOne SAFETY S-PHRASES: S2 : Keep out of the reach of children. SUMMARY OF ACUTE HAZARDS May cause skin irritation. ROUTE OF EXPOSURE, SIGNS AND SYMPTOMS INHALATION Not a respiratory irritant. EYE CONTACT Contact may cause eye irritation. Page 11

14 SKIN CONTACT Contact may cause skin irritation. INGESTION Possible irritation to mucous membranes of the mouth, throat, and stomach. SUMMARY OF CHRONIC HAZARDS None known. MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE Persons with pre-existing skin conditions or chemical allergies may be more susceptible to contact effects of the cured elastomer. Section 3 -- COMPOSITION/INFORMATION ON INGREDIENTS % by WT CAS No. INGREDIENT UNITS None as defined by OSHA Hazard Communication Standard 29 CFR Section 4 -- FIRST AID MEASURES If INHALED: Not a respiratory irritant. If on SKIN: Wash with soap and water. If irritation occurs, seek medical attention. If in EYES: Immediately flush with large amounts of water. If If SWALLOWED: irritation occurs, seek medical attention. If swallowed, call a physician immediately. Only induce vomiting at the instruction of a physician. Never give anything by mouth to an unconscious person. Section 5 -- FIRE FIGHTING MEASURES EXTINGUSING MEDIA Foam, dry chemical, carbon dioxide or water fog. SPECIAL FIRE FIGHTING PROCEDURES: Wear self-contained breathing apparatus (SCBA) and other protective clothing. Hazardous decomposition products possible (see Section 10). UNUSUAL FIRE AND EXPLOSION HAZARDS: Heat may build up and rupture closed containers. Section 6 -- ACCIDENTAL RELEASE MEASURES STEPS TO BE TAKEN IN CASE MATERIAL IS RELEASED OR SPILLED: Wipe up spills to prevent footing hazard. Avoid flushing into sewers, drains, waterways and soil. Wear protective clothing during clean up. Section 7 -- HANDLING AND STORAGE PRECAUTIONS TO BE TAKEN IN HANDLING AND STORING: Keep container closed and upright when not in use. To prevent freezing and possible rupture of container, do not store below 35 F. OTHER PRECAUTIONS: Avoid prolonged or repeated contact with skin or clothing. Empty containers may contain residues and vapors; treat as if full and observe all product precautions. Do not reuse empty containers. KEEP OUT OF REACH OF CHILDREN. Section 8 -- EXPOSURE CONTROLS/PERSONAL PROTECTION RESPIRATORY PROTECTION (SPECIFY TYPE): None required. VENTILATION - LOCAL EXHAUST: N/A SPECIAL: N/A MECHANICAL (GENERAL): N/A OTHER: N/A PROTECTIVE GLOVES: None required. EYE PROTECTION: None required. OTHER PROTECTIVE CLOTHING OR EQUIPMENT: None required. WORK/HYGIENIC PRACTICES: Where use can result in skin contact, wash exposed areas thoroughly before eating, drinking, smoking, or leaving work area. Launder contaminated clothing before reuse. Section 9 -- PHYSICAL AND CHEMICAL PROPERTIES BOILING POINT: 212 F ( mm Hg SPECIFIC GRAVITY (H20 = 1): 1.5 VAPOR PRESSURE (mm Hg): 68 F (20 C) MELTING POINT: N/A VAPOR DENSITY (AIR = 1): N/A Page 12

15 EVAPORATION RATE (ETHYL ACETATE = 1): >1 APPEARANCE/ODOR: Red Paste/Mild Odor SOLUBILITY IN WATER: Soluble VOLATILE ORGANIC COMPOUNDS(VOC)Content (Theoretical Percentage By Weight): Page 13

16 SDS 0218 SAFETY DATA SHEET Section 1 -- PRODUCT AND COMPANY IDENTIFICATION HMIS CODES PRODUCT NAME Health 1 Metacaulk Wrap Strip Flammability 0 Reactivity 0 PPI B PRODUCT CODES 66133, 66135, CHEMICAL FAMILY Organic/Inorganic USE Firestopping Material MANUFACTURER'S NAME EMERGENCY TELEPHONE NO. The RectorSeal Corporation Chemtrec 24 Hours 2601 Spenwick Drive (800) USA Houston, Texas USA (703) International DATE OF VALIDATION TECHNICAL SERVICE TELEPHONE NO. January 23, 2015 (800) or (713) DATE OF PREPARATION February 27, 2012 Section 2 -- HAZARDS IDENTIFICATION GHS CLASSIFICATION PHYSICAL HAZARDS: None HEALTH HAZARDS Acute Toxicity: Oral: Not Classified Dermal: Not Classified Inhalation: Not Classified Skin Corrosion/Irritation: Not Classified Serious Eye Damage/Eye Irritation: Not Classified Respiratory or Skin Sensitization: Not Classified Germ Cell Mutagenicity: Not Classified Carcinogenicity: Not Classified Reproductive Toxicology: Not Classified Target Organ Systemic Toxicity - Single Exposure: Not Classified Target Organ Systemic Toxicity - Repeated Exposure: Not Classified Aspiration Toxicity: Not Classified ENVIRONMENTAL HAZARDS Hazardous to the Aquatic Environment: Not Classified Acute aquatic toxicity: Not Classified Chronic aquatic toxicity: Not Classified Bioaccumulation potential: Not Classified Rapid degradability: Not Classified GHS Label elements, including precautionary statements Pictogram: None Signal Word: None Hazard Statements: None Precautionary Statements: P102 - Keep out of reach of children. P264 - Wash hands thoroughly after handling. SUMMARY OF ACUTE HAZARDS May cause skin irritation. ROUTE OF EXPOSURE, SIGNS AND SYMPTOMS INHALATION Not a respiratory irritant. EYE CONTACT Contact may cause eye irritation. SKIN CONTACT Contact may cause skin irritation. INGESTION Page 14

