1 STATE BANK OF INDIA T. SUNDUPALLI BRANCH (04427) REGION 2, KADAPA RURAL TIRUPATI (A.O) ELECTRICAL WORK BILL OF QUANTITIES SL. NO. DESCRIPTION QTY. UNIT RATE AMOUNT Rs. Rs. 1 Supply, installation, testing & commissioning of 125 A TPN SFU with 3 Nos. 100 A HRC fuses for R,Y,B phases and neutral link in a sheet steel enclosure with connector box and to be installed near the APSEB Meter Board. Double compression type cable gland shall be used for cable entry. 2 Supply, installation, testing & commissioning of 125 A On- load Four Pole Change Over Switch in a sheet steel enclosure with connector box. The cable entry should be through a double compression type cable gland for all cables. 3 Supply, installation, testing & commissioning of cubicle type compartmentalised wall mounting panel board with following: 100 A 4 pole MCCB as incomer 2 Nos. 63 A Four Pole MCB; and 2 Nos. 32 A Four Pole MCB as outgoing. 125 A Bus Bar with 25x6 mm copper flats for three phases and neutral and provided with heat shrinkable pvc sleeves. Ammeter A and CTs and with phase selector switch for the incoming side. 1 No. Voltmeter V and phase selector switch with 3 A control fuses on the incoming side. R-Y-B LED type lamp indicators with switch control on the incoming side. All meters are analog type. The panel should be manufactured with 16 guage sheet steel and zinc passivated before painting. The panel should be painted with one primary coat of red oxide and finished with two coats of Siemens grey above the primary coating. (Main DB). All cable entries should be through double compression type cable glands.

2 4 Supply, installation, testing & commissioning of double door 6 way TPN DB with following: 63 A FP MCB as incomer 12 Nos. 16/25/32 A SP MCB as outgoing to be used. (AC & Raw Power DB). Supply, installation, testing & commissioning of double door 6 way TPN DB with following: 32 A FP MCB as incomer 12 Nos. 6/10/16 A SP MCB as outgoing to be used. (LDB). 5 Supply, installation, testing & commissioning of double door SPN DB with following: 32 A FP MCB as incomer 2 Nos. 32 A DP MCB as outgoing to be used. (UPS Power DB). 6 Supply, installation, testing & commissioning of double door SPN DB with following: 32 A DP MCB as incomer 3 Nos. 10 / 16 A SP MCB as outgoing to be used. (UPS DB 1). 7 Supply, installation, testing & commissioning of double door SPN DB with following: 32 A DP MCB as incomer 32 A DP MCB & 3 Nos. 10 / 16 A SP MCB as outgoing to be used. (UPS DB 2). 8 Supply, installation, testing & commissioning of 32 A FP MCB Type Change Over Switch in a Four Pole DB box. to be used (UPS COS).

3 9 Supply, installation, testing & commissioning of industrial type 25 A three pin socket housed in powder coated sheet steel enclosure with 25 A DP MCB with locking connector for split Acs. 2 Nos 10 Supply, installation, testing & commissioning of 32 A DP MCB in a Double Pole DB box for cassette ACs and Output control for UPS 1. to be used. 7 Nos 11 Supply, installation, testing & commissioning of 4 nos. 6 A modular type switch & sockets housed in single manufacturers zinc boxes are to be fixed on partitions / work stations for UPS power points. 13 Nos 12 Supply, installation, testing & commissioning of 2 nos. 6 A modular type switch & sockets housed in single manufacturers zinc boxes are to be fixed on partitions / work stations for raw power points. 13 Nos 13 Supply, installation, testing & commissioning of 2 nos. 6 / 16 A modular type switch & sockets housed in single manufacturers zinc boxes are to be fixed on partitions / wall as required. 5 Nos 14 Supply and laying of ISI marked 25 mm. Dia medium grade PVC conduit for data cabling with fish wire. 76 Mtrs 15 Supply and installation of zinc passivated MS boxes for data outlet (I/O) 13 Nos 16 Supply, installation & termination of 3.5 core 50 sqmm. XLPE armoured aluminium cable with No. 8 bare Cu earth wire fixed on the wall / ceiling with clamping for connecting 100 A SFU and 125 A COS and from COS to Main DB in the UPS Room. 25 Mtrs 17 Supply, installation & termination of 4 core 25 sqmm. XLPE armoured aluminium cable with No. 8 bare Cu earth wire fixed on the wall / ceiling with clamping for connecting Main DB and AC DB. 8 Mtrs

