1 Architectural Inspection Building Assessment Survey Asset: FOREST HILLS HS - Q, STREET, New York, Inspection Id Inspection Type Time In Last Edited SA : Architectural - Senior :18 PM :15 PM AA : Architectural - Associate :08 PM :09 PM Asset Data Was the building fully accessible for inspection Inspection Access Comment Principal(s) Information Answer No Retaining Walls were inaccessible for inspection. Principal Name Organization Did you meet with this Principal? Did this Principal provide feedback? Benjamin Sherman Forest Hills HS - Queens No No Custodian Fireman Principal Name Organization Did you meet with this Principal? Did this Principal provide feedback? Summary of Principal's Feedback Building Square Footage Comments on the Area Comments on the Stories (Floors) plus Basements Comments on the Number of Classrooms 92 Neil Rosenblatt (AP) Forest Hills HS- Queens Yes Yes The Principal provided the following comments: 1 - The Toilet Rooms throughout the School need to be upgraded with Auto flush mechanisms installed for Water Closets. 2 - There are many broken and worn seats in the Auditorium. These are the original Seats and an upgrade is needed. 3 - The 4th Floor Theater Room needs to be upgraded. 4 - The School holds many family oriented events in the Auditorium and Air ing is much needed there, in addition to the Cafeteria and Gymnasiums. 5 - Many of the schools Science Labs are out-dated and need to be upgraded in order to maintain the latest in Lab technology. 6 - The Boys and Girls Locker Rooms are in disrepair and need to be upgraded. 7 - It has become vital to the School to have a Video Surveillance System in place for the safety of the building Students and Staff. Nilson Traslavina James Van-Vort None Comments on the Year Built 1941 Student Population 3799 Staff Population 295 Weather 4+B+SB+Attic Fair PB/A&W Page 1 of 70

2 Facade Photo Building Assessment Survey Main Entrance Photo Corner 110th Street and 66th Road - Southeast View Roof Photo Facade A Street Roof 14 - Northeast View PB/A&W Page 2 of 70

3 Building Assessment Survey Have any Systems/Major Building Components been upgraded? Have there been any New Building Additions? Tandem Schools? Leased Space? Yes Systems: Limited Exterior Doors replacement and refurbishment Year: 2017 Systems: Corridor Flooring at Basement, 1st, 2nd, and 3rd Floor replacement Year: 2015 Systems: Limited Foundation Wall Waterproofing; Library upgrades Year: 2012 Systems: Limited Roof Drain repairs; Limited Cupola Waterproofing; Complete Areaway reconstruction. Year: 2010 Systems: New HC Unisex Toilet Rooms at 4th Floor Year: 2009 Systems: Limited Roof Repairs (All Slate Roofs). Year: 2008 Systems: Complete Windows, Window Guards and Shades replacement; Limited roofing repairs (Slate Roofs); Limited Parapet repairs and Coping replacement; Limited Exterior Door replacement; Limited Exterior Bronze Door replacement Year: 2002 No No No Priority Priority Exist Last Year? Priority Category Description Component Affected Location Description Person(s) Notified Person(s) Title PhotoImage No Tripping Hazard Cracked and displaced stone steps are a potential tripping hazard. EXTERIOR STAIRS/RAMP S: EXTERIOR STAIRS/RAMP S South Courtyard Entrance Steps. James Van-Vort Fireman Structural Engineer Required Structural Type Description Component Affected Location Description Person(s) Notified Person(s) Title PhotoImage No condition recorded Accessibility Accessibility Status Is the primary or secondary entrance on an accessible route? Is the building a multi-story building? Are all floors of the building accessible through compliant means? Accessible classrooms exists on each floor? Boys and Girls or Unisex accessible toilets exist on at least every other floor? If the following spaces exist, are they ALL accessible? Art Room, Auditorium, Cafeteria, Computer, Gymnasiums, Library, Multipurpose Room, Science Labs Yes Yes Yes Yes Yes Yes Physical Breakdown Structure Exists Complies Required FUNCTIONAL ACCESSIBILITY Exterior Routes Exterior Entrances & Exits Yes Exterior H/C Lifts No No PB/A&W Page 3 of 70

4 Building Assessment Survey Physical Breakdown Structure Exists Complies Required Exterior Routes Exterior Ramps and Railings Yes Yes Interior Routes Corridor and Lobby H/C Lifts No No Interior Corridor Doors and Hardware Yes Yes Interior Corridors and Lobbies Interior Elevators Yes Yes Interior Lobby Doors and Hardware Interior Ramps Rooms & Spaces Art Rooms Rooms 452, 453, 464 Yes Auditorium 1st Floor Yes Cafeteria Basement - Student, Basement - Staff Classrooms Basement, 1st - 4th Floors Yes Computer Rooms Rooms 211, 363, 366 Yes Gymnasium 1st Floor - Boys, 1st Floor - Girls Library 2nd Floor Yes Main Office Room 138 Yes Multi-purpose Room Nurse's Room Rooms B13, B15 Yes Pool Science Lab Rooms 111, 152, 162, 252 Yes Toilet Rooms (Boys) Basement - 1st - 3rd Floors No Urinal Arrangement Water Closet Arrangement Toilet Rooms (Girls) Basement - 1st - 3rd Floors No Water Closet Arrangement Toilet Rooms (Staff) Basement - 1st - 4th Floors No Clear opening < 32" No Lever-type Hardware No No No Yes Yes Yes Yes Building Template PB/A&W Page 4 of 70

