Centennial Hills Skilled Nursing Facility Fire Protection Report July 13, 2016 Revised September 15, 2016 JBA Project No

Size: px
Start display at page:

Download "Centennial Hills Skilled Nursing Facility Fire Protection Report July 13, 2016 Revised September 15, 2016 JBA Project No"

Transcription

1 We Bring Buildings to Life Centennial Hills Skilled Nursing Facility Fire Protection Report July 13, 2016 Revised September 15, 2016 JBA Project No At the request of Yihong Liu + Associates, Ltd., JBA Consulting Engineers prepared the following Fire Protection Report (FPR) for the new Centennial Hills skilled nursing facility. INTRODUCTION Ochoa Development proposes to construct a new skilled nursing facility located on the southeast corner of the intersection of Riley Street and Rome Boulevard in Las Vegas, Nevada. This FPR is intended to address the fire protection and life safety features and requirements for the new skilled nursing facility. The skilled nursing facility will be single-story structure that contains the following: patient rooms, nurse stations, dining areas, recreation areas, offices, conference room, patios, storage rooms, waiting rooms, mechanical rooms, electrical rooms, and associated spaces. The skilled nursing facility is classified as a mixed-used building. The primary occupancies will include Group I-2, A-2, A-3, and B. All work will be performed in accordance with the Southern Nevada Amendments to the 2012 International Building Code (SNBC) as adopted by the City of Las Vegas, AIA guideline for Design and Construction of Hospital and Healthcare Facilities 2006, and the 2012 Southern Nevada Fire Code Amendments to the 2012 International Fire Code (SNFC) as adopted by the City of Las Vegas Fire and Rescue (LVFR). Due to licensing of the property the facility must also comply with NFPA 101, The Life Safety Code. PASSIVE FIRE-RESISTIVE ASPECTS The skilled nursing facility will be single-story structure with a total area of 42,308 ft2. In terms of allowable building area and height, Group I-2 occupancy figures were utilized as it is the most restrictive occupancy in the building. The building is considered an I-2 occupancy as the residents are incapable of self-preservation. The new building will be built of Type VA construction per SNBC Table 503. The building area limited by SNBC Table 503 is permitted to be increased due to the frontage and automatic sprinkler system protection. As such, the maximum allowable area for this building is 45,125 ft2 in accordance with SNBC Section 506. The proposed height and area are within the allowable limits. The code analysis for new skilled nursing facility has been prepared by the architect and detailed on Sheet G-003 of the architectural package. Refer to the code analysis for the calculation associated with the maximum allowable area. The building is classified as mixed-use nonseparated occupancy per SNBC Section As such, there are no requirements for occupancy separations or incidental use separations, except where detailed herein. Incidental use separations per SNBC Section 509 will apply. JBA Las Vegas West Patrick Lane Las Vegas, NV Worldwide Trusted Advisors