17 Possible irritation to mucous membranes of the mouth, throat, and stomach. SUMMARY OF CHRONIC HAZARDS None known. MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE Persons with pre-existing skin conditions or chemical allergies may be more susceptible to contact effects of the cured elastomer. Section 3 -- COMPOSITION/INFORMATION ON INGREDIENTS % by WT CAS No. INGREDIENT UNITS None as defined by OSHA Hazard Communication Standard 29 CFR Section 4 -- FIRST AID MEASURES If INHALED: Not a respiratory irritant. If on SKIN: Wash with soap and water. If irritation occurs, seek medical attention. If in EYES: Immediately flush with large amounts of water. If If SWALLOWED: irritation occurs, seek medical attention. If swallowed, call a physician immediately. Only induce vomiting at the instruction of a physician. Never give anything by mouth to an unconscious person. Section 5 -- FIRE FIGHTING MEASURES EXTINGUSING MEDIA Foam, dry chemical, carbon dioxide or water fog. SPECIAL FIRE FIGHTING PROCEDURES: Wear self-contained breathing apparatus (SCBA) and other protective clothing. UNUSUAL FIRE AND EXPLOSION HAZARDS: Fire conditions will activate product causing intumescence to occur. Section 6 -- ACCIDENTAL RELEASE MEASURES STEPS TO BE TAKEN IN CASE MATERIAL IS RELEASED OR SPILLED: Pick up debris to prevent footing hazard. Section 7 -- HANDLING AND STORAGE PRECAUTIONS TO BE TAKEN IN HANDLING AND STORING: Do not store near heat, sparks, or open flames. OTHER PRECAUTIONS: KEEP OUT OF REACH OF CHILDREN. Section 8 -- EXPOSURE CONTROLS/PERSONAL PROTECTION RESPIRATORY PROTECTION (SPECIFY TYPE): None required. VENTILATION - LOCAL EXHAUST: N/A SPECIAL: N/A MECHANICAL (GENERAL): N/A OTHER: N/A PROTECTIVE GLOVES: None required. EYE PROTECTION: None required. OTHER PROTECTIVE CLOTHING OR EQUIPMENT: None required. WORK/HYGIENIC PRACTICES: Where use can result in skin contact, wash exposed areas thoroughly before eating, drinking, smoking, or leaving work area. Launder contaminated clothing before reuse. Section 9 -- PHYSICAL AND CHEMICAL PROPERTIES BOILING POINT: N/A SPECIFIC GRAVITY (H20 = 1): N/A VAPOR PRESSURE (mm Hg): N/A MELTING POINT: N/A VAPOR DENSITY (AIR = 1): N/A EVAPORATION RATE (ETHYL ACETATE = 1): N/A APPEARANCE/ODOR: Black / Mild Odor SOLUBILITY IN WATER: Insoluble VOLATILE ORGANIC COMPOUNDS(VOC)Content (Theoretical Percentage By Weight): Page 15

18 SDS 0320 SAFETY DATA SHEET Section 1 -- PRODUCT AND COMPANY IDENTIFICATION HMIS CODES PRODUCT NAME Health 1 Metacaulk Pipe Collar Flammability 0 Reactivity 0 PPI B PRODUCT CODES 66350, 66351, 66352, 66353, CHEMICAL FAMILY Organic/Inorganic USE Firestopping Material MANUFACTURER'S NAME EMERGENCY TELEPHONE NO. The RectorSeal Corporation Chemtrec 24 Hours 2601 Spenwick Drive (800) USA Houston, Texas USA (703) International DATE OF VALIDATION TECHNICAL SERVICE TELEPHONE NO. January 23, 2015 (800) or (713) DATE OF PREPARATION February 28, 2012 Section 2 -- HAZARDS IDENTIFICATION GHS CLASSIFICATION PHYSICAL HAZARDS: None HEALTH HAZARDS Acute Toxicity: Oral: Not Classified Dermal: Not Classified Inhalation: Not Classified Skin Corrosion/Irritation: Not Classified Serious Eye Damage/Eye Irritation: Not Classified Respiratory or Skin Sensitization: Not Classified Germ Cell Mutagenicity: Not Classified Carcinogenicity: Not Classified Reproductive Toxicology: Not Classified Target Organ Systemic Toxicity - Single Exposure: Not Classified Target Organ Systemic Toxicity - Repeated Exposure: Not Classified Aspiration Toxicity: Not Classified ENVIRONMENTAL HAZARDS Hazardous to the Aquatic Environment: Not Classified Acute aquatic toxicity: Not Classified Chronic aquatic toxicity: Not Classified Bioaccumulation potential: Not Classified Rapid degradability: Not Classified GHS Label elements, including precautionary statements Pictogram: None Signal Word: None Hazard Statements: None Precautionary Statements: P102 - Keep out of reach of children. P264 - Wash hands thoroughly after handling. SUMMARY OF ACUTE HAZARDS May cause skin irritation. ROUTE OF EXPOSURE, SIGNS AND SYMPTOMS INHALATION Not a respiratory irritant. EYE CONTACT Contact may cause eye irritation. SKIN CONTACT Contact may cause skin irritation. INGESTION Page 16

