NYC Department of Education

Size: px
Start display at page:

Download "NYC Department of Education"

Transcription

1 Architectural Inspection Building Assessment Survey Asset: P.S QUEENS, AVENUE, New York, Inspection Id Inspection Type Time In Last Edited SA : Architectural - Senior :02 AM :35 AM AA : Architectural - Associate :01 AM :32 PM Asset Data Was the building fully accessible for inspection Inspection Access Comment Principal(s) Information Custodian Fireman Principal Name Organization Did you meet with this Principal? Did this Principal provide feedback? Summary of Principal's Feedback Answer Building Square Footage Comments on the Area Comments on the Stories (Floors) plus Basements 3+B Comments on the Number of Classrooms 35 No 2nd Floor Locker Room Shower Megan McCauley P.S Queens Yes Yes The Principal provided the following comments: 1 - The Student Toilet Rooms need an upgrade to the ceramic Floor and Wall Tiles; many of the tiles are cracked or broken with no bond to the wall. 2 - The Plumbing fixtures in all Student Toilet Rooms are out of date and require to be upgraded. Steven Cayea Jr. Was not present None Comments on the Year Built 1955 Student Population 520 Staff Population 105 Weather Facade Photo Fair 67th Avenue - Southwest view PB/A&W Page 1 of 42

2 Main Entrance Photo Building Assessment Survey Roof Photo Facade A - 67th Avenue Roof 2 - East View Have any Systems/Major Building Components been upgraded? Yes Systems: All Areaway metal Grating replacement with galvanized Gratings Year: 2015 Systems: Exterior Modernization Project including: All new Modified Bitumen Roofs; partial rebuilding of Parapets and repointing; New Coping and Flashing; Parapet attached Roof Barriers and non-attached Roof Barriers; limited Chimney repointing; Bulkhead repointing and Door installations; partial exterior Brick Wall repointing and repair; Auditorium Seating Year: 2014 Systems: Auditorium Stage and Window Curtain replacement Year: 2013 Systems: Entire sidewalk replaced at 67th Avenue and 230th Street; Eighty percent of VCT Flooring was replaced throughout the building. Year: 2010 Systems: Basement Flood elimination injections completed in Boiler Room Pit Year: 2008 Systems: Elevator installed - Roof 1 PB/A&W Page 2 of 42

3 Have there been any New Building Additions? Tandem Schools? Leased Space? Priority Building Assessment Survey Year: 2005 Systems: All Windows, Window Guards and Shades replacement; Irma Roofs (Roofs 2 and 3) replaced Year: 2001 Systems: All Parapets rebuilt Year: 2000 No No No Priority Exist Last Year? Priority Category Description Component Affected Location Description Person(s) Notified Person(s) Title PhotoImage No condition recorded Structural Engineer Required Structural Type Description Component Affected Location Description Person(s) Notified Person(s) Title PhotoImage No condition recorded Accessibility Accessibility Status Is the primary or secondary entrance on an accessible route? Is the building a multi-story building? Are all floors of the building accessible through compliant means? Accessible classrooms exists on each floor? Boys and Girls or Unisex accessible toilets exist on at least every other floor? If the following spaces exist, are they ALL accessible? Art Room, Auditorium, Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs Yes Yes Yes Yes Yes Yes Physical Breakdown Structure Exists Complies Required FUNCTIONAL ACCESSIBILITY Exterior Routes Exterior Entrances & Exits Yes Exterior H/C Lifts No No Exterior Ramps and Railings Yes Yes Interior Routes Corridor and Lobby H/C Lifts No No Interior Corridor Doors and Hardware Yes Yes Interior Corridors and Lobbies Yes Interior Elevators Yes Yes Interior Lobby Doors and Hardware Yes Interior Ramps No Rooms & Spaces Art Rooms Room 205 Yes Auditorium 1st Floor Yes Cafeteria 1st Floor Yes Classrooms 1st - 3rd Floor Yes Computer Rooms Room 104 Yes Gymnasium 1st Floor Yes Library Room 212/214 Yes Main Office Room 126 (P.S. 213), Room 325 (P4) Yes PB/A&W Page 3 of 42