2 City of Las Vegas 2 September 15, 2016 Centennial Hills Skilled Nursing Facility JBA Project No Las Vegas, NV The fire-resistance ratings for building elements will apply as provided in Table 1. Table 1: Structural Fire Resistance Ratings for Construction Type V-A Building Element Minimum Fire-Resistance Rating (Hours) Structural frame 1 Bearing walls 1 Non-bearing walls & partitions 0 Floors 1 Roofs 1 Based on SNBC Table 602, exterior walls of Type V-A construction are not required to be fire-resistance rated when the fire separation distance is equal to or greater than 30 feet. The fire separation distance for the new structure will be at least 30 feet in each direction. As such, non-bearing exterior walls will not require a fire-resistance rating due to the fire separation distances. Type V-A construction is permitted to utilize any building materials permitted by the SNBC. Habitable rooms in Group I-2 occupancies are required to have an exit access door leading directly into a corridor per SNBC Section Corridors are required to be continuous to the exits per SNBC Section The waiting rooms, nurse stations, and dining/recreation/activity areas will be constructed as required for corridors, will be provided with automatic fire detection, and will be equipped throughout with quick-response sprinklers. As such, the waiting rooms, nurse stations, and dining/recreation/activity areas are permitted to be open to a corridor per SNBC Section , and Corridor systems for the skilled nursing facility are detailed on small-scale drawing FP-1. The building will be provided with a court and will comply with SNBC Section Corridors walls are permitted to be constructed as non-rated smoke partitions per SNBC Section Smoke partitions are required to extend from the top of the foundation or floor below to the underside of the floor or roof sheathing, deck, or slab above and will be constructed in accordance with SNBC Section 710. For this project, the 1-hour roof consists of a bottom membrane beneath the joists such that walls are permitted to terminate at the bottom membrane of the 1-hour fire-resistance rated roof. Penetrations of smoke partitions will be in accordance with SBNC Section Ducts and air transfer openings in smoke partitions will be in accordance with SNBC Section Air transfer openings will require smoke dampers complying with Section Penetrations of the bottom roof membrane will be in accordance with SNBC Section and duct penetrations will be in accordance with SNBC Section Doors located in non-rated corridor walls that are not part of an exit, will not require a fire protection rating and will not be required to be equipped with self-closing or automatic-closing devices. These corridor doors will be required to provide an effective barrier to limit the transfer of smoke, and will be equipped with positive latching. Roller latches will not be permitted. Group I-2 occupancies with an occupant load exceeding 49 occupants are required to be separated into no fewer than two smoke compartments per SNBC Section Smoke compartments are not permitted to exceed 22,500 ft 2. The skilled nursing facility will be separated into two smoke compartments. Smoke compartments are required to be separated from adjacent smoke compartments by 1-hour fire-resistance rated smoke barriers constructed in accordance with SNBC Section 709. Smoke barriers will not be required where the smoke compartment boundary wall is separating the interior of the building from the outside, which includes exterior walls and court walls. Smoke barriers will form an effective membrane continuous from outside wall to outside wall and from below the underside of the floor or roof sheathing, deck or slab above, including continuity though concealed spaces. Openings in

3 City of Las Vegas 3 September 15, 2016 Centennial Hills Skilled Nursing Facility JBA Project No Las Vegas, NV smoke barriers will be in accordance with SNBC Section Exception 1 and 2, as applicable. Penetrations of smoke barriers will be in accordance with SNBC Section Ducts and air transfer openings in smoke barriers will be in accordance with SNBC Section 717. Locations of smoke compartments are detailed on the small-scale drawing provided as attached. Waste/linen collection rooms will be required to be separated from adjacent spaces by 1-hour fire-resistance rated construction. Doors serving 1-hour fire-resistance rated waste/linen collection rooms will have a minimum fire protection rating of 45 minutes. All other interior partitions will be permitted to be of nonrated construction. The fire riser room will be separated from the remainder of the building with 1-hour fire-resistance rated fire partitions in accordance with SNBC Section and will have direct exterior access. Skylights are permitted to be unprotected per SNBC Section Light transmitting plastic skylights will also comply with SNBC Section 2610, noting that the building will be fully sprinklered in accordance with NFPA 13. Through-penetrations will be protected by an approved penetration firestop system installed per manufacturer s requirements. Penetrations of fire-resistance rated construction, including fire-resistance rated walls and horizontal assemblies, will be in accordance with SNBC Section 714. Through-penetrations firestop systems will have an F-rating / T-rating of not less than 1 hour but not less than the required rating of the floor/wall penetration. Recessed fixtures installed in fire-resistance rated walls and partitions, are to be installed such that the required fire-resistance will not be reduced in compliance with SNBC Section Protection of joints between fire-resistance rated walls and floors will comply with SNBC Section 715. Openings, ducts, and air transfer openings will comply with SNBC Sections 716, and 717, respectively. INTERIOR FINISHES Wall and ceiling finishes within administrative spaces, rooms with a capacity of four persons or less and corridor walls for the bottom 48 inches, will be of materials having a maximum flame spread index of 75 or less and smoke-developed index of 450 (Class B) per NFPA 101, Section Wall and ceiling finishes for all other areas will be of materials having a maximum flame spread index of 25 and smokedeveloped index of 450 (Class A) per NFPA 101, Section All floor finishes will be in accordance with SNBC Section 804. Decorative materials and trim will be in accordance with SNBC Section 806. Materials located within plenums will have a maximum flame spread index and smoke-developed index of 25 and 50, respectively. EXITING SYSTEMS Master egress drawings will be submitted to the City of Las Vegas Department of Building and Safety (CLVDBS) by others for review and approval. Calculated occupant load factors will be in accordance with SNBC Table The overall facility will have a calculated occupant load of 736 occupants. Three means of egress are required, and six will be provided. Exit capacity will be based on 1 occupant per 0.2 inches per SNBC Section