19 Possible irritation to mucous membranes of the mouth, throat, and stomach. SUMMARY OF CHRONIC HAZARDS None known. MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE Persons with pre-existing skin conditions or chemical allergies may be more susceptible to contact effects of the cured elastomer. Section 3 -- COMPOSITION/INFORMATION ON INGREDIENTS % by WT CAS No. INGREDIENT UNITS None as defined by OSHA Hazard Communication Standard 29 CFR Section 4 -- FIRST AID MEASURES If INHALED: Not a respiratory irritant. If on SKIN: Wash with soap and water. If irritation occurs, seek medical attention. If in EYES: Immediately flush with large amounts of water. If If SWALLOWED: irritation occurs, seek medical attention. If swallowed, call a physician immediately. Only induce vomiting at the instruction of a physician. Never give anything by mouth to an unconscious person. Section 5 -- FIRE FIGHTING MEASURES EXTINGUSING MEDIA Foam, dry chemical, carbon dioxide or water fog. SPECIAL FIRE FIGHTING PROCEDURES: Wear self-contained breathing apparatus (SCBA) and other protective clothing. UNUSUAL FIRE AND EXPLOSION HAZARDS: Fire conditions will activate product causing intumescence to occur. Section 6 -- ACCIDENTAL RELEASE MEASURES STEPS TO BE TAKEN IN CASE MATERIAL IS RELEASED OR SPILLED: Pick up debris to prevent footing hazard. Section 7 -- HANDLING AND STORAGE PRECAUTIONS TO BE TAKEN IN HANDLING AND STORING: Do not store near heat, sparks, or open flames. OTHER PRECAUTIONS: KEEP OUT OF REACH OF CHILDREN. Section 8 -- EXPOSURE CONTROLS/PERSONAL PROTECTION RESPIRATORY PROTECTION (SPECIFY TYPE): None required. VENTILATION - LOCAL EXHAUST: N/A SPECIAL: N/A MECHANICAL (GENERAL): N/A OTHER: N/A PROTECTIVE GLOVES: None required. EYE PROTECTION: None required. OTHER PROTECTIVE CLOTHING OR EQUIPMENT: None required. WORK/HYGIENIC PRACTICES: Where use can result in skin contact, wash exposed areas thoroughly before eating, drinking, smoking, or leaving work area. Launder contaminated clothing before reuse. Section 9 -- PHYSICAL AND CHEMICAL PROPERTIES BOILING POINT: N/A SPECIFIC GRAVITY (H20 = 1): N/A VAPOR PRESSURE (mm Hg): N/A MELTING POINT: N/A VAPOR DENSITY (AIR = 1): N/A EVAPORATION RATE (ETHYL ACETATE = 1): N/A APPEARANCE/ODOR: Black / Mild Odor SOLUBILITY IN WATER: Insoluble VOLATILE ORGANIC COMPOUNDS(VOC)Content (Theoretical Percentage By Weight): Page 17

20 SDS 0720 SAFETY DATA SHEET Section 1 -- PRODUCT AND COMPANY IDENTIFICATION HMIS CODES PRODUCT NAME Health 1 Metacaulk Intumescent Sleeve Flammability 0 Reactivity 0 PRODUCT CODES PPI B 66582, CHEMICAL FAMILY Organic/Inorganic USE Intumescent Sleeve MANUFACTURER'S NAME EMERGENCY TELEPHONE NO. The RectorSeal Corporation Chemtrec 24 Hours 2601 Spenwick Drive (800) USA Houston, Texas USA (703) International DATE OF VALIDATION TECHNICAL SERVICE TELEPHONE NO. January 23, 2015 (800) or (713) DATE OF PREPARATION March 20, 2012 Section 2 -- HAZARDS IDENTIFICATION GHS CLASSIFICATION PHYSICAL HAZARDS: None HEALTH HAZARDS Acute Toxicity: Oral: Not Classified Dermal: Not Classified Inhalation: Not Classified Skin Corrosion/Irritation: Not Classified Serious Eye Damage/Eye Irritation: Not Classified Respiratory or Skin Sensitization: Not Classified Germ Cell Mutagenicity: Not Classified Carcinogenicity: Not Classified Reproductive Toxicology: Not Classified Target Organ Systemic Toxicity - Single Exposure: Not Classified Target Organ Systemic Toxicity - Repeated Exposure: Not Classified Aspiration Toxicity: Not Classified ENVIRONMENTAL HAZARDS Hazardous to the Aquatic Environment: Not Classified Acute aquatic toxicity: Not Classified Chronic aquatic toxicity: Not Classified Bioaccumulation potential: Not Classified Rapid degradability: Not Classified GHS Label elements, including precautionary statements Pictogram: None Signal Word: None Hazard Statements: None Precautionary Statements: P102 - Keep out of reach of children. P264 - Wash hands thoroughly after handling. SUMMARY OF ACUTE HAZARDS May cause skin irritation. ROUTE OF EXPOSURE, SIGNS AND SYMPTOMS INHALATION Not a respiratory irritant. EYE CONTACT Contact may cause eye irritation. SKIN CONTACT Contact may cause skin irritation. INGESTION Possible irritation to mucous membranes of the mouth, throat, and stomach. SUMMARY OF CHRONIC HAZARDS None known. Page 18