4 Building Assessment Survey Physical Breakdown Structure Exists Complies Required Rooms & Spaces Multi-purpose Room Nurse's Room Room 103 (P.S. 213), Room 303 (P4) Yes Pool Science Lab Toilet Rooms (Boys) 1st and 3rd Floor No Water Closet Arrangement Urinal Arrangement No No No 2nd Floor No Clear opening < 32" Urinal Arrangement Water Closet Arrangement Insufficient Latch Clearance Toilet Rooms (Girls) 1st and 3rd Floor No Water Closet Arrangement 2nd Floor No Clear opening < 32" Insufficient Latch Clearance Water Closet Arrangement Toilet Rooms (Staff) 1st - 2nd Floor Yes Building Template Inspection Architectural EXTERIOR AREAWAY Instance on AW1-AW4 Instance Instance Quantity 4 Instance EACH AWNINGS AND CANOPIES 3 - Fair CONCRETE: EXPOSED REBAR PB/A&W Page 4 of 42

5 EXTERIOR AWNINGS AND CANOPIES Roof Plan reference Building Assessment Survey Quantity 50 REPAIR Photo1 West Exit CHIMNEY Material Type(s) COPING CORNICE DOORS DOORS AND FRAMES Masonry 3 - Fair ROLL-UP DOOR: DETERIORATED DOOR AND FRAME - MINOR DETERIORATION Roof Plan reference Quantity 1 EACH MAINTENANCE PB/A&W Page 5 of 42

6 EXTERIOR DOORS DOORS AND FRAMES Photo1 Building Assessment Survey Facade I DOOR HARDWARE 3 - Fair LINTELS TRANSOM/SIDE LIGHT EXTERIOR WALLS Material Type(s) Masonry, Concrete Replacement Quantity 28,500 Replacement Uom Instance on All Facades Instance 3 - Fair Instance Quantity 28,500 Instance BRICK: OPEN JOINTS Roof Plan reference Elevation Quantity 400 PB/A&W Page 6 of 42

7 Building Assessment Survey Architectural Inspection EXTERIOR EXTERIOR WALLS REPOINT Photo1 Roof Plan reference Facade A BRICK: MINOR CRACKS AND SPALLING Elevation Quantity 20 RESTITCH Photo1 Facade D PB/A&W Page 7 of 42

8 EXTERIOR EXTERIOR WALLS Roof Plan reference Building Assessment Survey BRICK: MAJOR / THRU CRACKS Elevation Quantity 10 REMOVE AND REBUILD Urgency of Action PRIORITY 4 Photo1 Roof Plan reference Facade D, at Facade E BRICK: DETERIORATED MASONRY SILLS PB/A&W Page 8 of 42

9 EXTERIOR EXTERIOR WALLS Elevation Building Assessment Survey Quantity 20 L.F. REPAIR Photo1 Roof Plan reference Facade E CAST IN PLACE / PRE-CAST CONCRETE: MINOR CRACKS, SPALLED, DETERIORATED REBAR Elevation Quantity 10 REPAIR PB/A&W Page 9 of 42

10 Building Assessment Survey Architectural Inspection EXTERIOR EXTERIOR WALLS Photo1 Facade A EXTERIOR SOFFITS LOADING DOCK LOUVER PARAPETS Material Type(s) Masonry Replacement Quantity 4,500 Replacement Uom C.F. Instance on Facades D, F, G, H, K Instance 3 - Fair Instance Quantity 4,500 Instance C.F. BRICK: MINOR CRACKS, SPALLING Roof Plan reference Quantity 70 REPAIR PB/A&W Page 10 of 42

11 EXTERIOR PARAPETS Photo1 Building Assessment Survey Roof 2 - Facade L PLAZA DECK ROOF Roofing Replacement Quantity 38,500 Replacement Uom ROOF HATCH/SMOKE HATCH LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS ROOF BARRIER ROOF CAGE ROOF FENCE ROOFING Instance on Modified Bitumen: All Roofs Instance 1 - Good 1 - Good Instance Quantity 38,500 Instance Does the roof have major mechanical equipment sitting on Dunnage Steel less than 18" above the Roofing? Installation Year 2014 Source of Installation ROOFING DRAINS Specialties BULKHEAD/PENTHOUSE CUPOLA/ SPIRES/ TOWERS DORMER DUNNAGE STEEL SKYLIGHT/ROOF VENT Material Type(s) No Documented 1 - Good Glass PB/A&W Page 11 of 42

