INITIAL STRUCTURAL INTEGRITY ASSESSMENT REPORT (SIAR)

Size: px
Start display at page:

Download "INITIAL STRUCTURAL INTEGRITY ASSESSMENT REPORT (SIAR)"

Transcription

1 INITIAL STRUCTURAL INTEGRITY ASSESSMENT REPORT (SIAR) Assessor: Plot M-4/3, Road 7, Section 7 Mirpur, Dhaka Dhaka Dhaka Bangladesh Emkay Enterprises The Alliance for Bangladesh Worker Safety Page 1/7

2 Introduction to the Report The following report contains a site profile and summary of non-conformities identified during an onsite assessment commissioned by the Alliance for Bangladesh Worker Safety (Alliance) and conducted by a third-party Qualified Assessment Firm (QAF). The assessment was conducted against the Alliance for Bangladesh Worker Safety Assessment Protocols (APs) and Fire Safety and Structural Integrity Standard, which is harmonized with the factory assessment guidelines developed by Bangladesh University of Engineering and Technology (BUET) for the Bangladesh National Tripartite Plan of Action (NTPA). The goal of the Alliance process is to provide clear and practical technical requirements by which Bangladeshi Ready Made Garment (RMG) Factories producing for Alliance members may be consistently and fairly evaluated for fire, structural, and electrical safety in a non-duplicative manner. Each assessment will prompt action plans that will be used by RMG factories to systematically and sustainably improve safety conditions for garment workers. Beyond tracking and reporting on action steps taken in a transparent manner, the Alliance organization and its members will seek to further support factory improvements through technical assistance, training, implementation support for functional Worker Committees, and in some cases financial assistance and wage support for workers if factories are closed for remediation. The contents of the report do not constitute a guarantee of compliance with the applicable laws, the Alliance Standard or the absolute or continued safety against fire, electrical and/or structural integrity issues that may lead to injury or loss of life. The report is designed to provide a non-exhaustive summary of risk issues, based on a limited sampling and duration of time onsite by the named QAF. Neither the QAF nor the Alliance can certify or guarantee the quality, outcome, or effectiveness of actions taken in response to the report. For more information and report feedback please go to: The Alliance for Bangladesh Worker Safety Page 2/7

3 GENERAL INFORMATION General Information Country: Province: City: Bangladesh Dhaka Dhaka Zip Code: 1217 Audit Duration: Re-Audit: 1 Days 0 Hours Re-Audit After 0 Months Draft Report Date : 30 September 2015 Final Report Date : 11 November 2015 Are all Action Items From Previous Assessment Completed?: Buildings in Complex : Number of Building Levels (Stories) : Approximate Building Area (SF) : Date of Building Construction : Date of Last Building Renovation/Addition : Is the Building mixed use?: Ancillary Structures in Complex : Number of Ancillary Levels (Stories) : N/A There are 3 buildings. One Main Buildings and two Ancillary Buildings. Main Building: 12 Stories with one basement (B + G + 11). Total: 92,600 SF (Basement: 6,900; G.F: 7,600; 1st to 11th: 7,100 SF Each). 01. Main Building: ; 02. Boiler Shed: 2000; 03. Generator Building: No addition or renovation. No There are two ancillary structures. 01. Boiler Shed: Single story tin shed; 02. Generator Building: Single story RCC building. Approximate Ancillary Total: 381 SF; (Boiler Shed: 107, Generator Building: 274). The Alliance for Bangladesh Worker Safety Page 3/7