21 MEDICAL CONDITIONS AGGRAVATED BY EXPOSURE Persons with pre-existing skin conditions or chemical allergies may be more susceptible to contact effects of the cured elastomer. Section 3 -- COMPOSITION/INFORMATION ON INGREDIENTS % by WT CAS No. INGREDIENT UNITS None as defined by OSHA Hazard Communication Standard 29 CFR Section 4 -- FIRST AID MEASURES If INHALED: Not a respiratory irritant. If on SKIN: Wash with soap and water. If irritation occurs, seek medical attention. If in EYES: Immediately flush with large amounts of water. If If SWALLOWED: irritation occurs, seek medical attention. If swallowed, call a physician immediately. Only induce vomiting at the instruction of a physician. Never give anything by mouth to an unconscious person. Section 5 -- FIRE FIGHTING MEASURES EXTINGUSING MEDIA Foam, dry chemical, carbon dioxide or water fog. SPECIAL FIRE FIGHTING PROCEDURES: Wear self-contained breathing apparatus (SCBA) and other protective clothing. UNUSUAL FIRE AND EXPLOSION HAZARDS: Fire conditions will activate product causing intumescence to occur. Section 6 -- ACCIDENTAL RELEASE MEASURES STEPS TO BE TAKEN IN CASE MATERIAL IS RELEASED OR SPILLED: Pick up debris to prevent footing hazard. Section 7 -- HANDLING AND STORAGE PRECAUTIONS TO BE TAKEN IN HANDLING AND STORING: Do not store near heat, sparks, or open flames. OTHER PRECAUTIONS: KEEP OUT OF REACH OF CHILDREN. Section 8 -- EXPOSURE CONTROLS/PERSONAL PROTECTION RESPIRATORY PROTECTION (SPECIFY TYPE): None required. VENTILATION - LOCAL EXHAUST: N/A SPECIAL: N/A MECHANICAL (GENERAL): N/A OTHER: N/A PROTECTIVE GLOVES: None required. EYE PROTECTION: None required. OTHER PROTECTIVE CLOTHING OR EQUIPMENT: None required. WORK/HYGIENIC PRACTICES: Where use can result in skin contact, wash exposed areas thoroughly before eating, drinking, smoking, or leaving work area. Launder contaminated clothing before reuse. Section 9 -- PHYSICAL AND CHEMICAL PROPERTIES BOILING POINT: N/A SPECIFIC GRAVITY (H20 = 1): N/A VAPOR PRESSURE (mm Hg): N/A MELTING POINT: N/A VAPOR DENSITY (AIR = 1): N/A EVAPORATION RATE (ETHYL ACETATE = 1): N/A APPEARANCE/ODOR: Black / Mild Odor SOLUBILITY IN WATER: Insoluble VOLATILE ORGANIC COMPOUNDS(VOC)Content (Theoretical Percentage By Weight): Page 19

22 PRODUCT DATA SHEET Metacaulk 1000 Firestopping Sealant April 2016 For list of systems see metacaulk.com 1. Product Description Metacaulk 1000 is a one component, general purpose fire rated sealant and smoke seal for construction joints and through-penetrations. Metacaulk 1000 is a water based, extremely intumescent, non-sag caulking grade sealant that is easy to apply as well as to retrofit. It cures to an elastomeric seal that is suitable where dynamic movement is expected. In the event of a fire, Metacaulk 1000 will prevent the spread of flames, smoke, hot gases and water through joint openings and throughpenetrations. No dilution or mixing is required for use. No special skills are necessary for installation. Metacaulk 1000 is applied with a conventional caulking gun, bulk loading gun or can be troweled from the pail. For large applications, it can be pumped directly from the pail. Metacaulk 1000 systems are rated for 1, 2, 3 and 4 hours in accordance with the ASTM E814 (UL1479),UL 2079 and ULC-S test standards. Metacaulk 1000 is protected in a wet stage as well as in a dry stage against mold growth with a combination of biocides. Use Metacaulk 1000 for various applications: Top of the Wall Construction Joints Deflection Track Wall Systems Up to 2" (51 mm) PVC\CPVC (Open) Up to 3" (76 mm)pvc\cpvc & ABS (Closed) Crosslinked Polyethylene (PEX) tubing Steel, Copper, Cast Iron and EMT Pipe Flexible Conduit Fiberglass Insulated Pipe Armaflex Insulated Pipe Telephone, Communication and Power Cables HVAC Ductwork For a complete list of product applications or for additional technical information, call RECTORSEAL for the latest updated information. Metacaulk 1000 Features Water Based Excellent Freeze-Thaw Flexible Set Highly Intumescent Paintable VOC Compliant Safe and Easy to Use Minimum 3 Year Shelf Life 2. Material Properties Asbestos Fillers None Solvents None Hazardous Ingredients None Application Caulking Gun or Trowel Application temperature between 40 F F 4 C - 49 C Activation of Intumescence: Expansion Begins 375 F (190 C) Expansion Greatest 575 (302 C) to 1100 F(593 C) Color Red Cure Time 3 t o 4 weeks (at 77 F/ 25 C) Density /- 0.5 lbs./gal kg/l Elastomeric Freeze-Thaw Skin Over Time Yes Excellent 30 min. (at 77 F/ 25 C) ph Value 6.5 to 7 Volume Coverage: for 10.3 oz. tube (304ml) 18 cu. in. (295 cc) for 5 gallon (18.9 liter) 1155 cu. in. (5000 cu. cm/l) VOC Negligible ASTM E 84, UL 723 Tunnel Test Flame Spread 0 Smoke Index 0 Sound Transmission Class STC 62* *Tested in a UL 411 wall assembly/section to ASTM E Applications Metacaulk 1000 can be used in interior applications as a general purpose fire rated sealant and smoke seal for construction joints on both Page 20