5 Building Assessment Survey Architectural Inspection Inspection Architectural EXTERIOR AREAWAY Instance on AW1-AW7 Instance 3 - Fair Instance Quantity 7 Instance EACH AREAWAY STAIRS: DETERIORATED RAILINGS Roof Plan reference Quantity 10 L.F. Photo1 AWNINGS AND CANOPIES CHIMNEY Material Type(s) COPING AW3 Masonry 3 - Fair CAST STONE: CRACKED/BROKEN PIECES PB/A&W Page 5 of 70

6 EXTERIOR COPING Roof Plan reference Building Assessment Survey Quantity 10 L.F. -IN-KIND Photo1 Roof Plan reference Roof 10 - South Courtyard Arcade Coping CAST STONE: DISINTEGRATING / FREEZE THAW Quantity 20 L.F. -IN-KIND PB/A&W Page 6 of 70

7 EXTERIOR COPING Photo1 Building Assessment Survey CORNICE Roof Plan reference Roof 10, 11, - 15, Poor STONE: MAJOR CRACKS, SPALLING Quantity 1,000 Urgency of Action PRIORITY 4 Purpose of Action LEVEL 4 Photo1 DOORS DOORS AND FRAMES Facade D P, Z 5 - Poor WOOD: DETERIORATED DOOR - MAJOR DETERIORATION PB/A&W Page 7 of 70

8 EXTERIOR DOORS DOORS AND FRAMES Roof Plan reference Building Assessment Survey Quantity 6 EACH Urgency of Action PRIORITY 4 Photo1 Roof Plan reference Courtyard - Facade F METAL: DETERIORATED DOOR AND FRAME - MAJOR DETERIORATION Quantity 6 EACH Purpose of Action LEVEL 4 PB/A&W Page 8 of 70

9 EXTERIOR DOORS DOORS AND FRAMES Photo1 Building Assessment Survey DOOR HARDWARE LINTELS TRANSOM/SIDE LIGHT Roof Plan reference Exit H, K 3 - Fair 5 - Poor METAL: DENTED, MINOR RUSTING Quantity 50 MAINTENANCE Photo1 Facade O - Exit EXTERIOR WALLS Material Type(s) Concrete, Masonry PB/A&W Page 9 of 70

10 EXTERIOR EXTERIOR WALLS Replacement Quantity 70,000 Replacement Uom Instance on All Facades Instance 3 - Fair Instance Quantity 70,000 Instance Roof Plan reference Building Assessment Survey BRICK: CRACKS/DISPLACED/SPALLED BRICK AT BUILDING CORNERS Elevation Quantity 150 REMOVE AND REBUILD Urgency of Action PRIORITY 4 Photo1 Facade G BRICK: DETERIORATED MASONRY SILLS PB/A&W Page 10 of 70

11 EXTERIOR EXTERIOR WALLS Roof Plan reference Building Assessment Survey Elevation Quantity 10 L.F. REPAIR Photo1 Roof Plan reference Facade F BRICK: MINOR CRACKS AND SPALLING PB/A&W Page 11 of 70

12 EXTERIOR EXTERIOR WALLS Elevation Building Assessment Survey Quantity 30 RESTITCH Photo1 Roof Plan reference Facade F - E corner BRICK: OPEN JOINTS Elevation Quantity 2,500 REPOINT PB/A&W Page 12 of 70

13 Building Assessment Survey Architectural Inspection EXTERIOR EXTERIOR WALLS Photo1 Roof Plan reference Facade A CONCRETE MASONRY UNIT: MINOR CRACKS AND SPALLING Elevation Quantity 70 RESTITCH Photo1 Facade A PB/A&W Page 13 of 70

14 EXTERIOR EXTERIOR WALLS Building Assessment Survey EXTERIOR SOFFITS LOADING DOCK LOUVER PARAPETS Material Type(s) Masonry, Concrete Replacement Quantity 3,000 Replacement Uom C.F. Instance on Facades at Roofs 8, 9, 10, 11, 15, 16 Instance 4 - Between Fair and Poor Instance Quantity 3,000 Instance C.F. BRICK: OPEN JOINTS Roof Plan reference Quantity 200 REPOINT Photo1 Roof 16 PLAZA DECK Instance on Concrete: Roof 17 Instance 1 - Good Instance Quantity 2,000 Instance PB/A&W Page 14 of 70

15 Building Assessment Survey Architectural Inspection EXTERIOR PLAZA DECK Installation Year 2016 Source of Installation Inspector Estimate ROOF Roofing Replacement Quantity 80,000 Replacement Uom ROOF HATCH/SMOKE HATCH LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS ROOF BARRIER 3 - Fair RAILINGS/PANELS: DETERIORATED, MAJOR RUSTING Roof Plan reference Quantity 50 Photo1 Roof 3 ROOF CAGE ROOF FENCE ROOFING Instance on Modified Bitumen: Roof 14 Instance Instance Quantity 400 PB/A&W Page 15 of Poor