12 Building Assessment Survey Architectural Inspection EXTERIOR ROOF Specialties SKYLIGHT/ROOF VENT ROOF/GRAVITY TANK STAIRS/RAMPS: EXTERIOR BUILDING CHEEK/FLANK WALLS RAILINGS 4 - Between Fair and Poor BROKEN BRACKET Roof Plan reference Quantity 1 EACH Photo1 Roof Plan reference Exit DAMAGED Quantity 10 L.F. PB/A&W Page 12 of 42

13 EXTERIOR STAIRS/RAMPS: EXTERIOR RAILINGS Photo1 Building Assessment Survey STAIRS/RAMPS Roof Plan reference Facade H - Exit 4 - Between Fair and Poor STONE: OPEN JOINTS Quantity 10 L.F. REPOINT Photo1 Roof Plan reference Exit 8 - entry platform STONE: CRACKS, SPALLING Quantity 10 PB/A&W Page 13 of 42

14 Building Assessment Survey Architectural Inspection EXTERIOR STAIRS/RAMPS: EXTERIOR STAIRS/RAMPS Photo1 Roof Plan reference Exit 8 entry platform CONCRETE: WORN-OUT TREAD/RISER/NOSING Quantity 10 Photo1 West access Steps to playard CONCRETE: CRACKS/SPALLING - MAJOR PB/A&W Page 14 of 42

15 EXTERIOR STAIRS/RAMPS: EXTERIOR STAIRS/RAMPS Roof Plan reference Building Assessment Survey Quantity 10 Photo1 Exit 10 steps WINDOWS Replacement Quantity 7,000 Replacement Uom EXTERIOR GUARDS 3 - Fair RUST - MINOR Roof Plan reference Elevation Quantity 100 PB/A&W Page 15 of 42

16 Building Assessment Survey Architectural Inspection EXTERIOR WINDOWS EXTERIOR GUARDS MAINTENANCE Photo1 Roof Plan reference Facade G RUST - MAJOR Elevation Quantity 40 Photo1 Facade A PB/A&W Page 16 of 42

17 EXTERIOR WINDOWS EXTERIOR GUARDS Building Assessment Survey LINTELS WINDOWS INTERIOR POOLS Material Type(s) Instance on Aluminum - Other: All Facades Instance Aluminum 3 - Fair Instance Quantity 7,000 Instance Installation Year 2001 Source of Installation STRUCTURAL COLUMNS/BEAMS/BEARING WALLS Location/Instance Quantity 40 Documented 3 - Fair CONCRETE COLUMNS/BEAMS: CRACKED/SPALLED/REINFORCEMENT EXPOSED Cellar - Below Auditorium and in Basement REPAIR Purpose of Action LEVEL 5 Photo1 Room B10, Also Column in Sprinkler Valve Room FLOOR STRUCTURE 4 - Between Fair and Poor CONCRETE SLAB ON GRADE: MINOR CRACKS Location/Instance Basement Quantity 50 REPAIR Purpose of Action LEVEL 5 PB/A&W Page 17 of 42

18 INTERIOR STRUCTURAL FLOOR STRUCTURE Photo1 Building Assessment Survey Boiler Room Location/Instance Quantity 100 CONCRETE SLAB ON GRADE: WATER INFILTRATION IN NON- INSTRUCTIONAL SPACE Basement Urgency of Action PRIORITY 5 Purpose of Action LEVEL 5 Photo1 INSTALL WATERPROOFING FOUNDATION WALLS Material Type(s) Location/Instance Quantity 100 Lamp Storage Room M, K, M Concrete 4 - Between Fair and Poor CONCRETE: WATER INFILTRATION IN NON- INSTRUCTIONAL SPACE Basement Urgency of Action PRIORITY 5 Purpose of Action LEVEL 5 INSTALL WATERPROOFING PB/A&W Page 18 of 42