23 METACAULK 1000 vertical and horizontal surfaces. Metacaulk 1000 is also an excellent fire rated acoustical sealant and can be used in areas under constant vibration or movement. Metacaulk 1000 can also be used on various penetrations such as EMT, telephone & power cables, insulated pipes, etc. in concrete floors and walls, gypsum walls as well as wood floors. Use Metacaulk 1000 to prevent the spread of fire and smoke through joints in fire rated gypsum wallboard partitions, concrete block or concrete walls and/ or concrete or corrugated steel deck floor/ceiling assemblies. 4. Installation Data Install Metacaulk 1000 using standard caulking techniques or trowel from pails. Metacaulk 1000 may also be pumped from the pails. When damming materials are needed, use only materials approved for the specific application. TYPICAL TOP OF WALL INSTALLATION Step 1) Cut and fit the gypsum wallboard to the contour of the steel decking leaving a maximum 3/4" (19 mm) relief gap. Step 2) Pack the flute openings and relief gap with required amount of fiberglass insulation and recess to required depth. Step 3) Gun, trowel or pump the sealant as required to the specified depth. Properly tool sealant surface flush with the wall. Consult UL Directory for complete instructions and system listings. Metacaulk 1000 was tested at positive pressure with a minimum 0.01 (2.5 Pa) inches water and in accordance with ASTM E814 (UL 1479), UL 2079 and ULC-S Complies to Required Environmental Exposure Testing of Accelerated Aging and High Humidity as per UL 1479 Fire Test of Through-Penetration Firestops. FBC System Compatible indicates that this product has been tested, and is monitored on an ongoing basis, to assure its chemical compatibility with FlowGuard Gold, BlazeMaster and Corzan pipe and fittings. FBC, FlowGuard Gold, BlazeMaster and Corzan are licensed trademarks of the Lubrizol corporation. 6. Storage & Handling Metacaulk 1000 should be stored between 35 F (2 C) and 120 F (49 C). to obtain a minimum 3 year shelf life. NOTE: Do not dilute, no mixing is required. Best if protected from freezing. If freezing occurs, thaw completely before using. Keep products stored under protective cover in original containers. 7. Availability Metacaulk 1000 is available in 10.3 oz. (304 ml), 30 oz.(887 ml) caulking tubes and 20.2 oz. (597 ml) sausage pack and in 5 gallon (18.9 L) pails. 8. Limitations Metacaulk 1000 is not designed to be used in areas under continuous immersion or in areas which would be continuously wet. Metacaulk 1000 should not be used against hot uninsulated surfaces above 300 F (149 C). 9. Cautions FOR CHEMICAL EMERGENCY, SPILL, LEAK, FIRE, EXPOSURE OR ACCIDENT, CALL CHEMTREC-DAY OR NIGHT PRECAUTIONS: Do not take internally. May be harmful if swallowed. May cause eye and skin irritation if prolonged or repeated contact occurs. Wash after handling. FIRST AID: For any overexposure, get immediate medical attention after first aid is given. Eyes- Flush 15 minutes with clean water. Skin-Wash with soap and water. Inhalation-Remove to fresh air. Ingestion-Only if conscious, give large amounts of water and INDUCE VOMITING. FIRE AND SPILLS: Use water fog, CO 2, foam, or dry chemicals. Wipe up spills to prevent footing hazard. Clean up with scrapers and water. STORAGE AND HANDLING: Store away from heat sources. Keep container closed. Do not reuse empty container. KEEP OUT OF REACH OF CHILDREN. For additional information, refer to Material Safety Data Sheet. For additional technical service, call: fax: Testing Data For specific test criteria, refer to the UL's Fire Resistance Directory or Warnock Hersey International Listing Directory or call RECTORSEAL 10. LIMITED WARRANTY RectorSeal makes the Limited Express Warranty that when the instructions for storage and handling of our products are followed we warrant our products to be free from defects. THIS LIMITED EXPRESS WARRANTY IS EXPRESSLY IN LIEU OF ANY OTHER EXPRESS OR IMPLIED WARRANTIES, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PAR- TICULAR PURPOSE, AND OF ANY OTHER OBLIGATION ON THE PART OF RECTORSEAL. The sole remedy for breach of the Limited Express Warranty shall be the refund of the purchase price. All other liability is negated and disclaimed, and RectorSeal shall not be liable for incidental or consequential damages. Suggestions and recommendations covering the use of our products are based on our past experience and laboratory findings. However, as we have no control as to the methods and conditions of application, we only assume responsibility for the uniformity of our products within manufacturing tolerances. D-16 Page 21

24 PRODUCT DATA SHEET Metacaulk MC150+ Firestopping Sealant April 2016 For list of systems see metacaulk.com 1. Product Description Metacaulk MC 150+ is a one component, general purpose fire rated sealant and smoke seal for construction joints and throughpenetrations. Metacaulk MC 150+ is a water based, non-sag caulking grade sealant that is easy to apply as well as to retrofit. It cures to an elastomeric seal that is suitable where dynamic movement is expected. In the event of a fire, Metacaulk MC 150+ will prevent the spread of flames, smoke, hot gases and water through joint openings and through-penetrations. No dilution or mixing is required for use. No special skills are necessary for installation. Metacaulk MC 150+ is applied with a conventional caulking gun, bulk loading gun or can be troweled from the pail. For large applications, it can be pumped directly from the pail. Metacaulk MC 150+ systems are rated for up to 4 hours in accordance with ASTM E814 (UL1479) and ASTM E1966 (UL 2079) test standards. MC 150+ is protected in a wet stage as well as in a dry stage against mold growth with a combination of biocides. Use Metacaulk MC 150+ for various applications: Top of the Wall Construction Joints Deflection Track Wall Systems Up to 2" (51 mm)pvc/cpvc & ABS (Closed) Crosslinked Polyethylene (PEX) tubing Steel, Copper, Cast Iron and EMT Pipe Telephone, Communication and Power Cables For a complete list of product applications or for additional technical information, call RECTORSEAL for the latest information. Metacaulk MC 150+ Features Water Based Excellent Freeze-Thaw Flexible Set Paintable VOC Compliant Safe and Easy to Use Minimum 3 Year Shelf Life Intumescent 2. Material Properties Asbestos Fillers None Solvents None Hazardous Ingredients None Application Caulking Gun or Trowel Application temperature between 40 F F 4 C - 49 C Color Cure Time Red 3 to 4 weeks (at 77 F/ 25 C) Density /- 0.5 lbs./gal. Elastomeric Freeze-Thaw Skin Over Time 25 C) Yes Excellent ph Value 7 to 8 Volume Coverage: 30 min. (at 77 F/ for 10.3 oz. tube (304ml) 18 cu. in. (295 cm 3 ) for 5 gallon (18.9 liter) VOC 1155 cu. in. (18,927 cm 3 ) Negligible ASTM E 84, UL 723 Tunnel Test Flame Spread 10 Smoke Index 0 Sound Transimission Class STC Rating 51* *Tested in a UL 411 wall assembly/section to ASTM E Applications Metacaulk MC 150+ can be used in interior applications as a general purpose fire rated sealant and smoke seal for construction joints on both vertical and horizontal surfaces. Metacaulk MC 150+ is also an excellent fire rated acoustical sealant and can be used in areas under constant vibration or movement. Metacaulk MC 150+ can also be used on various penetrations such as EMT, telephone & power cables in concrete floors and walls, gypsum walls as well as wood floors. Use Metacaulk MC 150+ to prevent the spread of fire and smoke through joints in fire rated gypsum wallboard partitions, concrete block or concrete walls and/ or concrete or corrugated steel deck floor/ceiling assemblies. 4. Installation Data Install Metacaulk MC 150+ using standard caulking techniques or trowel from pails. Metacaulk MC 150+ may also be pumped from the pails. When damming materials are needed, use only materials approved for the specific application. Page 22