16 EXTERIOR ROOF Roofing ROOFING Instance Does the roof have major mechanical equipment sitting on Dunnage Steel less than 18" above the Roofing? Installation Year 1999 Source of Installation Roof Plan reference Building Assessment Survey No Documented MODIFIED BITUMEN: ROOFING: DELAMINATION Quantity 150 Photo1 ROOFING WITHOUT MAJOR EQUIPMENT REMOVAL Roof 14 Instance on Slate Roof: Roofs 1, 2, 3, 4, 5, 6, 7, 8, 9 Instance 3 - Fair Instance Quantity 72,000 Instance Does the roof have major mechanical equipment sitting on Dunnage Steel less than 18" above the Roofing? Installation Year 1964 Source of Installation No Documented SLATE ROOF: ROOFING: MAJOR ACTIVE ROOF LEAKS IN INSTRUCTIONAL SPACE PB/A&W Page 16 of 70

17 EXTERIOR ROOF Roofing ROOFING Roof Plan reference Building Assessment Survey Quantity 20 ROOFING Urgency of Action PRIORITY 5 Photo1 Roof Plan reference Roof 6 - Toilet Room 403A - Also in Corridor outside Room 452 SLATE ROOF: ROOFING: DAMAGED OR MISSING TILES Quantity 50 Urgency of Action PRIORITY 5 PB/A&W Page 17 of 70

18 EXTERIOR ROOF Roofing ROOFING Photo1 Building Assessment Survey Roof Instance on Built-Up: Roofs 10, 11, 12, 13, 15, 16, Instance 3 - Fair Instance Quantity 2,600 Instance Does the roof have major mechanical equipment sitting on Dunnage Steel less than 18" above the Roofing? Installation Year 1999 Source of Installation Roof Plan reference No Documented BUILT-UP: ROOFING: MAJOR ACTIVE ROOF LEAKS IN INSTRUCTIONAL SPACE Quantity 50 Urgency of Action PRIORITY 5 Photo1 ROOFING WITHOUT MAJOR EQUIPMENT REMOVAL Roof 11 - Corridor near Room 167 PB/A&W Page 18 of 70

19 EXTERIOR ROOF Roofing ROOFING Building Assessment Survey Instance on Metal: Roofs 2a, 3a Instance Instance Quantity 5,000 Instance Does the roof have major mechanical equipment sitting on Dunnage Steel less than 18" above the Roofing? Installation Year 1995 Source of Installation ROOFING DRAINS Specialties BULKHEAD/PENTHOUSE CUPOLA/ SPIRES/ TOWERS Roof Plan reference No Documented 4 - Between Fair and Poor LOSS OF PAINT Quantity 100 MAINTENANCE Photo1 Roof 14 - Cupola DAMAGED COVERING PB/A&W Page 19 of 70

20 EXTERIOR ROOF Specialties CUPOLA/ SPIRES/ TOWERS Roof Plan reference Building Assessment Survey Quantity 80 REPAIR COVERING Photo1 Roof Plan reference Cupola WATER INFILTRATION Quantity 50 REPAIR Urgency of Action PRIORITY 5 PB/A&W Page 20 of 70

21 EXTERIOR ROOF Specialties CUPOLA/ SPIRES/ TOWERS Photo1 Building Assessment Survey DORMER DUNNAGE STEEL SKYLIGHT/ROOF VENT ROOF/GRAVITY TANK STAIRS/RAMPS: EXTERIOR BUILDING CHEEK/FLANK WALLS Roof Plan reference Cupola- interior 3 - Fair STONE: DETERIORATED JOINTS AT COPING STONES Quantity 10 L.F. MAINTENANCE Photo1 Main Entrances PB/A&W Page 21 of 70

22 Building Assessment Survey Architectural Inspection EXTERIOR STAIRS/RAMPS: EXTERIOR BUILDING CHEEK/FLANK WALLS RAILINGS Roof Plan reference 3 - Fair RUST - MAJOR Quantity 10 L.F. Photo1 STAIRS/RAMPS Roof Plan reference North Exit 5 - Poor CONCRETE: CRACKS/SPALLING - MINOR Quantity 10 REPAIR PB/A&W Page 22 of 70

23 Building Assessment Survey Architectural Inspection EXTERIOR STAIRS/RAMPS: EXTERIOR STAIRS/RAMPS Photo1 Roof Plan reference Main Entrance HC Ramp STONE: CRACKS, SPALLING Quantity 10 Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6 Photo1 South Courtyard Entrance Steps STONE: DETERIORATED SUBSTRATE PB/A&W Page 23 of 70

24 EXTERIOR STAIRS/RAMPS: EXTERIOR STAIRS/RAMPS Roof Plan reference Building Assessment Survey Quantity 10 SUBSTRATE AND RESET Photo1 Roof Plan reference South Exit STONE: OPEN JOINTS Quantity 10 L.F. REPOINT PB/A&W Page 24 of 70

25 EXTERIOR STAIRS/RAMPS: EXTERIOR STAIRS/RAMPS Photo1 Building Assessment Survey Main Entrance WINDOWS Replacement Quantity 24,000 Replacement Uom EXTERIOR GUARDS 4 - Between Fair and Poor RUST - MAJOR Roof Plan reference Elevation Quantity 250 PB/A&W Page 25 of 70