4 18 Supply, installation & termination of 4 runs 6 sqmm. 1.1 KV grade PVC insulated multi strand copper wire in 32 mm. Dia. Rigid PVC conduit fixed on the wall / ceiling with clamping for connecting Main DB and LDB & UPS Power DB. 19 Supply, installation & termination of 3 runs of single core 6 sq mm. 1.1 KV grade pvc insulated flexible copper cable (green colour for earth) in 25 mm. Dia. ISI marked rigid PVC conduit on the wall and flexible PVC conduit on the ground for UPS and servo-stabiliser input and output. 20 Supply, installation & termination of 3 runs of single core 6 sq mm. 1.1 KV grade pvc insulated flexible copper cable (green colour for earth) in 25 mm. Dia. ISI marked rigid PVC conduit on the wall / partition from UPS DB 1 to UPS DB 2 & UPS COS. 21 Supply, installation & termination of 2 runs of 4 sq mm. and one run of 2.5 sq. mm.(green colour for earth) 1.1KV grade pvc insulated flexible copper wire in 25 mm. Dia. ISI marked rigid PVC conduit for A/Cs. 30 Mtrs. 12 Mtrs. 10 Mtrs. 235 Mtrs. 22 Supply, installation & termination of 3 runs of 2.5 sq mm. 1.1KV grade flexible copper wire (green colour for earth) in 20 / 25 mm. Dia. rigid PVC conduits as per IS 9537 Part I for UPS / Raw power circuits to be laid on wall / partitions. UPS circuit 100 Mtrs Raw power circuit 100 Mtrs. 23 Supply & installation of point wiring using 3 runs of 1.5 sq. mm.1.1 KV grade PVC insulated flexible copper wire (green colour for earth) in 20 mm. Dia. ISI marked pvc conduit as per IS 9537 Part 2 with 5 A modular type switch. 1 light controlled by one switch. (Safe Room & Locker Room Light Points) 12 Nos.

5 24 Same as Item no.23 but ceiling fan points with step type hum free electronic regulator and fixing of fan hook.(safe Room fan points) 12 Nos. 25 Same as Item no.23 but exhaust fan points with switch on switch board and socket near exhaust hole. 4 Nos. 26 Supply & installation of 600 x 600 mm square type modular 36 W LED light fixture complete with electronic driver, wiring, heat sink, opal acrylic diffuser etc. suitable for recessed mounting in gyp board or metric false ceiling. The fixture shall be provided with atleast three nos. 20 mm dia. Knock-out holes on the top side of the body for fixing down rods and wiring purposes.. 27 Supply & installation of box type 1x28 W, 4' slim tube light fixture with fluorescent lamp, electronic ballast and complete wiring with lamp 22 Nos. 32 Nos. 28 Supply & installation of 48 ceiling fan with suitable down rod 32 Nos. 29 Supply and fixing of 300 mm. Dia exhaust fan with frame and gravity louvres 30 Supply and installation of 1.1 KV grade single core 10 sqmm. PVC insulated flexible copper wire in 20mm. PVC conduit from earth pit to UPS Room 4 Nos. 25 Mtrs. 31 Supply and installation of earthing pit with 600X 600X3.15mm. Copper plate, GI pipe, 25x3 mm copper flat connection and funnel arrangement for watering and with chamber on the ground level as per IS (UPS earth) 32 Supply and installation of earthing pit with 40 mm dia GI pipe as per standard IS (EB earth). 2 Nos. 33 Supply and laying of 25x3 mm. GI flat from pipe earth to Main DB, COS, AC DB and SFU etc. 30 Mtrs.

6 34 Supply and laying of ISI marked 25 mm. Dia medium grade PVC conduit for telephone wiring. 35 Supply and installation of two pair 0.5 mm. telephone wire in the already provided PVC conduit. 76 Mtrs. 180 Mtrs. 36 Supply and installation of one module box with one module front plate and RJ-11 telephone outlet (2Nos.). 12 Nos. 37 Supply and installation of 30 pair Krone type telephone connector box 38 Supply and fixing of 3 nos. patty type 320 A Kit Kat fuse with carrier and Nuetral link on a wooden board. 39 Supply and fixing of 63 A TP MCB in sheet steel enclosure as control switch for APFC Panel near 125 A SFU. 40 Supply, installation, testing & commissioning of 4 stage Automatic Power Factor Control Panel (APFC Panel) of 20 KVAR capacity ( KVAR capacitors) as below: 63 A TP MCB as incomer. Three Pole MCBs and Heavy duty contactors for outgoing 32 A for 10 KVAR 25 A for 5 KVAR 16 A for 3 KVAR and 2 KVAR Necessary power and control wiring with 1.1 KV grade copper wire suitably. 41 Supply & fixing of 3 nos. of LED indicator lamps (R,Y,B) with 3 nos, lamp holders and 3 nos. 5A piano type switches on a suitable board and wiring with 1.1 KV grade 3 x 1.5 sq. mm. Copper flexible wire in pvc pipe tapping power from input of EB cut out. 42 Supply & fixing of 3 core 1.1 KV grade 2.5 sq mm. Flexible copper cable 3 metre long connected at one end with 15 A three pin socket and other end connected permanently to the switch board of Safe Room 1 Set 1 Set 3 Nos.

7 43 Supply & installation of 16 A modular DP switch housed in single manufacturers zinc boxes are to be fixed on partitions / work stations as master control above the counter for UPS power points. 44 Supply, installation & termination of 4 runs 25 sqmm. 1.1 KV grade PVC insulated multi strand copper wire for connecting from EB meter to Cut Out, from Cut Out to 125 A TPN SFU. 13 Nos. 5 Mtrs. 45 Supply & installation of 9 W LED Bulk Head Light Fixture. 6 Nos. TOTAL DISCOUNT IF ANY NETT NOTE: 1) MCCB FAULT LEVEL SHALL BE OF MINIMUM 16 KA. 2) FAULT LEVEL FOR ALL MCBS SHALL BE OF MINIMUM 3 KA 3) ALL COPPER WIRES & ALUMINIUM CABLES SHALL BE 1.1 KV GRADE SIGNATURE OF THE CONTRACTOR WITH SEAL