25 METACAULK MC 150+ TYPICAL GYPSUM WALLBOARD INSTALLATION Step 1) Cut opening in wall. Step 2) Clean penetration opening and surfaces from loose debris, dirt, oil and wax. Step 3) If required, install sleeve or wire mesh and backing material. STEP 4) Gun the sealant as required to the specified depth. Trowel surface flush with wall. (Application designs vary, please contact RectorSeal for exact details.) Consult UL Directory for complete instructions and system listings. 5. Testing Data For specific test criteria, refer to UL's Fire Resistance Directory or call RECTORSEAL. Metacaulk MC 150+ was tested at positive pressure with a minimum 0.01 (2.5 Pa) inches water and in accordance with ASTM E814 (UL 1479) and ASTM E1966 (UL 2079). FBC System Compatible* indicates that this product has been tested, and is monitored on an ongoing basis, to assure its chemical compatibility with FlowGuard Gold, BlazeMaster and Corzan pipe and fittings. FBC, FlowGuard Gold, BlazeMaster and Corzan are licensed trademarks of the Lubrizol Corporation. 6. Storage & Handling Metacaulk MC 150+ should be stored between 35 F (2 C) and 120 F (49 C) to obtain a minimum 3 year shelf life. NOTE: Do not dilute, no mixing is required. Best if protected from freezing. If freezing occurs, thaw completely before using. Keep products stored under protective cover in original containers. 7. Availability Metacaulk MC 150+ is available in 10.3 oz. (304 ml) and 30 oz.(887 ml) caulking tubes, 20.2 oz. (597 ml) sausage packs and in 5 gallon (18.9 L) pails. 8. Limitations Metacaulk MC 150+ is not designed to be used in areas under continuous immersion or in areas which would be continuously wet. Metacaulk MC 150+ should not be used against hot uninsulated surfaces above 300 F (149 C). 9. Cautions FOR CHEMICAL EMERGENCY, SPILL, LEAK, FIRE, EXPOSURE OR ACCIDENT, CALL CHEMTREC-DAY OR NIGHT PRECAUTIONS: Do not take internally. May be harmful if swallowed. May cause eye and skin irritation if prolonged or repeated contact occurs. Wash after handling. FIRST AID: For any overexposure, get immediate medical attention after first aid is given. Eyes- Flush 15 minutes with clean water. Skin-Wash with soap and water. Inhalation-Remove to fresh air. Ingestion-Only if conscious, give large amounts of water and INDUCE VOMITING. FIRE AND SPILLS: Use water fog, CO 2, foam, or dry chemicals. Wipe up spills to prevent footing hazard. Clean up with scrapers and water. STORAGE AND HANDLING: Store away from heat sources. Keep container closed. Do not reuse empty container. KEEP OUT OF REACH OF CHILDREN. For additional information, refer to Material Safety Data Sheet. For additional technical service, call: fax: RECTORSEAL 2601 Spenwick Drive, HOUSTON, TEXAS LIMITED WARRANTY RectorSeal makes the Limited Express Warranty that when the instructions for storage and handling of our products are followed we warrant our products to be free from defects. THIS LIMITED EXPRESS WARRANTY IS EXPRESSLY IN LIEU OF ANY OTHER EXPRESS OR IMPLIED WARRANTIES, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PAR- TICULAR PURPOSE, AND OF ANY OTHER OBLIGATION ON THE PART OF RECTORSEAL. The sole remedy for breach of the Limited Express Warranty shall be the refund of the purchase price. All other liability is negated and disclaimed, and RectorSeal shall not be liable for incidental or consequential damages. Suggestions and recommendations covering the use of our products are based on our past experience and laboratory findings. However, as we have no control as to the methods and conditions of application, we only assume responsibility for the uniformity of our products within manufacturing tolerances. D-16 Page 23