4 Structures Area (SF) : Number of Occupants : Exterior Facade Description : Structural System Description : Issues were not found during the structural integrity assessment that required the Emergency Escalation Protocol (and referral to NTC Review Panel)?: Total Occupant: 827 [Basement: 20 (Tunic Apparels Ltd. & O'dell Apparels Ltd.); G.F: 23 (Tunic Apparels Ltd. & O'dell Apparels Ltd.); 1st: 55 (Tunic Apparels Ltd.); 2nd: 20 (O'dell Apparels Ltd.); 3rd: 115 (Tunic Apparels Ltd.); 4th: 195 (Tunic Apparels Ltd.); 5th: 190 (Tunic Apparels Ltd.); 6th: 190 (Tunic Apparels Ltd.); 7th to 10th: Vacant (O'dell Apparels Ltd.); 11th: 19 (Tunic Apparels Ltd. & O'dell Apparels Ltd.)]. The exterior facade is infilled masonry wall with plaster finished and painted and windows are frame type. Building frame system with flat slab, column and structural wall. Yes The Alliance for Bangladesh Worker Safety Page 4/7

5 ASSESSMENT FINDINGS Structural System Design Are the available FoS for the columns adequate based on Preliminary calculation? High Non-Compliance Level: 3 FoS calculations were completed assuming an average live load of 42 psf for working area. A 40 ksi reinforcing steel strength was assumed according to design documents. FoS calculations were originally completed assuming a concrete compressive strength of Uploaded Document: 1. FoS calculation of Tunic Apparels Ltd. 2. Core test reports-tunic Apparels Ltd. 3. Equivalent Concrete Core Strength Calculation. Submit the previously conducted Bureau Veritas detail engineering assessment (DEA) report to the Alliance for review and approval as a DEA has already been completed from the factory end. Provide results of preliminary calculations in space provided. a) column capacity; FoS > Safe b) column capacity; FoS Needs Evaluation c) Column capacity; FoS Needs Evaluation d) Column capacity; FoS < Unsafe In case of a critically low FoS (<1.25), consider Immediate Escalation Protocol Are credible structural design documents available for review and kept on site? Medium Structural design document available and kept on site. But some column section for upper floor does not match with the provided structural drawing. Visual Assessment: Structural design document available and kept on site. But some column section for upper floor does not match with the provided structural drawing. Have a qualified structural engineer prepare credible as-built documents based on the requirements of Part 8 Section 8.19 of the Alliance Standard. Alliance Standard Part 8 Section 8.19 Required Structural Documentation for New and Existing Factories The Alliance for Bangladesh Worker Safety Page 5/7

6 If built after 2006, can documented compliance with the seismic and wind requirements of the 2006 BNBC be provided? Medium General conformance with BNBC 2006 wind requirement found in the factory provided detail engineering assessment report but seismic loading criteria was not indicated in design calculation report. Document Review: General conformance with BNBC 2006 wind requirement found in the factory provided detail engineering assessment report but seismic loading criteria was not indicated in design calculation report.., Photograph, Document Review: General conformance with BNBC 2006 wind requirement found in the factory provided detail engineering assessment report but seismic loading criteria was not indicated in design calculation report.., Photograph Have a qualified structural engineer document compliance with the seismic and wind requirements stated in the 2006 BNBC. Alliance Standards Part 8 Section 8.17 Design for Lateral Loads and 2006 BNBC Part 6 Section 1.5 Structural System Construction Have all areas of needed maintenance, including areas with efflorescence, dampness, standing water on rooftops, and corrosion been addressed. Medium Corrosion found at roof top exposed rebar. Photograph: Corrosion in exposed rebar, Visual Assessment, Photograph: Corrosion in exposed rebar, Visual Assessment Under guidance from a qualified structural engineer, address all areas of needed maintenance by correcting the identified issues. Alliance Standard Part 8 Section 8.26 Durability and Maintenance The Alliance for Bangladesh Worker Safety Page 6/7

7 Is the building free of active signs of water intrusion or ponding due to lack of performance of the façade system? Low Though water intrusion or ponding was not found during visual assessment, some wall found unplaster at outside face which can make the wall damp in future. Photograph: Un-plastered wall picture-1 Un-plastered wall picture-2, Visual Assessment, Photograph: Un-plastered wall picture-1 Un-plastered wall picture-2, Visual Assessment Repair the exterior façade system to prevent water intrusion. Alliance Standard Part 8 Section 8.26 Durability and Maintenance The Alliance for Bangladesh Worker Safety Page 7/7