19 INTERIOR STRUCTURAL FOUNDATION WALLS Photo1 Building Assessment Survey Boiler Room Pit (Wall) also in Room B L ROOF STRUCTURE VAULTS-BUNKERS Foundation Walls Slab Structure Vault/Ash Hoist Doors and Framing 3 - Fair NOT IN USE / DETERIORATED Location/Instance Ash Hoist Vault Quantity 1 EACH REMOVE AND SEAL Urgency of Action PRIORITY 1 Purpose of Action LEVEL 1 Photo1 No photo recorded AUDITORIUM Seats Ceiling Seats PLASTER: CRACKS/SPALLING Location/Instance Near Entrance Quantity 10 PB/A&W Page 19 of 42

20 INTERIOR AUDITORIUM Ceiling Photo1 Building Assessment Survey Near Entrance Door(s) Seats Fixed H/C Lift Seats Fixed Seating Seats DAMAGED/BROKEN/INOPERABLE Location/Instance Seats A/3, B/4, C/101,104 Quantity 4 EACH Photo1 Seat B/5 Floor Finish Seats Sliding-folding Partition Stage Stage Seats Seats PB/A&W Page 20 of 42

21 Building Assessment Survey Architectural Inspection INTERIOR AUDITORIUM Stage Stage Seats Stage Curtain Rigging Seats Stage Curtains Seats 1 - Good Walls Seats Window Curtains/Shades/Blinds Seats 1 - Good CAFETERIA Ceiling 1 - Good Door(s) 5 - Poor WOOD: DETERIORATED DOOR Location/Instance Entrances, Exit Quantity 3 EACH MAINTENANCE Photo1 Entrance PB/A&W Page 21 of 42

22 Building Assessment Survey Architectural Inspection INTERIOR CAFETERIA Fixed Equipment Floor Finish Sliding-folding Partition Stage Walls Window Curtains/Shades/Blinds CLASSROOMS/CORRIDORS/ADMIN SPACES Ceiling Door(s) 5 - Poor WOOD: DETERIORATED DOOR Location/Instance Rooms 103, 110, 206, 307, 313, and Others Quantity 19 EACH MAINTENANCE Photo1 Room 313 Floor Finish Location/Instance Quantity 60 TERRAZZO: CRACKS Corridor near Auditorium PB/A&W Page 22 of 42

23 Building Assessment Survey Architectural Inspection INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Floor Finish Photo1 Corridor near Auditorium VINYL TILES: TRIPPING HAZARD - ELECTRICAL OUTLET Location/Instance Room 104 Quantity 10 Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6 Photo1 Room 104 Walls MASONRY: CRACKS/SPALLING Location/Instance Stair F/2 Quantity 10 PB/A&W Page 23 of 42

24 Building Assessment Survey Architectural Inspection INTERIOR CLASSROOMS/CORRIDORS/ADMIN SPACES Walls Photo1 Corridor near Stair F/2 GLAZED BLOCK: CRACKS/SPALLING Location/Instance Corridor near Room 126 Quantity 10 Photo1 Corridor near Room 126 Specialties GYMNASIUM Ceiling Door(s) 3 - Fair WOOD: DETERIORATED DOOR Location/Instance Office Quantity 1 EACH MAINTENANCE PB/A&W Page 24 of 42

25 INTERIOR GYMNASIUM Door(s) Photo1 Building Assessment Survey Office Fixed Equipment 1 - Good Floor Finish Seating Sliding-folding Partition Stage Walls MASONRY: CRACKS/SPALLING Location/Instance Entrance Wall Quantity 80 Photo1 Entrance Wall PB/A&W Page 25 of 42

26 INTERIOR GYMNASIUM Walls Building Assessment Survey Window Curtains/Shades/Blinds INTERIOR DOOR HARDWARE 3 - Fair INTERIOR GUARDS DETERIORATED/TORN-OUT/MISSING Location/Instance Stair C/Bulkhead Quantity 20 Photo1 Stair C/Bulkhead KITCHEN Ceiling Door(s) 3 - Fair WOOD: DETERIORATED DOOR Location/Instance Office Quantity 1 EACH MAINTENANCE PB/A&W Page 26 of 42