26 EXTERIOR WINDOWS EXTERIOR GUARDS Photo1 Building Assessment Survey LINTELS Roof Plan reference Facade F 4 - Between Fair and Poor STEEL: MAJOR RUSTING Elevation Quantity 340 L.F. Photo1 PB/A&W Page 26 of 70

27 EXTERIOR WINDOWS LINTELS Building Assessment Survey Facade A WINDOWS Material Type(s) Aluminum Instance on Aluminum - Double Hung: All Facades Instance 4 - Between Fair and Poor Instance Quantity 24,000 Instance Installation Year 2002 Source of Installation Documented ALUMINUM - DOUBLE HUNG: INOPERABLE BALANCE Roof Plan reference Elevation Quantity 10 EACH MAINTENANCE Photo1 No photo recorded ALUMINUM - DOUBLE HUNG: AIR AND WATER INFILTRATION, OPEN JOINTS WITH DAMAGED CAULKING PB/A&W Page 27 of 70

28 EXTERIOR WINDOWS WINDOWS Roof Plan reference Building Assessment Survey Elevation Quantity 50 L.F. MAINTENANCE Urgency of Action PRIORITY 5 Photo1 Courtyard- Facade F POOLS STRUCTURAL COLUMNS/BEAMS/BEARING WALLS Location/Instance Quantity Fair STEEL COLUMNS/BEAMS: DETERIORATED MASONRY FIREPROOFING Room B70 PB/A&W Page 28 of 70

29 Building Assessment Survey Architectural Inspection STRUCTURAL COLUMNS/BEAMS/BEARING WALLS Purpose of Action LEVEL 5 Photo1 Mechanical Room B70 Location/Instance Quantity 30 STEEL COLUMNS/BEAMS: DETERIORATED CONCRETE FIREPROOFING Mechanical Room B70 Purpose of Action LEVEL 5 Photo1 Mechanical Room below Auditorium FLOOR STRUCTURE 3 - Fair CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED Location/Instance Attic over Gymnasium Quantity 100 REPAIR Purpose of Action LEVEL 5 PB/A&W Page 29 of 70

30 STRUCTURAL FLOOR STRUCTURE Photo1 Building Assessment Survey MER 319A CONCRETE SLAB ON GRADE: MINOR CRACKS Location/Instance Basement Quantity 50 REPAIR Purpose of Action LEVEL 5 Photo1 Mechanical Room B49 FOUNDATION WALLS Material Type(s) ROOF STRUCTURE Location/Instance Quantity 150 Concrete 4 - Between Fair and Poor CONCRETE: CRACKED/SPALLED/REINFORCEMENT EXPOSED Roof REPAIR Purpose of Action LEVEL 5 PB/A&W Page 30 of 70

31 STRUCTURAL ROOF STRUCTURE Photo1 Building Assessment Survey Roof 6, Also in MER 319A Location/Instance Roof 6 Quantity 75 STEEL COLUMNS/BEAMS: DETERIORATED CONCRETE FIREPROOFING Purpose of Action LEVEL 5 Photo1 Roof 6 VAULTS-BUNKERS Foundation Walls Slab Structure Vault/Ash Hoist Doors and Framing WATER INFILTRATION Location/Instance Basement Quantity 10 REPAIR Urgency of Action PRIORITY 5 PB/A&W Page 31 of 70

32 Building Assessment Survey Architectural Inspection STRUCTURAL VAULTS-BUNKERS Vault/Ash Hoist Doors and Framing Photo1 Ash Hoist Vault AUDITORIUM Instance on 1st Floor - 1,176 Seats Ceiling Instance on 1st Floor - 1,176 Seats PLASTER: CRACKS/SPALLING Location/Instance Near Entrance Stage Left Quantity 10 Photo1 Near Entrance Stage Left Door(s) Instance on 1st Floor - 1,176 Seats Fixed H/C Lift Instance on 1st Floor - 1,176 Seats Fixed Seating Instance on 1st Floor - 1,176 Seats Location/Instance Quantity Good 5 - Poor DAMAGED/BROKEN/INOPERABLE Seats A/7, F/107, J/6, W/17, V/101 and Others PB/A&W Page 32 of 70

33 Building Assessment Survey Architectural Inspection AUDITORIUM Fixed Seating EACH Photo1 Seat F/107 DAMAGED/BROKEN/INOPERABLE Location/Instance Seats U/17,T/7,G/102 Quantity 3 EACH Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6 Photo1 Seat U/17 Floor Finish Instance on 1st Floor - 1,176 Seats CONCRETE: CRACKS Location/Instance Seats L/2-L/14, Seats W/2-W/14 Quantity 60 PB/A&W Page 33 of 70

34 AUDITORIUM Floor Finish Photo1 Building Assessment Survey Seats L/2-L/14 Sliding-folding Partition Instance on 1st Floor - 1,176 Seats Stage Instance on 1st Floor - 1,176 Seats Stage Instance on 1st Floor - 1,176 Seats Stage Curtain Rigging Instance on 1st Floor - 1,176 Seats 1 - Good Stage Curtains Instance on 1st Floor - 1,176 Seats 1 - Good Walls Instance on 1st Floor - 1,176 Seats 3 - Fair STONE: CRACKS/SPALLING Location/Instance Column and Wall Near Stage Left, Left Aisle Near Entrance Quantity 30 Photo1 Near Stage Left PB/A&W Page 34 of 70