4 City of Las Vegas 4 September 15, 2016 Centennial Hills Skilled Nursing Facility JBA Project No Las Vegas, NV Doors used for egress will have a minimum clear width of 32 inches and will be in accordance with SNBC Section Where required for the movement of beds, doors will have a clear width not less than 41-1/2 inches and the height will not be less than 80 inches. Doors will swing in the direction of egress travel where serving an occupant load of 50 or more per SNBC Section Where two means of egress are required, the required means of egress will be separated by a distance of at least one-third of the length of the maximum overall diagonal dimensions per SNBC Section Illuminated exit signs will be provided at exit doors and where otherwise necessary to clearly indicate the direction of exit travel when two or more exits are required. Exit signs will not be provided within rooms requiring only one exit, per Exception 1 of SNBC Section Exit illumination will be provided throughout in accordance with SNBC Section Travel distance between any point in a Group I-2 occupancy sleeping room and an exit access door in that room will not be greater than 50 feet per SNBC Section Travel distance from any point in a smoke compartment to a smoke barrier door will not exceed 200 feet per SNBC Section Refuge areas will be provided within each smoke compartment. The size of the refuge will be required to accommodate the occupants and care recipients from the adjoining smoke compartment. The size of the refuge area will be not less than 30 net ft 2 for each care recipient confined to bed or litter, and not less than 6 ft 2 for each ambulatory care recipient not confined to bed or litter and for other occupants. FIRE PROTECTION SYSTEMS The new building will required to be protected by an automatic sprinkler system per SNBC Section As such, a wet pipe, hydraulically calculated automatic sprinkler system will be provided throughout. Sprinklers will be supplied from the site water distribution system. Where necessary to protect from freezing, dry type sprinklers will be used. Sprinklers will be designed and installed in accordance with 2013 NFPA 13, Standard for the Installation of Sprinkler Systems. A minimum safety margin of 10 psi will be incorporated in all new sprinkler system hydraulic calculation. All sprinkler system hydraulic calculations will incorporate a maximum velocity of 32 feet per second. A separate sprinkler system will be require for each smoke compartment. Smoke compartments containing sleeping rooms will be required to be equipped throughout with quick response sprinklers, per SNBC Section Sprinkler system design densities will comply with NFPA 13 and LVFR. Type I grease hoods will be provided with automatic suppression in accordance with SNBC Section and NFPA 96, Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations. Where associated duct systems exceed 75 feet in length, the ducts will be protected by wet pipe automatic sprinklers with high temperature links/bulbs and will be served by separate and independent supplies in accordance with NFPA 96. Activation of a kitchen hood suppression system will automatically shut down the energy source under the affected hood in accordance with NFPA 96 Sections and Fire extinguishers will be provided and placed in compliance with SNBC Section 906, SNFC, and NFPA 10, Standard for Portable Fire Extinguishers. Standpipes will not be required. Secondary water supply will not be required. Storage will not exceed 12-feet such that high-piled-storage is not an issue. The sprinkler system will be detailed on fire sprinkler shop drawings submitted to the LVFR for review and approval.

5

6