27 INTERIOR KITCHEN Door(s) Photo1 Building Assessment Survey Office Floor Finish Walls GLAZED BLOCK: CRACKS/SPALLING Location/Instance Near Exit Quantity 10 Photo1 Near Exit LIBRARY Instance on Room 212/214 Built-in Furnishing Instance on Room 212/214 Location/Instance Quantity 2 SINK/STORAGE CABINET - DAMAGED/DETERIORATED Right of Entrance L.F. PB/A&W Page 27 of 42

28 Building Assessment Survey Architectural Inspection INTERIOR LIBRARY Built-in Furnishing Photo1 Right of Entrance Ceiling Instance on Room 212/214 Door(s) Instance on Room 212/ Between Fair and Poor WOOD: DETERIORATED DOOR Location/Instance Right Entrance, Left Entrance Quantity 2 EACH MAINTENANCE Photo1 Floor Finish Instance on Room 212/214 Walls Instance on Room 212/214 LOCKER ROOM Right Entrance PB/A&W Page 28 of 42

29 Building Assessment Survey Architectural Inspection INTERIOR LOCKER ROOM Alternative use Yes Instance on 2nd Floor Alternative use Yes Ceiling Instance on 2nd Floor Door(s) Instance on 2nd Floor 3 - Fair WOOD: MISSING DOOR Location/Instance Entrance Quantity 1 EACH MAINTENANCE Photo1 Entrance 3 - Fair WOOD: DETERIORATED DOOR Location/Instance Entrance Quantity 1 EACH MAINTENANCE PB/A&W Page 29 of 42

30 INTERIOR LOCKER ROOM Door(s) Photo1 Building Assessment Survey Entrance Floor Finish Instance on 2nd Floor Locker Room Lockers Instance on 2nd Floor Walls MASONRY: CRACKS/SPALLING Location/Instance Rear Quantity 10 Photo1 MULTI-PURPOSE ROOM SCIENCE DEMO ROOM SCIENCE LAB SCIENCE PREP ROOM Rear PB/A&W Page 30 of 42

31 Building Assessment Survey Architectural Inspection INTERIOR SHOWER ROOM Alternative use Yes Instance on 2nd Floor Inaccessible Ceiling Door(s) Floor Finish Walls STAIRS/RAMPS: INTERIOR Do Letter Stair Signs Exist? Yes Ceiling Door(s) 3 - Fair WOOD: DETERIORATED DOOR Location/Instance Stair E/1 Quantity 1 EACH MAINTENANCE Photo1 Partition Railings Stairs and Landings Stair E/1 PB/A&W Page 31 of 42

32 Building Assessment Survey Architectural Inspection INTERIOR STAIRS/RAMPS: INTERIOR Stairs and Landings VINYL TILES: DETERIORATED SUBSTRATE Location/Instance Stair C/2 Quantity 10 Photo1 Stair C/2 VINYL TILES: BROKEN/DETERIORATED/MISSING TILES Location/Instance Stair C/Bulkhead Quantity 10 Photo1 Stair C/Bulkhead Walls BRICK: CRACKS/SPALLING Location/Instance Stair B/1 Quantity 10 PB/A&W Page 32 of 42

33 INTERIOR STAIRS/RAMPS: INTERIOR Walls Photo1 Building Assessment Survey Stair B/1 TOILET ROOMS - STAFF Ceiling Door(s) 5 - Poor WOOD: DETERIORATED DOOR Location/Instance Rooms 103, 203 Quantity 2 EACH MAINTENANCE Photo1 Floor Finish Stalls Walls TOILET ROOMS - STUDENTS Ceiling Room 203 PB/A&W Page 33 of 42

34 Building Assessment Survey Architectural Inspection INTERIOR TOILET ROOMS - STUDENTS Ceiling PLASTER: CRACKS/SPALLING Location/Instance Room 215, 115 Quantity 20 Photo1 Room 215 Door(s) 5 - Poor WOOD: DETERIORATED DOOR Location/Instance Rooms 215, 221 Quantity 2 EACH MAINTENANCE Photo1 Room 215 Floor Finish Location/Instance Quantity 10 CERAMIC TILE: BROKEN/MISSING TILES 3rd Floor - Boys PB/A&W Page 34 of 42