35 AUDITORIUM Walls Building Assessment Survey PLASTER: CRACKS/SPALLING Location/Instance Column Near Stage Left, Above Left Aisle Near Entrance Quantity 30 Photo1 Column Near Stage Left GYPSUM BOARD: DETERIORATED Location/Instance Along Entrance Wall, Near Windows Quantity 200 Photo1 Window Curtains/Shades/Blinds Instance on 1st Floor - 1,176 Seats CAFETERIA Instance on Basement - Staff (1,000 SF) Instance on Basement - Students Ceiling Instance on Basement - Staff (1,000 SF) Near windows 1 - Good PB/A&W Page 35 of 70

36 Building Assessment Survey Architectural Inspection CAFETERIA Ceiling Instance on Basement - Students Door(s) Instance on Basement - Students 5 - Poor WOOD: DETERIORATED DOOR Location/Instance Entrances Quantity 3 EACH MAINTENANCE Photo1 Entrance Instance on Basement - Staff (1,000 SF) 3 - Fair WOOD: DETERIORATED DOOR Location/Instance Entrance Quantity 1 EACH MAINTENANCE Photo1 Entrance Fixed Equipment PB/A&W Page 36 of 70

37 Building Assessment Survey Architectural Inspection CAFETERIA Fixed Equipment Instance on Basement - Staff (1,000 SF) Instance on Basement - Students Floor Finish Instance on Basement - Students Instance on Basement - Staff (1,000 SF) Sliding-folding Partition Instance on Basement - Students Instance on Basement - Staff (1,000 SF) Stage Instance on Basement - Staff (1,000 SF) Instance on Basement - Students Walls Instance on Basement - Students PLASTER: CRACKS/SPALLING Location/Instance Near Windows to Areaway Quantity 15 Photo1 Near Windows to Areaway GLAZED BLOCK: CRACKS/SPALLING Location/Instance Columns near Kitchen, Columns along Windows to Areaway Quantity 20 PB/A&W Page 37 of 70

38 CAFETERIA Walls Photo1 Building Assessment Survey Column near Kitchen Instance on Basement - Staff (1,000 SF) PLASTER: CRACKS/SPALLING Location/Instance All Four Columns Quantity 10 Photo1 Column near Servery Window Curtains/Shades/Blinds Instance on Basement - Students Instance on Basement - Staff (1,000 SF) CLASSROOMS/CORRIDORS/ADMIN SPACES Ceiling GYPSUM BOARD: DAMAGED/DETERIORATED Location/Instance Corridor near Room 409 Quantity 20 PB/A&W Page 38 of 70

39 Building Assessment Survey Architectural Inspection CLASSROOMS/CORRIDORS/ADMIN SPACES Ceiling Photo1 Corridor near Room 409 Location/Instance Quantity 350 PLASTER: CRACKS/SPALLING Rooms B01, 101, 201, 351, Corridor near Boys Gymnasium, and Others Photo1 Corridor near Boys Gymnasium PLASTER: CRACKS/SPALLING - ACTIVE LEAK Location/Instance Corridor near Rooms 167, 452 Quantity 30 Urgency of Action PRIORITY 5 Photo1 Corridor near Room 452 PB/A&W Page 39 of 70

40 Building Assessment Survey Architectural Inspection CLASSROOMS/CORRIDORS/ADMIN SPACES Ceiling Door(s) 5 - Poor WOOD: DETERIORATED DOOR Location/Instance Rooms 104, 140, 242, 336, 452 and Others Quantity 27 EACH MAINTENANCE Photo1 Room 140 Floor Finish VINYL TILES: DETERIORATED SUBSTRATE Location/Instance Corridor near Rooms 407, 419, 460, Rooms 366, 415, and others Quantity 2,800 Photo1 Corridor near Room 460 Location/Instance Rooms 101, 102 Quantity 150 WOOD: DAMAGED/DETERIORATED PB/A&W Page 40 of 70

41 Building Assessment Survey Architectural Inspection CLASSROOMS/CORRIDORS/ADMIN SPACES Floor Finish Photo1 Room 102 TERRAZZO: CRACKS Location/Instance Main Entrance Lobby Quantity 250 Photo1 Main Entrance Lobby Location/Instance Quantity 240 VINYL TILES: BROKEN/DETERIORATED/MISSING TILES Rooms 128, 140, 167, 211, 283, Corridor near Room Stair E/4, and others Photo1 PB/A&W Page 41 of 70

42 Building Assessment Survey Architectural Inspection CLASSROOMS/CORRIDORS/ADMIN SPACES Floor Finish Room 128 Walls STONE MOLDINGS: CRACKS/SPALLING Location/Instance Main Entrance Lobby Quantity 20 L.F. Photo1 Main Entrance Lobby PLASTER: CRACKS/SPALLING Location/Instance Rooms 101, 152, 201, 218, Corridor near Room 407 and Others Quantity 400 Photo1 Room 101 Specialties Classroom Locker(s) DAMAGED UNITS Location/Instance Rooms 340, 375 Quantity 26 PB/A&W Page 42 of 70