26 PRODUCT DATA SHEET Metacaulk Wrap Strip May 2015 Classified Through-Penetration Fire Stop System Numbers For list of systems see metacaulk.com 1. Product Description A strip of highly intumescent firestop material used primarily for plastic and insulated pipe applications. When exposed to heat, this product expands and forms a hard char to seal off the penetration preventing the passage of flames and hot gases. Metacaulk Wrap Strip Features Easy to install Cost effective Versatile, Flexible Highly intumescent Excellent freeze/thaw characteristics Long length means less waste Forms a very hard char when burned 2. Material Properties Asbestos Fillers Solvents Hazardous Ingredients None None None Size (Approx.) 1" x 1/4" x 12' 25 mm x 6 mm x 3.66 m 2" x 1/4" x 12' 50 mm x 6 mm x 3.66 m Activation of Intumescence: Expansion Begins 375 F (190 C) Expansion Greatest 575 (302 C) to 1100 F (593 C) Color Freeze-Thaw Black Excellent ASTM E 84, UL 723 Tunnel Test Flame Spread 5 Smoke Index 5 3. Applications Metacaulk Wrap Strip can firestop difficult penetrations such as plastic pipe, and insulated pipe. 4. Installation Data Metacaulk Wrap Strip is simple to install. Tightly wrap the required number of strips continuously around the penetrant to completely fill the annular space or as required by system design. Push the strips into the opening to the required depth. If a cold smoke seal is required, apply the recommended sealant in the opening over the strips. Consult UL Directory for complete instructions and system listings. 5. Testing Data Metacaulk Wrap Strip is classified by Underwriters Laboratories as a Fill, Void or Cavity Material. For specific test criteria, see UL Fire Resistance Directory or call RectorSeal. Metacaulk Wrap Strip was tested at positive pressure for a minimum.01 inches (2.5 Pa) of water in accordance with UL 1479 and ASTM E 814 test standards. Complies to Required Environmental Exposure Testing of Accelerated Aging and High Humidity as per UL 1479 Fire Test of Through-Penetration Firestops. FBC System Compatible* indicates that this product has been tested, and is monitored on an ongoing basis, to assure its chemical compatibility with FlowGuard Gold, BlazeMaster and Corzan pipe and fittings. FBC, FlowGuard Gold, BlazeMaster and Corzan are licensed trademarks of the Lubrizol Corporation. 6. Storage & Handling Metacaulk Wrap Strip should be stored in a cool, dry place. Keep products stored under protective cover, in their original containers. A stock rotation program is recommended. Page 24

27 METACAULK WRAP STRIP 7. Availability Metacaulk Wrap Strip is available in: 12 foot (3.66 m) roll boxes. 8. Limitations To be used only in the tested configurations or as recommended by RectorSeal. 9. Cautions FOR CHEMICAL EMERGENCY, SPILL, LEAK, FIRE, EXPOSURE OR ACCIDENT, CALL CHEMTREC-DAY OR NIGHT PRECAUTIONS: Do not take internally. May be harmful if swallowed. May cause eye and skin irritation if prolonged or repeated contact occurs. Wash after handling. FIRST AID: For any overexposure, get immediate medical attention after first aid is given. Eyes- Flush 15 minutes with clean water. Skin-Wash with soap and water. Ingestion-Only if conscious, give large amounts of water and INDUCE VOMITING. FIRE AND SPILLS: Use water fog, CO 2, foam, or dry chemicals. Wipe up spills to prevent footing hazard. Clean up with scrapers and water. STORAGE AND HANDLING: Store away from heat sources. KEEP OUT OF REACH OF CHILDREN. For additional information, refer to Material Safety Data Sheet. For additional technical service, call: or fax: or RECTORSEAL 2601 Spenwick Drive, HOUSTON, TEXAS LIMITED WARRANTY RectorSeal makes the Limited Express Warranty that when the instructions for storage and handling of our products are followed we warrant our products to be free from defects. THIS LIMITED EXPRESS WARRANTY IS EXPRESSLY IN LIEU OF ANY OTHER EXPRESS OR IMPLIED WARRANTIES, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PAR- TICULAR PURPOSE, AND OF ANY OTHER OBLIGATION ON THE PART OF RECTORSEAL. The sole remedy for breach of the Limited Express Warranty shall be the refund of the purchase price. All other liability is negated and disclaimed, and RectorSeal shall not be liable for incidental or consequential damages. Suggestions and recommendations covering the use of our products are based on our past experience and laboratory findings. However, as we have no control as to the methods and conditions of application, we only assume responsibility for the uniformity of our products within manufacturing tolerances. E-15 Page 25

28 PRODUCT DATA SHEET Metacaulk Pipe Collar Classified Through-Penetration Fire Stop System Numbers For list of systems see metacaulk.com November Product Description Metacaulk Pipe Collars are prefabricated for open and closed through-penetration firestop systems using 1 1/2"(38 mm) to 6" (152 mm) plastic pipe. An easy locking tab assures easy installation. The collar design greatly reduces the time and expense that is required to install competitive collars. Metacaulk Pipe Collar Features Saves on Labor Cost Easy Installation Economical No Measurement of Material Required Highly Intumescent Tested for PVC, CPVC, ABS and PVC/ABS Foam Core, FRPP 2. Material Properties Asbestos Fillers Solvents Hazardous Ingredients Activation of Intumescence: None None None 3. Applications Metacaulk Pipe Collars are used to seal off plastic pipe both in closed and vented (DWV) conditions. Also for use on up to 6" (152 mm) diameter ABS (cellular core or solid core), FRPP, PVC and CPVC pipe. The collar may be used on up to 3 hour rated concrete floors and walls, up to 2 hour rated gypsum walls and up to 2 hour rated wood floors. 4. Installation Data Metacaulk Pipe Collar are prefilled and very easy to install. 1) Select the proper collar to fit the diameter of pipe used. 2) Making sure annular space is within the limits set by the tested conditions, attach collar around the pipe on the underside of the floor or to each side of a wall by firmly placing against the wall or floor and securing interlocking tabs [1 1/2" (38 mm), 2" (51 mm), 3" (76 mm) and 4" (102 mm)] or fastening the buckle [6" (152 mm)]. 3) If needed, mark and predrill wall or floor for required anchors. Properly secure the appropriate anchor into each of the anchoring tabs. In concrete, use 1/4" (6 mm) x 1 1/4" (32 mm) hex washer head type concrete anchors or appropriate steel expansion/ wedge anchors. In gypsum, use 1/8" (3 mm) x 2" (51 mm)molly type hollow wall anchors or 1 1/2" drywall or drywall laminating screws. Fender washers have been provided to be used with the fasteners. 4) If an additional smoke seal is required, Metacaulk 1000 may be applied within the annular space before the attachment of the collar. Consult UL Directory for complete instructions and system listings. Expansion Begins 375 F (190 C) Expansion Greatest 575 (302 C) to 1100 F (593 C) 5. Testing Data Metacaulk Pipe Collars are classified by Underwriters Laboratories as a Firestop Device. For specific test criteria, see the UL Fire Resistance Directory or Page 26