35 INTERIOR TOILET ROOMS - STUDENTS Floor Finish Photo1 Building Assessment Survey rd Floor - Boys Stalls 4 - Between Fair and Poor RUST - MAJOR Location/Instance Room 221 Quantity 2 EACH Photo1 Walls LIFE SAFETY F.D. HOLDING AREA STEEL STAIRS SITE CONTAINERIZATION Drainage System for Asphalt Catch Basins/Manhole - Surrounded by asphalt Culverts - Asphalt Covering Drainage System for Concrete Catch Basins/Manhole - Surrounded by concrete Room 221 PB/A&W Page 35 of 42

36 Building Assessment Survey Architectural Inspection SITE Drainage System for Concrete Catch Basins/Manhole - Surrounded by concrete Culverts - Concrete Covering Drainage System for Soil DRINKING FOUNTAINS FENCES CONCRETE CURB: DAMAGED/DETERIORATED Location/Instance Along 67th Avenue Quantity 20 Photo1 Along 67th Avenue IRRIGATION SYSTEM PAVING Student Non-Use Gravel Exists? Asphalt Concrete Pavers Student Use Gravel Exists? Asphalt Location/Instance Quantity 350 No No 3 - Fair CRACKS - MAJOR Schoolyard PB/A&W Page 36 of 42

37 SITE PAVING Student Use Asphalt Photo1 Building Assessment Survey Schoolyard Concrete Pavers Site Sidewalks & Walkways Asphalt 4 - Between Fair and Poor CRACKS - MAJOR Location/Instance Near Playground, East of Building, South of Building Quantity 600 Photo1 Near Playground Concrete 3 - Fair DAMAGED/DETERIORATED/MISSING SECTIONS Location/Instance Along 67th Avenue Quantity 125 PB/A&W Page 37 of 42

38 SITE PAVING Site Sidewalks & Walkways Concrete Photo1 Building Assessment Survey Along 67th Avenue HEAVING Location/Instance Along 67th Street Quantity 50 Photo1 Along 67th Street Pavers DOT Sidewalk Asphalt Concrete 3 - Fair DAMAGED/DETERIORATED/MISSING SECTIONS Location/Instance Along 67th Avenue, 230th Street Quantity 75 Urgency of Action PRIORITY 4 Purpose of Action LEVEL 4 PB/A&W Page 38 of 42

39 SITE PAVING DOT Sidewalk Concrete Photo1 Building Assessment Survey Along 67th Avenue DAMAGED CURBS Location/Instance Along 230th Street Quantity 10 L.F. Urgency of Action PRIORITY 4 Purpose of Action LEVEL 4 Photo1 Along 230th Street Pavers PLAYGROUNDS Instance on Along 230th Street Benches Instance on Along 230th Street Fence Instance on Along 230th Street Pavement Instance on Along 230th Street 3 - Fair ASPHALT: CRACKS - MAJOR Location/Instance Near Stairs, Near Driveway Quantity 200 PB/A&W Page 39 of 42

40 Building Assessment Survey Architectural Inspection SITE PLAYGROUNDS Pavement Photo1 Near Stairs Play Equipment Instance on Along 230th Street Safety Surfacing Instance on Along 230th Street Unpaved Area Instance on Along 230th Street PLAYING SURFACE RETAINING WALLS Are there any Retaining Walls 6' OR higher facing public street/sidewalk? Location/Instance Quantity 10 No CAST IN PLACE CONCRETE: CRACKS/SPALLING - MINOR East of Building REPAIR Photo1 PB/A&W Page 40 of 42

41 SITE RETAINING WALLS Building Assessment Survey East of Building SEATING SITE WALLS (NOT RETAINING WALLS) STAIRS/RAMPS: EXTERIOR Railings 3 - Fair DAMAGED Location/Instance East of Building Quantity 12 L.F. Photo1 East of Building Site Cheek/flank Walls CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR Location/Instance East of Building Quantity 10 Photo1 Stairs/ramps East of Building PB/A&W Page 41 of 42

42 Building Assessment Survey Architectural Inspection SITE STAIRS/RAMPS: EXTERIOR Stairs/ramps CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR Location/Instance East of Building Quantity 35 Photo1 East of Building PB/A&W Page 42 of 42