43 Building Assessment Survey Architectural Inspection CLASSROOMS/CORRIDORS/ADMIN SPACES Specialties Classroom Locker(s) EACH Photo1 Room 375 Fixed Seating GYMNASIUM Instance on 1st Floor - Girls Instance on 1st Floor - Boys Ceiling Instance on 1st Floor - Girls PLASTER: CRACKS/SPALLING Location/Instance Above Entrance, Above Section E Quantity 140 Photo1 Above Entrance Instance on 1st Floor - Boys Location/Instance Quantity 20 PLASTER: CRACKS/SPALLING Near Stair Y, Section G PB/A&W Page 43 of 70

44 Building Assessment Survey Architectural Inspection GYMNASIUM Ceiling Photo1 Near Section G Door(s) Instance on 1st Floor - Girls Instance on 1st Floor - Boys 1 - Good Fixed Equipment Instance on 1st Floor - Boys Instance on 1st Floor - Girls Floor Finish Instance on 1st Floor - Girls Instance on 1st Floor - Boys Seating Instance on 1st Floor - Boys DAMAGED BLEACHERS Location/Instance Left and right sides Quantity 16 PB/A&W Page 44 of 70

45 GYMNASIUM Seating Photo1 Building Assessment Survey Left side Sliding-folding Partition Instance on 1st Floor - Boys Instance on 1st Floor - Girls Stage Instance on 1st Floor - Girls Instance on 1st Floor - Boys Walls Instance on 1st Floor - Girls WALL PADDING: DETERIORATED Location/Instance Near Entrance, Section A, C Quantity 100 Photo1 Near Entrance Instance on 1st Floor - Boys Location/Instance Quantity Fair WALL PADDING: DETERIORATED Near Entrance PB/A&W Page 45 of 70

46 GYMNASIUM Walls Photo1 Building Assessment Survey Near Entrance Window Curtains/Shades/Blinds Instance on 1st Floor - Girls Instance on 1st Floor - Boys DOOR HARDWARE 3 - Fair GUARDS 3 - Fair DETERIORATED/TORN-OUT/MISSING Location/Instance Stair E/4, P/1, Kitchen Storage Room B43A Quantity 80 Photo1 Kitchen Storage Room B43A KITCHEN Ceiling Instance on Basement (1,500 SF) Instance on Basement (1,500 SF) Door(s) Instance on Basement (1,500 SF) 4 - Between Fair and Poor METAL: DETERIORATED DOOR AND FRAME PB/A&W Page 46 of 70

47 Building Assessment Survey Architectural Inspection KITCHEN Door(s) Location/Instance Corridor near Office B43, Storage Quantity 2 EACH MAINTENANCE Photo1 Corridor near Office B43 Floor Finish Instance on Basement (1,500 SF) 5 - Poor VINYL TILES: BROKEN/DETERIORATED/MISSING TILES Location/Instance Office B43 Quantity 50 Photo1 Office B43 CONCRETE: CRACKS Location/Instance Storage Rooms B43A, B43G Quantity 60 PB/A&W Page 47 of 70

48 KITCHEN Floor Finish Photo1 Building Assessment Survey Storage Room B43G CERAMIC TILE: BROKEN/MISSING TILES Location/Instance Between Refrigerators, Near ramp, at Servery, Center Quantity 70 Photo1 Between Refrigerators Walls Instance on Basement (1,500 SF) CERAMIC TILE: BROKEN/ MISSING Location/Instance Right and Left Servery to Students Cafeteria, Servery Staff Cafeteria Quantity 20 PB/A&W Page 48 of 70

49 KITCHEN Walls Photo1 Building Assessment Survey Right Servery to Students Cafeteria LIBRARY Instance on 2nd Floor Built-in Furnishing Instance on 2nd Floor Ceiling Instance on 2nd Floor Door(s) Instance on 2nd Floor Floor Finish Instance on 2nd Floor Walls Instance on 2nd Floor LOCKER ROOM Instance on Basement - Boys (2,554 Lockers) Alternative use Instance on Basement - Girls (2,283 Lockers) Alternative use Ceiling Instance on Basement - Girls (2,283 Lockers) Instance on Basement - Boys (2,554 Lockers) Door(s) Instance on Basement - Boys (2,554 Lockers) 1 - Good 1 - Good 1 - Good 1 - Good 1 - Good No No PB/A&W Page 49 of 70

50 Building Assessment Survey Architectural Inspection LOCKER ROOM Door(s) 3 - Fair METAL: DETERIORATED DOOR Location/Instance Entrance Quantity 1 EACH MAINTENANCE Photo1 Entrance Instance on Basement - Girls (2,283 Lockers) 3 - Fair WOOD: DETERIORATED DOOR Location/Instance Entrance Quantity 1 EACH MAINTENANCE Photo1 Floor Finish Instance on Basement - Boys (2,554 Lockers) Instance on Basement - Girls (2,283 Lockers) Locker Room Lockers Entrance PB/A&W Page 50 of 70

51 Building Assessment Survey Architectural Inspection LOCKER ROOM Locker Room Lockers Instance on Basement - Boys (2,554 Lockers) 3 - Fair DAMAGED UNITS Location/Instance Back, Front, Center Aisles Quantity 112 EACH Photo1 Back Aisle Walls Instance on Basement - Boys (2,554 Lockers) Instance on Basement - Girls (2,283 Lockers) MULTI-PURPOSE ROOM SCIENCE DEMO ROOM Instance on Room 345 Alternative use No Instance on Rooms 151, 153, 163, 214A, 251, 342, 344, 353 Alternative use No Instance on Rooms 253, 340, 343, 351 Alternative use No Fixed Equipment Instance on Room Poor DEMO TABLE: DAMAGED/DETERIORATED Location/Instance Room 345 Quantity 1 EACH PB/A&W Page 51 of 70