29 METACAULK PIPE COLLAR call RectorSeal. Metacaulk Pipe Collars were tested at a minimum.01 inches (2.5 Pa) of water positive pressure in accordance with UL 1479 (ASTM E814) test standards. Complies to Required Environmental Exposure Testing of Accelerated Aging and High Humidity as per UL 1479 Fire Test of Through-Penetration Firestops. 8. Limitations Not for use in outdoor environments where long-term exposure to rainfall or saltwater spray may occur. No other limitations known if used as directed. 9. Cautions KEEP OUT OF REACH OF CHILDREN. FBC System Compatible* indicates that this product has been tested, and is monitored on an ongoing basis, to assure its chemical compatibility with FlowGuard Gold, BlazeMaster and Corzan pipe and fittings. FBC, FlowGuard Gold, BlazeMaster and Corzan are licensed trademarks of the Lubrizol Corporation. For additional technical service, call: or fax: or RECTORSEAL 2601 Spenwick Drive, HOUSTON, TEXAS Storage & Handling Metacaulk Pipe Collars should be stored in a dry place. Keep product stored under protective cover in original container. 7. Availability Metacaulk Pipe Collars are available for 1 1/2" (38 mm), 2" (51 mm), 3" (76 mm), 4" (102 mm) and 6" (152 mm)(trade diameter) plastic pipe. 10. LIMITED WARRANTY RectorSeal makes the Limited Express Warranty that when the instructions for storage and handling of our products are followed we warrant our products to be free from defects. THIS LIMITED EXPRESS WARRANTY IS EXPRESSLY IN LIEU OF ANY OTHER EXPRESS OR IMPLIED WARRANTIES, INCLUDING ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PAR- TICULAR PURPOSE, AND OF ANY OTHER OBLIGATION ON THE PART OF RECTORSEAL. The sole remedy for breach of the Limited Express Warranty shall be the refund of the purchase price. All other liability is negated and disclaimed, and RectorSeal shall not be liable for incidental or consequential damages. Suggestions and recommendations covering the use of our products are based on our past experience and laboratory findings. However, as we have no control as to the methods and conditions of application, we only assume responsibility for the uniformity of our products within manufacturing tolerances. H-16 Page 27

30 PRODUCT DATA SHEET Metacaulk Intumescent Sleeve Classified Through-Penetration Fire Stop System Numbers For list of systems see metacaulk.com May Product Description Metacaulk Intumescent Sleeve is a firestop seal for PVC, cc- PVC, CPVC, FRPP, PP, ABS and PVDF pipe and rigid non-metallic conduit installations. Easily installed without modifications, steel bolts or fasteners, the Intumescent Sleeve is an ideal approach for firestopping combustible pipes penetrating the uneven contours of a concrete fluted deck assembly. It eliminates the need for collars or wrap strips and is great for use on pipes that penetrate walls at less than a 90º angle. It also eliminates the need to firestop on both sides of a penetration. The Intumescent Sleeve easily wraps around pipes and is manufactured from a durable galvanized steel outer shell that is lined with a highly intumescent material. The Sleeve is fastened with either fiberglass tape, pop rivets or hose clamps around the pipe. When used with Metacaulk 1000 or 150+ Sealant, it produces an immediate smoke seal. Metacaulk Intumescent Sleeve Features Saves on Labor Cost Easy Installation Economical No Measurement of Material Required Can be retrofitted, easily removed and replaced Highly Intumescent Tested for PVC, CPVC, ABS and PVC/ABS Foam Core, FRPP, PP, PVDF 2. Material Properties Asbestos Fillers Solvents Hazardous Ingredients Activation of Intumescence: None None None Expansion Begins 375 F (190 C) 3. Applications Metacaulk Intumescent Sleeve will firestop both sides of wall when installed from either side and provides a cost-effective alternative to collars for pipes going through walls and floors. The Sleeve can also be used in applications that require retrofit. The Intumescent Sleeve can be used with PVC, cc-pvc, CPVC, FRPP, PP, ABS and PVDF pipe and rigid, nonmetallic conduits in sizes ranging from 2 in to 8.0 in. The Sleeve has been tested for use in concrete floor/ wall installations and concrete fluted deck assembly. For application with 8 in. (20 cm) diameter or smaller PVC and CPVC, the sleeve has been approved with an optional sleeve (S/10 or heavier) cast or grouted into the floor or wall. 4. Installation Data RectorSeal Intumescent Sleeves are pre-firestopped and very easy to install 1) Select the proper sleeve to fit the diameter of pipe used Use the 234 sleeve for 2 in. (51 mm) or 3 in. (76 mm) or 4 in. (102 mm) diameter pipe OR the 68 sleeve for 6 in. (152 mm) or 8 in. (203 mm) diameter pipe. 2) Determine the number of Sleeves required for application. 3) Determine method of sleeve fastening to be used (fiberglass tape, pop rivets, hose clamps or tie wire). 4) For installation, wrap the sleeve around pipe from above or below floor or either side of wall with the intumescent material side facing pipe, allowing bare metal end to overlap approximately 2 in. (51 mm). 5) Secure the sleeve around pipe with selected fastening method. 6) Push/slide the sleeve through assembly so that it is centered within floor and/or ceiling or centered Page 28