52 SCIENCE DEMO ROOM Fixed Equipment Photo1 Building Assessment Survey Room 345 Instance on Rooms 151, 153, 163, 214A, 251, 342, 344, Poor CABINETRY: MISSING/DAMAGED Location/Instance Rooms 151, 153, 163, 214, 251, 342, 344, 353 Quantity 24 L.F. Photo1 Room 342 SCIENCE LAB Instance on Rooms 111, 152 Alternative use No Instance on Rooms 162, 252 Alternative use No Fixed Equipment Instance on Rooms 111, Poor CABINETRY: MISSING/DAMAGED Location/Instance Room 111, 152 Quantity 98 L.F. PB/A&W Page 52 of 70

53 SCIENCE LAB Fixed Equipment Photo1 Building Assessment Survey Room 111 SCIENCE PREP ROOM Instance on Room 164 Alternative use No Instance on Room 356 Alternative use Yes Instance on Rooms 154A, 254, 352 Alternative use No Fixed Equipment Instance on Room Fair CABINETRY: MISSING/DAMAGED Location/Instance Room 356 Quantity 8 L.F. Photo1 No photo recorded Instance on Rooms 154A, 254, Poor CABINETRY: MISSING/DAMAGED Location/Instance Room 154A, 254, 352 Quantity 36 L.F. PB/A&W Page 53 of 70

54 SCIENCE PREP ROOM Fixed Equipment Photo1 Building Assessment Survey Room 352 SHOWER ROOM Instance on Basement - Boys Alternative use Yes Instance on Basement - Girls Alternative use Yes Ceiling Instance on Basement - Boys 3 - Fair PLASTER: CRACKS/SPALLING Location/Instance Back Quantity 10 Photo1 Door(s) Instance on Basement - Boys Instance on Basement - Girls Floor Finish Instance on Basement - Boys Back PB/A&W Page 54 of 70

55 Building Assessment Survey Architectural Inspection SHOWER ROOM Floor Finish Instance on Basement - Girls Walls Instance on Basement - Boys CERAMIC TILE: BROKEN/ MISSING Location/Instance Entrance Quantity 10 Photo1 Entrance Instance on Basement - Girls CERAMIC TILE: BROKEN/ MISSING Location/Instance Near Entrance Quantity 10 Photo1 STAIRS/RAMPS: Do Letter Stair Signs Exist? Near Entrance Yes PB/A&W Page 55 of 70

56 Building Assessment Survey Architectural Inspection STAIRS/RAMPS: Ceiling PLASTER: CRACKS/SPALLING Location/Instance Stairs EF/4, K/Basement, P/3 Quantity 30 Photo1 Stair EF/4 Door(s) METAL: DETERIORATED DOOR Location/Instance Stairs P/3, D/3 Quantity 2 EACH MAINTENANCE Photo1 Stair P/3 Partition Location/Instance Quantity Fair GLASS PANEL: DAMAGED/DETERIORATED Stairs C/4, G/1, 2, 3, P/2, R/4, and others PB/A&W Page 56 of 70

57 Building Assessment Survey Architectural Inspection STAIRS/RAMPS: Partition Photo1 Stair C/4 METAL PANEL: DAMAGED/DETERIORATED Location/Instance Stair P/2, G/1, R/Basement Quantity 15 Photo1 Stair P/2 Railings Stairs and Landings METAL: RUST - MAJOR Location/Instance Stairs C/Basement, D/Basement Quantity 50 PB/A&W Page 57 of 70

58 STAIRS/RAMPS: Stairs and Landings Photo1 Building Assessment Survey Stair C/Basement STONE: BROKEN/MISSING Location/Instance Stairs E/2, 3, 4, R/Basement, U/2, X/1, and others Quantity 250 Photo1 Stair E/2 CONCRETE: CRACKS/SPALLING - MAJOR Location/Instance Stair X/Bulkhead Quantity 25 Photo1 Stair X/Bulkhead PB/A&W Page 58 of 70

59 Building Assessment Survey Architectural Inspection STAIRS/RAMPS: Walls PLASTER: CRACKS/SPALLING Location/Instance Stairs E/4, R/4, K/Basement Quantity 90 Photo1 Stair E/4 TOILET ROOMS - STAFF Ceiling 3 - Fair PLASTER: CRACKS/SPALLING Location/Instance Room 239 Quantity 20 Photo1 Room 239 Location/Instance Quantity 10 PLASTER: CRACKS/SPALLING - ACTIVE LEAK Room 403A Urgency of Action PRIORITY 5 PB/A&W Page 59 of 70

60 TOILET ROOMS - STAFF Ceiling Photo1 Building Assessment Survey Room 403A Door(s) 5 - Poor METAL: DETERIORATED DOOR Location/Instance Room 233, 239, 339 Quantity 3 EACH MAINTENANCE Photo1 Room 239 Floor Finish 3 - Fair CERAMIC TILE: BROKEN/MISSING TILES Location/Instance Rooms B71, B72, 1st Floor - Men's Near Main Entrance Lobby Quantity 25 PB/A&W Page 60 of 70

61 TOILET ROOMS - STAFF Floor Finish Photo1 Building Assessment Survey Room B72 Stalls Walls PLASTER: CRACKS/SPALLING Location/Instance Rooms B71, 1st Floor - Women's, 333, 339 Quantity 50 Photo1 Room 339 CERAMIC TILE: BROKEN/ MISSING Location/Instance 1st Floor - Men's,Women's Near Main Entrance Lobby Quantity 15 PB/A&W Page 61 of 70

62 TOILET ROOMS - STAFF Walls Photo1 Building Assessment Survey st Floor - Mens TOILET ROOMS - STUDENTS Ceiling PLASTER: CRACKS/SPALLING Location/Instance Room 355 Quantity 10 Photo1 Room 355 Door(s) 5 - Poor METAL: DETERIORATED DOOR AND FRAME Location/Instance Room B69C Quantity 1 EACH MAINTENANCE PB/A&W Page 62 of 70

63 TOILET ROOMS - STUDENTS Door(s) Photo1 Building Assessment Survey Room B69C WOOD: DAMAGED LOUVER Location/Instance Rooms 155, 255, 355 Quantity 3 EACH MAINTENANCE Photo1 Room 355 Floor Finish CERAMIC TILE: BROKEN/MISSING TILES Location/Instance Rooms 106, 155 Quantity 35 Photo1 PB/A&W Page 63 of 70

64 TOILET ROOMS - STUDENTS Floor Finish Building Assessment Survey Room 155 Stalls Walls LIFE SAFETY F.D. HOLDING AREA STEEL STAIRS SITE CONTAINERIZATION 5 - Poor FENCING DAMAGED Location/Instance Near North Courtyard Quantity 100 REPAIR Photo1 Near North Courtyard CONTAINER DAMAGED Location/Instance Near North Courtyard Quantity 5 EACH PB/A&W Page 64 of 70

65 SITE CONTAINERIZATION Photo1 Building Assessment Survey Near North Courtyard Drainage System for Asphalt Catch Basins/Manhole - Surrounded by asphalt Culverts - Asphalt Covering Drainage System for Concrete Catch Basins/Manhole - Surrounded by concrete Culverts - Concrete Covering Drainage System for Soil Catch Basins/Manhole - Surrounded by Soil Culverts - Soil Covering DRINKING FOUNTAINS FENCES 3 - Fair WROUGHT IRON: RUST - MAJOR Location/Instance 67th Road Quantity 80 Photo1 67th Road PB/A&W Page 65 of 70

66 Building Assessment Survey Architectural Inspection SITE FENCES CONCRETE CURB: DAMAGED/DETERIORATED Location/Instance Along 67th Road Quantity 30 Photo1 Along 67th Road WROUGHT IRON: DAMAGED/DETERIORATED Location/Instance Along 67th Road Quantity 240 Photo1 Along 67th Road IRRIGATION SYSTEM PAVING Student Non-Use Gravel Exists? Asphalt Location/Instance Quantity 450 Yes 3 - Fair CRACKS - MAJOR Near Athletic Field PB/A&W Page 66 of 70

67 Building Assessment Survey Architectural Inspection SITE PAVING Student Non-Use Asphalt Photo1 Near Athletic Field Concrete 1 - Good Pavers 1 - Good Student Use Gravel Exists? No Asphalt Concrete Pavers 1 - Good Site Sidewalks & Walkways Asphalt 1 - Good Concrete DAMAGED CURBS Location/Instance Near Athletic Field Quantity 20 L.F. PB/A&W Page 67 of 70

68 SITE PAVING Site Sidewalks & Walkways Concrete Photo1 Building Assessment Survey Near Athletic Field Pavers 1 - Good DOT Sidewalk Asphalt Concrete 4 - Between Fair and Poor DAMAGED/DETERIORATED/MISSING SECTIONS Location/Instance Along 67th Road, 66th Road, 110th Street Quantity 1,375 Photo1 Along 110th Street DAMAGED CURBS Location/Instance Along 67th Road, 66th Road, 110th Street Quantity 300 L.F. PB/A&W Page 68 of 70

69 SITE PAVING DOT Sidewalk Concrete Photo1 Building Assessment Survey Along 66nd Road Pavers PLAYGROUNDS PLAYING SURFACE RETAINING WALLS Inaccessible SEATING Benches Concrete Metal/Wood/Plastic 1 - Good Bleachers SITE WALLS (NOT RETAINING WALLS) 3 - Fair BRICK: CRACKS/SPALLING - MAJOR Location/Instance Corner of 67th Road and 110th Street Quantity 10 Photo1 Corner of 67th Road and 110th Street Location/Instance Quantity 10 BRICK: CRACKS/SPALLING - MINOR 67th Road PB/A&W Page 69 of 70

70 Building Assessment Survey Architectural Inspection SITE SITE WALLS (NOT RETAINING WALLS) REPAIR Photo1 No photo recorded BRICK: DETERIORATED COPING STONE Location/Instance 67th Road Quantity 20 Photo1 STAIRS/RAMPS: EXTERIOR Railings Site Cheek/flank Walls Stairs/ramps 67th Road PB/A&W Page 70 of 70